LG ABNW24GM1E4 Installation Manual

INSTALLATION MANUAL
Ceiling Concealed Duct
AIR CONDITIONER
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
ENGLISH
P/NO: MFL67939944
Copyright © 2020 LG Electronics Inc. All Rights Reserved
www.lg.com
TABLE OF CONTENTS
2
ENGLISH
TABLE OF CONTENTS
3 TIPS FOR SAVING EN
4 IMPORTANT SAFETY IN
ERGY
STRUCTIONS
6 INTRODUCTION
6 Features
7 INSTALLATION OF IN
7
Selection of the best location
7
Installation of Unit
10
Indoor Unit Drain Piping
10
Drain test
11
Thermal Insulation
12
Wiring Connection
DOOR
13 INSTALLATION INSTRUCTION
Remote controller installation
16
Group control
17
18
Installer Setting - How to Enter Setting Mode
19
Installer Setting - Central Control Address Setting Installer
20
Installer Setting – Wired Controller Master / Slave Setting
21
Installer Setting - Static Pressure Step Setting
22
Installer Setting - Static Pressure Setting
23
Installer Setting - E.S.P.
24
Installer Setting - Thermistor
25
Installer Setting - Test Run Mode
26
Installer Setting - Celsius Setting
33 DIP SWITCH SETTING
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condi­tioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
TIPS FOR SAVING ENERGY
TIPS FOR SAVING ENRGY
3
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
!
!
!
IMPORTANT SAFETY INSTRUCTION
4
ENGLISH
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation work must be performed in accordance with the National Electric Code by quali­fied and authorized personnel only.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment mal­function, property damage, personal injury and/or death.
Installation
• Always perform grounding.
- Otherwise, it may cause electrical shock.
• For installation of the product, always contact the service center or a professional installation agency. - Otherwise, it may cause a fire, electrical shock, explosion or injury.
• Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.
- If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not
attached securely, it could result in a fire or electric shock due to dust, water, etc.
• Always install an earth leakage circuit breaker and a dedicated switching board. - No installation may cause a fire and electrical shock.
• Do not keep or use flammable gases or combustibles near the air conditioner. - Otherwise, it may cause a fire or the failure of product.
• Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.
- It may cause injury or an accident.
• Do not disassemble or repair the product randomly. - It will cause a fire or electrical shock.
• Do not install the product at a place that there is concern of falling down. - Otherwise, it may result in personal injury.
• Use caution when unpacking and installing. - Sharp edges may cause injury.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and Do not use Flammable gases. Otherwise, it may cause fire or explosion. There is the risk of death, injury, fire or explosion.
• Consult your local dealer regarding what to do in case of refrigerant leakage. When the air conditioner is to be installed in a small room, it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the concentration limit in the event of a leakage. Otherwise, this may lead to an accident due to oxygen depletion.
• Carry out the specified installation work after taking into account earthquakes. Failure to do so during installation work may result in the unit falling and causing accidents.
CAUTION
!
IMPORTANT SAFETY INSTRUCTION
• Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel according to local laws and regulations and this installation manual. An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.
• Be sure to switch off the unit before touching any electrical parts.
• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal connections or wires.
• If refrigerant gas leaks during installation, ventilate the area immediately. Toxic gas may be produced if the refrigerant gas comes into contact with fire.
Operation
• Turn off the unit if strange sounds, smell, or smoke comes from it. - Otherwise, it may cause electri­cal shock or a fire.
• Keep the flames away. - Otherwise, it may cause a fire.
• Do not touch the power cable with wet hands when it taking out . – Otherwise, it may cause a fire or electrical shock.
• Do not open the suction inlet of the indoor/outdoor unit during operation. - Otherwise, it may electri­cal shock and failure.
• Do not allow water to run into electrical parts. - Otherwise, it may cause the failure of machine or electrical shock.
• Never touch the metal parts of the unit when removing the filter. - They are sharp and may cause injury.
• Do not step on the indoor/outdoor unit and do not put anything on it. - It may cause an injury through dropping of the unit or falling down.
• When the product is submerged into water, always contact the service center. - Otherwise, it may cause a fire or electrical shock.
• Take care so that children may not step on the outdoor unit. - Otherwise, children may be seriously injured due to falling down.
5
ENGLISH
Installation
• Install the drain hose to ensure that drain can be securely done. - Otherwise, it may cause water leakage.
• Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors. - Otherwise, it may cause dispute with the neighbors.
• Always inspect gas leakage after the installation and repair of product. - Otherwise, it may cause the failure of product.
• Keep level parallel in installing the product. - Otherwise, it may cause vibration or water leakage.
Operation
• Avoid excessive cooling and perform ventilation sometimes. - Otherwise, it may do harm to your health.
• Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent. - The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.
• Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or art articles. - Otherwise, it may damage your properties.
• Do not place obstacles around the flow inlet or outlet. - Otherwise, it may cause the failure of appli­ance or an accident.
• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box cover are removed or opened.
6
ENGLISH
INTRODUCTION
Features
INTODUCTION
Air inlet vents
Air outlet vents
Remote Controller
Selection of the best location
- The place shall easily bear a load exceeding four times the indoor unit’s weight.
- The place shall be able to inspect the unit as the figure.
- The place where the unit shall be leveled.
- The place shall allow easy water drainage.(Suitable dimension “H” is neces­sary to get a slope to drain as figure.)
- The place shall easily connect with the out­door unit.
- The place where the unit is not affected by an electrical noise.
- The place where air circulation in the room will be good .
- There should not be any heat source or steam near the unit
- Confirm the positional relationship between the unit and suspension bolts.
- Thermal insulator the ceiling opening to clean the filter or service under the product.
Installation of Unit
Install the unit above the ceiling correctly.
Position of suspension Bolt
- Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
- Apply a filter Accessory at air return hole.
CASE 1
INSTALLATION OF INDOOR
INSTALLATION OF INDOOR
7
ENGLISH
Top view
Unit: mm
Air inlet vents
Inspection hole 600 x 600
Control box
E
C
D
J A B
I
F
H
Drainage hole
G
Front view
Unit: mm
Air outlet vents
1000
Front
600
20mm or more
Suction
󳤏󶐂󵬆 󳐖󵌕
Outlet air intake
󳄊󶇁󳤏󶐂󵬆 󴀐󶈕
Dimension
Chassis
M3 M2
M1
󳤏󵐐󵼓󴔏󵤕
Cloth tube
tube
󳌂󵸗󵄔 󳐖󵌕
󳌆󵤍󵤏󵛁
Ceiling Panel
󳈐󵄓
Check port
󳤏󶌑󵔄󶐊󵼏 󴀐󶈕
Internal Unit
󳌆󵤍󵤏󵛁󳈐󵄓
Ceiling Panel
Flexible
󳐊󶌄󵠂󶈈
discharge
󳘍󵔙󵤃󵰆󳐖󵌕
pipe
󳄊󶇁󳐊󶌄󵠂󶈈󵓁
Air outlet
󴀐󶈕
󳌆󵤍󵤏
(Unit:mm)
ABCDEFGH I J
1283.4 1321.6 619.2 700 30 360 15.2 1208 291.4 1250
1283.4 1321.6 619.2 700 30 270 15.2 1208 201.4 1250
933.4 971.6 619.2 700 30 270 15.2 858 201.4 900
Roof
- Install the unit leaning to a drainage hole side as a figure for easy water drainage.
Position of console Bolt
- A place where the unit will be leveled and that can support the weight of the unit.
- A place where the unit can withstand its vi­bration.
- A place where service can be easily per­formed.
- Select and mark the position for fixing bolts.
- Drill the hole for set anchor on the face of ceiling.
- Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
- Mount the suspension bolts to the set an­chor firmly.
- Secure the installation plates onto the sus­pension bolts (adjust level roughly) using nuts, washers and spring washers.
CASE 2
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local supply)
X 4
1 Set anchor
Old building New building
2 Plate washer 3 Spring washer
4 Nut
5 Suspension bolts
CAUTION
Tighten the nut and bolt to prevent unit falling.
!
INSTALLATION OF INDOOR
8
ENGLISH
ENGLISH
INSTALLATION OF INDOOR
CAUTION
!
• Install declination of the indoor unit is very important for the drain of the duct type air condi­tioner.
• Minimum thickness of the insulation for the connecting pipe shall be 5mm.
Front of view
• The unit must be declined to the drain hose connected when finished installation.
Ceiling
5~10mm
Drainage hole
CORRECT
Drainage hole
INCORRECT
Caution for gradient of unit and drain piping
Lay the drain hose with a downward inclination so water will drain out.
9
• Always lay the drain with downward inclination (1/100 to 1/50). Prevent any upward flow or reverse flow in any par t.
• 10 mm or thicker formed thermal insulator shall always be provided for the drain pipe.
• Upward routing not
CORRECT
• Install the P-Trap ( or U-Trap) to prevent a water leakage caused by the blocking of intake air filter.
Unit
Make sure to be closed.
allowed
INCORRECT
Applied U-Trap Dimension
A 70 mm B 2C C 2 x SP SP = External Pressure
(mmAq)
Ex) External Pressure
= 10 mmAq A 70 mm B 40 mm C 20 mm
Thermal insulator
(Local supply)
Drainage pipe (Local supply)
Drainage hole
C
A
B
U-Trap
ENGLISH
Indoor Unit Drain Piping
- Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.
- During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.
- The outside diameter of the drain connection on the indoor unit is 32 mm.
Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings
- Be sure to execute thermal insulator on the drain piping.
- Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit.
Thermal insulator material: Polyethylene foam with thickness more than 8 mm.
Drain test
- Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.
- Feed water to the flexible drain hose and check the piping for leakage.
- When the test is complete, connect the flexi­ble drain hose to the drain port on the indoor unit.
1 Remove the air filter.
2 Check the drain.
- Spray one or two glasses of water upon the evaporator.
- Ensure that water flows drain hose of in­door unit without any leakage.
t
Air filters
10
INSTALLATION OF INDOOR
Pipe clamp
Indoor unit
Maintenance drain port
Upward routing not allowed
Feed water
Flexible drain hose (accessory)
Main drain pipe
Glue the join