Lenze EVF9338−EV User Manual

EDKVF93−04
.BNC
Ä.BNCä
Global Drive
Information for the operator of the machine
9300 vector 110 ... 200 kW
EVF9335−EV ... EVF9338−EV
Frequency inverter
0
X1
X3
+UGL1 L2 L3 PE BR1 BR2 U V W-UG
BR1, BR2
+UG, -UG
L1, L2, L3, PE
U, V, W
LO HI
GNDA1A2A3A4ST1ST25934763
28E1E32
E2E4E5391
X4
X5
7
62
34
33
K32
K31
5
1
5
1
1
5
X6
X11
X8
X9
X10
9300vec0180

Key for overview

Position Description
9300 vector frequency inverter

Connections and interfaces

Position Description
L1, L2, L3, PE Mains connection
+UG, −UG DC supply (only for the variants V210, V240, V270, V300)
BR1, BR2 Connection of brake resistor (only for the variants V210, V240, V270, V300)
U, V, W, PE Motor connection
X1 AIF interface (automation interface)
slot for communication module (e.g. keypad XT EMZ9371BC) X3 Jumper for setting the analog input signal at X6/1, X6/2
X4 Terminal strip for connection of system bus (CAN)
X5 Terminal strips for connection of digital inputs and outputs
X6 Terminal strips for connection of analog inputs and outputs
X8 Sub−D connector (male) for connection of incremental encoder with TTL level or sin/cos encoder and KTY ther-
X9 Sub−D connector (male) for connection of digital frequency input signal
X10 Sub−D connector (female) for connection of digital frequency output signal
X11 Terminal strip for connection of relay output KSR for "safe standstill"
mal sensor of the motor

Status displays

Position LED red LED green Operating status
Off On Controller is enabled
On On Mains is switched on and automatic start is inhibited
Off Blinking slowly Controller is inhibited
Off On Motor data identification is active
Blinking quickly Off Undervoltage or overvoltage
Blinking slowly Off Active fault
0Fig. 0Tab. 0

Contentsi

1 About this documentation 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Document history 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Target group 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Validity information 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 Conventions used 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5 Notes used 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Safety instructions 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 General safety and application notes for Lenze controllers 9 . . . . . . . . . . . . . . . . . .
2.2 Residual hazards 13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Parameter setting 14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Parameter setting with the XT EMZ9371BC keypad 14 . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1 General data and operating conditions 14 . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.2 Installation and commissioning 15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.3 Display elements and function keys 15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.4 Changing and saving parameters 17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.5 Loading a parameter set 19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.6 Transferring parameters to other standard devices 20 . . . . . . . . . . . . . . . .
3.1.7 Activating password protection 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.8 Diagnostics 23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.9 Menu structure 24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Troubleshooting and fault elimination 26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Display of operating data, diagnostics 26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.1 Display of operating data 26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2 Diagnostics 27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Troubleshooting 28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.1 Status display via LEDs at the controller 28 . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.2 Fault analysis with the history buffer 29 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Drive behaviour in the event of faults 30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4 Fault elimination 31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4.1 Drive errors 31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4.2 Controller in clamp operation 32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5 System error messages 35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.1 General error messages 35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.2 Resetting system error messages 40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
EDKVF93−04 EN 2.0

1 About this documentation

Note!
This documentation contains all the information required by the machine operator to run the drive controllers of the 9300 vector series installed in your machine/system.
You may make further use of the information contained in this documentation without asking Lenze for permission if you do not change the contents.

1.1 Document history

What is new / what has changed?
Materialnummer Version Beschreibung
.BNC 2.0 04/2010 TD23 Neuauflage wegen Neuorganisation des
13238412 1.0 07/2007 TD19 Erstausgabe
About this documentation
Document history
Unternehmens
1
Tip!
Documentation and software updates for further Lenze products can be found on the Internet in the "Services & Downloads" area under
http://www.Lenze.com

1.2 Target group

This documentation is intended for qualified personnel according to IEC 364.
Qualified, skilled personnel are persons who have the qualifications necessary for the work activities to be undertaken during the assembly, installation, comissioning, and operation of the product.
EDKVF93−04 EN 2.0
5
1
About this documentation
Validity information

1.3 Validity information

... 9300 vector frequency inverters as of nameplate data:
Controller type
EVF Frequency inverter
Type no. / power
400 V 500 V
9335
110 kW
9336
132 kW
9337
162 kW
9338
200 kW
Design
E Built−in unit
Version
V Vector−controlled frequency inverter
132 kW 160 kW 200 kW 250 kW
  Nameplate
Type EVF 93xx ˘ x V Vxx 1x 7x
EVF 93xx ˘ x V Vxx Vx 6x
L
Inverter Id.-No.: Prod.-No.: Type: Input: Output:
0045042000129567000005
33.9335VE.1A.70
33 . 9335VE . 1A . 70 . V030
Hans-Lenze-Strasse1 D-31855Aerzen Madein EC
Ser.-No.:
  
Variant Integrated RFI filter A
400 V
V030 400 V ·
V060 400 V ·
V110 400 V ··
V210 400 V / 500 V
V240 400 V / 500 V ·
V270 400 V / 500 V ·
V300 400 V / 500 V ··
Hardware version
Software version
Integrated brake transistor
6
EDKVF93−04 EN 2.0
About this documentation
Conventions used
1

1.4 Conventions used

This documentation uses the following conventions to distinguish between different types of information:
Type of information Identification Examples/notes
Spelling of numbers
Decimal separator language−dependentIn each case, the signs typical for the target
Warnings
UL warnings
UR warnings
Text
Program name » « PC software
Icons
Page reference Reference to another page with additional
 
language are used as decimal separators. For example: 1234.56 or 1234,56
Are only given in English.
For example: »Engineer«, »Global Drive Control« (GDC)
information For instance: 16 = see page 16
EDKVF93−04 EN 2.0
7
1
About this documentation
Notes used

1.5 Notes used

The following pictographs and signal words are used in this documentation to indicate dangers and important information:
Safety instructions
Structure of safety instructions:
Danger!
Pictograph and signal word Meaning
Danger!
Danger!
Stop!
(characterises the type and severity of danger)
Note
(describes the danger and gives information about how to prevent dangerous situations)
Danger of personal injury through dangerous electrical voltage.
Reference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken.
Danger of personal injury through a general source of danger.
Reference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken.
Danger of property damage.
Reference to a possible danger that may result in property damage if the corresponding measures are not taken.
Application notes
Pictograph and signal word Meaning
Note! Tip!
Important note to ensure troublefree operation
Useful tip for simple handling
Reference to another documentation
8
EDKVF93−04 EN 2.0
Safety instructions
General safety and application notes for Lenze controllers

2 Safety instructions

2.1 General safety and application notes for Lenze controllers

(in accordance with Low−Voltage Directive 2006/95/EC)
For your personal safety
Disregarding the following safety measures can lead to severe injury to persons and damage to material:
ƒ Only use the product as directed.
ƒ Never commission the product in the event of visible damage.
ƒ Never commission the product before assembly has been completed.
ƒ Do not carry out any technical changes on the product.
ƒ Only use the accessories approved for the product.
2
ƒ Only use original spare parts from Lenze.
ƒ Observe all regulations for the prevention of accidents, directives and laws
applicable on site.
ƒ Transport, installation, commissioning and maintenance work must only be carried
out by qualified personnel. – Observe IEC 364 and CENELEC HD 384 or DIN VDE 0100 and IEC report 664 or
DIN VDE 0110 and all national regulations for the prevention of accidents.
– According to the basic safety information, qualified, skilled personnel are persons
who are familiar with the assembly, installation, commissioning, and operation of the product and who have the qualifications necessary for their occupation.
ƒ Observe all specifications in this documentation.
– This is the condition for safe and trouble−free operation and the achievement of
the specified product features.
– The procedural notes and circuit details described in this documentation are only
proposals. It is up to the user to check whether they can be transferred to the particular applications. Lenze Automation GmbH does not accept any liability for the suitability of the procedures and circuit proposals described.
ƒ Lenze controllers (frequency inverters, servo inverters, DC speed controllers) and the
accessory components can include live and rotating parts − depending on their type of protection − during operation. Surfaces can be hot.
– Non−authorised removal of the required cover, inappropriate use, incorrect
installation or operation create the risk of severe injury to persons or damage to material assets.
– For more information, please see the documentation.
EDKVF93−04 EN 2.0
ƒ High amounts of energy are produced in the controller. Therefore it is required to
wear personal protective equipment (body protection, headgear, eye protection, ear protection, hand guard).
9
2
Safety instructions
General safety and application notes for Lenze controllers
Application as directed
Controllers are components which are designed for installation in electrical systems or machines. They are not to be used as domestic appliances, but only for industrial purposes according to EN 61000−3−2.
When controllers are installed into machines, commissioning (i.e. starting of the operation as directed) is prohibited until it is proven that the machine complies with the regulations of the EC Directive 98/37/EC (Machinery Directive); EN 60204 must be observed.
Commissioning (i.e. starting of the operation as directed) is only allowed when there is compliance with the EMC Directive (2004/108/EC).
The controllers meet the requirements of the Low−Voltage Directive 2006/95/EC. The harmonised standard EN 61800−5−1 applies to the controllers.
The technical data and supply conditions can be obtained from the nameplate and the documentation. They must be strictly observed.
Warning: Controllers are products which can be installed in drive systems of category C2 according to EN 61800−3. These products can cause radio interferences in residential areas. In this case, special measures can be necessary.
Transport, storage
Please observe the notes on transport, storage, and appropriate handling. Observe the climatic conditions according to the technical data.
Installation
The controllers must be installed and cooled according to the instructions given in the corresponding documentation.
The ambient air must not exceed degree of pollution 2 according to EN 61800−5−1. Ensure proper handling and avoid excessive mechanical stress. Do not bend any
components and do not change any insulation distances during transport or handling. Do not touch any electronic components and contacts.
Controllers contain electrostatically sensitive devices which can easily be damaged by inappropriate handling. Do not damage or destroy any electrical components since this might endanger your health!
10
EDKVF93−04 EN 2.0
Safety instructions
General safety and application notes for Lenze controllers
Electrical connection
When working on live controllers, observe the applicable national regulations for the prevention of accidents (e.g. VBG 4).
The electrical installation must be carried out according to the appropriate regulations (e.g. cable cross−sections, fuses, PE connection). Additional information can be obtained from the documentation.
The documentation contains information on the installation according to EMC (shielding, earthing, arrangement of filters, and installation of the cables). Also observe this information with regard to drive controllers labelled with CE marking. The manufacturer of the system or machine is responsible for the compliance of the limit values required in connection with EMC legislation. In order to observe the limit values for radio interference emissions effective at the installation site, you have to mount the drive controllers into housings (e. g. control cabinets). The housings have to enable an EMC−compliant structure. Particularly observe that, for instance, control cabinet doors preferably are metallically connected to the housing in a circumferential manner. Reduce openings or apertures through the housing to a minimum.
Lenze controllers can cause a DC current in the PE conductor. If a residual current device (RCD) is used for the protection in the case of direct or indirect contact on a three−phase supplied controller, only one residual current device of type B is permissible on the current supply side of the controller. If the controller is supplied with one phase, also a residual current device (RCD) of type A may be used. Apart from the use of a residual current device (RCD) also other protective measures can be used, like for instance isolation from the environment by double or reinforced insulation or isolation from the supply system by a transformer.
2
Operation
If necessary, systems including controllers must be equipped with additional monitoring and protection devices according to the valid safety regulations (e.g. law on technical equipment, regulations for the prevention of accidents). The controllers can be adapted to your application. Please observe the corresponding information given in the documentation.
After the controller has been disconnected from the supply voltage, all live components and power connections must not be touched immediately because capacitors can still be charged. Please observe the corresponding stickers on the controller.
All protection covers and doors must be shut during operation. Notes for UL−approved systems with integrated controllers: UL warnings are notes that
only apply to UL systems. The documentation contains special UL notes.
Safety functions
Special controller variants support safety functions (e.g. "safe torque off", formerly "safe standstill") according to the requirements of appendix I No. 1.2.7 of the EC Directive "Machinery" 98/37/EC, EN 954−1 category 3 and EN 1037. Strictly observe the notes on the safety functions given in the documentation on the respective variants.
Maintenance and servicing
The controllers do not require any maintenance if the prescribed operating conditions are observed.
EDKVF93−04 EN 2.0
11
2
Safety instructions
General safety and application notes for Lenze controllers
Disposal
Recycle metals and plastics. Dispose of printed circuit board assemblies according to the state of the art.
The product−specific safety and application notes given in these instructions must be observed!
12
EDKVF93−04 EN 2.0
Safety instructions
Residual hazards
2

2.2 Residual hazards

Protection of persons
ƒ Before working on the controller, check that no voltage is applied to the power
terminals: – The power terminals U, V, W, +U
least five minutes after disconnecting from the mains.
– The power terminals L1, L2, L3, U, V, W, +U
live when the motor is stopped.
ƒ The leakage current to earth (PE) is >3.5 mA. EN 50178 requires a fixed installation.
ƒ The heatsink of the controller has an operating temperature of > 80 °C:
– Direct skin contact causes burns.
ƒ During the parameter set transfer, the control terminals of the controller can
assume undefined states. – For this reason, the connectors X5 and X6 have to be unplugged before the
transfer is executed. This ensures that the controller is inhibited and all control terminals are in the defined state LOW".
Device protection
, −UG, BR1, BR2 and 101 ... 104 remain live for at
G
, −UG, BR1, BR2 and 101 ... 104 remain
G
ƒ Frequent mains switching (e.g. inching mode via mains contactor) can overload and
destroy the input current limitation of the controller. – Thus, at least five minutes have to pass between two switch−on processes. – In case of frequent, safety−related disconnections use the "safe torque off" safety
function (STO).
Motor protection
ƒ Certain drive controller settings can overheat the connected motor:
– E. g. long−time operation of the DC injection brake. – Long−time operation of self−ventilated motors at low speeds.
Protection of the machine/system
ƒ Drives can reach dangerous overspeeds (e. g. setting of high output frequencies in
connection with motors and machines not suitable for this purpose): – The drive controllers do not provide protection against such operating conditions.
For this purpose, use additional components.
EDKVF93−04 EN 2.0
13
3
Parameter setting
Parameter setting with the XT EMZ9371BC keypad General data and operating conditions

3 Parameter setting

3.1 Parameter setting with the XT EMZ9371BC keypad

Description
The keypad is available as an accessory. A full description of the keypad can be obtained from the Instructions included in the keypad delivery.
Plugging in the keypad
It is possible to plug the keypad into the AIF interface or remove it during operation.
As soon as the keypad is supplied with voltage, it carries out a self−test. The keypad is ready for operation if it is in display mode.
3.1.1 General data and operating conditions
dABbc
Menu
p
SHPRG
0
b
Code Para
MCTRL-NOUT
z
YZ
0050
50.00_Hz
T
V
00
y
S
U
ca
Feature Values
Dimensions
Width a 60 mm
Height b 73.5 mm
Depth c 15 mm
Environmental conditions
Climate
Storage IEC/EN 60721−3−1 1K3 (−25 ... +60 °C)
Transport IEC/EN 60721−3−2 2K3 (−25 ... +70 °C)
Operation IEC/EN 60721−3−3 3K3 (−10 ... +60 °C)
Enclosure IP 20
9371BC011
14
EDKVF93−04 EN 2.0
Parameter setting with the XT EMZ9371BC keypad
dABbc
0
1
2
3
3.1.2 Installation and commissioning
E82ZWLxxx
50
u
00
en M
e d o
0_
C ra
p
Pa
d
G R
0.0
P H
5
S
MCTRL-NOUT
T
z
S
YZ
y
EMZ9371BC
ABbc
00
Hz
V
U
dABbc
Menu
p
SHPRG
Code
00
0050
Para
GLOBAL DRIVE
Init
z
T
V
YZ
y
S
U
dABbc
Menu
p
SHPRG
Code Para
50.00_Hz
MCTRL-NOUT
z
YZ
y
E82ZBBXC
Parameter setting
3
Installation and commissioning
00
0050
T
V
S
U
d
z
YZ
y
d
z
YZ
y
0050
50.00 Hz
T
S
0050
50.00 Hz
T
S
00
20 %
V
U
00
20 %
V
U
Fig. 3−1 Installation and commissioning of XT EMZ9371BC keypad or E82ZBBXC diagnosis terminal
Connect keypad to the AIF interface on the front of the standard device. The keypad can be connected/disconnected during operation.
As soon as the keypad is supplied with voltage, it carries out a short self−test.
The operation level indicates when the keypad is ready for operation:
Current state of the standard deviceMemory location 1 of the user menu (C0517):
Code number, subcode number, and current value
Active fault message or additional status messageActual value in % of the status display defined in C0004
must be pressed to leave the operation level
3.1.3 Display elements and function keys
9371BC018
EDKVF93−04 EN 2.0
0 1
2 3
dABbc
Menu
p
SHPRG
Code
0050
Para
50.00_Hz
MCTRL-NOUT
z
YZ
T
00
V
4 5
6
7
8
y
S
U
9371BC002
Fig. 3−2 Display elements and function keys of the XT EMZ9371BC keypad
Displays
Status displays of standard device
Display Meaning Explanation
Ready for operation
15
3
Parameter setting
Parameter setting with the XT EMZ9371BC keypad Display elements and function keys
Acceptance of the parameters
Display Meaning Explanation
Parameter is accepted immediately  Standard device operates immediately with
SHPRG Parameter must be acknowledged with
SHPRG Parameter must be acknowledged in case of
None Display parameter Change is not possible
Active level
Display Meaning Explanation
Menu Menu level is active Select main menu and submenus
Code Code level is active Select codes and subcodes
Para Parameter level is active Change parameters in the codes or
None Operating level is active Display operating parameters
Short text
Display Meaning Explanation
alphanumericalContents of the menus, meaning of the codes
Number
Active level Meaning Explanation
Menu level Menu number Display is only active for operation with
Code level Four−digit code number
Number
Active level Meaning Explanation
Menu level Submenu number Display is only active for operation with
Code level Two−digit subcode number
Parameter value
Cursor
Function keys
Pulse inhibit is active Power outputs are inhibited
The set current limit is exceeded in motor or generator mode
Speed controller 1 in the limitation Drive is torque−controlled
(Only active for operation with standard devices of the 9300 series)
Active fault
the new parameter value

controller inhibit 
and parameters
In the operating level display of C0004 in % and the active fault
Parameter value with unit
In the parameter level, the digit above the cursor can be directly changed
For description see the following table
Standard device operates with the new parameter value after being acknowledged
Standard device operates with the new parameter value after the controller is enabled again
subcodes
standard devices of the 8200 vector or 8200 motec series
standard devices of the 8200 vector or 8200 motec series
16
EDKVF93−04 EN 2.0
Function keys
Note!
Shortcuts with : Press and hold , then press the second key in addition.
Parameter setting
Parameter setting with the XT EMZ9371BC keypad
Changing and saving parameters
3
Key
Menu level Code level Parameter level Operating level
Go to the "Short setup"

 
  
!
"
#
$
1)
menu and load predefined configurations
Change between menu items
Quick change between menu items
Change between main menu, submenu and code level
Deactivate the function of the key $, the LED in the key goes off
Inhibit the controller, the LED in the key is lit.
Reset fault (TRIP−Reset): 1. Remove the cause of malfunction
Only active for operation with standard devices of the 8200 vector or 8200 motec series
1)
Change to the parameter level
Change of code number
Quick change of code number
2. Press $
3. Press #
3.1.4 Changing and saving parameters
Function
Change to the operating level
Accept parameters when SHPRG or SHPRG is displayed
Change of digit via cursor
Quick change of digit via cursor
Cursor to the right
Cursor to the left
Change to the code level
Note!
Your settings have an effect on the current parameters in the main memory. You must save your settings in a parameter set so that they are not lost when the mains are connected.
If you only need one parameter set, save your settings as parameter set 1, since parameter set 1 is loaded automatically after mains connection.
Step Key
1. Select the menu   ! " Use the arrow keys to select the desired menu
2. Change to the code level ! Display of the first code in the menu
3. Select code or subcode   Display of the current parameter value
4. Change to the parameter level
5. When SHPRG is displayed, inhibit the controller
6. Change parameter
7. Accept the changed parameter
sequence
1)
$
A ! " Move cursor below the digit to be changed
B   Change of digit
   
Action
The drive coasts
Quick change of digit
EDKVF93−04 EN 2.0
17
3
Parameter setting
Parameter setting with the XT EMZ9371BC keypad Changing and saving parameters
Step
Display of SHPRG or SHPRG    Confirm change to accept the parameter
Display  − The parameter has been accepted immediately
8. Enable the controller, if required #
9. Change to the code level
10. Change further parameters Restart the "loop" with step 1. or 3.
11. Save changed parameters
Select the parameter set in which the parameters are to be saved permanently
12.
Change to the code level
13. Set parameters for another parameter set
1)
The function of the $ key can be programmed: C0469 = 1: Controller inhibit C0469 = 2: Quick stop (Lenze setting)
sequence
1)
A Display of the operating level
B Display of the code with changed parameter
A   ! " Select the code C0003 "PAR SAVE" in the menu
B Change to the parameter level
C Save as parameter set 1:
D   When "OK" is displayed, the settings are permanently
A Display of the operating level B Display of C0003 "PAR SAVE"
ActionKey
Display "OK"
The drive runs again
"Load/Store"
Display "0" and "READY"
ð Set "1" "Save PS1" Save as parameter set 2:
ð Set "2" "Save PS2" Save as parameter set 3:
ð Set "3" "Save PS3" Save as parameter set 4:
ð Set "4" "Save PS4"
saved in the selected parameter set.
Restart the "loop" with step 1. or 3.
18
EDKVF93−04 EN 2.0
Parameter setting
Parameter setting with the XT EMZ9371BC keypad
Loading a parameter set
3
3.1.5 Loading a parameter set
The keypad serves to load a saved parameter set into the main memory when the controller is inhibited. After the controller is enabled, it operates with the new parameters.
Danger!
ƒ When a new parameter set is loaded, the controller is reinitialised and acts
as if it had been connected to the mains: – System configurations and terminal assignments can be changed. Make
sure that your wiring and drive configuration comply with the settings of the parameter set.
ƒ Only use terminal X5/28 as source for the controller inhibit! Otherwise the
drive may start in an uncontrolled way when switching over to another parameter set.
Note!
ƒ After switching on the supply voltage, the controller always loads parameter
set 1 into the main memory.
ƒ It is also possible to load other parameter sets into the main memory via the
digital inputs or bus commands.
Step Key
1. Inhibit controller Terminal X5/28 = LOW
2. Load the saved parameter set into the main memory
Select the parameter set to be loaded
3.
Change to the code level
4. Enable controller Terminal X5/28 = HIGH
sequence
A   ! " Select the code C0002 "PAR LOAD" in the menu
B Change to the parameter level
C Load parameter set 1:
D   "RDY" goes off. The parameter set is loaded completely
A Display of the operating level B Display of C0002 "PAR LOAD"
Action
"Load/Store"
The active parameter set is displayed, e. g. display "0" and "Load Default" If you want to restore the delivery status, proceed with D
ð Set "1" "Load PS1" Load parameter set 2:
ð Set "2" "Load PS2" Load parameter set 3:
ð Set "3" "Load PS3" Load parameter set 4:
ð Set "4" "Load PS4"
into the main memory if "RDY" is displayed again.
The drive is running with the settings of the loaded parameter set
EDKVF93−04 EN 2.0
19
3
Parameter setting
Parameter setting with the XT EMZ9371BC keypad Transferring parameters to other standard devices
3.1.6 Transferring parameters to other standard devices
Parameter settings can be easily copied from one standard device to another by using the keypad.
For this purpose use the "Load/Store" menu
Danger!
During the parameter transfer from the keypad to the standard device the control terminals can adopt undefined states!
Therefore the plugs X5 and X6 must be disconnected from the standard device before the transfer takes place. This ensures that the controller is inhibited and all control terminals have the defined state "LOW".
Copying parameter sets from the standard device into the keypad
Note!
After copying the parameter sets into the XT keypad (C0003 = 11), always the parameter set that was loaded last via C0002 is activated.
Like this the current parameters also remain active after copying:
ƒ Save the current parameters in the parameter set before copying and load
this parameter set in the controller via C0002.
Step Key
1. Connect the keypad to standard device 1
2. Inhibit controller Terminal X5/28 = LOW
3. Select C0003 in the "Load/Store" menu
4. Change to the parameter level
5. Copy all parameter set into the keypad
6. Start copying
7.
Change to the code level
8. Enable controller Terminal X5/28 = HIGH
9. Remove keypad from standard device 1
A B
sequence
!"

Action
The drive coasts. Select code C0003 "PAR SAVE" in the "Load/Store"
menu using the arrow keys.
Display "0" and "READY"
The settings saved in the keypad are overwritten.
Set "11" "Save extern"
The "RDY" status display goes off. As parameter value "BUSY" is displayed. If "BUSY" goes off after approx. one minute, all parameter sets were copied into the keypad. The "RDY" status display is lit.
Display of the operating level Display C0003 and "PAR SAVE"
20
EDKVF93−04 EN 2.0
Parameter setting
Parameter setting with the XT EMZ9371BC keypad
Transferring parameters to other standard devices
Copying parameter sets fom keypad into the standard device
3
Step Key
1. Connect the keypad to standard device 2
2. Inhibit controller Terminal X5/28 = LOW
3. Pull the plugs X5 and X6 All control terminals have the defined "LOW" status.
4. Select C0002 in the "Load/Store" menu
5. Change to the parameter level
6. Select the correct copy function The settings saved in the standard device are
l Copy all parameter sets available into the
EEPROM of the standard device and save them permanently.
l Copy individual parameter sets into the main
memory of the standard device.
7. Start copying
8.
Change to the code level
9. l If the function "Copy all parameter
sets into the EEPROM" (C0002 = 20) is selected, they might have to be loaded in the main memory manually.
l If the function "Copy individual
parameter sets into the main memory" (C0002 = 1x) is selected, they might have to be saved permanently in the EEPROM manually.
10. Plug in plugs X5 and X6
11. Enable controller Terminal X5/28 = HIGH
A B
sequence
!"

!"
Action
The "IMP" status display is it. The drive coasts
Select code C0002 "PAR LOAD" in the "Load/Store" menu using the arrow keys.
The active parameter set is shown, e. g. display "0" and "Load Default"
overwritten.
l The parameter set that was active before copying is
overwritten.
l The parameters are not yet active after copying.
Select parameter set and load it in the main memory. 19
Set "20" "ext −> EEPROM"
Copy parameter set 1 into the main memory: Set ð "11" "Load ext PS1"
Copy parameter set 2 into the main memory: Set ð "12" "Load ext PS2"
Copy parameter set 3 into the main memory: Set ð "13" "Load ext PS3"
Copy parameter set 4 into the main memory: Set ð "14" "Load ext PS4"
The "RDY" status display goes off. As parameter value "BUSY" is displayed. If "BUSY" goes off, the parameter sets selected were copied into the standard device. The "RDY" status display is lit.
Display of the operating level Display C0002 and "PAR LOAD" Select code C0003 "PAR SAVE" in the "Load/Store"
menu using the arrow keys and store the contents of the main memory permanently.
The drive is running with the new settings.
EDKVF93−04 EN 2.0
21
3
Parameter setting
Parameter setting with the XT EMZ9371BC keypad Activating password protection
3.1.7 Activating password protection
Note!
ƒ If the password protection is activated (C0094 = 1 ... 9999), you only have
free access to the user menu.
ƒ To access the other menus, you must enter the password. By this, the
password protection is annulled until you enter a new password.
ƒ Please observe that the password−protected parameters can be overwritten
as well when transferring the parameter sets to other standard devices. The password is not transferred.
ƒ Do not forget your password! If you have forgotten your password, it can
only be reset via a PC or a bus system!
Activate password protection
Step Key
sequence
1. Select the "USER menu"   ! " Change to the user menu using the arrow keys
2. Change to the code level ! Display of code C0051 "MCTRL−NACT"
3. Select C0094 Display of code C0094 "Password"
4. Change to the parameter level Display "0" = no password protection
5. Set password
A Select password (1 ... 9999)
B   Confirm password
6. Change to the code level
A Display of the operating level
B Display of C0094 and "Password"
7. Change to the "USER menu" " " 
The password protection is active now. You can only quit the user menu if you re−enter the password and confirm it with
Action
.
Remove password protection
Step Key
1. Change to the code level in the user menu
2. Select C0094 Display of code C0094 "Password"
3. Change to the parameter level Display "9999" = password protection is active
4. Enter password
5. Change to the code level
The password protection is deactivated now. All menus can be freely accessed again.
sequence
!
A Set valid password
B   Confirm
A Display of the operating level
B Display of C0094 and "Password"
Action
The password protection is deactivated by entering the password once again.
22
EDKVF93−04 EN 2.0
3.1.8 Diagnostics
In the "Diagnostic" menu the two submenus "Actual info" and "History" contain all codes for
ƒ monitoring the drive
ƒ fault/error diagnosis
In the operating level, more status messages are displayed. If several status messages are active, the message with the highest priority is displayed.
Priority Display Meaning
1 GLOBAL DRIVE INIT Initialisation or communication error between
2 XXX − TRIP Active TRIP (contents of C0168/1) 3 XXX − MESSAGE Active message (contents of C0168/1) 4
Special device states:
5
Source for controller inhibit (the value of C0004 is displayed simultaneously): STP1
STP3 Operating module or LECOM A/B/LI STP4 INTERBUS or PROFIBUS−DP STP5
STP6 C0040
6
Source for quick stop (QSP): QSP−term−Ext The MCTRL−QSP input of the MCTRL function block is on HIGH signal. QSP−C0135 Operating module or LECOM A/B/LI QSP−AIF INTERBUS or PROFIBUS−DP QSP−CAN
7 XXX − WARNING Active warning (contents of C0168/1) 8 xxxx Value below C0004
Parameter setting
Parameter setting with the XT EMZ9371BC keypad
Diagnostics
keypad and controller
Switch−on inhibit
9300 servo: Terminal X5/28 ECSxS/P/M/A: Terminal X6/SI1
9300 servo, ECSxA/E: System bus (CAN) ECSxS/P/M: MotionBus (CAN)
9300 servo, ECSxA: System bus (CAN) ECSxS/P/M: MotionBus (CAN)
3
EDKVF93−04 EN 2.0
23
3
Parameter setting
Parameter setting with the XT EMZ9371BC keypad Menu structure
3.1.9 Menu structure
For simple, user−friendly operation, the codes are clearly arranged in function−related menus:
Main menu Submenus Description
Display Display
User−Menu Codes defined in C0517
Code list All available codes
ALL All available codes listed in ascending order (C0001 ... C7999)
PS 1 Codes in parameter set 1 (C0001 ... C1999)
PS 2 Codes in parameter set 2 (C2001 ... C3999)
PS 3 Codes in parameter set 3 (C4001 ... C5999)
PS 4 Codes in parameter set 4 (C6001 ... C7999)
Load/Store Parameter set management
Diagnostic Diagnostic
Actual info Display codes to monitor the drive
History Fault analysis with history buffer
Short setup Quick configuration of predefined applications
Parameter set transfer, restore delivery status
Configuration of the user menu
The predefined applications depend on the type of the standard device (frequency inverter, servo inverter, position controller, ...)
Main FB Configuration of the main function blocks
NSET Setpoint processing
NSET−JOG Fixed setpoints
NSET−RAMP1 Ramp function generator
MCTRL Motor control
DFSET Digital frequency processing
DCTRL Internal control
Terminal I/O Connection of inputs and outputs with internal signals
AIN1 X6.1/2 Analog input 1
AIN2 X6.3/4 Analog input 2
AOUT1 X6.62 Analog output 1
AOUT2 X6.63 Analog output 2
DIGIN Digital inputs
DIGOUT Digital outputs
DFIN Digital frequency input
DFOUT Digital frequency output
State bus State bus (not with 9300 frequency inverter)
Controller Configuration of internal control parameters
Speed Speed controller
Current Current controller or torque controller
Phase Phase controller (not with 9300 frequency inverter)
Motor/Feedb. Input of motor data, configuration of speed feedback
Motor adj Motor data
Feedback Configuration of feedback systems
Monitoring Configuration of monitoring functions
24
EDKVF93−04 EN 2.0
Parameter setting
Parameter setting with the XT EMZ9371BC keypad
Menu structure
DescriptionSubmenusMain menu Description
DisplayDisplay
LECOM/AIF Configuration of operation with communication modules
LECOM A/B Serial interface
AIF interface Process data
Status word Display of status words
System bus Configuration of system bus (CAN)
Management CAN communication parameters
CAN−IN1
CAN−OUT1
CAN−IN2
CAN−OUT2
CAN−IN3
CAN−OUT3
Status word Display of status words
FDO Free digital outputs
Diagnostic CAN diagnostic
FB config Configuration of function blocks
CAN object 1
CAN object 2
CAN object 3
3
Func blocks Parameterisation of function blocks
The submenus contain all available function blocks
FCODE Configuration of free codes
Identify Identification
Drive Software version of standard device
Op Keypad Software version of keypad
EDKVF93−04 EN 2.0
25
4
Troubleshooting and fault elimination
Display of operating data, diagnostics Display of operating data

4 Troubleshooting and fault elimination

4.1 Display of operating data, diagnostics

4.1.1 Display of operating data
Description
Important operating parameters are measured by the controller. They can be displayed with the keypad or PC.
Some operating data can be calibrated to be displayed or selected directly with the unit of the process quantity (e.g. pressure, temperature, speed).
Note!
The calibration always affects all specified codes simultaneously.
Codes for parameter setting
Code Possible settings IMPORTANT
No. Name Lenze Selection
C0051 MCTRL−NACT −36000 {1 rpm} 36000 Actual speed value, function block
C0052 MCTRL−Umot 0 {1 V} 800 Motor voltage, function block MCTRL
C0053 UG−VOLTAGE 0 {1 V} 900 DC−bus voltage, function block MCTRL
C0054 Imot 0.0 {0.1 A} 5000.0 Actual motor current, function block
C0061 Heatsink temp 0 {1 °C} 100 Heatsink temperature
C0063 Mot temp 0 {1 °C} 200 Motor temperature
MCTRL
l Read only
l Read only l MCTRL−VACT = 100 % = C0090
l Read only l MCTRL−DCVOLT = 100 % = 1000 V
MCTRL
l Read only l MCTRL−IACT = 100 % = C0022
l Read only l If the temperature of the heatsink
> 85 °C, the controller sets TRIP OH
l Early warning is possible via OH4,
temperature is set in C0122
l Read only l Monitoring of the motor
temperature must be activated.
l KTY at X8/5, X8/8:
– At 150 °C, TRIP OH3 is set – Early warning is possible via OH7,
temperature is set in C0121
l PTC, thermal contact at T1, T2:
– Release sets TRIP or warning OH8
26
EDKVF93−04 EN 2.0
Troubleshooting and fault elimination
Display of operating data, diagnostics
Diagnostics
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0064 Utilization 0 {1 %} 150 Device utilisation I×t
l Read only l Device utilisation during the last
180 s of operating time
l C0064 > 100 % releases warning
OC5
l C0064 > 140 % limits the output
current of the controller to 67 % of the maximum current in C0022
C0150 Status word
Bit00 Bit08 Status code Bit01 IMP Bit09 Status code Bit02 Bit03 Bit04 Bit05 Bit06 Bit07
Bit10 Status code — Bit11 Status code — Bit12 Warning — Bit13 Message n = 0 Bit14 — CINH Bit15
Read only Decimal status word for networking via automation interface (AIF)
l Binary interpretation indicates the
bit states
4
4.1.2 Diagnostics
Description
Display codes for diagnostics
Codes for parameter setting
Code Possible settings IMPORTANT
No. Name Lenze Selection
C0093 Drive ident
C0099 S/W version
0 Invalid Defective power section 1 None No power section 14
... 20
21 ... 28
9321 ... 9333
x.y x
y
9335VC 400V ... 9383VC 400V
9334VC 500V ... 9383VC 500V
9321 VC ... 9333VC
Main version Subversion
Controller identification
l Read only
Display of the controller used
Software version
l Read only
EDKVF93−04 EN 2.0
27
4
Troubleshooting and fault elimination
Troubleshooting Status display via LEDs at the controller

4.2 Troubleshooting

Detecting breakdowns
A breakdown can be detected quickly via the LEDs at the controller or via the status information at the keypad.
Analysing errors
Analyse the error using the history buffer. The list of fault messages gives you advice how to remove the fault. (% 35)
4.2.1 Status display via LEDs at the controller
During operation the operating status of the controller is shown by 2 LEDs.
LED Operating status
Red Green
Off On Controller is enabled
On On Mains is switched on and automatic start is
Off Blinking slowly Controller is inhibited
Off On Motor data identification is being performed
Blinking quickly Off Undervoltage
Blinking slowly Off Active fault
inhibited
28
EDKVF93−04 EN 2.0
Troubleshooting and fault elimination
Troubleshooting
Fault analysis with the history buffer
4
4.2.2 Fault analysis with the history buffer
Retracing faults
Faults can be retraced via the history buffer. Fault messages are stored in the 8 memory locations in the order of their appearance.
The memory locations can be retrieved via codes.
Structure of the history buffer
Code Memory location Entry Note
C0168/1 C0169/1 C0170/1 Memory location 1 Active fault
C0168/2 C0169/2 C0170/2 Memory location 2 Last fault
C0168/3 C0169/3 C0170/3 Memory location 3 Last but one fault
C0168/4 C0169/4 C0170/4 Memory location 4 Last but two fault
C0168/5 C0169/5 C0170/5 Memory location 5 Last but three fault
C0168/6 C0169/6 C0170/6 Memory location 6 Last but four fault
C0168/7 C0169/7 C0170/7 Memory location 7 Last but five fault
C0168/8 C0169/8 C0170/8 Memory location 8 Last but six fault
Explanations regarding the codes
C0168 Fault indication and response
l The entry is effected as a LECOM error number l If several faults with different responses occur at the same time:
– Only the fault with the highest priority response is entered (1. TRIP, 2. message,
3. warning).
l If several faults with the same response (e.g. 2 messages) occur at the same time:
– Only the fault which occurred first is entered.
C0169 Time of fault occurence
l The reference time is provided by the power−on time meter (C0179). l If the same fault occurs several times in succession, only the time of the last occurrence
is stored.
C0170 Fault frequency
l Only the time of the last occurrence is stored.
If the fault is no longer pending or has been acknowledged:
l The contents of the memory locations
l The content of memory location 8 is
l Memory location 1 is deleted (= no active
1 ... 7 are shifted "up" to the next memory location.
deleted from the history buffer and cannot be retrieved anymore.
fault).
EDKVF93−04 EN 2.0
Clear history buffer
Set C0167=1 to clear the history buffer.
29
4
Troubleshooting and fault elimination
Drive behaviour in the event of faults Fault analysis with the history buffer

4.3 Drive behaviour in the event of faults

The controller responds differently to the three possible fault types TRIP, message, or warning:
TRIP
TRIP (display in keypad XT:  )
ƒ Switches the power outputs U, V, W to a high−resistance state until TRIP reset is
executed.
ƒ The fault indication is entered into the history buffer as "current fault" in C0168/1.
ƒ The drive coasts without any control!
ƒ After TRIP reset (% 40):
– The drive travels along the ramps to its setpoint. – The fault indication is moved to C0168/2 as "last fault".
Messages
Message (display in keypad XT:  )
ƒ Switches the power outputs U, V, W to a high−resistance state.
ƒ The fault indication is entered into the history buffer as "current fault" in C0168/1.
ƒ In case of a fault £5 s:
– The drive coasts without any control as long as the message is active! – If the message is not active anymore, the drive travels to its setpoint with
maximum torque.
ƒ In case of a fault > 5 s:
– The drive coasts without any control as long as the message is active! – If the message is not active anymore, the drive travels to its setpoint along the
adjusted ramps.
ƒ If the message is not active anymore, the fault indication is moved to C0168/2 as
"last fault".
Warnings
"Heatsink overtemperature" (keypad XT:OH  )
ƒ The drive continues to travel in a controlled way!
ƒ The warning signal goes off when the fault is not active anymore.
"Error in motor phase" (keypad XT:LP1)
"PTC monitoring" (keypad XT:OH51)
30
ƒ The drive continues to travel in a controlled way!
ƒ The fault indication is entered into the history buffer as "current fault" in C0168/1.
ƒ After TRIP reset, the fault indication is moved to C0168/2 as "last fault".
EDKVF93−04 EN 2.0
Troubleshooting and fault elimination
Fault elimination

4.4 Fault elimination

4.4.1 Drive errors
Malfunction Cause Remedy
An asynchronous motor with feedback rotates in an uncontrolled manner and with low speed
Motor does not rotate although the controller is enabled ( is off) and a speed setpoint has been specified.
The monitoring of the motor phases (LP1) does not respond if a motor phase is interrupted, although C0597 = 0 or 2
If during high speeds DC−injection braking (GSB) is activated, the fault OC1 (TRIP) or OU (TRIP) occurs
The motor phases are reversed so that the rotating field of the motor is not identical with the rotating field of the feedback system. The drive shows the following behaviour:
l V/f characteristic control (C0006 = 5)
– The motor rotates faster than the speed setpoint by
the value set in C0074 (influence of the speed controller, Lenze setting 10 % of n controller is enabled, it does not stop at zero speed setpoint or quick stop (QSP).
– The final motor current depends, among other
things, on the set value of the V and can rise to I fault message OC5.
l Vector control (C0006 = 1)
– The motor rotates slowly with maximum slip speed
(depending on motor data and maximum current) and does not react to a speed setpoint. The direction of rotation, however, is determined by the sign of the speed setpoint.
– The motor current rises up to I
may activate the fault message OC5 with a time delay.
The two terminal strips X5 are reversed. Since X5/A1 and X5/28 face each other, the controller can be enabled if the control terminals are internally supplied. All other connections, however, are assigned incorrectly so that the motor cannot start.
The function block MLP1 is not entered into the processing table.
During DC−injection braking the controller sets pulse inhibit for a short time (DCTRL−IMP) to reduce the magnetisation in the motor before a DC voltage is injected into the motor. At high speeds (e. g. in case of mid−frequency motors) the residual voltage which develops from the residual magnetism and high speed can generate such a high motor current that OC1 or OU are activated.
(C0022). This may activate the
max
). After the
max
boost (C0016)
min
(C0022). This
max
l Check motor cable for correct phase
relation.
l If possible, operate the motor with
deactivated feedback (C0025 = 1) and check the direction of rotation of the motor.
Check the position of the terminal strips:
l If you look at the connection unit in
reading direction, the left terminal strip X5 must be connected with the input signals and the right terminal strip X5 must be connected with the output signals.
Enter the function block MLP1 into the processing table. The function block MLP1 requires 30 ms of calculating time.
Prolong the duration of the pulse inhibit:
l Connect the output signal DCTRL−IMP
to the function block TRANSx and adjust the desired switch−off time there (usually 500 ms). If DCTRL−CINH1 is set to HIGH, the duration of the pulse inhibit is prolonged by the time adjusted.
4
Drive errors
EDKVF93−04 EN 2.0
31
4
4.4.2 Controller in clamp operation
Troubleshooting and fault elimination
Fault elimination Controller in clamp operation
The clamp operation is a permissible operating mode. But since, however, pulse inhibit is set again and again, the controller cannot provide the optimum power.
If the output power is optimal, the output current mainly is right below the clamp threshold.
9300vec110
Fig. 4−1 Output current when starting a motor with high load (shown with the oscilloscope in GDC)
Clamp threshold
Output current
Function
1. When the output current reaches 2.25 × I
2. The controller sets pulse inhibit for a short time. The motor current decreases as a function of the inductance in the motor circuit.
– An internal counter is increased by the value one.
3. After max. 250 m s the pulse inhibit is deactivated.
4. If a software clamp reoccurs within 2 s, the internal counter is again increased by the value one. Otherwise the counter is set to zero.
– If the counter reaches the value 4300, OC3 (TRIP) is activated.
, a software clamp is activated.
r
32
EDKVF93−04 EN 2.0
Troubleshooting and fault elimination
Fault elimination
Controller in clamp operation
If the DC−bus voltage (UDC) exceeds the switch−off threshold OU, pulse inhibit will be set. At the same time, an internal timer for a delay time (C0912) will be started.
Pulse inhibit will be reset, if the voltage falls below the switch−on threshold OU and the delay time has elapsed.
Thresholds for DC−bus overvoltage (OU)
Types EVF93xx−EVV210, EVF93xx−EVV240, EVF93xx−EVV270 and EVF93xx−EVV300
Mains voltage range C0173 Switch−off threshold OU Switch−on threshold OU
< 400 V Operation with or without
400 V Operation with or without
460 V Operation with or without
480 V Brake transistor 3 770 V 755 V
480 V Brake transistor 4 800 V 785 V
500 V Operation with or without
*
Lenze setting
brake transistor
brake transistor
brake transistor
brake transistor
0 770 V 755 V
*
1
2 770 V 755 V
5 900 V 885 V
770 V 755 V
4
Types EVF93xx−EV, EVF93xx−EVV060 and EVF93xx−EVV110
Mains voltage range C0173 Switch−off threshold OU Switch−on threshold OU
400 V Operation with or without
brake transistor
Read only 700 V 685 V
Codes for parameter setting
Code Possible settings IMPORTANT
No. Name Lenze Selection
C0912 OV delay time à {1 ms} − Delay time of the pulse enable after
an OU message
à Depending on C0082, C0086,
C0087, C0088, C0089, C0090, C0091, C0092 A change of one of the codes resets C0912 to the time of the selected motor
l The time is derived from the
double rotor time constant
EDKVF93−04 EN 2.0
33
4
Troubleshooting and fault elimination
Fault elimination Controller in clamp operation
Adjustment
U
DC
 
IMP
Fig. 4−2 Influence of the delay time (C0912)
01
t < C0912
t C0912³
Switch−off threshold OU
Switch−on threshold OU The period of time between exceeding the switch−off threshold OU and undershooting the
switch−on threshold OU equals or is higher than the delay time set in C0912. After undershooting the switch−on threshold OU, the pulse inhibit is deactivated.
The period of time between exceeding the switch−off threshold OU and undershooting the
switch−on threshold OU is lower than the delay time set in C0912. The pulse inhibit is deactivated after the delay time in C0912 has elapsed.
t = C0912
9300vec142
ƒ The delay time in [ms] is set under C0912. The Lenze setting can be changed by the
factor 0.5 ... 2.
34
EDKVF93−04 EN 2.0
Troubleshooting and fault elimination
System error messages
General error messages
4

4.5 System error messages

4.5.1 General error messages
Note!
If you use GDC or a fieldbus module to retrieve the fault (C0168/x), the error message will be represented by an error number.
Display Error number
x = 0: TRIP x = 1: Message x = 2: Warning
−−− −−− No fault
CCr x071 System fault
CE0 x061 Communication
CE1 x062 Communication
CE2 x063 Communication
CE3 x064 Communication
CE4 x065 BUS−OFF state Controller has received too many
EEr x091 External fault
H05 x105 Internal fault Contact Lenze
H07 x107 Wrong power
Error Cause Remedy
error
error at the process data input object CAN−IN1
error at the process data input object CAN−IN2
error at the process data input object CAN−IN3
(TRIP−Set)
stage
Processor is overloaded or there is a fault in the program processing
Strong interference on control cables Shield control cables
Ground or earth loops in the wiring Check wiring
Fault during transmission of control commands via automation interface X1
CAN−IN1 object receives faulty data, or communication is interrupted
CAN−IN2 object receives faulty data, or communication is interrupted
CAN−IN3 object receives faulty data, or communication is interrupted
incorrect telegrams via system bus X4, and has disconnected from the bus
A digital input assigned with TRIP−set function has been activated (in the most basic configurations the input X5/E4 is LOW−active and linked with the TRIP−set function)
The two terminal strips at X5 are reversed
During initialisation of the controller, a wrong power stage was detected
Reduce processor load. Remove function blocks that are not needed from the processing table
Plug in automation module firmly, bolt down, if necessary
l Check cable at X4 l Check sender l Increase monitoring time under
C0357/1 if necessary
l Check cable at X4 l Check sender l Increase monitoring time under
C0357/2 if necessary
l Check cable at X4 l Check sender l Increase monitoring time under
C0357/3 if necessary
l Check wiring l Check bus termination (if any) l Check shield contact of the cables l Check PE connection l Check bus load l Reduce baud rate (observe cable
length)
l Check external encoder l Check signal at the digital input
X5/E4: – Either connect HIGH level or – Change polarity in C0114 to
HIGH−active. CAUTION! When changing to HIGH level, the wire−break protection gets lost.
Check the position of the terminal strips:
l If you look at the connection unit in
reading direction, the left terminal strip X5 must be connected with the input signals and the right terminal strip X5 must be connected with the output signals.
Contact Lenze
EDKVF93−04 EN 2.0
35
4
Troubleshooting and fault elimination
System error messages General error messages
Display
H10 x110 Sensor fault −
H11 x111 Sensor fault −
ID1 x140 Error during motor
ID2 x141 Error during motor
LP1 x032 Motor phase
LU x030 Undervoltage DC bus voltage is smaller than the value
NMAX x200 Maximum system
OC1 x011 Overcurrent
x = 0: TRIP x = 1: Message x = 2: Warning
heatsink temperature
temperature inside the device
data identification
data identification
failure
speed exceeded (C0596)
(motor current >
2.25−fold rated controller current, hardware monitoring)
Sensor of the heatsink temperature detection indicates undefined values
Sensor of the internal temperature detection indicates undefined values
l No motor connected l Stator resistance too high l Controller inhibited externally
Motor too small l Check entered motor data
Controller inhibited externally Enable controller and repeat motor data
A current−carrying motor phase has failed
The current limit is set too high Set a lower current limit value under
This monitoring is not suitable for field frequencies >480 Hz and synchronous servo motors
set under C0173
Active load too high Check drive dimensioning
Drive is not speed−controlled, torque excessively limited
Current speed is detected incorrectly Check parameter setting of the
Short circuit/earth fault l Remove cause of short circuit/earth
Capacitive charging current of the motor cable too high (especially with lower powers)
Acceleration/deceleration times too short in proportion to the load (C0012, C0013, C0105)
RemedyCauseErrorError number
Contact Lenze
l Fault message can only be reset by
mains switching
Contact Lenze
l Fault message can only be reset by
mains switching
l Check motor connection l Check motor data entry l Enable controller and repeat motor
data identification. The controller enable must be pending continuously until the end of the identification process.
– When setting parameters with
Global Drive Control, use the input assistant for motor data
l The measurements for the inverter
error characteristic and the stator resistance are correct (save measured values in C0003). In the operating mode U/f characteristic control, the motor data identification can be completed.
identification. The controller enable must be pending continuously until the end of the identification process.
l Check motor l Check supply cables
C0599
Deactivate monitoring with C0597= 3
l Check mains voltage l Check supply module
If required, increase torque limit
incremental encoder (C0025)
fault
l Check motor and cable l If required, measure the insulation
resistance
Use shorter or low−capacitance motor cable
l Increase the gain (P component) of
the current controller (C0075)
l Reduce integral−action time (integral
action component) of the Imax controller (C0076)
36
EDKVF93−04 EN 2.0
Troubleshooting and fault elimination
System error messages
General error messages
4
Display
x = 0: TRIP x = 1: Message x = 2: Warning
OC2 x012 Earth fault
OC3 x013 Overload during
acceleration
OC5 x015 I × t overload
RemedyCauseErrorError number
The drive is connected to the coasting machine. The coasting is caused by a short−time pulse inhibit, e.g. at
l OU (overvoltage in the DC bus) l external or internal controller inhibit
l Encoder error l Tracks for encoder feedback of the
motor speed are reversed
DC−injection braking at high speeds l See 31
One of the motor phases has earth contact
Excessive capacitive charging current of the motor cable
Acceleration/deceleration times too short in proportion to the load (C0012, C0013, C0105)
The utilisation of the controller exceeds 100 % (C0064 > 100 %)
The utilisation of the controller exceeds 110 % (C0064 > 110 %)
l The maximum current is reduced
Reversed motor phases when operating with feedback or reversed encoder tracks so that the direction of rotation has changed
l Activate flying restart circuit l Operate with speed feedback in the
vector control operating mode
l Check wiring of the encoder l In case of drive problems with
activated feedback, the feedback can be analysed. Here, the signal of the feedback is not used for control. For this test the function block DFIN must be entered into the processing table. In the Lenze setting, DFIN is entered at position 1 of the processing table (C0465/1 = 200). – Deactivate feedback with
C0025 = 1
– Connect feedback at the digital
frequency input DFIN (X9)
– Set DFIN constant (C0425) to the
number of increments of the encoder
– In C0426, the speed detected by
the encoder is indicated
l Check motor l Check supply cables
Use motor cable which is shorter or of lower capacitance
l Increase the gain (P component) of
the current controller (C0075)
l Reduce integral−action time (integral
action component) of the I controller (C0076)
l Increase ramp times l 32, "controller in clamp operation
(fault OC3)"
Check drive dimensioning
l The utilisation of the controller is
calculated from the mean value of the motor current over a time of 180 s. When operating with rated power (150 % overload capacity), the controller can be operated at a utilisation of up to 100 %.
l When C0064 = 95 %, the warning is
cancelled.
Check drive dimensioning
l When C0064 = 95 %, the reduction of
the maximum current is cancelled. The warning is cancelled.
l NOTE: Operation at increased rated
power (120 % overload capacity) is not possible.
l Check the motor cable connection for
correct phase relation
l If possible, operate the motor with
deactivated feedback (C0025 = 1) and check the direction of rotation of the motor.
l See also 31
max
EDKVF93−04 EN 2.0
37
4
Troubleshooting and fault elimination
System error messages General error messages
Display
OH x050 Heatsink
OH3 x053 Motor temperature
OH4 x054 Heatsink
OH7 x057 Motor temperature
OH8 x058 PTC at terminals
OU x020 Overvoltage in the
PEr x074 Program fault An error has been detected in the
PI x079 Initialisation error l A fault was detected during transfer
PR0 x075 Parameter set error Error while loading a parameter set. The
PR1 PR2 PR3 PR4
Sd3 x083 Encoder error at X9
x = 0: TRIP x = 1: Message x = 2: Warning
x072 x073 x077 x078
temperature is higher than the value set in the controller
is higher than the value set in the controller
temperature is higher than the value set in C0122
is higher than the value set in C0121
T1, T2 indicates motor overheating
DC bus
Parameter set error l Fault while loading a parameter set
Ambient temperature Tu > 40 °C or 50 °C l Allow controller to cool and ensure
Heatsink very dirty Clean heatsink
Wrong mounting position Change mounting position
Motor too hot because of excessive current or frequent and too long acceleration
No KTY is connected to X8 Connect KTY or switch off monitoring
Ambient temperature Tu > 40 °C or 50 °C.
Heatsink very dirty Clean heatsink
Wrong mounting position Change mounting position
The value entered in C0122 is too low Enter higher value
Motor too hot because of excessive current or frequent and too long acceleration
No KTY is connected to X8 Connect KTY or switch off monitoring
The value entered in C0121 is too low Enter higher value
Motor too hot because of excessive current or frequent and too long acceleration
Terminals T1, T2 are not assigned Connect PTC or thermal contact or
Only for variants V210, V240, V270, V300:
l Wrong values in C0173 l Wrong values in C0174
program flow. The parameter set 1 is loaded automatically. Parameter data which has been changed and not has been saved, will get lost.
of parameter sets between the controllers
l Parameter set does not match the
controller
parameters saved do not match the software version of the controller.
CAUTION! The Lenze setting is loaded automatically.
l The transmission of parameter sets
with keypad XT has been interrupted (e.g. by an early disconnection of the keypad XT)
CAUTION! The Lenze setting is loaded automatically.
Cable interrupted Check cable for wire breakage
RemedyCauseErrorError number
better ventilation
l Check ambient temperature in the
control cabinet
Check drive dimensioning
(C0583 = 3)
l Allow controller to cool and ensure
better ventilation
l Check ambient temperature in the
control cabinet
Check drive dimensioning
(C0584 = 3)
Check drive dimensioning
switch off monitoring (C0585=3)
l Set correct values in C0173 l Set correct values in C0174
Contact Lenze
Correct parameter set
l Correct parameter set l Save all parameter sets with C0003
and reset the fault message by mains switching
Set the required parameters and save them with C0003
38
EDKVF93−04 EN 2.0
Troubleshooting and fault elimination
System error messages
General error messages
4
Display
Sd5 x085 Encoder at X6/1,
Sd6 x086 Sensor error at X8 KTY at X8 indicates undefined values l Check supply cable for firm
x = 0: TRIP x = 1: Message x = 2: Warning
Pin X9/8 is not assigned Assign pin X9/8 with 5 V or switch off
Current at X6/1, X6/2 < 2 mA l Check cable for wire breakage
X6/2 is defective
RemedyCauseErrorError number
monitoring (C0587 = 3)
l Check encoder
connection
l Switch off monitoring with
C0594 = 3 if necessary
EDKVF93−04 EN 2.0
39
4
Troubleshooting and fault elimination
System error messages Resetting system error messages
4.5.2 Resetting system error messages
Eliminate the cause of TRIP fault message
After you have eliminated the cause of a TRIP fault message, you must reset the fault message with the command "TRIP reset". Only then the drive restarts.
Note!
A TRIP fault message can have several causes. Only if all causes of the TRIP have been eliminated, the TRIP reset can be executed.
TRIP reset
ƒ Keypad XT: Press &. Then press ' to enable the controller.
ƒ Fieldbus module: Set C0043 = 0
ƒ Control word: C0135
ƒ Terminal: X5/E5 = HIGH
ƒ Control word via AIF
ƒ Control word via system bus (CAN)
Mains switching always executes TRIP reset.
Codes for parameter setting
Code Possible settings IMPORTANT
No. Name Lenze Selection
C0043 Trip reset 0
0 no/trip reset Reset actual error 1 trip active There is a TRIP error
40
EDKVF93−04 EN 2.0
F
(
Ê  ü
© 04/2010
Lenze Automation GmbH Hans−Lenze−Str. 1 D−31855 Aerzen Germany
+49(0)51 54 /82−0
+49(0)51 54 /82 − 28 00
Lenze@Lenze.de
www.Lenze.com
Service Lenze Service GmbH
Breslauer Straße 3 D−32699 Extertal Germany
(
Ê 
008000/ 2446877 (24 h helpline)
+49(0)5154/ 82−11 12
Service@Lenze.de
EDKVF93−04 § .BNC § EN § 2.0 § TD23
10987654321
(
Loading...