LEYBOLD TRIVAC B, D 40 B, D 65 B Operating Instructions Manual

Page 1
GA 01.203/10.02
TRIVA C®B
Rotary Vane Vacuum Pump D 40 B, D 65 B
Cat. No. 112 86/96 113 45/46/47/55/56/57
Operating Instructions
Vacuum Solutions
Application Support
Service
LEYBOLD VACUUM
Page 2
GA 01.203/10.02 - 07/02

Contents

2
Contents
Page
IMPORTANT SAFETY CONSIDERATIONS . .4
1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Supplied equipment . . . . . . . . . . . . . . . . . . . . . . 9
1.3 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.4 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5 Transportation . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.6 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . 10
2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.2 Connection to the system . . . . . . . . . . . . . . . . 13
2.3 Electrical connection . . . . . . . . . . . . . . . . . . . . 14
2.4 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.6 Switching off/shutdown . . . . . . . . . . . . . . . . . . 17
3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.1 Checking the oil level . . . . . . . . . . . . . . . . . . . . 18
3.2 Oil change . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.3 Cleaning the dirt trap . . . . . . . . . . . . . . . . . . . . 19
3.4 Removing and fitting the internal demister . . . . 20
3.5 Disassembly and reassembly of the
electric motor . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.6 Replacing the shaft seal . . . . . . . . . . . . . . . . . 22
3.7 Removing and remounting the pump module . . 23
3.8 Leybold service . . . . . . . . . . . . . . . . . . . . . . . . 25
3.9 Storing the pump . . . . . . . . . . . . . . . . . . . . . . . 25
3.10 Maintenance plan . . . . . . . . . . . . . . . . . . . . . . 26
4 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 27
EEC Declaration of Conformity . . . . . . . . .28
EEC Manufacturer’s Declaration . . . . . . . .29
We reserve the right to modify the design and the specified data.The illustrations are not binding.
Page 3
Note
We strongly recommend that you read these Operating Instructions with care so as to ensure optimum operation of the pump right from the start.
Indicates procedures that must be strictly observed to prevent hazards to persons.
Indicates procedures that must strictly be observed to prevent damage to, or destruction of the pump.
Figures
The references to diagrams, e.g. (1/2) consist of the Fig. No.and the Item No. in that order.
Leybold-Service
If a pump is returned to LEYBOLD, indicate whether the pump is free of substances damaging to health or whether it is contaminated.
If it is contaminated also indicate the nature of the hazard. LEYBOLD must return any pumps without a „Declaration of Contamination“ to the sender’s address.
Disposal of Waste Oil
Owners of waste oil are entirely self-responsible for proper disposal of this waste.
Waste oil from vacuum pumps must not be mixed with other substances or materials.
Waste oil from vacuum pumps (Leybold oils which are based on mineral oils) which are subject to normal wear and which are contaminated due to the influence of oxygen in the air, high temperatures or mechanical wear must be disposed of through the locally available waste oil disposal system.
Waste oil from vacuum pumps which is contaminated with other substances must be marked and stored in such a way that the type of contamination is apparent. This waste must be disposed of as special waste.
European, national and regional regulations concerning waste disposal need to be observed.Waste must only be transported and disposed of by an approved waste disposal vendor.
3
GA 01.203/10.02 - 07/02
Warning
Caution
Page 4
GA 01.203/10.02 - 07/02
4

IMPORTANT SAFETY CONSIDERATIONS

The Leybold TRIVAC B vacuum pump is designed for safe and efficient operation when used properly and in accordance with this manual. It is the responsibility of the user to carefully read and strictly observe all safety precautions described in this section and throughout the manual. This product must be operated and maintained by trained personnel only. Consult local, state, and national agencies regarding specific requirements and regulations. Address any further safety, operation and/or maintenance questions to your nearest Leybold Vacuum office.
Warning Failure to observe the following precautions could result in serious personal injury:
• Before beginning with any maintenance or service work on the TRIVAC B, disconnect the pump from all power supplies.
• Do not operate the pump with any of the covers removed. Serious injury may result.
• If exhaust gases must be collected or contained, do not allow the exhaust line to become pressur ised.
• Make sure that the gas flow from the exhaust port is not blocked or restricted in any way.
• The standard version of the TRIVAC B is not suited for operation in explosion hazard areas.Contact us before planning to use the pump under such circumstances.
• Before starting up for the first time, the motor circuit (3 phase) must be equipped with a suitable protective motor switch. Please take note of the information in these Operating Instructions or on the electric motor (wiring diagram).
• The TRIVAC B is not suited for pumping of:
- combustible and explosive gases or vapours
- radioactive and toxic substances
- pyrophorous substances.
• Avoid exposing any par t of the human body to the vacuum.
• Never operate the TRIVAC B without a connected intake line or blank flange.
• The location at which the TRIVAC B (including its accessories) is operated should be such that angles over 10° from the vertical are avoided.
• The location of the TRIVAC B should be such that all controls are easily accessible.
• Under certain ambient conditions the TRIVAC B may attain a temperature of over 80 °C (176 °F).There then exists the danger of receiving burns. Note the symbols on the pump pointing to the hazards, and in the case of a hot pump wear the required protective clothing.
• Before pumping oxygen (or other highly reactive gases) at concentrations exceeding the concentration in the atmosphere (> 21 % for oxygen) it will be necessary to use a special pump. Such a pump will have to be modified and de-greased, and an inert special lubricant (like PFPE) must be used.
• Before operating the TRIVAC B with atmospheric gas ballast (optional) check first compatibility with the pumped media so as to avoid hazardous conditions during operation right from the start.
• Before commissioning the TRIVAC B, make sure that the media which are to be pumped are compatible with each other so as to avoid hazardous situations. All relevant safety standards and regulations must be obser ved.
• It is recommended to always operate the TRIVAC B with a suitable exhaust line which is properly connected. It must slope down and away from the pump.
• When moving the TRIVAC B always use the allowed means. A lifting eye is provided as standard on the pump.
Page 5
GA 01.203/10.02 - 07/02
5
Failure to observe the following precautions could result in damage to the pump:
• Do not allow the ingestion of small objects (screws, nuts, washers, pieces of wire, etc.) through the inlet port. Always use the screen which is supplied with every pump.
• Do not use the pump for applications that produce abrasive or adhesive powders or condensable vapours that can leave adhesive or high viscosity deposits. Please contact Leybold Sales or Service to select a suitable separator. Also pease contact Leybold Sales or Service when planning to pump vapours other than water vapour.
• This pump is suited for pumping water vapour within the specified water vapour tolerance limits.
• Avoid vapours that can condense into liquids upon compression inside the pump, if these substances exceed the vapour tolerance of the pump (> 25 mbar for water vapour).
• Before pumping vapours, the TRIVAC B should have attained its operating temperature, and the gas ballast should be set to position I (position 0 = closed, position I = max. water vapour tolerance, 25 mbar). The pump will have attained its operating temperature about 30 min utes after starting the pump.During this time the pump should be separated from the process, by a valve in the intake line, for example.
• In the case of wet processes we recommend the installation of liquid separators upstream and downstream of the pump as well as the use of the gas ballast.
• The exhaust line should be laid so that it slopes down and away from the pump so as to prevent condensate from backstreaming into the pump. For this preferably use the flange on the side of the motor.
• The entry of par ticles and fluids must be avoided under all circumstances.
• Reactive or aggressive substances in the pump chamber may impair the operating oil or modify it. In addition, such substances may be incompatible with the materials of the pump (Viton, gre y cast iron, aluminium, steel, resins, glass etc.).
• Corrosion, deposits and cracking of oil within the pump are not allowed.
This information will help the operator to obtain the best performance from the equipment:
• Normal amounts of humidity within the range of the pump’s vapour tolerance will not significantly affect pump performance when the gas ballast is active.Preferably use the e xhaust flange located on the side of the motor.
Caution: In the case of custom pumps (with a Cat. No. deviating from the Cat No. stated in the EC Declaration of Conformity) please note the information provided on a separate sheet.
Caution
Note
Page 6
GA 01.203/10.02 - 07/02

Description

6
2 31
1 Description
TRIVAC B pumps are oil-sealed rotary vane pumps.The TRIVAC D 40 B and D 65 B are dual-stage pumps. The number in the type designation (40 or 65) indicates the pumping speed in m3· h-1.
TRIVAC B pumps can pump gases and vapours and evacuate vessels or vacuum systems in the fine vacuum range.
Those of standard design are not suitable for pumping greater than atmospheric concentrations of oxygen, hazardous gases, or extremely aggressive or corrosive media.
The drive motor of the TRIVAC B is directly flanged to the pump at the coupling housing. The pump and motor shafts are directly connected by a flexible coupling. The bearing points of the pump module are force lubricated sliding bearings. All controls as well as the oil-level glass and the nameplate are arranged on the front. All connections are to be found at the sides of the pump. The oil-level glass is provided with prisms for better observation of the oil level.
The pump module consists of assembly parts which are pin-fitted so as to allow easy disassembly and reassembly. The pump module can be easily removed without special tools.
Key to Fig. 1
1 Oil filter OF 40-65 2 Roots pump adapter 3 Exhaust filter AF 40-65
Fig. 1 TRIVAC B with accessories
Warning
Page 7
GA 01.203/10.02 - 07/02
Description
7
1.1 Function
The rotor (2/7), mounted eccentrically in the pump housing (2/6), has two radially sliding vanes (2/5) which divide the pump chamber into several compartments. The volume of each compartment changes periodically with the rotation of the rotor.
As a result, gas is sucked in at the intake port (2/1).The gas passes through the dirt trap sieve (2/2), flows past the open anti-suckback valve (2/3) and then enters the pump chamber.In the pump chamber, the gas is passed on and compressed, after the inlet aperture is closed by the vane.
The oil injected into the pump chamber is used for sealing and lubricating. The slap noise of the oil in the pump which usually occurs when attaining the ultimate pressure is prevented by admitting a very small amount of air into the pump chamber.
The compressed gas in the pump chamber is ejected through the exhaust valve (2/10). The oil entrained in the gas is coarsely trapped in the internal demister (2/11); there the oil is also freed of mechanical impurities. The gas leaves the TRIVAC B through the exhaust por t.
During compression, a controlled amount of air – the so­called gas ballast – can be allowed to enter the pump chamber by opening the gas ballast valve (position I). The gas ballast stops condensation of vapours in the pump chamber up to the limit of the water vapour tolerance as specified in the technical data for the pump.
The gas ballast valve is opened (position I) and closed (position 0) by turning the gas ballast knob (7/5) on the front.
To enable the TRIVAC B to be used at intake pressures as high as 1,000 mbar, a special lubricating system was developed featuring force-lubrication of the sliding bearings.
An oil pump (3/6) pumps the oil from the oil reservoir (3/5) into a pressure-lubrication system which supplies oil to all bearing points (3/2).From there the oil enters the pump chamber area (3/4) of the vacuum pump.
The oil pump is fitted in the front end plate on the coupling side of the pump module.The oil suction line is placed low, resulting in a large usable oil reservoir.
Fig. 2 Sectional drawing of the TRIVAC B
Key to Fig. 2
1 Intake por t 2 Dirt trap 3 Anti-suckback valve 4 Intake channel 5 Vanes 6 Pump chamber 7 Rotor 8 Cover plate, connection for inert gas ballast
9 Exhaust channel 10 Exhaust valve 11 Internal demister 12 Spring buckles 13 Cover plate, connection for oil filter
Page 8
GA 01.203/10.02 - 07/02
Description
8
The oil is separated from the gas in the TRIVAC B in two steps as described above. First, small droplets are coalesced into large drops in the internal demister (2/11) fitted above the exhaust valve (2/10). Then, the large drops fall into the oil reservoir as the exhaust gas is diverted by the inner walls of the oil case.Thus a low loss of oil is obtained. This and the large usable oil reservoir ensure long intervals between oil changes even at high intake pressures.
The vacuum is maintained by the TRIVAC B through an integrated hydropneumatic anti-suckback valve (2/3) which is controlled via the oil pressure.
During operation of the TRIVAC B the control piston (4/3) remains sealed against a spring (4/2) by the oil pressure.
The valve disc (4/6) of the anti-suckback valve is held at the lower position by its own weight (valve open).
When the pump stops (because it has been switched off or because of a failure), the oil pressure drops and the spring (4/2) presses the control piston (4/3) up. Thus a connection is provided between the oil case or the oil reservoir (4/1) and the piston (4/4) of the anti-suckback
valve. Due to the pressure difference between the oil case and the intake port the oil presses the piston (4/4) up and the valve plate (4/6) against the valve seat (4/5). The quantity of oil in the oil reservoir (4/1) prevents the entry of air into the intake port (2/1) at the beginning of this process.
After the oil has flowed out from the reservoir and when the valve plate rests on the valve seat, air follows in, which vents the pump chamber and forces the v alve disc (4/6) against its seat.
This effectively prevents backstreaming of oil or oil vapours. The anti-suckback valve (2/3) operates independently of the operating mode of the pump, i.e. also with gas ballast.
Fig. 3 Schematic of the lubr icating system
Fig. 4 Hydropneumatic anti-suckback valve
Key to Fig. 3
1 Accessories 2 Bearings 3 Non-return valve 4 Pump chamber of the TRIVAC 5 Oil reservoir 6 Oil pump
Key to Fig. 4
1 Oil reservoir 5 Valve seat 2 Spring 6 Valve disk 3 Control piston 7 Gas inlet 4 Anti-suckback piston
Page 9
GA 01.203/10.02 - 07/02
Description
9
1.2 Supplied Equipment
The equipment supplied with the TRIVAC B pump includes:
Pump with motor, including initial filling of N 62 or HE­200 oil,
1 centering ring, 1 centering ring with dir t trap, 2 clamping rings DN 40 KF. For protection during shipment, the connection ports are
each blanked off by rubber diaphragms and supporting rings.
Switches, motor protection switch, mains cable etc. are not included.
1.3 Accessories
Cat. No. / Ref. No.
Separator AK 40-65, DN 40 KF . . . . . . . . . . . . . 188 16
Exhaust filter AF 40-65, DN 40 KF . . . . . . . . . . 189 16
Drain tap for condensate trap, exhaust filter oil drain of the pump,
vacuum-tight . . . . . . . . . . . . . . . . . . . . . . . . . . . 190 90
oil-tight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190 90
Exhaust filter with Iubricant return
AR 40-65, DN 40 KF . . . . . . . . . . . . . . . . . . . . 189 22
Exhaust filter with Iubricant return
ARS 40-65 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189 57
Dust filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186 15
Fine vacuum adsorption trap (with zeolite) . . . . 187 15
Adsorption trap
(with aluminium oxide) . . . . . . . . . . . . . . . . . . . 854 16
Oil filter OF 40-65 . . . . . . . . . . . . . . . . . . . . . . . 101 92
Chemical filter CF 40-65 . . . . . . . . . . . . . . . . . . 101 97
Chemical filter with safety cut-off valve
CFS 40-65 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 77
Adapter for RUVAC 151/251 Roots pumps . . . . 168 30
Adapter for gas ballast port
M 16 x 1.5 – DN 16 KF . . . . . . . . . . . . . . . . . . .168 40
M 16 x 1.5 – 3/8inch NPT . . . . . . . . . . . . .99 175 011*)
Oil N 62 1l 177 01 (order from 5l 177 02 LH Cologne, Germany) 20 l 177 03
Oil HE-200 1 qt 98 198 006 (order from 12 qt case 98 198 049 LHVP, Export Pa., 1 gal 98 198 007 USA) 5 gal 98 198 008
The oil grades N 62 and HE-200 are interchangeable.
*) order from LHVP, Export Pa. USA
1.4 Spare par ts
Set of gaskets . . . . . . . . . . . . . . . . . . . . . . . . . 197 22
Pump module, complete D 40 B . . . . . . 200 10 933
D 65 B . . . . . . 200 10 944
Module-gasket . . . . . . . . . . . . . . . . . . . . . 200 10 744*)
Oil case gasket . . . . . . . . . . . . . . . . . . . . 200 10 741*)
Internal demister . . . . . . . . . . . . . . . . . . 390 26 014*)
*) included in gasket set
1.5 Transpor tation
• Pumps which are filled with operating
agents must only be moved while standing upright. Otherwise oil may escape. Avoid any other orientations during transport.
• Check the pump for the presence of any
oil leaks, since there exists the danger that someone may slip on spilt oil.
• When lifting the pump you must make
use of the crane eyes provided on the pump for this purpose; also use the recommended type of lifting device.
Caution
Warning
Page 10
GA 01.203/10.02 - 07/02
Description
10
1.6 Technical data
D 65 B D 40 B
Druck
mbar
Saugvermögen
-1
m
h
3
-1
.
10
0
10
1
10
2
-5
10-410-310
10
-2
10
-1
10
0
10
1
10
3
10
Ultimate partial pressure without gas ballast Ultimate total pressure without gas ballast Ultimate total pressure with gas ballast
Fig. 5 Pumping speed characteristics of the TRIVAC D 40 B and TRIVAC D 65 B, 50 Hz operation, SI units
m3· h
-1
m3· h
-1
mbar
mbar
mbar
DN
l
IP
46 40
< 1 · 10
-4
< 5 · 10
-3
40
40 KF
1,7/2,6
54
50 Hz operation, SI units
75 65
< 1 · 10
-4
< 5 · 10
-3
40
40 KF
2,0/3,3
54
Nominal pumping speed* Pumping speed* Ultimate partial pressure
without gas ballast* Ultimate total pressure
with gas ballast* Water vapour tolerance*
Connection ports Oil filling min./max. Type of protection
* as per DIN 28 400 and following numbers
D 40 B D 65 B
Page 11
GA 01.203/10.02 - 07/02
Description
11
Fig. 6 Dimensional drawing for the TRIVAC rotary vane pumps (Dimensions a, l, b to b2and h1are approximate)
dimensions in mm
h
2
b
1
h
o
l
m
n
DN
c
a
b
2
b
h
1
Type DN a b b1b2chh1h
2
l* m n o
D 40 B (Part No. 112 86) 40 KF mm 135 264 234 206 166 355 336 308 670 382 191 190
in. 5.31 10.4 9.21 8.11 6.54 14 13.2 12.1 26.4 15 7.52 7.48 D 40 B (Part No. 113 45) mm (in.) 135 (5.31) 712 (28) D 40 B (Part No. 113 47) mm (in.) 135 (5.31) 670 (26.4) D 65 B (Part No. 112 96) mm (in.) 213 (8.39) 750 (29.5) D 65 B (Part No. 113 55) mm (in.) 213 (8.39) 790 (31.1) D 65 B (Part No. 113 57) mm (in.) 213 (8.39) 750 (29.5)
* Depending on the motor
USA pumps max. length D 40 B 760 mm (30“) D 65 B 840 mm (33.1“)
D 40 B D 65 B
1.6.1 Motor related data
1)
Motor with UL cable NEMA 5-158 and 2.5 m long cable
Cat.-No. l G Cat.-No. l G Motor-connection voltage, Motor Rated Speed Motor noise Order No.
(mm) (kg) (mm) (kg) frequency power current level motor
112 86 670 65 - - - 3~, 230-240/380-420 V ±5 %, 50 Hz 1500 W 6,9/4 A 1400 53 dB(A) 380 66 011
240-265/415-460 V ±5 %, 60 Hz 6,4/3,7 A 1700 57 dB(A)
---112 96 748 80 3~, 230-240/380-420 V ±5 %, 50 Hz 2200 W 9,7/5,6 A 1320 53 dB(A) 380 66 012 240-265/415-460 V ±5 %, 60 Hz 8,7/5 A 1640 57 dB(A)
113 451)712 73 113 55 790 84 3~, 230-380 V ±5 %, 50 Hz 2500 W 10,2/5,9 A 1400 56 dB(A) 200 10 411 113 471)670 69 113 57 748 80 3~, 200-346 V ±10 %, 50/60 Hz 2200 W 10,5/6 A 1380 55 dB(A) 200 10 412
9,5/5,5 A 1660 59 dB(A)
113 46 4101)50 113 56 4881)61 without motor - - - - -
Page 12
GA 01.203/10.02 - 07/02

Operation

12
2.1 Installation
The standard pump is not suited for installation in explosion hazard areas. When planning such an application please contact us first.
The TRIVAC B pump can be set up on a flat, horizontal surface. Rubber feet under the coupling housing ensure that the pump can not slip.
If you wish firmly install the pump in place, insert bolts or similar through the bore holes in the rubber feet.
The rubber feet act as vibration absorbers. They must therefore not be compressed by screws.
When installing the TRIVAC B pump, make sure that the connections and controls are readily accessible.
Max. tilt for the pump (without further attachment) with possibly fitted standard accessories is 10ϒ from the vertical.
The site chosen should allow adequate air circulation to cool the pump (keep front and rear unobstructed). The ambient temperature should not exceed +40 ϒC (104 ϒF) and not drop below +12 ϒC (55 ϒF) (see Section 2.5.3).
The max. amount of heat given off approximately corresponds to the rated motor power.
2 Operation
Fig. 7 Connections and controls
Key to Fig. 7
1 Eye for moving the pump 2 Intake port 3 Exhaust port 4 Oil-level glass 5 Gas ballast knob 6 Threaded connection M 16 x 1.5
(for inert gas ballast) 7 Adapter 8 Cover plate 9 Cover plate;connection for oil filter
Caution
1
2
3
4
5
67
8
9
Warning
Caution
Page 13
GA 01.203/10.02 - 07/02
Operation
13
2.2 Connection to the System
Before connecting the TRIVAC B, remove the shipping seals from the connection flanges (7/2) and (7/3).
Retain the shipping seals in case you need to store the pump in the future.
The pump is shipped with intake and exhaust flanges mounted for horizontal connection of the connecting lines. You can easily convert the ports for vertical connection by removing the four capscrews, rotating the flanges as required, and reinstalling the capscrews. Connect the intake and exhaust lines with a centering ring and a clamping ring each. Use the center ing ring with dirt trap for the intake port.
Connect the intake and exhaust line using anti-vibration bellows, without placing any strain on the pump.
The intake line must be clean. Deposits in the intake line may outgas and adversely affect the vacuum. The connecting flanges must be clean and undamaged. The maximum throughput of the pump is equivalent to the pumping speed of the pump (see Section 1.6). The cross-section of the intake and exhaust lines should be at least the same size as the connection ports of the pump. If the intake line is too narrow, it reduces the pumping speed. If the exhaust line is too narrow, overpressures may occur in the pump; this might damage the shaft seals and cause oil leaks. The maximum pressure in the oil case must not exceed 1.5 bar (absolute).
When pumping vapours, it is advisable to install condensate traps on the intake and exhaust sides.
Install the exhaust line with a downward slope (lower than the pump) so as to prevent condensate from flowing back into the pump. If this is not possible, insert a condensate trap.
In order to reduce the emission of oil vapours we recommend the installation of an additional exhaust filter.
Depending on the type of application or the kind of pumped media, the corresponding regulations and information sheets must be observed.
The pumps may be operated with an inert gas ballast via a connection which is provided for this purpose. The cover plate (7/8) can be removed to gain access to this M 16 x 1.5 threaded port (7/6). Matching connectors are available (see Section 1.3).
The inlet pressure for the gas ballast should be about 1000 mbar (absolute) and sufficient quantities of gas must be available (about 1/10of the pumping speed).
Never operate the pump with a sealed exhaust line.There is the danger of injury.
Before starting any work on the pump, the personnel must be informed about possible dangers first. All safety regulations must be observed.
Caution
Warning
Caution
Caution
Page 14
GA 01.203/10.02 - 07/02
Operation
14
Fig. 8 Connection diagram for TRIVAC B with 50 Hz 3-phase motor
Delta connection Star connection
2.3 Electrical Connections
Before beginning with any work on the wiring, ensure that mains supply for the pump is off. Electrical connections must be done by a qualified electrician as defined by VDE 0105 in accordance with the VDE 0100 guidelines.
TRIVAC B pumps are supplied without accessories for electrical connection. They must be connected via the appropriate cable, and a suitable motor protection switch. Set the switch in accordance with the rating on the motor nameplate. Fig. 8 shows the connection for pumps with 230/380 V, 50 Hz motors. In the case of pumps equipped as standard with a 60 Hz motor, please observe the diagram on or at the motor.
After connecting the motor and after every time you alter the wiring, check the direction of rotation. To do so, briefly switch on the motor and check whether a suitable cover (e. g. a blank flange) is sucked on at the intake port. If not, interchange two phases of the connection. Observe the direction arrow on the coupling housing!
Warning
Caution
Page 15
GA 01.203/10.02 - 07/02
Operation
15
2.4 Star t-up
Each time before starting up check the oil level.
For pumps with 3-phase motors, check the direction of rotation before starting the pump for the first time and after each change in the electrical connection (see Section 2.3.2).
On initial start-up, after prolonged idle periods or after an oil change, the specified ultimate pressure cannot be attained until the oil is degassed.
This can be done by running the pump for approx. 30 min. with the intake line closed and the gas ballast valve (7/5) open.
Before starting the pump ensure that the pump and the fitted accessories meet the requirements of your application and that safe operation can be guaranteed.
Avoid exposure of any par t of the body to the vacuum. There is the danger of injur y. Never operate the pump with an open intake port. Vacuum connections as well as oil-fill and oil-drain openings must never be opened during operation.
The safety regulations which apply to the application in each case must be observed. This applies to installation, operation and during maintenance (service) as well as waste disposal and transportation.
The standard pump is not suited for pumping of hazardous gases or vapours.
Our technical sales department is available for further advice in these matters.
2.4.1 Areas of Application
Before pumping oxygen (or other highly reactive gases) at concentrations exceeding the concentration in the atmosphere (> 21 % for oxygen) it will be necessary to use a special pump.Such a pump will have to be modified and de-greased, and an inert special lubricant (like PFPE) must be used.
The pump is not suitable for pumping of: – ignitable and explosiv e gases or v apours
– oxidants – pyrophorous gases.
The pumps are not suitable for pumping of liquids or very dusty media. Suitable protective devices must be installed.
Our technical sales department is available for further advice in these matters.
Caution
Warning
Warning
Caution
Page 16
GA 01.203/10.02 - 07/02

Operation

16
In cyclic operation, the TRIVAC B should not be switched off during the intervals between the individual working phases (power consumption is minimal when the pump is operating at ultimate pressure), but should continue to run with gas ballast valve open and intake port closed (if possible via a valve).
Once all vapours have been pumped off from a process (e.g. during dr ying), the gas ballast valve can be closed to improve the attainable ultimate pressure.
2.5.3 Operating Temperature
Proper operation of the TRIVAC B is ensured in the ambient temperature range between 12 °C to 40 °C (55 °F to 104 °F).
At operating temperature, the surface temperature of the oil case may lie between 40 °C and over 80 °C, depending on the load. There is the danger of receiving burns.
If – due to the ambient conditions – this temperature range is exceeded at either end of the range, then the operating range of the TRIVAC B can be adapted.
The Leybold sales department will be pleased to answer any questions in this matter.
2.5 Operation
TRIVAC B pumps can pump condensable gases and vapours, provided that the gas ballast valve (7/5) is open and the pump has attained its operating temperature.
2.5.1 Pumping of Non-Condensable Gases
If the process contains mainly permanent gases, the pump may be operated without gas ballast (position 0), provided that the saturation vapour pressure at operating temperature is not exceeded during compression.
If the composition of the gases to be pumped is not known and if condensation in the pump cannot be ruled out, run the pump with the gas ballast valve open in accordance with Section 2.5.2.
2.5.2 Pumping of Condensable Gases and V apours
With the gas ballast valve open (position I) and at operating temperature, TRIVAC B pumps can pump pure water vapour up to the water vapour tolerance specified by the technical data. If the vapour pressure increases above the permissible level, the water vapour will condense in the oil of the pump.
When pumping vapours ensure that the gas ballast valv e is open and that the pump has warmed up for approximately 30 minutes with the intake line closed.
Vapour phases may only be pumped up to the permissible limit after the pump has attained its operating temperature.
During pumping, vapours may dissolve in the oil. This changes the oil properties and thus there is a risk of corrosion in the pump. Therefore, don’t switch off the pump immediately after completion of the process. Instead, allow the TRIVAC B to continue operating with the gas ballast valve open and the intake line closed until the oil is free of condensed vapours.
We strongly recommend operating the pump in this mode for about 30 minutes after completion of the process.
Caution
Warning
Page 17
GA 01.203/10.02 - 07/02
Operation
17
2.6 Switching Off/ Shutdown
Under normal circumstances, all that you need do is to electrically switch off the TRIVAC B.No further measures will be required.
When pumping condensable media let the pump continue to operate with the gas ballast valve open and the intak e line closed before switching off (see Section 2.5.2). When pumping aggressive or corrosive media, let the pump continue to operate even during long non-working intervals (e.g. overnight) with the intake line closed and the gas ballast valve open. This avoids corrosion during idle periods.
If the TRIVAC B is to be shutdown for an e xtended period after pumping aggressive or corrosive media or if the pump has to be stored, proceed as follows:
When pumping harmful substances, take adequate safety precautions.
Our technical sales department is available for further advice in these matters.
Drain the oil (see Section 3.2). Add clean oil until the oil-level is at the “min” mark (see
Section 3.2) and let the pump operate for some time. Then drain the oil and add clean oil until the oil lev el is at
the “max.” mar k (see Section 3.2). Seal the connection ports. Special conservation or anti-
corrosion oils aren’t necessary.
Please also take note of the information given in Section 3.9 (storage and storage conditions).
2.6.1 Shut-Down through Monitoring Components
When the pump has been switched off due to overheating sensed by the motor coil protector, the pump must only be started manually after the pump has cooled down to the ambient temperature and after having removed the cause first.
2.6.2 Failure of the Control System or the Mains Power
In order to prevent the pump from running up unexpectedly after a mains power failure, the pump must be integrated in the control system in such a way that the pump can only be switched on again manually. This applies equally to emergency cut-out arrangements.
Caution
Warning
Caution
Warning
Warning
Page 18
GA 01.203/10.02 - 07/02

Maintenance

18
3 Maintenance
Disconnect the electrical connections before disassembling the pump. Make absolutely sure that the pump cannot be accidentally started.
If the pump has pumped harmful substances, ascertain the nature of hazard and take adequate safety measures. Observe all safety regulations.
If you send a pump to LEYBOLD for repair please observe the information provided in Section 3.8.
When disposing of used oil, you must observe the applicable environmental regulations!
Due to the design concept, TRIVAC B pumps require very little maintenance when operated under normal conditions. The work required is described in the sections below.
All work must be carried out by suitably trained personnel. Maintenance or repairs carried out incorrectly will affect the life and performance of the pump and may cause problems when filing warranty claims.
LEYBOLD offers practical courses on the maintenance, repair, and testing of TRIVAC B pumps. Fur ther details are available from LEYBOLD on request.
If the TRIVAC B is used in ambient air which is much contaminated, make sure that the air circulation and the gas ballast valve are not adversely affected. When the TRIVAC B has been pumping corrosive media we recommend that possibly planned maintenance work be carried out immediately in order to prevent corrosion of the pump while it is at standstill.
3.1 Checking the Oil Level
During operation of the TRIVAC-B the oil level must always remain between marks (9/2) and (9/3) on the oil­level glass. The amount of oil must be checked and topped up as required.
Fill in oil only after the pump has been switched off.
3.1.1 Checking the Condition of N 62 or HE 200 Oil
The ageing process for the standard operating fluid N 62 resp.HE 200 (see Chapter 1.2.1) will depend very much on the area of application for the pump.
a) Visual check
Normally the oil is clear and transparent. If the oil darkens, it should be changed.
b) Chemical check
The neutralisation number of N 62 oil is determined according to DIN 51558.If it exceeds 2, the oil should be changed.
c) Viscosity check
If the viscosity of N 62 at 25 °C exceeds a level of 240 mPas (20% higher than the viscosity of fresh oil) an oil change is recommended.
If gases or liquids dissolved in the oil result in a deterioration of the ultimate pressure, the oil can be degassed by allowing the pump to run for approx. 30 min. with the intake port closed and the gas ballast valve open.
When wanting to check the oil, switch off the pump first and drain out from the warm pump the required amount of oil through the oil drain (9/4) into a beaker or similar.
Please note the safety information given in Chapter 3.2.
Caution
Caution
Caution
Warning
Caution
Caution
Page 19
GA 01.203/10.02 - 07/02
Maintenance
19
3.2 Oil Change
Before pumping oxygen (or other highly reactive gases) at concentrations exceeding the concentration in the atmosphere (> 21 % for oxygen) it will be necessary to use a special pump.Such a pump will have to be modified and de-greased, and an inert special lubricant (like PFPE) must be used.
Hazardous substances may escape from the pump and the oil.Take adequate safety precautions. For example wear gloves, face protection or breathing protection.
Observe all safety regulations.
For proper operation of the pump, it is essential that the pump has an adequate supply of the correct and clean oil at all times.
The oil must be changed when it looks dirty or if it appears chemically or mechanically worn out (see Section 3.1.1).
The oil should be changed after the first 100 operating hours and then at least every 2,000 to 3,000 operating hours or after one year. At high intake pressures and intake temperatures and/or when pumping contaminated gases, the oil will have to be changed more frequently.
Further oil changes should be made before and after long-term storage of the pump.
If the oil becomes contaminated too quickly, install a dust filter and/or oil filter (see Section 1.3).
Contact us for more information in this matter.
Required tool:
Allen key size 8.
Only change the oil after the pump has been switched off and while the pump is still warm.
If there is the danger that the operating agent may present a hazard in any way due to decomposition of the oil, or because of the media which have been pumped, you must determine the kind of hazard and ensure that all necessary safety precautions are taken.
Remove the oil-drain plug (9/4) and let the used oil drain into a suitable container. When the flow of oil slows down, screw the oil-drain plug back in, briefly switch on the pump (max. 10 s) and then switch it off again. Remove the oil-drain plug once more and drain out the remaining oil.
Screw the oil-drain plug back in (check the gasket and reinstall a new one if necessary).
Remove the oil-fill plug (9/1) and fill in with fresh oil. Screw the oil-fill plug (9/1) back in.
We can only guarantee that the pump operates as specified by the technical data if the lubricants recommended by us are used.
3.3 Cleaning the Dir t Trap
A wire-mesh sieve is located in the intake por t of the pump to act as a dirt trap for coarse particles. It should be kept clean to avoid a reduction of the pumping speed.
For this purpose, remove the dirt trap (2/2) from the intake port and rinse it in a suitable vessel with solvent. Then thoroughly dry it with compressed air.
If the dirt trap is defective, replace it with a new one.
The cleaning intervals depend on the application. If the pump is exposed to large amounts of abrasive materials, a dust filter should be fitted into the intake line.
Fig. 9 Oil change
Key to Fig. 9
1 Oil-fill plug 2 Oil-level mark “maximum” 3 Oil-level mark “minimum” 4 Oil-drain plug
Caution
Caution
1
2
3
4
Caution
Warning
Warning
Page 20
GA 01.203/10.02 - 07/02
Maintenance
20
3.4 Removing and Fitting the Internal Demister
Required tools:
Allen keys size 6 and 8
Required spare parts:
Gasket for oil case . . . . . . . . . . . . . . . . . . 200 09 148
Internal demister: . . . . . . . . . . . . . . . . . . . . 390 26 014
The internal demister is spring-mounted in a frame. When it is clogged, it rises periodically to reduce the pressure difference created. The resultant noise at high intake pressures indicates that the internal demister is dirty.
Periodically clean or replace the internal demister; the maintenance interval depends on the application. Use a suitable solvent for cleaning.
Shutdown the pump and drain the oil (see Section 3.2). Remove the six recessed screws (10/6) on the oil case
(10/4). Don’t remove the non-recessed screws; they hold the motor flange in place.
Pull the oil case forward off the pump. Remove the gasket (10/5). Unscrew screw (10/1). Remove small washer (10/1), spring (10/1), large washer
(10/1) and O-ring (10/1) Lift off the frame (10/2) and remove the internal demister
(10/3). Clean all parts and check that they are in perfect
condition; if not, replace them with new parts. Reassemble in the reverse order. Torque for the screws (10/6) is 12 Nm.
Fig. 10 Removal and fitting of the internal demister
Key to Fig. 10
1 Screw with small washer, spr ing,
large washer and O-ring 2 Frame for demister 3 Demister 4 Oil case 5 Gasket 6 Fixing screws
Page 21
Maintenance
GA 01.203/10.02 - 07/02
21
3.5 Disassembly and Reassembly of the Electric Motor
Before starting any disassembly work, always disconnect the motor from the mains. Reliably prevent the pump from running up.
Required tools:
Screwdriver 1.0 x 5.5 mm (for junction box), open-jaw wrenches size 7 and size 19 (for junction bo x), Allan k eys size 3 and size 6.
Possibly a puller for the coupling. Disconnect the mains connection. Support the motor.
Unscrew the four non-recessed hex. socket screws (11/5).
Remove the intermediate flange (11/4) together with the electric motor.
Remove the gasket (11/1). Loosen the threaded pin and pull the coupling with the
blade wheel (11/2) off the motor shaft. Unscrew the hex.socket screws (11/3). Remove the electric motor (11/6). Clean all parts and check that they are in perfect
condition; if not, replace them with new parts. Reassemble in the reverse order.
In the case of 60 Hz motors (USA versions) the coupling must not be pushed on to the shaft right up to the stop.On the other hand if it is not pushed on far enough the pump module may be damaged during operation. Push the coupling on in such a way that the distance between the front end of the coupling and the gasket (11/1) on the intermediate flange amounts to 43.7 mm.
Fig. 11 Disassembly and reassembly of the electric motor
Key to Fig. 11
1 Gasket 2 Coupling with fan blades 3 Hex.socket screws 4 Intermediate flange 5 Hex.socket screws 6 Electric motor
Caution
Warning
1
2
3
4
5
6
Page 22
GA 01.203/10.02 - 07/02
Maintenance
22
3.6 Replacing the Shaft Seal
Required tools:
Allen keys size 3, 5 and 8, flat-nose pliers, plastic hammer, shaft seal driver, possibly a puller for the coupling.
Required spare parts:
Shaft seal . . . . . . . . . . . . . . . . . . . . . . . . . 239 53 007
Bushing . . . . . . . . . . . . . . . . . . . . . . . . . . . 231 92 034
Oil marks under the coupling housing are signs of a damaged shaft seal.
The shaft seal can be replaced without removing or disassembling the pump module.
Shutdown the pump. Drain the oil (see Section 3.2). Support the motor. Unscrew the four non-recessed hex. socket screws
(11/5) and remove the motor (11/6). Remove gasket (11/1). Remove coupling element (12/1).
Unscrew screw (12/2) and pull off the spring washer (12/3).
Pull off the coupling half (12/4). Remove key (12/5). Pull off the compression ring (12/6) and O-ring (12/7). Unscrew the hex. socket screws (12/9) and pull out the
centering disc (12/10). If the centering disc does not come loose, use the forcing
thread into which screws (12/9) can be screwed in. Remove the O-ring (12/11). Force the shaft seal (12/8) out of the centering disk. Pull off the bushing (12/12) from the shaft. We recommend the use of a new shaft seal and bushing
for reassembly. Before fitting the new shaft seal, moisten it slightly with a
little vacuum pump oil. Using a suitable plastic or aluminium cylinder (shaft seal
driver) and a plastic hammer, force the shaft seal (12/8) carefully and without bending it into the centering disk (for position of shaft seal, see Fig. 12).
Fig. 12 Exchanging the shaft seal
Key to Fig. 12
1 Coupling element 2 Cylinder head screw 3 Spring washer 4 Coupling (one half) 5Key 6 Compression ring 7 O-ring 8 Shaft seal
9 Screws 10 Centering disk 11 O-ring 12 Bushing
1
2
3
4
5
6
7
8
9
10
11
12
Page 23
GA 01.203/10.02 - 07/02
Maintenance
23
If you do not have a shaft seal driv er, place the shaft seal on the centering disk and carefully
force it in with light blows of the plastic hammer. The shaft seal must not be bent. Push the bushing (12/12) on to the shaft. Insert the O-ring (12/11) into its groove. Carefully push the centering disk (12/10) with the shaft
seal onto the shaft and up against the end plate; fasten it with the screws (12/9).
Push the O-ring (12/7) and the compression disk (12/6) on to the shaft.
Insert the key (12/5). Mount the pump-half of the coupling (12/4) on the shaft. Install the spring washer (12/3) and tighten the screw
(12/2). Insert the coupling element (12/1) into the coupling and
mount the motor (see Section 3.5).
3.7 Removing and Remounting the Pump Module
Required tools:
Allen keys size 3, 5, and 8 mm, box wrench size 13, possibly pliers, torque wrench.
Required spare parts:
Gaskets: . . . . . . . . . . . . . . . . . . . . . . . 239 73 039
. . . . . . . . . . . . . . . . . . . . . . . 200 90 148
3.7.1 Removing the Pump Module
Drain the oil and remove the oil case (see Section 3.4). Unscrew the hex.nuts (13/1). Pull the entire pump module (13/2) forward off the tie
rods (13/5).
When doing so, ensure that the individual pin-fitted parts are not loosened. Further disassembly of the pump module should only be carried out by a trained service
engineer. Remove the gasket (13/3). Remove the coupling element (13/4).
After removing the protective shipping
materials, handle the new pump module
with care. Before installing a new pump module, remo v e the f our tie
rods from the new module and insert them in the old one for protection during shipment.
Caution
Caution
Page 24
GA 01.203/10.02 - 07/02
Maintenance
24
3.7.2 Remounting the Pump Module
When installing a new pump module, it is also advisable to use a new gasket (13/3).
Check the coupling element (13/4) for damage; if necessary, install a new one.
Use the tie rods supplied with the new pump module only if the old ones are damaged. To do so, unscrew the old tie rods with lock nuts, and screw in the new ones. With the aid of the lock nuts, tighten the tie rods.Then remove the lock nuts.
Push the gasket (13/3) onto the tie rods (13/5), push the coupling element (13/4) onto one coupling half.
Push the entire pump module (new or repaired) onto the tie rods.
Screw on the hex.nuts (13/1) and carefully cross-tighten them (torque 17 Nm).
Mount the oil case together with the gasket (see Section
3.4). Fill in oil.
Fig. 13 Removing and remounting the pump module
Key to Fig. 13
1 Hex.nuts 2 Pump module 4 Gasket 5 Coupling element 6 Tie rods
Page 25
GA 01.203/10.02 - 07/02
Maintenance
25
3.8 Leybold Service
If a pump is returned to Leybold, indicate whether the pump free of substances damaging to health or whether it is contaminated. If it is contaminated also indicate the nature of the hazard. For this you must use a form which has been prepared by us which we will provide upon request.
A copy of this form is reproduced at the end of these Operating Instructions: “Declaration of Contamination of Vacuum Instruments and Components”.
Please attach this form to the pump or enclose it with the pump.
This “Declaration of Contamination” is required to meet German Law and to protect our personnel.
Leybold must return any pumps without a “Declaration of Contamination” to the sender’s address.
The pump must be packed in such a way, that it will not be damaged during shipping and so that any contaminants are not released from the package.
3.8.1 Waste Disposal of Used Pump Materials
The corresponding environmental and safety regulations apply. This applies equally to used filters and filter elements (oil filter, exhaust filter and dust filter).
– In the case of hazardous substances
determine the kind of hazard first and observe the applicable safety regulations. If the potential hazard still persists, the pump must be decontaminated before starting with any maintenance work. For professional decontamination we recommend our Leybold service.
– Never exchange the oil or the filters
while the pump is still warm. Let the pump cool down to uncritical temperatures first. You must wear suitable protective clothing.
3.9 Storing the Pump
Before putting a pump into operation once more it should be stored in a dry place preferably at room temperature (20 °C). Before the pump is shelved it must be properly disconnected from the vacuum system, purged with dry nitrogen and the oil should be changed too.
The inlets and outlets of the pump must be sealed with the shipping seals which are provided upon delivery. The gas ballast switch must be set to the “0” position and if the pump is to be shelved for a longer period of time it should be sealed in a PE bag containing some desiccant (silica gel).
When a pump is put into operation after it has been shelved for over one year, standard maintenance should be run on the pump and the oil should also be exchanged (see Operating Instructions).We recommend that you contact the Leybold service.
Warning
Achtung
Warning
Page 26
GA 01.203/10.02 - 07/02
Maintenance
26
3.10 Maintenance Plan
(Recommendation)
No.
Rotary vane pumps
TRIVAC D 40 B TRIVAC D 65 B
Measurement/test quantity
Operating/auxiliary
materials
VE VP t
6m a n-a
Remarks
1 Operate the pump for at least 0.8
hours with gas ballast.
x Condensed water is thus removed from the oil.
2 Check the oil level, change the oil
if required.
Oil: N 62 or special and alternative oils, see Section 1.3
x x Refill:only after the pump has been switched off.
3 Check the quality of the oil,
change the oil if required.
visually
chemically
mechanically
x x
x
x
Visually: normally light and transparent, oil change is required when discolorations increase.
Chemically: to DIN 51558 when the neutralisation number exceeds 2; then an oil change will be required.
Mechanically: when dynamic viscosity at 25 °C exceeds 240 mPas; then an oil change will be required. Disposal of waste oil: see Chapter 3.8.1
4 Clean the dirt trap in the intake
port, change it as required.
Suitable cleaning agent and compressed air.
x ❏ Clean dirt trap with a cleaning agent and blow it
out with compressed air under a suction hood. ❏ Replace the defective dirt trap.
Use a cleaning agent which complies with the national / international specifications.
Observe the safety regulations when using cleaning agents.
Interval
Refer also to the Operating Instructions
– Chapter: individual components.
5 Clean the internal demister,
change it as required.
Suitable cleaning agent. x Already clean before the maintenance interval has
elapsed when the noise level increases. ❏ Clean the internal demister using a cleaning
agent.
❏ Replace the defective internal demister. ❏ Dispose of the defective internal demister as
special waste. Cleaning agent according to national / international specifications.
Observe the safety regulations when using cleaning agents.
6 Check the edges of the teeth on
the coupling element for any damages, change the coupling element as required.
x
7 Change the oil -
and
clean the oil level glass.
Oil: N 62 or special and alternative oils.
Suitable cleaning agent and compressed air.
8 Check the fan of the pump and the
motor as well as the cooling fins on the motor for deposits and clean as required.
Brush and industrial vacuum cleaner.
x
x Already clean before the maintenance interval has
elapsed when the pump or the motor gets too warm. Caution: switch off the pump and ensure that it can not run up inadvertently (disconnect from the mains).
Oil change:
• First oil change after 100 operating hours.
• Pump switched off and cold. Change the oil when the pump is cold in order to avoid releasing absorbed gases.
❏ Clean the oil level glass with a cleaning agent and blow it out with compressed air under a suction hood. Cleaning agent according to national / international specifications.
Observe the safety regulations when using cleaning agents. Quantity of oil: see Operating Instructions,
Chapter 1.6. Waste disposal of oil: see Operating Instructions, Chapter 3.8.1.
Page 27
GA 01.203/10.02 - 07/02

Troubleshooting

27
4 Troubleshooting
Fault Possible cause Remedy Repair*
Pump does not start.
Pump does not reach ultimate pressure.
Wiring is malfunctioning. Motor protection switch incorrectly set (3-phase motors only).
Operating voltage does not match motor.
Motor is malfunctioning. Oil temperature is below 12 ϒC. Oil is too viscous. Exhaust filter or exhaust line is clogged. Pump is seized up (sign: pump is jammed).
Check and repair wiring. Set motor protection switch properly.
Replace the motor. Replace the motor. Heat the pump and pump oil or use different oil. Change the oil. Replace the filter or clean the exhaust line. Repair the pump.
-
2.3
3.5
3.5
2.5.3/3.2
3.2
­Service
Measuring technique or gauge is unsuitable.
External leak
1)
. Anti-suckback valve is malfunctioning. Exhaust valve is malfunctioning. Oil is unsuitable. Intake line is dirty. Pump is too small.
Use correct measuring technique and gauge. Measure the pressure directly at pump’s intake port. Repair the pump. Repair the valve. Repair the valve. Change the oil (degas it, if necessary). Clean vacuum lines. Check the process data; replace the pump, if necessary.
­Service
Service Service
3.2
-
-
Pumping speed is too low.
Dirt trap in the intake port is clogged. Exhaust filter is clogged.
Connecting lines are too narrow or too long.
Clean the dirt trap; Precaution: install a dust filter in intake line. Exchange the filter element. Use adequately wide and short connecting lines.
3.3
-
2.2
Pump gets hotter than usually observed.
Cooling air supply is obstructed. Ambient temperature is too high. Process gas is too hot. Oil level is too low. Oil is unsuitable. Oil cycle is obstructed. Exhaust filter or exhaust line is obstructed. Exhaust valve is malfunctioning. Pump module is worn out.
Set pump up correctly. Set pump up correctly. Change the process. Add oil. Change the oil. Clean or repair the oil lines and channels. Replace the exhaust filter, clean the exhaust line. Repair the valve. Replace the pump module.
Oil is turbid. Condensation. Degas the oil or change the oil and clean the pump. Precau-
tion: open the gas ballast valve or insert a condensate trap.
2.5.2/3.2
2.1
2.1/2.5.3
-
3.2
3.2 Service
­Service
3.7
Pump is excessively noisy.
Oil level is much too low (oil is no longer visible). Silencing nozzle is clogged. Intake pressure is too high. Internal demister is clogged. Coupling element is worn. Vanes or bearings are damaged.
Add oil. Clean or replace the silencing nozzle. Lower the intake pressure. Clean or replace demister. Install new coupling element. Repair pump.
3.2 Service
-
3.4
3.5 Service
After switching off pump under vacuum, pressure in system rises too fast.
System has a leak. Anti-suckback valve is malfunctioning.
Check the system. Repair the valve.
­Service
Oil in the intake line or in vacuum vessel.
Oil comes from the vacuum system. Anti-suckback valve is obstructed. Sealing surfaces of anti-suckback valve are damaged or dirty. Oil level is too high.
Check the vacuum system. Clean or repair the valve. Clean or repair the intake port and the anti-suckback valve. Drain the excess oil.
­Service Service
3.2
* Repair information: refer to the Section in the Operation Instruction stated here.
1) Bubble test: the warm pump with degassed oil is running without gas ballast and the intake blanked off.The exhaust line is led in to a vessel with water.If an evenly spaced line of bubbles appears, then the pump has an external leak.
Key to the maintenance plan - see 3.10
VE = Maintenance before switching on the system VP = Maintenance before starting production t = Daily maintenance 6m = Six monthly maintenance a = Annual maintenance n-a = Maintenance every n years.
We recommend that you service the pump every two years covering the following:
• Cleaning
• Checking of the individual components
• Exchange of all seals
• Functional check. This check should be run by the Leybold service.
Page 28
GA 01.203/10.02 - 07/02
28
We – LEYBOLD Vakuum GmbH – herewith declare that the products defined below meet the basic requirements regarding safety and health of the relevant EC directives by design, type and versions which are brought into circulation by us.
In case of any product changes made without our approval, this declaration will be void.
Designation of the products: Rotary vane pump
- dual stage
Types: TRIVAC B; D 40 B
D 65 B
Cat. Nos.: 112 86; 113 45; 113 47;
112 96; 113 55; 113 57

EEC Declaration of Conformity

The products conform to the following directives:
• EC Directive on Machinery (98/37/EG)
• EC Directive on Low-Voltages (73/23)+(93/68/EWG)
• EC EMC Directive (89/336/EWG) (91/263/EWG) + (92/31/EWG) + (93/68/EWG)
Applied harmonised standards:
• DIN EN 292 Part 1 11.91
• DIN EN 292 Part 2 06.95
• DIN EN 1012 Part 2 07.96
• DIN EN 60 204 Part 1 11.98
Applied national standards and technical specifications:
• DIN 31 001 April 1983
Cologne, August 20, 2001
————————————————————— K. Kilian, Business Area Manager LPV Division Industrial
Cologne, August 20, 2001
————————————————————— Dr.Bahnen, Head of R&D LPV Division Industrial
Page 29
GA 01.203/10.02 - 07/02
29
We – Leybold Vacuum GmbH – herewith declare that operation of the incomplete machine defined below, is not permissible until it has been determined that the machine into which this incomplete machine is to be installed, meets the regulations of the EEC Directive on Machinery.
Designation of the products: Rotary vane pump
- dual stage
Types: TRIVAC B; D 40 B without motor
D 65 B without motor
Cat. Nos.: 113 46
113 56

EEC Manufacturer’s Declaration

in the sense of the Directive on Machinery 89/392/EWG, Annex IIb
Applied harmonised standards:
• DIN EN 292 Part 1 11.91
• DIN EN 292 Part 2 06.95
• DIN EN 1012 Part 2 07.96
• DIN EN 60 204 Part 1 11.98
Applied national standards and technical specifications:
• DIN 31 001 April 1983
Cologne, August 20, 2001
————————————————————— K. Kilian, Business Area Manager LPV Division Industrial
Cologne, August 20, 2001
————————————————————— Dr.Bahnen, Head of R&D LPV Division Industrial
Page 30
GA 01.203/10.02 - 07/02
30
Page 31
GA 01.203/10.02 - 07/02
31
Page 32
GA 01.203/10.02 - 07/02
LISS_04929_2002 bicom/OF 07.02
Printed in Germany on chlorine-free bleached paper
LEYBOLD V A CUUM GmbH
Bonner Strasse 498 (Bayenthal) D-50968 Cologne Tel.: +49(0)221 347-0 Fax: +49(0)221 347-1250 http://www.leyboldvac.de e-mail:[email protected]
USA:
LEYBOLD VA CUUM USA 5700 Mellon Road Export, PA 15632 Phone: +1-724-327 57 00 Fax: +1-724-733 12 17 Internet:http://www. leyboldvacuum.com
Canada:
LEYBOLD Canada Inc. 7050 Telford Way, Unit 5 Mississauga, Ontario Canada L5S 1V7 Phone: +1-905-672 77 04 Fax: +1-905-672 22 49 e-mail: [email protected]
AMERICA EUROPE ASIA
Deutschland:
LEYBOLD VAKUUM GmbH Bonner Straße 498 D-50968 Köln Phone: +49-221-347-1234 Fax: +49-221-347-1245 Internet: www.leyboldvac.
de e-mail: sales
@
leybold
vakuum.com
Belgien/Niederlande/ Luxemburg:
LEYBOLD N.V. Leuvensesteenweg 542, 9A B-1930
Zaventem Phone: +32-2-71 10 083 Fax: +32-2-72 08 338
LEYBOLD B.V.
Computerweg 7 NL-3606 AV Maarssen Phone: +31-346-583 999 Fax: +31-346-583 990
Frankreich:
LEYBOLD S.A. 7, Avenue du Quebec Z.A. de Courtaboeuf, B.P. 42 F-91942
Courtaboeuf
Cedex Phone: +33-1-69 82 48 00 Fax: +33-1-6907 57 38 e-mail: Compuserve:100635,43
Groß-Britannien/Irland:
LEYBOLD LTD. Waterside Way, Plough Lane GB-London SW 17 OHB Phone: +44-208-97170 00 Fax: +44-208-9717001
Italien:
LEYBOLD S.P.A. Via Trasimeno 8 I-20128 Milano Phone: +39-02-27 22 31 Fax: +39-02-27 20 96 41
Spanien:
LEYBOLD S.A. C/. Mataró, 27 Polígono Industrial Les Grases E-08980 Sant Feliu de Llobregat (Barcelona) Phone: +34-93-666 46 16 Fax: +34-93-666 43 70
Schweden:
LEYBOLD AB Box 9084 40092 Göteborg Phone: +46-31-68 84 70 Fax: +46-31-68 39 39
Schweiz / Liechtenstein:
LEYBOLD AG Leutschenbachstraße 55 CH-8050 Zürich Phone: +41-1-308 40 50 Fax: +41-1-302 43 73
Volksrepublik China:
LEYBOLD (Tianjin) VACUUM EQUIPMENT MANUFACTURING Co., Ltd. Beichen Economic Development Area (BEDA) Tianjin 300400, China Phone: +86-22 26 972 016 Fax: +86-22 26 972 017 e-mail:
Japan:
LEYBOLD Co., Ltd. Head Office Tobu A.K. Bldg. 4th Floor 23-3, Shin-Yokohama 3­chome Kohoku-ku,Yokohama-shi Kanagawa ken 222-0033 Phone: +81-45-471 33 30 Fax: +81-45-471 33 23
Korea:
LEYBOLD Korea Ltd. 4th Fl. Shinan Bldg., 173-1 Jangchoog-dong 2ga, Choong-ku Seoul 100-392, Korea C.P.O.Box 709
Phone: +82-2-227 11 567 Fax: +82-2-227 11 568
Singapore:
BALZERS and LEYBOLD Singapore Pte. Ltd. 1 Tuas South Street 3 Singapore 638043 Phone: +65-865 18 65 Fax: +65-862 22 95
Taiwan:
LEYBOLD Taiwan, Ltd. 2 F, No 416-1, Sec. 3 Chung-Hsin Rd. Chu Tung, Hsinchu. Taiwan R.O.C: 310 Phone: +886-3-583 39 88 Fax: +886-3-583 39 99
Sales Net worldwide
Loading...