LG Electronics PACKAGED TERMINAL AIR CONDITIONER/HEAT PUMP User Manual

Page 1
LG
Packaged Terminal
Air Conditioner/Heat Pump
SERVICE MANUAL
LG
CAUTION
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
• FOR AUTHORIZED SERVICE ONLY.
Page 2
—2—
1. PREFACE
1.1 SPECIFICATIONS...............................................3
1.2 FEATURES AND BENEFITS..............................5
1.3 CONTROL LOCATIONS.....................................6
1.4 ADDITIONAL CONTROLS..................................9
2.
DISASSEMBLY INSTRUCTIONS
2.1 MECHANICAL PARTS......................................13
2.1.1 FRONT GRILLE.......................................13
2.1.2 CONTROL BOX.......................................14
2.2 AIR HANDLING PARTS....................................15
2.2.1
ELECTRIC HEATER AND CROSS FLOW FAN
(Electric heater model only)
......15
2.2.2 AXIAL FAN...............................................15
2.2.3 SHROUD..................................................16
2.3 ELECTRICAL PARTS .......................................16
2.3.1 OUTDOOR MOTOR ................................16
2.3.2 INDOOR MOTOR ....................................16
2.3.3 COMPRESSOR.......................................16
2.3.4 CAPACITOR............................................16
2.3.5 POWER CORD........................................17
2.3.6 P.C.B........................................................17
2.4 REFRIGERATION CYCLE................................18
2.4.1 CONDENSER..........................................18
2.4.2 EVAPORATOR........................................18
2.4.3 CAPILLARY TUBE...................................18
3.
INSTALLATION
3.1 HOW TO INSTALL THE UNIT...........................21
3.2 WALLSLEEVE INSTALLATION........................22
3.2.1 WALL SLEEVE INSTALLATION DATA...22
3.2.2 PREPARATION OF FRONT GRILLE......23
3.2.3 UNIT INSTALLATION..............................24
3.3 ELECTRICAL REQUIREMENTS ......................27
3.3.1
ELECTRICAL DATA (FOR 230V/208 MODEL)...............
27
3.3.2 ELECTRICAL SAFETY
.................................
27
4.
FIELD INSTALLED ACCESSORIES
.........
28
5.
FERFORMANCE DATA
.......................................
44
6.
TROUBLESHOOTING GUIDE
6.1 OUTSIDE DIMENSIONS...................................50
6.2 PIPING SYSTEM...............................................50
6.3 TROUBLESHOOTING GUIDE..........................51
7. SCHEMATIC DIAGRAM..........................56
8. EXPLODED VIEW......................................57
1. PREFACE
This
SERVICE MANUAL provides various service information, including the mechanical and electrical
parts, etc. This room air conditioner was manufactured and assembled under a strict quality control system. The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.
CONTENTS
Page 3
—3—
1.1 SPECIFICATIONS
Models
Cooling Capacity W
Btu/h
Heating Capacity W
Btu/h Electric Heatier Capacity W Power Input Cooling/Heating W Running Current Cooling/Heating A Starting Current Cooling/Heating A EER W/W
Btu/h.W COP W/W Power Supply Ø / V / Hz Air Flow Rate
Indoor,Max m
3
G/min(cfm)
Outdoor,Max
m3G/min(cfm) Moisture Removal l/h Sound Level Indoor,H/M/L dB(A)+3
Outdoor,Max dB(A)+3 Refrigerant & Charge g(oz) Compressor Type
Model
Motor Type
Oil Type
Oil Charge cc
O.L.P Name Fan Type(In/Out)
Motor Type
Motor OutputW Power Supply Cable No.*mm
2
Dimension W*H*D mm
inch Net Weight Indoor kg(lbs) Tool Code(Chassis) Functions Temperature Control
Energy Saver Switch Prefilter(washable/anti-fungus) Plasma Filter Steps, Fan/Cool/Heat Airflow Direction Control(up&down) Airflow Direction Control(left&right) Remocon Type Setting Temperature
Cooling
Range
Heating Auto Operation (Micom Control) Panel Touch Type Timer Air Discharge Air Ventilation Device Control(Defrost) Hot Start Look Cabinet Type(Chassis Type) Special Function
LP070CED1 LP090CED1 LP120CED1 LP150CED1
2227 2608 3458 4103 7600 8900 11800 14000
-- - -
-- - -
2000 3700 3700 3700
650 810 1105 1475
2.6 3.2 4.4 5.8
-/- -/- -/- -/-
3.42 3.2 3.12 2.78
11.7 11.0 10.7 9.5
-- - -
1 / 265 / 60 1 / 265 / 60 1 / 265 / 60 1 / 265 / 60
8.5(300) 8.5(300) 12.0(420) 12.0(420)
-- - -
0.9 1.2 1.5 2.0
45/-/43 45/-/43 49/-/47 49/-/47
60/58 60/58 63/61 63/61
R22,645(22.8) R22, 690(24.3) R22, 680(24.0) R22, 650(22.9)
Rotaty(Non Tropical) Rotaty(Non Tropical) Rotaty(Non Tropical) Rotaty(Non Tropical)
2R9S276A6A 2R12S276A6B 2P16S276A1A 2K20S276A6A
PSC PSC PSC PSC
ATMOS M60 or SUNISO 4GDID ATMOS M60 or SUNISO 4GDID ATMOS M60 or SUNISO 4GDID ATMOS M60 or SUNISO 4GDID
260 290 270 410
Internal Internal Internal Internal
Cross Flow Fan / Axial Fan Cross Flow Fan / Axial Fan Cross Flow Fan / Axial Fan Cross Flow Fan / Axial Fan
4 POLES 4 POLES 4 POLES 4 POLES
50 50 50 50
3*2.1 3*2.1 3*2.1 3*2.1
1066*406*505 1066*406*505 1066*406*505 1066*406*505
42*16*19-7/8 42*16*19-7/8 42*16*19-7/8 42*16*19-7/8
39.8(88) 39.3(87) 42.5(94) 46.3(102) YA YA YA YA
Thermistor Thermistor Thermistor Thermistor
OO O O OO O O
-- - -
2/2/2 2/2/2 2/2/2 2/2/2
Manual Manual Manual Manual
-- - -
-- - ­54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C)
-- - -
Micom Micom Micom Micom
12h, On/Off 12h, On/Off 12h, On/Off 12h, On/Off
Rear Rear Rear Rear
OO O O
-- - -
-- - -
L-Look L-Look L-Look L-Look
-- - -
Electric Heater Electric Heater Electric Heater Electric Heater
LP 12 0 C E M 1
12 34 5 6 7 8 9 Digits 1,2 - LG Packaged Terminal Air Conditioner Digit 6 - Product Type
Digits 3,4 - Unit Cooling Capacity C = Air Conditoner 07 = 7,000 Btu/h H = Heat Pump 09 = 9,000 Btu/h Digit 7- Electric Heat 12 = 12,000 Btu/h E = Electric Heater 15 = 15,000 Btu/h Digit 8 - D = Digital M = Mechanical Digit 9 - Electric Voltage 1 = 265V, 60Hz None = 230V, 60Hz
Page 4
—4—
Models
Cooling Capacity W
Btu/h
Heating Capacity W
Btu/h Electric Heater Capacity W Power Input Cooling/Heating W Running Current Cooling/Heating A Starting Current Cooling/Heating A EER W/W
Btu/h.W COP W/W Power Supply Ø / V / Hz Air Flow Rate
Indoor,Max m3G/min(cfm) Outdoor,Max
m3G/min(cfm) Moisture Removal l/h Sound Level Indoor,H/M/L dB(A)+3
Outdoor,Max dB(A)+3 Refrigerant & Charge g(oz) Compressor Type
Model
Motor Type
Oil Type
Oil Charge cc
O.L.P Name Fan Type(In/Out)
Motor Type
Motor OutputW Power Supply Cable No.*mm
2
Dimension W*H*D mm
inch Net Weight Indoor kg(lbs) Tool Code(Chassis) Functions Temperature Control
Energy Saver Switch Prefilter(washable/anti-fungus) Plasma Filter Steps, Fan/Cool/Heat Airflow Direction Control(up&down) Airflow Direction Control(left&right) Remocon Type Setting Temperature
Cooling
Range
Heating Auto Operation (Micom Control) Panel Touch Type Timer Air Discharge Air Ventilation Device Control(Defrost) Hot Start Look Cabinet Type(Chassis Type) Special Function
LP070HED1 LP090HED1 LP120HED1 LP150HED1
2139 2726 3517 4220 7300 9300 12000 14400 1817 2345 3165 3869 6200 8000 10800 13200 2000 3700 3700 3700
630/550 830/690 1155/990 1565/1335
2.5/2.2 3.3/2.7 4.6/3.9 6.2/5.3
-/- -/- -/- -/-
3.39 3.28 3.04 2.69
11.6 11.2 10.4 9.2
3.3 3.4 3.2 2.9
1 / 265 / 60 1 / 265 / 60 1 / 265 / 60 1 / 265 / 60
8.5(300) 8.5(300) 12.0(420) 12.0(420)
-- - -
0.9 1.2 1.5 2.0
45/-/43 45/-/43 49/-/47 49/-/47
60/58 60/58 63/61 63/61
R22, 625(22.0) R22, 730(25.8) R22, 970(34.2) R22, 890(31.4)
Rotaty(Non Tropical) Rotaty(Non Tropical) Rotaty(Non Tropical) Rotaty(Non Tropical)
2R10S276A6C(RSM284) 2R13S276A6C 2P17S276(PSM312) 2K21S276A6C
PSC PSC PSC PSC
ATMOS M60 or SUNISO 4GDID ATMOS M60 or SUNISO 4GDID ATMOS M60 or SUNISO 4GDID ATMOS M60 or SUNISO 4GDID
260 290 350 410
Internal Internal Internal Internal
Cross Flow Fan / Axial Fan Cross Flow Fan / Axial Fan Cross Flow Fan / Axial Fan Cross Flow Fan / Axial Fan
4 POLES 4 POLES 4 POLES 4 POLES
50 50 50 50
3*2.1 3*2.1 3*2.1 3*2.1
1066*406*505 1066*406*505 1066*406*505 1066*406*505
42*16*19-7/8 42*16*19-7/8 42*16*19-7/8 42*16*19-7/8
41.2(91) 41.8(92) 45.0(99) 48.3(106) YA YA YA YA
Thermistor Thermistor Thermistor Thermistor
OOOO OOOO
-- - -
2/2/2 2/2/2 2/2/2 2/2/2
Manual Manual Manual Manual
-- - -
-- - ­54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C) 54˚F~86˚F(12.2˚C~30˚C)
-- - -
Micom Micom Micom Micom
12h, On/Off 12h, On/Off 12h, On/Off 12h, On/Off
Rear Rear Rear Rear
OOOO OOOO
-- - -
L-Look L-Look L-Look L-Look
-- - -
Electric Heater Electric Heater Electric Heater Electric Heater
Page 5
1.2 FEATURES AND BENEFITS
The PTAC has many features, some of which are different than those found on conventional PTAC units. The servicer must be familiar with these features in order to properly service the unit.
• IIR (Infinite Impulse Response) The IIR function senses the temperature several times per second and makes micro-adjustments several times per
• Compressor Restart Delay
This feature extends the overall life of compressor by preventing the short-cycling of the air-conditioner. When the compressor restarts, LG PTAC is designed to give a minimum of three minutes to have a time of equalizing the refrigerant pressures for optimizing cycling.
• Fan-Only Setting - High/Low
The fan can run at HIGH or LOW speed without COOLING or HEATING to provide air circulation and ventilation.
• Indoor Fan Speed Selections - High/Low
The fan can run at HIGH or LOW speed for either COOLING or HEATING.
• Two Fan motors
The unit has two fan motors to provide quiet operation and maximum efficiency.
—5—
THE SLEEVE AND THE REAR GRILLE
(Available as an option)
REAR GRILLE (Aluminum Rear Grille)
AIR FILTER
VERTICAL AIR DEFLECTOR
(Horizontal Louver)
SLEEVE ASSEMBLY (Including Aluminum Rear Grille)
R
O
O
D
N
I
INLET GRILLE
(Air Intake)
EXPANDED METAL GRILLE
(Superior for a performance)
Page 6
Indoor Filters
The unit uses two indoor filters which slide in and cut easily. The filters may be cleaned by washing and brushing without removing the front grille.
Rotary Compressor
The unit uses a rotary compressor for quiet, reliable operation and long life.
2 Position Discharge Grille
The discharge grille can provide air flows upward at an angle of 40 off vertical or 15 degree off vertical. The angle is changed by removing the front grille and 4 screws that fasten the discharge grille to the front grille and rotating the louvers to an alternate position.
Indoor Room Freeze Protection
When the unit senses the room temperature falls to less than 40° F the unit activates the fan motor and either the electric resistance heater or the hydronic heater to prevent pipes or fixtures from freezing. This also overrides front desk control of the unit mounted or wall mounted controls.
Door Switch/Occupancy Sensor
The unit is capable of accommodating a field installed door switch and occupancy sensor to operate the energy management feature. For additional information, refer to the unit operation section.
Compressor Overload Protection
This feature prevents the damage of the compressor by sensing the indoor tube temperature in heating. If the indoor temperature is over 130˚ F, the outdoor fan will be switched off and back on when the temperature drops below 120˚ F.
Outdoor Air Temperature Switchover
This will effectively change the unit from heat pump mode to total electric resistance heat.
Temperature limits
The unit is programmed to provide both heating and cooling temperature limits by dip switches on control panel from 54˚ F to 86˚ F. Temperature limits help to prevent overheating and overcooling and reduce energy costs.
Condensate Drain Valve
The unit has a condensate drain valve to prevent water from collecting or freezing in the basepan.
Quick Heater Recovery
The unit is designed to operate the electric heater to warm the room to the temperature set point as soon as heat pump cycle is on in heating. This feature has an advantage of reducing the time to reach the set point and improving the temperature increase for better comfort.
Reverse Cycle Defrosting - (PTHDs only)
The unit will activate the reverse cycle defrost when the outdoor coil temperature has remained at a cold temperature to form the ice on the coil.This ice will reduce airflow though the coil and will also reduce the efficiency of unit. The LG PTHP will employ an active reverse cycle defrost function to melt the ice off the outdoor coil for insuring room comfort conditions and savings from extended operation.
High Temperature Heat Pump Operation Protection
The compressor will be switched off to prevent damage when the heat pump is operated in high outdoor temperatures.
Remote Thermostat Control
Each unit is built to be operated from any standard 4 or 5 wire remote-mounted thermostat, if desired. The unit has a built-in low voltage power source which can accommodate a large variety of thermostat choices-manual, auto changeover, or programmable. A remote thermostat can also be added to any installed unit.
Zone Sensor
Occupants enjoy ultimate comfort with consistent climate control. Attach an optional, inexpensive remote Zone Sensor to exactly match the functions of the PTAC without disabling any features.
—6—
Page 7
—7—
1.3 CONTROL LOCATIONS
OPERATION
ELECTRIC HEATING MODEL COOLING ONLY MODEL
VENT OPEN
VENT
CLOSE
TEMPERATURE CONTROL
Set the Thermostat control to the desired temperature mark 5 (the mid-point is a good starting position). If the room temperature is not satisfactory after a reasonable time, adjust the control to a cooler or warmer setting, as appropriate.
OPERATION MODE SELECTOR
OFF Turns air conditioner off. LOW FAN Low speed fan operation without cooling. HIGH FAN High speed fan operation without cooling. LOW COOL Cooling with the low speed fan operation. HIGH COOL Cooling with the high speed fan operation. LOW HEAT Heating with the low speed fan operation. HIGH HEAT Heating with the high speed fan operation.
VENTILATION
The ventilation lever is located to the lower left side of the unit. The ventilation lever must be in the CLOSE position in order to maintain the best cooling conditions. When fresh air is necessary in the room, set the ventilation lever to the OPEN position. The damper is opened and outdoor air is drawn into the room. This will reduce the cooling or heating efficiency.
When the air conditioner has performed a cooling or heating operation and is turned off or set to the fan position, wait at least 3 minutes before resetting to the cooling operation.
A slight heat odor may come from the unit when first switching to HEAT after the cooling season is over. This odor, caused by fine dust particles on the heater, will disappear quickly. This is harmless.
CAUTION
NOTE
Page 8
—8—
ELECTRONIC CONTROLS
The controls will look like one of the following.
TEMP
MODE
HEAT
E/SAVE
FANFAN
COOLCOOL
HIGHHIGH
LOWLOW TIMERTIMER
FAN TIMER
'
F
ON
OFFONOFF
POWER
MODE
-
Push this button to cycle through the modes from COOL FAN
HEATCOOL.
- COOL
• Fan runs continually for normal cooling operation.
- ENERGY SAVER
• The fan stops when the compressor stops cooling. Approximately every 3 minutes the fan will turn on and the unit will check the room air temperature to determine if cooling is needed.
- FAN
• Fan operation without heating or cooling.
- HEAT
• Fan runs continually for normal heating operation.
TIMER
- SHUT-OFF TIME
• You will usually use shut-off time while you sleep.
• If unit is running, use Timer to set number of hours until shut-off.
• For your sleeping comfort, once Time is set, the Temperature setting will raise 2° F after 30 minutes, and once again after another 30 minutes.
• Push Timer to cycle through the settings from 1 Hour 2 Hours ... 12 Hours maximum.
TEMPERATURE SETTING
• Use this button to automatically control the temperature of the room. The temperature can be set within a range of 54° F to 86° F by increments of 2° F.
• The setting appears in the display.
FAN SPEED
• Every time you push this button, it cycles through the settings as follows: {High(F2) Low(F1) High(F2) Low(F1)}
• To turn the air conditioner ON, push this button. To turn the air conditioner OFF, push the button again.
• This button takes priority over any other button.
Page 9
—9—
REMOVING THE FRONT GRILLE
Additional controls are available after removing the front grille and option cover of control box. To remove the front grille, pull out the bottom of front grille and then lift up. To replace the front grille, place the tabs over the top of the unit and push the bottom of front grille until the clips snap into place.
ADDITIONAL CONTROLS
The additional controls are located behind the option cover of control box. The standard settings will be in the OFF position. The authorized servicer has to check switches and ensure the switches are in the desired position.
TEMPERATURE LIMITING
Temperature Limiting can save money by limiting the lowest temperature for cooling and the highest temperature for heating. The temperature limiting is controlled by switches #1 - #3. This temperature limiting is not available with the Remote Wall Thermostat.
ON
ONREMOTE
OFF
ON ON ON
Remote/Local Energy Saver Temperature Limit 1 Temperature Limit 2 Temperature Limit 3 PTAC/PTHP UNIT TYPE
LOCALLOCAL
1
OFF
OFF
2
OFF
OFF
3
OFF
OFF
4
OFF
OFF
5
LOCAL
1
OFF2OFF3OFF4OFF
5
LOCAL
LOCAL
1
OFF
OFF
2
OFF
OFF
3
OFF
OFF
4
OFF
OFF
5
LOCAL
1
OFF2OFF3OFF4OFF5OFF6OFF
7
LOCALLOCAL
1
OFF
OFF
2
OFF
OFF
3
OFF
OFF
4
OFF
OFF
5
LOCAL
1
OFF2OFF3OFF
4
OFF
5
1.4 ADDITIONAL CONTROLS
Temperature Temperature Temperature
Cooling Operation
Limit #1 Limit #2 Limit #3
OFF OFF OFF 54° F (12.2° C) 86° F (30.0° C)
ON OFF OFF 56° F (13.3° C)
OFF ON OFF 58° F (14.4° C)
ON ON OFF 60° F (15.5° C)
OFF
ON OFF ON 64° F (17.7° C)
OFF ON ON 66° F (18.9° C) 74° F (23.3° C)
ON ON ON 68° F (20.0° C) 72° F (22.2° C)
OFF ON 62° F (16.6° C)
#6
ON ON
Lowest Temp. Highest Temp. Lowest Temp. Highest Temp.
54° F (12.2° C) 86° F (30.0° C) 86° F (30.0° C) 86° F (30.0° C) 86° F (30.0° C) 86° F (30.0° C) 86° F (30.0° C) 86° F (30.0° C)
#7
OFF
ON
54° F (12.2° C)
54° F (12.2° C)
54° F (12.2° C)
54° F (12.2° C)
54° F (12.2° C)
54° F (12.2° C)
54° F (12.2° C)
Cooling+Electric Heater+Heat PumpOFFOFF Cooling+Electric HeaterONOFF Heat Pump Only Cooling Only
Heating Operation
86° F (30.0° C) 84° F (28.9° C) 82° F (27.8° C) 80° F (26.7° C) 78° F (25.5° C) 76° F (24.4° C)
Unit Type
Page 10
—10—
TEMPERATURE LIMITING
Temperature Limiting can save money by limiting the lowest temperature for cooling and the highest temperature for heating. The temperature limiting is controlled by dip switch #1 - #3. This temperature limiting is not available with the Remote Wall Thermostat.
OFF OFF OFF 54°F (12.2°C) 86°F (30.0°C) 54°F (12.2°C) 86°F (30.0°C)
ON OFF OFF 56°F (13.3°C) 86°F (30.0°C) 54°F (12.2°C) 84°F (28.9°C)
OFF ON OFF 58°F (14.4°C) 86°F (30.0°C) 54°F (12.2°C) 82°F (27.8°C)
ON ON OFF 60°F (15.5°C) 86°F (30.0°C) 54°F (12.2°C) 80°F (26.7°C)
OFF OFF ON 62°F (16.6°C) 86°F (30.0°C) 54°F (12.2°C) 78°F (25.5°C)
ON OFF ON 64°F (17.7°C) 86°F (30.0°C) 54°F (12.2°C) 76°F (24.4°C)
OFF ON ON 66°F (18.9°C) 86°F (30.0°C) 54°F (12.2°C) 74°F (23.3°C)
ON ON ON 68°F (20.0°C) 86°F (30.0°C) 54°F (12.2°C) 72°F (22.2°C)
Temperature Temperature Temperature
Limit #1 Limit #2 Limit #3
Lowest Temp. Highest Temp. Lowest Temp. Highest Temp.
Cooling Operation Heating Operation
REMOVING THE FRONT GRILLE
Additional controls are available after removing the front grille and option cover of control box. To remove the front grille, pull out the bottom of front grille and then lift up.
To replace the front grille, place the tabs over the top of the unit and push the bottom of front grille until the clips snap into place.
ADDITIONAL CONTROLS
The additional controls are located behind the option cover of control box. The standard settings will be in the OFF position. The authorized service man has to check switches and ensure the switches are in the desired position.
ON
ONREMOTE
OFF
ON ON ON
Remote/Local Energy Saver Temperature Limit 1 Temperature Limit 2 Temperature Limit 3
LOCAL
1
OFF
2
OFF3OFF4OFF
5
LOCAL
1
OFF2OFF3OFF4OFF
5
LOCAL
1
OFF
2
OFF3OFF4OFF
5
LOCAL
1
OFF2OFF3OFF4OFF
5
Page 11
Wiring Schematic for Remote Heat Pump
Wiring Schematic for Straight Cool Unit.
—11—
REMOTE/LOCAL CONTROL
When remote/local switch #1 is on, it allow the unit to operate by the Remote Wall Thermostat. The unit control by knobs are not available.
ENERGY SAVER
The energy saver switch #2 is on. This switch is set at cycle fan to provide continuous fan operation in cool or heat modes. When the switch is off the continuous fan allows continuous circulation of room air and make the more balanced temperature of the room. When the switch is on, the fan is on or off with the compressor or with the heater.
FRONT DESK CONTROL
When the pair wire is connected to the connector FD2 and FD1, the unit can be turned ON or OFF with a switch located at the Front Desk Control panel. When the front desk switch is ON, the fan operates according to the setting without working compressor and heater. When the front desk switch is OFF, the unit can operate according to the setting of controls.
REMOTE WALL THERMOSTAT
When the wires are connected, the unit will be controlled by a remote wall thermostat. The thermostat connections supply the 24 Volt AC. When you install the digital/electronic thermostat, you must set it to 24 Volt AC. See the installation Instruction in this manual for the Remote Wall Thermostat.
Note: The following figures show wiring
schematics for heat pump and straight
cool units with electric heat, respectively.
GL GH O W Y R C
Low Fan
High Fan
Reversing V alve
Heater
Compressor
24 Volt-L
24 Volt-N
FD2 FD1 DR2 DR1 MS2 MS1
Front Desk Control
Front Desk Control
Door Switch
Door Switch
Motion Sensor
Motion Sensor
(Molex Housing Spec 396-06V)
(Molex Housing Spec 396-07V)
Wire # AWG Maximum Length
#22 #20 900 ft (270 m) #18 1500 ft (450 m) #16 2000 ft (610 m)
600 ft (180 m)
Page 12
—12—
(Molex Housing Spec 396-09V)
FRONT DESK CONTROL
When the pair wire is connected to the connector LOand LI, the unit can be turned ON or OFF with a switch located at the Front Desk Control panel. When the front desk switch is ON, the fan operate according to the condition of setting without working compressor and heater. When the front desk switch is OFF, the unit can operate according to the setting of controls.
REMOTE WALL THERMOSTAT
When the wires are connected, the unit will be controlled by a remote wall thermostat.
The thermostat connections supply the 24 Volt AC. When you install the digital / electronic thermostat, you must set it to the 24 Volt AC. See the installation Instruction in this manual for the Remote Wall Thermostat.
REMOTE/LOCAL CONTROL
When remote/local switch #1 is on, it allow the unit to operate by the control of Remote Wall Thermostat. The unit control by knobs are not available.
ENERGY SAVER
The energy saver switch #2 is on. This switch is set at continuous fan to provide continuous fan operation in cool or heat modes. When the switch is off the continuous fan allows continuous circulation of room air and make the more balanced temperature of the room. When the switch is on the fan is on or off with the compressor or with the heater.
Wire # AWG Maximum Length
#22 600ft(180m) #20 900ft(270m) #18 1500ft(450m) #16 2000ft(610m)
GL GH O W Y R CLO LI
Front Desk Switch
LO LI GL GH O W Y R C
Low Fan
High Fan
Reversing Valv e
Heater
Compressor
24 Volt-L
24 Volt-N
Wiring Schematic for Remote Heat Pump
Wiring Schematic for Straight Cool Unit.
Note:The following figures show
wiring schematics for heat pump and straight cool units with electric heat, respectively.
Page 13
—13—
2.1 MECHANICAL PARTS
2.1.1 FRONT GRILLE
1. Remove the front grille. (See Figure 1)
2. To remove the front grille, pull out the bottom of the front grille and then lift up. Re-install the component by referring to the removal procedure.
3. To replace the front grille, place the tabs over the top of the unit and push the bottom of front grille until the clips snap into place.
• This Room Air Conditioner (PTAC) discharges air from the top of the unit through reversible, 2-position discharge grille louvers. The unit is shipped from the factory with the discharge grille louvers at an angle of 40˚ off vertical. In the alternate position, the louvers will be at an angle of 15˚ off vertical.
To adjust air direction, remove the front grille. Remove the 4 screws that fasten the discharge grille to the front grille.
Flip the discharge grille 180°, then reattach the discharge grille to the front grille with 4 screws.
2. DISASSEMBLY INSTRUCTIONS
— Before the following disassembly, POWER SWITCH is set to OFF and disconnected the power cord.
Figure 1
40˚
15˚
Screws
Page 14
—14—
2.1.2 CONTROL BOX
1. Remove the front grille. (Refer to section 2.1.1)
2. Remove the two screws which fasten the control
box. (See Figure 2)
3. Pull the control box from the Air guide.
4. Remove the control box cover. (See Figure 3)
5. Disconnect wire housings on the control box.
6. Pull the control box assembly out from the unit.
(See Figure 4)
7. Re-install the components by referring to the
removal procedure.
Figure 2
Figure 3
Figure 4
Page 15
—15—
Figure 8
2.2 AIR HANDLING PARTS
2.2.1 HEATER ASSEMBLY AND CROSS FLOW FAN
1. Remove the front grille. (Refer to section 2.1.1)
2. Remove the control box assembly. (Refer to section 2.1.3)
3. Remove the 3 screws which fasten the net steel. (See Fig. 5)
4. Remove the 3 screws which fasten the electric heater assembly.(Electric heater model only) (See Fig.5).
5. Loosen the hexagon screw with the Hex­wrench(See Fig.6)
6. Remove the 4 screws which fasten the indoor motor and the earth wire. (See Fig. 6, 7)
7. Re-install the components by referring to the removal procedure, above.
2.2.2 FAN
1. Remove the brace.
2. Remove the 4 screws which fasten the condenser with the shroud and the basepan.
3. Move the condenser sideways carefully.
4. Remove the clamp which secures the fan with plier.
5. Remove the fan. (See Fig. 8)
6. Re-install the components by referring to the removal procedure, above.
Figure 5
Figure 6
Figure 7
Page 16
—16—
2.2.3 SHROUD
1. Remove the axial fan. (Refer to section 2.2.3)
2. Remove the 4 screws which fasten the condenser with the shroud and the basepan.
3. Remove the shroud.
4. Re-install the component by referring to the
removal procedure.
2.3. ELECTRICAL PARTS
2.3.1 OUTDOOR MOTOR
1. Remove the clamp cord and disconnect a wire housing in control box. (Refer to section 2.1.2)
2. Remove the axial fan. (Refer to section 2.2.3)
3. Remove the 2 screws which fasten the motor. (See Figure 10)
4. Remove the motor
5. Re-install the component by referring to the
removal procedure, above.
2.3.2 INDOOR MOTOR (Refer to section 2.2.2)
2.3.3 COMPRESSOR
1. Discharge the refrigerant system using a refrigerant recovery system. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the refrigerant. Leave the valve in place after servicing the system.
2. Disconnect the 3 leads from the compressor.
3. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.
4. Remove the 3 nuts and the 3 washers which fasten the compressor. (See Figure 11)
5. Remove the compressor.
6. Re-instill the components by referring to the removal procedure, above.
2.3.4 CAPACITOR
1. Remove the control box. (Refer to section 2.1.2)
2. Remove 1 screw and disconnect the leads which connected to the box type capacitor. (See Figure 12)
3. Remove 1 screw and the clamp which fastens the can-type capacitor.
4. Disconnect all the leads of capacitor terminals.
5. Re-install the components by referring to the removal procedure, above.
Figure 9
Figure 10
Figure 11
Figure 12
Page 17
—17—
2.3.5 POWER CORD
1. Remove the control box. (Refer to section 2.1.2)
2. Disconnect the grounding screw from the control box.
3. Disconnect 2 receptacles.
4. Remove a screw which fastens the clip cord.
5. Separate the power cord from the control box. (See Figure 13)
6. Re-install the component by referring to the removal procedure, above. (Use only one ground-marked hole for ground connection.)
7. If the supply cord of this appliance is damaged, it must be replaced by an exact replacement part. (The special cord means the cord which has the same specification marked on the supply cord fitted to the unit.)
2.3.6 P.C.B.
1. Remove the escutcheon.
2. Remove the two knobs.
3. Remove the 2 screws which fasten P.C.B. cover.
4. Disconnect all the leads which connected to the P.C.B.
5. Remove the two screws which fasten the P.C.B. board.
6. Re-install the components by referring to the removal procedure, above.
Figure 13
Figure 14
After servicing control box ,make sure that AC and DC wires are separated and tied up properly.
The wires should also be pressed a little downwards to prevent touching it to the display pcb.
WARNING
Page 18
—18—
2.4 REFRIGERATION CYCLE
2.4.1 CONDENSER
1. Remove the brace and the shroud. (Refer to section 2.2.2)
2. Remove the 4 screws which fasten the shroud. (Refer to section 2.2.2)
3. Push forward the shroud and remove the 2 screws which fasten the condenser with the basepan.
4. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.
5. Remove the condenser.
6. Re-install the components by referring to notes. (See Figure 15)
2.4.2 EVAPORATOR
1. Remove the front grille. (Refer to section 2.1.1)
2. Discharge the refrigerant completely.
3. Remove the control box assembly. (Refer to section 2.1.2)
4. Remove the 4 screws which fasten the evaporator at the left side and the right side.
5. Move the evaporator sideward carefully and then unbraze the interconnecting tube at the evaporator connectors.
6. Remove the evaporator.
7. Re-install the components by referring to notes. (See Figure 16)
2.4.3 CAPILLARY TUBE
1. After discharging the refrigerant completely, unbraze the interconnecting tube at the capillary tube.
2. Remove the capillary tube.
3. Re-install the components by referring to notes.
Figure 15
Figure 15
Discharge the refrigerant system using a refrigerant recovery system. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the refrigerant. Leave the valve in place after servicing the system.
CAUTION
Figure 16
Page 19
—19—
— Replacement of the refrigeration cycle.
1. When replacing the refrigeration cycle, be sure to discharge the refrigerant system using a refrigerant recovery system. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the refrigerant. Leave the valve in place after servicing the system.
2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.
3. Solder service valves into the pinch-off tube ports, leaving the valves open.
4. Solder the pinch-off tubes with service valves.
5. Evacuate as follows.
1) Connect the vacuum pump, as illustrated
Figure 17 A.
2) Start the vacuum pump, slowly open manifold
valves A and B with two full turns counterclockwise and leave the valves closed. The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold
and entire system.
3) Operate the vacuum pump for 20 to 30 minutes,
until 600 microns of vacuum are obtained. Close valves A and B, and observe the vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop
the vacuum pump.
4)
Remove the hose from the vacuum pump and place it on the charging cylinder. See Figure 16 B. Open valve C. Discharge the line at the manifold connection.
5) The system is now ready for final charging.
6. Recharge as follows :
1) Refrigeration cycle systems are charged from the high-side. If the total charge cannot be put in the high-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.
2)
Connect the charging cylinder as shown in Figure 17B. With valve C open, discharge the hose at the manifold connection.
3) Open valve A and allow the proper charge to enter the system. Valve B is still closed.
4) If more charge is required, the high-side will not take it. Close valve A.
5) With the unit running, open valve B and add the balance of the charge.
a. Do not add the liquid refrigerant to the low-
side.
b. Watch the low-side gauge; allow pressure to
rise to 30 lbs. c. Turn off valve B and allow pressure to drop. d. Repeat steps B and C until the balance of the
charge is in the system.
6) When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.
NOTES
If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.
CAUTION
Page 20
—20—
Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment. pinch-off tool capable of making a vapor-proof seal, leak detector, tubing cutter, hand tools to remove components, service valve.
A
COMPOUND GAUGE
EVAPORATOR (LOW PRESSURE SIDE)
COMPRESSOR
CAPILLARY TUBE
CONDENSER (HIGH PRESSURE SIDE)
SEE INSETS
BELOW
MANIFOLD
GAUGE
B
Figure 17A-Pulling Vacuum
Figure 17B-Charging
A
B
EXTERNAL VACUUM PUMP
LOW
B
HI
A
CHARGING CYLINDER
C
Page 21
—21—
3. INSTALLATION
3.1 HOW TO INSTALL THE UNIT
For existing sleeve, you should measure the wall sleeve
dimensions. Install the new air conditioner according to these installation instructions to achieve the best performence. All wall sleeves used to mount the new air conditioner must be in good structural condition and have a rear grille that securely attaches to the sleeve or the flange of the sleeve to secure the new air conditioner.
• To avoid vibration and noise, make sure the unit is installed securely and firmly.
When installing the sleeve, make certain there is nothing within 20" of the back that would interfere with heat radiation and exhaust air flow.
1) Take out the insulation strip from the upper packing.
2) Attach the insulation strip onto the rear upper side of the
wall sleeve.
3) To improve unit energy efficiency, it is recommended the
change of outside grille for an unit protection and an addition of a plastic rear grille. (This is optional.)
4) Insulation strip prevents the exhaust air from re-entering
from either side of condenser space which may decrease the cooling efficiency of condenser.
406 mm
(16")
1,066 mm
(42")
349 mm (13
3
/4")
505 mm
(20")
406 mm
(16")
1066 mm
(42")
349 mm (13 3/4")
Over 20"
HEAT
RADIATION
WALL
WALL
INSULATION SLEEVE
INTAKE
AIR
COOLED
AIR
1/4" Bubble
of the level
Front
Insulation Strip
Rear
Sleeve
280 mm
(11")
• There are sharp edges that can cause serious cuts.
• When lifting the air conditioner, it is HEAVY.
Use 2 people to lift.
CAUTION
Dimension of air conditioner
Dimension of sleeve assembly (optional)
Wall opening 16-1/4"x42-1/4"
Insulation strip must be attached to prevent the re-circulation of exhaust air to inward side from the either side of condenser space. The insulation strip is provided with the box. Refer to the diagram below.
Recommended
13-3/4"
TOP VIEW
42"
GRILLE
ROOM
CABINET
Page 22
—22—
3.2 WALL SLEEVE INSTALLATION
3.2.1 Wall Case Installation Data
General
Generally, units are installed 3" to 5" above the floor (flush to finished floor installation is possible) as near to the center of the room as possible; underneath a window or a glass panel is typical. Normal installation of the wall case allows installation flexibility; from flush with the finished interior wall to a minimum of 1/4" of the wall case extending beyond the finished exterior of the building. Special consideration must be given to installations where the wall case does not extend a minimum of 1/4" beyond the finished exterior wall.
Regardless of the installation, there are several things to consider when selecting a location for installing the unit. For instance, drapery location could interfere with air discharge, and placement of furniture may have an impact on the performance of the unit. The following information is intended to minimize installation problems and assure you of trouble-free installation.
Refer to page 24 for required wall opening dimensions. Minimum recommended interior and exterior case projection for standard wall thicknesses are shown in the drawings in this manual. The case may be installed flush with the finished indoor wall.
Mounting an outdoor grille or louver section to the building face may cause a space between the outdoor coil and the louver section. Air splitters, aligned with the ends of the outdoor coil, must be installed between the outdoor coil inlet and outlet air streams. Gaps between the outdoor coil and the louver section may allow condenser air recirculation and affect the operation of the unit. See page 40 for requirements for custom louver sections.
For new construction, early planning with the architect is necessary. Unit location, electrical connection locations, and wall openings of the proper dimensions are essential to avoid the necessity of rework, fillers,
framing, moving electrical outlets, and other expensive modifications.
For existing construction it is important that carpentry, masonry and electrical work be performed by competent, qualified personnel. Since installations in
existing construction may involve removal of building material from the structure, locating the wall case must be done correctly.
The wall case should be level from side to side and from level to 1/4 bubble tilt to the outdoors. The condensate disposal system in the unit is designed to dissipate the condensate water generated during cooling operation in accordance with ARI standards and actually uses this water for maximum unit efficiency. A level unit will also insure proper performance of the Internal Condensate Removal (ICR) system optional on heat pump units.
Page 23
—23—
3.2.2
PREPARATION OF THE FRONT GRILLE
Carefully remove shipping tape from the front grille.
Brick, Frame, Stucco and Shingle Construction
For new construction, the opening for the wall case should be framed and the wall case inserted into the opening during construction. Lintels should be used when the building material is heavy and is not self supporting (such as brick). The wall case will fit an opening of six courses of standard brick or five courses of jumbo brick. Wall framing in this type construction is normally on 16" centers and the wall case will fit a framed opening spanning three 16" O.C. 2" x 4" stud spaces.
For existing construction the indoor and outdoor wall will need to be cut out, allowing for clearances of 1/8" on all sides of the wall case. Work should begin on the inside wall. Cut the correct dimensions and mark (using drill holes) the outside wall from each corner of the inside cutout. Studding that interferes with the opening must be removed and a suitable frame constructed to secure the wall case and provide adequate support for case and chassis.
Preparation of the Wall Case for All Types of Construction
As shipped, the LG wall sleeve is ready for installation. Do not remove the stiffener from inside the wall case or the weather closure panel from the outside face of the wall case until the outdoor grille and chassis are ready to be installed.
Installation of Wall Case in Wall Opening
1.
Position the wall case into the wall. The room side edge of the wall case should be at least flush with the finished wall for line cord installations and permanent connection installations when no sub-base is used, and should project into the room at least 2-3/8" when a sub-base is used. If the minimum exterior dimensions are not met, refer to page 23.
The outside edge of the wall case should extend at least 1/4" beyond the outside wall. This is necessary for proper caulking, to prevent sealing thedrain holes in the rear flange of the wall case, and to facilitate the installation of an accessory drain, if used.
2. The wall case should be secured to the wall at both sides. Use a minimum of two screws or other fastening device on each side. See Figure 2 page 19. Mark the wall case on each side 2" from the bottom and 2" from the top at a point where basic wall structure is located. Drill wall case and use fasteners appropriate for wall construction. All holes for fasteners in the side of the wall case must be at least 2" up from the bottom of the wall case. Never locate screws or
put other holes in the bottom of the wall case.
If the wall opening is greater than the case dimensions, spacers must be used on the sides between the wall case and the wall support structure to prevent distorting the wall case.
3. Caulk or gasket the entire opening on the outside between the wall case and exterior wall surface (4 sides) to provide total water and air seal.
4. Caulk or gasket room-side opening between wall case and interior wall surface (4 sides). Opening beneath or around the wall case can allow outdoor air to leak into the room resulting in increased operating costs and improper room temperature control.
Care should be taken in location of electrical supply entry in relationship to wall sleeve to assure access to receptacle or junction box once unit is installed.
1
1
1
Shipping Tape
The wall case should be level from side to side and from level to 1/4 bubble tilt to the outdoors. The condensate disposal system in the unit is designed to dissipate the condensate water generated during cooling operation in accordance with ARI standards and actually uses this water for maximum unit efficiency. A level unit will also insure proper performance of the Internal Condensate Removal (ICR) system optional on heat pump units.
Page 24
—24—
Page 25
—25—
1/4"
CAULK*
GRILLE
OUTDOOR
*Caulk around
perimeter of wall
case all four
sides where it
joins the building
- Interior and
Exterior.
Sub-Base Connected
FRAME AND BRICK VENEER INSTALLATION
WALL SECTION – DETAILED SIDE VIEW
LINTEL
2-3/8"
CAULK*
STEEL LINTEL
CAULK*
BY INSTALLER
MOUNTING SCREWS
WALL CASE
ROOM
CABINET
GRILLE
OUTDOOR
2" MIN.
SIDE CHANNEL
1-5/16"
CAULK*
3-11/16"
3" MIN.
5" MAX.
1/4"
MIN.
CAULK*
CARPET
OR TOP OF
POWER SUPPLY CONDUIT
(RAK204)
SUB-BASE
FINISHED FLOOR
(ALTERNATE ENTRY)
Cord Set Connected
CAULK*
RAB71 13-3/4"
RAB77 13-7/8"
20-7/8" (RAB71)
21" (RAB77)
WALL CASE
BY INSTALLER
MOUNTING SCREWS
ROOM
CABINET
2" MIN.
CAULK*
CONDUIT
POWER SUPPLY
(BY OTHERS)
WALL RECEPTACLE
CARPET
*Caulk around perimeter of wall case all four sides
OR TOP OF
FINISHED FLOOR
where it joins the building - Interior and Exterior.
Page 26
—26—
3.2.3 UNIT INSTALLATION
1. Remove the shipping screw from the ventilation door. (See Figure 20)
2. Remove the front gille by pulling it out at the bottom to release it, then lift it up along the unit top front. (See Figure 21)
3. Slide the unit into the wall sleeve and secure with 6 screws through the unit flange holes. (See Figure 22)
4. Reinstall the front grille by hooking the top over the unit top, then pushing it in at the bottom. (See Figure 23)
Figure 20
Figure 21
Figure 22
Figure 23
Page 27
—27—
Standard 265V grounding receptacle rated 20A
Use 20AMP,time delay fuse or 20AMP circuit breaker (2500W Heater
15 AMP Circuit Breaker)
Use 25AMP,time delay fuse or 25AMP circuit breaker (2500W Heater
15 AMP Circuit Breaker)
Standard 265V grounding receptacle rated 25A
CAUTION
1. Do not use an extension cord with this unit.
2. When the unit is in the OFF position, the power supply to the electrical controls is still energized.
3. Disconnect the power to the unit before servicing the unit.
4. Remove the power cord from the wall receptacle.
5. Remove or turn off the protective device (fuses or circuit breaker).
Wirings including installation of the receptacle must comply with the NEC and local codes, local regulations.
FUSE- Use a time-delay fuse or circuit breaker. Refer to the nameplate
for proper power supply requirements.
3.3.1 ELECTRICAL DATA (FOR 265V MODEL)
3.3.2 ELECTRICAL SAFETY
IMPORTANT GROUNDING INSTRUCTIONS
The air conditioner has a three-prong grounding plug on its power supply cord which must be plugged into properly grounded three-prong wall receptacle for your protection against possible shock hazard.
FUSE – Use a time-delay fuse or circuit breaker. Refer to the nameplate for proper power supply requirements. 265 VOLT UNITS
These units are equipped with a three-prong grounding plug on the power supply cord which must be plugged into a matching properly grounded three-prong wall receptacle for your protection against possible shock hazard. If such an outlet is not present, one must be installed by a qualified electrician in accordance with the National Electrical Code and local codes and ordinances. NOTE: DO NOT USE AN EXTENSION CORD on 265 Volt units.
"If unit equipped with cords and plugs as long as they are installed with
sub-bases, and the cord and plug are enclosed within the sub-base." "The sub-base must have means for permanent connection." "The sub-base must have an outlet for the connection of the cord and plug." "To complete the installation of this PTAC, there must be a sub-base"
3.3 ELECTRICAL REQUIREMENTS
Page 28
—28—
Control Panel Key Lock
Part No: AYCP101
Description
The Key Lock kit prevents tampering of the controls used to set temperatures and heating or cooling functions.
Receiving
Upon receipt of the product, inspect the shipping carton for signs of visible damage. Report any damage or shortage to the carrier and note it on the delivery receipt. Unit must be stored in its original shipping carton in a dry, secure place prior to its installation and use.
Installation
The installation and servicing of the equipment referred to in this booklet should be performed by qualified, experienced technicians.
1. Remove front from unit by pulling bottom out and then
lifting upward. (Figure 24)
2. Remove existing door assembly by lifting door halfway and using both hands, bow door just enough for door hinge pins to slide out of mating holes. (Figure 25)
3. Install the new door assembly with the key lock by bowing the door with both hands and aligning the door hinge pins with their bracket in the front. (Figure 26)
Important Note:
Personal Risk Hazard Underwriter’s Laboratories Inc. listed. For institutional use only where supervisory monitoring is available. Any other use may increase the risk of personal injury or property damage.
Note: The installation and servicing of this equipment must be performed by qualifieed.
experienced technicians
NOTICE:
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
WARNING - Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION - Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may
also be used to alert against unsafe practices.
CAUTION –Indicates a situation that may result in equipment or property-damage-only accidents.
4. FIELD INSTALLED ACCESSORIES
Door
Front
Hinge Pins (Each Side)
Brackets (Each Side)
Figure 24 - Remove Front
Figure 25 - Door Removal
Figure 26 - New Door Installation
Page 29
—29—
Condensate Disposal Pump Kit Installation
Part No: AYSB3101
Description
The internal condensate pump serves as a means for disposing of condensate generated during heat pump operation by transferring it to the indoor coil. The warm coil surface and the warm room air help in evaporation of the condensate while adding humidity to the room. As with any equipment of this type, the addition of this kit will decrease the effective heating capacity of the unit. This kit is not intended for use in seacoast or corrosive environments.
NOTE:
Under extreme high humidity conditions, the internal condensate pump may not be able to dispose of all the condensate produced, and condensate would then drip from the outside of the wall sleeve. If this condensation is unacceptable, then a drain system (including factory approved drain kit for the wall sleeve) should be installed.
Receiving
Upon receipt of the product, inspect the shipping carton for signs of visible damage. Report any damage or shortage to the carrier and note it on the delivery receipt. Unit must be stored in its original shipping carton in a dry, secure place prior to its installation and use.
Installation
The installation and servicing of the equipment referred to in this booklet should be performed by qualified, experienced technicians.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Important Note:
The unit OFF switch does not disconnect all electrical power to this unit.
1. Remove front by rotating bottom outward and then lifting up and out from chassis.
2. Unplug and remove the PTAC chassis from the wallsleeve. Move the chassis where the front and back of the chassis can be easily accessed.
3. Remove the top cover assembly, net steel.(Figure 27)
4. Lift the heater/discharge deck assembly approximately 10 inches by unscrewing three screws (two on the left side, one on the right side of the discharge deck) holding the discharge deck to the chassis. Lift upward being careful not to pinch heater wires. (Figure 28)
5. Place coil cover on top of the evaporator coil with flanges pointing down. Make sure cover is over entire top of coil. (Figure 28)
6. Position the short end of the condensate tube through the back wall of the partition panel using existing hole. The condensate tube should protrude through the partition panel by 1-3/4 inches. Rotate the condensate tube so the tube lays flat on the coil cover. (Figures 28 & 29)
Mounting Screws
Condensate T ube
Figure 27
Figure 28
Page 30
—30—
7. Position the condensate tube through existing hole (located right side of blower deck).
8. Make sure the holes in the condensate tube are facing inward toward the blower wheel.
9. Lower the discharge deck over the condensate tube and screw the discharge deck to the chassis with the existing screws. Replace the discharge screen and screw the screen to the discharge deck with the existing screws.
10. Using the overflow tube holder and the overflow tube,
hold the tube with the metal holder and screw the holder to the partition panel with the provided 1/2 inch #8 screw. (Figures 30 & 31)
11. Place the pump bracket onto the end of the pump by feeding the pump cord through the hole in the bracket and pushing the bracket onto the threads of the pump. Slide the supplied washer onto the threads of the pump. Screw the pump nut onto the threads of the pump and tighten the nut so that the bracket is secure against the pump. (Figure 32)
12. Position the pump in the back left corner of the basepan and screw the pump bracket to the basepan with the provided two 1/2 inch #8 screws. (Figure 33)
13. Remove the protective adhesive backing from the plastic U clip and mount the U clip to the plastic condenser shroud in approximately the position shown. (Figure 34)
14. Snap the provided round plastic grommet into the top condenser baffle. (Figure 34)
Condensate T ube
Screws
Holder
Tube
Figure 29
Figure 32
Figure 33
Figure 30
Figure 31
Page 31
—31—
15. Place one of the hose clamps over one end of the 16-inch vinyl hose. Place the same end over the barbed discharge tube of the pump assembly. Place a hose clamp on the other end of the 16 inch hose. Place this same end over the shorter leg of the overflow tube and secure the hose with the hose clamp. (Figure 34)
16. Place a hose clamp over one end of the 11-inch long hose. Push this same end over the longer leg of the over­flow tube and secure with the hose clamp. Place another hose clamp over the other end of the 11-inch hose. Push this same end over the condensate tube protruding out from the back of the partition panel and secure with the hose clamp. (Figure 34)
17. Route the condensate pump cord through the U clip on the condenser shroud, through the plastic grommet in the sheet metal condenser wing, through the plastic ring in the panel, and then through the hole in the panel where the compressor wires are routed through the panel.
NOTE: The permagum may have to be removed to feed the wires through the panel, make sure wires have no slack and replace the permagum to prevent air leaks. (Figures 34 and
35)
18. To gain access inside the control panel, remove the knobs and escutcheon. Remove the two screws holding the panel in position. Tilt the control panel forward, being careful not to pinch any wires. (Figure 36)
19. Lift the control panel up so the control panel is free of its hinges. Position the control panel so there is easy access for mounting components to the control panel. (Figure 36)
20. Connect the condensate pump to the ICR relay on the terminal board per Figure 37.
21. Install the basepan drain plug into the basepan drain hole by pushing it up into the drain hole from the bottom of the basepan. This will defeat the thermostatic controlled drain valve. The basepan drain is located to the left of the outside coil (as viewed from the back of the unit).
U Clip
Plastic Grommet
Overflow Tube
Figure 34
Permagum
Plastic Ring
Grommet
Condensate Pump Cord
Figure 35
Mode Switch
Thermostat
Remove two screws to gain access inside Control Panel
Fuse Holder Knockouts under panel
Figure 36
Figure 37 - Internal Condensate Removal Pump
Wiring
Page 32
—32—
Architecture Grille Aluminum - Single Pack
Part No: AYAGALA01
Description
Outdoor grilles are attached to the wall sleeve and exposed to the exterior wall. The grilles are an industry standard size of 42" x 16".
Receiving
Upon receipt of the product, inspect the shipping carton for signs of visible damage. Report any damage or shortage to the carrier and note it on the delivery receipt. The unit must be stored in its original shipping carton in a dry, secure place prior to its installation and use.
Installation
The installation and servicing of the equipment referred to in this booklet should be performed by qualified, experienced technicians.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Important Note:
The unit OFF switch does not disconnect all electrical power to this unit.
Note:
A baffle kit must not be used with a stamped aluminum grille on any PTAC installation.
Stamped Aluminum Grille
1. Prepare the wall sleeve for installation of the grille by
removing the cardboard stiffener and rear enclosure panel from the sleeve. These items may be removed from inside of the building.
Note:
The sleeve stiffener must be taken out before the rear sleeve enclosure panel can be removed from the sleeve.
2. Prepare the stamped aluminum grille for installation on the
sleeve by inserting the six (6) plastic grommets into the square holes located near the outer edges of all four sides of the grille. With the grille positioned so the flanges of all four sides are in the up position, insert the grommets so the square end protrudes through the grille in the opposite direction from the flanges.
3. Turn the grille so it can be removed through the rear sleeve
opening.
4. Install the stamped aluminum grille by aligning the guide
pins located in the lower right and left hand corners of the grille with the corresponding holes in the rear of the wall sleeve.
5. Secure the grille by threading each of the screws into the
plastic grommets.
6. Remove the wire handle (not shown in the picture) from the
center of the grille prior to installing the chassis into the sleeve.
Note:
Be sure to keep a firm grip on wire handle and grille to prevent it from dropping and/or causing possible injury or property damage.
Architectural Grille
1. Remove the cardboard sleeve stiffener and the rear
enclosure of the sleeve as described in Step 1 of the stamped aluminum grille instructions.
2. Turn the grille so it can be removed through the rear sleeve
opening.
3. Install the grille by aligning the four screws supplied to their
corresonding holes in the architectural grille.
Stamped Aluminum Grille
Architecture Grille
Page 33
—33—
4. Secure the grille to the sleeve by tightening the four screws to their corresponding holes in the grille.
5. Remove the wire handle after the installation is complete.
Note:
The stamped aluminum grille includes 6 screws, washers, nuts, and plastic grommets. The architectural grille includes 4 screws.
Condensate Drain kit
Part No: AYDR101
Description
Condensate water will drain from the chassis into the sleeve during normal heat pump operation. This can also occur during times of high humidity when in cooling operation. Install either the outdoor or indoor drain kit components to control the condensate water where normal drainage from the wall sleeve is not possible or undesirable. See Figure 38 for all components of the drain kit.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Important Note:
The unit OFF switch does not disconnect all electrical power to this unit.
Receiving
Upon receipt of the product, inspect the shipping carton for signs of visible damage. Report any damage or shortage to the carrier and note it on the delivery receipt. The product must be stored in its original shipping carton in a dry, secure place prior to its installation and use.
Installation
The installation and servicing of the equipment referred to in this booklet should be performed by qualified, experienced technicians.
Drain Installation
Note:
The optional drain kit serves only as a link between the unit and field-supplied condensate drain system. Installing the kit without connecting it to a drainage system will result in inadequate condensate removal, possible leakage and corrosion.
Algaecide: Some algaecide products may cause damage to the unit basepan and therefore should not be used. Contact your sales representative when considering the use of a commercial algaecide. See Figure 38 for components of the drain kit.
DRAIN FITTING
PLATE B
BLANK-OFF
PLATE C
BLANK-OFF
PLATE C
GASKETS A
1/2" DRAIN FITTING
MTG. SCREWS
MTG. SCREWS
BLANK-OFF
PLATE D
GASKET E FOR
PLATE D
Figure 38 – Components of Drain Kits
Page 34
—34—
Outdoor Drain Kit Installation
Before installing the wall sleeve louvered condenser grille, it must be determined if the optional outdoor wall sleeve drain kit is to be installed. The drain kit will allow the condensate from the outdoor and indoor coils to be routed to a suitable area. The drain kit can be installed so the condensate can be drained from the right or left hand side of the wall sleeve. See Figure 39. See local codes for proper condensate disposal.
To install the outdoor drain components proceed as follows:
1. Remove the rear enclosure panel and the sleeve stiffener. These items may be removed from the inside of the building.
2. The drain fitting can be installed on the left or right hand side of the sleeve. (Illustration will be for a right hand installation.) Insert the drain fitting in the opening of gasket A and hole of plate B. Secure this assembly to the rear of the sleeve with two sheet metal screws into holes G provided in sleeve. See Figures 40 and 41.
3. Locate the other gasket A on the back of blank off plate C and secure the assembly to the left rear of wall sleeve with sheet metal screws provided. See Figure 42 for finished left hand side installation.
If the unit chassis is to be installed right away, install the condenser grille to wall sleeve with hardware provided. See condenser grille installation instructions.
If the unit chassis will not be installed right away, replace the rear enclosure panel in the wall sleeve. This will help protect the inside of the building from weather damage.
If a subbase is used, be sure the right hand subbase cover is removed before the chassis is installed in the sleeve. Slide the chassis into the wall sleeve until the chassis flanges
contact the front edge of sleeve. Secure the chassis to the wall sleeve on each side with screws provided.
Re-install the cabinet front.
See the following pages for installation instructions of indoor drain kit.
1/2" DRAIN
FITTING
DRAIN FITTING
PLATE B
GASKETS A
MTG. SCREWS
BLANK-OFF
PLATE C
Figure 39 – Outdoor Drain Kit Installation
G
PLATE "B"
DRAIN FITTING
BLANK-OFF PLATE
SHEET METAL SCREWS
Figure 40 Figure 41
Figure 42
See Detail A
Sleeve overflow port Do not close up this port
Gasket
MTG. Screws (2)
1/2" Outdoor Drain Fitting
Detail A
Cover
Plate
Wall Sleeve Bottom
(4) Mounting Screws
Gasket (2)
Blank-off Plate (2)
Figure 43
Page 35
—35—
Indoor Drain Kit Installation
The internal drain is installed on the bottom of the wall sleeve when it is required to drain the condensate into a drain system inside of the building. The components of the wall sleeve drain kit are shown in Detail A. Use components C (2), D, E, mounting screws (6) and the Outdoor drain fitting.
1. The components D, E, and drain fitting of the kit are mounted on the bottom of the wall sleeve prior to the installation of the sleeve. It may be located in a feasible area on the bottom of the sleeve which is inside of the room except when a subbase is used. When a subbase is installed, the drain may be a minimum of 3 1/2 " from the front flange of the wall sleeve. The minimum clearance should provide adequate clearance for the subbase, see Figures 43 and 44.
2. Cut out the template in the lower right hand corner of these instructions to locate the field drilled holes. (Two to mount the plate and one for the Outdoor drain fitting). See Detail A on how the components have to be installed after the holes are drilled in the bottom of the wall sleeve. If the drain fitting is not connected to an indoor drainage system immediately after the wall sleeve is installed, it must be plugged with a cork to prevent indoor water damage in case it rains.
An indoor tube or hose (furnished by others) must be installed on the drain fitting and interconnected to the drain system inside of the building.
Install the two blank-off plates C and gaskets A on the outdoor portion of the wall sleeve as shown in Figure 43. These components may be installed after the sleeve is secured in the wall opening just prior to the installation of the condenser grille and chassis.
Leveling Legs
Part No: AYLL101
Description
Leveling legs are designed to provide extra front support and leveling of the wall sleeve. Two leg assemblies are required per unit and are provided in each kit. Four screws are also provided with each kit for attachment to the wall sleeve. See Figure 45.
The leveling legs must be installed before the chassis is installed, but after the wall sleeve is in place. Holes must be drilled in each side of the wall sleeve, below the duct package holes, for attachment to the wall sleeve.
Receiving
• Compare kit identification number with sales order to ensure that the correct kit has been received.
• Inspect the leveling legs for shipping damage. File damage claims with the delivering carrier immediately.
Installation
The installation and servicing of this equipment should be performed by qualified, experienced technicians.
Important Note:
The unit OFF switch does not disconnect all electrical power to this unit.
Checklist
The following is an abbreviated guide to leveling leg installation. Refer to appropriate areas for more detailed information.
Figure 44
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
WARNING
Page 36
—36—
Leveling Leg Assembly
To install the leveling leg assembly, complete the following:
1. Drill two 1/8-inch holes in each side of the wall sleeve, as shown in Figure 45, using the leveling leg assembly as a template. Locations near the front of the sleeve provide more support.
2. Adjust the leveling legs to the approximate height needed and install them on either side of the wall sleeve, using the screws provided. Bottom of wall sleeve can be anywhere from three to five inches above the screw base. Caulk around screws to prevent water leaks.
3. Level the sleeve horizontally from side-to-side. Provide a slight slope (one-quarter bubble in the sight glass) toward the outside. Check the level again after the unit has been installed. Adjust the legs as needed.
Installation on Wall Sleeve
1. Drill four 1/8-inch diameter holes in the wall sleeve, two on each side, using the leveling legs as a template. Caulk around screws to prevent water leaks.
2. Attach the legs to the wall sleeve, using the screws provided.
3. Adjust the leveling legs to level the wall sleeve from side to side and provide a slight pitch to the outside (one-quarter bubble in sight glass).
Adjuster Screw
Speed Grip Nut
Leveler Bracket
1/8" Diameter holes
(four required per unit field-drilled)
1"
1/4"
1/2"
NOTES:
1. Two leveling legs are supplied in each kit.
2. One kit is required per unit.
3. Fout mounting screws are provided in each kit.
Figure 45 - Leveling Leg Assembly
Figure 46 - Leveling Leg Installation on Wall Sleeve
Page 37
—37—
Hard Wire Kit
Part No: AYAGALA01
Description
Hard Wire Junction Box (Direct Wire Sub-Base) The hard wire junction box kit is used to hard wire the unit when it is not desirable to use the standard unit subbase or the unit power cord. The junction box provides a protected enclosure for electrical connections as required by some electrical codes. The hard wire junction box is intended to be mounted on the floor or the adjacent wall.
The junction box is furnished with approximately 2-1/2 feet of 1/2-inch flexible steel conduit and a metal box for securing the conduit to the unit cabinet at the incoming power opening.
An optional 230/208V or 265V power switch assembly is available for use with the hard wire junction box or subbase. The switch provides a POWER ON/OFF function at the unit as required by some electrical codes. A replacement junction box cover plate is provided with each switch kit. For additional information, refer to the Power Switch Installation Instructions.
Receiving
Upon receipt of the product, inspect the shipping carton for signs of visible damage. Report any damage or shortage to the carrier and note it on the delivery receipt. Unit must be stored in its original shipping carton in a dry, secure place prior to its installation and use.
Installation
The installation and servicing of this equipment should performed by qualified, experienced technicians.
Junction Box Kit Installation and Wiring Procedure
EIectrical connections at the unit must be made after the unit chassis is installed in the wall sleeve. The installer must determine and supply the mounting components for attaching the junction box to the wall or door.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Important Note:
The unit OFF switch does not disconnect all electrical power to this unit.
CAUTION Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
Important Note:
All wiring must comply with applicable local and national codes. Types and location of disconnect switches must comply with all applicable codes.
1. Remove the cover plate from the junction box
2. Mount the junction box to the wall or floor within 28 inches (711
mm) of the lower right corner of the wall sleeve.
3. If a disconnect switch is to be used, make electrical
connections to it and mount the switch in the junction box. Refer to the Power Switch Installation Instructions.
4. Remove control panel assembly by removing the two screws
holding control panel in place. Rotate the panel forward.
5. Disconnect the power cord leads from all electrical connections
including the ground wire.
6. Remove the power cord clamp and the power cord from the
unit.
7. For 208/230-volt units, remove and discard the white lead from
the wire assembly. For 265-volt units, remove and discard the red lead from the wire assembly.
8. Remove the retaining ring from the threaded portion of the
straight conduit clamp. Insert the three wires into the metal box through one of the two openings in the box. Replace the hole cover grommet into the unused hole to prevent objects from entering the box.
9. Replace the retaining ring back on the conduit clamp inside the
metal box and tighten the ring securely.
10. Insert the three wires extending from the metal box into the
incoming power opening on the unit so that approximately 20 inches (508 mm) of the wires protrude through the opening.
11. Attach the metal box to the chassis with the two screws
provided.
12. Insert the wire tie into the 1/4-inch diameter hole located just
above the incoming power opening. Tie all wires together securely with the wire tie. See Figure 48.
Page 38
—38—
265 Volt Units
1. Remove and discard the red lead from the wire assembly .
2. Connect the black lead to the center terminal of the fuse holder.
3. Connect the white lead to the common (C) terminal on the capacitor.
4. Connect the ground wire to the partition panel where the ground wire on the power cord was located. Use the supplied green ground screw.
5. Connect the white lead of the wire assembly at the junction box to the white lead of the field power source.
6. Connect the black lead of the wire assembly at the junction box to the black lead of the field power source.
7. Connect the ground wire of the field power supply to the bare ground wire of the wire assembly at the junction box.
8. Install the junction box cover plate.
9. Reinstall the control panel assembly.
Figure 49 - Electrical Wiring Routing
Figure 48 - Metal Box Location
Figure 48 - Mounting Hard Wire Junction Box Kit
Wall Sleeve
Ground Wie
with Eyelet
Terminal
Cover plate
28 Inch es Max
Conduit
with Straight Clamp
Power Leads
with Push on
Connectors
Metal Box
Control Panel
Base Pan
Bracket
Right Side of Chassis
Wire Tie
3/16 Inch
Diamenter Hole
Electrical Supply Wires
Back of Control Panel
Page 39
—39—
Fuse Holder Kit
Part No: AYFH1101
Description
This optional fuse holder kit can be installed directly in the chassis or in the optional subbase. Fuse holder kits are available in 230/ 208 volt ratings. The installer should supply time delay fuses at 15, 20, 25, or 30 amps in accordance with the Maximum Overcurrent Protection as listed on the unit nameplate. Fuses may be purchased from the parts department.
Note:
The installation and servicing of this equipment must be performed by qualified, experienced technicians only.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Important Note:
The unit OFF switch does not disconnect all electrical power to this unit.
CAUTION Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
Important Note:
All wiring must comply with applicable local and national codes. Type and location of fused disconnect switch(es) must comply with all applicable codes. Failure to follow these codes could result in overheating and equipment failure.
Receiving
Upon receipt of the product, inspect the shipping carton for signs of visible damage. Report any damage or shortage to the carrier and note it on the delivery receipt. Unit must be stored in its original shipping carton in a dry, secure place prior to its installation and use.
Installation
The installation and servicing of the equipment referred to in this booklet should be performed by qualified, experienced technicians.
Fuse Holder Kit Installation (Without Subbase)
1. Remove front by rotating bottom outward and then lifting up and out from chassis.
Mode Switch
Thermostat
Remove two screws to gain access inside Control Panel
Fuse Holder Knockouts under panel
Figure 50 - Control Panel
Page 40
—40—
2. To gain access inside the control panel, after removing the knobs and escutcheon, remove the screws holding panel in position. Tilt control panel forward, being careful not to pinch any wires. (Figure 50)
3. As viewed from the front, remove both knockouts on the control panel.
4. Insert two fuse holders from the front. The fuse holders should be oriented so the quick-connect tabs are toward the center of the unit. Attach fuse holders using the screws and nuts provided. (Figure 50)
5. Remove both power cord leads, one lead from the capacitor and one from the electronic board.
6. Install one power cord lead on the center terminal of one fuse holder. (Figure 51)
7. Install the remaining power cord lead on the center terminal of the second fuse holder. (Figure 51)
8. Connect BK-10 wire from the side terminal of one fuse holder to the Line terminal on the electronic board. (Figure 50)
9. Connect RD-10 wire from the side terminal of the other fuse holder to the common (C) terminal on the capacitor. (Figure 51)
10. Tilt control panel back to original location, being careful
not to pinch any wires. Align the control panel with the cover and screw panels into place with original screws. Replace escutcheon and control knobs.
Fuse Holder Kit Installation (With Subbase)
See previous section for installation in the control panel.
1. Remove both knockouts at the fuse holder location. (Figure 52)
2. Install the fuse holders using screws provided. The side connector tab on the fuse holders should be towards the left.
3. Connect a stripped BK-9 wire to the center of the quick­connect tab of the fuse holders. Wire nut the other end of this wire to the black field connection wire (TB1). (Figure 53)
4. Connect the other stripped BK-9 wire to the quick-connect tab on the side of the same fuse holder. Wire nut the other end to black subbase wire leading to receptacle. (Figure 53)
5. Connect the stripped RD-9 wire to the center quick-connect tab of the second fuse holder. Wire nut the other end to the red field connection wire (TB3). (Figure 53)
6. Connect the other stripped RD-9 wire to the quick-connect tab on the side of the second fuse holder. Wire nut other end to red subbase wire which leads to receptacle. (Figure 53)
7. Insert time delay fuses into the fuse holders. Size all fuses by the Maximum Overcurrent Protection shown on the nameplate. Also refer to the serial plate on the unit.
Figure 51 - Fuse Holder Diagram
Control Panel Installation
Figure 52 - Subbase (Left Side)
Figure 53 - Fuse Holder Diagram Subbase Installation
FUSEHOLDERS
WH
GN
BK
Terminal Blocks Behind
the Control Panel
Transformer
Status Light
Control Board
Fuse Holder
Knockouts
Leveling
Leg
Power Switch
Knockouts
Electrical
Receptacle
Fuseholder
Fuseholder
BK-9
RD-9
Field Connection
Wiring
Green
Black
Red
Page 41
—41—
Remote Escutcheon Kit
Part No: AYRE110
Description
This kit provides an attractive replacement escutcheon (see Figure 54). The kit allows the removal of control knobs and graphics, which are not required when a wall thermostat is used to control the unit.
Receiving
Upon receipt of the product, inspect the shipping carton for signs of visible damage. Report any damage or shortage to the carrier and note it on the delivery receipt. The unit must be stored in its original shipping carton in a dry, secure place prior to its installation and use.
Installation
The installation and servicing of the equipment referred to in this booklet should be performed by qualified, experienced technicians.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Important Note:
The unit OFF switch does not disconnect all electrical power to this unit.
1. Grasp the cabinet front as shown in Figure 55.
2. Pull the bottom of the cabinet front away from the chassis until the retaining clips disengage as in Figure 56.
3. Lift the cabinet front off the chassis.
4. Lifting the front edge of the escutcheon, slide the tabs at the top of the escutcheon out of the retaining holes and remove the escutcheon. See Figure 57.
TEMP/TIME
MODE
HEATHEAT
E/SAVEE/SAVE
FANFAN
COOLCOOL
HIGHHIGH
LOWLOW TIMERTIMER
FAN T IMER
'
F
ON
OFFONOFF
F1 LOW F2 HIGH
Figure 51Standard Escutcheon
Figure 55
Figure 56
Page 42
—42—
5. Replace the escutcheon with the one from this kit by inserting the tabs at the top of the escutcheon into the retaining holes and laying the escutcheon flat on the control panel.
6. Replace the front by reversing steps 1 through 4.
7. Store the control knobs and escutcheon just removed from the unit for possible reinstallation if the wall thermostat is no longer desired.
Subbase
Part No: AYSB3101 (265V 20A)
AYSB4101 (265V 30A)
Description
The subbase may be installed on the wall sleeve before or after installing the wall sleeve. The subbase is prewired. Electrical connections can be made on the left side after the access cover is removed. A grounding screw is provided.
Receiving
Upon receipt of the product, inspect the shipping carton for signs of visible damage. Report any damage or shortage to the carrier and note it on the delivery receipt. The unit must be stored in its original shipping carton in a dry, secure place prior to its installation and use.
Installation
The installation and servicing of the equipment referred to in this booklet should be performed by qualified, experienced technicians.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Important Note:
The unit OFF switch does not disconnect all electrical power to this unit.
CAUTION Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
Note:
When using a subbase, the wall sleeve must be installed a minimum of 3-1/4 inches (83 mm) above a finished floor and a minimum of 2-3/
4 inches (70 mm) from a finished wall.
1. Remove parts B and C (Figure 58, next page) from the subbase and join together using two metal screws provided. This assembly now becomes the right front cover (Part F) of the subbase. (Figure 58, next page)
2. Position subbase under the front of the wall sleeve.
3. Align the back edge of the flange on cover A (Figure 54, next page) to front of the wall sleeve flange. (Figure 60, next page)
4. Drill four 1/8 inch holes in wall sleeve to line up with holes in subbase. (Figure 58, Location D, next page) Mount subbase to wall sleeve with four sheet metal screws provided with kit. (Figure 58, Location D, next page)
5. Remove the left front cover from the subbase. (Figure 58, Part A, next page)
6. Position skirting on each side of wall sleeve to prevent the entry of foreign materials. Trim skirting to desired length. Attach skirting with four sheet metal screws provided with kit. (Figure 58, Location E, next page)
7. Wire subbase for appropriate voltage (Figure 61, next page).
Escutcheon
Figure 57
Page 43
—43—
Note:
The proper subbase must be ordered to obtain the correct electrical receptacle. (Figure 62)
8. After wiring is complete, mount covers A and F to the subbase with provided screws. (Figure 59)
9. When installing optional accessories to the subbase, refer to each installation instruction for that accessory.
Figure 58
Figure 59 - Part/Location Identification
Figure 60 - Dimensions
Figure 61 - Wiring Diagram
Figure 61 - NEMA Plug Configurations
Wall Sleeve (Outdoor Side)
13 3/4"
16"
16"
2 5/8"
Left End View
2 3/4"
2 3/4"
Wall Sleeve Inside Edge
Back of Flange "A"
Part/Location Identification
A
Left Front Cover
B
Right Front Cover
C
Front Cord Panel
D
Wall Sleeve Hole Location
E
Skirting Hole Location
F
Right Cover Assembly
Wall Sleeve
D
Concentric
2" (50 mm)
Ground Screw Location
13-7/8" (352 mm)
1-3/8" (35 mm)
Knockouts In Bottom
3-1/16"
(78 mm)
Concentric Knockouts In Rear
Front View
NEMA 7-20R Receptacle
Field Wiring
NEMA 7-30R Receptacle
265 VAC Field Schematic
Line Voltage
4" (101 mm)
Top View
Receptacle Provided Inside subbase Accessory
20-5/16" (515.5 mm)
2-5/8" (67 mm)
2" (50 mm) Max. Adjustment
Cover Wiring Access
E
A
B
Subbase Box Assy
F
C
Low Voltage Compartment
D
E
11-13/16"
2-13/16" (71 mm)
(300 mm)
Voltage Subbase ReceptacleUnit Plug
Page 44
5. PERFORMANCE DATA
—44—
Voltage (V) 1 / 265 / 60 1 / 265 / 60 1 / 265 / 60 1 / 265 / 60 1 / 265 / 60 1 / 265 / 60 1 / 265 / 60 1 / 265 / 60 Cooling Data Cooling Capacity (Btu/h) 7600 8900 11800 14000 7300 14400 9300 12000 Cooling Amps (A) 2.6 3.21 4.4 5.8 2.5/2.2 6.2/5.3 3.3 3.9 Cooling Power (W) 650 810 1105 1475 630/550 1565/1335 830 1155 EER (Btu/h.Watt) 11.7 11 10.7 9.5 11.6 9.2 11.2 10.4 Moisture Removal (Pts/h) 2 2.6 3.3 4.4 2 4.4 2.6 3.3 Heat Pump Heating Data Heating Capacity (Btu/h) - - - - 6200 13200 8000 10800 Heating Amps (A) 2.6 3.21 4.4 5.8 2.5/2.2 6.2/5.3 2.7 3.9 Heating Power (W) 650 810 1105 1475 630/550 1565/1335 690 990 COP (W/W) - - - - 3.3 2.9 3.4 3.2 Airflow Indoor CFM (Wet)@0.3ESP(Hi) 300 300 420 420 300 420 300 420 Indoor CFM (Wet)@0.3ESP(Lo) 255 255 355 355 255 355 255 355 Indoor CFM (Dry)@0.3ESP(Hi) 320 320 450 450 320 450 320 450 Indoor CFM (Dry)@0.3ESP(Lo) 275 275 385 385 275 385 275 385
LP070CED1 LP090CED1 LP120CED1 LP150CED1 LP070HED1 LP150HED1 LP090HED1 LP120HED1
Air conditioner and Heat Pump Performance Data
Heater Size(kw) 2.0 2.0 3.7 3.7 3.7 3.7 3.7 3.7 Btu/Hr 6800 6800 11900 11900 11900 11900 11900 11900 Heating Watt 2040 2040 3740 3740 3740 3740 3740 3740 Heating Amps 7.6 7.6 14.0 14.0 14.0 14.0 14.0 14.0
LP070CED1 LP070HED1 LP090CED1 LP090HED1 LP120CED1 LP120HED1 LP150CED1 LP150HED1
Electric Heat Data
Page 45
Min Max Min Max Min Max Min Max Min Max Min Max Min Max Min Max
LP070CED1 LP090CED1 LP120CED1 LP150CED1 LP070HED1 LP090HED1 LP120HED1 LP150HED1
—45—
Rating wattage
80
100 70
60 80
90 70
60 80
80 70
60
620 680 780 840 1065 1145 1435 1515 600 660 800 860 1115 1195 1525 1605 630 690 790 850 1075 1155 1445 1525 610 670 810 870 1125 1205 1535 1615 630 690 790 850 1075 1155 1445 1525 610 665 810 870 1125 1205 1535 1615 625 685 785 845 1070 1150 1440 1520 605 660 805 865 1120 1200 1530 1610 615 675 775 835 1060 1140 1430 1510 595 655 795 855 1110 1190 1520 1600 615 675 775 835 1060 1140 1430 1510 595 655 795 855 1110 1190 1520 1600 610 670 770 830 1055 1135 1425 1505 590 650 790 850 1105 1185 1515 1595 605 665 765 825 1050 1130 1420 1500 585 645 785 845 1100 1180 1510 1590 605 665 765 825 1050 1130 1420 1500 585 645 785 845 1100 1180 1510 1590 600 660 760 820 1045 1125 1415 1495 580 640 780 840 1095 1175 1505 1585
Model Temperature
Return AirOutdoor Air
Dry Bulb Wet Bulb
Total Wattage Input Total Wattage Input Total Wattage Input Total Wattage Input Total Wattage Input Total Wattage Input Total Wattage Input Total Wattage Input
Cooling Wattage-Air conditioners and Heat Pumps
Page 46
Model
—46—
Cooling Change of Temperature-Air conditioners and Heat Pumps
Min Max Min Max Min Max Min Max Min Max Min Max Min Max Min Max
LP070CED1 LP090CED1 LP120CED1 LP150CED1 LP070HED1 LP090HED1 LP120HED1 LP150HED1
Rating Btu/h Rating CFM
90
85 80 75 70
80
75 70 65 60
70
65 60 55
7450 7750 8750 9050 11650 11950 13850 14150 7150 7450 9150 9450 11850 12150 14250 14550
185 225 230 260 300 330 315 355 185 225 230 260 300 330 315 355
1326151413261514
8 13 11 14 9 13 8 12 8 13 11 14 9 13 8 12 19 22 19 22 18 22 16 20 19 22 19 22 18 22 16 20 30 33 28 30 26 30 25 27 30 33 28 30 26 30 25 27
9 14 11 14 9 13 8 12 9 14 11 14 9 13 8 12 18 21 18 20 15 20 15 18 18 21 18 20 15 20 15 18 26 29 24 27 23 26 21 24 26 29 24 27 23 26 21 24 35 36 32 33 29 33 29 30 35 36 32 33 29 33 29 30 12 15 12 14 9 13 9 13 12 15 12 14 9 13 9 13 17 20 16 18 13 17 13 17 17 20 16 18 13 17 13 17 22 24 20 22 18 21 17 21 22 24 20 22 18 21 17 21
WetDry
Room AirRoom Air
Bulb
Bulb
Temperature Across Temperature Across Temperature Across Temperature Across Temperature Across Temperature Across Temperature Across Temperature Across
Indoor Coil (
T) Indoor Coil ( T) Indoor Coil ( T) Indoor Coil ( T) Indoor Coil ( T) Indoor Coil ( T) Indoor Coil ( T) Indoor Coil ( T)
Page 47
—47—
Rating ampere 2.4 2.4 3.2 3.2 4.2 4.2 5.7 5.7 2.4 2.4 3.2 3.2 4.2 4.2 5.7 5.7
100 2.4 2.6 2.9 3.1 3.9 4.3 5.6 6.2 2.5 2.7 3 3.2 4.1 4.5 5.5 6.1
95 2.3 2.5 2.7 3 3.7 4.1 5.3 5.9 2.4 2.6 2.8 3.1 3.9 4.3 5.2 5.8 90 2.2 2.4 2.6 2.9 3.6 3.9 5.1 5.6 2.2 2.5 2.7 3 3.7 4.1 5 5.5 85 2.1 2.3 2.5 2.7 3.4 3.8 4.8 5.3 2.1 2.3 2.6 2.9 3.5 3.9 4.7 5.2 80 2 2.2 2.3 2.6 3.2 3.6 4.6 5.1 2.1 2.2 2.5 2.7 3.3 3.7 4.5 4.9
LP070CED1 LP090CED1 LP120CED1 LP150CED1 LP070HED1 LP090HED1 LP120HED1 LP150HED1
Amperage Amperage Amperage Amperage Amperage Amperage Amperage Amperage
Cond Inlet Air Temperature
Model Model Model Model Model Model Model Model
Min Max Min Max Min Max Min Max Min Max Min Max Min Max Min Max
Heating Change of Temperature - Heat Pumps
Cooling Ampere Chart - Air conditioners and Heat Pumps
Model
Min Max Min Max Min Max Min Max
LP070HED1 LP090HED1 LP120HED1 LP150HED1
Rating Btu/h Rating CFM
50
85 75 65
45
85 75 65
40
85 75 65
6100 6300 7900 8100 10700 10900 13100 13300
220 250 260 290 330 360 350 390
22 24 24 27 27 30 28 30 24 25 26 29 29 32 30 31 26 27 28 30 31 34 32 33 19 22 22 24 24 29 27 30 21 24 24 26 26 30 29 31 23 25 25 28 28 32 31 33 17 20 20 22 23 27 27 30 19 22 22 24 24 29 29 31 21 24 24 25 26 30 31 33
WetDry
Room AirRoom Air
Bulb
Bulb
Temperature Across Temperature Across Temperature Across Temperature Across
Indoor Coil (
T) Indoor Coil ( T) Indoor Coil ( T) Indoor Coil ( T)
Page 48
—48—
Heating Wattage - Heat Pumps Temperature
Min Max Min Max Min Max Min Max
LP070HED1 LP090HED1 LP120HED1 LP150HED1
Total Wattage
Input
Total Wattage
Input
Total Wattage
Input
Total Wattage
Input
Rating wattage
585
80
50 75
70 65 85 80
45 75
70 65 85 80
40 75
70 65 85 80
35 75
70 65
540 560 680 700 975 1005 1320 1350 600 640 755 800 1065 1155 1405 1550 585 620 735 785 1045 1135 1385 1525 570 610 720 770 1025 1115 1355 1500 545 595 705 750 1005 1090 1335 1475 530 580 685 730 980 1065 1310 1450 585 620 720 770 1035 1120 1360 1490 570 610 705 750 1010 1100 1335 1470 550 590 695 730 990 1090 1310 1445 535 575 675 710 965 1060 1280 1420 520 560 655 690 945 1040 1265 1395 565 600 690 735 985 1080 1305 1435 550 590 670 720 975 1060 1280 1415 535 575 650 700 955 1040 1255 1385 520 555 640 685 930 1020 1230 1365 500 540 620 660 910 995 1210 1335 565 585 660 705 970 1050 1250 1385 550 570 640 690 945 1025 1230 1355 540 555 620 675 925 1005 1200 1325 520 540 610 660 900 980 1180 1295 505 520 590 640 885 960 1150 1260
Outside Air
Dry Bulb
Room Air
Dry Bulb
Page 49
—49—
Voltage Amps Watts Btu/h COP CFM(Dry) Heating Btu/h Outdoor Ambient 62
57 52
Rating Point 47
42 37 32 27 24
Watts
Outdoor Ambient
62 57 52
Rating Point 47
42 37 32 27 24
265 265 265 265
2.2 2.7 3.9 5.3
550 690 990 1335
6200 8000 10800 13200
3.3 3.4 3.2 2.9
300 300 420 420
7200 9700 13100 15700 6900 9200 12400 14900 6500 8600 11600 14100 6200 8000 10800 13200 5900 7500 10100 12400 5600 7000 9300 11600 5300 6500 8500 10800 5000 6000 7800 10000 4800 5700 7400 9500
580 745 1085 1425 575 735 1055 1405 555 715 1025 1370 550 690 990 1335 540 670 955 1300 525 650 925 1265 515 635 875 1220 510 605 835 1180 505 590 810 1170
Model LP070HED1 LP090HED1 LP120HED1 LP150HED1
Heat Pump Reverse Cycle Heating Capacity
Page 50
—50—
6. TROUBLESHOOTING GUIDE
6.1 OUTSIDE DIMENSIONS
1,066mm (42")
505mm (20")
406mm (16")
406mm (16")
6.2 PIPING SYSTEM
Following is a brief description of the important components and their functions in the refrigeration system. Refer to Figure 63 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle.
MOTOR
COMPRESSOR
OIL
(LIQUID REFRIGERANT)
CAPILLARY TUBE
OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH
SUCTION LIME COOL LOW PRESSURE VAPOR
COOLED AIR
COMPLETE LIQUID BOIL OFF POINT
LIQUID PRESSURE DROP
ROOM AIR HEAT LOAD
VAPOR INLET
HOT DISCHARGED AIR
LIQUID OUTLET
HIGH PRESSURE VAPOR LIQUID PEFRIGERANT LOW PRESSURE VAPOR
ROOM AIR CONDITIONER
EVAPORATOR COILS CONDENSER COILS
CYCLE OF REFRIGERATION
Figure 63
Page 51
—51—
6.3 TROUBLESHOOTING GUIDE
In general, possible trouble is classified in two causes. The one is Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit is running but cooling is ineffective
Ineffective Cooling
Check of outdoor coil (heat exchanger) & the fan operation.
Check gas leakage.
Repair gas leak.
Replacement of unit if the unit is beyond repair.
Satisfactory operation with temperature difference of inlet & outlet air 44.6~50˚ F (7~10˚ C)
Check heat load increase.
Unexpected residue
Overloaded Circuit
Check of inside gas pressure.
Adjusting of refrigerant charge
Malfunction of compressor
Replacement of compressor
Check of cold air circulation for smooth flow.
Dirty indoor coil (Heat exchanger)
Malfunction of fan
Clogged of air filter
Obstruction at air outlet
Correct above trouble
Check clogging in refrigeration circuit.
Repair clogging in refrigeration circuit.
Page 52
—52—
Fails to Start
Check circuit breaker and fuse.
Gas leakage of feeler bulb of thermostat
Check control switch.
Only fan fails to start.
Improper wiring.
Defect of fan motor capacitor.
Irregular motor resistance ( ). Irregular motor insulation ( ).
Replacement of fan motor
Regular but fails to start
Replacement of compressor (locking of rotor, metal)
Improper thermostat setting
Loose terminal connection.
Improper wiring
Irregular motor resistance ( )
Irregular motor insulation ( )
Replacement of compressor (Motor damaged)
Drop of power voltage.
Check capacitor.
Replacement.
Only compressor fails to start.
Defect of compressor capacitor.
Check power source.
Check control switch setting.
Page 53
—53——53—
COMPLAINT CAUSE REMEDY
Check voltage at outlet. Correct if none. Check voltage to rotary switch. If none, check
power supply cord. Replace cord if circuit is open. Check switch continuity. Refer to wiring diagram
for terminal identification. Replace switch if defective.
Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal.
Test capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged.
Fan blade hitting shroud or cross flow fan hitting scroll. Realign assembly.
Units using slinger ring condenser fans must have 1/4to 5/16inch clearance to the base. If it is hitting the base, shim up the bottom of the fan motor with mounting screw(s).
Check fan motor bearings; if motor shaft will not rotate, replace the motor.
Check voltage. See limits on this page. If not within limits, call an electrician.
Test capacitor. Check bearings. Does the fan blade rotate freely? If not, replace fan motor.
Pay attention to any change from high speed to low speed. If the speed does not change, replace the motor.
Check grommets; if worn or missing, replace them. If cracked, out of balance, or partially missing,
replace it. If cracked, out of balance, or partially missing,
replace it. Tighten it. If knocking sounds continue when running or
loose, replace the motor. If the motor hums or noise appears to be internal while running, replace motor.
No power Power supply cord
Rotary switch
Wire disconnected or connection loose
Capacitor (Discharge capacitor before testing.)
Will not rotate
Revolves on overload.
Grommets Fan
Turbo fan
Loose set screw Worn bearings
Fan motor will not run.
Fan motor runs intermittently
Fan motor noise.
Page 54
—54—
NAME PLATE RATING MINIMUM MAXIMUM
265V 239V 292V
COMPLAINT CAUSE REMEDY
Check voltage. See the limits on the preceding. page. If not within limits, call an electrician.
Check the wire connections, if loose, repair or replace the terminal. If wires are off, refer to wiring diagram for identification, and replace. Check wire locations. If not per wiring diagram, correct.
Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if circuit is open.
Check the position of knob If not at the coldest setting, advance the knob to this setting and restart unit. Check continuity of the thermostat. Replace thermostat if circuit is open.
Check the capacitor. Replace if not within ±10% of manufacturers rating. Replace if shorted, open, or damaged.
Check the compressor for open circuit or ground. If open or grounded, replace the compressor.
Check the compressor overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool it, and retest.)
Voltage
Wiring
Rotary
Thermostat
Capacitor (Discharge capacitor before servicing.)
Compressor
Overload
Compressor will not run, but fan motor runs.
ROOM AIR CONDITIONER VOLTAGE LIMITS
Page 55
—55—
COMPLAINT CAUSE
REMEDY
Check the voltage. See the limits on the preced­ing page. If not within limits, call an electrician.
Check overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)
If not running, determine the cause. Replace if required.
Remove the cabinet. inspect the interior surface of the condenser; if restricted, clean carefully with a vacuum cleaner (do not damage fins) or brush. Clean the interior base before reassembling.
If condenser fins are closed over a large area on the coil surface, head pressures will increase, causing the compressor to cycle. Straighten the fins or replace the coil. Test capacitor. Check the terminals. If loose, repair or replace. Check the system for restriction. If restricted, clean of replace. Close if open. Determine if the unit is properly sized for the area to be cooled. Check the set screw or clamp. If loose or missing, correct. If the blower or fan is hitting air guide, rearrange the air handling parts. Carefully rearrange tubing not to contact, compressor, shroud, and barrier.
Voltage
Overload
Fan motor
Condenser air flow restriction
Condenser fins (damaged)
Capacitor Wiring Refrigerating system Air filter Exhaust damper door Unit undersized
Cross flow fan
Copper tubing
Compressor cycles on overload.
Insufficient cooling or heating
Excessive noise.
Page 56
—56—
7. SCHEMATIC DIAGRAM
OUTDOOR FAN MOTOR
COMP
INDOOR FAN MOTOR
R
GN/YL
OR(BR)
OLP
NEUTRAL
BK1
RD BL RD BL
CAPACITOR
TB1
WH
FAN
BK2 BK3 BK4
BK BK
"A"
BK
BK BL RD
OR(BR) YL
YL
F
HERM
BK
BK
RD
RD
BL
BL
"B"
BK
BL
BL
RD
RD
OR
OR
BR
BR
YL
YL
LIVE
BK
WH
GN/YL
OR
OR
TB2
OR
BK
INDOOR COIL THERMISTOR
INDOOR AIR
THERMISTOR
THERMISTOR
INDOOR COIL
THERMISTOR
INDOOR AIR
In part "A", there are 3 types.
Type.1
OUTDOOR FAN MOTOR
Type.2
OUTDOOR FAN MOTOR
Type.3
OUTDOOR FAN MOTOR
OR(BR)
OR(BR)
OR(BR)
BK
BK BL RD
OR(BR) YL
YL
BK
BL
BL RD
OR(BR) YL
YL
BK BL RD
RD OR(BR) YL
YL
In part "B", there are 2 types.
Type.1
BK BL
INDOOR FAN MOTOR
GN/YL
Type.2
INDOOR FAN MOTOR
GN/YL
BL
RD
RD
OR
OR
BR
BR
YL
YL
BK
BK BL RD
RD OR
OR BR
BR YL
YL
CN-IDAT
CN-IDPT
CN-AUX_S
CN-THERMO_S
CN-LINK
CN-ODT
CN-DISP1
CN-IDF
CN-DISP2
CN-4WAY
P/NO:3850A20594H
CN-ODF
CN-ICR
Page 57
—57—
8.1 EXPLODED VIEW(ELECTRICAL COOLING)
C
D
F
E
B
552111
35211A
147911
346810
152302-1
359011
753000
W50400
152302
135312
135800
330870
354210
349600
546810
559011
549990
130411
554170
554030
135515
337000
349600-1
552114
552113
135500
567502
550140
A
237200
W0CZZ-2
W0CZZ
W6640
238310
268711-2
249951
135511
147910
TEMP/TIME
MODE
H E
A T
H E
A T
E /SA
V
E
E /SA
V
E
FANFA
N
C
O O
L
C
O O
L
H
IG
H
H
IG
H
L
O W
L
O W
T IM
E R
T IM
E R
FAN
TIM
ER
'
F
ON OFFONOFF
ON
O
FF
ON
O
FF
268711-1
249941-1
249941-2
268711-4
264110
148000
352390
149400
263230-2
263230-1
435300-1
435300
Page 58
58
8.2 EXPLODED VIEW(ELECTRICAL HEATING)
C
D
F
E
B
352115
552116
352116
147911
346810
152302-1
359011
753000
W50400
152302
135312
135800
330870
354210
349600
546810
559011
549990
130411
554170
554030
135515
337000
349600-1
552112
552113
135500
567502
550140
A
237200
W0CZZ-2
W0CZZ
W6640
238310
268711-2
249951
135511
147910
TEMP/TIME
MODE
H E
A T
H E
A T
E /SA
V
E
E /SA
V
E
FANFA
N
C
O O
L
C
O O
L
H
IG
H
H
IG
H
L
O W
L
O W
T IM
E R
T IM
E R
FAN
TIM
ER
'
F
ON OFFONOFF
ON
O
FF
ON
O
FF
268711-1
249941-1
249941-2
268711-4
264110
552206
148000
352390
149400
263230-2
263230-1
435300-1
435300
Page 59
P/No.: 3828A20308K
February, 2007
Printed in Korea
Loading...