INSTALLATION/OWNER'S MANUAL
AIR
CONDITIONER
www.lg.com
Please read this installation manual completely before installing the
product. Installation work must be performed in accordance with the
national wiring standards by authorized personnel only. This equipment shall
be provided with a supply conductor complying with the national regulation.
PDI Premium
PQNUD1S40
MFL67982922
Rev.00_051018
Copyright © 2018 LG Electronics Inc. All Rights Reserved.
ENGLISH
ITALIANO ESPAÑOL
FRANÇAIS
DEUTSCH
PORTUGUÊS
TÜRKÇE
РУССКИЙ ЯЗЫК
2
TIPS FOR SAVING ENERGY
ENGLISH
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
• Do not cool excessively indoors. This may be harmful for your health and may consume
more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may
block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
IMPORTANT SAFETY INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and
ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you
and others.
• Installation work must be performed in accordance with the National Electric
Code by qualified and authorized personnel only.
• The information contained in the manual is intended for use by a qualified
service technician familiar with safety procedures and equipped with the
proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in
equipment malfunction, property damage, personal injury and/or death.
WARNING
Installation
• Be sure to request to the service center or installation specialty store when
installing products. It will cause fire or electric shock or explosion or injury.
• Request to the service center or installation specialty store when reinstalling
the installed product. It will cause fire or electric shock or explosion or injury.
• Do not disassemble, fix, and modify products randomly.
It will cause fire or electric shock.
In-use
• Do not place flammable stuffs close to the product. It will cause fire.
• Do not allow water to run into the product.
It will cause electric shock or breakdown.
• Do not give the shock to the product.
It will cause breakdown when giving the shock to the product.
• Request to the service center or installation specialty store when the product
becomes wet. It will cause fire or electric shock.
!
!
!
!
3
ENGLISH
4
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Do not give the shock using sharp and pointed objects.
It will cause breakdown by damaging parts.
CAUTION
In-use
• Do not clean using the powerful detergent like solvent but use soft cloths.
It will cause fire or product deformation.
• Do not press the screen using powerful pressure or select two buttons.
It will cause product breakdown or malfunction.
• Do not touch or pull the lead wire with wet hands.
It will cause product breakdown or electric shock.
• If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard.
!
Disposal of your old appliance
1 When this crossed-out wheeled bin symbol is attached to a product it means the product
is covered by the European Directive 2002/96/EC.
2 All electrical and electronic products should be disposed of separately from the municipal
waste stream via designated collection facilities appointed by the government or the local
authorities.
3 The correct disposal of your old appliance will help prevent potential negative conse-
quences for the environment and human health.
4 For more detailed information about disposal of your old appliance, please contact your
city office, waste disposal service or the shop where you purchased the product.
According to IEC 60335-1
This appliance is not intended for use by person (including children) with reduced
physical, or mental capabilities, or lack of experience and knowledge, unless they
have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety. Children should be supervised to ensure that
they do not play with the appliance.
According to EN 60335-1
This appliance can be used by children aged from 8 years and above and person
with reduced physical, sensory or mental capabilities or lack of experience and
knowledge if they have been given supervision or instruction concerning use of
the appliance in a safe way and understand the hazards involved. Children shall
not play with the appliance. Cleaning and user maintenance shall not be made by
children without supervision.)
TABLE OF CONTENTS
5
TABLE OF CONTENTS
2 TIPS FOR SAVING
ENERGY
3 IMPORTANT SAFETY
INSTRUCTIONS
6 NAME OF EACH PART
7 COMPONENTS
8 INSTALLATION METHOD
8
Diagram of overall product configuration
13 How to wire the product (when EHP
product is connected)
14 How to wire the product (when GHP
product is connected)
15 Wiring
19 SETTING AND USING
METHOD
19 Glossary
20 Setting
22 Setting up detailed functions (EHP
products)
30 Setting detailed functions (GHP
products)
36 How to Use Power Indicator (EHP
products)
39 How to Use the Power Indicator (GHP
products)
43 Operating condition display
ENGLISH
6
NAME OF EACH PART
ENGLISH
NAME OF EACH PART
① Front cover
② LED display
Displays current status of power indicator
③ Menu button
Use for checking initial setting and electric power
④ LCD display
Displays setting information and power usage
⑤ SELECT button
Use for initial setting
⑥ Navigation button
Use for checking initial setting and electric power
⑦ Power supply
Supply power for power indicator
① Front cover
② LED display
③ Menu button
④ LCD display
⑤ SELECT button
② LED display
⑥ Navigation button
POWER
POWER
PQNUD1S40
WHM
ODU
CHECK
WHM
WHM
MENU
SELECT
ODU
CHECK
WHM
⑦ Power supply
COMPONENTS
7
ENGLISH
COMPONENTS
Power indicator Power supply
Front cover
Screws
155 mm
POWER
POWER
WHM
MENU
SELECT
PQNUD1S40
ODU
CHECK
WHM
270 mm
120 mm
WHM
ODU
CHECK
WHM
155 mm
8
INSTALLATION METHOD
ENGLISH
INSTALLATION METHOD
Diagram of overall product configuration
When interlocked to pulse type wattmeter
• When interlocked to EHP product
- Independent Operation of Power Indicator (interlocked to EHP products)
Power cable for 3 phase 4 wire
Power cable for single phase
Communication cable (2 wire shielded cable): Between outdoor unit and central controller
Communication cable (2 wire shielded cable): Between indoor unit and outdoor unit
Pulse signal wire
Refrigerant pipe
CAUTION
• Depending on the electric power, use the wattmeter for remote reading by sending the
pulse signal.
• Use the wattmeter with the pulse width of 50 ms ~ 400 ms.
• The wattmeter pulse must be able to sink at least 3 mA or more of current in the power
indicator.
• Use the wattmeter of 1 W/pulse, 2 W/pulse, 4 W/pulse, 6 W/pulse, 8 W/pulse, 10 W/pulse,
100 W/pulse and PT/CT (1 ~ 50 000).
• When setting the wattmeter, set it to Master Mode.
• Maximum of 8 wattmeters can be installed.
• The distance between power indicator and wattmeter should be shorter than 10 m in
normal circumstance.
• When electrical or mechanical noise is expected, more shorter wiring is needed.
• For watt-hour meter setting, inquire to the corresponding vendor.
h EHP (Electric Heat Pump): It is an electric air conditioner to drive the compressor by electric power.
!
Power In
single phase
220-240 V~, 50/60 Hz
Wattmeter
Pulse signal
(00) (01) (02) (03)
Power cable of indoor unit
POWER
WHM
MENU
SELECT
PQNUD1S40
CHECK
ODU
WHM
Pulse signal
Pulse signal
RS-485
(LGAP)
Wattmeter
Power In 3
phase 4 wire
380-415 V 3N~, 50/60 Hz
(70) ( 71) (72) (73)
INSTALLATION METHOD
9
ENGLISH
• Interlocked Operation with Central Controller (interlocked to EHP product)
Power cable for 3 phase 4 wire
Power cable for single phase
Communication cable (2 wire shielded cable): Between outdoor unit and central controller
Communication cable (2 wire shielded cable): Between indoor unit and outdoor unit
Pulse signal wire
Refrigerant pipe
CAUTION
• Depending on the electric power, use the wattmeter for remote reading by sending the
pulse signal.
• Use the wattmeter with the pulse width of 50 ms ~ 400 ms.
• The wattmeter pulse must be able to sink at least 3 mA or more of current in the power
indicator.
• Use the wattmeter of 1 W/pulse, 2 W/pulse, 4 W/pulse, 6 W/pulse, 8 W/pulse, 10 W/pulse,
100 W/pulse and PT/CT (1 ~ 50 000).
• When setting the wattmeter, set it to Slave Mode.
• Maximum of 8 wattmeters can be installed.
• The distance between power indicator and wattmeter should be shorter than 10 m in
normal circumstance.
• When electrical or mechanical noise is expected, more shorter wiring is needed.
• For watt-hour meter setting, inquire to the corresponding vendor.
!
Power In
single phase
220-240 V~,
50/60 Hz
Wattmeter
Pulse signal
POWER
(00) (01) (02) (03)
Power cable of indoor unit
(70) (71) (72) (73)
RS-485
(LGAP)
Wattmeter
Power In 3
phase 4 wire
380-415 V 3N~,
50/60 Hz
RS-485
(LGAP)
MENU
SELECT
ODU
WHM
CHECK
Pulse signal
Pulse signal
WHM
PQNUD1S40
10
INSTALLATION METHOD
ENGLISH
• When interlocked to GHP product
- Independent Operation of Power Indicator (interlocked to GHP product)
Power cable for 3 phase 4 wire
Power cable for single phase
Communication cable (2 wire shielded cable): Between outdoor unit and central controller
Communication cable (2 wire shielded cable): Between indoor unit and outdoor unit
Pulse signal wire
Refrigerant pipe
Gas pipe
Pulse signal wire(Gas)
CAUTION
• Use the wattmeter for remote reading to send pulse signal depending on wattage.
• Use the wattmeter with the pulse width of 50 ms ~ 400 ms.
•
The wattmeter pulse must be able to sink at least 3 mA or more of current in the power indicator.
• Use the wattmeter for 1 W/Pulse, 2 W/Pulse, 4 W/Pulse, 6 W/Pulse, 8 W/Pulse, 10 W/Pulse,
100 W/Pulse, PT / CT (1 ~ 50 000).
• Use the gas meter for remote reading to send pulse signal depending on gas consumption.
• Use the gas meter with the pulse width of 50 ms or more.
• Use the gas meter containing the max. gas pressure of 0.2 m3/h ~ 10 m3/h.
•
Gas meter pulse must be able to sink at least 3 mA of current or more in the power indicator.
• Use the gas meters for 1 ℓ/ Pulse, 2 ℓ/ Pulse, 4 ℓ/ Pulse, 6 ℓ/ Pulse, 8 ℓ/ Pulse, 10 ℓ/ Pulse,
100 ℓ/ Pulse, VT / Pr (1 ~ 50 000).
• Set to Master Mode when setting the wattmeter or gas meter.
• Wattmeter or gas meter can be installed up to 4.
• Connection cable for the power indicator and wattmeter (gas meter) must not exceed 10 m in
normal circumstance.
•
Reduce the length of connection cable if there is any electrical or mechanical noise on the site.
• For watt-hour meter and gas meter setting, inquire to the corresponding vendor.
h GHP (Gas engine Heat Pump): It is a gas air-conditioner to drive the compressor with LNG or LPG as
a heat source and the gas engine electric power.
!
(00) (01) (02) (03)
(70) (71) (72) (73)
RS-485
Pulse signal(Power)
POWER
WHM
PQNUD1S40
MENU
SELECT
ODU
CHECK
WHM
Pulse signal(Power)
Pulse signal(Gas)
Pulse signal(Gas)
(LGAP)
Wattmeter
Power In 3
phase 4 wire
380-415 V 3N~,
50/60 Hz
Gas meter
Gas
INSTALLATION METHOD
11
ENGLISH
- When linked with the GHP product, the central controller is linked only possible model of
ACS IV series or later.
Power cable for 3 phase 4 wire
Power cable for single phase
Communication cable (2 wire shielded cable): Between outdoor unit and central controller
Communication cable (2 wire shielded cable): Between indoor unit and outdoor unit
Pulse signal wire
Refrigerant pipe
Gas pipe
Pulse signal wire(Gas)
CAUTION
• Use the wattmeter for remote reading to send pulse signal depending on wattage.
• Use the wattmeter with the pulse width of
50 ms ~ 400 ms.
•
The wattmeter pulse must be able to sink at least 3 mA or more of current in the power indicator.
• Use the wattmeter for 1 W/Pulse, 2 W/Pulse, 4 W/Pulse, 6 W/Pulse, 8 W/Pulse, 10 W/Pulse,
100 W/Pulse, PT / CT (
1 ~ 50 000
).
• Use the gas meter for remote reading to send pulse signal depending on gas consumption.
• Use the gas meter with the pulse width of 50 ms or more.
• Use the gas meter containing the max. gas pressure of
0.2 m3/h ~ 10 m3/h.
•
Gas meter pulse must be able to sink at least 3 mA of current or more in the power indicator.
•
Use the gas meters for 1 ℓ/ Pulse, 2 ℓ/ Pulse, 4 ℓ/ Pulse, 6 ℓ/ Pulse, 8 ℓ/ Pulse, 10 ℓ/ Pulse,
100 ℓ/ Pulse, VT / Pr (1 ~ 50 000).
• Set to Slave Mode when setting the wattmeter or gas meter.
• Wattmeter or gas meter can be installed up to 4.
• Connection cable for the power indicator and wattmeter (gas meter) must not exceed 10 m in
normal circumstance.
•
Reduce the length of connection cable if there is any electrical or mechanical noise on the site.
• For watt-hour meter and gas meter setting, inquire to the corresponding vendor.
!
RS-485
Pulse signal(Power)
POWER
WHM
PQNUD1S40
ODU
(00) (01) (02) (03)
(70) (71) (72) (73)
MENU
SELECT
CHECK
WHM
Pulse signal(Power)
Pulse signal(Gas)
Pulse signal(Gas)
(LGAP)
RS-485
(LGAP)
Wattmeter
Power In 3
phase 4 wire
380-415 V 3N~,
50/60 Hz
Gas meter
Gas
12
INSTALLATION METHOD
ENGLISH
When interlocked to RS-485 type wattmeter (EHP products only)
Interlock function with RS-485 type wattmeter is available only for EHP products.
• Independent Operation of Power Indicator
• Interlocked operation with central controller
CAUTION
• Use the wattmeter (Interlock function with OMNISYSTEM only) that sends the electric energy through 485 communications.
• When setting the wattmeter, set to Master Mode for independent operation and Slave
Mode for interlocked operation.
• When using the 485 wattmeter, maximum of 1 unit can be installed.
• For 485 watt-hour meter setting, inquire to the corresponding vendor
!
POWER
WHM
PQNUD1S40
(00) (01) (02) (03)
RS-485(Only for the OMNISYSTEM)
MENU
SELECT
ODU
CHECK
WHM
RS-485(LGAP)
POWER
WHM
PQNUD1S40
RS-485(Only for the OMNISYSTEM)
MENU
SELECT
ODU
CHECK
WHM
Wattmeter
380-415 V 3N~, 50/60 Hz
Power cable for 3 phase 4 wire
Communication cable (2 wire shielded cable):
Between outdoor unit and central controller
Communication cable (2 wire shielded cable):
Between indoor unit and outdoor unit
Communication cable (2 wire shielded cable):
Between indoor unit and outdoor unit
Refrigerant pipe
Wattmeter
380-415 V 3N~, 50/60 Hz
Power In 3
phase 4 wire
Power In 3
phase 4 wire
RS-485
(00) (01) (02) (03)
(LGAP)
Power cable for 3 phase 4 wire
Communication cable (2 wire shielded cable):
Between outdoor unit and central controller
Communication cable (2 wire shielded cable):
Between indoor unit and outdoor unit
Communication cable (2 wire shielded cable):
Between indoor unit and outdoor unit
Refrigerant pipe
INSTALLATION METHOD
13
ENGLISH
How to wire the product (when EHP product is connected)
Wiring Power Supply
CAUTION
• Power must be turned on after the product is wired completely.
!
Connection of pulse type
wattmeter system
POWER
24 V~ power is supplied
for power supply device
220-240 V~ power cable
connection terminal
Grounding cable connection terminal
PQNUD1S40
WHM
SELECT
ODU
MENU
WHM
CHECK
Connect when using
remote reading function
Connect when using
485 type wattmeter
Connect to central control (outdoor unit)
485 communication line
LN
220-240 V~
24 V~
Fixing clamp
24 V~ power cable connection terminal
14
INSTALLATION METHOD
ENGLISH
How to wire the product (when GHP product is connected)
Wiring Power Supply
CAUTION
• Power supply must be applied after wiring the product is completed, if applicable.
!
Connected to pulse-type
wattmeter (1~4 ports)
Connected to pulse-type
gas meter (5~8 ports)
POWER
24 V~ power is supplied
from the power supply
220-240 V~ power cable
connection terminal
Grounding cable connection terminal
PQNUD1S40
WHM
MENU
SELECT
CHECK
ODU
WHM
Connect to central control (outdoor unit)
485 communication line
LN
220-240 V~
24 V~
Fixing clamp
24 V~ power cable connection terminal