Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national
wiring standards by authorized personnel only. Please retain this
installation manual for future reference after reading it thoroughly.
Original instruction
[EU Representative]
[
Manufacturer
MFL68026607
Rev.08_042221
LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V.
Krijgsman 1, 1186 DM Amstelveen, The Netherlands
] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si, Gyeongsangnam-do, KOREA
4PREFACE
5SAFETY INSTRUCTIONS
12 INSTALLATION PART
13 GENERAL INFORMATION
13Model Information
14Model name and related information
15Parts and Dimensions
18Control Parts
20Remote Controller
21Typical Installation Example
27Cycle Diagram
29Water cycle
31 INSTALLATION
31Transporting the Unit
32Installation places
33Seasonal Wind and Cautions in Winter
34Foundation for Installation
35Electrical Wiring
43Wiring of main power supply and equipment capacity
44Water Piping and Water Circuit Connection
46Water Charging
46Pipe Insulation
47Water pump Capacity
47Pressure Drop
48Performance curve
49Water Quality
49Frost protection
50Water Volume and Expansion Vessel Pressure
51 ACCESSORIES INSTALLATION
51Accessories supported by LG Electronics
52Accessories supported by 3rd party Companies
53Before Installation
53Thermostat
562nd Circuit
593rd Party Boiler
69DHW Tank Kit
70Solar Thermal Kit
71Dry Contact
73External Controller - Setting up programmable digital input operation
74Remote Temperature Sensor
76Solar pump
77External pump
78Wi-fi Modem
79Energy State
80Digital Input for energy saving (ESS, Smart Grid)
812Way Valve
823Way Valve(A)
833Way Valve(B)
84Electric Heater
88Final check
89 CONFIGURATION
89DIP Switch Setting
95 SERVICE SETTING
95How to enter service setting
95Service setting
96Service Contact
97Model Information
98RMC Version lnformation
99Open Source License
100 INSTALLER SETTING
100How to enter installer setting
101Installer setting
1033 Minutes Delay
104Select Temperature Sensor
105Dry Contact Mode
106Central Control Address
107Pump test run
108Air cooling set temp
109Water cooling set temp
110Air heating set temp
111Water heating set temp
112DHW set temp
113Screed drying
115Heater on temperature
117Water supply off temp. during cooling
119Tank disinfection setting 1, 2
120Tank setting 1
121Tank setting 2
123Heater priority
124DHW time setting
125TH on/off Variable, heating air
126TH on/off Variable, heating water
127TH on/off Variable, cooling air
128TH on/off Variable, cooling water
129Heating temp. setting
130Cooling temp. setting
131Pump setting in heating
132Pump setting. in cooling
133Forced operation
134CN_CC
135Pump Capacity
136Seasonal auto temp
138Modbus Address
139CN_EXT
140Anti-freezing Temperature
141Add Zone
142Use External Pump
1433rd Party Boiler
144Meter Interface
145Pump Prerun/Overrun
146Solar Thermal System
148Energy state
149Data logging
150Password Initialization
151Overview settings
153 COMMISSIONING
153Check List before Starting Operation
154Starting Operation
155Starting Operation flow chart
155Airborne Noise Emission
156Vacuum & Charge of Refrigerant
158How to drain remaining water in the product
159Troubleshooting
TABLE OF CONTENTS
3
ENGLISH
PREFACE
4
ENGLISH
PREFACE
This installation manual is to present information and guide about understanding, installing,
and checking .
Your careful reading before installation is highly appreciated to make no mistake and to prevent
potential risks. The manual is divided into nine chapters. These chapters are classified according
to installation procedure. See the table below to get summarized information.
ChaptersContents
Chapter 1
• Warning and Caution concerned with safety.
• This chapter is directly related with human safety. We strongly recommend reading
this chapter carefully.
Chapter 2
Chapter 3
Chapter 4
Chapter 5
Chapter 6
Chapter 7
Chapter 8
• Items Inside product Box
• Before starting installation, please make it sure that all parts are found inside the
product box.
• Fundamental knowledge about
• Model identification, accessories information, refrigerant and water cycle diagram,
parts and dimensions, electrical wiring diagrams, etc.
• This chapter is important to understand
• Installation about the unit.
• Installation location, constraints on installation site, etc
• Electrical wiring at the unit.
• System set-up and configuration.
• Information about water pump
• Information about supported accessories
• Specification, Constraints, and wiring are described.
• Before purchasing accessories, please find supported specification to buy proper
one.
• Information about DIP switch setting
• check and input service contact
• information about model and open source license
• Information on the installer setup mode that sets the detailed functions of the
remote control
• Incorrectly setting the installer setup mode may result in product failure, personal
injury, or property loss, so this chapter requires a deeper understanding
Chapter 9
• Check points before starting operation are explained.
• Troubleshooting, maintenance, and error code list are presented to correct
problems
SAFETY INSTRUCTIONS
SAFETY INSTRUCTIONS
5
ENGLISH
Read the precautions in
this manual carefully
before operating the
unit.
This symbol indicates
that the Operation
Manual should be read
carefully.
The following safety guidelines are intended to prevent
unforeseen risks or damage from unsafe or incorrect operation
of the appliance. The guidelines are separated into ‘WARNING’
and ‘CAUTION’ as described below.
This symbol is displayed to indicate matters and
!
operations that can cause risk. Read the part with this
symbol carefully and follow the instructions in order to
avoid risk.
WARNING
!
This indicates that the failure to follow the instructions can
cause serious injury or death.
This appliance is filled
with flammable
refrigerant (for R32)
This symbol indicates
that a service personnel
should be handling this
equipment with
reference to the
Installation Manual.
CAUTION
!
This indicates that the failure to follow the instructions can
cause the minor injury or damage to the product.
WARNING
!
Installation
• Do not use a defective or underrated circuit breaker. Use this
appliance on a dedicated circuit.
- There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified
electrician, or an Authorized Service Center.
- There is risk of fire or electric shock.
SAFETY INSTRUCTIONS
6
ENGLISH
• Always ground the unit.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric
shock
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not install, remove, or reinstall the unit by yourself
(customer).
- There is risk of fire, electric shock, explosion, or injury
• For antifreeze, always contact the dealer or an authorized
service center.
- Almost the antifreeze is a toxic product.
• For installation, always contact the dealer or an authorized
Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• Do not install the unit on a defective installation stand.
- It may cause injury, accident, or damage to the unit.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the unit could fall with it, causing
property damage, unit failure, and personal injury.
• Do not install the water pipe system as Open loop type.
- It may cause failure of unit.
• Use a vacuum pump or inert (nitrogen) gas when doing
leakage test or purging air. Do not compress air or oxygen and
do not use flammable gases.
- There is the risk of death, injury, fire or explosion.
• Make sure the connected condition of connector in product
after maintenance.
- Otherwise, it may cause product damage
• Do not touch leaked refrigerant directly.
- There is risk of frostbite.
SAFETY INSTRUCTIONS
• Compliance with national gas regulations shall be observed.
• Refrigerant tubing shall be protected or enclosed to avoid
damage.
• The installation of pipe-work shall be kept to a minimum.
• A brazed, welded, or mechanical connection shall be made
before opening the valves to permit refrigerant to flow
between the refrigerating system parts. A vacuum valve shall
be provided to evacuate the interconnecting pipe and/or any
uncharged refrigerating system part.
• Any person who is involved with working on or breaking into a
refrigerant circuit should hold a current valid certificate from an
industry-accredited assessment authority, which authorizes
their competence to handle refrigerants safely in accordance
with an industry recognized assessment specification.
• Pipe-work shall be protected from physical damage and shall
not be installed in an unventilated space, if that space is
smaller than
1) The minimum floor area : 49.4 m
2
2) The maximum refrigerant charge amount : 2.4 kg
• Do not use means to accelerate the defrosting process or to
clean, other than those recommended by the manufacturer.
• Do not pierce or burn.
• Be aware that refrigerants may not contain an odour.
• Dismantling the unit, treatment of the refrigerant oil and
eventual parts should be done in accordance with local and
national standards.
• Ducts connected to an appliance shall not contain an ignition
source.
• Copper in contact with refrigerants shall be oxygen-free or
deoxidized, for example Cu-DHP as specified in EN 12735-1
and EN 12735-2.
7
ENGLISH
Operation
• Take care to ensure that power cable could not be pulled out
or damaged during operation.
- There is risk of fire or electric shock.
SAFETY INSTRUCTIONS
8
ENGLISH
• Do not place anything on the power cable.
- There is risk of fire or electric shock.
• Do not plug or unplug the power supply plug during operation.
- There is risk of fire or electric shock.
• Do not touch (operate) the unit with wet hands.
- There is risk of fire or electric shock.
• Do not place a heater or other appliances near the power
cable.
- There is risk of fire or electric shock.
• Do not allow water to run into electric parts.
- There is risk of fire, failure of the unit, or electric shock.
• Do not store or use flammable gas or combustibles near the
unit.
- There is risk of fire or failure of unit.
• Do not use the unit in a tightly closed space for a long time.
- It may cause damage to the unit.
• When flammable gas leaks, turn off the gas and open a
window for ventilation before turning the unit on.
- There is risk of explosion or fire.
• If strange sounds or smell or smoke comes from unit, turn the
breaker off or disconnect the power supply cable.
- There is risk of electric shock or fire.
• Stop operation and close the window in storm or hurricane. If
possible, remove the unit from the window before the
hurricane arrives.
- There is risk of property damage, failure of unit, or electric
shock.
• Do not open the front cover of the unit while operation. (Do
not touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or unit failure.
• Do not touch any electric part with wet hands. you should be
power off before touching electric part.
- There is risk of electric shock or fire.
• Do not touch refrigerant pipe and water pipe or any internal
parts while the unit is operating or immediately after operation.
- There is risk of burns or frostbite, personal injury.
SAFETY INSTRUCTIONS
• If you touch the pipe or internal parts, you should be wear
protection or wait time to return to normal temperature.
- Otherwise , it may cause burns or frostbite, personal injury.
• Turn the main power on 6 hours ago before the product
starting operation.
- Otherwise, it may cause compressor damage.
• Do not touch electric parts for 10 minutes after main power
off.
- There is risk of physical injury, electric shock.
• The inside heater of product may operate during stop mode. It
is intended to protect the product.
• Be careful that some part of the control box are hot.
- There is risk of physical injury or burns.
• When the unit is soaked (flooded or submerged), contact an
Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious that water could not be poured to the unit directly.
- There is risk of fire, electric shock, or unit damage.
• Ventilate the unit from time to time when operating it together
with a stove, etc.
- There is risk of fire or electric shock.
• Turn the main power off when cleaning or maintaining the unit.
- There is risk of electric shock.
• Take care to ensure that nobody could step on or fall onto the
unit.
- This could result in personal injury and unit damage.
• For installation, always contact the dealer or an Authorized
Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• If the unit is not used for long time, we strongly recommend
not to switch off the power supply to the unit.
- There is risk of water freezing.
• The appliance shall be stored in a well-ventilated area where
the room size corresponds to the room area as specified for
operation.
9
ENGLISH
SAFETY INSTRUCTIONS
10
ENGLISH
•
The appliance shall be stored in a room without continuously
operating open flames (for example an operating gas appliance)
and ignition sources (for example an operating electric heater).
• The appliance shall be stored so as to prevent mechanical
damage from occurring.
•
Servicing shall only be performed as recommended by the equipment
manufacturer. Maintenance and repair requiring the assistance of
other skilled personnel shall be carried out under the supervision of
the person competent in the use of flammable refrigerants.
• When mechanical connectors are reused indoors, sealing parts
shall be renewed. When flared joints are reused indoors, the
flare part shall be re-fabricated.
• Be aware that refrigerants may not contain an odor.
• Periodic(more than once/year) cleaning of the dust or salt
particles stuck on the heat exchangers by using water.
• Keep any required ventilation openings clear of obstruction.
CAUTION
!
Installation
• Always check for gas (refrigerant) leakage after installation or
repair of unit.
- Low refrigerant levels may cause failure of unit.
• Keep level even when installing the unit.
- To avoid vibration or water leakage.
• Use two or more people to lift and transport the unit.
- Avoid personal injury.
• Do not install the unit in potentially explosive atmospheres.
• Connect the water for filling or refilling the heating system as
specified by EN 1717/EN 61770 to avoid contamination of
drinking water by return flow.
Operation
• Do not use the unit for special purposes, such as preserving
foods, works of art, etc.
- There is risk of damage or loss of property.
SAFETY INSTRUCTIONS
11
• Use a soft cloth to clean. Do not use harsh detergents,
solvents, etc.
- There is risk of fire, electric shock, or damage to the plastic
parts of the unit.
• Do not step on or put anything on the unit.
- There is risk of personal injury and failure of unit.
•
Use a firm stool or ladder when cleaning or maintaining the unit.
- Be careful and avoid personal injury.
•
Do not turn on the breaker or power under condition that front
panel cabinet, top cover, control box cover are removed or opened.
-
Otherwise it may cause fire, electric shock, explosion or death.
• The appliance shall be disconnected from its power source
during service and when replacing parts.
• Means for disconnection must be incorporated in the fixed
wiring in accordance with the wiring rules.
• The Installation kit supplied with the appliance are to be used
and that old Installation kit should not be reused.
•
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in order
to avoid a hazard. Installation work must be performed in accordance
with the national wiring standards by authorized personnel only.
• In order to avoid a hazard due to inadvertent resetting of the
thermal cut-out, this appliance must not be supplied through
an external switching device, such as a timer, or connected to
a circuit that is regularly switched on and off by the utility.
• This equipment shall be provided with a supply conductor
complying with the national regulation.
• The instructions for service to be done by specialized
personnel, mandated by the manufacturer or the authorized
representative may be supplied in only one Community
language which the specialized personnel understand.
•
This appliance is not intended for use by persons (including
children) with reduced physical, sensory or mental capabilities or
lack of experience and knowledge, unless they have been given
supervision or instruction concerning use of the appliance by a
person responsible for their safety. Children should be supervised
to ensure that they do not play with the appliance.
ENGLISH
INSTALLATION PART
12
ENGLISH
INSTALLATION PART
Thank you for choosing LG Electronics Air-to-Water Heat Pump
Before starting installation, please make it sure that all parts are found inside the product box.
ItemImage
Installation
Manual
Outdoor Unit
Chassis
UN36A
(Product heating capacity :
5, 7, 9 kW)
Outdoor Unit
UN60A Chassis
(Product heating capacity :
9, 12, 14, 16 kW)
Remote Controller
Remote Controller Cable
Damper
Drain Cap
Drain Nipple
GENERAL INFORMATION
GENERAL INFORMATION
With advanced inverter technology, is suitable for applications like under floor
heating, under floor cooling, and hot water generation. By Interfacing to various accessories user
can customize the range of the application.
In this chapter, general information of is presented to identify the installation
procedure. Before beginning installation, read this chapter carefully and find helpful information
on installation.
Model Information
Buyer Model Name
13
ENGLISH
H M 16 1 M U3 3
Series Number
Chassis Name
U3 : UN60A Chassis
U4 : UN36A Chassis
- Additional Information : serial number refers to the barcode on the product.
- Max allowable pressure
High side : 4.32 MPa / Low side : 2.4 MPa
GENERAL INFORMATION
14
ENGLISH
Model name and related information
Model NameCapacity (kW)
ChassisPhase(Ø)Capacity(kW)Heating
1)
Cooling
55.55.5
UN36A1
777
999
999
1
UN60A
121212
141414
161616
121212
3
141414
161616
1 : tested under EN14511
(water temperature 30 °C ’ 35 °C at outdoor ambient temperature 7 °C / 6 °C)
2 : tested under EN14511
(water temperature 23 °C ’ 18 °C at outdoor ambient temperature 35 °C / 24 °C)
h All appliances were tested at atmospheric pressure.
2)
Power Source
(Unit)
220-240 V~
50 Hz
380-415 V 3N~
50 Hz
Parts and Dimensions
GENERAL INFORMATION
15
ENGLISH
UN36A (5, 7, 9 kW)
4
5
10
3
4
5
9
6
7
2
8
1
h The shape may differ depending on the model.
Description
NoNameRemarks
1Entering water pipeMale PT 1 inch
2Leaving water pipeMale PT 1 inch
3StrainerFiltering and stacking particles inside circulating water
4Top cover-
5Control BoxPCB and terminal blocks
6Plate Heat ExchangerHeat exchanger between refrigerant and water
7Water PumpCirculating the water
8Pressure GageIndicates circulating water pressure
9Safety valveOpen at water pressure 3 bar
10compressor-
16
ENGLISH
GENERAL INFORMATION
UN60A (9, 12, 14, 16 kW)
3D View
Side View
h The shape may differ depending on the model.
GENERAL INFORMATION
NoNameRemarks
1Entering water pipeMale PT 1 inch
2Leaving water pipeMale PT 1 inch
3StrainerFiltering and stacking particles inside circulating water
4Top cover5Front Panel6Side Panel7Signal ANetwork Kit cables
8Signal BNetwork Kit cables
9Signal C10Outdoor Entry Power Cable11
Water Pump
12
Plate Heat Exchanger
13
Pressure Gage
14
Safety valve
15
Heater Control Box
16
Outdoor Control Box
Circulating the water
Heat exchanger between refrigerant and water
Indicates circulating water pressure
Open at Water pressure 3 bar
Heater PCB and terminal blocks
Outdoor PCB and terminal blocks
17
ENGLISH
GENERAL INFORMATION
2
1
2
1
2
1
18
ENGLISH
Control Parts
Control box before structural change (Until August, 2020)
UN36A (5, 7, 9 kW)UN60A (9, 12, 14, 16 kW)
Control box after structural change (From September, 2020)
h The shape may differ depending on the model. Refer to “Exploded View” in SVC Manual.
Description
NoNameRemark
1Terminal blocksThe terminal blocks allow easy connection of field wiring
2Main PCB
The main PCB(Printed Circuit Board) controls the functioning of the
unit
GENERAL INFORMATION
1
2
2
1
Control box before structural change (Until January, 2021)
UN36A (5, 7, 9 kW)
Control box after structural change (From February, 2021)
19
ENGLISH
h The shape may differ depending on the model. Refer to “Exploded View” in SVC Manual.
Description
NoNameRemark
1Terminal blocksThe terminal blocks allow easy connection of field wiring
2Main PCB
The main PCB(Printed Circuit Board) controls the functioning of the
unit
GENERAL INFORMATION
20
ENGLISH
Remote Controller
Operation display
window
Back button
Up/Down/Left/Right
Button
Operation display windowOperation and Settings status display
Back buttonWhen you move to the previous stage from the menu’s setting stage
Up/down/left/right buttonWhen you change the menu’s setting value
OK buttonWhen you save the menu’s setting value
On/Off buttonWhen you turn ON/OFF the Unit
OK
On/Off Button
OK Button
GENERAL INFORMATION
Typical Installation Example
CAUTION
!
If is installed with pre-existing boiler, the boiler and should not be
operated together. If entering water temperature of is above 55 °C, the system
will stop operation to prevent mechanical damage of the product. For detailed electric wiring
and water piping, please contact authorized installer.
Some installation scenes are presented for example. As these scenes are conceptual
figures, installer should optimize the installation scene according to the installation
conditions.
CASE 1: Connecting Heat Emitters for Heating and Cooling
(Under floor loop, Fan Coil Unit, and Radiator)
OutdoorIndoor
R
T
M / F
21
ENGLISH
Floor heating loopFan coil unit
Radiator
NOTE
• Room thermostat
- Type of thermostat and specification should be complied with chapter 4 and chapter 7 of
• 2way valve
- It is important to install 2way valve to prevent dew condensation on the floor and radiator
while cooling mode.
- Type of 2way control valve and specification should be complied with chapter 4 and
chapter 7 of installation manual.
- 2way valve should be installed at the supply side of the collector.
• By-pass valve
- To secure enough water flow rate, by-pass valve should be installed at the collector.
- By-pass valve should guarantee minimum water flow rate in any case. Minimum water
flow rate is described in water pump characteristics curve.
High Temperature
Low Temperature
M / F
Magnetic Filter (Mandatory)
installation manual.
Room Thermostat
(Field supply)
2way valve
(Field supply)
Shut-off valve
By-pass valve(Field supply)
R
Remote controller
GENERAL INFORMATION
DHW
tank
22
ENGLISH
CASE 2: Connecting DHW Tank
OutdoorIndoor
Hot water
City water
R
T
M / F
DHW
DHW
tank
tank
Floor heating loopFan coil unit
Radiator
NOTE
• DHW tank
- It should be equipped with internal electric heater to generate sufficient heat energy in
very cold season.
- DHW : Domestic Hot Water
• 3way valve
- Type of 3way valve and specification should be complied with chapter 4 and chapter 7 of
High Temperature
Low Temperature
Shut-off valve
M / F
Magnetic Filter (Mandatory)
installation manual.
Room Thermostat(Field supply)
2way valve
(Field supply)
By-pass valve(Field supply)
R
Remote controller
3way valve
(Field supply)
CASE 3: Connecting Solar thermal system
OutdoorIndoor
R
T
M / F
Solar heat source
Hot water
GENERAL INFORMATION
23
ENGLISH
Floor heating loopFan coil unit
DHW
tank
City water
Radiator
NOTE
• DHW tank
- It should be equipped with internal electric heater to generate sufficient heat energy in
very cold season.
- DHW : Domestic Hot Water
• Pump
- Maximum power consumption of pump should be less than 0.25 kW.
High Temperature
Low Temperature
Shut-off valve
M / F
Magnetic Filter (Mandatory)
Room Thermostat(Field supply)
2way valve
(Field supply)
By-pass valve(Field supply)
R
Remote controller
3way valve
(Field supply)
Pump(Field supply)
GENERAL INFORMATION
24
ENGLISH
CASE 4: Connecting 2ndCircuit
OutdoorIndoor
R
T
M / F
[Room A] Main Zone zone (Low Temp.)
Mix
Mix Kit
Buffer
Tank
[Room B] Additional zone (High Temp.)
nd
2
circuit temp. sensor
Floor heating loop
RadiatorRadiator
Floor heating loop
NOTE
• Mix Kit
- You can install it when you want to set the temperature of two rooms individually
- When heating, Main Zone can not be higher than Add Zone.
- When cooling, Main Zone can not be lower than Add Zone.
- The types and specifications of the Mix Kit are to comply with Chapters 4 and 7 of the
M / F
Installation Manual.
High Temperature
Low Temperature
Shut-off valve
Magnetic Filter (Mandatory)
Pressure Regulation valve
(Field supply)
Room Thermostat
(Field supply)
2way valve (Field supply)
By-pass valve(Field supply)
Air vent (Field supply)
3way valve
(Field supply)
Pump(Field supply)
Mix Kit (Field supply)
CASE 5: Connecting 3rdParty
OutdoorIndoor
3 Way V/V direction
Boiler On : Ơ
Boiler Off : ȯ
GENERAL INFORMATION
25
ENGLISH
R
T
M / F
Buffer
Tank
Boiler
Floor
heating loop
Floor
heating loop
Floor
heating loop
NOTE
• DHW tank
- 3rd Party Boiler
- You can control the boiler automatically and manually by comparing the outside
temperature and the set temperature.
• 3way valve
- It is a valve for DHW use.
- Not installed when installing Buffer Tank
- Type of 3way valve and specification should be complied with chapter 4 and chapter 7 of
installation manual.
High Temperature
Low Temperature
Shut-off valve
Magnetic Filter (Mandatory)
M / F
Reverse check valve
Room Thermostat(Field supply)
2way valve (Field supply)
By-pass valve(Field supply)
Air vent (Field supply)
3way valve
(Field supply)
Pump(Field supply)
Aquastat V/V
GENERAL INFORMATION
26
ENGLISH
CASE 6 : Connecting backup heater
Outdoor
Indoor
R
T
Buffer
M/F
Tank
Floor heating
loop
Floor heating
loop
Floor heating
loop
NOTE
• Backup heater(Accessory)
- You can retain sufficient capacity even though ambient temperature will be decreased
in winter.