Shield connection support with fixing screws (2 items)
1 support for the shield sheet for the supply connections
1 support for the shield sheet for the motor cable
EMC shield sheet with fixing screws (2 items)
1 shield sheet for the supply connections
1 shield sheet for the motor cable and the feed cable for the motor temperature monitoring with PTC thermistor or thermal contact (NC contact)
EMC shield sheet with fixing screws for shielded control cables
Cover for the supply connections
Connections and interfaces
PositionDescription
L1, L2, L3, PE Mains connection
+UG, −UGDC supply
U, V, W, PEMotor connection
T1, T2Connection of PTC thermistor or thermal contact (NC contact) of the motor
X1AIF interface (automation interface)
Slot for communication module (e. g. XT EMZ9371BC keypad)
X3Jumper for setting analog input signal at X6/1, X6/2
X4System bus (CAN) connection
X5Connection of digital inputs and outputs
X6Connection of analog inputs and outputs
X8Connection of incremental encoder with TTL level or SinCos encoder and KTY temperature sensor of the motor
X9Connection of digital frequency input signal
X10Connection of digital frequency output signal
X11Connection of KSR relay output for "safe standstill" (for variants V004 and V024 only)
Status displays
PositionLED red LED greenOperating status
OffOnController is enabled
OnOnMains is switched on and automatic start is inhibited
This documentation contains all the information required by the machine
operator to run the drive controllers of the 9300 vector series installed in your
machine/system.
You may make further use of the information contained in this documentation
without asking Lenze for permission if you do not change the contents.
1.1Document history
What is new / what has changed?
Material numberVersionDescription
.MUW3.011/2013TD06Error corrections
133305742.103/2010TD14Change of the company’s address
133305742.003/2010TD14New edition due to reorganisation of the company
132177391.007/2007TD23First edition
About this documentation
Document history
UL−warnings updated
Revision for software version 8x
1
Tip!
Information and auxiliary devices related to the Lenze products can be found
in the download area at
http://www.Lenze.com
1.2Target group
This documentation is directed at qualified skilled personnel according to IEC 60364.
Qualified skilled personnel are persons who have the required qualifications to carry out
all activities involved in installing, mounting, commissioning, and operating the product.
EDKVF93−01 EN 3.0
5
1
About this documentation
Validity information
1.3Validity information
... 9300 vector frequency inverters as of nameplate data:
Product series
EVF =Frequency inverter
Type no. / rated power
400 V480 V
9321 = 0.37 kW0.37 kW
9322 = 0.75 kW0.75 kW
9323 = 1.5 kW1.5 kW
9324 = 3.0 kW3.0 kW
9325 = 5.5 kW5.5 kW
9326 = 11 kW11 kW
Type
E =Panel−mounted unit
C =Built−in unit in "cold plate" technique
Nameplate
EVF 93xx ˘x V Vxxx 1x 8x
9300vec112
Design
V =Vector−controlled frequency inverter
Variant
˘Standard
V003 = In "cold plate" technique
V004 = With "safe standstill" function
V024 = With "safe standstill" function and for IT mains
V100 = For IT mains
Hardware version
Software version
6
EDKVF93−01 EN 3.0
About this documentation
Conventions used
1
1.4Conventions used
This documentation uses the following conventions to distinguish between different
types of information:
Type of informationIdentificationExamples/notes
Spelling of numbers
Decimal separatorlanguage−dependentIn each case, the signs typical for the target
Warnings
UL warnings
UR warnings
Text
Program name» «PC software
Icons
Page referenceReference to another page with additional
Documentation referenceReference to another documentation with
language are used as decimal separators.
For example: 1234.56 or 1234,56
Given in English and French
For example: »Engineer«, »Global Drive
Control« (GDC)
information
For instance: 16 = see page 16
additional information
For example: EDKxxx = see
documentation EDKxxx
EDKVF93−01 EN 3.0
7
1
About this documentation
Notes used
1.5Notes used
The following pictographs and signal words are used in this documentation to indicate
dangers and important information:
Safety instructions
Structure of safety instructions:
Danger!
Pictograph and signal wordMeaning
Danger!
Danger!
Stop!
(characterises the type and severity of danger)
Note
(describes the danger and gives information about how to prevent dangerous
situations)
Danger of personal injury through dangerous electrical voltage.
Reference to an imminent danger that may result in death or
serious personal injury if the corresponding measures are not
taken.
Danger of personal injury through a general source of danger.
Reference to an imminent danger that may result in death or
serious personal injury if the corresponding measures are not
taken.
Danger of property damage.
Reference to a possible danger that may result in property
damage if the corresponding measures are not taken.
Application notes
Pictograph and signal wordMeaning
Note!
Tip!
Special safety instructions and application notes
Pictograph and signal wordMeaning
Warnings!
Warnings!
Important note to ensure troublefree operation
Useful tip for simple handling
Reference to another documentation
Safety note or application note for the operation according to
UL or CSA requirements.
The measures are required to meet the requirements according
to UL or CSA.
8
EDKVF93−01 EN 3.0
Safety instructions
General safety and application notes for Lenze controllers
2Safety instructions
2.1General safety and application notes for Lenze controllers
(in accordance with Low−Voltage Directive 2006/95/EC)
For your personal safety
Disregarding the following safety measures can lead to severe injury to persons and
damage to material assets:
ƒ Only use the product as directed.
ƒ Never commission the product in the event of visible damage.
ƒ Never commission the product before assembly has been completed.
ƒ Do not carry out any technical changes on the product.
ƒ Only use the accessories approved for the product.
2
ƒ Only use original spare parts from Lenze.
ƒ Observe all regulations for the prevention of accidents, directives and laws
applicable on site.
ƒ Transport, installation, commissioning and maintenance work must only be carried
out by qualified personnel.
– Observe IEC 364 and CENELEC HD 384 or DIN VDE 0100 and IEC report 664 or
DIN VDE 0110 and all national regulations for the prevention of accidents.
– According to this basic safety information, qualified, skilled personnel are persons
who are familiar with the assembly, installation, commissioning, and operation of
the product and who have the qualifications necessary for their occupation.
ƒ Observe all specifications in this documentation.
– This is the condition for safe and trouble−free operation and the achievement of
the specified product features.
– The procedural notes and circuit details described in this documentation are only
proposals. It is up to the user to check whether they can be transferred to the
particular applications. Lenze Automation GmbH does not accept any liability for
the suitability of the procedures and circuit proposals described.
ƒ Depending on their degree of protection, some parts of the Lenze controllers
(frequency inverters, servo inverters, DC speed controllers) and their accessory
components can be live, moving and rotating during operation. Surfaces can be hot.
– Non−authorised removal of the required cover, inappropriate use, incorrect
installation or operation, creates the risk of severe injury to persons or damage to
material assets.
– For more information, please see the documentation.
EDKVF93−01 EN 3.0
ƒ High amounts of energy are produced in the controller. Therefore it is required to
wear personal protective equipment (body protection, headgear, eye protection, ear
protection, hand guard).
9
2
Safety instructions
General safety and application notes for Lenze controllers
Application as directed
Controllers are components which are designed for installation in electrical systems or
machines. They are not to be used as domestic appliances, but only for industrial purposes
according to EN 61000−3−2.
When controllers are installed into machines, commissioning (i.e. starting of the operation
as directed) is prohibited until it is proven that the machine complies with the regulations
of the EC Directive 2006/42/EC (Machinery Directive); EN 60204 must be observed.
Commissioning (i.e. starting of the operation as directed) is only allowed when there is
compliance with the EMC Directive (2004/108/EC).
The controllers meet the requirements of the Low−Voltage Directive 2006/95/EC. The
harmonised standard EN 61800−5−1 applies to the controllers.
The technical data and supply conditions can be obtained from the nameplate and the
documentation. They must be strictly observed.
Warning: Controllers are products which can be installed in drive systems of category C2
according to EN 61800−3. These products can cause radio interferences in residential areas.
In this case, special measures can be necessary.
Transport, storage
Please observe the notes on transport, storage, and appropriate handling.
Observe the climatic conditions according to the technical data.
Installation
The controllers must be installed and cooled according to the instructions given in the
corresponding documentation.
The ambient air must not exceed degree of pollution 2 according to EN 61800−5−1.
Ensure proper handling and avoid excessive mechanical stress. Do not bend any
components and do not change any insulation distances during transport or handling. Do
not touch any electronic components and contacts.
Controllers contain electrostatic sensitive devices which can easily be damaged by
inappropriate handling. Do not damage or destroy any electrical components since this
might endanger your health!
10
EDKVF93−01 EN 3.0
Safety instructions
General safety and application notes for Lenze controllers
Electrical connection
When working on live controllers, observe the applicable national regulations for the
prevention of accidents (e.g. VBG 4).
The electrical installation must be carried out according to the appropriate regulations
(e.g. cable cross−sections, fuses, PE connection). Additional information can be obtained
from the documentation.
This documentation contains information on installation in compliance with EMC
(shielding, earthing, filter, and cables). These notes must also be observed for CE−marked
controllers. The manufacturer of the system is responsible for compliance with the limit
values demanded by EMC legislation. The controllers must be installed in housings (e.g.
control cabinets) to meet the limit values for radio interferences valid at the site of
installation. The housings must enable an EMC−compliant installation. Observe in
particular that e.g. the control cabinet doors have a circumferential metal connection to
the housing. Reduce housing openings and cutouts to a minimum.
Lenze controllers may cause a DC current in the PE conductor. If a residual current device
(RCD) is used for protection against direct or indirect contact for a controller with
three−phase supply, only a residual current device (RCD) of type B is permissible on the
supply side of the controller. If the controller has a single−phase supply, a residual current
device (RCD) of type A is also permissible. Apart from using a residual current device (RCD),
other protective measures can be taken as well, e.g. electrical isolation by double or
reinforced insulation or isolation from the supply system by means of a transformer.
2
Operation
If necessary, systems including controllers must be equipped with additional monitoring
and protection devices according to the valid safety regulations (e.g. law on technical
equipment, regulations for the prevention of accidents). The controllers can be adapted to
your application. Please observe the corresponding information given in the
documentation.
After the controller has been disconnected from the supply voltage, all live components
and power terminals must not be touched immediately because capacitors can still be
charged. Please observe the corresponding stickers on the controller.
All protection covers and doors must be shut during operation.
Safety functions
Certain controller versions support safety functions (e.g. "Safe torque off", formerly "Safe
standstill") according to the requirements of the EC Directive 2006/42/EC (Machinery
Directive). The notes on the integrated safety system provided in this documentation must
be observed.
Maintenance and servicing
The controllers do not require any maintenance if the prescribed operating conditions are
observed.
EDKVF93−01 EN 3.0
Disposal
Recycle metal and plastic materials. Ensure professional disposal of assembled PCBs.
The product−specific safety and application notes given in these instructions must be
observed!
11
2
Safety instructions
Thermal motor monitoring
2.2Thermal motor monitoring
Note!
From software version 8.1 onwards, the 9300 vector controllers are provided
with an I2xt function for sensorless thermal monitoring of the connected
motor.
2
ƒ I
xt monitoring is based on a mathematical model which calculates a
thermal motor utilisation from the detected motor currents.
ƒ The calculated motor utilisation is saved when the mains is switched off.
ƒ The function is UL−certified, i.e. additional protective measures for the motor
are not required in UL−approved systems.
ƒ Nevertheless, I
because other influences on the motor utilisation such as changes in the
cooling conditions (e.g. cooling air flow interrupted or too warm) cannot be
detected.
2
xt monitoring does not provide full motor protection
2
x t load of the motor is displayed in C0066.
Die I
The thermal loading capacity of the motor is expressed by the thermal motor time
constant (t, C0128). Find the value in the rated motor data or contact the manufacturer of
the motor.
2
x t monitoring has been designed such that it will be activated after 179 s in the
The I
event of a motor with a thermal motor time constant of 5 minutes (Lenze setting C0128),
a motor current of 1.5 x I
and a trigger threshold of 100 %.
N
Two adjustable trigger thresholds provide for different responses.
ƒ Adjustable response OC8 (TRIP, warning, off).
– The trigger threshold is set in C0127.
– The response is set in C0606.
– The response OC8, for instance, can be used for an advance warning.
ƒ Fixed response OC6−TRIP.
– The trigger threshold is set in C0120.
Behaviour of the I2 x t monitoringCondition
The I2 x t monitoring is deactivated.
C0066 is set = 0 % and
MCTRL−LOAD−I2XT is set = 0.00 %.
I2 x t monitoring is stopped.
The current value in C0066 and at the
MCTRL−LOAD−I2XT output is frozen.
I2 x t monitoring is deactivated.
The motor load is displayed in C0066.
When C0120 = 0 % and C0127 = 0 %, set controller
inhibit.
When C0120 = 0 % and C0127 = 0 %, set controller
enable.
Set C0606 = 3 (off) and C0127 > 0 %.
12
Note!
An error message OC6 or OC8 can only be reset if the I2 x t load falls below the
set trigger threshold by 5 %.
EDKVF93−01 EN 3.0
Forced ventilated or naturally ventilated motors
2.2.1Forced ventilated or naturally ventilated motors
Parameter setting
2
The following codes can be set for I
CodeMeaningValue rangeLenze setting
C0066Display of the I2 x t load of the motor0 ... 250 %−
C0120Threshold: Triggering of error "OC6"0 ... 120 %0 %
C0127Threshold: Triggering of error "OC8"0 ... 120 %0 %
C0128Thermal motor time constant0.1 ... 50.0 min5.0 min
C0606Response to error "OC8"TRIP, warning, offWarning
x t monitoring:
Calculate release time and I2xt load
Formula for release timeInformation
t +*(t) ln
ȡ
ȧ
ȧ
Ȣ
1 *
I
ȣ
z ) 1
I
Mot
ǒ
Ǔ
I
N
2
100
ȧ
ȧ
Ȥ
Mot
I
r
tThermal motor time constant (C0128)
zThreshold value in C0120 (OC6) or C0127 (OC8)
Actual motor current (C0054)
Rated motor current (C0088)
Safety instructions
Thermal motor monitoring
2
Formulae for I2 x t loadInformation
L(t)Chronological sequence of the I2 x t load of the motor
2
I
Mot
ǒ
L(t) +
If the controller is inhibited, the I2 x t load is reduced:
Ǔ
100% ǒ1 * e
I
N
L(t) + L
Start
Ǹ
e
*t
t
t
*
t
I
Ǔ
Mot
IrRated motor current (C0088)
tThermal motor time constant (C0128)
L
Start
(Display: C0066)
Actual motor current (C0054)
I2 x t load before controller inhibit
If an error is triggered, the value corresponds to the
threshold value set in C0120 (OC6) or
C0127 (OC8).
Read release time in the diagram
Diagram for detecting the release times for a motor with a thermal motor time constant
of 5 minutes (Lenze setting C0128):
I = 3 × I
L [%]
MotN
120
100
50
0
0100200300400500600700800900
Fig. 2−1I2 × t−monitoring: Release times for different motor currents and trigger thresholds
I = 2 × I
MotN
Actual motor current (C0054)
I
Mot
I
Rated motor current (C0088)
r
2
LI
TTime
x t load of the motor (display: C0066)
I = 1.5 × I
MotN
I = 1 × I
MotN
1000
t [s]
9300STD105
EDKVF93−01 EN 3.0
13
2
Safety instructions
Thermal motor monitoring
Self−ventilated motors
2.2.2Self−ventilated motors
Due to the construction, self−ventilated standard motors are exposed to an increased heat
generation in the lower speed range compared to forced ventilated motors.
Warnings!
For complying with the UL 508C standard, you have to set the
speed−dependent evaluation of the permissible torque via code C0129/x.
Parameter setting
The following codes can be set for I
CodeMeaningValue rangeLenze setting
C0066Display of the I2 x t load of the motor0 ... 250 %−
C0120Threshold: Triggering of error "OC6"0 ... 120 %0 %
C0127Threshold: Triggering of error "OC8"0 ... 120 %0 %
C0128Thermal motor time constant0.1 ... 50.0 min5.0 min
C0606Response to error "OC8"TRIP, warning, offWarning
C0129/1S1 torque characteristic I1/I
C0129/2S1 torque characteristics n2/n
2
x t monitoring:
rated
rated
10 ... 200 %100 %
10 ... 200 %40 %
Effect of code C0129/x
I / I
N
1.1
1.0
3
0.9
0.8
0.7
0
0.6
0
00.1
Fig. 2−2Working point in the range of characteristic lowering
2
C0129/1
0.132
C0129/2
1
0.20.30.4
n / n
N
9300STD350
The lowered speed / torque characteristic (Fig. 2−2) reduces the permissible thermal load
of self−ventilated standard motors. The characteristic is a line the definition of which
requires two points:
ƒ Point : Definition with C0129/1
This value also enables an increase of the maximally permissible load.
ƒ Point : Definition with C0129/2
With increasing speeds, the maximally permissible load remains unchanged
(I
Mot
= I
rated
).
In Fig. 2−2, the motor speed and the corresponding permissible motor torque () can be
read for each working point (on the characteristic () ... ). can also be calculated
using the values in C0129/1and C0129/2 (evaluation coefficient "y", 15).
14
EDKVF93−01 EN 3.0
Loading...
+ 32 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.