The instructions below must be followed to prevent product malfunction, property damage, injury or death to the user or other people. Incorrect operation due to ignoring any instructions will cause harm or damage. The level of seriousness is classified by the symbols below.
TABLE OF SYMBOLS
This symbol indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
This symbol indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
This symbol indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury.
Note:
This symbol Indicates situations that may result in equipment or property damage accidents only.
This symbol indicates an action that should not be performed.
INSTALLATION
Don’t use or store ammable gas or combustibles near the unit.
There is risk of re, explosion, and physical injury or death.
Do not install, remove, or re-install the unit by yourself
(end-user). Ask the dealer or an an LG trained service
provider to install the unit.
Improper installation by the user may result in water leakage, re,
explosion, electric shock, physical injury or death.
Multi V Ducted Indoor Units
For replacement of an installed unit, always contact an
LG trained service provider.
There is risk of re, electric shock, explosion, and physical injury or death.
The outdoor unit is shipped with refrigerant and the service
valves closed. Do not open service valves on the unit until
all non-condensibles have been removed from the piping
system and authorization has been obtained from the commissioning agent.
There is a risk of physical injury or death.
Do not run the compressor with the service valves
closed.
There is risk of explosion, physical injury, or death.
Periodically check that the outdoor unit is not damaged.
There is risk of explosion, physical injury, or death.
Replace all control box and panel covers.
If cover panels are not installed securely, dust, water and animals may
enter the unit, causing re, electric shock, and physical injury or death.
Always check for system refrigerant leaks after the unit has
been installed or serviced.
Exposure to high concentration levels of refrigerant gas may lead to
illness or death.
4
Due to our policy of continuous product innovation, some specifications may change without notification.
Do not install the unit using defective hanging, attaching,
or mounting hardware.
There is risk of physical injury or death.
Wear protective gloves when handling equipment.
Sharp edges may cause personal injury.
Dispose of the packing materials safely.
• Packing materials, such as nails and other metal or wooden parts
may cause puncture wounds or other injuries.
• Tear apart and throw away plastic packaging bags so that children
may not play with them and risk suffocation and death.
Do not install the unit in any location exposed to open
ame or extreme heat. Do not touch the unit with wet hands.
There is risk of re, electric shock, explosion, and physical injury or death.
Install the unit considering the potential for earthquakes.
Improper installation may cause the unit to fall, resulting in physical
injury or death.
Do not change the settings of the protection devices.
If the pressure switch, thermal switch, or other protection device is
shorted and forced to operate improperly, or parts other than those
specied by LG are used, there is risk of re, electric shock, explosion,
and physical injury or death.
If the air conditioner is installed in a small space, take measures to prevent the refrigerant concentration from exceeding safety limits in the event of a refrigerant leak.
Consult the latest edition of ASHRAE (American Society of Heating,
Refrigerating, and Air Conditioning Engineers) Standard 15. If the refrigerant leaks and safety limits are exceeded, it could result in personal
SAFETY INSTRUCTIONS
CAUTION
INSTALLATION – CONTINUED
injuries or death from oxygen depletion.
Be very careful when transporting the product.
• Do not attempt to carry the product without assistance.
• Some products use polypropylene bands for packaging. Do not use polypropylene bands to lift the unit.
• Suspend the unit from the base at specified positions.
• Support the unit at a minimum of four points to avoid slippage from rigging apparatus.
• Failure to follow these directions may result in minor or moderate physical injury.
Note:
Properly insulate all cold surfaces to prevent “sweating.”
Cold surfaces such as uninsulated pipe can generate condensate that
may drip and cause a slippery oor condition and/or water damage to
walls.
When installing the unit in a hospital, mechanical room, or
similar electromagnetic eld (EMF) sensitive environment,
provide sufcient protection against electrical noise.
Inverter equipment, power generators, high-frequency medical equipment, or radio communication equipment may cause the air conditioner to
operate improperly. The unit may also affect such equipment by creating
electrical noise that disturbs medical treatment or image broadcasting.
Do not use the product for special purposes such as preserving foods, works of art, wine coolers, or other precision
air conditioning applications. This equipment is designed to
provide comfort cooling and heating.
There is risk of property damage.
Do not make refrigerant substitutions. Use R410A only.
If a different refrigerant is used, or air mixes with original refrigerant, the
unit will malfunction and become damaged.
Do not install the unit in a noise sensitive area.
When connecting refrigerant tubing, remember to allow for
pipe expansion.
Improper piping may cause refrigerant leaks and system malfunction.
Take appropriate actions at the end of HVAC equipment life
to recover, recycle, reclaim or destroy R410A refrigerant according to applicable U.S. Environmental Protection Agency
(EPA) rules.
Periodically check that the outdoor unit is not damaged.
There is a risk of equipment damage.
Install the unit in a safe location where no one can step on or
fall onto it.
attaching, or mounting hardware.
Do not install the unit with defective hanging,
There is risk of unit and property damage.
Install the drain hose to ensure adequate drainage.
There is a risk of water leakage and property damage.
Don’t store or use ammable gas/combustibles near the
unit.
There is risk of product failure.
Always check for system refrigerant leaks after the unit has
been installed or serviced.
Low refrigerant levels may cause product failure
The unit is shipped with refrigerant and the service valves
closed.
non-condensibles have been removed from the piping system and authorization to do so has been obtained from the
com-missioning agent.
Do not open service valves on the unit until all
There is a risk of refrigerant contamination, refrigerant loss and equipment damage.
Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
High voltage electricity is required to operate this system.
Adhere to the National Electrical Codes and these
instructions when wiring.
Improper connections and inadequate grounding can cause accidental
injury or death.
Always ground the unit following local, state, and National
Electrical Codes.
The information contained in this manual is intended for use
by an industry-qualied, experienced, trained electrician
familiar with the U.S. National Electric Code (NEC) who is
equipped with the proper tools and test instruments.
Failure to carefully read and follow all instructions in this manual can
result in equipment malfunction, property damage, personal injury or
death.
Ensure the unit is connected to a dedicated power source
that provides adequate power.
If the power source capacity is inadequate or the electric work is not performed properly, it may result in re, electric shock, physical injury or death.
Note:
Do not cut, lengthen or shorten the communications and
power cable between any dry contact unit and its connected
Multi V Ducted Indoor Units
indoor unit. Do not install the unit in a location where the communications and power cable cannot be safely and easily connected between the two units. Do not allow strain on this cable.
Poor cable connections can cause equipment malfunction.
Turn the power off at the nearest disconnect before servicing
the equipment.
Electric shock can cause physical injury or death.
Properly size all circuit breakers or fuses.
There is risk of re, electric shock, explosion, physical injury or death.
Refer to local, state, and federal codes, and use power wires
of sufcient current capacity and rating.
Wires that are too small may generate heat and cause a re.
Secure all eld wiring connections with appropriate wire
strain relief.
Improperly securing wires will create undue stress on equipment power
lugs. Inadequate connections may generate heat, cause a re and
physical injury or death.
Properly tighten all power connections.
Loose wiring may overheat at connection points, causing a re, physical
injury or death.
6
Due to our policy of continuous product innovation, some specifications may change without notification.
Do not provide power to or operate the unit if it is ooded
or submerged.
There is risk of re, electric shock, physical injury or death.
Use a dedicated power source for this product.
There is risk of re, electric shock, physical injury or death.
Do not operate the disconnect switch with wet hands.
There is risk of re, electric shock, physical injury or death.
Do not allow water, dirt, or animals to enter the unit.
There is risk of unit failure, re, electric shock, physical injury or death.
Avoid excessive cooling and periodically perform ventilation
to the unit.
Inadequate ventilation is a health hazard.
Do not touch refrigerant piping during or after operation.
It can cause burns or frostbite.
Do not operate the unit with the panel(s) or protective
cover(s) removed; keep ngers and clothing away from
moving parts.
The rotating, hot, cold, and high-voltage parts of the unit can cause
physical injury or death.
Periodically check power cable and connection for damage.
Cable must be replaced by the manufacturer, its service agent, or similar
qualied persons in order to avoid physical injury and/or electric shock.
Securely attach the electrical cover to the unit.
Non-secured electrical covers can result in burns or electric shock due to
dust or water in the service panel.
Periodically verify the hanging bolts and other hardware
securing the unit have not deteriorated.
If the unit falls from its installed location, it can cause property damage,
product failure, physical injury or death.
If refrigerant gas leaks out, ventilate the area before operating the unit.
If the unit is mounted in an enclosed, low-lying, or poorly ventilated area
and the system develops a refrigerant leak, it may cause re, electric
shock, explosion, physical injury or death.
Do not open the inlet grille of the unit during operation.
Do not operate the unit with the panels or guards removed.
Do not insert hands or other objects through the inlet or
outlet when the unit is powered. Do not touch the electro-
static lter, if the unit includes one. The unit contains sharp,
rotating, hot, and high voltage parts that can cause personal
injury and/or electric shock.
Ensure no power is connected to the unit other than as
directed in this manual. Remove power from the unit before
removing or servicing the unit.
There is risk of unit failure, re, electric shock, physical injury or death.
Do not open the inlet grille of the unit during operation.
Do not operate the unit with the panels or guards removed.
Do not insert hands or other objects through the inlet or outlet with the unit is plugged in. Do not touch the electrostatic
lter, if the unit includes one.
The unit contains sharp, rotating, hot, and high voltage parts that can
cause personal injury and/or electric shock.
Installation Manual
To avoid physical injury, use caution when cleaning or
servicing the air conditioner.
Note:
Clean up the site after installation is nished, and check
that no metal scraps, screws, or bits of wiring have been left
inside or surrounding the unit.
Do not use this equipment in mission critical or specialpurpose applications such as preserving foods, works of art,
wine coolers or refrigeration. This equipment is designed to
provide comfort cooling and heating.
Provide power to the compressor crankcase heaters at least
six (6) hours before operation begins.
Starting operation with a cold compressor sump(s) may result in severe
bearing damage to the compressor(s). Keep the power switch on during
the operational season.
Due to our policy of continuous product innovation, some specifications may change without notification.
This manual describes how to install LG ducted indoor units (IDU)
for Multi V Variable Refrigerant Flow (VRF) heat pump and heat
recovery systems. Table 1 lists the available models. Refer to LG’s
Multi V Indoor Unit Engineering Manual for complete detailed
engineering data and selection procedures.
Safety
Safety of personnel is the primary concern during all procedures.
Read and understand the safety summary at the front of this manual.
Read and understand this installation procedure before beginning
installation. Use the appropriate tools and accessories during installation. Plan your work and do not work alone, if possible. Know how
to obtain emergency medical and fire fighting assistance.
Installation Personnel
This equipment is intended for installation by personnel trained
in the required construction, mechanical, electrical, and/or other
disciplines.
Applicable Codes
Personnel must be familiar with and follow the applicable national,
state, and/or local codes.
INTRODUCTION
Figure 1: High-Static Ducted, BG/BR/B8/BH Chassis
Figure 2: Built-In Ducted, B3/B4 Chassis
Installation Manual
Installation work must be performed by trained personnel and in accordance with national wiring standards and all local or other applicable
codes. Improper installation can result in re, electric shock, physical
injury, or death.
Note:
Please read all instructions before installing this product. Become familiar
with the unit, its components and connections, and the order of installation. Incorrect installation can degrade or prevent proper operation.
Required Tools (field provided)
• Level
• Screwdriver
• Electrical lineman pliers
• Electric drill
• Holesaw
• Drill
• Flaring tool set
• Tubing cutter
• Tube/pipe reamer
• Torque wrenches
• Allen wrench
• Gas-leak detector
• Thermometer
Required Parts (field provided)
• Pipes - vapor line and liquid line, with insulation
• 3/8” or 1/2” nuts, at washers, and lock/split washers
• 3/8” or 1/2” threaded hanger rods
• Insulated drain hose
• Additional drain hose
• Connecting cable (power and control)
Due to our policy of continuous product innovation, some specifications may change without notification.
R410A refrigerant has a higher operating pressure in comparison to R22 refrigerant and, therefore, all piping system materials
installed must have a higher resisting pressure than the materials traditionally used in R22 systems.
R410A refrigerant is an azeotrope of R32 and R125, mixed at 50:50, so the ozone depletion potential (ODP) is 0.
• Do not place the refrigerant cylinder in direct sunlight. Refrigerant cylinder may explode causing severe injury or death.
Note:
• Because R410A is a combination of R32 and R125, the required additional refrigerant must be charged in its liquid state. If the
refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• Do not heat piping more than necessary during installation. Piping may become soft and fail when pressurized.
• Do not use any piping that has not been approved for use in high-pressure refrigerant systems. Piping wall thickness must comply
with the applicable local, state, and federal codes for the 551 psi design pressure of R410A. Inadequate piping may fail when
pressurized.
Multi V Ducted Indoor Units
12
Due to our policy of continuous product innovation, some specifications may change without notification.
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and
must comply with applicable local and national codes. Ensure the communication cable
is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU communications cable at any other point.
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
codes. Power Supply (V/Hz/Ø): 208-230/60/1
Due to our policy of continuous product innovation, some specifications may change without notification.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and
67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
13
GENERAL DATA
Specications − High-Static BG Chassis
Table 3: High-Static BG Chassis IDU Specications
Model No.ARNU073BGA4ARNU093BGA4ARNU123BGA4ARNU153BGA4ARNU183BGA4
Cooling Mode Performance
Capacity (Btu/h)
Power Input1 (W)
Heating Mode Performance
Capacity (Btu/h)
Power Input1 (W)
Entering Mixed Air
Cooling Max. (°F WB)
Heating Min. (°F DB)
Unit Data
2
Refrigerant Type
Refrigerant Control
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cable4 (No. x AWG)
Fan
Type
Motor
Housing
Motor/Drive
Airflow Rate H/M/L (CFM)
Standard Mode
Multi V Ducted Indoor Units
Airflow Rate H/M/L (CFM)
High Mode (Factory Set)
External Static Pressure (in. wg)
Standard Mode
External Static Pressure (in. wg)
High Mode (Factory Set)
Piping
Liquid Line (in., O.D.)
Vapor Line (in., O.D.)
Condensate Line (in., I.D.)
1
Power Input is rated at high speed.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and
must comply with applicable local and national codes. Ensure the communication cable
is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU communications cable at any other point.
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and
67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
14
Due to our policy of continuous product innovation, some specifications may change without notification.
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and
must comply with applicable local and national codes. Ensure the communication cable
is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU communications cable at any other point.
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
codes. Power Supply (V/Hz/Ø): 208-230/60/1
3/8 Flare3/8 Flare3/8 Flare3/8 Flare
5/8 Flare5/8 Flare5/8 Flare5/8 Flare
1111
GENERAL DATA
Specications − High-Static BG Chassis
Installation Manual
Brushless Digitally Controlled / Direct
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and
67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Due to our policy of continuous product innovation, some specifications may change without notification.
Model No. ARNU283BRA4 ARNU363BRA4ARNU5423BRA4 ARNU483BRA4 ARNU543BRA4
Cooling Mode Performance
Capacity (Btu/h)
Power Input1 (W)
Heating Mode Performance
Capacity (Btu/h)
Power Input1 (W)
Entering Mixed Air
Cooling Max. (°F WB)
Heating Min. (°F DB)
Unit Data
2
Refrigerant Type
Refrigerant Control
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cable4 (No. x AWG)
Fan
Type
Motor
Housing
Motor/Drive
Airflow Rate H/M/L (CFM)
Standard Mode
Airflow Rate H/M/L (CFM)
Multi V Ducted Indoor Units
High Mode (Factory Set)
External Static Pressure (in. wg)
Standard Mode
External Static Pressure (in. wg)
High Mode (Factory Set)
Piping
Liquid Line (in., O.D.)
Vapor Line (in., O.D.)
Condensate Line (in., I.D.)
1
Power Input is rated at high speed.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and
must comply with applicable local and national codes. Ensure the communication cable
is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU communications cable at any other point.
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and
67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
16
Due to our policy of continuous product innovation, some specifications may change without notification.
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and
must comply with applicable local and national codes. Ensure the communication cable
is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU communications cable at any other point.
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
codes. Power Supply (V/Hz/Ø): 208-230/60/1
Due to our policy of continuous product innovation, some specifications may change without notification.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and
67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and
must comply with applicable local and national codes. Ensure the communication cable
is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU communications cable at any other point.
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
codes. Power Supply (V/Hz/Ø): 208-230/60/1
18
Due to our policy of continuous product innovation, some specifications may change without notification.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and
67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Model No.ARNU073L1G4 ARNU093L1G4 ARNU123L2G4 ARNU153L2G4 ARNU183L2G4 ARNU243L3G4
Cooling Mode Performance
Capacity (Btu/h)
Power Input1 (W)
Heating Mode Performance
Capacity (Btu/h)
Power Input1 (W)
Entering Mixed Air
Cooling Max. (°F WB)
Heating Min. (°F DB)
Unit Data
2
Refrigerant Type
Refrigerant Control
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cable4 (No. x AWG)
Fan
Type
Motor
Housing
Motor/Drive
Airflow Rate H/M/L (CFM)
Standard Mode
Airflow Rate H/M/L (CFM)
High Mode (Factory Set)
External Static Pressure (in. wg)
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and
must comply with applicable local and national codes. Ensure the communication cable
is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU communications cable at any other point.
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
codes. Power Supply (V/Hz/Ø): 208-230/60/1
Due to our policy of continuous product innovation, some specifications may change without notification.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and
67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
19
GENERAL DATA
Specications − Vertical Air Handler NJ Chassis
Table 8: Vertical Air Handler NJ Chassis IDU Specications
Model No.ARNU123NJA4ARNU183NJA4ARNU243NJA4ARNU303NJA4ARNU363NJA4
Cooling Mode Performance
Capacity (Btu/h)
Power Input1 (W)
Heating Mode Performance
Capacity (Btu/h)
Power Input1 (W)
Entering Mixed Air
Cooling Max. (°F WB)
Heating Min. (°F DB)
Unit Data
2
Refrigerant Type
Refrigerant Control
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cable4 (No. x AWG)
Fan
Type
Motor
Housing
Motor/Drive
Airflow Rate H/M/L (CFM)
Standard Mode
Airflow Rate H/M/L (CFM)
Multi V Ducted Indoor Units
High Mode (Factory Set)
External Static Pressure (in. wg)
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and
must comply with applicable local and national codes. Ensure the communication cable
is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU communications cable at any other point.
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
codes. Power Supply (V/Hz/Ø): 208-230/60/1
20
Due to our policy of continuous product innovation, some specifications may change without notification.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and
67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Model No.ARNU423NKA4ARNU483NKA4ARNU543NKA4
Cooling Mode Performance
Capacity (Btu/h)
Power Input1 (W)
Heating Mode Performance
Capacity (Btu/h)
Power Input1 (W)
Entering Mixed Air
Cooling Max. (°F WB)
Heating Min. (°F DB)
Unit Data
2
Refrigerant Type
Refrigerant Control
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cable4 (No. x AWG)
Fan
Type
Motor
Housing
Motor/Drive
Airflow Rate H/M/L (CFM)
Standard Mode
Airflow Rate H/M/L (CFM)
High Mode (Factory Set)
External Static Pressure (in. wg)
Standard Mode
External Static Pressure (in. wg)
High Mode (Factory Set)
Piping
Liquid Line (in., O.D.)
Vapor Line (in., O.D.)
Condensate Line (in., I.D.)
Specications − Vertical Air Handler NK Chassis
Table 9: Vertical Air Handler NK Chassis IDU Specications
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and
must comply with applicable local and national codes. Ensure the communication cable
is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU communications cable at any other point.
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
codes. Power Supply (V/Hz/Ø): 208-230/60/1
Due to our policy of continuous product innovation, some specifications may change without notification.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and
67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
21
GENERAL DATA
Electrical − High-Static BH/BG/BR/B8 Chassis
Table 10: High-Static BH/BG/BR/B8 Chassis Indoor Unit Electrical Data.
ModelVoltage RangeMCAMOPRated Amps (A)
Power SupplyPower Input (W)
HzVoltsPhaseCoolingHeating
BH Units
ARNU073BHA4
ARNU093BHA41.321.06150150
ARNU123BHA41.321.06150150
ARNU153BHA41.321.06150150
ARNU183BHA41.321.06150150
ARNU243BHA41.321.06150150
187-253
1.32
15
1.06
150150
60208-2301
BG Units
ARNU073BGA4
ARNU093BGA43.32.65450450
ARNU123BGA4
ARNU153BGA43.32.65450450
ARNU183BGA43.32.65450450
ARNU243BGA43.32.65450450
ARNU283BGA43.32.65450450
ARNU363BGA43.32.65450450
ARNU423BGA43.32.65450450
187-253
3.3
3.32.65450450
15
2.65
450450
60208-2301
BR Units
ARNU283BRA4
ARNU363BRA44.43.5450450
ARNU423BRA44.43.5450450
Multi V Ducted Indoor Units
ARNU483BRA44.43.5450450
ARNU543BRA44.43.5450450
187-253
4.4
15
3.5
450450
60208-2301
B8 Units
ARNU363B8A4
ARNU423B8A46.55.2800800
ARNU483B8A46.55.2800800
ARNU763B8A46.55.2800800
ARNU963B8A4
187-253
6.5
15
6.55.2800800
5.2
800800
60208-2301
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
22
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use circuit breaker.
Due to our policy of continuous product innovation, some specifications may change without notification.
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
187-253
1.2
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use circuit breaker.
15
0.97
60208-2301
115115
Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use circuit breaker.
Table 13: Vertical Air Handler NJ/NK Chassis Electrical Data.
ModelVoltage RangeMCAMOPRated Amps (A)
Multi V Ducted Indoor Units
NJ Units
ARNU123NJA4
ARNU183NJA41.41.12228228
ARNU243NJA41.41.12228228
ARNU303NJA41.41.12228228
ARNU363NJA41.41.12228228
208-230
1.4
1.12
15
Power SupplyPower Input (W)
HzVoltsPhaseCoolingHeating
228228
60208-2301
NK Units
ARNU423NKA4
ARNU483NKA42.31.8366366
ARNU543NKA42.31.8366366
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
208-230
2.3
15
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use circuit breaker.
1.8
366366
60208-2301
24
Due to our policy of continuous product innovation, some specifications may change without notification.