LG PRHR063A INSTALLATION MANUAL

<![if ! IE]>

<![endif]>ESPAÑOL FRANÇAIS ENGLISH

INSTALLATION MANUAL

AIR

CONDITIONER

Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Please retain this installation manual for future reference after reading it thoroughly.

PRHR083A/PRHR063A/PRHR043A/PRHR033A/PRHR023A (Heat Recovery Unit)

Original instruction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

http://www.lghvac.com

 

 

MFL32987321

 

 

 

 

 

 

www.lg.com

 

Rev.00_052418

 

 

 

 

 

 

Copyright © 2018 LG Electronics Inc. All Rights Reserved.

<![if ! IE]>

<![endif]>ENGLISH

2 TIPS FOR SAVING ENERGY

TIPS FOR SAVING ENERGY

Here are some tips that will help you minimize power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:

Do not cool excessively indoors. This may consume more electricity.

Block sunlight with blinds or curtains while you are operating the air conditioner.

Keep doors or windows closed tightly while you are operating the air conditioner.

Adjust the direction of the air flow vertically or horizontally to circulate indoor air.

Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.

For your records

Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:

Model number :

Serial number :

You can find them on a label on the side of each unit.

Dealer’s name :

Date of purchase :

IMPORTANT SAFETY INSTRUCTIONS 3

IMPORTANT SAFETY INSTRUCTIONS

READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.

Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product

! WARNING

It can result in serious injury or death when the directions are ignored

! CAUTION

It can result in minor injury or product damage when the directions are ignored

! WARNING

Installation or repairs made by unqualified persons can result in hazards to you and others.

The information contained in the manual is intended for use by a qualified service contractor familiar with safety procedures and equipped with the proper tools and test instruments.

Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.

! WARNING

Have all electric work done by a licensed electrician according to "Electric Facility Engineering Standard" and "Interior Wire Regulations" and the instructions given in this manual and always use a special circuit.

-If the power source capacity is inadequate or electric work is performed improperly, electric shock or fire may result.

Ask the dealer or an authorized contractor to install the HR unit.

-Improper installation by the user may result in water leakage, electric shock, or fire.

<![if ! IE]>

<![endif]>ENGLISH

 

4

IMPORTANT SAFETY INSTRUCTIONS

 

 

<![if ! IE]>

<![endif]>ENGLISH

• Always ground the product.

 

 

- There is risk of fire or electric shock.

 

• Make the connections securely so that the outside force of

 

 

the cable may not be applied to the terminals.

 

- Inadequate connection and fastening may generate heat and

 

 

cause a fire.

 

• For re-installation of the installed product, always contact a

 

dealer or an Authorized Service Center.

 

- There is risk of fire, electric shock, explosion, or injury.

 

• Do not install, remove, or re-install the unit by yourself

 

(customer).

 

- There is risk of fire, electric shock, explosion, or injury.

 

- All work should be performed by a qualified, licensed

 

 

contractor.

 

• Do not store or use flammable gas or combustibles near the

 

HR Unit.

 

- There is risk of fire or failure of product.

 

• Use a properly rated breaker or fuse.

 

- There is risk of fire or electric shock.

 

• Do not damage or use an unspecified power cord.

 

- There is risk of fire, electric shock, explosion, or injury.

 

• Do not touch the power switch with wet hands.

 

- There is risk of fire, electric shock, explosion, or injury.

 

• Securely install the cover of control box and the panel.

 

- If the cover and panel are not installed securely, dust or

 

 

water may enter the HR unit and fire or electric shock may

 

 

result.

 

• Be cautious when unpacking and installing the product.

 

- Sharp edges could cause injury. Be especially careful of the

 

 

case edges.

 

• Safely dispose of the packing materials.

 

 

- Packing materials, such as nails and other metal or wooden

 

 

parts, may cause puncture wounds or other injuries.

 

 

- Tear apart and throw away plastic packaging bags so that

 

 

children may not play with them and risk suffocation and

 

 

death.

IMPORTANT SAFETY INSTRUCTIONS 5

! CAUTION

Avoid a place where rain may enter since the HR unit is for indoor installations only.

-There is risk of property damage, failure of product, or electric shock.

Do not install a HR unit in a space where persons exists such as living room, office or meeting room with not only low but also open ceiling.

Always check for gas (refrigerant) leakage after installation or repair of product.

-Low refrigerant levels may cause failure of product.

Keep level even when installing the product.

-To avoid vibration or water leakage.

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.

-Children should be supervised to ensure that they do not play with the appliance.

<![if ! IE]>

<![endif]>ENGLISH

<![if ! IE]>

<![endif]>ENGLISH

6

TABLE OF CONTENTS

 

 

TABLE OF CONTENTS

2TIPS FOR SAVING ENERGY

3IMPORTANT SAFETY INSTRUCTIONS

7FEATURES

9INSTALLATION PART

10 INSTALLATION

10 Selection of the best location

10 Dimensional drawings

13 HR Unit Installation

16Insulation

17Wiring Connection

18HR Unit PCB

19Setting the HR Unit switches

26COIL EXCHANGING METHOD

27JOINT METHOD OF HR UNIT

FEATURES 7

FEATURES

Control Box

Connection Pipe (to outdoor unit)

Connection Pipe

(to outdoor unit)

Connection Pipe (to indoor unit)

Model

 

 

PRHR023A

 

PRHR033A

 

PRHR043A

 

 

 

 

 

 

Max. Connectable No. of Indoor Units

16

 

24

 

32

 

 

 

 

 

 

Max. Connectable No. of Indoor Units of a branch

8

 

8

 

8

 

 

 

 

 

 

 

 

Power Input

Cooling [W]

 

 

39.8

 

 

 

 

 

 

 

 

 

Heating [W]

 

 

37.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Net. Weight

kg

 

14.9

 

16.7

 

18.2

 

 

 

 

 

 

 

lbs

 

32.8

 

36.8

 

40.1

 

 

 

 

 

 

 

 

 

 

 

 

Shipping

kg

 

20.7

 

22.5

 

24.0

 

 

 

 

 

 

 

Weight

lbs

 

45.6

 

49.6

 

52.9

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions

mm

 

 

 

786 X 218 X 657

 

 

 

 

 

 

 

 

(WxHxD)

Inch

 

 

 

30.9 X 8.6 X 25.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Casing

 

 

 

Galvanized steel plate

 

 

 

 

 

 

 

 

 

 

 

Liquid Pipe

 

Ø9.52[3/8] – Ø6.35[1/4]

 

 

 

[mm/inch]

 

 

 

Indoor side

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Pipe

 

Ø15.88[5/8] – Ø12.7[1/2]

 

 

 

 

 

[mm/inch]

 

 

 

 

 

 

 

 

Connecting

 

 

 

 

 

 

 

 

Liquid

Ø9.52[3/8]

 

Ø12.7[1/2]

 

Ø15.88[5/8]

Pipes

 

[mm/inch]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor side

Low Pressure

Ø22.2[7/8]

 

Ø28.58[1-1/8]

 

Ø28.58[1-1/8]

 

[mm/inch]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Pressure

Ø19.05[3/4]

 

Ø22.2[7/8]

 

Ø22.2[7/8]

 

 

[mm/inch]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound Absorbing Insulation Material

 

Polyethylene Foam

 

 

 

 

 

 

 

 

 

Current

Minimum circuit Amps(MCA)

 

0.17

 

 

 

 

 

 

 

 

 

Maximum fuse Amps(MFA)

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Supply

 

 

 

1Ø, 208/230 V, 60 Hz

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>ENGLISH

<![if ! IE]>

<![endif]>ENGLISH

8 FEATURES

Connection Pipe

(to outdoor unit)

Control Box

Connection Pipe

(to indoor unit)

Connection Pipe (to outdoor unit)

Model

 

 

PRHR063A

 

PRHR083A

 

 

 

 

Max. Connectable No. of Indoor Units

48

 

64

 

 

 

 

Max. Connectable No. of Indoor Units of a branch

8

 

8

 

 

 

 

 

 

Power Input

Cooling [W]

75.9

 

 

 

 

 

 

Heating [W]

72.1

 

 

 

 

 

 

 

 

 

Net. Weight

kg

 

27.2

 

30.7

 

 

 

 

 

lbs

 

60.0

 

67.7

 

 

 

 

 

 

 

 

 

Shipping

kg

 

33.8

 

37.3

 

 

 

 

 

Weight

lbs

 

74.5

 

82.2

 

 

 

 

 

 

 

 

Dimensions

mm

 

1 113 X 218 X 657

 

 

 

 

 

(WxHxD)

Inch

 

43.8 X 8.6 X 25.9

 

 

 

 

 

 

 

 

 

Casing

 

 

Galvanized steel plate

 

 

 

 

 

 

Indoor

Liquid Pipe [mm/inch]

Ø9.52[3/8] – Ø6.35[1/4]

 

 

 

 

 

 

side

Gas Pipe [mm/inch]

Ø15.88[5/8] – Ø12.7[1/2]

 

 

Connecting

 

 

 

 

 

 

Liquid [mm/inch]

Ø15.88[5/8]

 

Pipes

 

 

Outdoor

 

 

 

 

 

Low Pressure [mm/inch]

Ø28.58[1-1/8]

 

 

side

 

 

 

 

 

High Pressure [mm/inch]

Ø22.2[7/8]

 

 

 

 

 

 

 

 

 

Sound Absorbing Insulation Material

Polyethylene Foam

 

 

 

 

 

 

Current

Minimum circuit Amps(MCA)

0.27

 

 

 

 

 

 

Maximum fuse Amps(MFA)

15

 

 

 

 

 

 

 

 

Power Supply

 

 

1Ø, 208/230 V, 60 Hz

 

 

 

 

 

 

LG PRHR063A INSTALLATION MANUAL

INSTALLATION PART 9

INSTALLATION PART

-Installation Manual

-Hanging bolts (4 x M10 or M8), Nut(8 x M10 or M8), Flat washers(8 x M10)

-Reducers

[Unit : mm(inch)]

Gas pipe

Models

Liquid pipe

High pressure

Low pressure

 

 

 

PRHR023A

 

 

OD19.05(3/4)

Ø15.88(5/8) Ø12.7(1/2)

OD22.2(7/8) Ø19.05(3/4) Ø15.88(5/8)

 

 

 

 

OD9.52(3/8)

Ø6.35(1/4)

 

 

 

 

 

 

 

 

 

 

 

 

 

HR unit

 

 

OD12.7(1/2)

Ø9.52(3/8)

OD15.88(5/8) Ø12.7(1/2)

reducer

 

 

 

 

 

 

 

 

PRHR033A

 

 

OD22.2(7/8)

Ø19.05(3/4) Ø15.88(5/8)

 

 

PRHR043A

OD15.88(5/8) Ø12.7(1/2) Ø9.52(3/8)

OD28.58(1-1/8) Ø22.2(7/8) Ø19.05(3/4)

PRHR063A

 

 

 

 

 

 

 

 

PRHR083A

 

 

 

 

 

 

 

 

 

OD12.7(1/2)

Ø9.52(3/8)

OD15.88(5/8)

Ø12.7(1/2)

OD19.05(3/4)

Ø15.88(5/8)

<![if ! IE]>

<![endif]>ENGLISH

Loading...