LG RCAW Operation & Maintenance Manual

Page 1
Operation & Maintenance Manual
LG
MODELS: RCAW - Compact (50Hz)
website http://www.lgservice.com
IMPORTANT
• Please read this Operation & Maintenance Manual completely before Operating & Maintenance the product.
• Please retain this Operating & Maintenance for future reference after reading it thoroughly.
R134a
Chiller Air-cooled Screw
Page 2
2 Chiller Air-cooled Screw
SAFETY CONSIDERATIONS
Warning...................................................................................................................................3
Caution....................................................................................................................................7
GENERAL
Manipulation of HMI Unit.......................................................................................................11
CONTROLS
PLC and HMI Unit.................................................................................................................21
Machine on/off control...........................................................................................................30
START-UP
Pre Start-up ..........................................................................................................................31
Start-up Procedure................................................................................................................32
Operation Limits....................................................................................................................34
OPERATION
Sequence of Operation.........................................................................................................37
Sensors.................................................................................................................................42
SERVICE
Cycle Components................................................................................................................43
Control System .....................................................................................................................56
Maintenance .........................................................................................................................67
TROUBLE SHOOTING............................................................................................................68
APPENDIX
Wiring Diagram .....................................................................................................................76
Cycle Diagram.......................................................................................................................77
Check List .............................................................................................................................78
Air cooled Screw Operation & Maintenance Manual
TABLE OF CONTENTS
Page 3
Safety Considerations
Operation & Maintenance Manual 3
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical com­ponents, and equipment location (roof, elevated structures, etc). Only trained, qualified installers and service technicians should install, start up, and service this equipment. When working on this equipment, observe pre­cautions in the literature, and on tags, stickers, and labels attached to the equipment, and any other safety pre­cautions that apply. Follow all safety codes. Wear safety glasses and work gloves. Use care in handling, rigging, and setting this equipment, and in handling all electrical components.
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring Instructions in the manual will cause harm or damage. The seriousness is classified by the following indications.
We do not have any responsibility for any failure caused by careless management and natural disaster, and power cord failure regardless of warranty period.
The content in the manual could be changed for the improvement of product without notice.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Have all electric work done by a licensed elec­trician according to "Electric Facility Engineering Standard" and "Interior Wire Regulations" and the instructions given in this manual and always use a special circuit.
• If the power source capacity is inadequate or electric work is performed improperly, electric shock or fire may result.
Ask the dealer or an authorized technician to install the chiller.
• Improper installation by the user may result in water leakage, electric shock, or fire.
SAFETY CONSIDERATIONS
Page 4
Safety Considerations
4 Chiller Air-cooled Screw
For re-installation of the installed product, always contact a dealer or an Authorized Service Center.
There is risk of fire, electric shock, explosion, or injury.
Do not install, remove, or re-install the unit by yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
Do not store or use flammable gas or combustibles near the chiller.
• There is risk of fire or failure of product.
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
When installing and moving the chiller to another site, do not charge it with a different refrigerant from the refrigerant spec­ified on the unit.
• If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may mal­function and the unit may be damaged.
Do not reconstruct to change the settings of the protection devices.
• If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by LGE are used, fire or explosion may result.
Ventilate before operating chiller when gas leaked out.
• It may cause explosion, fire, and burn.
Securely install the cover of control box and the panel.
• If the cover and panel are not installed securely, dust or water may enter the air-cooled unit and fire or electric shock may result.
If the chiller is installed in a small room, mea­sures must be taken to prevent the refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
• Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxygen in the room could result.
Always ground the product.
• There is risk of fire or electric shock.
Always intstall dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock.
Page 5
Safety Considerations
Operation & Maintenance Manual 5
Do not damage or use an unspecified power cord.
• There is risk of fire, electric shock, explosion, or injury.
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock.
Be cautious that water could not enter the product.
There is risk of fire, electric shock, or product damage.
Do not touch the power switch with wet hands.
There is risk of fire, electric shock, explosion, or injury.
When the product is soaked (flooded or submerged), contact an Authorized Service Center.
• There is risk of fire or electric shock.
Take care to ensure that nobody could step on or fall onto the air-cooled unit.
• This could result in personal injury and product damage.
Be careful of the rotating part.
• Be careful not to put your finger or a stick in the rotating part of the fan or pump.
• Do not operate the fan with the protective net removed. It can cause body injury.
Use of undesignated refrigerant and oil is pro­hibited.
• Do not use undesignated refrigerant, freezer oil and brine.
• It can have a critical effect on the compressor and component defects.
• If you would like to use a substitute for the refrig­erant, please contact the manufacturer.
Redesigning the control box is prohibited.
• Lock the control box with possible locking device and if you need to open the control box inevitably, turn off the main power first.
Do not touch the wiring or parts within the control box.
• It can cause electric shock, fire or defects.
Be careful of leakage.
If you find a leakage in the connected part such as pump, piping etc., immediately stop the operation.
• It can cause electric shock, leakage or defects.
Follow the permitted pressure level.
• Follow the regulated pressure for cold water, cool­ing water, refrigerant etc.
• It can cause electricity leakage or burn/frostbite eruption or leakage.
Be cautious of fire, earthquake and lightning.
• If there is natural disaster such as fire or earth­quake, or risk of lightning, immediately stop oper­ating the unit.
• If you continue to operate the unit, it can cause a fire or electric shock.
Page 6
Safety Considerations
6 Chiller Air-cooled Screw
Changing the set value is prohibited.
• Do not change the set value of the safety device.
• If you operate the product with incorrectly set val­ues, it can cause defect, fire or explosion.
• When you change the control setting value, please consult with the specialized expert.
Electric shock prevention.
• When installing the freezer, always ground the wire.
• It can cause electric shock.
Follow all safety codes.
• When working on this equipment, observe pre­cautions in the literature, and on tags, stickers, and labels attached to the equipment, and any other safety precautions that apply.
Wear safety equipment.
• Wear safety glasses and work gloves.
Use care in handling, rigging, and setting this equip­ment, and in handling all electrical components.
Shut off all power to this equipment during installation and service.
Electrical shock can cause personal injury and death.
• There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
Always run fluid through heat exchangers when adding or removing refrigerant charge.
It prevent potential damage to heat exchanger tubes.
• Use appropriate brine solutions in cooler fluid loops to prevent the freezing of heat exchangers when the equipment is exposed to temperatures below 32°F(0°C).
Do not attempt to unbraze factory joints when servicing this equipment. Cut lines with a tub­ing cutter as required when performing ser­vice.
• Compressor oil is flammable and there is no way to detect how much oil may be in any of the refrig­erant lines.
• Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to system.
Do not re-use compressor oil.
• It may cause damage to the product.
Do not vent refrigerant relief valves within a building.
• Outlet from relief valves must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE (American National Standards Institute/American Society of Heating, Refrigeration and Air Conditioning Engineers) 15 (Safety Code for Mechanical Refrigeration).
• The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.
• Provide adequate ventilation in enclosed or low overhead areas. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Refrigerant causes eye and skin irritation.
Page 7
Safety Considerations
Operation & Maintenance Manual 7
Do not leave refrigerant system open to air any longer than necessary.
• Seal circuits being serviced and charge with dry nitrogen to prevent oil contamination when timely repairs cannot be completed.
Always check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Do not install the product where the noise or hot air from the air-cooled unit could damage the neighborhoods.
• It may cause a problem for your neighbors.
Keep level even when installing the product.
• To avoid vibration or water leakage.
Do not install the unit where combustible gas may leak.
• If the gas leaks and accumulates around the unit, an explosion may result.
Use power cables of sufficient current carrying capacity and rating.
• Cables that are too small may leak, generate heat, and cause a fire.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer chiller, not a precision refriger­ation system.
• There is risk of damage or loss of property.
Keep the unit away from children.
• It can cause the injury, such as cutting the finger. Also the damaged fin may result in degradation of capacity.
When installing the unit in a hospital, commu­nication station, or similar place, provide suffi­cient protection against noise.
The inverter equipment, private power generator, high­frequency medical equipment, or radio communication equipment may cause the chiller to operate erroneous­ly, or fail to operate. On the other hand, the chiller may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
Do not install the product where it is exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, could cause product malfunction or inefficient opera­tion.
Page 8
Safety Considerations
8 Chiller Air-cooled Screw
Do not use the chiller in special environments.
• Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the chiller or damage its parts.
Make the connections securely so that the outside force of the cable may not be applied to the terminals.
• Inadequate connection and fastening may gener­ate heat and cause a fire.
Be sure the installation area does not deterio­rate with age.
• If the base collapses, the chiller could fall with it, causing property damage, product failure, or per­sonal injury.
Be very careful about product transportation.
When transporting the chiller, always consult with the specialized expert. When transporting the chiller, make sure to comply with the method regulated in the manual. If not, it can cause overturn, fall etc.
Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
Tear apart and throw away plastic packaging bags so that children may not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
Turn on the power at least 12 hours before starting operation.
• Starting operation immediately after turning on the main power switch can result in severe damage to internal parts. Keep the power switch turned on during the operational season.
Do not touch any of the refrigerant piping dur­ing and after operation.
• It can cause a burn or frostbite.
Do not operate the chiller with the panels or guards removed.
• Rotating, hot, or high-voltage parts can cause injuries.
Do not directly turn off the main power switch after stopping operation.
• Otherwise it may result in oil supply shortage or other problems.
Use a firm stool or ladder when cleaning or maintaining the chiller.
• Be careful and avoid personal injury.
Page 9
Safety Considerations
Operation & Maintenance Manual 9
Be careful of disposal.
• When disposing the device, request to the spe­cialized expert.
Be careful of high voltage.
Install separate wiring for the power and always install and use dedicated power supply and circuit breaker.
• It can cause electric shock or fire.
Be careful of high temperature.
• Because the machine part can be hot, do not
touch it with any part of your body.
• It can cause burns.
Be careful of restarting.
• When the safety device of the product operates, resolve the cause before re-operating.
If you repeat this arbitrarily, it can cause fire and defect.
Be careful of device installation.
• Be careful of the clearance of the device during the installation and make sure there are no sur­rounding obstacles for the air cooling type and that it is well ventilated.
Be careful of sound or odor.
• If you hear a weird sound or smell weird odor, immediately stop operating the unit and contact the service center.
• It can cause fire, explosion and injury.
Check.
• Execute the periodic check. If an issue is found, stop operating the unit and contact the service center.
Insufficient check can cause fire, explosion and defect.
Use appropriate tools.
• Use appropriate tools used for the repair and make sure to calibrate the measuring devices precisely before use.
If you use inappropriate tools etc, it can cause an accident.
Be careful of air cooling type heat exchanger.
• Because the condenser of the air cooling type device is sharp, do not touch the condenser.
• Protective net must always be kept installed.
• It can cause an injury.
It can cause an injury.
• Check the safety label of the safety device.
• Follow upper precautions and labels. If not, it can cause injury or damage such as a fire etc.
• To prevent the generation of condensed water, the connecting pipe to the evaporator, as well as the evaporator itself, must be insulated.
Do not use jumpers or other tools to short out components, or to bypass or otherwise depart from recommended procedures.
• Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
Do not attempt to bypass or alter any of the factory wiring.
• Any compressor operation in the reverse direction will result in a compressor failure that will require compressor replacement.
Page 10
Safety Considerations
10 Chiller Air-cooled Screw
Consult a water treatment specialist for proper treatment procedures.
• Hard scale may require chemical treatment for its prevention or removal
Water must be within design flow limits, clean and treated.
This make it possible to ensure proper machine per­formance and reduce the potential of tubing damage due to corrosion, scaling, erosion, and algae.
• LG assumes no responsibility for chiller or con­denser damage resulting from untreated or improperly treated water.
Rig unit from the top heat exchanger only.
• Rigging from the bottom heat exchanger will cause the unit to be lifted unsafely.
• Personal injury or damage to the unit may occur
Welding is not recommended in the cooler heads or nozzles.
• In the event that welding must be performed, remove the chilled water flow switch and entering and leaving fluid thermistors before welding.
• Reinstall flow switch and thermistors after welding is complete. Failure to remove these devices may cause component damage.
Harsh chemical, household bleach or acid cleaners should not be used to clean outdoor or indoors coils of any kind.
• These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion at the fin/tube interface where dissimilar materials are in contact. If there is dirt below the surface of the coil, use the Environmentally Sound Coil Cleaner.
Do not use high-pressure water or air to clean coils.
• It may cause fin damage
High Velocity Water or Compressed Air should never be used to clean a coil. The force of the water or air jet will bend the fin edges and increase airside pressure drop. Reduced unit performance or nuisance unit shutdown may occur.
Do not overcharge system.
• Overcharging results in higher discharge pressure with higher cooling fluid consumption, possible compressor damage and higher power consump­tion.
Do not add oil at any other location.
• It may cause improper unit operation
Compressor oil is pressurized.
• Use proper safety precautions when relieving pressure.
Turn controller power off before servicing con­trols.
• This ensures safety and prevents damage to con­troller.
Page 11
General
Operation & Maintenance Manual 11
GENERAL
This manual is composed of information on control, operation, start-up, service and troubleshooting of RCAW Air Cooled Chiller.
Manipulation of HMI(Human Machine Interface) Unit
If it is strongly recommended that the user NOT change any programing without consulting LGE service personnel. Unit damage may occur from improper programming.
The menu structure of the HMI unit is shown in the below. As you can see, there are 7 menu items for user interface. Moving among menu items are accomplished by the manipulation of the arrow keys . To see the detail information of the each menu item, press the arrow key . To start up the chiller start button must be pressed for more than 3 sec­onds. Similarly, to shut down the chiller, stop button must be pressed for more than 3 seconds.
Main Menu
System Setting User Setting Content
System Setting
Main Display Par. Setting Content
Par. Setting
System Setting Delay Setting Content
Alarm Display
Delay Setting User Setting Content
Delay Setting
Par. Setting Alarm Display Content
LG
Flooded Air-Cool Screw Chiller
SYS 2.71 PG 14.01
I/O Display
User Setting Alarm Display Content
User Setting
I/O Display Main Display Content
Fig. 1
Page 12
General
12 Chiller Air-cooled Screw
Main Menu
The main menu is composed of 4 screen cuts. Moving among them is accomplished by the manipulation of the arrow keys . The main menu shows configured control parameter of the PLC, temperature inputs, and accumulated com­pressor running hour and current running capacity
In the below main menu, hand/auto mode is configured to be auto control, control mode is configured to be local control. These two items are configurable through user setting menu. The auto control represents the operation mode using scheduling program without key manipulation or remote signal. Contrarily, hand control represents the operation mode using key manipulation or remote signal.
All temperature readings are displayed on the main menu. The temperature readings include chilled water entering tem­perature (CHW In Temp), outdoor air temperature (Ambient Temp), compressor exhaust temperature (Exhaust Temp), chilled water leaving temperature (CHW Out Temp), and condenser refrigerant leaving temperature (Condensate Temp).
Compressor running hours(Comp Running Hrs) means accumulated running hours of the compressor. This value can be initialized by operator if needed. For example, if we replace the compressor with new one, the value must be initial­ized.
The running capacity can be 0%, 25%, 50%, 75%, or 100% according to the actual compressor capacity control.
Main Menu
System Setting User Setting Content
Date2009/03/03 CHW In Temp
Ambient Temp Exhaust Temp
CHW Out Temp Condensate Temp
Status Message Closed-down
Comp Running Hrs Running Capacity
Hand/Auto Mode Control Mode Start Interval Modbus
Auto Control Local Control Complete Use
13:05:00 +17.9 °C
+16.9 °C +17.3 °C
+17.9 °C +17.2 °C
2Hr 0%
Fig. 2
Page 13
General
Operation & Maintenance Manual 13
User Setting
The user setting is composed of 8 screen cuts. Moving among them is accomplished by the manipulation of the arrow keys . Through user setting, operator can configure control parameters of the chiller. The Control parameters of compressor controls, start mode, control mode and scheduling program. To initiate configuration, press the SET key. With confirming highlighted item after pressing the SET key, the operator can change the value of a digit of the selected item by the arrow keys or can change the selected digit by the arrow keys . After changing the value of all digits of the selected item, pressing ENT makes the highlighted item to be changed to the next one. Pressing ESC dur­ing changing makes the changed to be canceled.
The compressor control parameters (Temp Setting) include chilled water leaving temperature reference setpoint (Target Temp), compressor shutdown temperature (Outage Temp), compressor restart temperature(Restart Temp). The chilled water leaving temperature reference setpoint is desirable temperature configured by the operator. The allowable range of the temperature is 5°C ~ 12°C(41°F ~ 53.6°F). The default value of it is 7°C (44.6°F).
Setting Values
Value Setting Keys
SET
ENTER
Moving to Next Item
ESC
Canceling Setting
Moving to Next Digit
User Setting
I/O Display Main Menu Content
Temp Setting Target Temp
Outage Temp Restart Temp
Mode Selection Control Mode
Hand/Auto Mode Modbus
Time Modify Date Setting
Time Setting
Week Modify
Week Setting Week
Revision Code Oil Preheat 0
Mon Start Mon Stop Tues Start Tues Stop
Sun Start Sun Stop
5 °C ~12 °C
SET
SET
Non-use
SET
Changing Value
7.0
°C
5.0
°C
12.0
°C
Remote
Hand
Use
Local Control
Auto Control
2009/03/03
13:20:10
OFF Mon
Min
OFF Delay
08:00:00 18:00:00 06:00:00 17:00:00
10:00:00 14:30:00
Fig. 3
Page 14
General
14 Chiller Air-cooled Screw
Compressor shutdown temperature means the temperature where the compressor must be shut downed by low temper­ature. Here, the default value is 5.0°C(41°F). Compressor restart temperature means the temperature where the com­pressor must restart after shutdown. Here the default value is 12°C(53.6°F). By difference between the shutdown tem­perature and the restart temperature, the compressor is protected from frequent starting.
Operation mode and control mode of main menu are able to be changed in user setting. The operation mode can be either hand or auto. When the operation mode is auto, the chiller runs according to programmed schedule. Contrary, when the start mode is hand, the chiller runs according to key manipulation by operator or remote signal.
The control mode can be either local or remote. When the mode is local, the chiller runs according to key manipulation by operator, Contrary, when the mode is changed to remote, a remote contact is substitute the key operation, and con­sequently, the chiller can be operated remotely.
Through the time amending, the operator can change system clock. Because the clock is maintained even with power loss, there is no need to set the clock again after power on.
Through the revision code, the operator can change password. Some functions of the HMI unit are protected by the password.
Oil preheating time is also configurable in user setting in the unit of minute.
Page 15
General
Operation & Maintenance Manual 15
The I/O display is composed of 9 screen cuts. Through the I/O Display, switch status of signal inputs to the PLC can be identified. In the I/O display, ON means close status of a contact and OFF means open status of contact.
The remote control means remote start input to the PLC. When the contact is closed and the control mode is remote, the chiller starts from stop. When the control mode is local, the switch input is disregarded.
The oil system means the serially connected input of oil flow switch and oil level switch. When both of the oil flow and the oil level are normal during running compressor, both are closed, and consequently the oil system is also closed. When anyone of them is abnormally opened, the switch input to the PLC is also changed into open. The PLC considers the open status of the switch to be oil system alarm.
The compressor contactor switches indicate the status of compressor run. When only the main contactor is closed, the compressor is in the Star-start phase, and when the both of them are closed, the compressor is in the Delta-start phase. Because the contactor switches are contactor status input to the PLC, the contactor inputs must be differentiated from output to the contactors. When there is any problem with a contactor, the input from the contactor and the output the contactor can be different. Consequently, the PLC evaluates the normality of the contactors by checking inputs after making outputs to the contactors be on.
The antifreeze S/W indicated the contact status from the anti-freezing switch. The switch is normally closed, and opens when temperature is under setting value. The PLC considers the openness of the switch to be anti-freezing switch alarm.
The pressure means the serially connected input of high pressure cutout switch and low pressure cutout switch. Both switches are packaged in a dual pressure switch. Both switches are normally open. But if compressor discharge pres­sure is over the setting value of the high pressure cutout switch or if compressor suction pressure is under the setting value of the low pressure cutout switch, the cutout switch opens. The PLC considers the openness of the switch to be pressure alarm.
I/O Display
I/O Display
User Setting Alarm Display Content
Remote Control System Oil Main Contactor
Contactor
Low Temp Switch Pressure Switch Phase Protect Chilled Flow
Dif-pressure Comp Overload Fan 1A1B Fan 2A3A
Fan4A5A OFF
OFF OFF OFF
Fan2B3B Fan4B5B Emergency Stop
Alarm Output OFF M1 Contactor OFF M2 Contactor OFF M3 Contactor OFF
25% Magnet Valve 50% Magnet Valve
OFF OFF OFF OFF
75% Magnet Valve Pump
Fan1A1B Fan2A3A
Fan4A5A Fan2B3B
Fan4B5B OFF SV2 Magnet Valve OFF
DISCRETE INPUTS2
DISCRETE INPUTS1
DISCRETE INPUTS3
DISCRETE INPUTS4
DISCRETE INPUTS6
DISCRETE INPUTS5
DISCRETE OUTPUT1
DISCRETE OUTPUT2
DISCRETE OUTPUT
3
OFF OFF OFF OFF
OFF OFF OFF OFF
OFF OFF OFF OFF
OFF OFF OFF OFF
Fig. 4
Page 16
General
16 Chiller Air-cooled Screw
The liquid flow switch detects chilled water flow, and the water flow must build during running the chiller. The openness of the switch during starting up or running compressor is considered to be water flow alarm by the PLC.
The DP switch means differential pressure switch input to the PLC. Normally, the switch must be closed when the com­pressor runs. The switch opens when the differential pressure between condenser and evaporator is lower than the set­ting value even with running compressor. The PLC considers the openness of the switch with running compressor to be differential pressure alarm.
The overload switch is compressor internal protector that measures the temperature of motor winding and compressor discharge. When any of the temperatures exceeds predetermined value, the switch opens. The PLC considers the openness of the switch to be compressor overload alarm.
The fan contactor inputs are interconnected with their own overload relay contact, so they must be closed with running fans.
The emergency stop switch must be closed, when the emergency switch is in normal position. When the switch is pushed by operator, the emergency stop switch opens and all output from the PLC are disconnected. The PLC consid­ers the openness of the switch to be emergency alarm.
The discrete outputs generated from the PLC are also displayed on the screen cut. Alarm means the alarm notification to external devices by the PLC. If any system alarm is detected by the PLC, the
alarm will be closed by the PLC. Main contactor, M2 contactor, and M3 contactor are outputs to the magnetic contactors for the compressor. When the
compressor starts, main contactor(M1) and M3 contactor are energized to start the compressor with star winding topolo­gy. After a few seconds, the winding topology is changed into delta topology by de-energizing the M3 and energizing M2 instead. During running the compressor, the main contactor and the M2 contactor hold to be energized.
The 25% mgv, 50% mgv, and 75% mgv represent outputs to magnet valves for compressor loading. The magnet valves are installed on the compressor. The capacity control by the control of the magnet valves is shown in the below table.
The fan outputs are outputs to the magnetic contactors of the fans by the PLC.
Step
100% Off Off Off
75% On Off Off 50% Off On Off
MINIMUM Off Off On
Magnet Valve
75% 50% 25%
Table 1
Page 17
General
Operation & Maintenance Manual 17
Alarm Display
Through the alarm display, recent 10 alarms are displayed with their invocation time. The alarm also can be cleared in this screen cut. After pressing SET key, the value at affirm entry is changed to clear by
pressing the arrow keys . Pressing ENT key after the value is changed into clear makes the clearance of the alarm history be effective.
Fig. 5
Alarm Display
Delay Setting User Setting Content
Alarm History 1/10 5E Alarm 2009/03/03 Date 12:53:50Time Clear ----
Alarm History 2/10 5E Alarm 2009/03/03 Date 12:53:50Time Clear
Alarm History 10/10 5E Alarm 2009/03/03 Date 12:53:50Time Clear
Page 18
General
18 Chiller Air-cooled Screw
System Setting
The system setting is composed of 2 screen cuts. Through the system setting, the temperature readings can be adjust­ed when there are some problems with the sensor themselves. Additionally running hours can be cleared in this screen. After pressing SET key, the value at running hrs clear entry is changed to clear by pressing the arrow keys
.
Pressing ENT key after the value is changed into clear makes the clearance of the alarm history be effective.
Fig. 6
System Setting
Main Display Par. Setting Content
Temp and Hours Correction Chilled In
Chilled Out Condensate Temp
Ambient Temp Exhaust Temp Limit Comp Hrs
Clear Comp Hrs
+0.0 °C +0.0 °C +0.0 °C
+0.0 °C +0.0 °C 100000
----
Page 19
General
Operation & Maintenance Manual 19
Parameter Setting
Fig. 7
Par. Setting
System Setting Delay Setting Content
Fan Start Temp3 Fan Start Temp2 Fan Start Temp1 Load Interval
Limit Temp Low Temp Outage DT Restart DT
H Exhaust Temp
90.0 °C
SET
SET
10.0~20.0
1.0~5.0
1.0~3.0
SET
1.0~3.0
34.0~37.9
29.0~33.9
25.0~28.9
29.0~200.0
35.0 °C
30.0 °C
26.0 °C 60S
15.0 °C
2.0 °C
2.0 °C
2.0 °C
80.0~150.0
The system setting is composed of 3 screen cuts. Through the parameter setting, the control parameters of control oper­ations can be identified and changed. To initiate the change, press the SET key. With confirming highlighted item after pressing the SET key, the operator can change the value of a digit of the selected item by the arrow keys or can change the selected digit by the arrow keys . After changing the value of all digits of the selected item, pressing ENT makes the highlighted item to be changed to the next one. Pressing ESC during changing makes the changed to be canceled.
Firstly, Fan control transition points (fan full opening, fan off1, and Fan off2) can be configured. From the transition points, fan full opening means the condenser refrigerant leaving temperature setpoint for running all condenser fans. When actual temperature is over the setpoint, all condenser fans must run. Similarly, the fan off1 means the condenser refrigerant leaving temperature setpoint for running 8 condenser fans. And the fan off2 means the condenser refrigerant leaving temperature setpoint for running 6 condenser fans. Consequently, minimum 6 condenser fans run when the chiller operates, and the number of condenser fans is proportional to the condenser refrigerant leaving temperature. The configurable range is shown in the below picture.
Secondly, system clock can be also changed here. The compressor discharge alarm point temperature cannot be changed only, only informative to operator. The load limit temp is the temperature setpoint where the capacity override is activated. When the chilled water leaving
temperature is over the value, the compressor is prevented from running with 100% capacity and the capacity of the compressor is limited to 75%.
The anti-freezing temp is another method to protect the chiller from too low chilled water temperature additional to anti­freezing switch shown in I/O display.
Page 20
General
20 Chiller Air-cooled Screw
Delay Setting
Fig. 8
Delay Setting
Par. Setting Alarm Display Content
Temp Alarm System Oil Water Flow System Pressure
Start Interval Comp Start Delay Comp Stop Delay
Fan Feedback Contactor-feed DP Delay Comp Protect
Fan Stop Delay 30S
SET
SET
SET
15.0~60.0
0.3~1.5
0.3~5.0
90.0~350.0
0.5~1.5
1.0~30.0
10.0~900.0
1.0~20.0
0.0~900.0
8~15 20~200 60~200
3.0S
30.0S
9.0S
3.0S
10Min 30S 60S
2.0S
3.0S
300.0S
1.0S
The delay setting is composed of 3 screen cuts. In this display, control sequence delay and alarm determination delay are configurable.
Start interval is delayed interval between consecutive starts. The delay is counted after the compressor is shut downed and the next start is delayed for the elapse of the time. The startup delay is the delay between water pump run and com­pressor run at startup phase. When the PLC receives start signal from operator, the PLC initiate the water pump firstly. And after the defined delay, the PLC starts the compressor sequentially.
The outage delay is delay between minimization of the compressor capacity and compressor stop. When the PLC receive stop signal from operator the PLC reset the capacity valves into minimum capacity position. And after the defined delay, the PLC stop the compressor sequentially.
Oil preheat is startup delay of the chiller after receiving start signal. When the chiller is stopped preheating is performed automatically. So through this delay, the preheating time is reserved.
The fan feedback delay is delay to check switch inputs from the magnetic contactors of the fans after energizing the magnetic contactors. Similarly, the contactor feedback is delay to check switch inputs from the magnetic contactors of the compressors after energizing the magnetic contactors.
DP means the delay for the determination of differential pressure alarm after the switch is opened. Comp protect is the delay for the determination of compressor overload alarm by the internal protector of the compressor. Similarly, dis­charge temp means the delay for the determination of high compressor discharge temperature alarm.
Page 21
Controls
Operation & Maintenance Manual 21
PLC and HMI Unit
PLC and HMI Unit
CONTROLS
The HMI (Human Machine Interface) side of the PLC (Programmable Logic Controller) and HMI assembly is shown on the door side as shown in the below picture. The HMI is composed of wide full dot LCD with 4 line display and back light, 9 functional keys, and 15 indicating LEDs for rich user interface.
Through the LCD interface, the operator can monitor the status of chiller operation and control in detail. And the control configurations also can be performed through the LCD interface. For the monitoring and the configuration 7 menu items are prepared in the LCD display from main menu to parameter setting as shown in the below picture. In the below pic­ture, amendable menu contents for the configuration are depicted with shaded color.
Fig. 9
ESC SET ENTER
START STOP
Arrow keys Indicating LED
Full dot LCD :4 line text display with backlight
Page 22
Controls
22 Chiller Air-cooled Screw
Among the menu items, some items are protected from access with authorization code system. The user setting is pro­tected with user code, and delay setting, system setting, and parameter setting are protected from system code. The dual authorization code system enables only authorized operators to configure operation settings, and also enable only service engineers to configure control parameter settings.
The functions of the LEDs are shown in the below table. Through the LED, the operators can identity the status of chiller control without any manipulation.
Fig. 10
Main Menu User Setting I/O Display Alarm Display
System Setting Para. Setting
Delay Setting
Hand/Auto
Mode
Control Mode
Start Interval
Expiration
Chilled Water
In Temp
Ambient
Temp
Exhaust
Temp
Chilled Water
Out Temp
Condensate
Temp Comp
Running Hour
Running
Capacity
Target Temp
Outage Temp
Restart Temp
Hand/Auto
Mode
System Clock
Control Mode
Oil Preheating
Delay
Schedule
Program
Amendable Item
Remote
Control Input
Oil Check
System Input
Comp Contactor
Contact Inputs
Low Temp
Switch Input
Pressure
Switch Input
Phase
Protect Input
Chilled Water
Flow Input
Differential
Pressure Input
Compressor
Overload Input
Fan Contactor Contact Inputs
Emergency
Switch Input
Alarm Output
Comp Contactor
Outputs
Solenoid Valve
Output
Fan Contactor
Outputs
Pump Output
Alarm Clear
Current Alarms
Protected with
User Code
Protected with
System Code
Protected with
System Code
Protected with
System Code
Chilled Water In
Temp Amending
Chilled Water Out
Temp Amending
Cond Ref Out
Temp Amending
Ambient
Temp Amending Comp Discharge
Temp Amending
Comp Running
Hour Clear
Fan Control
Transition Temp
Fan Load
Interval
Comp Discharge
Temp Hi Limit
Chilled Water Out
Temp Hi Ovrd Outage Temp
Restart Temp
Start Interval
Comp Start
Delay
Comp Stop
Delay
Oil Preheat
Delay
Fan Control
Feedback
Comp Control
Feedback
System Code
Comp Overload
Delay
Differential
Pressure Delay Fan Shutdown
Delay
Discharge Temp
Delay
MODBUS
Usage
System Clock
Status Message
Control Mode
MODBUS
Usage
User Code
Comp Loading Valve Outputs
Page 23
Controls
Operation & Maintenance Manual 23
The back side of the PLC and HMI assembly is shown in the below picture. The PLC is composed of base board and extension board. The base board has power connector (POW: CN1), discrete output connector (DO-1: CN2), discrete input connector (DI-1: CN4), and MODBUS communication connector. The extension board has discrete output connec­tor (DO-2: CN3), discrete input connector (DI-2: CN5), and RTD temperature input connector (RTDI: CN6).
LED
OUTPUT1 Auto/Manual Control
Automatic Control: ON Manual Control: OFF
OUTPUT2 Local/Remote Control
Remote Control: ON Local Control: OFF
OUTPUT3 Remote Start Input
Run: ON Stop: OFF
OUTPUT4 Start Interval Lapse
Delaying: ON Complete: OFF
OUTPUT5 Compressor Recycle
Recycle Stop: ON Running: OFF
OUTPUT6
Condenser Coil Warning: ON
Contamination Normal: OFF
OUTPUT7 MODBUS Application
Applying: ON Non-applying: OFF
OUTPUT8 Preheating Application
Applying: ON Non-applying: OFF
OUTPUT9 Preheating Performing
Performing: ON Complete: OFF
Indication
Indicating Status
POW: CN1 DO - 1: CN2 DI - 1: CN4
DO - 2: CN3 DI -
2: CN5
RTDI: CN6
Fig. 11
Table 2. Indicating LED
Page 24
Controls
24 Chiller Air-cooled Screw
On the top side of the PLC, DIP switches and indicating LEDs are installed. Normally, the D2 LED has to blink with 4 Hz frequency, and D3~D6 has to be off. The other LEDs blink according to communication status of the PLC.
All switches of the 4-position DIP switch have to be positioned at off, and switches of the 8-position DIP switch have to indicate MODBUS slave device address. The 8-position DIP switch represents 8 bit hexa number with two digits in inverted value. For example, the factory setting position shown in the below picture (switch2~8: ON and switch 1: OFF) represent 0x7E and its inverted value is 0x01. The factory setting means MODBUS slave address of the chiller is 0x01:
D2D3D4D5D6D7D8D9
12341234
ONONONONONONON
OFF
OFF
OFF
OFF
OFF
5678
Modbus Address: 0x01
MODBUS
Communication
RS-232
Communication
PLC Normal:
OFF
4Hz Blink
Fig. 12
Page 25
Controls
Operation & Maintenance Manual 25
Actual locations of the connectors are shown in the above pictures and detail descriptions of the connectors are shown in the below table. The power of discrete outputs is 220VAC and the power of the discrete inputs is 24VDC.
CN5
CN3
CN1 CN2 CN4
Fig. 13
CN6
MODBUS
Fig. 14
Page 26
Controls
26 Chiller Air-cooled Screw
Connector
Pin
DescriptionWire No.
CN1
(POW)
AC1 AC2
FG
O01
26
27
71
72
24VDC-Positive
CN2
(DO-1)
O02 O03
O04 O05 O06 O07 O08 COM
73 74
75
76 77
78
7
24VDC-Ground
Frame Ground System Alarm
M1 Contactor (Main Contactor) M2 Contactor ( Contactor)
M3 Contactor (Wye Contactor) 25% Magnet Comp Loading Valve
50% Magnet Comp Loading Valve 75% Magnet Comp Loading Valve Water Pump
Common: 220VAC Live
Connector
Pin
Description
Wire No.
CN3
(DO-
2)
O09 O10
O11
79
80
Fan1A1B
O12 O13 O14 O15 O16 COM
81 82 83
85 88 87
7
Fan2A3A Fan2B3B
-
­SV2 Magnet Valve
-
-
-
Common: 220VAC Live
Table 3
Table 4
Page 27
Controls
Operation & Maintenance Manual 27
Connector
Pin
DescriptionWire No.
CN4
(DI-
1)
I01 31
Remote Control I02 32 System Oil Pressure I03 33 I04 34
I05 35 I06 36
Low Water Temperature Switch
I07 37
System Pressure Switch
I08 38
Phase Protector
I09 39
Chilled Water Flow Switch
I10 40
Differential Pressure Switch
I11 41
Comp Overload (Internal Protector)
I12 42
Fan1A1B
I13 43
Fan2A3A
I14 44
Fan2B3B I15 45
-
I16 46
-
24V 26 24VDC-Positive 24G 27 24VDC-Ground
M1 Contactor (Main Contactor)
M2 Contactor ( Contactor)
Emergency Switch
Connector Pin DescriptionWire No.
CN5
(DI-
2)
I01~I16
26 24VDC-Positive
24G 27 24VDC-Ground
-
-
24V
Table 5
Table 6
Page 28
Controls
28 Chiller Air-cooled Screw
Connector
MODBUS
Pin
Description
RX2/D2+
TX2/D2-
Wire No.
MODBUS on RS-485: D+
MODBUS on RS-485: D
-
CN6
(RTDI)
RTD1+
RTD1-
RTD1-
RTD2+
RTD2-
RTD2-
RTD3+
RTD3­RTD3­RTD4+
RTD4-
RTD4-
RTD5+
RTD5-
RTD5-
11
10
13
12
15 14
17
16
19
18
Chilled Water In Temperature
Chilled Water Out Temperature
Compressor Exhaust Temperature
Ambient Temperature
Refrigerant Cond Out Temperature
-
-
-
-
--
--
-
-
-
-
Table 7
The MODBUS communication capability is provided by standard. Using the MODBUS communication, the chiller can be integrated in conventional BMS network. The MODBUS also can be translated to LonWorks or BACnet using 3rd party translator for flexible connectivity to BMS network. The communication configuration of the MODBUS communication is as following:
1) Signal: RS-485
2) Mode: RTU
3) Baud rate: 19,200BPS
4) Parity: even
5) Character: 8 Bit
6) Stop Bit: 2 Bit
Page 29
Controls
Operation & Maintenance Manual 29
The MODBUS address map of registers is shown in the below table.
MODBUS Address Meaning Indicating UnitNO Write
1
46101
Chilled Water Out Temp
Chilled Water In Temp
Ref Cond Out Temp Ambient Temp
Comp Exhaust Temp
Comp Capacity Rate Running Hours
Running Status
Control Status
2
46102
3
46103
4 46104 5 46105 6
46106 7 46108 8 46109
9
46110
10 46115
11 06111
Actual Value x 10 [°C]
Actual Value x 10 [°C] Actual Value x 10 [°C] Actual Value x 10 [°C] Actual Value x 10 [°C]
% Hour
65: Starting, 66: Delaying, 67: Running 68: Shut-downing, 69: Stop
BIT0: Fault, BIT1: Comp Main MC BIT2: Comp MC, BIT3: Comp Y MC
Actual Value(5°C ~ 12°C) x 10 [°C] 0: Stop, 1: Start
YES YES
-
-
-
-
-
-
-
-
-
-
-
Table 8
Page 30
Controls
30 Chiller Air-cooled Screw
Machine On/off Control
There are two modes to turn on/off the machine. One is the Hand Mode and the other is the Auto Mode. HAND MODE Hand Mode is the default set mode from the factory, and the user can turn on/off the
power of the product by pressing the Start/Stop button on the control box for 3 seconds. You can set up this mode by selecting [User Setting] and selecting the [Hand Control] from [Hand/Auto Mode].
AUTO MODE Auto Mode is the mode to control the power on/off of the machine by scheduling the start and stop time. You can set up this mode by selecting [User Setting] and selecting the [Auto Control] from [Hand/Auto Mode]. When the product is shipped from the factory, the default on/off time is set to [Start – 08:00 / Stop – 17:00]. To change the on/off time, set the mode to [Hand Control], and use the button to search the day. When you find the day you want, press the [SET] key and then [ENTER] to move to the row you want to change. Then use the to change the value and press the
to change the set value. After changing the value, press the [ENTER] button. After changing the set value, switch from the [Hand Control] mode to the [Auto Control] mode to schedule the unit to operate at the set time.
The operating key to change the setting is as follows ; [Set] : Change setting / [Enter] : Move down
: Move left/right / : Convert value
If the Start time is later than the Stop time when you press the [ENTER] button to save the set value, it will return to the default setting.
[Example]
Lets assume that you want to change the default setting of [Start – 08:00 / Stop 17:00] to [Start18:00 / Stop 22:00]. If you change the Start time to 18:00 first and press the [ENTER] key, the saved
setting will be recognized as [Start –18:00 / Stop – 17:00], and cause an error to return to the default setting of [Start – 08:00 / Stop – 17:00]. In this case, you need to first change the Stop time to 22:00 and then change the Start time to 18:00, the unit can be scheduled to [Start –18:00 / Stop – 22:00].
Page 31
Start-up
Operation & Maintenance Manual 31
Pre Start-Up
Do not attempt to start the chiller until the following checks have been completed.
Check auxiliary facilities, such as the chilled water circulating pump, air-handling equipment, or other equip­ments to which the chiller supplies liquid are operational. Consult manufacturer’s instructions. If the unit has field-installed accessories, be sure all are properly installed and wired correctly. Refer to unit wiring diagrams.
Open compressor suction and discharge shutoff valves.
Open liquid line, oil line, and economizer service valves.
Fill the chiller fluid circuit with clean water (with recommended inhibitor added) or other non-corrosive fluid to
be cooled. Bleed all air out of high points of system. An air vent is included with the cooler. If outdoor tempera­tures are expected to be below 32°F(0°C), sufficient inhibited propylene glycol or other suitable corrosion inhib­ited antifreeze should be added to the chiller water circuit to prevent possible freeze-up. The chilled water loop must be cleaned before the unit is connected.
Check and inspect all water piping. Make sure flow direction is correct and that piping is made to the correct connection on evaporator and condenser. Open all water flow valves to the evaporator.
Turn on the chilled water pump manually, measure the water pressure drop across the evaporator, and check that water flow is correct per the design flow rates.
Check all electrical connections in control panel to be sure they are tight and provide good electrical contact. Connections are tightened at the factory, but can loosen enough in shipment to cause a malfunction.
Check the actual line voltage to the unit to make sure it is the same as called for on the compressor name­plate, within + 10%, and that phase voltage unbalance does not exceed 5%. Verify that adequate power supply and capacity is available to handle load. To determine percent voltage imbalance: The maximum voltage deviation is the largest difference between a voltage measurement across 2 legs and the average across all 3 legs.
Verify power supply phase sequence. Fan motors are 3 phase. Check rotation of fans by using the quick test. Fan rotation is counterclockwise as viewed from top of unit. If fan is not turning counterclockwise, reverse 2 of the power wires at the main terminal block.
Oil separator heaters must be firmly seated under the oil separator, and must be energized for 24 hours prior to start-up. The oil separator should be warm to touch.
If wind velocity is expected to be greater than 8 km/h wind baffles and brackets must be field-fabricated.
START-UP
Page 32
Start-up
32 Chiller Air-cooled Screw
Do not manually operate contactors. Serious damage to the machine may result. The following procedure should be followed.
Be sure that water side load such as air-handling equipment, or other equipment to which the chiller supplies liquid are working. Starting of the water side load equipments can be delayed if the chilled water temperature is too high.
Be sure that water circulating pump is operating if not on automatic control from the chiller.
Check and inspect all fuses. All fuses inside of the power panel and control panel should be properly located
and maintained.
Switch on the unit circuit breaker and switch on the start switch installed on the door of control panel.
Check and inspect the status of the LEDs of the PLC (Programmable Logic Controller) and the HMI (Haman
Machine Interface) unit. The HMI unit should display welcome screen after switching on.
Check and inspect the voltage monitoring relay inside of the power panel. The relay should not indicate any fault code.
Using the HMI unit, configure chilled water leaving temperature setpoint.
Start the system by setting the unit start menu on HMI Unit.
After running the unit for a short time, check the oil level in each compressor, rotation of condenser fans and
check for flashing in the refrigerant sight glass.
Ambient temperature during unit operating must be within 64.4°F ~ 129.2°F(18°C ~ 54°C).
To obtain proper temperature control, water loop volume must be within allowable range of the volume.
Start-Up Procedure
Page 33
Start-up
Operation & Maintenance Manual 33
After the above procedure, allow unit to operate and confirm that everything is functional properly. Check to see that chilled water leaving temperature agrees with the setpoint. Additionally, check all sensors to have valid reading values through the HMI unit. The PLC uses 5 RTD thermistors to sense temperatures and the thermis­tors include: Ambient, Condenser Refrigerant Leaving, Compressor Discharge, Chilled Water Entering, and Chilled Water Leaving.
Temperature (°F) Resistance() Resistance() Resistance()Temperature(°F)
RTD Temperature Vs Resistance Table
Temperature(°F)
-328
-310
-292
-274
-256
-238
-220
-202
-184
-166
-148
-130
-112
-94
-76
-58
-40
-22
-4 14 32
18.49 50 68 86
104 122 140 158 176 194 212 230 248 266 284 302 320 338 356 374 382 410
103.90 428 446 464 482 500 518 536 554 572 590 608 626 644 662 680 698 716 734 752
-
-
183.17
22.80 107.79 186.32
27.08 111.67 190.45
31.32 115.54 194.07
35.53 119.40 197.69
39.71 123.24 201.29
43.87 127.07 204.88
48.00 130.89 208.45
52.11 134.70 212.02
56.19 138.50 215.57
60.25 142.29 219.12
64.30 146.06 222.65
68.33 149.82 226.17
72.33 153.58 229.67
76.33 157.31 233.17
80.31 161.04 236.65
84.27 164.76 240.13
88.22 168.46 243.59
92.16 172.16
-
-
247.04
96.09 175.84
100.00
179.51
Table 9
Page 34
Start-up
34 Chiller Air-cooled Screw
Temperature
Voltage
Temperature Temperature limits during the operation of the unit are as follows. Maximum ambient temperature: 129.2°F(54°C) Minimum ambient temperature: 64.4°F(18°C) Maximum outlet water temperature: 59°F(15°C) Minimum outlet water temperature: 41°F(5°C) * Temperature of inlet water must not exceed 68°F(20°C) during continuous operation.
Permitted maximum voltage and minimum voltage are displayed on PDB. And if you need other electric data, please refer to PDB. When using the 3 phase voltage, never operate the motor of the compressor when the imbalance among the phases exceed 5% The formula to calculate the voltage imbalance is as follows. % Voltage Imbalance = 100 x (Max Voltage from average voltage / Average Voltage) Max Voltage from average voltage is the absolute value of the maximum gap from the average voltage of the 2 phases.
Example)
Voltage source 400-3phase(1,2,3)-50Hz 12 : 405V / 23 : 394V / 31 : 410V Average voltage : (405 + 394 + 410) / 3 = 403 Difference between average voltage and each voltage : Average – 12 = |403 – 405| = 2V Average – 23 = |403 – 394| = 9V Average – 31 = |403 – 410| = 7V Maximum voltage compared to average voltage : 9V % Voltage imbalance : 100 x (9 / 403) = 2.23% Because the permitted range of the imbalance the voltage is less than 5%, the device can operate.
Operation Limits
Page 35
Start-up
Operation & Maintenance Manual 35
Flow Rate
The basic flow rate of the chiller must follow the values of the table showing the maximum, minimum and designed flow rate. Higher or lower flow rates are permitted to make the lower or higher temperature rise. In order to assure appropriate heat exchange and turbulent flow inside the evaporator, the flow rate must exceed the Minimum flow rate.
gpm l/s gpm l/s gpm l/s
RCAW100*BAA
RCAW090*BAA
116.9 7.4 234 14.7 467.6 29.5
107.7 6.8 215 13.6 430.8 27.2
Maximum
Model
Minimum Norminal
Table 10
Compact
Page 36
Start-up
36 Chiller Air-cooled Screw
n Compact
Fig. 15
Note: For flow out of this range, consult LG.
* : P – 380V, Q - 400V, R - 415V
0
20
40
60
80
100
120
140
160
0 5 10 15 20 25 30 35
40 RT
40 RT
60 RT
60 RT
50 RT
50 RT
70 RT
70 RT
80 RT
80 RT
90 RT
90 RT
100 RT
100 RT
Compact model 40 ~ 100 RT
Pressure drop (kPa)
Water flow rate (l/s)
0
5
10
15
20
25
30
35
40
45
50
55
60
0 50 100 150 200 250 300 350 400 450 500
40 RT
40 RT
80 RT
80 RT
60 RT
60 RT
50 RT
50 RT
70 RT
70 RT
90 RT
90 RT
100 RT
100 RT
40 RT
60 RT
50 RT
70 RT 80 RT
90 RT
100 RT
40 RT
80 RT
60 RT
50 RT
70 RT
90 RT
100 RT
Compact model 40 ~ 100 RT
Pressure drop (ft wg)
Water flow rate (gpm)
Chilled water pressure drop (SI Unit)
Chilled water pressure drop (English Unit)
Page 37
OPERATION
Sequence of Operation
The sequence of the operation is depicted by the flow chart in the below. When the start is in effect, the condenser fan and water pump run concurrently. Additionally, for the minimum load position of the compressor, the MV1 is turned on. After condenser fan feedback delay, the feedback inputs from the contactors are checked. The PLC shutdown the chiller if there is problem with the contactor feedback. Similarly, 9 seconds after the water pump run, water flow is checked.
When there is no problem with the water flow, startup delay is initiated. For the 30~60 second delay, chilled water leav­ing temperature is checked whether the water temperature is enough high to run the compressor.
When the PLC decides to turn on the compressor, it starts the compressor in star-start, and transits to delta-start after 4 seconds. During starting the compressor, the compressor contactors are also checked whether there is any problem with the feedback from the contactors, and SV1 oil solenoid valve is opened for proper oil circulation.
After the start, normal controls are initiated. The normal controls include capacity control, mid pressure refrigerant con­trol for motor cooling, condenser fan control, and alarm control.
When the chiller is requested to be stopped, the load condition of the compressor is changed into minimum load position by turning on MV1 and Turning off MV2 and MV3. After 60 second of shutdown delay, the compressor is stopped.
Even with the stop of the compressor, the chilled water pump still runs for 4-10 minutes to protect the compressor from frequent restart and to withdraw latent heat from evaporator of the chiller.
The shutdown delay and water pump run delay can be configured in delay setting screen of the HMI unit.
Operation
Operation & Maintenance Manual 37
Page 38
Operation
38 Chiller Air-cooled Screw
Condenser
Fan=ON
Water Pump
= ON
Alarm
Y Start
: M4
: M1=ON & M3=ON : Oil Heater=OFF : Oil Solenoid Valve(SV1)=ON
: Temp Leaving > Setpoint ?
MV1=
ON
: 25%
Alarm
M3 = OFF
DELTA Start
Stop logic
No
No
Yes
Yes
0.5 Sec
4 Sec
9 Sec
Yes
3
SecYes
No
No
:
Flow S/W
: 30 - 60 sec
No
Yes
Yes
: M1=ON & M2=ON
Capacity
Control
Mid-pressure
Refrigerant
Valve Control
Alarm
Control
Condenser
Fan Control
: SV2
Y-DELTA START
STOP
Start
Contactor
Check
Flow
Check
Water Temp. Check
Comp.
Contactor
Check
Stop?
Fig. 16
Page 39
Operation
Operation & Maintenance Manual 39
Fig. 17
MV2=OFF & MV3=OFF
MV1=ON, SV2=OFF
M2 =OFF & M1=OFF
SV1=OFF
Water Pump
=OFF
Fan = OFF
4-10Min
Yes
Stop logic
60 Sec
stop
MV1=OFF
Stop?
Page 40
Operation
40 Chiller Air-cooled Screw
Delay control for the chiller is summarized in the below picture. There are two essential delays, stop to start delay and oil pre-heating delay in the picture. The stop to start delay is the duration between the stoppage of the compressor and the restart of the compressor. The factory setting value of the delay is 10 minutes and con­figurable through delay setting of the HMI unit. The delay is designed to protect the compressor from frequent starting. The other delay, oil pre-heating delay is activated only after power-on reset. The delay is also config­urable through user setting of the HMI unit. The delay is designed to protect the cooling cycle of the chiller from improper oil circulation especially at low ambient condition
During running compressor, the condenser fans are controlled to get proper high pressure side condition of the cooling cycle. The control points of the condenser fans are determined by refrigerant leaving condenser temper­ature, and they are configurable through parameter setting of the HMI unit.
Power on
Reset
Stop to Start
Delay
Oil Pre-heating
Delay
Condenser fan run
Water pump run
START
Compressor Run
Start Delay
Stop
Delay
Fan
Stop
Delay
Fan
Stop
Delay
START
Stop to
Start
Delay
Condenser Fan Run
Water Pump Run
Compressor Run
Start Delay
Stop
Delay
Fig. 18
Page 41
Operation
Operation & Maintenance Manual 41
Fig. 19
Table 11
CONTROL POINT DEFAULT RANGE
T1 34 30 ~ 34 T2 39 35 ~ 39 T3 44 40 ~ 45 T4 - ­T5 - -
100RT
Page 42
Operation
42 Chiller Air-cooled Screw
To monitor the inlet water temperature, outlet water temperature, discharge temperature of the compressor, ambient temperature and discharge temperature of the condenser of the cooler during chiller operation, RTD (Resistance Temperature Detect) is used.
Inlet water temperature sensor of Cooler
Outlet water temperature sensor of Cooler
Compressor discharge temperature sensor
Ambient temperature sensor
Condenser discharge temperature sensor
The resistor value for the measured temperature is as follow.
Sensors
RTD (Resistance Temperature Detect)
Temperature (°F) Resistance() Resistance() Resistance()Temperature(°F)
RTD Temperature Vs Resistance Table
Temperature(°F)
18.49 103.90 183.17
22.80 107.79 186.32
27.08 111.67 190.45
31.32 115.54 194.07
35.53 119.40 197.69
39.71 123.24 201.29
43.87 127.07 204.88
48.00 130.89 208.45
52.11 134.70 212.02
56.19 138.50 215.57
60.25 142.29 219.12
64.30 146.06 222.65
68.33 149.82 226.17
72.33 153.58 229.67
76.33 157.31 233.17
80.31 161.04 236.65
84.27 164.76 240.13
88.22 168.46 243.59
92.16 172.16
-
-
247.04
96.09 175.84
100.00
179.51
-328
-310
-292
-274
-256
-238
-220
-202
-184
-166
-148
-130
-112
-94
-76
-58
-40
-22
-4 14 32
50 68
86 104 122 140 158 176 194 212 230 248 266 284 302 320 338 356 374 382 410
428 446 464 482 500 518 536 554 572 590 608 626 644 662 680 698 716 734 752
-
-
Table 12
Page 43
Service
Operation & Maintenance Manual 43
Cycle Components
The structure of the air-cooled cooling cycle is shown in the below.
The unit is equipped with semi-hermetic screw compressor developed especially for applications in air-condi­tioning. The construction of the compressor is shown in the below.
SERVICE
No. PART No. PART No. PART No. PART
(1) Compressor (7) Flow Control Device (13) Oil Level Switch (19) Relief Valve (2) Condenser (8) Flow Control Device (14) Oil Solenoid Valve (20) Temperature Sensor (3) Reciever (9) Dryer (15) Oil Flow Switch (21) Low Pressure Switch (4) Oil Filter (10) Evapolator (16)
Discharge Temp. Sensor
(22) Water Flow Switch
(5)
Oil Seperator / Economizer
(11) Oil Heater (17)
Oil High Pressure Switch
(23) Ref. Solenoid Valve
(6) Flow Control Device (12) Oil Level Sight Glass (18) Anti-freezing Switch (24) Check Valve
Compressor
Table 13
Fig. 21
Fig. 20
Page 44
Service
44 Chiller Air-cooled Screw
As shown in the below, during rotation of the rotors the meshing shifts from the suction side to the discharge side. The meshing rotors enclose a working space, which is continuously reduced as it moves in the axial direc­tion. This causes a V-shaped lobe space to form between each of the male and female lobes. This lobe space increases to a maximum size (suction and sealing process). As the rotors rotate further, the new meshing on the suction side closes the V-shaped lobe space. The lobe space is then constantly reduced by continuing inter­meshing of the lobes (compression process).
The reduction in lobe space takes place on the lower side of the rotors towards the discharge side. The volume is steadily reduced and it is thereby compressed in the sealed condition. As soon as the peaks of the rotor teeth are free to the outlet port, the vapor is discharge to the high-pressure side and flows to the oil separator where the high-pressure gas will be separated from the lubrication oil. The size and geometry of the discharge port determine the so called internal volume ratio (Vi) of the compressor. This ratio m ust have a defined relation­ship to operating pressure ratio to avoid losses in efficiency due to under or over compression.
The screw compressor is equipped with 4-step capacity control system. The capacity control system is consist­ing of a modulation slide valve, piston rod, cylinder, piston and piston rings. The slide valve and the piston are connected by a piston rod. The principle of operation is using the oil pressure to drive the piston in the cylinder. The positive pressure differential causes the piston to move toward the right side in the cylinder. When the slide valve moves toward the right side, the effective compression volume in the compression chamber increases.
Number Description Number Description
1 Compressor casing 18 Discharge fixed ring 2 Motor casing 19 Disc spring 3 Oil separator 20 Bearing lock nut 4 Motor rotor assembly 21 Male rotor 5 Motor stator assembly 22 Suction bearings 6 Motor rotor washer 23 Suction bearings inner/outer spacer ring 7 Motor rotor spacer ring 24 Oil guiding ring 8 Oil separator baffle 25 Suction filter
9 Oil separator cartridge 26 Oil heater 10 Piston 27 Refrigeration Lubricant 11 Piston spring 28 Suction flange 12 Piston rod 29 Discharge flange 13 Bearing seatÅfs cover plate 30 Cable box 14 Modulation solenoid valve 31 Power bolt 15 Modulation slide valve 32 Thermostat terminals 16 Slide valve key 33 Motor cable cover plate 17 Discharge bearings 34 Discharge check valve
Table 14
Fig. 22
Page 45
Service
Operation & Maintenance Manual 45
This means the displacement of refrigerant gas also increases, as a result the refrigeration capacity also increases. However, when any of the step solenoid valve is energized, the high pressure oil in the piston cylin­der bypasses to the suction port causing the piston and the slide valve to moved toward the left side, then some of the refrigerant gas by pass from the compression chamber back to the suction end. As a result, the refrigera­tion capacity decreases because of the reduction of displacement of refrigerant gas flowing in the system. The piston spring is used to push the piston back to its original position, i.e. minimum load position in order to reduce the starting current for the next starting-up. If the compressor started at full load capacity it may result in over current start. The capillary is used to maintain and restrain a suitable amount of oil flow into the cylinder. If the oil filter cartridge, capillary, or modulation solenoid valves are not working well in the capacity control sys­tem, this may result in the abnormality and ineffectiveness of the capacity control system.
The main functions of the lubrication oil in the screw compressor are lubrication, internal sealing, cooling and capacity control. The positive oil pressure in the cylinder pushes the piston and the slide valve that is connected by a piston rod to move forward and backward in the compression chamber. The design with positive pressure differential lubrication system in the screw compressor is available to omit an extra oil pump in the compressor like reciprocating compressor. However, in some special applications, it is still necessary to install an extra oil pump to the compressor for safety.
Fig. 23
Page 46
Service
46 Chiller Air-cooled Screw
The bearings used in the compressor required a small but steady quantity of oil for lubrication; the oil injection into the compression chamber creates an oil sealing film in the compression housing for increasing the efficien­cy and absorbing a part of heat of compression. In order to separate the oil from the mixed refrigerant gas, an oil separator is required to ensure the least amount of oil carried into the system. Pay more attention to the oil temperature, which has a very significant factor to the compressor bearings life. High oil temperature will reduce the oil viscosity and cause the poor lubrication and heat absorption in the compressor as well. The oil viscosity is recommended to keep over 10mm2/ s at any temperature. The oil temperature just keeps above system condensing temperature to avoid the refrigerant migration into system in the summer. There is high oil viscosity in the low ambient temperature circumstance, it could cause compressor in heavy duty to be started up resulting less oil pressure in oil line to load the compressor. The better solution is to have higher condensing temperature in a short time by warming up the oil.
The compressor is equipped two oil sight glasses as a standard, one is the oil high level sight glass, and the other is the oil low level sight glass. The normal oil level in the compressor oil tank should be maintained above the top of the low oil sight glass and in the middle level of high oil sight glass when compressor is running. Applicable oil types are shown in the below.
UNITS
COLOR, ASTM
SPECIFIC GRAVITY
VISCOSITY
FLASH POINT
POUR POINT
T.A.N
COPPER STRIP 100°C/3hr
MOISTURE
FLOC POINT
DIELETRIC STRENGTH2.5mm
-
-
104°F
212°F
°F °F
mg KOH/g
-
ppm
°F
KV
MOBIL EAL ICI EMKARATECPI SOLEST
68 120 220 370 68 100 RL411 RL375 RL421
- - - - 0.5 0.5 1.5 L2.0 L1.0
0.945 0.94 0.95 0.955 0.971 0.966 0.9723 0.9783 0.9759 64 131 215.9 385.96 62.5 95.8 48 74.1 134
8.9 14.53 20.8 29.23 8.3 10.5 7.3 10.1 15
510.8 489.2 519.8 575.6 489.2 500 523.4 474.8 509
-45.4 -33.7 -13 -5.8 -45.4 -34.6 -40 -31 -34.6
- - - - - <0.05 <0.05 <0.05 -
-- - -- - - --
- - - <100 <100 - - - -
-- - -- - - --
-- - -- - - --
Fig. 24
Table 15
Page 47
Service
Operation & Maintenance Manual 47
In order to protect the compressor, the compressor has been installed three PTC temperature sensors inside motor coil and another one at the discharge side of compressor. These sensors are connected to an INT69 control module to monitor the motor coil temperature and discharge temperature as well. If the temperature in one of the areas moni­tored exceeds the nominal response temperature of the respective PTC thermistor, the sensor resistance increases and the INT69 control module switches the motor contactor off. The cutout temperature of the motor winding tempera­ture is 248°F(120°C) and the cut in temperature is 167°F(75°C). The cutout temperature of the motor winding is 230°F(110°C) and the cut in temperature is 140°F(60°C). Compressor trouble shooting is shown in the above.
SYMPTOMS
COMPRESSOR
DOES NOT RUN
COMPRESSOR CYCLES
OFF
ON LOW SATURATED
SUCTION TEMPERATURE
COMPRESSOR
SHUTS
DOWN ON HIGH
PRESSURE
CONTROL
UNIT OPERATES
LONG OR
CONTINUOUSLY
SYSTEM NOISES
COMPRESSOR
LOSES OIL
HOT LIQUID LINE
FROSTED LIQUID LINE
COMPRESSOR LOAD-
ERS NOT WORKING
PROPERLY
CAUSE REMEDY
Check main disconnect. Check control circuit for ground or short. Replace fuse. Use Navigator to reset current alarms. Check connections from CCP to contactor. Check wiring and rewire. Check line voltage. Determine location of voltage drop and remedy deficiency. Check motor winding for open or short. Replace compressor if necessary. Replace compressor. Check oil pump operation, oil pressure transducer, verify oil solenoid valve operation. Repair leak and recharge. Replace transducer. Add refrigerant. Repair/replace as needed. Remove and clean strainer. Replace switch. Open valve or replace if defective. Check wiring. Repair or replace motor(s) if defective. Clean coil. Check wiring. Repair or replace valve if defective. Clean condenser. Add refrigerant. Replace control. Clean or replace. Replace or repair. Evaluate load requirements. Check loader solenoid valves. Replace if necessary. Support piping as required. Add refrigerant. Check for plugged liquid line strainer. Replace compressor (worn bearings). Check for loose compressor bolts securing compressor to cooler. Find and repair leak. Replace compressor. Repair leak and recharge. Open valve or remove restriction. Replace coil. Replace valve. Rewire correctly.
Power line open Control fuse open High-Pressure Switch (HPS) tripped Loose terminal connection Improperly wired controls Low line voltage
Compressor motor defective Seized compressor
Pre-lubrication not successful Loss of charge
Bad transducer Low refrigerant charge Failed expansion device Partially plugged or plugged strainer High-pressure switch erratic in action Compressor discharge valve partially closed Condenser fan(s) not operating (air cooled units) Condenser coil plugged or dirty (air cooled units) Condenser water valve not operating (water cooled units) Circuit overcharged Low refrigerant charge Control contacts fused Partially plugged or plugged strainer Defective insulation Service load exceeding design capacity Inefficient compressor Piping vibration Expansion valve hissing
Compressor noisy Leak in system
Mechanical damage to rotors Shortage of refrigerant due to leak Shutoff valve partially closed or restricted Burned out coil Defective loader solenoid valve Miswired solenoid
Table 16
Page 48
Service
48 Chiller Air-cooled Screw
Maintenance and cleaning of condenser coil
Periodically cleaning the surface of the coil is essential in maintaining the normal operation of the unit. By removing any contaminant or hazardous substance on the coil, you can extend the life of the coil and the unit. The following mainte­nance and cleaning method is recommended as part of the periodical maintenance activity to extend the life of the coil.
Remove fiber on surface : Use the vacuum cleaner to clean any fiber or dust on the surface. If you cannot use the vacuum cleaner, use a soft non-metallic brush to clean the surface. When using both methods to clean the surface, clean in the same direction as the pin. Because the pin can bend very easily, you can bend the pin or scratch the protec­tive coating on the surface by applying the cleaning utensil across the pin.
Periodical water cleaning: Periodically cleaning the pin with water helps the maintenance of the coil installed on the coast or industrial site. But due to the fragility of the installed coil, you must rinse the coil with water at low speed in order to prevent any damage to the coil. It is recommended to clean once every one to two months.
Condenser
If you use a water hose to clean the coil, be careful as dust or fiber can get inside the coil. Completely remove any fiber or dust on the surface before cleaning it with clean water.
Never use any type of cleaner such as chemical, bleach, acid or alkali cleaner etc. on the coil. These types of cleaners can accelerate the corrosion of the pin and tube, and make it difficult to rinse with water.
Never clean the coil using high speed water or pressured air. Doing so can bend the coil and increase the pressure drop on the air side of the condenser. This can result in performance dete­rioration or cause the product to stop operating.
Page 49
Service
Operation & Maintenance Manual 49
Condenser fan
The fan motor and the fan must be fixated firmly on the top plate of the condenser with the metallic bracket. Shroud pro­tects the parts from the fan rotating in high speed. Assembly of the condenser fan is as shown in the picture. as follows. Apply the grease on the exposed part of the motor to protect it from the rain. You have to apply the grease again on the fan axis and then reinstall the Shroud. Also there is an axis support on the fan axis of the fan motor, which must be inserted accurately at this location for maximum performance of the fan motor. And then the bolt must be firmly tight­ened.
Shrou
d
Fan
Motor
Fig. 25
Page 50
Service
50 Chiller Air-cooled Screw
Cooler
Flow Switch
Flow Switch is installed on the water outlet nozzle for all units as factory setting. The following pictures shows the Flow Switch in generally installed method.
Fig. 26
Table 17
parts name Qty cover insulation plate microswitch adjusting screw metal fitting for flow adjusting screw flow adjusting screw actuating plate adjusting spring
1 1 1 1
1 1
1 1
Page 51
Service
Operation & Maintenance Manual 51
Dual Pressure Switch
Differential Pressure Switch
Differential pressure switch is also used for checking lubrication trouble. When the differential pressure between con­denser and evaporator is larger than the setting value(5kg/cm2), the switch will be closed. Contrary, when the setting value is under the setting value, the switch will be opened. This switch is also returned to be closed automatically when the differential pressure is recovered from low pressure status.
Dual pressure switch has low pressure cutout switch and high pressure cutout switch inside. The cutoff points can be adjustable. The factory setting values are shown in the below.
The low pressure switch and the high pressure switch are normally closed and tripped to opening when the detected pressure exceeds the setting value. After recovering from high pressure or low pressure status, the switch resets to normal position automatically.
Low Pressure Cutout 3.2kgf/cm
2
High Pressure Cutout 22kgf/cm
2
Table 18
Fig. 27
Fig. 28
Page 52
Service
52 Chiller Air-cooled Screw
Anti-freezing Switch
The anti-freezing switch is used to detect too low water temperature. The switch is normally closed and tripped when the chilled water leaving temperature is under 35.6°F(2°C). The switch returns to the normal status when the tempera­ture increases over 41°F(5°C). The Anti-freezing switch is installed on the evaporator.
Fig. 29
Page 53
Service
Operation & Maintenance Manual 53
Refrigerant Cycle
Leakage test
As described in the installation manual, the unit is sufficiently charged with R134a refrigerant as factory setting. If the refrigerant pressure is lower than the factory setting, you must check for leakage. If the pressure inside the unit has dropped, use the Nitrogen to do a leakage test. When repairing the leaking part, you must use good refrigeration prac­tice. After the leakage is repaired, any water inside the chiller must be removed and vacuumed.
Charging the refrigerant
Insert the coupling to the refrigerant charging port. In order to avoid the damage to the tube from residual water freezing within the evaporator, circulate the water in the evaporator (EVA) while charging the refrigerant to the designated amount. For the amount of refrigerant to charge, refer to the installation manual or PDB.
Charging the oil
Insert the coupling in the oil port. Check whether the oil level is above in the Sight Glass window. Remove the coupling and insert the oil port cap. After inserting the oil, operate the product and check whether the oil level is above with the naked eye. If not, supplement the oil.
Page 54
Service
54 Chiller Air-cooled Screw
Oil Filter
The oil filter is installed on the oil separator in oil return line to the compressor. Differential pressure between the inlet and outlet of the oil filter must be checked periodically. On the oil separator, the core valves for connection of the inlet/outlet with pressure gauge are installed. If the differential pressure is over 5kg/cm2it is recommended to disas­semble the oil filter and wash the oil filter mesh.
Oil Flow Switch
The oil flow switch is also installed on the oil separator in oil return line to the compressor. The setpoint range of the flow switch covers 3.4~4.2 l/min at increasing flow and 3.0~3.8 l/min at decreasing flow. Maximum flow rate of the oil flow switch is 67l/min.
Item Name Note Qty
Bolt M10 x 40L 8 Service flange Ø136 x 15t 1 Gasket Ø90 x 1.5t 1 Spring Ø37 x 2d 1 Oil Filter Cartridge 30 mesh/inch 1 O-ring Ø28.24 x 2.62W 1 Oil filter Body Ø136 x 270L 1
Refrigerant Cycle
Fig. 30
Fig. 31
Table 19
Page 55
Service
Operation & Maintenance Manual 55
Oil Heater
Solenoid Valve
One of the Solenoid Valve is installed between the Flash Gas Tank where the oil separator is installed and the other is installed between the oil filter and Flash Gas Tank. Valve on the compressor side is turned on during Full Load operation, and off during other operations. Valve on the oil filter side is turned on when the unit is operating to pass the oil to the compressor, and off when the operation stops to prevent the oil from back flowing.
The oil heater prevents poor lubrication due to too low viscosity. The oil heater is also installed on the oil sepa­rator. The 150W oil heater has 220VAC power input.
Fig. 32
Fig. 33
Include Cable wire Include DIN plug wire
3.3689585755445252817213838351-3/8
3.0689585755445222567213838281-1/8
EVR25
kgmmmmmmmmmmmmmmmmmmmmmmmmmmin
12/20W10W
weight
B
1
Max
B
L
5
max
L
3
L
4
L
2
LH
4
H
3
H
2
H
1
Connect
MODEL
Page 56
Service
56 Chiller Air-cooled Screw
Control System
The structures of the power panel and control panel are shown in the below. The power panel in the left is composed of the electrical components related to 400VAC main power, and the control in the right is composed of low-voltage com­ponents such as the PLC and the HMI unit.
Both panels are designed to be water proof by dual door system. The panels comply with IP55.
C
ontrol Panel
ower Panel
Fig. 34
Page 57
Service
Operation & Maintenance Manual 57
Power Panel
On the left side of the power panel, terminal blocks for main power connection are prepared. The field supplied 400VAC main power lines and neutral line for control power are connected to these terminal blocks.
There are three magnetic contactors for the wye-delta starting of the compressor and OCR (Over Current Relay) for the compressor. For wye-delta starting, there are three magnetic contactors installed inside of the power panel.
By the wye-delta starter, the starting inrush current is reduced by 1/3 of direct starting method. The line voltage(VL) of the both of wye and delta winding configuration is 400VAC, but the phase voltages(VP) of the wye winding configuration is reduced by 1/3 of the delta winding configuration. Additionally, the line current (IL) is also reduced by 1/3 of the delta winding configuration. Consequently, the current of the wye winding configuration is reduced by 1/3 of delta winding configuration. Using the principle, the compressor starts with the wye winding configuration. And the winding configura­tion is changed into delta configuration after few seconds for the normal operation of the compressor.
Fig. 35
Main Power
Compressor Wye-delta Starter
Compressor OCR
Page 58
Service
58 Chiller Air-cooled Screw
L1
L3
L2
1M
2M
1
4
5
2
3
6
1M
1M
2M
S
S
S
3
L
P
V
V
=
PLII=
Wye Starting Delta Running
L1
L3 L2
1M
2M
1M
1M
2M
2M
S
S
S
1
4
5
2
6
3
LPVV=
PL
IIx
=
3
Fan contactor & OCR
Fuse assembly
Voltage monitoring relay : 5E
Fuse for the 5E Power input
Fig. 36
Fig. 37
There is one magnetic contactor for each condenser fan. On the right bottom side of the power panel, voltage monitoring relay is installed to monitor proper power input. There
are three fuses installed for the 400VAC power input to the voltage monitoring relay. The ventilation fan of the power panel is controlled by the thermostat. If the ambient temperature inside of the power panel is over 95°F(35°C), the venti­lation fan runs.
Page 59
Service
Operation & Maintenance Manual 59
n Compressor OCR (Over Current Relay)
The compressor OCR is thermal type and used to protect the compressor from overload condition. The OCR contact used for the control system is normally closed and the OCR contact switch is to be opened if it detects excessive cur­rent. The OCR needs manual reset by switch on the OCR to be recovered to normal after tripping. The tripping point ranges and factory settings are shown in the below table
n Condenser Fan OCR
The condenser fan OCR is also thermal type and used to protect the condenser fan from overload condition. The OCR contact used for the control system is normally closed, and the OCR contact switch is to be opened if it detects exces­sive current. The OCR needs manual reset by switch on the OCR to be recovered to normal after tripping. The tripping point ranges and factory settings are shown in the below table.
Model Range[A] Trip[A]
RCAW090PBAA 165~235 177
RCAW1008BAA 165~235 173
Model Range[A] Trip[A]
RCAW090PBAA 6.5~8.5 8
RCAW1008BAA 4.5~6.5 6.2
Table 20
Table 21
Page 60
Service
60 Chiller Air-cooled Screw
n Voltage Monitoring Relay (5E)
The voltage monitoring relay is used for the verification of proper power supply of 400VAC. The voltage monitoring relay is shown in the below. Existing 3-phase voltage will be shown ordinally every 3 seconds as shown in the below.
The voltage monitoring relay monitors 5 abnormal conditions of the power supply. The abnormal conditions include over voltage, under voltage, phase reverse, phase loss, and voltage unbalance. Among the abnormal conditions, the phase reverse and the voltage unbalance are selectively protective. The others are mandatory. When any abnormal condition is encountered, the type of abnormal condition and abnormal value detected are displayed instead of normal display. Some examples of the abnormal conditions are shown in the below.
Along with the selectivity of protection, reset method after any abnormal condition invocation can be configured through 4-position DIP switches. The functions of the DIP switches are shown in the below. According to factory setting, only the switch positioned at ʻ5S/1Sʼ is off, and the others are on. Please don't change factory setting for proper protection.
V
R S T
S
V
R S T
S
V
R S T
S
V
R S T
S
V
R S T
S
V
R S T
S
UNDER VOLTAGE
UNBALANCE VOLTAGE
PHASE LOSS NO INPUT
OVER VOLTAGE REVERSE PHASE
V
R S T
S
V
R S T
S
V
R S T
S
Fig. 38
Fig. 39
Page 61
Service
Operation & Maintenance Manual 61
The voltage unbalance tripping is activated when the unbalance exceeds +5% more than 3 seconds. Similarly, phase loss tripping has 2 second delay and phase reverse tripping has 0.5 second delay.
The over voltage tripping point and tripping delay are configurable through rotary switch on the voltage monitoring relay. The under voltage tripping point and tripping delay are also configurable through another rotary switch on the voltage monitoring relay. The factory setting of the rotary switches are shown in the below table.
Rate Voltage 380VAC 400VAC
Over Voltage Value 416VAC 440VAC
Over Voltage Delay 4S
Under Voltage Value 342VAC 360VAC
Under Voltage Delay 4S
Table 23
Table 22
REV.
UNBAL.
AUTO
5S/1S
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Reverse phase protected
Reverse phase unprotected
Unbalance protected
Unbalance unprotected
Auto reset
Manual reset
Auto reset delay 5 sec
Auto reset delay 1 sec
OFF
UNBAL.
AUTO
5S 1S
REV.
Page 62
Service
62 Chiller Air-cooled Screw
Assist Relay
Assist Relay is the relay to check power supply of 220V to the controller. Assist Relay is as follows.
Compressor Contactor
Compressor Contactor controls the start, stop and static range of the compressor motor when the product is operating. Rated voltage of Compressor Contactor is 400V.
Fig. 40
Fig. 41
Page 63
Service
Operation & Maintenance Manual 63
Fan Contactor
Fan Contactor controls the start, stop and static range of the fan motor when the product is operating. Rated voltage of Fan Contactor is 400V.
Fig. 42
Page 64
Service
64 Chiller Air-cooled Screw
Control Panel
On the external door of the control panel there is emergency switch for the instant cutting out of control outputs from the PLC. By pushing the emergency switch, the 220VAC power supplied to the PLC relay outputs are cut out instantly. By turning the switch in clock-wise direction, the power to the output is recovered.
On the internal door of the control panel, operator can access the HMI unit. Along with the HMI unit, power indication lamp and start/stop switch are installed on the door. The start/stop switch is to switch on or off the control power to the control system, and the power supply status is indicated through the power lamp.
Sight glass for the HMI unit & PLC
Emergency switch
HMI unit & PLC
Power lamp
External Door of Control Panel
Internal Door of Control Panel
Fig. 43
Page 65
Service
Operation & Maintenance Manual 65
In the control panel, the PLC is installed as a central control station. The PLC is assembled with the HMI unit in a black case. The PLC is supplied 24VDC power from the SMPS (Switched Mode Power Supply) on the right side.
The relay is to confirm proper 220VAC power supply and start/stop switch which is installed on the door is positioned at start. The ventilation fan of the control panel runs permanently after power on.
Control fuse
Control Relay
Switched Mode Power Supply
Fig. 44
Page 66
Service
66 Chiller Air-cooled Screw
ETC
Temp. Sensor in Control Box
This is used to detecting the temperature within the Control Box when operating the product. The shapes and character­istics are as follows.
Ventilation Fan
Ventilation Fan is attached on both sides of the Power Box and the Control Box. This fan responds to the temperature increase within both boxes while the product is operating and sends the air outside to prevent any issues from tempera­ture increase within each box.
Fig. 45
Fig. 46
Page 67
Service
Operation & Maintenance Manual 67
Maintenance
Maintenance Schedule
Check Point
Daily Monthly
Every
2 months
Every
3 months
Every
6 months
Every
1 year
Every
2 years
Every
3 years
Every
6 years
1. Cycle Status
Check
2. Electric part
Check
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Monthly check
3. Safety switches
Check Monthly check
4. Water Loop System
Check
Clean
Check every 6 months
5. Condenser cleanness
Check
6. Cooling tower cleanness
Check Clean Annual clean
7. Refrigerant system leakage
Check
Monthly check
8. Oil filter
Check
Replace
Check every 6 months. Clean if necessary.
9. Dryer filter
Check
Replace
Annual replacement
10. Oil Level
Check
Annual check
11. Oil color
Check
Replace
12. Compressor insulation
Check
Annual check
13. Temperature sensor
Check
Check every 6 months
14. Compressor bearing
Check
Check or
replace
Check every 6 months. When the operating pressure
of the cooler is out of the range, clean the unit.
10h 500h 1000h 1500h 2500h 5000h 10000h 15000h 30000h
---
-- -
Table 24
Page 68
Trouble Shooting
68 Chiller Air-cooled Screw
If a stoppage occurs more than once as a result of any of the safety devices, determine and correct the cause before attempting another restart.
TROUBLE SHOOTING
General Malfunction
Before specific alarm trouble shooting, general troubles and their possible remedies are introduced. When the unit does not run at all, you have to check power supply to the chiller, refrigerant, configuration, and alarm invocation. For the power supply check, you have to check voltage applied to the terminal block inside of the power panel. If the power is absent, please check power feeder and check whether any protective device is tripped.
When the power is applied properly, refrigerant pressure must be inspected by pressure gauge installed on the chiller, when the pressure is out of range, please check whether any leakage point is by soap bubble test. If there is problem with the configuration of the PLC or too much delay is configured, the chiller will not start or the start is delayed for long time. Please recover the configuration value to factory setting before starting the chiller. Lastly, alarm invocation has to be checked. You can find whether any alarm is invoked through the HMI unit. Follow specific alarm trouble shooting procedure if any alarm is invoked. Normally, the compressor of the chiller will cycle according to the chilled water leaving temperature, the compressor shutdown temperature and the compressor restart temperature. But the case where the compressor runs too long without cycling can be encountered. When the refrigerant is not enough, the chiller will operate continuously because the chiller cannot work at 100% power. At this case, the leakage is also to be inspected. When magnetic contactors for the compressor are mechanically welded, the chiller operation will be continued, because the PLC cannot stop the compressor by control signal even if the compressor must be stopped. When there is no problem with the refrigerant and compressor contactor, Air inside of the water loop can be a cause, because air inside of water loop obstructs ther­mal exchange. When the problem is revealed, the air must be purged. When there is non-condensables in the refriger­ant circuit, remove the refrigerant and recharge. Even after running condenser fan and chilled water pump, the compressor will not run caused by alarm or trouble with temperature reading. Please follow specific alarm trouble shooting procedure at this case.
Page 69
Trouble Shooting
Operation & Maintenance Manual 69
Symptom
Unit does not run
Compressor operates too long continuously
Possible Cause
Possible Remedy
Check over current protection device Check no-fused disconnect (if equipped) Restore power to unit
Check for leak and add refrigerant Check unit configuration
Check Alarm status. See separate alarm trouble shooting procedure and follow trouble shooting instructions Check the PLC input channels also to verify alarm status Input
Check fulfillment of oil heating time Check fulfillment of comp start delay time Check chilled water temp out Check water flow
Check for leak and add refrigerant Replace the contactors
Purge water loop Remove refrigerant and recharge
Check Alarm status. See separate alarm trouble shooting procedure and follow trouble shooting instructions
Check for temperature inputs. See operation and control. Check capacity control overrides Check the PLC input channels also to verify alarm status Input
Check for power to unit
Low refrigerant charge Wrong or incorrect unit
configuration Active alarm
Active operating mode
Low refrigerant charge Compressor or control con-
tacts welded Air in chilled water loop Non-condensables in refriger-
ant circuit Active alarm
Active operating mode
Table 25
Circuit does not run
Page 70
Trouble Shooting
70 Chiller Air-cooled Screw
Alarm
Specific alarms, their recognition method, and their possible causes are listed here. To clear alarm and recover from the alarm, clear the alarm history after correction of the cause of the alarm.
The emergency trouble means that the emergency switch installed on the right side of the control panel is pushed by operator. This switch input is normally closed and the trouble means the switch input is opened. When the emergency switch is opened output power for the output control from the PLC is disconnected. By pulling the emergency switch, the alarm can be corrected.
5E relay, voltage monitoring relay signals alarm when there is trouble with the power supply. The trouble includes over voltage, under voltage, reversed phase, phase loss, and voltage unbalance. Please be sure that all fuses for detecting of power supply are not melted in case of phase loss alarm.
Liquid flow trouble means the absence of water flow or shortage of the water flow under 70% of rated water at default value. Water pump malfunction and shortage of water volume must be observed concurrently to solve the problem.
Pressure trouble means tripping of high pressure cutout switch or low pressure cutout switch. Both of them are pack­aged in dual pressure switch. When the problem is encountered, proper amount of the refrigerant inside of the chiller must be inspected firstly. If there is no problem with the amount of the refrigerant, contaminated heat exchanger can be a reason. Please consider the operating ambient temperature range of the chiller is from 64.4°F~129.2°F(18°C~54°C).
Oil trouble means oil flow absence from the oil separator to the compressor or low oil level in the oil separator. This alarm is checked after 120 second after running the compressor.
The delay is adjustable through delay setting of the HMI unit. Shortage of oil must be inspected firstly. When the chiller runs under low ambient temperature without enough pre-heating, much amount of oil can be remained in evaporator instead of the oil separator. In this case, oil must be added up to the oil separator.
Low differential pressure between the evaporator and the condenser will not guarantee proper oil circulation, so the dif­ferential pressure must be inspected through pressure gauge.
M1 and M2 are magnetic contactors for screw compressor. The malfunctions of the magnetic contactors mean OCR trip by overload condition or problem with the contacts of the magnetic contactors themselves.
INT69 trouble means that the internal protector inside of terminal box of the compressor detect abnormally high temper­ature on the motor winding or compressor discharge.
There can be two sources for the anti-freezing S/W trouble. Actually, the alarm is recognized by tripping of anti-freezing switch of low water temperature detected by temperature sensor. In case of the low water temperature, the setting point for the determination of the alarm can be changed by HMI unit.
When there is mechanically welded contact problem with the magnetic contactors for the compressor, the PLC cannot stop the compressor and consequently you can encounter this alarm at the case. Therefore, in this case you must turn off the circuit breaker located before the malfunctioning magnetic contactor.
Fan trouble is similar with the M1 or M2 trouble in the case of the compressor. It means OCR trip by overload condition or problem with the contacts of the magnetic contactors.
Discharge temp trouble is invoked when the compressor discharge temperature is over 176°F(80°C). This can be caused by shortage of refrigerant or too high ambient temperature
COMM fault trouble means communication failure between the HMI unit and the PLC, loosed connection is frequently encountered cause the trouble
Page 71
Trouble Shooting
Operation & Maintenance Manual 71
Displayed Alarm
Message
Recognition
Possible Cause
Possible Remedy
Turn the emergency switch clockwise to return
Emergency switch input(switch off)
Trip of emergency
Emergency Stop
Review chilled CHW tempera­ture, ambient temperature or applicable sensor
Trip of differential pres­sure switch (switch off) after the compressor run (default: DP < 4kgf/cm2)
Too high chilled CHW tempera­ture
Too low ambient temperature
Dp Alarm
Check power
Repair or replace 5E protective
switch
Trip of voltage moni­toring relay (switch off)
Over voltage
Under voltage
Reversed phase
Voltage unbalance
Missing phase
5E Alarm
Repair or replace CHW pump
Remove air and supplement
water
CHW line side valve open
Flow switch setting or device
error
CHW flow switch input (switch off) after the CHW pump run
CHW pump malfunction
Shortage of CHW volume
CHW line side valve closed
Flow switch setting or device
error
Waterflow Alarm
Remove over charging refriger­ant
Repair or replace high pressure switch
Vacuum and recharge after removing refrigerant
Adjust high pressure switch set­ting
Repair or replace controller
Charge additional refrigerant
Repair or replace an external fan
motor
Trip of high pressure switch
Over charge of refrigerant
High pressure switch error
Air mixed into refrigerant
High pressure switch setting too
low
Controller DI point error
Insufficient refrigerant
External fan motor error
Pressure Alarm
Page 72
Displayed Alarm
Message
Recognition
Possible Cause
Possible Remedy
Trouble Shooting
72 Chiller Air-cooled Screw
Charge additional refrigerant
Test/Repair as necessary and
charge additional refrigerant
Adjust low pressure switch setting
Repair or replace Low pressure
switch
Repair or replace controller
Trip of low pressure
switch
Insufficient refrigerant
Refrigerant leakage
Low pressure switch setting too
high
Low pressure switch error
Controller DI point error
Pressure Alarm
Replace oil dryer
Replace oil service valve
Repair or replace oil flow switch
Repair or replace controller
Supplement oil
Oil flow switch input
(switch off) 120 sec­ond after the compres­sor run
Oil dryer clogged
Oil service valve error or closed
Oil flow switch error
Controller DI error
Shortage of oil
Replace oil level switch
Repair or replace controller
Supplement oil
Oil level switch input
(switch off) 120 sec­ond after the compres­sor run
Oil level switch error
Controller DI point error
Shortage of oil
System Oil Alarm
Replace M1 contactor
Check voltage, check condenser
fan motor, clean heat exchanger, repair overload relay, repair or replace compressor
Repair or replace controller
M1 magnetic contactor
contact input or over­load relay contact input (switch off) after the compressor run
Malfunction of M1
Compressor overload
Controller DI or DO point error
M1 Contactor Alarm
Replace M2 contactor
Repair or replace controller
M2 magnetic contactor
contact input after the compressor run
Malfunction of M2
Controller DI or DO point error
M2 Contactor Alarm
Page 73
Displayed Alarm
Message
Recognition
Possible Cause
Possible Remedy
Trouble Shooting
Operation & Maintenance Manual 73
Review voltage
Repair or replace controller
Test or replace comp
Test or replace internal protective
switch
Check condenser fan motor
Clean condenser fin
Trip of compressor
internal protector (switch off) by high compressor winding temperature
Voltage error
Controller DI or DO point error
Comp error
Internal protective switch error
Condenser fan motor error
Contamination of condenser fin.
Comp overload Alarm
Charge additional refrigerant or review valve condition
Repair or replace controller
Repair comp
Test or replace internal protec-
tive switch
Check ambient temperature
Trip of compressor
internal protector (switch off) by high discharge temperature
Refrigerant flow rate insufficient
Controller AI point error
Comp error
Internal protective switch error
Too high ambient temperature.
Increase CHW flow or replace
pump
Increase set value of chilled CHW temp out
Lower anti-freezing set value
Replace anti-freezing switch
Check ambient temperature
Repair or replace controller
Supplement refrigerant
Clean cooler
Replace M1 or M2
Trip of anti-freezing switch (switch off) (Default: chiller CHW temp out 35.6°F(2°C)
CHW flow insufficient
Too low set value of chilled CHW
temp out
Too high anti-freezing set value
Anti-freezing switch error
Too low ambient temperature
Controller DI error
Refrigerant insufficient
Contamination of cooler
Malfunction of M1 or M2
Low temp
Page 74
Displayed Alarm
Message
Recognition
Possible Cause
Possible Remedy
Trouble Shooting
74 Chiller Air-cooled Screw
Charge additional refrigerant or review valve condition
Repair comp
Check ambient temperature
Compressor discharge
temperature is over 194°F(90°C) after the compressor run
Refrigerant flow rate insufficient
Comp error
Too high ambient temperature
Exhaust Temp Alarm
Check connection between PLC and HMI unit
Communication failure
Communication failure between
the PLC and the HMI unit
Contact fault alarm
Replace FAN1A1B motor, check magnetic contactor or relay
Check FAN1A1B lock
FAN1A1B magnetic
contactor contact input or overload relay con­tact input (switch off) after the compressor run
Malfunction of FAN1A1B
Condenser FAN1A1B overload
FAN1A1B Alarm
Replace FAN2A3A motor, check magnetic contactor or relay
Check FAN2A3A lock
FAN2A3A magnetic
contactor contact input or overload relay con­tact input (switch off) after the compressor run
Malfunction of FAN2A3A
Condenser FAN2A3A overload
FAN2A3A Alarm
Replace FAN4A5A motor, check magnetic contactor or relay
Check FAN4A5A lock
FAN4A5A magnetic
contactor contact input or overload relay con­tact input (switch off) after the compressor run
Malfunction of FAN4A5A
Condenser FAN4A5A overload
FAN4A5A Alarm
Page 75
Displayed Alarm
Message
Recognition
Possible Cause
Possible Remedy
Trouble Shooting
Operation & Maintenance Manual 75
FAN2B3B Alarm
FAN4B5B Alarm
Exhaust temp sensor close
Exhaust temp sensor open
CHW In temp sensor close
CHW In temp sensor open
CHW out temp sensor close
CHW out temp sensor open
Condensate temp close
Condensate temp open
Ambient temp close
Ambient temp open
FAN2B3B magnetic contactor contact input or overload relay con­tact input (switch off) after the compressor run
FAN4B5B magnetic contactor contact input or overload relay con­tact input (switch off) after the compressor run
Compressor discharge temperature sensor close
Compressor discharge temperature sensor open
Chilled water in temper­ature sensor close
Chilled water in temper­ature sensor open
Chilled water out tem­perature sensor close
Chilled water out tem­perature sensor open
Condensation tempera­ture sensor close
Condensation tempera­ture sensor open
Ambient temperature sensor close
Ambient temperature sensor open
Malfunction of FAN2B3B
Condenser FAN2B3B overload
Malfunction of FAN4B5B
Condenser FAN4B5B overload
Sensor line is short
Malfunction of Sensor
Sensor line is cut out or loose
Malfunction of Sensor
Sensor line is short
Malfunction of Sensor
Sensor line is cut out or loose
Malfunction of Sensor
Sensor line is short
Malfunction of Sensor
Sensor line is cut out or loose
Malfunction of Sensor
Sensor line is short
Malfunction of Sensor
Sensor line is cut out or loose
Malfunction of Sensor
Sensor line is short
Malfunction of Sensor
Sensor line is cut out or loose
Malfunction of Sensor
Replace FAN2B3B motor, check
magnetic contactor or relay
Check FAN2B3B lock
Replace FAN4B5B motor, check
magnetic contactor or relay
Check FAN4B5B lock
Check sensor line
Change sensor
Check sensor line
Change sensor
Check sensor line
Change sensor
Check sensor line
Change sensor
Check sensor line
Change sensor
Check sensor line
Change sensor
Check sensor line
Change sensor
Check sensor line
Change sensor
Check sensor line
Change sensor
Check sensor line
Change sensor
Table 26
Page 76
Appendix
76 Chiller Air-cooled Screw
Appendix
Wiring Diagram
Fig. 47
SYMBOL
Fuses
P/Box Heat dissipation fan
LEGEND
DESCRIPTION
Assist relay
C/Box Heat dissipation fan
Oil heater
Inner temperature controller
Oil seperator sol. v/v
Comp. capacity control v/v
Mid pressure air charging sol. v/v
Comp. magnetic switch 1
F1~F3
CF1
CF2
R1 R2
CCH1
THC
SV1
SV2
M2M1 M3
M1M2M3
Comp. magnetic switch 2 ( )
Comp. magnetic switch 3 ( Y )
Fan1A~Fan4A over current relays
Comp over current relay
Fan1A~Fan4A magnet contactors
FN1A ~ FN4A
FN1B ~ FN4B
Fan1B~Fan4B magnet contactors
OLC1
OLF1A ~ OLF4A
OLF1B ~ OLF4B
Fan1B~Fan4B over current relays
L0
Power indicator lamp
Emergency switch
SW1
HP
LP
5E
Low pressure switch
Reverse phase protector
High pressure switch
Mold option switch
RST
N
RST
F3
VOLTAGE
MONITORING
(5E)
TO MAN CONTROL
UNIT
L
M
220VAC
N
2
R
1
CB
F1
L0
CF1
R1
CF2
3
3
4
START/STOP SWITCH
L
4
220VAC
LM
4
N
2
SMPS
4
2
-V+V
26 27
24VDC-P
24VDC-G
COOLER IN TEMP
COOLER OUT TEMP
COMP DISCHARGE TEMP
AMBIENT TEMP
COND OUT TEMP
26 27 1011 1213141516 17 18 19 27 26 31 32 3334 35 36 37 38 39
40
41
42
43 44 45
27 26
REMOTE RUN
OIL FLOW OIL FLOW
OLC1 M1
M2
ANTI-FREEZING
LP HP
CHILLED WATER FLOW
HIGH-LOW DIFFERENTIAL
INT69
5E
OLF1A
OLF2A
OLF2B
FN1A
FN2A
FN2B
101
OLF1B
OLF3B
FN1B
FN3A
FN3B
104
110
102
105
111
103
106
112
EMERGENCY SWITCH
RTD1
+24V
-24V
RTD1 RTD2RTD2 RTD3RTD3 RTD4 RTD4 RTD5 RTD5
-(2) +(1) -(4) +(3) -(6) +(5) -(8) +(7) -(10) +(9)
24V-G IO1 IO2 IO3 IO4 IO5 IO6 IO7 IO8 IO9 I10 I11 I12 I13 I14 I15 I16
COM O01 O02 O03 O04 O05 O06 O07 O08 O09 O10 O11 O12 O13 O14 O15 O16 O17 O18 O19 O20COM
7 71 72 73 74 75 76 77 78 7 79 80 81 85
CHILLED WATER PUMP
SV1
M1
M2
M3 MV1 MV2
MV3
FN1A FN1B FN2A FN2B FN3A FN3B
FAULT
A1 A1 A1
A2 A2 A2
A1
A1
A1 A1 A1 A1
A2 A2 A2 A2 A2 A2
R2
EMRG
EMRG
47
2
HMI
UNI
T
MAIN CONTROL UNIT
Output (Primary) Output (Secondary)
Intput (Primary)
Intput (Secondary)
FAN 1B FAN 2B FAN 3B
OLF1B
4.5A (3.5-5)
OLF2B
4.5A (3.5-5)
OLF3B
4.5A (3.5-5)
1L1 3L2 5L3 1L1 3L2 5L3 1L1 3L2 5L3
1L1 3L2 5L3 1L1 3L2 5L3 1L1 3L2 5L3
2T1 4T2 6T3 2T1 4T2 6T3 2T1 4T2 6T3
2T1 4T2 6T3 2T1 4T2 6T3 2T1 4T2 6T3
FN1B FN2B FN3B
FAN 1A FAN 2A FAN 3A
40472
4
INTERNAL
PROTECTOR
(INT69)
11122
4
1
2
OLF1A
4.5A (3.5-5)
OLF2A
4.5A (3.5-5)
OLF3A
4.5A (3.5-5)
FN1A FN2A FN3
A
L1
L2
L3
M3
2T1
T2
T3
4T2 6T3
2T1
4T2 6T3
1L1
3L2 5L3
1L1
3L2 5L3
40
OLC1
107A
(100~135)
202
M1 F2
CCH1
THC
COMP
W
VU
X
Y
Z
FG
TO MAIN CONTROL UNIT
400VAC3P 4W
M2 M1
89
32
97 98
24V 24V-G 24V
46
2
4
Transformer
R2
R2
R2
R2
301
302
303 304
301
302
304305
CCW COM
COM
CW
SV2
RCAW1008
Page 77
Appendix
Operation & Maintenance Manual 77
Fig. 48
SYMBOL
Fuses
P/Box Heat dissipation fan
LEGEND
DESCRIPTION
Assist relay
C/Box Heat dissipation fan
Oil heater
Inner temperature controller
Oil seperator sol. v/v
Comp. capacity control v/v
Mid pressure air charging sol. v/v
Comp. magnetic switch 1
F1~F3
CF1
CF2
R1
CCH1
THC
SV1
SV2
M2M1 M3
M1M2M3
Comp. magnetic switch 2 ( )
Comp. magnetic switch 3 ( Y )
Fan1A~Fan4A over current relays
Comp over current relay
Fan1A~Fan4A magnet contactors
FN1A ~ FN4A
FN1B ~ FN4B
Fan1B~Fan4B magnet contactors
OLC1
OLF1A ~ OLF4A
OLF1B ~ OLF4B
Fan1B~Fan4B over current relays
L0
Power indicator lamp
Emergency switch
SW1
HP
LP
5E
Low pressure switch
Reverse phase protector
High pressure switch
Mold option switch
RCAW090PBAA
Page 78
Appendix
78 Chiller Air-cooled Screw
n Cycle Diagram
Fig. 49
DESCRIPTION
No
Compressor
1
Condensing coil
2
Receiver
3
Oil Filter
4
Oil separater
5
Ejector for Oil Return
6
Expansion Devices
7,8
Filter Drier
9
Evaporator
10
SYMBOL
Oil heater
High pressure switch
LEGEND
OH
DESCRIPTION
HPS
LPS
Low pressure switch
Temperature sensor
TS
Oil level sensor
OLS
Oil flow switch
OFS
Water flow switch
Relief valve
WFS
AFS
Anti-freezing switch
OS
S
Insulation
Oil sol. valve
Sight glass
Refrigerant sol. valve
Economizer (Flash gas tank)
11
Check valve
Service valve
3
2
6
4
5
7
1
9
10
8
Oil Pipe Line
Low Pressure Line
High Pressue Line
TS
OS
S
Liquid Injection Line
HPS
TS
AFS
LPS
TS
TS
WFS
OFS
OH
OLS
Pipe line
11
RCAW090,100
Page 79
Appendix
Operation & Maintenance Manual 79
n Check List
1. Project information
2. Model information
Checklist for installation, and operation
Contents Description
PJT name
Address
Installing contractor
Sales office
Start-up performer
Contents Description
PJT name
Address
Installing contractor
Sales office
Start-up performer
Contents Description
Unit
Model: Serial:
Compressor A
Model: Serial:
Compressor B
Model: Serial:
Page 80
Appendix
80 Chiller Air-cooled Screw
3. PRELIMINARY EQUIPMENT CHECK
4. Chilled Water System Check
CheckContents
NoYesDrain pipe is not clogged.
NoYesInlet piping to cooler includes strainer.
NoYesChilled water flow switch is operational.
NoYesChilled water pump starter interlocked with chiller.
NoYesChilled water pump is operating with the correct rotation.
NoYesAll air has been purged from the system.
NoYesThere is no leakage.
No
No
YesAll piping is connected properly.
YesAll chilled water valves are open.
CheckContents
Is there any physical damage? Yes No
ơ If yes, where?
Will this prevent start-up. Yes No
All screws and bolts are tight. Yes No
Power supply agrees with the unit nameplate. Yes No
Electrical power wiring is installed properly. Yes No
Unit is properly grounded. Yes No
Electrical circuit protection has been sized and installed properly. Yes No
All terminals are tight. Yes No
All plug assemblies are tight. Yes No
Oil heaters energized for 8 hours before start-up. Yes No
Relief valve vents piping per local codes. Yes No
Page 81
Appendix
Operation & Maintenance Manual 81
5. START-UP & OPERATION
Ambient air temperature
%
C
C
C
Compressor capacity
psigCooler pressure drop
psigRefrigerant high pressure
psigRefrigerant low pressure
lbsAdditional refrigerant charge
Gpm(l/s)Chilled water flow rate
Chilled water inlet temperature
%Brine concentration
NoYesThere is no abnormal noise or vibration
lbsAdditional oil charge
Chilled water inlet temperature
NoYesAlarm is not generated, and the unit operates normally.
NoYes
Voltage imbalance is within 2%
NoYes
Voltage at terminal block is within 10%
No
No
Yes
There is leakage of refrigerant. (Comp, Condenser, Economizer, Cooler…)
Yes
All refrigerant line service valves are open. (discharge, suction, economizer, oil line part…)
CheckContents
Page 82
P/No.: MFL63291701
Printed in Korea
After reading this manual, keep it in a place easily accessible to the user for future reference.
Loading...