LG PRCKD40E INSTALLATION MANUAL

LG AHU CONTROL KIT
Installation Manual
LG
IMPORTANT
• Please read this installation manual completely before installing the product.
• Please retain this installation manual for future reference after reading it thoroughly.
Visit us at : http://www.lgservice.com
Models: PRCKD20E
PRCKD40E
2 AHU CONTROL KIT
AHU CONTROL KIT Installation Manual
TABLE OF CONTENTS
Safety Precautions...............................................................................3
Installation configuration ......................................................................5
Supplies ...............................................................................................6
Wiring diagram .....................................................................................9
Installation flowchart ..........................................................................13
CONTROL KIT Installation.................................................................14
Pipe temperature sensor connection .................................................16
Outdoor communication cable connection.........................................17
Precaution..........................................................................................18
AHU sensor specification...................................................................20
AHU sensor connection .....................................................................21
AHU controller setting ........................................................................27
Communication PCB setting ..............................................................32
Electric wiring work ............................................................................34
Test run ..............................................................................................36
Safety Precautions
Installation Manual 3
Installation
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
Be sure not to do.
Be sure to follow the instruction.
WARNING
Do not use the existing manifold gauge for R22 refrigerant.
• To charge the refrigerant stably, always use the manifold gauge for high pressure (R410A).
Install the air conditioner at a designated location using the designated material.
• Heat exchanger inlet/outlet pipe location.
Do not store or use flammable gas or volatile substance near the air conditioner.
• It can cause a fire or problem to the product.
Do not mix existing R22 pipe and installation products for the installation.
• When you mix the mineral oil of R22 and R410A oil (PVE), it can decompose with water to cause problems to the product.
Do not mix other refrigerant with the designated refrigerant (R410A) during the installation or moving the air conditioner.
• When other refrigerant is mixed with the original refrigerant, it can cause a problem in the refrigerant cycle and damage the product.
System air conditioner can only be installed by specialized service provider with air condition installation certifications.
• Inappropriate installation can cause leakage, fire and electric shock.
When moving or reinstalling the air conditioner, please contact the
MULTI VTM AHU
installation service provider.
• Inappropriate installation can cause leakage, fire and electric shock.
Do not disassemble, repair or reconfigure the product arbitrarily.
• It can cause a fire and electric shock.
WARNING
CAUTION
Safety Precautions
4 AHU CONTROL KIT
Operation
Installation
Do not install the air conditioner outdoors.
• If installed outdoor inevitably, consult Multi
VTM
AHU installation service provider.
Do not let any worker or user climb on top of the product.
• The person can get seriously injured.
Make sure that water does not get inside the product (Controller). Especially, do not clean the product with water.
• It can cause electric shock and problems.
When the air conditioner is submersed in water, always consult
MULTI V
TM AHU
installation service provider.
• It can cause a fire and electric shock.
Do not keep any heating devices near the product.
• It can cause a fire.
After the product installation and repair, always check for gas leakage.
• It can cause problems in the product.
When installing the product, always make sure to level to the product.
• It can cause vibration and leakage.
Do not install the product where flammable gas leaks.
• It can cause a fire and problems to the product.
Operation
If the refrigerant leaked while installing the product, always ventilate the room.
• The refrigerant gas can react with the fire to turn into hazardous gas to cause an accident.
CAUTION
Installation Manual 5
Installation Scene
Installation configuration
RA
OA
SA
60H
8 -1
No. Name Remarks
Air Handling Unit -
CONTROL KIT PRCKD20E / PRCKD40E
EXPANSION KIT PATX13A0E/20A0E/25A0E/35A0E
Outdoor unit Multi V
Pipe temperature sensor IN Sensor: Ø5, Length: 5m,Cable color: Black
Pipe temperature sensor OUT Sensor: Ø7, Length: 5m, Cable color: Red
-1
Temperature sensor RA -50~50°C/ AC 24V / DC 0~10V
-2 Temperature sensor SA -50~50°C/ AC 24V / DC 0~10V
-1 Return Fan -
-2 Supply Fan -
MCC MCC
Installation components
Installation configuration diagram
Precaution during installation configuration
1. MCC is the construction of the equipment by the equipment provider and must be separately discussed before the installation.
2. Temperature or Temperature/Humidity sensor must be installed on the SA/RA duct for normal operation.
RA
2
220V0V/ 60H
EAEAOA
7 -1 7 -2
8 -1
9
MCC
z/1P1PHASE
SA
1
8 -2
5
6
RA: Return air
EA: Exhaust air
OA: Outdoor air
SA: Supply air
3
Powe r ca ble Refrigerant pipe Pipe temperature sensor Signal cable Communication cable Refrigerant flow (Air conditioning) Refrigerant flow (Heating)
4
Basic parts supplied
Sensor (Separately sold)
To operate the product, you must separately purchase and install the following temperature or temperature/humidity sensor.
Separate specification and installation location for the applied sensor can be checked fromAHU sensor specification”.
6 AHU CONTROL KIT
Supplies
Supplies
CONTROL KIT
- Quantity: 1EA
- Maximum number of outdoor units that can be connected:
- Quantity: 4EA
- Bolt quantity: 4EA Specification: M10/70mm
- Nut quantity:4EA Specification: M10
- Quantity: 1EA
- Quantity: 1EA - Quantity: 1EA
- Quantity: 1EA
- Quantity: 1EA
- Maximum number of outdoor units that can be connected:
- Quantity: 8EA
Model name
PRCKD20E
PRCKD40EE
Wired remote
controller
Installation bolt/nut
Installation
manual
User manual
온도조절 운전/정지
Installation
manual
User
manual
Item Specification
Temperature sensor - Power: AC24V
- Output signal: DC 0~10V
- Temperature range: -50~50°C
Temperature/ - Power: AC24V
Humidity sensor - Output signal: DC 0~10V
- Temperature range: -40~70°C
- Humidity range: 0~95%RH
Supplies
Installation Manual 7
Product configuration
PRCKD20E
* ( ) refers to the quantity applied to the PRCKD40E model.
No. Part name
Wired remote controller
Door
Selection switch
Lamp
Transformer
Terminal block #1
Terminal block #2
Wiring circuit breaker
Specification
- 1 AHU Controller -
1.6T
ON/OFF
Power/SA/RA
Input: 220V Output: 24V Capacity: 100VA
15A * 1.25mm
20A * 1.25mm
15A
Quantity
No.
1 Controller Case
2 250V, 5A 3
35A2
1-
2
2 2(4)
2
1 1.6T 1
1
Part name Specification
Fuse
Relay
Communication PCB
Communication PCB case
Control box
Quantity
1
-
-
-
1
2(4)
Supplies
8 AHU CONTROL KIT
BE
4-Ø12 Hole
A
FH G F
CD
(Side) (Front) (Rear)
(Floor)
PRCKD20E / PRCKD40E
Remarks
A (mm) 600 Length
B (mm) 750 Height
C (mm) 280 Width
D (mm) 500
Hole connecting to AHU
E (mm) 650
F 4-Ø16 Hole Pipe sensor connector
G 10-Ø25 Hole Sensor/Communication cable connector
H Ø30 Hole Power cable connector
Weight
Product 43.5 Product weight
Packaging 48 Weight after packaging
Depending on the installation personnel, the cable drawn to the F/G/H hole can be changed, and use the flexible pipe and connector that fits each hole.
Installation Manual 9
Wiring diagram
Part diagram
PRCKD40E
AHU controller part
Terminal block part #2
Terminal block part #1
Safety part
Communication PCB part #2
Communication PCB part
AHU controller part
Terminal block part #2
Terminal block part #1
(Inside product)
Safety part
Communication PCB part #2
Communication PCB part
Communication PCB #1 part is not attached to the PRCKD20E model.
Wiring diagram
10 AHU CONTROL KIT
AHU controller part
Communication PCB part (PRCKD20E)
Wiring diagram
Installation Manual 11
Communication PCB part (PRCKD40E)
Safety part (Transformer, wiring circuit breaker)
Wiring diagram
12 AHU CONTROL KIT
Terminal block part #1
Terminal block part #2
Installation flowchart
Installation Manual 13
Installation flowchart
This order can change depending on the construction site. Therefore please read
the installation manual prior to the applicable work.
CONTROL KIT installation
Pipe temperature
sensor connection
Outdoor unit communication
cable connection
AHU sensor connection
AHU controller setting
Communication PCB setting
Because 2 Outdoor units can be connected to 1 communication PCB, be careful not to get the pipe temperature sensor and communication cable connection to 1 Outdoor unit mixed and connected.
Temperature sensor that fits the specification must be installed in the SA duct and RA duct. (Specification: -50~50°C/ AC 24V / DC 0~10V)
Install the temperature sensor only for the SA/RA duct and Dip switch does not need to be set.
Depending on the installation site, if the optional sensor is applied, set the dip switch according to the setting method.
Be careful of Dip switch setting according to whether Outdoor unit is connected or not.
When connecting Outdoor unit, make sure to set Rotary switch differently.
Electric wiring
Outdoor unit address setting
Operation check
After completing the installation of CONTROL KIT, always set the address of Outdoor unit.
14 AHU CONTROL KIT
1. Check the location to install CONTROL KIT from the AHU product.
2. Check location of the hole on the rear side of CONTROL KIT and check whether accessories exist for the installation.
CONTROL KIT Installation
Product installation location check
CONTROL KIT Installation
Detail
650 mm
500
mm
4-Ø12 Hole
4 holes
Installation bolt (4EA)
Installation nut (4EA)
Installation accessories
<AHU>
<Rear side of CONTROL KIT>
Installation location (Factory condition)
The installation location of CONTROL KIT is coordinated prior to the AHU factory