LG HSNC096QMA4 Owner’s Manual

TEST RUNNING
16
Settlement of outdoor unit
Anchor the outdoor unit with a bolt and nut(ø10mm) tightl
y and horizontally on a concrete or rigid mount.
e mounting base securely with a nail or wire
assumin
g the influence of wind and earthquake.
In the case when the vibration of the unit is conveye
d to the hose, secure the unit with an anti-
vibratio
n bushing.
1.
Check that all tubing and wiring have been properl
y connected.
2.
Check that the gas and liquid side service valves ar
e fully open.
Prepare remote control
Remove the battery cover by pulling it according to the
arro
w direction.
Inser
t new batteries making
sur
e that the (+) and (–) of
batter
y are installed correctly.
Reattac
h the cover by
pushin
g it back into position.
NOTE
:
•Use 2 AAA(1.5volt)batteries.Do not use rechargeabl
e batteries.
•Removethebatteriesfromtheremote control if thesystemis not goingto be used for a long time
.
Evaluation of the performance
Operate unit for 15~20 minutes, then check the system refrigerant charge:
1.
Measure the pressure of the gas side service valve
.
2.
Measure the temperature of the intake and discharg
e of air.
NOTE
: If the actual pressure is higher than shown, the
syste
m is most likely over-charged, and charge
shoul
d be removed. If the actual pressure are
lowe
r than shown, the system is most likely
undercharged
, and charge should be added.
The air conditioner is now ready for use.
A
C
B
g
R-22 35°C (95°F) 4~5kg/cm2G(56.8~71.0 P.S.I.G.)
R-410
A 35°C (95°F) 8.5~9.5kg/cm2G(120~135 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side
servic
e valve.
This is performed when the unit is to be relocated or the refrigerant circuit is serviced.
Pum
p Down means collecting all refrigerant in the
outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the coolin
g operation.
5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm
2
G(14.2 to 7.1 P.S.I.G.), fully close the
ga
s side valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been collected in th
e outdoor unit.
PUMP DOWN
3. Ensure the difference between the intake temperature an
d the discharge is more than 8°C(46°F) (Cooling) or
(Heating)
.
4. For reference; the gas side pressure of optimum conditio
n is as below.(Cooling)
Discharge temperature
Discharge air
Intake temperature
Bolt
WARNING: Outdoor unit is heavy weight Please use two person or more people to lift and transport the outdoor unit and Don’t install the outdoor unit at a place that concern of falling down ,Otherwise it may result in personal injury.
Tubin
connection
Loading...