LG PLNWKB000 INSTALLATION MANUAL

INSTALLATION/OWNER'S MANUAL
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
LonWorks (ACP Lonworks) PLNWKB000, PLNWKB100
P/NO : MFL68130102
www.lg.com
EXPLANATORY NOTES
i
EXPLANATORY NOTES
Copyrights
The contents of this ACP Lonworks User Guide are protected by international copyright laws, and the Computer Program Protection Act. The contents of the User Guide and the programs mentioned herein may only be used under license from LG Electronics in strict adherence to the user agreement.
You may not reproduce or distribute, by any means, copies of this User Guide, or any part of it, without prior approval from LG Electronics.
Copyright © 2014 LG Electronics. All rights reserved.
Registered Trademarks
ACP Lonworks is a registered trademark of LG Electronics. All other products and company names are trademarks of their respective owners and are used for illustrative purposes only.
ENGLISH
TIPS FOR SAVING ENERGY
ii
TIPS FOR SAVING ENERGY
ENGLISH
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air
conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidif ying functions.
Notes
Lonworks Gateway (Following referred as ACP Lonworks)
ACP Lonworks-Free Volt (PLNWKB000)
y
ACP Lonworks 24 V~ (PLNWKB100)
y
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
IMPORTANT SAFETY INSTRUCTIONS
iii
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored.
CAUTION
It can result in minor injury or product damage when the directions are ignored.
WARNING
yInstallation or repairs made by unqualified persons can result in hazards to you and others.
yInstallation MUST conform with local building codes or, in the absence of local codes, with the
Nation Electrical Code NFPA 70/ANSI C1-1003 or current edition and Canadian Electrical Code Part1 CSA C.22.1.
yThe information contained in the manual is intended for use by a qualified ser vice technician
familiar with safety procedures and equipped with the proper tools and test instruments.
yFailure to carefully read and follow all instructions in this manual can result in equipment
malfunction, property damage, personal injury and/or death.
ENGLISH
Installation
yAny question about the product installation should be asked to the ser vice center or the
professional installation agency.
- It may cause fire, electric shock, explosion or injury.
yConsult the service center or the professional installation agency about reinstalling the installed
product.
- It may cause fire, electric shock, explosion or injury.
yPlease use the standardized parts.
- It may cause fire, electric shock, explosion, injury, or failure.
yDo not keep or use combustible gas or inflammable material near the product.
- IT may cause fire or electric shock.
yDo not disassemble, repair or modify the product at random.
- It may cause failure of the product.
IMPORTANT SAFETY INSTRUCTIONS
iv
ENGLISH
yDo not install where raindrop can fall.
- It may cause failure of the product.
yDo not install the product at wet place.
- It may cause failure of the product.
yProvided product and adaptor shall only be installed and used inside a building.
- It may cause fire or failure of the product. *Do not install or use outside.
yInstall stably in a place that can endure the weight of the ACP Lonworks.
- If the installation place is not strong enough, the ACP Lonworks may fall and damaged.
yMake sure to enquire to the specialty store of the product purchase or service center for electric
works.
- It may cause fire or electric shock.
yDo not damage the power cord or bend it by force.
- It may cause fire or electric shock
yYou need to use a safely insulated power supply which follows IEC61558-2- 6 and NEC Class2
- If you do not follow, It may cause fire, electric shock, explosion or injury.
yDo not connetion 220 V power to 24 V products
- If you do not follow, It may cause fire, electric shock, explosion or injury.
yDo not connect power cord to the control signal connector.
- It may cause fire or explosion.
Operation
yDo not change or extend the power cord with your own discretion.
- It may cause fire or electric shock
yDo not place any heating device near the product.
- It may cause fire
yDo not use any heating device near the power cord.
- It may cause fire or electric shock.
yDo not let water flow into the product
- It may cause electric shock or failure.
yDo not put heavy weight on the power cord.
- It may cause fire or electric shock.
yDo not put heavy weight on the product.
- It may cause the failure of the product.
yIf the product is flooded, consult the service center or the professional installation agency.
- It may cause fire or electric shock.
IMPORTANT SAFETY INSTRUCTIONS
yLet the children or the old and the weak be controlled by the guardian to use.
- It may cause accident or failure.
yDo not give any shock to the product.
- Any shock to the product may cause failure.
yGrab the head of the plug of the power cord to pull when disconnecting the plug, and do not click
the plug with wet hands.
- It may cause fire or to deform the product.
yDo not use the product in certain environments as follows.
- If the product is used in a place with oil, steam, or sulfuric acid gas, performance may be de graded or product may be damaged.
yDo not press the switch or button with sharp objects.
- It may cause electric shock or failure of the product.
yPlease check the operation temperature.
- If the product is used in an environment with the temperature exceeding the operation boundary, it may cause a severe damage. Please check the usage temperature boundary in the manual. If there is no specified tempera­ture, please use the product within the boundary of 0 ~40 °C.
yDo not put a container, etc. with water on the product.
- It may cause fire or electric shock.
yDo not click the switch with wet hand.
- It may cause electric shock or failure of the product.
yPlease read installation and user manual for connection with PC or peripheral devices.
- It may cause fire or failure of the product.
yIf a warning window appears on PC, product stops, or it does not work, immediately stop the
usage.
- It may cause fire or failure of the product.
yWhen doing service work or cleaning, please shut off the power to the equipment always.
- It causes the deformation of the product or fire.
-
v
ENGLISH
CAUTION
Operation
yDo not use strong detergent such as solvent, but a soft cloth.
- It may cause fire or to deform the product.
yPlease check the rated capacity of the power.
- It may cause fire or failure of the product.
vi
ENGLISH
MEMO
TABLE OF CONTENTS
vii
TABLE OF CONTENTS
ACP LONWORKS
1
FUNCTIONS AND SPECIFICATION
1 ACP Lonworks Functions
3 ACP Lonworks Components
4 Names of each part of ACP
Lonworks
6 ACP Lonworks Hardware
Specification
INSTALLING ACP
7
LONWORKS
7 Installing ACP Lonworks
NOTES
45
45 Troubleshooting
49 Guide to Open Source Software
50 Function Block
60 Control/Monitoring Point list
70 Network Variables
ENGLISH
9 Check points during the ACP
Lonworks installation
10 Setting the indoor unit address
12 Setting the PI485 and connecting
the cable
14 Installing ACP Lonworks and
connecting cables
20 Connecting LON communication
cable(TP/FT-10) of ACP Lonworks.
21 Setting the ACP Lonworks network
address
41 Accessing ACP Lonworks
viii
ENGLISH
MEMO
ACP LONWORKS FUNCTIONS AND SPECIFICATION
1
ACP LONWORKS FUNCTIONS AND SPECIFICATION
ACP Lonworks(ACP Lonworks Gateway) is the central controller that can manage up to 64 equipments in one space individually or as combined. (48 equipments on PLNWKB100 version 2.2.0 or later)
• In case of air conditioner indoor unit, Up to 64 indoor units (up to 48 indoor units on PLNWKB100 version 2.2.0 or later)
• In case of AHU unit, up to 16 units
* It is required a separate ACP Lonworks for each other product type(air conditioner, AHU). ACP
Lonworks can’t to connect air conditioner indoor unit, AHU unit at the same time.
ACP Lonworks Functions
Major functions of the ACP Lonworks are as follows.
Environment setting function using the ACP Lonworks external buttons
ACP Lonworks can use the external buttons installed outside of the ACP Lonworks to set the following functions.
• Set Network environment (IP address, Net mask, Gateway)
• Set ACP ID when demand linkage
• SW upgrade function
• Data backup function
• Data recovery function
• RS-485 communication logging function
• ACP IV-screen display language setup
• Check the network connection function
• Set the module type
ENGLISH
PLNWKB000
PLNWKB000
LON SVC
ACP LONWORKS FUNCTIONS AND SPECIFICATION
2
Embedded web server function
Without an installation of a separate PC program, when IP address of ACP Lonworks is input in the
ENGLISH
address window using Internet Explorer, the central control program in ACP Lonworks web server is automatically run, and the functions of various contents can be used.
Internet
Internet Explorer
• Controlling of Up to 64 indoor units (up to 48 indoor units on PLNWKB100 version 2.2.0 or later)
• Monitoring of error and operation status
• Controlling the peak power / demand power
• System setting function
PLNWKB000
Devices that can interface with ACP Lonworks
Device ACP Lonworks
AC Ez o
Simple Central Controller o
AC Smar t IV o
AC Manager IV o
Air Conditioner o
ERV o
AWHP o
Remote Shutdown o
Demand Controller o
AHU o
LON SVC
ACP LONWORKS FUNCTIONS AND SPECIFICATION
P/NO : MFL67206331
www.lg.com
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
QUICK GUIDE
AIR CONDITIONER
LonWorks (ACP Lonworks) PLNWKB000, PLNWKB100
ACP Lonworks Components
Inside the packaged box of the ACP Lonworks, there are the components as in the following drawing. Open the packaged box of the ACP Lonworks, and check if all of the corresponding components are included.
PLNWKB000
LON SVC
3
ENGLISH
ACP Lonworks
(ACP Lonworks Gateway)
Power Supply Adaptor Input: 100 -240 V~
50/60 Hz, 1.2 A
Output: DC 12 V
3.33 A, 40 W MA X
Power Cord 250 V~, 3 A
Quick Guide
ACP Lonworks
User’s Guide
Notes
May be different from the image that has been shown and items sold separately parts.
y
Power Supply Adaptor and Power Cord are not included in PLNWKB100 (24 V~ power use)
y
ACP LONWORKS FUNCTIONS AND SPECIFICATION
4
Names of each part of ACP Lonworks
ENGLISH
ACP Lonworks is composed as follows.
PLNWKB000
⑪ ⑫
Notes
and ④ may be different for each model.
N/A
PLNWKB000
ACP LONWORKS FUNCTIONS AND SPECIFICATION
Number Item Description
Adaptor connection jack
Basic external input/output
RS-485 communication
button(SERVICE SWITCH)
Cover Front cover of the ACP Lonworks
RS-232 console port Reserved communication port
Jack for DC 12 V to connect to the power supply adaptor (not supported by PLNWKB100)
Power port
Buttons and LCD
signal connectors
port
RS-485, LON communication ports and BMS connection
Mini USB port USB to Serial port for software debugging
USB port For software update and data backup
Power switch Switch to turn on or off the power of the ACP Lonworks
Ethernet port Ethernet port to connect to internet and AC Manager
SD card slot For RS-485 communication data backup.
24 V~ port for power connection (not supported by PLNWKB000)
Buttons and LCD to set network environment and to display other information
Connection por ts to connect to external input/output signals (DI:2, DO:2)
RS-485 communication ports to connect to air conditioner and ventilation equipment (4EA)
RS-485 communication ports(2E A) and LON comunication port(1EA)
BMS connection button(SERVICE SWITCH)
5
ENGLISH
Caution
If four times the power connector for the connection, as shown by using the right connection, but please note that an electric shock.
Use the designated parts must be connected to a power source.
Connector manufacturers: PHOENIX CONTACT
y
PartNo: MVSTBR 2,5 / 2-ST-5, 08 2P 5.00 mm
Its contents can only be applied to PLNWKB100 model.
ACP LONWORKS FUNCTIONS AND SPECIFICATION
6
ACP Lonworks Hardware Specification
ENGLISH
ACP Lonworks hardware specification is as follows.
Category Description
Boundary of usage temperature 0 °C ~ 40 °C
Rated Voltage DC 12 V(PLNWKB000), 24 V~(PLNWKB100)
Rated Current Max 2.3 A
CPU
RAM 128MB DDR2 SDRAM * 2EA
ROM 4GB i-NAND Flash
Communication ports
External input/output ports DI, DO
LED
LCD
i.MX515 – 32Bit 800 MHz speed (Option:MPC5668G, 116 MHz)
yEthernet 10 / 100 BASE-T
yUSB: USB Host (SW upgrade, data backup)
mini USB Device (Debug)
yRS-485 communication ports 6EA
yLon communication port 1EA
ySD card slot (RS- 485 communication logging)
yRS-232 Console Port (HMI)
27EA (RS communication status, Ethernet communication status, power status, operation status)
20 ×4 Character-LCD (network environment setting and information display)
INSTALLING ACP LONWORKS
7
INSTALLING ACP LONWORKS
Installing ACP Lonworks
This chapter describes how to install the ACP Lonworks to use.
In order to use the ACP Lonworks, the installation should be performed by the following order.
STEP 1. Check the cautions during the ACP Lonworks installation
Before installing the ACP Lonworks, check the cautions.
STEP 2. Study the cable connections diagram of the entire system
Study the cable connection diagram of the site where the ACP Lonworks is installed.
STEP 3. Set the indoor unit address
Set the address of the ACP Lonworks not to be overlapped with the connecting indoor unit.
STEP 4. Set PI485 and connect cables
Set DIP switch of PI485 correctly, and connect RS- 485 communication cable.
STEP 5. Install ACP Lonworks and connect cables
Install the ACP Lonworks, and set network and other settings.
STEP 6. Set ACP Lonworks network address
Set the network address to be able to access the ACP Lonworks through internet.
ENGLISH
STEP 7. Set ACP Lonworks functions
Set language, etc.
STEP 8. Set ACP Lonworks module type
Set connected product type.
STEP 9. Set Web GUI access environment
Set the access environment in Web GUI, which is the operation program of the ACP Lonworks.
STEP 10. Input indoor unit and ventilator information
Set the access environment in Web GUI, which is the operation program of the ACP Lonworks.
STEP 11. Verify and check ACP Lonworks installation
Verify and check whether the ACP Lonworks is properly installed.
INSTALLING ACP LONWORKS
8
ENGLISH
Caution
Installing the ACP Lonworks
The ACP Lonworks installation work needs the professional technique.
Therefore, the installation described in this chapter should be performed by the certified installation professional. Consult the service center or the professional installation agency certified by us about any question or request related to the installation.
INSTALLING ACP LONWORKS
Check points during the ACP Lonworks installation
• The number of PI485 connected to one RS- 485 communication line ACP Lonworks provides 6 RS-485 ports. (CH 1~6)
- CH1~4 : ACP Lonworks provides 4 RS-485 ports for indoor unit connection.
Up to 64 indoor units (Up to 48 indoor units on PLNWKB100 version 2.2.0 or later)
- CH5 : ACP Lonworks provides 1 RS- 485 port for AHU unit connection. (Up to 16 AHU units)
- CH6 : No Use
Up to 16 PI485 for outdoor unit can be connected to one RS- 485 port, and up to 31 PI485 for SINGLE/ventilation can be connected.
• The number of the indoor units that can be connected to one ACP Lonworks One ACP can be connected Up to 64 indoor units (Up to 48 indoor units on PLNWKB100 version 2.2.0 or later)
To one RS-485 port, all of 64 indoor units (48 indoor units on PLNWKB100 version 2.2.0 or later), which is the maximum number that can be connected to the ACP Lonworks, may be connected.
But, to improve the communication performance of RS- 485, it is recommended to be divided and connected to 4 por ts.
• RS-485 communication cable connection
There is a polarity in RS- 485 communication cable connection, so be careful not to reverse the connection of the two cables.
Do not let the length of RS-485 communication cable exceed total of 1 km.
RS-485 communication cable must be connected with BUS type.
9
ENGLISH
• IP address of the ACP Lonworks
IP address of the ACP Lonworks, address of Gateway, and Net mask must be requested to the person in charge of the network of the corresponding site.
Caution
RS-485 Connection of the ventilation equipment
To connect ventilation equipment, it is recommended to use the ports other than RS-485 communication ports which are connected to air conditioners.
INSTALLING ACP LONWORKS
10
Setting the indoor unit address
ENGLISH
By considering the entire installation configuration connecting to one ACP Lonworks, set the address to each indoor unit not to be overlapped.
Address range that can be set to indoor units are determined as selected module type.
• Module 0: 00~FF in hexadecimal can be set to the indoor unit address, but it can be connected Up to 64 indoor units (Up to 48 indoor units on PLNWKB100 version
2.2.0 or later)
• Module 1: 00~0F in hexadecimal can be set to the AHU unit address, and it can be connected up to 16 AHU units.
Notes
Assigning indoor and outdoor unit number
If the outdoor unit product is Multi V, it is recommended to assign the address by setting the first digit of the address as the number of the outdoor unit, and classifying the second digit as the number or the indoor unit, for easy composition and classification of the system.
Outdoor unit
(group) number
Indoor unit
number
INSTALLING ACP LONWORKS
The following example sets the address to the indoor unit.
PLNWKB000
PLNWKB000
LON SVC
ACP
Lonworks
ventilator
ventilator
When the ACP Lonworks is interconnected with the AC Manager, the ventilator can be installed together and controlled. The above figure shows the example that sets the addresses of 30 and 31 to the ventilators and connects to the ACP Lonworks.
11
ENGLISH
Notes
How to set the central control address of the indoor unit
The central control address setting method may be different for each indoor unit product or remote control type, so set the address by referring to the manual of the indoor unit product or wired remote controller.
INSTALLING ACP LONWORKS
12
Setting the PI485 and connecting the cable
ENGLISH
After setting the address of the indoor unit, install the PI485 and set the DIP switch.
And then, connect the RS485 cable for communication with the ACP Lonworks.
Notes
Installing the PI485
Installing the PI485 depends on the outdoor unit.
y
So, install the PI485 by referring to the PI485 manual or the installation technique information.
y
To connect PI485 and the ACP Lonworks, two RS-485 cables need to be connected to BUS-A and BUS-B of PI485. Connect RS- 485 cable by referring to the following figure.
BUS_B
BUS_A
10V GND
If several PI485 are connected to each other to be connected to one ACP Lonworks, connect each BUS-A and BUS-B of PI485 to be connected to BUS-A and BUS-B of another PI485.
INSTALLING ACP LONWORKS
The following figure is an example of connecting several PI485 with each other to connect to one ACP Lonworks.
PNF-B17C0
PLNWKB000
LON SVC
BUS A BUS B
BUS_B
BUS_A
10V GND
BUS_B
BUS_A
10V GND
13
ENGLISH
BUS_B
BUS_A
10V GND
INSTALLING ACP LONWORKS
14
Installing ACP Lonworks and connecting cables
ENGLISH
After setting PI485, the ACP Lonworks shall be installed in an adequate place, and RS- 485 cable shall be connected for the communication with PI485.
And, Ethernet cable (LAN cable) shall be connected for the connection with internet or AC Manager.
To fix the ACP Lonworks, the following 2 methods may be used.
Install in DIN RAIL or fix to the wall considering the environment of the site.
Power
PLNWKB000
LON SVC
LAN cable RS-485 cable
INSTALLING ACP LONWORKS
Installing the ACP Lonworks in DIN RAIL
ACP Lonworks can be installed in DIN RAIL with width 35 mm and height 7.5 mm.
Proceed as the follows to install the ACP Lonworks in an adequate place.
The installation method of the ACP Lonworks is explained here with the example of installing the ACP Lonworks in DIN RAIL.
• Decide the space to install the ACP Lonworks.
• Before installing the ACP Lonworks, check if it is the adequate place to connect the ACP
Lonworks with the power, RS-485, and LAN, LON cables.
• Install DIN RAIL.
• Hook the top part of the ACP Lonworks on DIN R AIL.
• Push the main body of the ACP Lonworks until you hear the sound of installation.
• Pull the ACP Lonworks to check if it is fixed.
Hooking on DIN R AIL
PLNWKB000
LON SVC
15
ENGLISH
Fixing to DIN RAIL
Caution
After installing to DIN RAIL, do not fix to the wall using screws.
y
ACP Lonworks may be damaged.
y
DIN Rail fixing Screw Spec: M3, screw head height 2.0 ~ 1.75 mm, screw head diameter 7.0 ~
y
5.5 mm
INSTALLING ACP LONWORKS
16
Fixing the ACP Lonworks to the wall
ACP Lonworks can be installed by fixing to the wall. To install the ACP Lonworks in an adequate
ENGLISH
place, proceed according to the following explanation. It explains here on how to install the ACP Lonworks with the example of installing the ACP Lonworks on the wall.
• Decide the space to install the ACP Lonworks.
Before installing the ACP Lonworks, check if it is the adequate place to connect the ACP Lonworks with the power, RS-485, and LAN, LON cables.
• Fix to the wall using the driver. it can be fixed as in the following figure according to the
location to install.
PLNWKB000
SVC
LON
INSTALLING ACP LONWORKS
Connecting RS-485 cable to the ACP Lonworks
After fixing the ACP Lonworks in the installation place, RS-485 cable that was connected to PI485 shall be connected to the ACP Lonworks.
To connect RS- 485 cable to the ACP Lonworks, proceed as the following order.
• First, among the connectors that can be connected to the ACP Lonworks , connect the end of
RS-485 cable connected to BUS-A of PI485 to Tx part.
Next, connect the end of RS-485 cable connected to BUS-B of PI485 to Rx part.
• RS-485 cable that was connected to PI485 shall be connected to CH port (RS- 485 port) of the ACP Lonworks.
There are 1~6 CH ports
It must be plugged into one of 1~4 ports for air conditioner and ventilator indoor units.
It must be plugged into one of 5 port for AHU units.
6 port is not used.
17
ENGLISH
PLNWKB000
INSTALLING ACP LONWORKS
18
Information: Connecting RS-485 of the ACP Lonworks
ENGLISH
Up to 16 outdoor units can be connected to one RS-485 port of the ACP Lonworks, and up to48 indoor units(In case of AHU Unit, up to 16 AHU units) can be connected to one ACP Lonworks.
If there are many outdoor units to connect, the outdoor unit connections shall be appropriately connected to CH1 to CH4 in BUS format. Otherwise, the ACP Lonworks may malfunction. The following is an example of dividing to CH1 and CH2 and connecting in BUS format.
PLNWKB000
ACP Lonworks
BUS-B
BUS-A
BUS-B
BUS-A
LON SVC
The next shows the wrong example (STAR connection) of RS- 485 connection of the ACP Lonworks.
BUS-B
BUS-A
Caution
PLNWKB000
ACP Lonworks
LON SVC
If a different type of connection is made other than BUS format as in the figure, the product may malfunction. So be careful during the installation.
INSTALLING ACP LONWORKS
Connecting Ethernet cable (LAN cable) to the ACP Lonworks
After connecting the ACP Lonworks and RS -485 cable, Ethernet cable shall be connected to the ACP Lonworks .
ACP Lonworks may be connected to hub through Ethernet cable, or directly to AC Manager.
Connecting the ACP Lonworks and hub
It is the case of connecting the ACP Lonworks to the basic internet network installed at the site, and it is generally connected to the hub.
In such case, Ethernet cable shall be connected as a direct cable.
Use Ethernet cable (direct cable) to connect to LAN port of the ACP Lonworks.
Connecting ACP Lonworks and PC
It is the case of installing AC Manager in a separate PC and connecting ACP Lonworks and PC directly.
In such case, Ethernet cable shall be connected as a cross cable.
Use Ethernet cable (cross cable) to connect to LAN port of the ACP Lonworks.
19
ENGLISH
Connection with
허브와 연결
hub
다이렉트 케이블
Direct cable
AC Manager Plus가
Direct connection
설치된 PC와 직접연결
with PC
크로스 케이블
Cross cable
Caution
Ethernet cable types
You must distinguish if the Ethernet cable to connect is a direct cable or a cross cable.
y
Also, connect after checking the existence of problem in the cable using LAN tester.
y
INSTALLING ACP LONWORKS
20
Connecting LON communication cable(TP/FT-10) of
ENGLISH
ACP Lonworks.
LON communication cable(TP/FT-10) should be connected LON por t of ACP Lonworks.
ACP Lonworks can connect with BMS through LON communication cable(TP/FT-10).
There is non-polarity in TP/FT-10 communication cable conection.
Connect two line communication cable with BMS.
LonWorks
Adapter
BMS Control (PC)
PLNWKB000
LON
SVC