LG ABUQ24GGLA0, ABUQ18GHLA0 INSTALLATION MANUAL

www.lg.com
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
P/NO : MFL67448509
Single A Air Conditioner Installation Manual
CONTENTS
Safety Precautions ..............................................................................................3
Installation of Outdoor Unit................................................................................6
Wiring Connection...............................................................................................9
Connecting Pipes ..............................................................................................12
Leakage test and Evacuation ...........................................................................15
Test running .......................................................................................................17
Function..............................................................................................................19
Self-diagnosis Function....................................................................................20
Installation Guide at the Seaside .....................................................................21
2 Air Conditioner
To prevent the injury of the user or other people and property damage, the following instructions must be followed.
n Be sure to read before installing the air conditioner. n Be sure to observe the cautions specified here as they include important items related to safety. n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
n The meanings of the symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
n Installation
Be sure not to do.
Be sure to follow the instruction.
Safety Precautions
Always perform grounding.
• Otherwise, it may cause electri­cal shock.
Donʼt use a power cord, a plug or a loose socket which is damaged.
• Otherwise, it may cause a fire or electrical shock.
For installation of the product, always contact the service cen­ter or a professional installation agency.
Otherwise, it may cause a fire, elec­trical shock, explosion or injury.
Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.
If the electrical part cover of the indoor unit and the service panel of the out­door unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.
Always install an air leakage breaker and a dedicated switching board.
• No installation may cause a fire and electrical shock.
Do not keep or use flammable gases or combustibles near the air conditioner.
• Otherwise, it may cause a fire or the failure of product.
Ensure that an installation frame of the out­door unit is not damaged due to use for a long time.
• It may cause injury or an accident.
Do not disassemble or repair the product ran­domly.
• It will cause a fire or electrical shock.
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not com­press air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
• There is the risk of death, injury, fire or explosion.
Installation Manual 3
Safety Precautions
4 Air Conditioner
Safety Precautions
Do not install the product at a place that there is concern of falling down.
• Otherwise, it may result in personal injury.
Use caution when unpacking and installing.
• Sharp edges may cause injury.
Take the power plug out if necessary, holding the head of the plug and do not touch it with wet hands.
• Otherwise, it may cause a fire or electrical shock.
Do not use the power cord near the heating tools.
• Otherwise, it may cause a fire and electrical shock.
Do not open the suction inlet of the indoor/outdoor unit during operation.
• Otherwise, it may electrical shock and failure.
Do not allow water to run into electrical parts.
• Otherwise, it may cause the failure of machine or electrical shock.
Hold the plug by the head when taking it out.
• It may cause electric shock and damage.
Never touch the metal parts of the unit when removing the filter.
• They are sharp and may cause injury.
Do not share the outlet with other appliances.
• It will cause an electric shock or a fire due to heat genera­tion.
Do not use the damaged power cord.
• Otherwise, it may cause a fire or electrical shock.
Do not modify or extend the power cord randomly.
• Otherwise, it may cause a fire or electrical shock.
Take care so that the power cord may not be pulled dur­ing operation.
• Otherwise, it may cause a fire or electrical shock.
Unplug the unit if strange sounds, smell, or smoke comes from it.
• Otherwise, it may cause elec­trical shock or a fire.
Keep the flames away.
• Otherwise, it may cause a fire.
Do not step on the indoor/outdoor unit and do not put anything on it.
• It may cause an injury through dropping of the unit or falling down.
Do not place a heavy object on the power cord.
• Otherwise, it may cause a fire or electrical shock.
When the product is submerged into water, always contact the service center.
• Otherwise, it may cause a fire or electrical shock.
Take care so that children may not step on the outdoor unit.
• Otherwise, children may be seriously injured due to falling down.
n Operation
Installation Manual 5
Safety Precautions
n Installation
Install the drain hose to ensure that drain can be securely done.
• Otherwise, it may cause water leakage.
Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors.
• Otherwise, it may cause dispute with the neigh­bors.
Always inspect gas leakage after the instal­lation and repair of product.
• Otherwise, it may cause the failure of product.
Keep level parallel in installing the product.
• Otherwise, it may cause vibration or water leakage.
Avoid excessive cooling and perform venti­lation sometimes.
• Otherwise, it may do harm to your health.
Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.
• The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.
Do not use an appliance for special purposes such as preserving animals vegetables, pre­cision machine, or art articles.
• Otherwise, it may damage your properties.
Do not place obstacles around the flow inlet or outlet.
• Otherwise, it may cause the failure of appli­ance or an accident.
n Operation
1. Installation Places
• If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
• Ensure that the spaces indicated by arrows around front, back and side of the unit.
• Do not place animals and plants in the path of the warm air.
• Take the air conditioner weight into account and select a place where noise and vibration are min­imum.
• Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
More than 300mm
Installation of Outdoor Unit
Installation of Outdoor Unit
2. Piping length and the elevation
6 Air Conditioner
Unit : mm
FREE JOINT SINGLE OUTDOOR
Ceiling Cassette
Model Capacity
Pipe Size Length A(m) Elevation B(m)
Additional
Refrigerant
(g/m)
Gas Liquid Standard Max. Standard Max.
AUUQ18GH1 5kW Ø12.7(1/2) Ø6.35(1/4) 7.5 30 5 15 20 AUUQ21GH1 6kW Ø12.7(1/2) Ø6.35(1/4) 7.5 30 5 15 20 AUUQ24GH1 7kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40 AUUQ36GH1 10kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40 AUUQ42GH1 12.5kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40 AUUQ48GH1 13.4kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40 AUUQ54GH1 15.8kW Ø19.05(3/4) Ø9.52(3/8) 7.5 50 5 30 40
Model Capacity
Pipe Size Length A(m) Elevation B(m)
Additional
Refrigerant
(g/m)
Gas Liquid Standard Max. Standard Max.
ATUQ18GPLE3 5kW Ø12.7(1/2) Ø6.35(1/4) 7.5 30 5 15 20 ATUQ21GPLE3 6kW Ø12.7(1/2) Ø6.35(1/4) 7.5 30 5 15 20
ATUQ24GNLE3 7kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40 ATUQ36GMLE3 10kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40 ATUQ42GMLE3 12.5kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40 ATUQ48GMLE3 13.4kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40 ATUQ54GMLE3 15.8kW Ø19.05(3/4) Ø9.52(3/8) 7.5 50 5 30 40
More than 300mm
Fence or
obstacles
Sunroof
More than 700mm
More than
More than 300mm
300mm
More than 600mm
Installation Manual 7
Installation of Outdoor Unit
Ceiling Suspended Air conditioner
Ceiling Concealed Duct
Ceiling Concealed Duct – Low static
Model Capacity
Pipe Size Length A(m) Elevation B(m)
Additional
Refrigerant
(g/m)
Gas Liquid Standard Max. Standard Max.
AVUQ18GJLA0 5kW Ø12.7(1/2) Ø6.35(1/4) 7.5 30 5 15 20 AVUQ21GJLA0 6kW Ø12.7(1/2) Ø6.35(1/4) 7.5 30 5 15 20 AVUQ24GJLA0 7kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40
AVUQ36GKLA0 10kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40
AVUQ42GLLA0 12.5kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40 AVUQ48GLLA0 13.4kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40 AVUQ54GLLA0 15.8kW Ø19.05(3/4) Ø9.52(3/8) 7.5 50 5 30 40
Model Capacity
Pipe Size Length A(m) Elevation B(m) Additional
Gas Liquid Standard Max. Standard Max. (g/m)
ABUQ18GHLA0
ABUQ18GL2A0
5kW Ø12.7(1/2) Ø6.35(1/4) 7.5 30 5 15 20
ABUQ21GHLA0
ABUQ21GL2A0
6kW Ø12.7(1/2) Ø6.35(1/4) 7.5 30 5 15 20
ABUQ24GGLA0
ABUQ24GL3A0
7kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40
ABUQ36GGLA0 10kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40 ABUQ42GRLA0 12.5kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40 ABUQ48GRLA0 13.4kW Ø15.88(5/8) Ø9.52(3/8) 7.5 50 5 30 40 ABUQ54GRLA0 15.8kW Ø19.05(3/4) Ø9.52(3/8) 7.5 50 5 30 40