LG TS-C096EMA0, TS-H096EMA0, TS-C126EMA0, TS-H126EMA0, TS-C096YDA0 Diagram

...
LG
Room Air Conditioner
SERVICE MANUAL
LG
MODELS: TS-C096EMA0
TS-H096EMA0 TS-C126EMA0 TS-H126EMA0 TS-C096YDA0 TS-H096YDA0 TS-C126TDA0 TS-H126TDA0
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
Air Conditioner Service Manual
TABLE OF CONTENTS
LG Model Name ...............................................................................................................................................3
Safety Precautions..........................................................................................................................................5
Dimensions....................................................................................................................................................10
Symbols Used in this Manual...................................................................................................................10
Indoor Unit................................................................................................................................................10
Outdoor Unit.............................................................................................................................................13
Product Specifications .................................................................................................................................14
Installation .....................................................................................................................................................18
Selection of the Best Location..................................................................................................................18
Piping Length and Elevation.....................................................................................................................18
How to Fix Installation Plate.....................................................................................................................19
Drill a Hole in the Wall..............................................................................................................................19
Drain hose junction...................................................................................................................................19
Flaring work and connection of piping.......................................................................................................20
Flaring work..............................................................................................................................................20
Connection of Piping Indoor.....................................................................................................................20
Connection of the Pipes-Outdoor.............................................................................................................24
Connecting the cable between indoor unit and outdoor unit...................................................................25
Connect the Cable to the Indoor Unit.......................................................................................................25
Connect the Cable to the Outdoor Unit ....................................................................................................26
Checking the drainage and forming the pipings........................................................................................27
Checking the Drainage.............................................................................................................................27
Form the Piping........................................................................................................................................27
AIR PURGING ................................................................................................................................................28
Air purging................................................................................................................................................28
Air purging with vacuum pump.................................................................................................................28
Test Running .................................................................................................................................................30
Operation .......................................................................................................................................................31
Function of Controls.................................................................................................................................31
Display Function ......................................................................................................................................35
Self-diagnosis Function............................................................................................................................35
Remote Control Operations......................................................................................................................36
Disassembly ..................................................................................................................................................37
Indoor Unit................................................................................................................................................37
Schematic Diagram.......................................................................................................................................40
Electric Control Device.............................................................................................................................40
Wiring Diagram.........................................................................................................................................41
Components Location ..............................................................................................................................44
Troubleshooting Guide.................................................................................................................................46
Refrigeration Cycle Diagram ....................................................................................................................46
2-way, 3-way Valve .................................................................................................................................47
Cycle Parts...............................................................................................................................................53
Electronic Parts........................................................................................................................................54
Exploded View...............................................................................................................................................61
Replacement Parts List ................................................................................................................................63
2 Room Air Conditioner
LG Model Name
12 - 345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China M: Mexico K: Turkey R22 V: Vietnam E: Turkey R410A S: Out Sourcing H: Thailand
2 Product Type A~Z S: Split Type Air Conditioner
3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 1~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T
Nano Plasma F+4Way+(A/changeove)+A/clean+ U
R Mirror W White B Blue D Wood M Metal C Cherry
2003
Service Manual 3
2004~
12 - 345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z
L Chang_won R22 A Chang_won R410A C Chang_won R407C T China K Turkey R22 E Turkey R410A H Thailand
N India Z Brazil D Indonesia X Mexico V Vietnam S Out sourcing
Refrigerant
2 Product Type A~Z S: Split Type Air Conditioner
3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V
CHASSIS Look
D K
L G M N D P
Division Panel Type(Deluxe) Fighting 'Look'
(LG1) (LG2)-SEMI PANEL OEM1 OEM2 Panel Type(Deluxe) LG3
, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 1~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
R Mirror W White B Blue D Wood M Metal C Cherry
S4/S5
S6 SQ SR
ST
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F NBF F+(A/changeove)+A/clean+Low A G NBF F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K NBF F+(A/changeove)+A/clean L NBF F+(A/changeove)+A/clean+4way M NBF F+(A/changeove)+A/clean+PTC N NBF F+(A/changeove)+Autoclean+4way+PTC P NBF F+(A/changeove)+A/clean+4way+Low A+PTC Q (Nano)Plasma+ION+A/Clean S 4way+(Nano)Plasma F+
Negative ION+Healthy dehumidification
+A/Clean T Nano Plasma F+4Way+(A/changeove)+A/clean+Oxy generator U 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean+Oxy generator
V Dry contact W Wire remocon 8
4 Room Air Conditioner
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
Installation
Do not use damaged power cords, plugs, or a loose socket.
• There is risk of fire of electric shock. • There is risk of electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire of electric shock. • No grounding may cause electric shock.
Always use the power plug and socket with the ground terminal.
.Do not modify or extend the power cord.
Service Manual 5
Safety Precautions
For re-installation of the installed product, always contact a dealer or an authorized ser­vice center.
• There is risk of fire, electric shock, explosion, or
injury.
Be cautious when unpacking and installing the product.
• Sharp edges could cause injury. Be especially care-
ful of the case edges and the fins on the condenser and evaporator.
Do not install, remove, or re-install the unit by yourself.
• There is risk of fire, electric shock, explosion, or injury.
For installation, always contact the dealer or an Authorized service center
There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective instal­lation stand.
• It may cause injury, accident, or damage to the product.
6 Room Air Conditioner
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Operation
Wax
Thinner
Safety Precautions
Do not turn the air-conditioner ON or OFF by
Use a dedicated outlet for this appliance.
plugging or unplugging the power plug.
• There is risk of fire or electrical shock. • There is risk of fire or electrical shock.
Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.
• There is risk of fire or electrical shock. • There is risk of fire and electric shock.
Do not place a heater or other appliances near the power cable.
Do not allow water to run into electrical parts. Do not store or use flammable gas or com-
bustibles near the air conditioner.
• There is risk of fire, failure of the product, or electric shock.
• There is risk of fire or failure of product.
Service Manual 7
90˚
Safety Precautions
Unplug the unit if strange sounds, odors, or smoke comes from it.
There is risk of electric shock or fire. There is risk of fire, electric shock, or product dam-
Be cautious that water could not enter the product.
age.
Installation
Always check for gas (refrigerant) leakage after installation or repair of product.
Install the drain hose to ensure that water is drained away properly.
• Low refrigerant levels may cause failure of product. • A bad connection may cause water leakage.
Keep level even when installing the product. Use two or more people to lift and transport
the air conditioner.
• To avoid vibration or water leakage. • Avoid personal injury.
8 Room Air Conditioner
Operation
Wax
Safety Precautions
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the
plastic parts of the product.
Do not step on or put anyting on the product. (outdoor units)
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
There is risk of personal injury.
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
There is risk of personal injury and failure of product. There are sharp and moving parts that could cause
personal injury.
Service Manual 9
Dimensions
Installation plate
D
H
W
Indoor Unit
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
Indoor Unit
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
Dimensions
Symbols Used in this Manual
NOTICE
Model
Dimension
W mm 915
H mm 171 D mm 282
10 Room Air Conditioner
SE Chassis
Dimensions
Installation plate
D
H
W
Model
Dimension
W mm 840
H mm 270 D mm 161
SY Chassis
Service Manual 11
Dimensions
Installation plate
D
H
W
Dimensions
Model
Dimension
W mm 895
H mm 282 D mm 166
ST Chassis
Service Manual 12
MODEL
DIM unit
W mm
H mm
D mm
Dimensions
Service Manual 13
Outdoor Unit
D
W
H
TS-C096EMA0 TS-C096YDA0
575
520
Gas side
(3-way valve)
Liquid side
(2-way valve)
TS-H096EMA0 TS-H096YDA0
0
TS-C126EMA0 TS-C126TDA0
TS-H126EMA0 TS-H126TDA0
770
540
260
245
Models TS-C096EMA0 TS-H096EMA0
Product Specifications
Service Manual 14
Cooling Capacity
Heating Capacity -
Power Input Cooling 930 950
Heating - 940
Running Current Cooling 4.5 4.5
Heating - 4.5
Starting Current Cooling 6 6
Heating - 6
EER 2.44(2.84) 2.39(2.78)
COP - 2.8 Power Supply 1Φ,220-240,50 1Φ,220-240,50 Air Circulation Indoor,Max
Outdoor,Max 1680 1680
Moisture Removal Features Temperature Control
Plasma Filter - ­Nano Plasma Filter - ­Deodorizing Filter Optional Optional
CHAOS Wind(Auto Wind) Airflow Direction(4-Way:Optional) Steps, Fan/Cool 3/4 3/4 Airflow Direction Contorl(up&down) Airflow Direction Contorl(left&right) Remocon Type Wireless Simple Wireless Simple Setting Temperature Range Cool
Temperature Increment Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) 3 3
Special Function Refrigerant(R22)Charge 490g 780g Blower Motor Input 29 29
Output 11 11
Motor Input 52 66.6
Motor Output 36 27
Circuit Breaker A
Power Cord 3*0.75 3*0.75
Connecting Cable 3*0.75 3*0.75
Connecting Tube Liquid Side 6.35(1/4) 6.35(1/4)
(φ. Socket Flare) Gas Side 9.52(3/8) 9.52(3/8)
Length,std 5 5
Drain Hose (O.D , I.D) 21.5,16(0.85,0.63) 21.5,16(0.85,0.63)
Dimension Indoor 171*915*282 171*915*282
Outdoor520*575*260 540*770*245
Net Weight Indoor
Outdoor 33 25
Unit
kcal/h.(W)
Btu/h.
kcal/h.(W)
Btu/h.
W W
A A A A
kcal/h.W(W/W)
Btu/h.W
W/W
Φ,V,Hz
/min(CFM)/min(CFM)
/h.(pts/h.)
g W
W
W
W
AWG#:P*
AWG#:P*
mm(in)
mm(in)
m(in)
mm(in)
mm
mm
kg
kg
Heat
2268(2637) 2268(2637)
9,000 9,000
- 9,000
9.68 9.47
430 430
0.95 0.95
Thermistor Thermistor
Yes Yes
4-Way 4-Way
Auto Auto
Manual Manual
18 - 30 18 - 30
- 16 - 30
11
Yes Yes
24h, Off 24h, Off
Yes Yes Yes Yes
--
--
10 9
2268(2637)
Models TS-C126EMA0 TS-H126EMA0
Product Specifications
Service Manual 15
Cooling Capacity
Heating Capacity
Power Input Cooling 1290 1280
Heating - 1280
Running Current Cooling 6.3 6.1
Heating - -
Starting Current Cooling 10.1 9.6
Heating 7.35 7.7
EER 2.35(2.73) 2.36(2.75)
COP - 2.8 Power Supply 1Φ,220-240,50 1Φ,220-240,50 Air Circulation Indoor,Max
Outdoor,Max 1680 1680
Moisture Removal Features Temperature Control
Plasma Filter - ­Nano Plasma Filter - ­Deodorizing Filter Optional Optional
CHAOS Wind(Auto Wind) Airflow Direction(4-Way:Optional) Steps, Fan/Cool 3/4 3/4 Airflow Direction Contorl(up&down) Airflow Direction Contorl(left&right) Remocon Type Wireless Simple Wireless Simple Setting Temperature Range Cool
Temperature Increment Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) 3 3
Special Function Refrigerant(R22)Charge 680g 930g Blower Motor Input 29 29
Output 11 11
Motor Input 66.6 109
Motor Output 27 42
Circuit Breaker A
Power Cord 3*1.0 3*1.0
Connecting Cable 3*1.0 3*1.0
Connecting Tube Liquid Side 6.35(1/4) 6.35(1/4)
(φ. Socket Flare) Gas Side 12.7(1/2) 12.7(1/2)
Length,std 5 5
Drain Hose (O.D , I.D) 21.5,16(0.85,0.63) 21.5,16(0.85,0.63)
Dimension Indoor 171*915*282 171*915*282
Outdoor 245*540*770 245*540*770
Net Weight Indoor
Outdoor 33 33
Unit
kcal/h.(W)
Btu/h.
kcal/h.(W)
Btu/h.
W W
A
A
A
A
kcal/h.W(W/W)
Btu/h.W
W/W
Φ,V,Hz
/min(CFM)/min(CFM)
/h.(pts/h.)
g W
W
W
W
AWG#:P*
AWG#:P*
mm(in)
mm(in)
m(in)
mm(in)
mm
mm
kg
kg
Heat
3024(3516) 3024(3516)
12,000 12,000
- 3024(3516)
- 12,000
9.30 9.38
550 550
1.5 1.5
Thermistor Thermistor
Yes Yes
4-Way 4-Way
Auto Auto
Manual Manual
18 - 30 18 - 30
- 16 - 30
11
Yes Yes
24h, Off 24h, Off
Yes Yes Yes Yes
--
--
10 10
Models TS-C096YDA0 TS-H096YDA0
x
y
y
&
&
R
,
u
Product Specifications
Service Manual 16
Cooling Capacity
Heating Capacity -
Power Input Cooling 900 900
Heating - 900
Running Current Cooling 4.4 4.4
Heating --
Starting Current Cooling 6 6
Heating - -
EER 2.52(2.93) 2.52(2.93)
COP - 2.9 Power Supply 1Φ,220-240,50 1Φ,220-240,50 Air Circulation Indoor,Max
Outdoor,Ma
Moisture Removal Features Temperature Control
Plasma Filter - ­Nano Plasma Filter - -
Deodorizing Filter Optional Optional
CHAOS Wind(Auto Wind) Airflow Direction(4-Way:Opti Steps, Fan/Cool 3/4 3/4 Airflow Direction Contorl(up Airflow Direction Contorl(left Remocon Type Wireless Simple Wireless Simple Setting Temperature
Temperature Increment Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) 3 3
Special Function
Refrigerant(R22)Charge 430g 630g
Blower Motor Input 29 29
Output 11 11 Motor Input 52 66.6 Motor Outp
Circuit Breaker A
Power Cord 3*0.75 3*0.75 Connecting Cable 3*0.75 3*0.75
Connecting Tube Liquid Side 6.35(1/4) 6.35(1/4) (φ. Socket Flare) Gas Side 9.52(3/8) 9.52(3/8)
Length,std 5 5
Drain Hose (O.D , I.D) 21.5,16(0.85,0.63) 21.5,16(0.85,0.63)
Dimension Indoor 161*270*840 161*270*840
Outdoor 520
Net Weight Indoor
Outdoor 22 33
Unit
kcal/h.(W)
Btu/h.
kcal/h.(W)
Btu/h.
W W
A A A A
kcal/h.W(W/W)
Btu/h.W
W/W
Φ,V,Hz/min(CFM)/min(CFM)
/h.(pts/h.)
Cool Heat
g W W W W
AWG#:P* AWG#:P*
mm(in) mm(in)
m(in)
mm(in)
mm mm
kg kg
2268(2637) 2268(2637)
9,000 9,000
- 9,000
10.00 10.00
450 450
1560 1560
1.1 1.1
Thermistor Thermistor
Yes Yes
4-Wa
Auto Auto
Manual Manual
18 - 30 18 - 30
- 16 - 30 11
Yes Yes
7h
Off 7h, Off
Yes Yes
Yes Yes
--
36 27
--
*575*260 540*770*245
77
2268(2637)
4-Wa
Models TS-C126TDA0 TS-H126TDA0
x
y
y
&
&
R
,
u
Product Specifications
Service Manual 17
Cooling Capacity
Heating Capacity
Power Input Cooling 1260 1180
Heating - 1350
Running Current Cooling 6 5.6
Heating - 6.1
Starting Current Cooling 10.7 9
Heating - 8
EER 2.4(2.79) 2.56(2.98)
COP - 2.6
Power Supply 1Φ,220-240,50 1Φ,220-240,50 Air Circulation Indoor,Max
Outdoor,Ma
Moisture Removal Features Temperature Control
Plasma Filter - ­Nano Plasma Filter - -
Deodorizing Filter Optional Optional
CHAOS Wind(Auto Wind) Airflow Direction(4-Way:Opti Steps, Fan/Cool 3/4 3/4 Airflow Direction Contorl(up Airflow Direction Contorl(left Remocon Type Wireless Simple Wireless Simple Setting Temperature
Temperature Increment Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) 3 3
Special Function
Refrigerant(R22)Charge 770g 860g
Blower Motor Input 42 42
Output 11 11 Motor Input 109 109 Motor Outp
Circuit Breaker A
Power Cord 3*1.0 3*1.0 Connecting Cable 3*1.0 3*1.0
Connecting Tube Liquid Side 6.35(1/4) 6.35(1/4)
(φ. Socket Flare) Gas Side 12.7(1/2) 12.7(1/2)
Length,std 5 5
Drain Hose (O.D , I.D) 21.5,16(0.85,0.63) 21.5,16(0.85,0.63)
Dimension Indoor 166*282*895 166*282*895
Outdoor 245*540*770 245*540*770
Net Weight Indoor
Outdoor 33 33
Unit
kcal/h.(W)
Btu/h.
kcal/h.(W)
Btu/h.
W W
A
A
A
A
kcal/h.W(W/W)
Btu/h.W
W/W
Φ,V,Hz/min(CFM)/min(CFM)
/h.(pts/h.)
Cool Heat
g W W W W
AWG#:P* AWG#:P*
mm(in) mm(in)
m(in)
mm(in)
mm mm
kg kg
3024(3516) 3024(3516)
12,000 12,000
-
- 12,000
9.52 10.17
450 450
1680 1680
1.5 1.5
Thermistor Thermistor
Yes Yes
4-Wa
Auto Auto
Manual Manual
18 - 30 18 - 30
- 16 - 30 11
Yes Yes
7h
Off 7h, Off
Yes Yes
Yes Yes
--
42 42
--
88
3024(3516)
4-Wa
Installation
More than 10cm
More than
5cm
More than 2.3m
More than
5cm
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
I
More than 10cm More than 10cm
More than 60cm
More than 60cm
More than 70cm
Installation
Selection of the Best Location
Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in front of the
unit.
Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway.
Ensure that the space around the left and right of the unit is more than "A". The unit should be installed as high on the wall as possible, allowing a minimum of "B" from ceiling.
Use a stud finder to locate studs to prevent unnecessary damage to the wall.
Install the indoor unit on the wall where the height from the floors more than 2.3 meters.
Grade
5K~28K 10 5
30K~38K 30 12
Clearance(cm)
AB
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location.
Consult local codes regarding rooftop mounting.
Piping Length and Elevation
Max.
(m)
Max.
Elevation
B (m)
Capacity
(Btu/h)
5k~14k
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
30k~38k
Pipe Size
GAS LIQUID
3/8"(Ø9.52) 1/4"(Ø6.35) 4 or 7.5 7 15 20
1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 7 15 20
1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30
3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50
Standard
Length
Length
A (m)
Additional
Refrigerant
(g/m)
Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
Ensure that the space around the back and sides is more than 10cm. The front of the unit should have more than 70cm of space.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a
place where noise and vibration are minimum.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
18 Room Air Conditioner
If case more than 5m
Capacity is based on standard length and maxi­mum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters.
How to Fix Installation Plate Drill a Hole in the Wall
Installation Plate
Type "A" screw
Chassis
Hook
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
Installation plate
Left rear piping Right rear piping
Ø70mm
Ø70mm
DB
A
C
Connecting
part
Adhesive
Drain hose
Only the desired direction
Installation
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with four type A screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning the centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typi­cally. Drilling the hole through the wall for pip­ing connections must be done safely.
Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Open the Front Grille.
Pass Telephone Control Cord Wire through the hole
which the power cord goes through.
Connect Telephone Control Cord Wire to the phone jack
of telephone PCB of Control Box.
Fix Telephone Control Cord Wire inside Control box so
as not to disconnect.
Close the Front Grille.
CHASSIS
(Grade)
7k, 9k, 12k 75 65 105 65
18k, 24k 105 65 260 65
ABCD
Distance (mm)
Drain hose junction
Remove the rubber stopple in the desired drain direc­tion.
Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure by.
Service Manual 19
Flaring work and connection of piping
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Drain hose
Pipe
Reamer
Point down
Flare nut
Copper tube
Flaring work and connection of piping
Flaring work
Carry out flaring work using flaring tool as shown below.
Flaring work
Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the follow­ing procedure.
Cut the pipes and the cable.
Use the piping kit accessory or pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than the measured distance.
Cut the cable 1.5m longer than the pipe length.
Copper
pipe
Slanted Uneven Rough
90°
Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared sec-
tion and re-flare it.
Burr removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe in a downward direc­tion as you remove burrs in order to avoid dropping burrs into the tubing.
Outside diameter A
mm inch mm
Ø6.35 1/4 0~0.5
Ø9.52 3/8 0~0.5
Ø12.7 1/2 0~0.5
Ø15.88 5/8 0~1.0
Ø19.05 3/4 1.0~1.3
Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
Firmly hold copper pipe in a die in the dimension shown in the table above.
20 Room Air Conditioner
Connection of piping -- Indoor
Preparing the indoor unit's piping and drain hose for instal­lation through the wall.
Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis.
Replace the plastic tubing holder in the original position.(Optional)
When install, make sure that the remaining parts must be removed clearly so as not to damage the pip­ing and drain hose, especially power cord and connecting cable.
Flaring work and connection of piping
Drain hose
Connecting
cable
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Plastic bands
Insulation material
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Indoor unit tubing Flare nut Pipes
Drain hose
Connecting pipe
Connecting cable
Tape
Drain hose
For right rear piping
Route the indoor tubing and the drain hose in the direction of rear right.
Insert the connecting cable into the indoor unit from the out­door unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.
Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
Connecting the pipings to the indoor unit and drain hose to drain pipe.
Align the center of the pipes and sufficiently tighten the flare nut by hand.
Tighten the flare nut with a wrench.
Outside diameter Torque
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
When extending the drain hose at the indoor unit, install the
drain pipe.
NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.
*Foamed polyethylene or equivalent is recommended.
Indoor unit installation
Hook the indoor unit onto the upper portion of the installa­tion plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installa­tion plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(click­ing sound).
Wrap the insulation material around the con­necting portion.
Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Wrap the area which accommodates the rear piping hous-
ing section with vinyl tape.
Service Manual 21
Flaring work and connection of piping
Drain pipe
Connecting cable
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Indoor unit tubing Flare nut Pipes
Installation plate
Spacer
Indoor unit
8cm
Plastic bands
Insulation material
Vinyl tape
Adhesive
Drain hose
Indoor unit drain hose
(narrow)
Wrench
Indoor unit tubing
Connection pipe
Flare nut
Open-end wrench (fixed)
Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
For left rear piping
Route the indoor tubing and the drain hose to the required piping hole position.
Insert the piping, drain hose, and the connect­ing cable into the piping hole.
Connecting the pipings to the indoor unit and the drain hose to drain pipe.
Align the center of the pipes and sufficiently tighten the flare nut by hand.
Tighten the flare nut with a wrench.
Outside diameter Torque
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.
Tape the drain hose and the connecting cable.
Connecting cable
Indoor unit installation
Hang the indoor unit from the hooks at the top of the instal­lation plate.
Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.
When extending the drain hose at the indoor unit, install the drain pipe.
Wrap the insulation material around the con­necting portion.
Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
22 Room Air Conditioner
Flaring work and connection of piping
Vinyl tape(narrow)
Connection pipe
Connecting cable
Indoor unit piping
Pipe
Vinyl tape (wide)
Wrap with vinyl tape
Drain hose
Vinyl tape(narrow)
Pipe
Wrap with vinyl tape(wide)
Piping for passage through piping hole
Tubing holder
Drain hose
Connecting
cable
Wrap the area which accommodates the rear piping hous­ing section with vinyl tape.
Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
Indoor unit installation
Remove the spacer.
Ensure that the hooks are properly seated on the installa-
tion plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Installation Information (For left piping)
Good case For left piping. Follow the instruction below.
Press on the upper side of clamp. ( )
Reroute the pipings and the drain hose across the back of the chassis.
Set the pipings and the drain hose to the back of the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.
Unfold the tubing to downward slowly. ( )
Bend the tubing to the left side of chassis.
Service Manual 23
Flaring work and connection of piping
Outdoor unit
Gas side piping (Bigger diameter)
Liquid side piping (Smaller diameter)
Torque wrench
Connection of the pipes-Outdoor
Bad case
Following bending type from right to left could cause
problem of pipe damage.
Align the center of the pipings and sufficiently tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Outside diameter Torque
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
24 Room Air Conditioner
Air
Conditioner
Main power source
NORMAL CROSS-SECTIONAL AREA 0.75mm
2
The power connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Type "B" approved by HAR or SAA).
The power cord connected to the "A" unit should be complied with the following specifications(Type "B" approved by HAR or SAA).
Connecting the cable between indoor unit and outdoor unit
Connect the cable to the Indoor unit.
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.). The earth wire should be longer than the common wires. The above circuit diagram is subject to change without notice. When installing, refer to the circuit diagram on the control box inside Indoor Uint.
When installing, refer to the circuit diagram on the Control Box of Indoor Unit.
When installing, refer to the wiring diagram on the Control Cover Inside Outdoor Unit.
The above circuit diagram is subject to change without notice.
Be sure to connect wires according to the wiring diagram.
Connect the wires firmly, so that not to be pulled out easily.
Connect the wires according to color codes by referring the
wiring diagram.
Connecting the cable between indoor unit and outdoor unit
(mm2)
NORMAL CROSS
-SECTIONAL AREA
Unit(A) Indoor Indoor Indoor Indoor Outdoor Outdoor
Cable Type(B) H05VV-F H05VV-F H05VV-F H05VV-F H05RN-F H05RN-F
5k~9k 12k 14K~18k 24k~28k 30k, 32k 36k, 38k
1.0 1.0 1.5 2.5 2.5 5.5
Grade
If a power plug is not to be used, provide a circuit
breaker between power source and the unit as shown below.
Circuit Breaker
Use a circuit breaker or time delay fuse.
(mm2)
NORMAL
CROSS
-SECTIONAL AREA
Cable Type(B) H07RN-F H07RN-F H07RN-F
Grade
5k~12k 14k~18k 24k~28k
1.0 1.5 2.5
Service Manual 25
Connecting the cable between indoor unit and outdoor unit
Terminal block
Over 5mm
Cover control
Connecting cable
Connecting cable
Connect the cable to the outdoor unit
Remove the control cover from the unit by loosening the screw.
Connect the wires to the terminals on the con­trol board individually.
Secure the cable onto the control board with the cord clamp.
Refix the control cover to the original position with the screw.
Use a recognized circuit breaker "A" between the power source and the unit. A disconnecting device to adequately discon­nect all supply lines must be fitted.
Circuit
Breaker
(A)
5k~14k 18k 24k~28k 30k, 32k 36k, 38k
15 20 30 30 40
Grade
Outdoor Unit
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. (Refer to page 26))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal func-
tion of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.
26 Room Air Conditioner
Checking the drainage and forming the pipings
Pull the right and the left side.
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Waving
Water leakage
Water leakage
Ditch
Less than 50mm gap
Water leakage
Taping
Drain hose
Pipings
Connecting cable
Trap is required to prevent water from entering into electrical parts.
Seal small openings around pipings with a gum type sealer.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap
Checking the drainage and forming the pipings
Checking the drainage Form the piping
To remove the front panel from the indoor unit.
Set the air direction louvers up-and-down to the position(horizontally) by hand.
Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off.
To check the drainage.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the indoor
unit without any leakage and goes out the drain exit.
Form the piping by wrapping the connecting portion of the indoor unit with insulation mate­rial and secure it with two kinds of vinyl tapes.
If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
Tape the piping, drain hose and connecting cable from down to up.
Secure the tapped piping along the exterior wall using sad­dle or equivalent.
Drain piping
The drain hose should point downward for easy drain flow.
Do not make drain piping.
In cases where the Outdoor unit is installed above the Indoor unit perform the following.
Tape the piping and connecting cable from down to up.
Secure the taped piping along the exterior wall. Form a trap
to prevent water entering the room.
Fix the piping onto the wall by saddle or equivalent.
Service Manual 27
Air purgingd
Lo Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Pressure gauge
AIR PURGING
Air purging
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
Pressure in the system rises.
Operating current rises.
Cooling(or heating) efficiency drops.
Moisture in the refrigerant circuit may freeze and block cap-
illary tubing.
Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system.
Air purging with vacuum pump
Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been complet­ed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Leak test
Do a leak test of all joints of the tubing(both indoor and out­door) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
28 Room Air Conditioner
Soap water method
Gas side
Liquid side
Cap
Hexagonal wrench
2-way valve
(Open)
3-way valve
(Close)
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Pressure gauge
Open
Close
(1) Remove the caps from the 2-way and 3-way valves.
(2) Remove the service-port cap from the 3-way valve.
(3) To open the 2-way valve turn the valve stem counter-
clockwise approximately 90°, wait for about 2~3 sec, and close it.
(4) Apply a soap water or a liquid neutral detergent on the
indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping.
(5) If bubbles come out, the pipes have leakage.
Evacuation
Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
Air purgingd
Required time for evacuation when 30 gal/h vacuum
If tubing length is less than 10m (33 ft)
pump is used
if tubing length is longer than 10m (33 ft)
10 min. or more 15 min. or more
When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
Finishing the job
With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
Turn the valve stem of gas side valve counter-clockwise to fully open the valve.
Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready to test run.
Service Manual 29
Test running
Bolt
Tubing connection
Discharge temperature
Discharge air
Intake temperature
Power button
TEST RUNNING
1. Check that all tubing and wiring have been properly con-
NOTE: If the actual pressure is higher than shown, the system is
nected.
2. Check that the gas and liquid side service valves are fully
open.
Settlement of outdoor unit
The air conditioner is now ready for use.
Anchor the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
In the case when the vibration of the unit is conveyed to the hose, secure the unit with an anti-vibration bushing.
1. Connect a low-pressure gauge manifold hose to the
2. Open the gas side service valve halfway and purge the air
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the cooling
Evaluation of the performance
5. When the low-pressure gauge reading becomes 1 to
Operate unit for 15~20 minutes, then check the system refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of air.
3. Ensure the difference between the intake temperature and
the discharge is more than 8°C(46°F) (Cooling) or
Power-Failure Compensation Function User Selection ON/OFF
1) Operation Sequence
(Heating).
most likely over-charged, and charge should be removed. If the actual pressure are lower than shown, the system is most likely undercharged, and charge should be added.
PUMP DOWN
This is performed when the unit is to be relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the unit cooling mode.
Pump Down Procedure
charge port on the gas side service valve.
from the manifold hose using the refrigerant gas.
operation.
0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been collected in the outdoor unit.
Press the forced switch until BUZZER sounds 2 times (beep~beep~).
Release the forced switch if BUZZER sounds.
4. For reference; the gas side pressure of optimum condition
is as below.(Cooling)
Refrigerant
Outside ambient
TEMP.
The pressure of the gas side
service valve.
R-22 35°C (95°F) 4~5kg/cm2G(56.8~71.0 P.S.I.G.)
R-410A 35°C (95°F) 8.5~9.5kg/cm2G(120~135 P.S.I.G.)
30 Room Air Conditioner
Check the function selection ON/OFF with the operation LED.
2) Checking function-selection ON/OFF
- Function-Selection ON: One time blinking of operation LED
would repeat 4 times.
- Function-Selection OFF: Two times blinking of operation LED
would repeat 4 times.
Operation
Function of Controls
• DISPLAY
1) C/O Model
Operation Indicator
ON while in appliance operation, OFF while in appliance pause.
Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Comp. Running Incidator
While in appliance operation, ON while in outdoor unit compressor running, OFF while in compressor off.
2) H/P Model
Operation Indicator
ON while in appliance operation, OFF while in appliance pause.
Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Operation
Timer Indicator
ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Defrost Indicator
OFF except when hot start during heating mode operation or while in defrost control.
Cooling Mode Operation
When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop.
When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp Setting Temp+0.5°C Compressor OFF Temp Setting Temp-0.5°C
While in compressor running, operating with the airflow speed set by the remote control. While in compressor not running, operating with the low airflow speed regardless of the setting.
Healthy Dehumidification Mode
When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature.
26°C Intake Air Temp 25°C 24°C Intake Air Temp<26°C Intake Air Temp-1°C 18°C Intake Air Temp<24°C Intake Air Temp-0.5°C Intake Air Temp<18°C 18°C
Service Manual 31
Operation
While in compressor off, the indoor fan repeats low airflow speed and pause.
While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat. Compressor ON Temp. Setting Temp+0.5°C Compressor OFF Temp. Setting Temp-0.5°C
In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Heating Mode Operation
When the intake air temp reaches +3°C above the setting temp, the compressor is turned off. When reaches
the setting temp, the compressor is turned on. Compressor ON Temp. Setting Temp. Compressor OFF Temp. Setting Temp.+3°C
While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 28°C , it
operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it oper­ates with Super-Low(while in sleep mode, with the medium airflow speed).
While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it
operates with the low airflow speed.
If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the
outdoor fan is turned on/off according to the indoor pipe temp.
While in defrost control, both of the indoor and outdoor fans are turned off.
Defrost Control
While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing, reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
After 40 min heating mode operation, at 4 min interval, whether to carry out defrost control or not and the time of defrost control are determined according to the following conditions.
1) While in heating mode operation, the maximum of the indoor pipe temperature is measured and it is com-
pared with the present indoor pipe temperature to get the difference of the indoor pipe temperatures (=the maximum temperature of indoor pipe ? the present temperature of indoor pipe), according to which, whether to carry out defrost control or not is determined.
2) According to the need of defrost control shown above and the elapsed time of heating mode operation at that
moment, the defrost control time is determined.
3) When the determined time of defrost control is below 7 min, heating mode operation continues without carry-
ing out defrost control. According to the procedure stated above, the determination is made again. When the defrost control time is 7 min or longer, defrost control is then carried out.
While in defrost control, the minimum temp of the indoor pipe is measured and it is compared with the present temp of the indoor pipe to get the difference of the indoor pipe temperatures (=the present temperature of the indoor pipe ? the minimum temperature of the indoor pipe). When the difference is 5°C or higher, defrost con­trol is completed and heating mode operation is carried out.
While in defrost control, if the defrost time determined before the start of defrost control is completed, defrost control stops and heating mode operation is carried out regardless of the above condition.
When the indoor pipe temp is 42°C or above, defrost control is not carried out even if the condition is one of the defrost conditions above.
While in defrost control, the compressor is on and the indoor fan, the outdoor fan, and the 4 way valve are off.
32 Room Air Conditioner
Operation
Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow speed selection key on the remote control.
Sleep Timer Operation
When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli­ance operation, the operation of the appliance stops.
While the appliance is on pause, the sleep timer mode cannot be input.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C. After another 30 min elapse, it increases by 1°C again.
When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.
Chaos Natural Wind Mode
When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air­flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
Jet Cool Mode Operation (C/O Model)
If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Jet Cool Mode Operation (H/P Model)
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Forced Operation
Operation procedures when the remote control can't be used.
The operation will be started if the power button is pressed.
If you want to stop operation, re-press the button.
Cooling Model
Operating mode Cooling Cooling Healthy Dehumidification Heating
Indoor FAN Speed
Setting Temperature
High High High High
22°C22°C23°C24°C
Room Temp. ≥ 24°C 21°C ≤ Room Temp. < 24°C Room Temp. < 21°C
Heat pump Model
While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation.
Service Manual 33
Operation
Test operation
During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem­perature and resets in 18±1 minutes.
During test operation, if remote controller signal is received, the unit operates as remote controller sets. If you want to use this operation, open the front panel upward and Press the power button let it be pressed for about 3 seconds.
If you want to stop the operation, re-press the button.
Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions.
Protection of the evaporator pipe from frosting
If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool­ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting.
When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the outdoor fan is turned on according to the condition of the room temperature.
Buzzer Sounding Operation
When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
When the appliance-pause key is input by the remote control, the long "beep" sounds.
34 Room Air Conditioner
Display Function
3sec 3sec 3sec
(once)
1. Heating Model 2. Cooling Model
Operation
Operation Indicator
Cooling, Soft Dry, Fan, Heating Cooling, Soft Dry, Fan
Deicer Indicator
Hot-start, Deice
Operation Indicator
Compressor on Indicator
Self-diagnosis Function
Error
Code
1
Error Display LED
(Indoor body operation LED)
Error contents
Indoor room temperature thermistor open/short
Indoor pipe temperature thermistor open/short.
OUT
DOOR
SVC check point
Indoor Thermistor assembly check
Service Manual 35
36 Service Manual
3
4
Disassembly
Earth Conductor
Indoor Unit
Disconnect the unit from power supply before mak­ing any checks. Be sure the power switch is set to OFF.
To remove the Grille from the Chassis.
Set the up-and-down air discharge louver to open position (horizontally) by finger pressure.
Remove the securing screws.
To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift it straight upward.
Disassembly
1. Before removing the control box, be sure to
take out the wire screwed at the other end.
Service Manual 37
Disassembly
Screw
2. To remove the Control Box.
Remove securing screws.
Pull the control box out from the chassis
carefully.
3. To remove the Discharge Grille.
Unhook the discharge grille and pull the discharge grille out from the chassis carefully.
4. To remove the Evaporator.
Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right 1EA).
When repair, do not damage the Caution label.
38 Room Air Conditioner
Unhook the tab on the right inside of the chassis
Motor cover
Bearing
Cross-flow fan
at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.
5. To remove the Motor Cover
Remove 2 securing screw.
Pull the motor cover out from the chassis
carefully.
Disassembly
6. To remove the Cross-Flow Fan
Loosen the screw securing the cross-flow fan to the fan motor (do not remove).
Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan.
Remove the left end of the cross-flow fan from the self-aligning bearing.
Service Manual 39
Schematic Diagram
Schematic Diagram
Electric Control Device
Heat Pump Model(LED TYPE)
40 Room Air Conditioner
Wiring Diagram
Indoor Unit
Models: SE 9k,12k Cooling only Model
Schematic Diagr am
POWER
YL
/
MOTOR
BL
BR
GN
BR
SH-CAPA
YL
/
BL
BR
GN
T/BLOCK
YL
/
BL
BR
GN
TO OUTDOOR UNIT
YL
OR
BK
PWB ASM
CN-MOTOR
CN-TAB2 CN-TAB1
RY-COMP
CN-DISPLAY
DISPLAY PWB ASM
CN-TH
SSR
ZNR
CN-U/D
FORCE S/W
FUSE
)
(250V/2A
CN-FORCE
CN-SUB
INDOOR WIRING DIAGRAM
Models: SE 9k,12k Heat pump Model
POWER
YL
/
N
BL
BR
G
BR
K C O L
1(L)32(N)
B
/ T
R B
TO OUTDOOR UNIT
SH-CAPA
BL
L B
MOTOR
BR
YL
/
N G
YL
/
N G
OR
PWB ASM
MOT
­N C
OR
BK
YL
BK
RD
BK
RD
4
B1 A T
­N C
B2
N-TA C
RY-COMP
RY-4WAY
RY-FAN
CN-DISPLAY
DISPLAY PWB ASM
SSR
FUSE
(250V/2A
ZNR
INDOOR WIRING DIAGRAM
THERMISTOR
N-TH C
D
STEP
U/
MOTOR
N­C
FORCE S/W
)
CN-FORCE
UB S
SUB PCB
N­C
THERMISTOR
STEP MOTOR
SUB PCB
CN-F/G
F/G
MOTOR
STEP
CN-F/G
R
G
TO
EP
F/
MO
ST
Service Manual 41
Wiring Diagram
Indoor Unit
Models: SY 9k,ST 12k Cooling only Model
Schematic Diagr am
POWER
YL
/
MOTOR
BL
BR
GN
BR
SH-CAPA
BL
BR
2(N)1(L)
T/BLOCK
BL
BR
TO OUTDOOR UNIT
CN-MOTOR
CN-MOTOR
OR
BK
YL
CN-TAB1
CN-TAB2
YL
/
GN
DISPLAY PWB ASM
3
YL
/
GN
PWB ASM
SSR
ZNR
FUSE
4 3
(250V/2A
RY-COMP
)
INDOOR WIRING DIAGRAM
FORCE S/W
CN-TH
THERMISTOR
STEP MOTOR
CN-U/D
Models: SY 9k,ST 12k Heat pump Model
POWER
L Y
/
L
N
R
MOTOR
B
B
G
YL
BR
SH-CAPA
L Y
/
R
BL
B
BK
GN
1(L)2(N)
T/BLOCK
YL
/
BK
BL
BR
GN
TO OUTDOOR UNIT
R
R
PWB ASM
O
O
T
OT
MO N-
C
N-M
TRIAC
C
OR
BK
SSR
1 B A
-T N C
2 B A
-T N C
34
RY-COMP
RY-4WAY
RY-FAN
RD
DISPLAY PWB ASM
43
D R
FORCE S/W
H T
N­C
THERMISTOR
ZNR
D
STEP
U/
-
MOTOR
N C
FUSE
(250V/2A
)
INDOOR WIRING DIAGRAM
Service Manual 42
Schematic Diagram
Outdoor Unit
Models: Cooling only Model
BLUE
CAPACITOR
H
C
F
BLUE
GREEN
R
C
BROWN
OVERLOAD PROTECT
BROWN
TERMINAL BLOCK
RED
BLUE
S
COMP
YELLOW/GREEN
BROWN
BLUE
1(L)
2(N)
BLUE
BROWN
YELLOW
THE UNIT INDOOR
OUTDOOR DIAGRAM WIRING
Models: Heat pump Model
BLUE
RED
FAN
YELLOW
S
R
COMP
C
BROWN
YELLOW/GREEN
OVERLOAD PROTECT
BROWN
1(L)
YELLOW/GREEN
OUTDOOR DIAGRAM WIRING
RED
BLUE
BROWN
BLUE
3
2(N)
BLUE
BROWN
THE UNIT INDOOR
H
VALVE,REVERSING
BLUE
4
RED
BLACK
CAPACITOR
C
BLUE
BLUE
TERMINAL BLOCK
RED
F
FAN
YELLOW
43 Room Air Conditioner
Schematic Diagram
Components Location
MAIN P.W.B ASSEMBLY
TOP VIEW
BOTTOM VIEW
44 Room Air Conditioner
DISPLAY ASSEMBLY
Schematic Diagram
Service Manual 45
Troubleshooting Guide
INDOOR UNIT OUTDOOR UNIT
INDOOR UNIT OUTDOOR UNIT
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
COMPRESSOR
ACCUMU LATOR
GAS SIDE
GAS SIDE
3-WAY VALVE
LIQUID SIDE
LIQUID SIDE
3-WAY VALVE
CAPILLARY TUBE
CAPILLARY TUBE
CHECK VALVE
(Heating Model only)
COOLING HEATING
REVERSING VALVE (Heating Model Only)
Troubleshooting Guide
Refrigeration Cycle Diagram
(1) Cooling Only Models
(2) Cooling & Heating Models
46 Room Air Conditioner
2-way, 3-way Valve
Valve cap
Open position Closed position
Pin
Service port
Service port cap
To outdoor unit
Flare nut
To piping connection
To outdoor unit
Hexagonal wrench (4mm)
Open position Closed position
To piping connection
Flare nut
Troubleshooting Guide
2-way Valve (Liquid Side) 3-way Valve (Gas Side)
Works
Shipping
Air purging
1.
(Installation)
Operation
Pumping down
2. (Transfering)
Evacuation
3.
(Servicing)
Gas charging
4.
(Servicing)
Pressure check
5.
(Servicing)
Gas releasing
6. (Servicing)
Shaft position Shaft position Service port
Closed Closed Closed
(with valve cap) (with valve cap) (with cap)
Open Closed Open
(counter-clockwise) (clockwise) (push-pin or with
vacumm pump)
Open Open Closed
(with valve cap) (with valve cap) (with cap)
Closed Open Open
(clockwise) (counter-clockwise) (connected manifold
gauge)
Open Open Open
(with charging
cylinder)
Open Open Open
(with charging
cylinder)
Open
(with charging cylinder)
Open
(with charging cylinder)
Service Manual 47
Open Open
Open Open
Troubleshooting Guide
Lo
Closed
Purge the air
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
2-Way valve
3-Way valve
CLOSE
Pumping Down
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the open position.
– Remove the valve stem caps and confirm that
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(2) Operate the unit for 10 to 15 minutes.
(3) Stop operation and wait for 3 minutes, then
(4) Air purging of the charge hose.
(5) Set the 2-way valve to the closed position.
connect the charge set to the service port of the 3-way valve.
– Connect the charge hose with the push pin to
the service port.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.
48 Room Air Conditioner
(6) Operate the air conditioner at the cooling
cycle and stop it when the gauge indicates 1kg/cm2g.
(7) Immediately set the 3-way valve to the closed
position.
– Do this quickly so that the gauge ends up indi-
cating 3 to 5kg/cm2g.
(8) Disconnect the charge set, and mount the 2-
way and 3-way valves stem nuts and the ser­vice port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
Do not use the existing charge set for R-22. It is necessary to use new charge set for R-410A. The pressure of R-410A is 1.6 times higher than that of R-22. Thus, the high pressure side gauge of charge set should be used higher pressure gauge of 50kg/cm2 range.
Balance Refrigerant of the 3-way Valve
Lo
Open
Open
3-Way valve
3-Way valve
Gas side
CLOSEOPEN
Outdoor unit
Liquid side
Indoor unit
(Gas leakage)
Troubleshooting Guide
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat.
(2) Connect the charge set to the 3-way valve’s
port.
Leave the valve on the charge set closed. Connect the charge hose to the service port.
(3) Open the valve (Lo side) on the charge set and
discharge the refrigerant until the gauge indi­cates 0 kg/cm2G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not running is higher than 1 kg/cm2G), discharge the refrig­erant until the gauge indicates 0.5 to 1
2
kg/cm sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will also be discharged.
G. if this is the case, it will not be neces-
Service Manual 49
Troubleshooting Guide
Lo
Open
Open
Vacuum pump
3-Way valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way valve
CLOSE
OPEN
Evacuation
(All amount of refrigerant leaked)
Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that the gauge needle does not move (approxima­tely 5 minutes after turning off the vacuum pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted, replenish as needed.
Use vacuum pump equipped with check value applied to be prevented from flowing backward.
50 Room Air Conditioner
Gas Charging
(After Evacuation)
Troubleshooting Guide
Indoor unit
Check valve
Charging cylinder
Lo
(1)
OPEN
Procedure
(1) Connect the charge hose to the charging
cylinder.
– Connect the charge hose which you dis-con-
nected from the vacuum pump to the valve at the bottom of the cylinder.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the sys­tem can be charged with liquid.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to purge the air. (Be careful of the liquid refriger­ant). The procedure is the same if using a gas cylinder.
Liquid side
Gas side
CLOSE
3-Way
Open
valve
Open
3-Way valve
\
Outdoor unit
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
(4) Immediately disconnect the charge hose from
the 3-way valves service port.
– Stopping partway will allow the gas to be dis-
charged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the spec-
ified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not suffi­cient, wait approximately 1 minute and then repeat the procedure (pumping down-pin).
(5) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
This unit is charged with R-410A. Pay attention not to charge R-22.
Service Manual 51
52 Room Air Conditioner
Troubleshooting Guide
Additional gas charging
(Gas leakage)
• When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal operating suc­tion pressure.
• Use the graph or the equation below to get operating suction pressure according to indoor and outdoor tem­perature. Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.
The method of using graph
- Find outdoor temperature.
- Find indoor temperature onto the curve of outdoor temperature.
- Read suction pressure at the axis of ordinates.
The method of using equation
-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.
13
(At operating the Unit for 10 minutes)
Suction Pressure
(Kg/cm
2
.g)
Outdoor Temp.
(˚C)
Indoor Temp. (˚C)
12 11 10
9 8 7 6 5
5 10152025303540
50˚C
40˚C
30˚C
20˚C 10˚C
0˚C
P = 3 + 0.0123 x Tout
1.5
+ 0.8 x Tin
0.5
Where, P : Suction Pressure(kg/cm
2
.
g) Tout : Outdoor Temperature(˚C) Tin : Indoor Temperature(˚C)
Operating Suction Pressure (For R401A)
(According to Indoor & Outdoor Temperature)
Cycle Parts
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Troubleshooting Guide
Temp. Difference
Operating Current
Temp. difference : approx. 0°C Current : less than 80% of
rated current
Temp. difference : approx. 8°C Current : less than 80% of
rated current
Temp. difference : less than 8°C Current : over the reated
current
Temp. difference : over 8°C
All amount of refrigerant leaked out. Check refrigeration cycle.
Refrigerant leakege Clog of refrigeration cycle Defective compressor
Excessive amount of refrigerant
Normal
NOTICE
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Suction pressure Temperature
(Compared with (Compared with Cause of Trouble Description
the normal value) the normal valve)
High
Higher
Normal refrigerant rise at the beginning of
Lower Higher refrigerant (Leakage)
Defective compressor Current is low. Defective 4-way reverse valve
Excessive amount of High pressure does not quickly
operation.
Insufficient amount of Current is low.
Clogging Current is low.
NOTICE
1. The suction pressure is usually 8.5~9.5 kg/cm2G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
Service Manual 53
Troubleshooting Guide
Electronic Parts
Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
(After 10 seconds)
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
NO
Check the voltage of power(About AC 220V, 60Hz)
(About AC 220/240V, 50Hz)
Main power's voltage
Voltage applied to the unit
Connecting method of Indoor/Outdoor connecting
cable
Check PWB Assembly
- Fuse
- Pattern damage
- Varistor(ZNR01J)
Check the connection housing for contacting
Connector related to CN-NI, RY-COMP NO.3
Connector related to CN-MOTOR
Connector contacting of Outdoor Fan/Compressor
Display PCB Assembly Check
YES
Primarily, the operating condition of Micom is OK.
Check each load(Indoor/Outdoor Fan Motor, Compressor, Stepping Motor) and contacting condition of related connector
Items
SMPS Transformer (Indoor unit)
- Input Voltage
- Output Voltage(C03D)
IC01D(7805) Output (Indoor/Outdoor unit)
IC01A(KIA7036, Reset IC) OSC01B(8MHz)
54 Room Air Conditioner
Main PCB Board Operation Check
Content Remedy
- About AC220V/240V±10% - Check the power voltage
- About DC12V
DC +5V
Voltage of IC No.1,
(DC +4.5V over) and Soldering condition.
Replace Trans
Replace IC01D
Replace faulty parts
The product is not operate with the remote controller.
Turn on Main Power
While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.
When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller. (When operated in the Sleeping Mode, the wind speed is set to the low speed by force.)
Troubleshooting Guide
Cause by the remote control
When the mark( ) is displayed in LCD screen, replace battery.
Check the connecting circuit between the remote controller MICOM (No. ) - R16(1.5k) - IR LED - TR - R17(1Ω).
or
MICOM (No. ) - R1(1.5k) - IR LED - TR - R2(1).
61
Caused by other parts except the remote control
Check the contact of CN-DISP1 connector.
Check Display PCB Assembly
- Voltage between CN DISP1 - : DC +5V
Check point
Check the connecting circuit between CN-DIS1 ­R11L(100) - C01A(100nF) - MICOM PIN
Check Receiver Assembly
Service Manual 55
Troubleshooting Guide
Compressor/Outdoor Fan are unable to drive.
Turn on Main Power
Operate "Cooling Mode( )" by setting the desired temperature of the remote controller is less than one of the indoor temperature by 1°C at least.
When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor Fan is stopped.
Check the related circuit of RY-FAN.
Check the indoor temperature sensor is disconnected or not(About 10k/ at 25°C).
Check Relay(RY - COMP) for driving compressor.
When the power(About AC220V/240V) is applied to the connecting wire terminal support transferred to compressor, PWB Assembly is normal.
Check the circuit related to the relay.
Check point COMP ON COMP OFF
Between Micom(No.
59) and GND
Between IC01M(No. 15) Below DC 1V
and GND (app)
Turn off Main Power
Check the electrical wiring diagram of outdoor side.
Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor.
Check the "open" or "short" of conmecting wires between indoor and outdoor.
DC5V DC0V
About DC12V
56 Room Air Conditioner
When indoor Fan does not operate.
Turn off Main power
Check the connection of CN-MOTOR
Check the Fan Motor
Check the Fuse(AC250V/T2A)
Troubleshooting Guide
Check the related circuit of indoor Fan Motor.
The pin NO 58 of Micom, and the part for driving TRIAC(the input and output signal of IC01M, PIN NO 1, 16)
Check the pattern
Check the TRIAC
- TRIAC Open: Indoor Fan Motor never operate
- TRIAC short: Indoor Fan Motor always operates in case of ON or OFF.
Turn ON Main Power
Check the TRIAC high speed operation by remote control.
(The Indoor Fan Motor is connected)
The voltage of PIN NO 1(orange) and 3(yellow) of CN-MOTOR.
About AC 180V over About AC 50V over
TRIAC is not damaged TRIAC Check
Service Manual 57
Troubleshooting Guide
When Vertical Louver does not operate.
Confirm that the Vertical Louver is normally geared with the shaft of
Stepping Motor.
If the regular torque is detected when rotating the Vertical Louver with
hands Normal
Check the connecting condition of CN-U/D Connector
Check the soldering condition(on PWB) of CN-U/D Connector
Check the operating circuit of the Vertical Louver
Confirm that there is DC +12V between pin (RED) of CN-U/D and GND.
Confirm that there is a soldering short at following terminals.
- Between , , and of MICOM
- Between , , and of IC01M
- Between , , and of IC01M
60 61 62 63
If there are no problems after above checks
Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver
58 Room Air Conditioner
When Heating does not operate
Operate Heating Mode( ) by setting the desired temperature of the remote control is higher than one of the indoor temperature by 2°C at least.
In heating Mode, the indoor fan operates in case the pipe temperature is higher than 28°C.
Check the connector of intake and pipe sensor(thermistors)
Check the related circuit of RY-4WAY
Check the indoor room temperature is disconnected or not (about
10K/at 25°C).
Check the indoor pipe temperature is disconnected or not (about
5K/at 25°C).
Troubleshooting Guide
Turn ON Main Power
Check the DC voltage on the PWB ASSEMBLY
The details of check are as followings
Comp Relay.
Check point
Between Micom
(NO.59) and GND
Between IC01M
(NO.15) and GND
Comp ON
DC 5V
Below DC 1V
Comp OFF
DC 0V
About DC
12V
4 way Relay
Check point
Between Micom
(NO.51) and GND
Between IC02M
(NO.11) and GND
4 way ON
DC 5V
Below DC 1V
4 way OFF
DC 0V
About DC 12V
Outdoor fan Relay
Check point
Between Micom
(NO.53) and GND
Between IC02M
(NO.12) and GND
Fan ON
DC 5V
Below DC 1V
Fan OFF
DC 0V
About DC 12V
Service Manual 59
Troubleshooting Guide
Check the electrical wiring diagram of outdoor side.
Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor, 4 way.
Check the "open" or "short" of connecting wires between indoor and outdoor.
Turn off Main Power
60 Room Air Conditioner
135301
152302
342800
264110
263230
359011
131410 733010
135312
135311
159901
268712
146811
668713
346810
266090
135516
35211B
354210
249951
268714
267110
Exploded View
Exploded View
Indoor Unit
Service Manual 61
Exploded View
559010
552202
552111
649950
430410
552203-2
546810
435301
437210
561410
567502
554160
552203-1
552116
447910
W0CZZ
552201
554031
237205
437212
237204
435511
550140
552102-1
Outdoor Unit: 9k Heat Pump,12k Series
62 Room Air Conditioner
Service Manual 63
554031
435512
437212
435511
W0CZZ
552202
552116
554160
550140
552203-2
552203-1
430410
447910
649950
552111
552201
552102-1
552102-2
437210
435301
559010
546810
561410
Outdoor Unit: 9k Cool Only Seriess
Exploded View
Replacement Parts list
Replacement Parts list
Service Manual 64
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
Parts List (Indoor)
LOCATION
No.
430410 3041A20013H 3041A20092B 3041A20013H 3041A20092B R 435301 3530A10059B 3530A20093E 3530A10059B 3530A20093E R 435511 2H02384C 2H02384C 2H02384C 2H02384C R 437210 3721A20050E 3721A10099K 3721A20050E 3721A10099K R 437212 3721A20054F 3720A10016S 3721A20054F 3720A10016S R 435512 3550A20046B -- 3550A20046B -- R 447910 4790A10025D 4790A10007B 4790A10025D 4790A10007B R 546810 4681A10020M 4681A10020A 4681A10020M 4681A10020J R 550140 4984AR4361A 4984AR4390A 4984AR4361A 4984AR4390A R
552102 5210A21761V 5424AR3531E 5210A31413A 3H01535Y R 552203-1 5220AR2609D 5220AR2609F 5220AR2609F 5220AR2609F R 552203-2 5220AR2578C 5220A20003E 5220AR2578F 5220A20003E R
554031 5403A20106E 5403A20113G 5403A20106E 5403A20113Q R
554160 2520UCAK044 2520UCAJ020 2520UCAK044 TBZ31018301 R
559010 5900AR1266D 5901A10057A 5900AR1266D 5901A10057A R
567502 6750U-L002A 6750U-L016A 6750U-L002A -- R
W0CZZ 2A00986Q 2H01451P 2A00986Q 2H01451S R
DESCRIPTION
BASE ASSEMBLY ,OUT
GRILLE DISCHARGE
COVER ASSEMBLY ,CONTROL
PANEL ASSEMBLY,FRONT
Panel Assembly,Rear
COVER
BARRIER ASSEMBLY,OUTDOOR
MOTOR ASSEMBLY,OUTDOOR
ISOLATOR,COMP TUBE CAPILLARY
VALVE,SERVICE VALVE,SERVICE
CONDENSER ASSEMBLY,BEND
COMPRESSOR,SET
FAN ASSEMBLY,PROPELLER
O.L.P
CAPACITOR,DRAWING
TS-C096EMA0 TS-C126EMA0 TS-C096YDA0 TS-C126TDA0
PART No.
REMARK
LOCATION
Replacement Parts List
Parts List (Indoor)
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
65 Room Air Conditioner
No.
131410 3141A20035B 3141A20035B 3141A20019G 3141A20035C R 135311 3531A10367D 3531A10367D AEB30975809 AEB31754004 R 135312 3531A11023V 3531A11023V AEB30975913 AEB30934408 R 135516 3551A30166A 3551A30166A 3551A30166A 3551A30166A R 146811 4681A20117A 4681A20117A 4681A20117A 4681A20117A R 152302 5230A20064A 5230A20064A MDJ32395201 MDJ34608301 R 263230 6323A20043A 6323A20043A 6323A24001A 6323A20004A R 264110 6411A30001R 6411A30001R 6411A30001R 6411A30001R R 267110 6711A20091M 6711A20091M 6711A20111D 6711A20111D R 268712 6871A20996A 6871A20996A 6871A30044D 6871A30044D R 268714 6871A20925A 6871A20925A EBR32724404 EBR32724407 R 268714 6871A20995C 6871A20994A - - R 268714 6871A20994A 6871A20993A - - R 268714 6871A20993A - - - R 342800 4280A20004A 4280A20004A 4280A20004A 4280A20004A R 346810 4681A10023P 4681A10023P 4681A10023P 4681A10023S R
35211B 5211A21144T 5211A21144U 5211A21144H 5211A21144U R
354210 5421A20262C 5421A20263B ADL31252801 5421A20263E R 354210 5421A20263B 5421A20262C ADL31252601 5421A20262C R 359011 5901A20017H 5901A20017H 5901A20017A 5901A20017H R 733010 3301A20020G 3301A20020G 3301A20020J 3301A20020G R
W0CZZ 3H01487A 3H01487A 3H01487A 3H01487A R
DESCRIPTION
CHASSIS ASSEMBLY
GRILLE ASSEMBLY,DISCHARGE
GRILLE ASSEMBLY,FRONT
COVER ASSEMBLY, MOTOR
MOTOR ASSEMBLY ,STEP
FILTER(MECH.),A/C
THERMISTOR,ASSEMBLY
POWER CORD ASSEMBLY
REMOTE CONTROLLER ASSEMBLY
PWB(PCB) ASSEMBLY,DISPLAY
PWB(PCB) ASSEMBLY,MAIN PWB(PCB) ASSEMBLY,MAIN PWB(PCB) ASSEMBLY,MAIN PWB(PCB) ASSEMBLY,MAIN
BEARING
MOTOR ASSEMBY,INDOOR
TUBE ASSEMBLY,TUBING EVAPORATOR ASSEMBLY,FIRST EVAPORATOR ASSEMBLY,FIRST
FAN ASSEMBLY,CROSS FLOW
PLATE ASSEMBLY,INSTALL
CAPACITOR,DRAWING
TS-H096EMA0 TS-H126EMA0 TS-H096YDA0 TS-H126TDA0
PART No.
Remark
Replacement Parts List
Parts List (Outdoor)
Service Manual 66
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
LOCATION
No.
430410 3041A20013H 3041A20092B 3041A20013H 3041A20092B R 435301 3530A10059B 3530A20093E 3530A10059B 3530A20093E R 435511 2H02384C 2H02384C 2H02384C 2H02384C R 437210 3721A20050E 3721A10099K 3721A20050E 3721A10099K R 437212 3721A20054F 3720A10016S 3721A20054F 3720A10016S R 447910 4790A10025D 4790A10007B 4790A10025D 4790A10007B R 546810 4681A10020M 4681A10020A 4681A10020M 4681A10020J R 550140 4984AR4361A 4984AR4390A 4984AR4361A 4984AR4390A R
552102 5210A21761V 5424AR3531E 5210A31413A 3H01535Y R 552203-1 5220AR2609D 5220AR2609F 5220AR2609F 5220AR2609F R 552203-2 5220AR2578C 5220A20003E 5220AR2578F 5220A20003E R
554031 5403A20106E 5403A20113G 5403A20106E 5403A20113Q R
554160 2520UCAK044 2520UCAJ020 2520UCAK044 TBZ31018301 R
559010 5900AR1266D 5901A10057A 5900AR1266D 5901A10057A R
567502 6750U-L002A 6750U-L016A 6750U-L002A -- R
W0CZZ 2A00986Q 2H01451P 2A00986Q 2H01451S R
DESCRIPTION
BASE ASSEMBLY ,OUT
GRILLE DISCHARGE
COVER ASSEMBLY ,CONTROL
PANEL ASSEMBLY,FRONT
Panel Assembly,Rear
BARRIER ASSEMBLY,OUTDOOR
MOTOR ASSEMBLY,OUTDOOR
ISOLATOR,COMP TUBE CAPILLARY
VALVE,SERVICE VALVE,SERVICE
CONDENSER ASSEMBLY,BEND
COMPRESSOR,SET
FAN ASSEMBLY,PROPELLER
O.L.P
CAPACITOR,DRAWING
TS-C096EMA0 TS-C126EMA0 TS-C096YDA0 TS-C126TDA0
PART No.
REMARK
Replacement Parts List
Parts List (Outdoor)
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
Service Manual 67
LOCATION
No.
430410 3041A20092B 3041A20092B 3041A20092B 3041A20092B R
435301 3530A20093E 3530A20093E 3530A20093E 3530A20093E R
435511 2H02384C 2H02384C 2H02384C 2H02384C R
437210 3721A10099K 3721A10099K 3721A10099K 3721A10099K R
437212 3720A10016S 3720A10016S 3720A10016S 3720A10016S R
447910 4790A10007B 4790A10007B 4790A10007B 4790A10007B R
546810 4681A10020A 4681A10020J 4681A10020A 4681A10020J R
550140 4984AR4390A 4984AR4390A 4984AR4390A 4984AR4390A R 552102-1 5210A21761X 5210A31782B 3H01535W 5210A31413E R 552102-2 5210A26883A 5424AR3531E 3H03750G 5424AR3531E R
552201 5220A30001A 5220A30001A 5220A23002D 5220A23002C R
552202 5220AR3084C 5220AR3084C 5220AR3084C 5220AR3084C R 552203-1 5220AR2609F 5220AR2609F 5220AR2609F 5220AR2609F R 552203-2 5220AR2578F 5220A20003E 5220AR2578F 5220A20003E R
554031 5403A20188B 5403A20113P 5403A20188B 5403A20101N R
554160 2520UCAK052 2520UCAJ047 TBZ30817001 TBZ31126301 R
559010 5901A10057A 5901A10057A 5901A10057A 5901A10057A R
567502 6750U-L002A 6750U-L027A 6750U5L005B -- R
W0CZZ 2A00986Q 2H01451S 2H01451P 2H01451S R
DESCRIPTION
BASE ASSEMBLY ,OUT
GRILLE DISCHARGE
COVER ASSEMBLY ,CONTROL
PANEL ASSEMBLY,FRONT
GRILLE REAR
BARRIER ASSEMBLY,OUTDOOR
MOTOR ASSEMBLY,OUTDOOR
ISOLATOR,COMP TUBE CAPILLARY TUBE CAPILLARY
VALVE,CHECK
VALE,REVERSING
VALVE,SERVICE VALVE,SERVICE
CONDENSER ASSEMBLY,BEND
COMPRESSOR,SET
FAN ASSEMBLY,PROPELLER
O.L.P
CAPACITOR,DRAWING
TS-H096EMA0 TS-H126EMA0 TS-H096YDA0 TS-H126TDA0
PART No.
REMARK
Loading...