LG PQNFB16A1 User Manual [en, de, es, fr, it]

ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH CHINESE
LG BNU-LW(Lonworks Gateway)
Installation Manual
LG
IMPORTANT
• Please retain this Installation Manual for future reference after reading it thoroughly.
2 Lonworks Gateway
BNU-LW (Lonworks Gateway)
TABLE OF CONTENTS
Safety Precautions.................................................................................................3
Overall system diagram.........................................................................................7
External wiring diagram ........................................................................................8
How to set the address for the central controller of the indoor unit
connected to BNU-LW (Lonworks Gateway).......................................................8
Communication line specification .......................................................................9
Name of each part................................................................................................10
Installation order..................................................................................................11
BNU-LW wiring order...........................................................................................12
Air conditioner/ventilation function table..........................................................13
Air conditioner indoor unit function ...................................................................13
Ventilation indoor unit function..........................................................................14
BNU-LW remote diagnosis function...................................................................15
Setting method..................................................................................................15
Configuration ....................................................................................................16
Setting the indoor unit address..........................................................................18
Setting the indoor unit address .........................................................................18
Interfacing with simple central controller..........................................................19
Appendix...............................................................................................................20
A/C Objects.......................................................................................................20
Air conditioner control/monitoring point ............................................................21
Ventilation control/monitoring point...................................................................22
Network variables .............................................................................................23
Safety Precautions
Installation Manual 3
ENGLISH
Do not operate or stop the unit by inserting or pulling out the power plug.
• It will cause electric shock or fire due to heat generation.
Ask for Product equipment at the service center or establishment certainly at the specialty store.
• It can cause an accident, electric shock, explosion or injury.
Use standard parts.
• Use of non standard parts can cause electric shock, explosion, injury, breakdown.
Operation
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
Be sure not to do.
Be sure to follow the instruction.
WARNING
Standard Parts
WARNING
CAUTION
BNU-LW
BNU-LW
Safety Precautions
4 Lonworks Gateway
If water enters the product, turn the power switch of the main body of appliance off.
• After taking the power-plug out from the socket, contact the service center.
Keep the product away from the places which can have moisture.
• Water may enter the unit and degrade the insulation. It may cause an electric shock.
BNU-LW
During usage
While re-installing the established product, notify the service center or establishment specialty
store.
• It can cause an accident, electric shock, explosion, injury.shock.
Do not use the power cord near Flammable gas or combustibles, such as gasoline, benzene, thinner,
etc.
• It may cause an explosion or fire
Do not disjoint randomly or repair and remodel the product.
• It may cause fire and electric shock
BNU-LW
BNU-LW
Do not change or extend the conductor at random.
• It can cause fire and electric shock.
Do not use concert with in the octopus-like legs way.
• It can cause fire and electric shock
Unplug the unit if strange sounds, smell, or smoke comes from it.
• It may cause fire and electric shock accident.
BNU-LW
BNU-LW
BNU-LW
Thinner
Wax
Safety Precautions
Installation Manual 5
ENGLISH
Do not put firearms near product.
• It can cause fire.
Do not put an electric heater or conductor near to the product.
• It can cause fire and electric shock.
Do not spill water inside product.
• It can cause electric shock and breakdown.
BNU
-LW
BNU-LW
BNU-LW
Do not place heavy goods on wire.
• It can cause fire and electric shock.
Hold the plug by the head of the power plug when taking it out.
• It may cause electric shock and damage.
Do not place heavy goods on product.
• It can cause product breakdown.
BNU-LW
BNU-LW
That increase in case of product was been flood certainly in the service center or establishment specialty store commit .
• I am responsible for fire and electric shock.
Protect the product from handling by a children.
• It can cause accident and product breakdown.
Do not apply shock to product.
• I am responsible for breakdown in case of shock to product.
BNU-LW
BNU-LW
BNU-LW
Safety Precautions
6 Lonworks Gateway
During usage
CAUTION
Clean by soft hands using a cleaning material like a soft cloth.
• It can result in fire and product transformation.
Do not place any live part on the surface having water.
• It can cause product breakdown.
Use recommended Adapter.
• Otherwise it can result in product breakdown
BNU-LW
Wax
Thinner
BNU-LW
BNU-LW
Avoid contact to the metallic goods such as necklace, coin, key, a watch which may touch the battery even for a short-time.
• It may cause product breakdown and injury.
Hold the plug by the head of the power plug when taking it out.
• It may cause electric shock and damage.
BNU-LW
Overall system diagram
Installation Manual 7
ENGLISH
Overall system diagram
* PNF-B16A1 (Lon Gateway) can be used in connection with the simple central
controller.
* Can be connected to 64 indoor units (Ventilation+Air conditioner)
Simple central
controller
485 communication
Ventilation A/C
External wiring diagram
8 Lonworks Gateway
When the address of the indoor unit of the air conditioner is duplicated with that of the ventilation unit, it will not operate normally.
Maximum of 64 units of the indoor unit (Air conditioner+Ventilation) can be connected to the BNU­LW.
It is recommended to connect 16 units of PI485 and maximum of d32 PI485 units to the BNU-LW.
Ventilation products cannot be interfaced with the simple central controller.
External wiring diagram
How to set the address for the central controller of the indoor unit connected to BNU-LW (Lonworks Gateway)
LON protocol BMS system
<Maximum number of connected indoor unit: 64 units>
Air conditioner
RS485
BNU-LW
RI485 Central controller address(0.0) (0.1) ............(0.F)
RI485
Central controller address(2.0)
Central controller address(2.4)
Central controller address(1.0)
(2.1) (2.2) (2.3)
(2.5) (2.6) (2.7)
(1.1)............(1.F)
External wiring diagram
Installation Manual 9
ENGLISH
1. RS-485 communication line specification: 0.75mm2or above 2C shield, product to product: 200M, total length: 1km
2. FT-10 communication line: Refer to the following table.
* Nod to node distance (max): 250m, maximum distance: 450m * AWG: American Wire Gauge
Cable Type Line thickness (AWG) Diameter
TIA 568A Category 5 cable 24 0.5mm Belden 88471 (PVC jacket) or 16 1.3mm
equivalent cable Belden 85102(Tefzel jacket) or 16 1.3mm
equal cable Level IV cable 22 0.65mm JY(st)Y 2x2x0.8 20.4 0.8mm
Communication line specification
Name of each part
10 Lonworks Gateway
Name of each part
1 2
3 4 5 6 7 8
BUS_A: 485 communication line A (+)
BUS_B: 485 communication line B (-)
F1, F2: Fire detection function (external device) contact point connection
LAN: LAN port necessary for web function
LON: TP/FT-10 communication line (Lonworks system communication line) non-polarity
PWR: Connection to DC 12V power adapter
12V: Connection when not using DC 12V power adapter
GND: Connection when not using GNS adapter
ALIVE/WINK: It flashes every 1 second when it is normal
It flashes 5 times when receiving WINK command from Lonworks system (Green)
SERVICE: It is turned off when it is normal and flashes when it is not connected to the
Lonworks system. It is turned on when the service switch is pressed.
SERVICE SWITCH: When you press the switch the Neuron ID is transmitted to the
Lonworks system, and the service LED is turned on.
BNU-LW (PNF-B16A1) product is a product certified of LON-MARK, an international standard. (Lon Mark Version 3.3)
1
8
2
3
4
5
6
7
LONWORKS GATEWAY
No. 6 and No. 7,8 are all for power supply. Therefore, only one of two combinations should be used. When DC 12V is used for the power, Connect No. 6 to the power (not necessary to use No. 7,8.) When DC 12V is NOT used for the power, Connect No. 7, 8 to the power (not necessary to use No. 6.)
Installation order
Installation Manual 11
ENGLISH
Installation order
1. Install the product according to the setting of the central controller address of the indoor unit and the DIP S/W of PI485. (Set the DIP switch No. 4 to ON.) (Refer to the PI485 installation manual for details.)
2. Connect BUS_A and BUS_B (485 communication line) while paying attention to the connecting polarity. (Refer to the next page.)
3. LON (TP/FT-10 lineLonworks Gateway communication line connection) TP/FT-10 communication line does not have polarity. Connect the 2 communication lines to BMS.
4. PWR (Power supply) You can select either one of the two for the power supply.
Use DC 12V power adapter Connect to No. 6 in name of each part.
When separate DC12 can be supplied Connect 12V and GND to No. 7 and 8 terminals.
5. When you press the service switch after connecting to the Lonworks system, the service LED is turned on and the neuron ID is automatically transmitted to the Lonworks system.
6. Check whether the service LED is in normal condition (OFF condition) within 10 minutes. If the service LED is in normal condition, the installation has been done normally.
7. When using the fire detection port, connect the two terminals of the fire diction sensor to F1 and F2. (Fire detection sensor must be used for DC output of 12V or below.)
8. After the installation, connect the LAN cable between the PCs to use the web server so that you can check whether the LG product has been installed normally. – Refer to the remote diagnosis function part (page 16) for details.
When connecting the signal line to the terminal of Lonworks Gateway, always use a manual driver. (Careful attention is required not to damage the terminal block and PCB.)
BNU-LW wiring order
12 Lonworks Gateway
BNU-LW wiring order
[Wiring sequence]
1. Connect 485 communication line
- Pay attention to BUS A and BUS B polarity (Refer to the G/W manual for DIP S/W information for 485 G/W.)
2. Connect the Lonworks communication line (TP/FT-10)
- No polarity.
3. Power supply (Select one from No. 1 or 2)
Use DC 12V adapter
- Connect to No. 6 jack from name of each part.
Supply DC 12V to installation site
- Connect 12V and GND to No. 7 and 8 terminals.
4. Interface with simple central controller
- Set the DIP S/W No. 2 of the simple central controller to ON and configure the setting according to the rotary S/W address. (Refer to setting part when connection to simple central controller (page 20) for details.)
5. Connect fire detection sensor
- When the signal of DC 12 or below is transmitted in case of a fire, the indoor unit and ventilation product that is connected to BNU-LW will all be turned off.
LG does NOT supply this section ( Connection and Installation)
LonWorks Adaptor
TP/FT-10
F1 F2 LAN LON PWR 12V GND
Fire detection sensor (Use DC 12V or below)
BMS Control (PC)
A B
+10V
GND
PI485 terminal
Central
controller
VOC
GND
C
D
PI485
10V
GND
BUS_A
BUS_B
LG supply
Power
Air conditioner/ventilation function table
Installation Manual 13
ENGLISH
Air conditioner/ventilation function table
Air conditioner indoor unit function
Indoor unit individual control O O Operating mode change O O Fan level change O O Temperature adjustment function O O Lock function O O Automatic fan direction O O Indoor unit temperature check X O Error check X O Simultaneous operation/stop O X
Function
BMS
BNU-LW
Air conditioner
BMS
BNU-LW
Air conditioner
Classification Control Monitoring
Binding (connection) function: Binding function refers to the case when the output of a unit has been
bound to the input of another unit and the process of input change from the output change. The binding function is possible with Lon unit of other manufacturer.
Ex) When the ON/OFF output of the indoor unit No. 1 is bound to ON/OFF input of indoor unit of No. 2
and when the indoor unit No. 1 is turned on, the indoor unit No. 2 also gets turned on from receiving the signal.
Air conditioner/ventilation function table
14 Lonworks Gateway
Ventilation indoor unit function
Indoor unit individual control O O Operating mode change O O Fan level change O O User operation mode
OO
(Quick ventilation, power save, heating) Lock function O O Error check X O Simultaneous operation/stop O X
Function
BMS
BNU-LW
Ventilation
BMS
BNU-LW
Ventilation
Classification Control Monitoring
Binding (connection) function: Binding function refers to the case when the output of a unit has been
bound to the input of another unit and the process of input change from the output change. The binding function is possible with Lon unit of other manufacturer.
Ex) When the ON/OFF output of the indoor unit No. 1 is bound to ON/OFF input of indoor unit of No. 2
and when the indoor unit No. 1 is turned on, the indoor unit No. 2 also gets turned on from receiving the signal.
BNU-LW remote diagnosis function
Installation Manual 15
ENGLISH
1. Connect the LAN line between the PC and the LAN port of the BNU-LW.
2. Set the network IP of the used PC to
192.168.1.xxx (except 101).
3. Enter 192.168.1.101 in the Internet Explorer.
4. The above picture is shown when connected normally.
Initial ID: lonwork
Initial password: lonwork
Enter the total number of connected
indoor units in the Total Unit block.
BNU-LW remote diagnosis function
Setting method
LAN(cross cable)
BNU-LW remote diagnosis function
16 Lonworks Gateway
Configuration
After entering the ID and password, the air condition and ventilation products currently connected are displays as shown in the picture.
A part displays the number of air condition and ventilation products are currently connected.
• When you would like to control a product Select the product – Set the address – Command ON/OFF – Select the mode – Click on check to control the product.
When you would like to check the current status Click on Reload and you will be able to check the current indoor unit status in the “B” part.
When you would like to change the IP, click on [Set up Network place] to change the IP.
"A"
"B"
BNU-LW remote diagnosis function
Installation Manual 17
ENGLISH
A
B
C
D
A: It displays the current IP, Gateway,
Subnet mask information. When you would like to use the
SVCnet Server, it displays the SVCnet Server information.
It displays the MAC address information.
It displays the current version information of the BNU-LW.
B: When you would like to change the IP
and Gateway, Subnet mask information, press the Edit button next to the information you would like to change.
C: This is the space to enter the SVCnet
Server information to connect. SVCnet Server is the service that monitors the air conditioner status connected to BNU-LW through the LAN in the future by the LG Electronics Service Center to provide early notification in case of a problem.
D: In order to prevent the network or
arbitrary change, a security function has been applied for you to enter the initial login password to change the network setting.
Setting the indoor unit address
18 Lonworks Gateway
Setting the indoor unit address
Setting the indoor unit address
When using the wired remote controller
When using the wireless remote controller
Timer Cancel
Program Week
Hour Min
Holiday
Set/Clr
RESET
ZONE
1234
Operation unit
Humidify
JET
AUTO
AUTO SWING OPERATION
FAN SPEED
Program set
SUB FUNCTION
SET TEMP
Room Temp
HI MED LO
Heater Defrost Filter
Preheat
Out door
Time
Timer
On Set no. Time
Off
01 03 05 07 09 11 13 15 17 19 21 23
Plasma
ON OFF
SET
CANCEL
PLASMA
Group No. Indoor unit No.
Temperature adjustment
1. Press the week day and reservation set/cancel buttons simultaneously for 3 seconds.
2. By using the temperature adjustment button, set the indoor unit address. Setting range: 00~FF
3. When you press the week day and reservation set/cancel buttons simultaneously for 3 seconds, the address setting is completed.
Address setting mode
1. Press the top left button for more than 3 seconds. While the top left button pressed, press the Reset button .
The wireless remote controllers have different shapes according to the model.
2. By using the temperature adjustment button, set the indoor unit address. Setting range: 00~FF
3. After setting the address, press the ON/OFF button toward the indoor unit 1 time.
4. The indoor unit will display the set address to complete the address setting. (The address display time and method can differ by the indoor unit type.)
5. Reset the remote controller to use the general operation mode.
Address check mode
1. With the top right button pressed, press the Reset button.(Press the left button for more than 3 seconds.)
2. Press the ON/OFF button toward the indoor unit 1 time, and the indoor unit will display the set address in the display window. (The address display time and method can differ by the indoor unit type.)
3. Reset the remote controller to use the general operation mode.
The above function might not work for some remote controllers depending on the manufactured
date of the wired/wireless remote controller. It is not relevant for the consumer use and you can set the address with a remote controller that has the address setting functionality during the installation.
Group No.
Indoor unit No.
Temperature
adjustment
Interfacing with simple central controller
Installation Manual 19
ENGLISH
Interfacing with simple central controller
How to interface with simple central controller
When interfacing with simple central controller, turn the DIP S/W No. 2 of the simple central controller ON.
Set the rotary S/W to the group address of the indoor unit you would like to control.
How to set PI-485
How to set PI-485
BNU-LW uses LGAP communication protocol. You can set the DIP S/W No. 1 and No. 4 of PI-485 ON.
Appendix
20 Lonworks Gateway
Appendix
A/C Objects
The appendix carries information necessary for interfacing with BMS and not necessary for actual installation.
Standard Fundtion Block
SCC(8500)FB
Indoor/
Ventilator unit
Network Varlables
SNVT
_
switch nviOnOff SNVT_hvac_mode nviHeatCool SNVT_switch nviFanSpeedcmd SNVT_switch nviLock SNVT
_
switch nviSwing SNVT_switch nviSetPoint SNVT_switch nviUser SNVT_switch nviSpaceTemp
SNVT
_
switch nvoOnOff SNVT_hvac_mode nvoHeatCool SNVT_switch nvoFanSpeed SNVT_switch nvoLock SNVT
_
switch nvoSwing SNVT_temp_P nvoSetPoint SNVT_hvac_status nvoUnitStatus SNVT_count nvoUser
SWITCH(3200)FB
Total
Control
SNVT_switch nviTotalOnOff_Indoor
SNVT_switch nviTotalOnOff_Vent
SNVT_switch nvoSwitch
You can enable control and monitoring as shown in the figure for one air conditioner/ventilation unit.
The network variable can differ from the actual.
(Refer to the XIF file for correct network variable.)
Control Monitoring
On/Off command Mode selection command Fan level selection command Indoor unit lock command Fan direction command Temperature setting command
Ventilation additional function command (Only applies for ventilation product)
Air conditioner total On/Off control Ventilation total On/Off control
On/Off status monitoring Mode status monitoring Fan level status monitoring Lock status monitoring Fan direction status monitoring Temperature setting status
monitoring Current temperature monitoring
Error display Ventilation additional function
status monitoring (Only applies for ventilation product)
Appendix
Installation Manual 21
ENGLISH
Air conditioner control/monitoring point
1 ON/OFF (setting) SNVT_switch nviOnOff_nn input Stop
Operation
2 ON/OFF (status) SNVT_switch nvoOnOff_nn output Stop
Operation
3 Lock (setting) SNVT_switch nviLock_nn input Cancel Setting
4 Lock (status) SNVT_switch nvoLock_nn output Cancel Setting
5 Operation Mode (setting) SNVT_hvac_modenviHeatCool_nn input Auto Heating Cooling Fan Dry
6 Operation Mode (status) SNVT_hvac_mode nviHeatCool_nn output Auto Heating Cooling Fan Dry
7 Swing(setting) SNVT_switch nviSwing_nn input Cancel Setting
8 Swing(status) SNVT_switch nvoSwing_nn output Cancel Setting
9 Fan speed(setting) SNVT_switch nviFanSpeedCmd_nn input Low Med High Auto
Super Low
10 Fan speed(status) SNVT_switch nvoFanSpeed_nn output Low Med High Auto
Super Low
11 Set Room Temperature SNVT_temp_p nviSetPointCmd_nn input °C
12 Set Room Temperature SNVT_temp_p nvoSetPoint_nn output °C
13 Room Temperature SNVT_temp_p nvoSpaceTemp_nn output °C
14 Error Code SNVT_hvac_status nvoUnitStatus_nn output no errorRefer to the LG Air Conditioner Error Code.
Point
No.
Name
Object
Type
Unit
code 0 code 1 code 2 code 3 code 4 code 5 code 9 code
14
Object Name
(nn: Air conditioner and ventilation
group/indoor unit address)
Appendix
22 Lonworks Gateway
Ventilation control/monitoring point
1 ON/OFF (setting) SNVT_switch nviOnOff_nn input Stop Operation
2 ON/OFF (status) SNVT_switch nvoOnOff_nn output Stop Operation
3 Lock (setting) SNVT_switch nviLock_nn input Cancel Setting
4 Lock (status) SNVT_switch nvoLock_nn output Cancel Setting
5 Operation Mode (setting) SNVT_hvac_modenviHeatCool_nn input Auto
Heat exchange
Normal
6 Operation Mode (status) SNVT_hvac_mode nviHeatCool_nn output Auto
Heat exchange
Normal
7 Fan speed(setting) SNVT_switch nviFanSpeedCmd_nn input Low High Very high
8 Fan speed(status) SNVT_switch nvoFanSpeed_nn output Low High Very high
9 Error Code SNVT_hvac_status nvoUnitStatus_nn output Refer to the LG Air Conditioner Error Code.
10 User Mode(setting) SNVT_count nviUser_nn output Quick
Power save
heat
11 User Mode(status) SNVT_count nvoUser_nn output Quick
Power save
heat
Point
No.
Name
Object
Type
Unit
code 0 code 1 code 2 code 3 code 5 code 9
Object Name
(nn: Air conditioner and ventilation
group/indoor unit address)
Appendix
Installation Manual 23
ENGLISH
Network variables
1) Individual operation/stop input/output (Air conditioner/ventilation)
Valid Range
SNVT_switch
( Index : 95 )
NV Filed Operation
Function Operation/stop input
Input Using NV Network input variable : SNVT_switch nviOnOff_n
Operation It controls the operation/stop of each product (air conditioner/ventilation)
Function Operation/stop status display
Output Using NV Network output variable : SNVT_switch nvoOnOff_n
Operation It monitors the operating status of each product (air conditioner/ventilation)
2) Operating mode input/output (Air conditioner/ventilation)
Function Operating mode command input
Input Using NV Network input variable : SNVT_hvac_mode nviHeatCool_n
Operation It controls the operating mode of each air conditioner/ventilation product.
Function Operating mode status display
Output Using NV etwork output variable : SNVT_hvac_mode nvoHeatCool_n
Operation It monitors the operating status of each air conditioner/ventilation product.
value not used (set in 0% usually)
0 = Air conditioner/ventilation product OFF
state 1 = Air conditioner/ventilation product ON
Default Value
HVAC_AUTO : 0 = AUTO mode(air conditional), Auto (ventilation)
HVAC_HEAT : 1 = Heat mode(air conditional), heat exchange(ventilation)
HVAC_COOL: 3 = Cool mode (cool)
HVAC_FAN_ONLY: 9 = Fan mode (fan) normal ventilation
HVAC_DEHUMID:14=Dry Mode (dehumidication)
Default Value
Valid Range
SNVT_hvac_mode
( Index : 108 )
NV Operation
Appendix
24 Lonworks Gateway
1: Air conditioner, ventilation low fan
2: Air condition med fan, ventilation high fan
value 3: Air condition high fan, ventilation very high fan
4: Air condition, ventilation auto fan
5. Air conditioner super low fan
state 0: Product not applied, 1: Product applied
Default Value
3) Fan level command input/output (Air conditioner/ventilation)
Valid Range
SNVT_switch
( Index : 95 )
NV Filed Operation
Function Fan level command input
Input Using NV Network input variable : SNVT_switc nviFanSpeedCmd_n
Operation It controls the fan level of each indoor unit.
Function Fan level status display
Output Using NV Network output variable : SNVT_switch nvoFanSpeed_n
Operation It monitors the fan level of each product (air conditioner/ventilation)
value not used (set in 0% usually)
0 = Air conditioner/ventilation product lock OFF
state 1 = Air conditioner/ventilation product lock ON
Default Value
4) Lock input/output (Air conditioner/ventilation)
Valid Range
SNVT_switch
( Index : 95 )
NV Filed Operation
Function Lock setting command input
Input Using NV Network input variable : SNVT_switch nviLock_n
Operation It controls the lock status of each product (air conditioner/ventilation)
Function Lock status display
Output Using NV Network output variable : SNVT_switch nvoLock_n
Operation It monitors the lock status of each product (air conditioner/ventilation)
Appendix
Installation Manual 25
ENGLISH
value not used (set in 0% usually)
0 = Fan direction fixed for air conditioner product
state 1 = Fan direction auto for air conditioner product
Default Value
5) Fan direction auto input/output (Only applies to air conditioner)
Valid Range
SNVT_switch
( Index : 95 )
NV Filed Operation
Function Fan direction auto command input
Input Using NV Network input variable : SNVT_switch nviSwing_n
Operation It controls the fan direction of each product (air conditioner/ventilation)
Function Fan direction auto status display
Output Using NV Network output variable : SNVT_switch nvoSwing_n
Operation It monitors the fan direction of each product (air conditioner/ventilation)
6) Temperature setting input/output (Only applies to air conditioner)
Function Set temperature range input
Input Using NV Network input variable : SNVT_switch nviSetPoint_n
Operation It controls the temperature setting of each product (air conditioner/ventilation)
Function Set temperature range status display
Output Using NV Network output variable : SNVT_switch nvoSetPoint_n
Operation It monitors the set temperature of each product (air conditioner/ventilation)
At Cool mode : 18 ~ 30°C
At Heat mode : 18 ~ 30°C
At Dry mode and Fan mode : Not available
Default Value
Valid Range
SNVT_switch
( Index : 95 )
NV Operation
Appendix
26 Lonworks Gateway
7) Indoor temperature status display (Only applies to air conditioner)
Function Indoor temperature status display
Output Using NV Network output variable : SNVT_switch nvoSpaceTemp_n
Operation It monitors the indoor temperature.
8) Error output (Air conditioner/ventilation)
Function Error status display
Output Using NV Network input variable : SNVT_hvac_Status nvoUnitStatus_n
Operation It monitors the error status of each product (air conditioner/ventilation)
At Cool mode : 10 ~ 40°C
At Heat mode : 10 ~ 40°C
At Dry, Fan mode : Not available
Default Value
Valid Range
SNVT_switch
( Index : 95 )
NV Operation
Mode Currently operating mode display
Heat_output_primary Not used
Heat_output_Secondary Not used
Cool_output Not used
Cool_output Not used
Econ_output Not used
fan_output Not used
In_alarm Error code display
Valid Range
SNVT_switch
( Index : 112 )
NV Filed Operation
* Refer to the Error Code table of the product manual for the error code.
Appendix
Installation Manual 27
ENGLISH
10) Total operation/stop air conditioner indoor unit
Function Total stop command input
Input Using NV Network input variable : SNVT_switch nviTotalONOFF_indoor
Operation It turns ON or OFF all the indoor units.
11) Total operation/stop ventilation indoor unit
Function Total stop command input
Input Using NV Network input variable : SNVT_switch nviTotalONOFF_indoor
Operation It turns ON or OFF all the ventilation units.
0 = Not used
value
1 = Quick mode
2 = Power save mode
3 = Heat
9) Ventilation function command (Only applies to ventilation product)
Valid Range
SNVT_count
( Index : 8 )
NV Filed Operation
Function Ventilation user operating mode input
Input Using NV Network input variable : SNVT_count nviUser_n
Operation It controls the product function of each ventilation product.
Function Ventilation user operating mode status
Output Using NV Network output variable : SNVT_count nvoUser_n
Operation It monitors the function status of each ventilation product.
value not used
state
1 = All ON indoor/Vent unit
0 = All OFF indoor/Vent unit
Default Value
Valid Range
SNVT_switch
( Index : 95 )
NV Filed Operation
Memo
28 Lonworks Gateway
ITALIANO
LG BNU-LW(Lonworks Gateway)
LG
Importante
• Leggere per intero questo manuale d'intallazione prima di installare il prodotto.
• Dopo aver letto interamente il manuale, conservarlo per riferimento futuro
Manuale d'installazione
2 Lonworks Gateway
BNU-LW (Lonworks Gateway).
SOMMARIO
Precauzioni per la sicurezza .................................................................................3
Schema generale del sistema...............................................................................7
Schema del cablaggio esterno .............................................................................8
Impostazione dell’indirizzo dell’unità di controllo centrale dell’unità interna
collegata al BNU-LW (Lonworks Gateway).........................................................8
Specifiche linea di comunicazione......................................................................9
Identificazione delle parti ....................................................................................10
Sequenza di installazione....................................................................................11
Ordine di cablaggio BNU-LW ..............................................................................12
Tabella delle funzioni condizionatore/ventilazione...........................................13
Funzionamento dell’unità interna del condizionatore intern .............................13
Funzionamento unità interna di ventilazione ....................................................14
Funzionamento diagnosi remota BNU-LW ........................................................15
Metodo di impostazione....................................................................................15
Configurazione..................................................................................................16
Impostazione dell’indirizzo dell’unità interna....................................................18
Impostazione dell’indirizzo dell’unità intern.......................................................18
Interfacciamento con l’unità di controllo centrale semplice............................19
Appendice.............................................................................................................20
Oggetti A/C .......................................................................................................20
Punto di monitoraggio/controllo condizionatore................................................21
Punto di monitoraggio/controllo ventilazione ....................................................22
Punto di monitoraggio/controllo ventilazione ....................................................23
Loading...
+ 139 hidden pages