All rights reserved. No part of this manual may be reproduced or transmitted in any form without written permission from Lenze AC Tech Corporation. The information and technical data in this manual are subject to change
without notice. Lenze AC Tech Corporation makes no warranty of any kind with respect to this material, including, but not limited to, the implied warranties of it’s merchantability and fitness for a given purpose. Lenze AC
Tech Corporation assumes no responsibility for any errors that may appear in this manual.
All information given in this documentation has been carefully selected and tested for compliance with the hardware and software described. Nevertheless, discrepancies cannot be ruled out. We do not accept any responsibility nor liability for damages that may occur. Any necessary corrections will be implemented in subsequent
editions.
This document printed in the United States
Page 3
Contents
About theseInstructions ....................................................................................................... 2
1 Safety Information .................................................................................................... 3
2 Technical Data ..........................................................................................................7
2.1 Standards and Application Conditions ...................................................................................7
2.2 SMV Type Number Designation .............................................................................................8
This documentation applies to the SMV frequency inverter and contains important technical data
regarding the installation, operation, and commissioning of the inverter.
These instructions are only valid for SMV frequency inverters with software revision 4.23 or
higher for version 4.23 software, the drive nameplate illustrated below would show “42” in the “F”
location.
Please read these instructions in their entirety before commissioning the drive.
C A B D E F
Type:
ESV751N04TXB
Id-No: 00000000
INPUT:
3~ (3/PE)
400/480 V
2.9/2.5 A
50-60 HZ
TYPE-4X INDOOR USE ONLY
OUTPUT:
3~ (3/PE)
0 - 400/460 V
2.4/2.1 A
0.75 KW/1HP
0 - 500 HZ
For detailed information
refer to instruction
Manual: SV01
000000000000000000
ESV751N04TXB000XX## ##
ABCDEF
CertificationsTypeInput RatingsOutput RatingsHardware VersionSoftware Version
Scope of deliveryImportant
• 1 SMV Inverter
with EPM installed (see Section 4.4)
• 1 Operating Instructions manual
After receipt of the delivery, check immediately whether the items delivered match
the accompanying papers. Lenze AC Tech does not accept any liability for deficiencies
claimed subsequently.
Claim:
• visible transport damage immediately to the forwarder.
• visible deficiencies /incompleteness immediately to your Lenze AC Tech representative
Related Documents
The documentation listed herein contains information relevant to the operation of the SMVector frequency inverter.
To obtain the latest documentation, visit the Technical Library at http://w ww.lenzeamericas.com.
ALSV01SMVector Additional I/O Module Installation and Operation Manual
DBV01SMVector Dynamic Braking
PTV01SMVector Potentiometer Install Instructions
RKV01SMVector ESVZXK1 Remote Keypad
RKVU01SMVector ESVZXH0 Remote Keypad (for NEMA 1 15-60HP (11-45kW) Drives)
2Lenze SMVector 13465100 EDBSV01 EN v18
Page 5
Safety Information
1 Safety Information
General
Some parts of Lenze AC Tech controllers can be electrically live and some surfaces can be hot. Nonauthorized removal of the required cover, inappropriate use, and incorrect installation or operation
creates the risk of severe injury to personnel and/or damage to equipment.
All operations concerning transport, installation, and commissioning as well as maintenance must be
carried out by qualified, skilled personnel who are familiar with the installation, assembly, commissioning,
and operation of variable frequency drives and the application for which it is being used.
Installation
Ensure proper handling and avoid excessive mechanical stress. Do not bend any components and do not
change any insulation distances during transport, handling, installation or maintenance. Do not touch
any electronic components or contacts. This drive contains electrostatically sensitive components, which
can easily be damaged by inappropriate handling. Static control precautions must be adhered to during
installation, testing, servicing and repairing of this drive and associated options. Component damage
may result if proper procedures are not followed.
To ensure proper operation, do not install the drive where it is subjected to adverse environmental
conditions such as combustible, oily, or hazardous vapors; corrosive chemicals; excessive dust, moisture
or vibration; direct sunlight or extreme temperatures.
This drive has been tested by Underwriters Laboratory (UL) and is UL Listed in compliance with the
UL508C Safety Standard. This drive must be installed and configured in accordance with both national
and international standards. Local codes and regulations take precedence over recommendations
provided in this and other Lenze AC Tech documentation.
The SMVector drive is considered a component for integration into a machine or process. It is neither a
machine nor a device ready for use in accordance with European directives (reference machinery directive
and electromagnetic compatibility directive). It is the responsibility of the end user to ensure that the
machine meets the applicable standards.
Electrical Connection
When working on live drive controllers, applicable national safety regulations must be observed. The electrical
installation must be carried out according to the appropriate regulations (e.g. cable cross-sections, fuses,
protective earth [PE] connection). While this document does make recommendations in regards to these
items, national and local codes must be adhered to.
The documentation contains information about installation in compliance with EMC (shielding, grounding, filters
and cables). These notes must also be observed for CE-marked controllers. The manufacturer of the system
or machine is responsible for compliance with the required limit values demanded by EMC legislation.
Application
The drive must not be used as a safety device for machines where there is a risk of personal injury or material damage.
Emergency Stops, over-speed protection, acceleration and deceleration limits, etc must be made by other
devices to ensure operation under all conditions.
The drive does feature many protection devices that work to protect the drive and the driven equipment
by generating a fault and shutting the drive and motor down. Mains power variances can also result in
shutdown of the drive. When the fault condition disappears or is cleared, the drive can be configured to
automatically restart, it is the responsibility of the user, OEM and/or integrator to ensure that the drive is
configured for safe operation.
Lenze SMVector 13465100 EDBSV01 EN v18 3
Page 6
Safety Information
Explosion Proof Applications
Explosion proof motors that are not rated for inverter use lose their certification when used for
variable speed. Due to the many areas of liability that may be encountered when dealing with these
applications, the following statement of policy applies:
Lenze AC Tech Corporation inverter products are sold with no warranty of fitness for a particular
purpose or warranty of suitability for use with explosion proof motors. Lenze AC Tech Corporation
accepts no responsibility for any direct, incidental or consequential loss, cost or damage that may
arise through the use of AC inverter products in these applications. The purchaser expressly agrees to
assume all risk of any loss, cost or damage that may arise from such application.
Operation
Systems including controllers must be equipped with additional monitoring and protection devices
according to the corresponding standards (e.g. technical equipment, regulations for prevention of
accidents, etc.). The controller may be adapted to your application as described in this documentation.
DANGER!
• After the controller has been disconnected from the supply voltage, live components and power connection
must not be touched immediately, since capacitors could be charged. Please observe the corresponding
notes on the controller.
• Close all protective covers and doors prior to and during operation.
• Do not cycle input power to the controller more than once every two minutes.
• For SMVector models that are equipped with a Disconnect Switch (11th character in model number is L or M),
the Disconnect Switch is intended as a motor service disconnect and does not provide branch circuit protection
to the inverter or motor. When servicing the motor, it is necessary to wait 3 minutes after turning this switch
to the off position before working on motor power wiring as the inverter stores electrical power. To service the
inverter, it is necessary to remove mains ahead of the drive and wait 3 minutes.
Safety Notifications
All safety information given in these Operating Instructions includes a visual icon, a bold signal word
and a description.
Signal Word! (characterizes the severity of the danger)
NOTE (describes the danger and informs on how to proceed)
Signal WordMeaningConsequences if ignored
Icon
DANGER!
WARNING!
WARNING!
Hot Surface
STOP!
NOTE
Warns of hazardous electrical voltage.Death or severe injuries.
Warns of potential, very hazardous
situations.
Warns of hot surface and risk of burns.
Labels may be on or inside the
equipment to alert people that surfaces
may reach dangerous temperatures.
Warns of potential damage to material
and equipment.
Designates a general, useful note.None. If observed, then using the control-
Risk of severe injury to personnel and/or
damage to equipment.
Risk of severe injury to personnel.
Damage to the controller/drive or its
environment.
ler/drive system is made easier.
4Lenze SMVector 13465100 EDBSV01 EN v18
Page 7
Safety Information
Harmonics Notification in accordance with EN 61000-3-2, EN 61000-3-12:
Operation in public supply networks (Limitation of harmonic currents i.a.w. EN 61000-3-2,
Electromagnetic Compatibility (EMC) Limits). Limits for harmonic current emissions (equipment input
current up to 16A/phase).
DirectiveTotal Power
EN 61000-3-2
EN 61000-3-12
(1) For compliance with EMC regulations, the permissable cable lengths may change.
(2) The additional measures described only ensure that the controller meets the requirements of the EN 61000-3-2.
The machine/system manufacturer is responsible for the machine’s compliance with the regulations.
connected to Mains
(public supply)
< 0.5kWwith mains choke
0.5 ... 1kWwith active filter
> 1kWcomplies without additional measures
16 ... 75ampAdditional measures are required for compliance with the standard
Additional Measures Required for Compliance
Safety Information in accordance with EN 61800-5-1:
DANGER! - Risk of Electric Shock
Capacitors retain charge for approximately 180 seconds after power is removed. Disconnect
incoming power and wait at least 3 minutes before touching the drive.
DANGER! - Risque de choc électrique
Les condensateurs restent sous charge pendant environ 180 secondes après une coupure
de courant. Couper l’alimentation et patienter pendant au moins 3 minutes avant de toucher
l’entraînement.
WARNING!
• This product can cause a d.c. current in the PE conductor. Where a residual currentoperated (RCD) or monitoring (RCM) device is used for protection in case of direct or
indirect contact, only an RCD or RCM Type B is allowed on the supply side of this product.
• Leakage Current may exceed 3.5mA AC. The minimum size of the PE conductor shall
comply with local safety regulations for high leakage current equipment.
• In a domestic environment, this product may cause radio interference in which case
supplementary mitigation measures may be required.
(2)
Lenze SMVector 13465100 EDBSV01 EN v18 5
Page 8
Safety Information
Safety Information in accordance with UL:
Note for UL approved system with integrated controllers: UL warnings are notes which apply to UL systems.
The documentation contains special information about UL.
•Integral solid state protection does not provide branch circuit protection. Branch circuit protection
must be provided in accordance with the National Electrical Code and any additional local codes. The
Warnings!
use of fuses or circuit breakers is the only approved means for branch circuit protection.
•When protected by CC and T Class Fuses, suitable for use on a circuit capable of delivering not
more than 200,000 rms symmetrical amperes, at the maximum voltage rating marked on the drive.
•Additionally suitable when protected by a circuit breaker having an interrupting rating not less than
200,000 rms symmetrical amperes, at the maximum voltage rating marked on the drive. (Excludes
ESV113xx2T, ESV153xx2T, ESV113xx4T, ESV153xx4T, ESV183xx4T, ESV223xx4T, ESV303xx4T,
ESV113xx6T, ESV153xx6T, ESV183xx6T, ESV223xx6T, and ESV303xx6T).
•Use minimum 75°C copper wire only, except for control circuits.
•For control circuits, use wiring suitable for NEC Class 1 circuits only.
•Torque Requirements (in accordance with UL) are listed in section 3.2.1,
Power Connections and in 3.2.3, Control terminals
•Shall be installed in a pollution degree 2 macro-environment.
•NEMA 1 (IP31) models shall be installed in a pollution degree 2 macro-environment.
•All models are suitable for installation in a compartment handling Conditioned Air (i.e., plenum rated).
WARNING!
The opening of branch-circuit protective device may be an indication that a fault has been interrupted. To reduce the risk of fire or electric shock, current carrying parts and other components
of the controller should be examined and replaced if damaged.
AVERTISSEMENT!
Le déclenchement du dispositif de protection du circuit de dérivation peut être dû à une coupure
qui résulte d’un courant de défaut. Pour limiter le risque d’incendie ou de choc électrique, examiner
les pièces porteuses de courant et les autres éléments du contrôleur et les remplacer s’ils sont
endommagés. En cas de grillage de l’élément traverse par le courant dans un relais de surcharge,
le relais tout entier doit être remplacé.
NOTE
Control and communications terminals provide reinforced insulation (i.e. considered SELV or PELV,
providing protection in case of direct contact) when the drive is connected to a power system rated
up to 300VAC between phase to ground (PE) and the applied voltage on Terminals 16 and 17 is less
than 150VAC between phase to ground. Otherwise, control and communications terminals provide
basic insulation.
6Lenze SMVector 13465100 EDBSV01 EN v18
Page 9
Technical Data
2 Technical Data
2.1 Standards and Application Conditions
Conformity
Approvals
Input voltage phase imbalance
Supported Power Systems
Humidity
Temperature range
Installation height
Vibration resistance
Earth leakage current
Max Permissable Cable Length
Enclosure
Protection measures against
Compliance with EN 61000-3-2
Requirements
Compliance with EN 61000-3-12
Requirements
Operation in public supply networks (Limitation of harmonic currents i.a.w. EN 61000-3-2, Electromagnetic Compatibility
(EMC) Limits). Limits for harmonic current emissions (equipment input current up to 16A/phase).
(1) The stated cable lengths are permissible at default carrier frequencies (refer to parameter P166).
(2) The additional measures described only ensure that the controller meets the requirements of the EN 61000-3-2.
(2)
(2)
The machine/system manufacturer is responsible for the machine’s compliance with the regulations.
CELow Voltage (2006/95/EC) & EMC (2004/108/EC) Directives
NEMA 1 and NEMA 4X model enclosures are plenum rated in accordance with UL
508C and are suitable for installation in a compartment handling conditioned air.
Earth fault, phase loss, over voltage, under voltage, motor stalling, over temperature
motor overload (125% of FLA), short circuit (SCCR=200kA at rated voltage)
< 0.5kWwith mains choke
0.5 ... 1kWwith active filter
> 1kWwithout additional measures
16 ... 75ampAdditional measures required for compliance with EN 61000-3-12
without restrictions.
− For corner grounded 400/500V systems, operation is
possible but reinforced insulation to control circuits is
compromised.
Lenze SMVector 13465100 EDBSV01 EN v18 7
Page 10
Technical Data
2.2 SMV Type Number Designation
The table herein describes the Type numbering designation for the SMVector Inverter models.
S = Single Phase Input only
Y = Single or Three Phase Input
T = Three Phase Input only
Input Line Filter
F = Integral EMC Filter
L = Integral EMC Filter and Integrated Disconnect Switch (NEMA 4X/IP65 Models only)
M = Integrated Disconnect Switch (NEMA 4X/IP65 Models only)
X = No EMC Filter/ No Disconnect Switch
Enclosure:
B = NEMA 1/IP31; Indoor only
C = NEMA 4X/IP65; Indoor only; Convection cooled
D = NEMA 4X/IP65; Indoor only; Fan cooled
E = NEMA 4X/IP65; Indoor/Outdoor; Convection cooled
F = NEMA 4X/IP65; Indoor/Outdoor; Fan cooled
NOTE
Prior to installation make sure the enclosure is suitable for the end-use environment
Variables that influence enclosure suitability include (but are not limited to) temperature, airborne
contaminates, chemical concentration, mechanical stress and duration of exposure (sunlight,
wind, precipitation).
152N02TXB
8 Lenze SMVector 13465100 EDBSV01 EN v18
Page 11
Technical Data
2.3 Ratings
120V / 240VAC Models
Mains = 120V Single Phase (1/N/PE) (90...132V), 240V Single Phase (2/PE) (170...264V); 48...62Hz
Type
ESV251--1S--0.330.256.83.41.720024
ESV371--1S--0.50.379.24.62.42003232
ESV751--1S--10.7516.68.34.22005241
ESV112--1S--1.51.12010.06.02007474
NOTES:
Output Current: The Output Current Maximum (%) is a percentage of the Output Current Continuous Amps (In) rating
and is adjustable in parameter P171.
240VAC Models
Type
ESV251--2S--0.330.253.41.720020
ESV371--2S--0.50.375.12.420030
ESV751--2S--10.758.84.220042
ESV112--2S--1.51.112.06.020063
ESV152--2S--21.513.37.020073
ESV222--2S--32.217.19.620097
PowerMains CurrentOutput CurrentHeat Loss (Watts)
HpkW
120VA240VACont (In)AMax I%N1/IP31 N4X/IP65
No filter
Mains = 240V Single Phase (2/PE) (170...264V); 48...62Hz
PowerMains CurrentOutput CurrentHeat Loss (Watts)
HpkW
240V
A
Cont (In)AMax I%N1/IP31 N4X/IP65
No filter
N4X/IP65
W/ filter
N4X/IP65
W/ filter
240V Single Phase (2/PE) (170...264V), 240V Three Phase (3/PE) (170...264V); 48...62Hz
Type
ESV371--2Y--0.50.375.12.92.42002726
ESV751--2Y--10.758.85.04.22004138
ESV112--2Y--1.51.112.06.96.02006459
ESV152--2Y--21.513.38.17.02007569
ESV222--2Y--32.217.110.89.620010393
PowerMains CurrentOutput CurrentHeat Loss (Watts)
HpkW
1~ (2/PE)A3~ (3/PE)
A
Cont (In)AMax I%N1/IP31 N4X/IP65
No filter
N4X/IP65
W/ filter
240V Three Phase (3/PE) (170...264V); 48...62Hz
Type
PowerMains CurrentOutput CurrentHeat Loss (Watts)
HpkW
240V
A
Cont (In)AMax I%N1/IP31 N4X/IP65
No filter
N4X/IP65
W/ filter
Lenze SMVector 13465100 EDBSV01 EN v18 9
Page 12
Technical Data
ESV112--2T--1.51.16.9620064
ESV152--2T--21.58.1720075
ESV222--2T--32.210.89.6200103
ESV402--2T--54.018.616.5200154139
ESV552--2T--7.55.52623200225167
ESV752--2T--107.53329200274242
ESV113--2T--15114842180485468
ESV153--2T--20155954180614591
NOTES:
Output Current: The Output Current Maximum (%) is a percentage of the Output Current Continuous Amps (In) rating
and is adjustable in parameter P171.
Output Current: The Output Current Maximum (%) is a percentage of the Output Current Continuous Amps (In) rating
and is adjustable in parameter P171.
For 400...480 VAC models, the output current maximum (%) in the 400V column is used when P107 = 0
For 400...480 VAC models, the output current maximum (%) in the 480V column is used when P107 = 1
PowerMains CurrentOutput CurrentHeat Loss (Watts)
HpkW
400VA480VACont (In)AMax I%N1/IP31 N4X/IP65
400V 480V 400V 480V
No filter
N4X/IP65
W/ filter
10 Lenze SMVector 13465100 EDBSV01 EN v18
Page 13
Technical Data
600VAC Models
600V Three Phase (3/PE) (425...660V); 48...62Hz
Type
ESV751--6T--10.7521.72003731
ESV152--6T--21.53.22.72005143
ESV222--6T--32.24.43.92006857
ESV402--6T--546.86.120010167
ESV552--6T--7.55.510.29200148116
ESV752--6T--107.512.411200172152
ESV113--6T--151119.717180380356
ESV153--6T--20152522180463431
ESV183--6T--2518.53127180560519
ESV223--6T--30223632180640592
ESV303--6T--40304741180930
ESV373--6T--5037.559521801163
ESV453--6T--604571621801395
NOTES:
Output Current: The Output Current Maximum (%) is a percentage of the Output Current Continuous Amps (In) rating
and is adjustable in parameter P171.
PowerMains CurrentOutput CurrentHeat Loss (Watts)
HpkWA
Cont (In)AMax I%N1/IP31 N4X/IP65
No filter
STOP!
• For installations above 1000m a.m.s.l., derate In by 5% per 1000m, do not
exceed 4000m a.m.s.l.
• Operation above 40°C, derate In by 2.5% per °C, do not exceed 55°C.
N4X/IP65
W/ filter
Output Current (In) derating for Carrier Frequency (P166) for NEMA 1 (IP31) Models:
- If P166=2 (8 kHz), derate In to 92% of drive rating
- If P166=3 (10 kHz), derate In to 84% of drive rating
Output Current (In) derating for Carrier Frequency (P166) for NEMA 4X (IP65) Models:
- If P166=1 (6 kHz), derate In to 92% of drive rating
- If P166=2 (8 kHz), derate In to 84% of drive rating
- If P166=3 (10 kHz), derate In to 76% of drive rating
Lenze SMVector 13465100 EDBSV01 EN v18 11
Page 14
Installation
b2
Mounting Screws
Q
N
Q
S
P1
3 Installation
3.1 Dimensions and Mounting
WARNING!
Drives must not be installed where subjected to adverse environmental conditions such as: combustible, oily, or
hazardous vapors; corrosive chemicals; excessive dust, moisture or vibration; direct sunlight or extreme temperatures.
_ = Last digit of part number: C = N4X Indoor (convection cooled) ~ = Last digit of part number: D = N4X Indoor (fan cooled)
E = N4X In/Outdoor (convection cooled) F = N4X In/Outdoor (fan cooled)
Severe damage to the drive can result if it is operated after a long period of storage or inactivity
without reforming the DC bus capacitors.
If input power has not been applied to the drive for a period of time exceeding three years (due to
storage, etc), the electrolytic DC bus capacitors within the drive can change internally, resulting
in excessive leakage current. This can result in premature failure of the capacitors if the drive is
operated after such a long period of inactivity or storage.
In order to reform the capacitors and prepare the drive for operation after a long period of inactivity,
apply input power to the drive for 8 hours prior to actually operating the motor.
3.2.1 Power Connections
STOP!
If the kVA rating of the AC supply transformer is greater than 10 times the input kVA
rating of the drive(s), an isolation transformer or 2-3% input line reactor must be added
to the line side of the drive(s).
DANGER! Hazard of electrical shock!
Circuit potentials up to 600 VAC are possible. Capacitors retain charge after power is
removed. Disconnect power and wait at least three minutes before servicing the drive.
STOP!
• Verify mains voltage before connecting to drive.
• Do not connect mains power to the output terminals (U,V,W)! Severe damage to the drive will result.
• Do not cycle mains power more than once every two minutes. Damage to the drive may result.
If the cable connection between the drive and the motor has an in-line contactor or
circuit breaker then the drive must be stopped prior to opening/closing the contacts.
Failure to do so may result in 0vercurrent trips and/or damage to the inverter.
PE L1 L2 N
PE L1 L2 L3
PE L1 L2
PE L1 N
M
PES
3~
PES = Protective Earth Shielding
WARNING!
Leakage current may exceed 3.5 mA AC. The minimum size of the protective
earth (PE) conductor shall comply with local safety regulations for high leakage
current equipment.
STOP!
In the case of a Spinning Motor:
To bring free-wheeling loads such as fans to a rest before starting the drive, use the DC injection
braking function. Starting a drive into a freewheeling motor creates a direct short-circuit and may
result in damage to the drive.
Confirm motor suitability for use with DC injection braking.
Consult parameter P110 for starting / restarting into spinning motors.
Lenze SMVector 13465100 EDBSV01 EN v18 17
Page 20
Installation
backplate using saddle clamp
3.2.1.5 Installation Recommendations for EMC Compliance
For compliance with EN 61800-3 or other EMC standards, motor cables, line cables and control or communications
cables must be shielded with each shield/screen clamped to the drive chassis. This clamp is typically located at the
conduit mounting plate.
The EMC requirements apply to the final installation in its entirety, not to the individual components used. Because
every installation is different, the recommended installation should follow these guidelines as a minimum. Additional
equipment (such as ferrite core absorbers on power conductors) or alternative practices may be required to meet
conformance in some installations.
Motor cable should be low
capacitance (core/core <75pF/m,
core/shield <150pF/m). Filtered
drives can meet the class A limits
of EN 55011 and EN 61800-3
Category 2 with this type of motor
cable up to 10 meters.
NOTE: Refer to Appendix A for
recommended cable lengths. Any
external line filter should have its
External
Control
Circuits
Control and signal cabling
should be separated from
power cables by
a minimum of 300mm
360° shield termination to
chassis connected to the drive
chassis by mounting hardware
or with the shortest possible wire
or braid.
3.2.1.6 NEMA 4X (IP65) Input Terminal Block
For NEMA 4X (IP65) models with integrated EMC filter and/or integrated line disconnect, the input terminal block is
located on the right-hand side of the SMV inverter in the NEMA 4 X (IP65) enclosure. The single and three phase models
are illustrated herein. Refer to paragraph 3.2.3 Control Terminals for pin out information.
Enclosure / Backplate
From
Motor
From
AC Supply
Screened motor cable:
core/core <75pF/M
core/shield <150pF/M
1256
13A13B 13C 14 30 16 17
25 411
L1
PE
UVW
Single Phase (2/PE) 120/240 VAC models
(ESVxxxN01SMC) with integrated line
disconnect
L2
N
1256
13A13B13C 14 30 16 17
25 411
L1
PE
W
V
U
Single Phase (2/PE) 240 VAC models
with Filter and/or integrated line
disconnect
L2
1256
UVW
Three Phase (3/PE) models
with Filter and/or integrated line
disconnect
WARNING
Power remains present for up to 3 minutes on power input terminals (L1, L2 and L3) and output
terminals (U, V and W) even when the disconnect switch is in the OFF position. Remove input power
ahead of the drive and wait 3 minutes before removing the terminal cover.
18Lenze SMVector 13465100 EDBSV01 EN v18
25 411
PE
13A13B13C 14 30 16 17
L1
L2
L3
Page 21
Installation
-
40HP (30kW)
50/60HP (37.5/45kW)
BRAKE
BBRAKE
B+
3.2.1.7 Dynamic Brake Connections
For NEMA 1 and NEMA 4X Drives rated up to 30HP (22kW) the Dynamic Brake connections are made as illustrated
herein. Refer to the SMV Dynamic Brake Instructions (DBV01) for complete information.
NEMA 1 (IP31) up to 30HP (22kW)NEMA 4X (IP65) up to 30HP (22kW)
+
The SMV 40...60Hp (30...45kW) models include a dynamic brake transistor as standard and only require the connection
of an external resistor kit for dynamic braking operation. The dynamic brake resistor connections for 40...60 Hp
(30...45kW) drives are standard built-in connections as illustrated in the diagram below. In the 40Hp (30kW) model
drives, the dynamic brake connector is on the right-hand side of the drive and the terminals from top to bottom are B-,
BRAKE and B+. In the 50/60HP (37.5/45 kW) model drives, the dynamic brake connector is on the left-hand side of the
drive and the terminals from top to bottom are B+, BRAKE and B-.
B+
B-
External resistor kits must be connected to terminals B+ and BRAKE (no connection to B-). Refer to the table herein
for external resistor kit selection. Refer to parameter P189 for enabling the dynamic brake function in the 40...60Hp
(30...45kW) models.
400/480 VAC SMV InverterResistor Kit
TypeHpkWResistance (W) Power (W)Catalog #SAP#
ESV303**4T**403023.51020841-01313317724
ESV373**4T**5037171400841-01513317626
ESV453**4T**6045171400841-01513317626
600 VAC SMV InverterResistor Kit
TypeHpkWResistance (W) Power (W)Catalog #SAP#
ESV303**6T**4030351070841-01413317624
ESV373**6T**5037241560841-01613317628
ESV453**6T**6045241560841-01613317628
Lenze SMVector 13465100 EDBSV01 EN v18 19
Page 22
Installation
3.2.2 Fuses/Cable Cross-Sections
NOTE: Observe local regulations. Local codes may supersede these recommendations
WARNING: Use a FUSE * for 240V drives requiring > 40A protection and for 400/480/600V drives requiring >32A protection.
ESV153N06TXB, ESV153N06TX~, ESV153N06TM~M40 A* use Fuse only40 A *48
3~(3/PE)
ESV183N06TXB, ESV183N06TX~, ESV183N06TM~M50 A* use Fuse only50 A *68
ESV223N06TXB, ESV223N06TX~, ESV223N06TM~M63 A* use Fuse only60 A *108
ESV303N06TXBM80 A* use Fuse only70 A *166
ESV373N06TXBM100 A* use Fuse only90 A *164
ESV453N06TXBM125 A* use Fuse only110 A *252
Miniature circuit
Fuse
breaker
M10 AC10 A10 A1.514
M20 AC20 A20 A2.512
M10 AC10 A10 A1.514
M16 AC16 A12 A1.514
M10 AC10 A10 A1.514
M10 AC10 A10 A1.514
Fuse
Breaker
(1)
(N. America)
20 Lenze SMVector 13465100 EDBSV01 EN v18
Page 23
Installation
ALsw
ALsw
ALsw
6254 11
13A
13B
13C
TXA
512
14 30
2
AOUT
DIGOUT
2k … 10k
+10 V
+12 V
AIN
AIN
COM
COM
ALsw
17
16
TXB
13D
13D
13D
252
4 … 20 mA
52
0 … 10 V
1 2 4
13A 13B 13C
+12 VDC - 0 %
. . .
+30 VDC + 0 %
ALsw
+15V
1 2 4
13A 13B 13C
ALsw
COM
4.5 lb-in
(0.5 Nm)
0.25 in (6 mm)
AWG 26…16
(<1mm²)
Notes for Fuse and Cable Table:
(1) Installations with high fault current due to large supply mains may require a type D circuit breaker.
(2) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN or JJS or equivalent.
(3) Thermomagnetic type breakers preferred.
_ 11th digit of part number: F = Integral EMC Filter
L = Integral EMC Filter and Integrated Disconnect Switch (NEMA 4X/IP65 Models only)
M = Integrated Disconnect Switch (NEMA 4X/IP65 Models only)
X = No EMC Filter/ No Disconnect Switch
* = Last digit of part number: C = N4X Indoor only (convection cooled)
E = N4X Indoor/Outdoor (convection cooled)
~ = Last digit of part number: D = N4X Indoor only (fan cooled)
F = N4X Indoor/Outdoor (fan cooled)
Observe the following when using Ground Fault Circuit Interrupters (GFCIs):
- capacitive leakage currents between the cable screens during operation (especially with long, screened motor cables)
- connecting several controllers to the mains at the same time
- RFI filters
3.2.3 Control Terminals
Control Terminal Strip for 0.33 - 10 HP (0.25 - 7.5 kW):
COM
4.5 lb-in
(0.5 Nm)
0.25 in (6 mm)
AWG 26…16
(<1mm²)
AIN
COM
5 1 2
2k … 10k
+10 V
AIN
6 25 4 11
13A
13B
13C
14 30
DIGOUT
16
AOUT
1 2 4
17
+12 VDC - 0 %
+30 VDC + 0 %
13A 13B 13C
+15V
PNP NPN
. . .
5 2
0 … 10 V
1 2 4
COM
4 … 20 mA
13A 13B 13C
25 2
Control Terminal Strip for 15HP (11 kW) and Greater Drives:
NOTE
Lenze SMVector 13465100 EDBSV01 EN v18 21
Control and communications terminals provide basic insulation when the drive is connected to a power system rated up
to 300V between phase to ground (PE) and the applied voltage on terminals 16 and 17 is less than 250 VAC between
phase to phase and ground (PE).
Page 24
Installation
Control Terminal Strip Descriptions
Terminal DescriptionImportant
1
Digital Input: Start/Stopinput resistance = 4.3kW
2
Analog Common
5
Analog Input: 0...10 VDCinput resistance: >50 kW
6
Internal DC supply for speed pot+10 VDC, max. 10 mA
25
Analog Input: 4...20 mAinput resistance: 250W
4
Digital Reference/Common+15 VDC / 0 VDC, depending on assertion level
11
Internal DC supply for external devices+12 VDC, max. 50 mA
13A
Digital Input: Configurable with P121
13B
Digital Input: Configurable with P122
13C
Digital Input: Configurable with P123
13D*
Digital Input: Configurable with P124
14
Digital Output: Configurable with P142, P144DC 24 V / 50 mA; NPN
30
Analog Output: Configurable with P150…P1550…10 VDC, max. 20 mA
2*
Analog Common
TXA*
RS485 TxA
TXB*
RS485 TxB
16
Relay output: Configurable with P140, P144
17
* = Terminal is part of the terminal strip for the 15HP (11kW) and higher models only.
Assertion level of digital inputs
The digital inputs can be configured for active-high or active-low by setting the Assertion Level Switch (ALsw) and P120.
If wiring to the drive inputs with dry contacts or with PNP solid state switches, set the switch and P120 to “High” (+). If
using NPN devices for inputs, set both to “Low” (-). Active-high (+) is the default setting.
HIGH = +12 … +30 V
LOW = 0 … +3 V
NOTE
An F_AL fault will occur if the Assertion Level switch (ALsw) position does not match the parameter
P120 setting and P100 or any of the digital inputs (P121...P124) is set to a value other than 0.
input resistance = 4.3kW
AC 250 V / 3 A
DC 24 V / 2 A … 240 V / 0.22 A, non-inductive
22Lenze SMVector 13465100 EDBSV01 EN v18
Page 25
4 Commissioning
4.1 Local Keypad & Display
SMV Models: 0.33-10HP (0.25-7.5kW)SMV Models: 15HP (11kW) and greater
Commissioning
4-Character Display
FWDAUTO
CTRL
REV
RUN
STOP
AUTO
4-Character plus CTRL Display
REMOTE
LOCAL
MAN
AUTO
Display START BUTTON
In Local Mode (P100 = 0, 4, 6), this button will start the drive.
RUN
STOP BUTTON
Stops the drive, regardless of which mode the drive is in.
STOP
WARNING!
When JOG is active, the STOP button will not stop the drive!
ROTATION
In Local Mode (P100 = 0, 4, 6), this selects the motor rotation direction:
- The LED for the present rotation direction (FWD or REV) will be on
- Press R/F; the LED for the opposite rotation direction will blink
- Press M within 4 seconds to confirm the change
- The blinking direction LED will turn on, and the other LED will turn off
When rotation direction is changed while the drive is running, the commanded direction LED will blink until the
drive is controlling the motor in the selected direction.
Rotation is set in P112. When P112 = 0, rotation is forward only. When P112 = 1 rotation is forward and reverse.
MODE
RPM
Hz
%
AMPS
/UNITS
FWD
RUN
REV
STOP
Used to enter/exit the Parameter Menu when programming the drive and to enter a changed parameter value.
UP AND DOWN BUTTONS
Used for programming and can also be used as a reference for speed, PID setpoint, or torque setpoint.
When the p and q buttons are the active reference, the middle LED on the left side of the display will be on.
Lenze SMVector 13465100 EDBSV01 EN v18 23
Page 26
Commissioning
FWD
REV
AUTO
Display INDICATING LEDs (on 4-character display)
FWD LED: Indicate the present rotation direction is forward. Refer to ROTATION description above.
REV LED: Indicate the present rotation direction is reverse. Refer to ROTATION description above.
AUTO LED: Indicates that the drive has been put into Auto mode from one of the TB13 inputs (P121…P124 set
to 1…7). Indicates that PID mode is active (if PID mode is enabled). Indicates that sequencer mode is active (if
sequencer mode is enabled).
RUN LED: Indicates that the drive is running.
RUN
p q LED: Indicates that the p q are the active reference.
NOTE
If the keypad is selected as the auto reference (P121…P124 is 6) and the corresponding
TB-13 input is closed, the AUTO LED and p q LEDs will both be on.
FUNCTIONS THAT FOLLOW ARE APPLICABLE TO SMV DRIVES 15HP (11kW) AND HIGHER
CTRL
CTRL
The CTRL pushbutton selects the start and speed reference control sources for the drive.
Press [ ] mode button to accept the new control mode selection.
CTRL LEDs
MAN
REMOTE
LOCAL
REMOTE
LOCAL
REMOTE
LOCAL
REMOTE
LOCAL
AUTO
MAN
AUTO
MAN
AUTO
MAN
AUTO
[LOCAL] [MAN]
[LOCAL] [AUTO]
[REMOTE] [MAN]
[REMOTE] [AUTO]
If P100 = 6 the CTRL button is used to toggle
start control between the terminal strip [REMOTE]
and the keypad [LOCAL]
If P113 = 1 the CTRL button is used to toggle
reference control between the TB-13x setup
[AUTO] and P101 [MANUAL]
If P100 = 6 and P113 = 1, it is possible to
change the start and reference control sources at
the same time
START CONTROLREFERENCE CONTROL
KeypadP101 Settings
KeypadTerminal 13x Settings
Terminal StripP101 Settings
Terminal StripTerminal 13x Settings
- REM/LOC LED indicating the present start control source is ON
- Press [CTRL]; the LED for other start control source will blink
- Press [M] within 4 sec to confirm the change
- Blinking LED will turn ON (the other LED will turn OFF)
- AUT/MAN LED indicating present reference control is ON
- Press [CTRL]; the other reference control will blink
- Press [M] within 4 sec to confirm change
- Blinking LED will turn ON (the other LED will turn OFF)
24Lenze SMVector 13465100 EDBSV01 EN v18
Page 27
Commissioning
Display START CONTROL
The REMOTE/LOCAL LEDs indicate the current start control source. If the start control source is a remote keypad
or the network, then both LEDs will be OFF.
REFERENCE CONTROL
The AUTO/MANUAL LEDs indicate the current reference control source.
IF P113 = 0 or 2, the AUTO/MANUAL LEDs will match the AUTO LED on the 4-character display. IF P113 = 0
and no AUTO reference has been setup on the terminal strip, the MANUAL LED will turn ON and the AUTO LED
will turn OFF.
IF P113 = 1, the AUTO/MANUAL LEDS show the commanded reference control source as selected by the [CTRL]
button. If the [CTRL] button is used to set the reference control source to AUTO but no AUTO reference has been
setup on the terminal strip, reference control will follow P101 but the AUTO LED will remain ON.
UNITS LEDs
HZ: current display value is in HzIn Speed mode, if P178 = 0 then HZ LED will be ON. If
%: current display value is in %
RPM: current display value is in RPM
AMPS: current display value is in Amps
/UNITS current display value is a per unit (i.e./sec,
/min, /hr, etc.)
4.2 Drive Display and Modes of Operation
Speed Mode Display
In the standard mode of operation, the drive frequency output is set directly by the selected reference (keypad, analog
reference, etc.). In this mode, the drive display will show the drive’s output frequency.
PID Mode Display
When the PID mode is enabled and active, the normal run display shows the actual PID setpoint. When PID mode is not
active, the display returns to showing the drive’s output frequency.
Torque Mode Display
When the drive is operating in Vector Torque mode, the normal run display shows the drive’s output frequency.
Alternate (Run-Screen) Display
When P179 (Run Screen Display) is set to a value other than 0, one of the diagnostic parameters (P501…P599) is
displayed. Example: if P179 is set to 1, then diagnostic parameter P501 (Software version) is displayed. If P179 =2,
then P502 (Drive ID) is displayed.
P178 > 0, the Units LEDs follow the setting of P177 when
the drive is in run (non-programming) mode.
In Torque mode, the HZ LED will be ON when the drive is
in run (non-programming) mode.
In Pid mode, the Units LEDs follow the setting of P203
when the drive is in run (non-programming) mode.
If P179 > 0, the Units LEDs will show the unit of the
diagnostic parameter that is being displayed.
Lenze SMVector 13465100 EDBSV01 EN v18 25
Page 28
Commissioning
4.3 Parameter Setting
Status/Fault messages Change Parameters
StoP
60.0
CL
Err
F.AF
F.UF
4.4 Electronic Programming Module (EPM)
The EPM contains the drives operational memory. Parameter settings are stored in the
EPM and setting changes are made to the “User settings” in the EPM.
An optional EPM Programmer (model EEPM1RA) is available that allows:
As the EPM Programmer is battery operated, parameter settings can be copied to an EPM and inserted into a drive
without power being applied to the drive. This means that the drive will be fully operational with the new settings on
the next application of power.
Additionally, when the drives parameter settings are burned into an EPM with the EPM Programmer, the settings are
saved in two distinct locations; the “User settings” and the “OEM default settings”. While the User settings can be
modified in the drive, the OEM settings cannot. Thus, the drive can be reset not only to the “factory” drive default
settings (shown in this manual), but can be set to the Original Machine settings as programmed by the OEM.
The user area contents of the EPM are what are copied into the OEM space by the EPM programmer. When parameter
modifications are made to the drive and then a copy made via the EPM Programmer, these are the settings that will
be available by the OEM selections from P199. The EPM Programmer is the only way to load the OEM area of the EPM.
While the EPM can be removed for copying or to use in another drive, it must be installed for the drive to operate (a
missing EPM will trigger an F.F1 fault)
M
PASS
0225
M
P194 = 0000
60 s
p100
p104
p541
15 s
M
20.0
12.0
M
EPM Module
in SMV Drive
V0106
26Lenze SMVector 13465100 EDBSV01 EN v18
Page 29
Commissioning
4.5 Parameter Menu
4.5.1 Basic Setup Parameters
CodePossible Settings
No.NameDefault Selection
Start Control Source00 Local KeypadUse RUN button on front of drive to start
P100
1 Terminal StripUse start/stop circuit wired into the terminal strip.
2 Remote Keypad OnlyUse RUN button on optional Remote Keypad to start
3 Network Only• Start command must come from network
4 Terminal Strip or Local KeypadAllows start control to be switched between
5 Terminal Strip or Remote KeypadAllows start control to be switched between
6 CTRL button selectAllows start control to be switched between
WARNING!
P100 = 0 disables TB-1 as a STOP input! STOP circuitry may be disabled if parameters are
reset back to defaults (see P199)
NOTE
• P100 = 4, 5: To switch between control sources, one of the TB-13 inputs (P121...P124)
must be set to 08 (Control Select);
TB-13x OPEN (or not configured): Terminal strip control
TB-13x CLOSED: Local (P100 = 4) or Remote (P100 = 5) keypad
• P100 = 0, 1, 4, 6: Network can take control if P121...P124 = 9 and the corresponding
TB-13x input is CLOSED.
• The STOP button on the front of the drive is always active except in JOG mode.
• TB-1 is an active STOP input if P100 is set to a value other than 0.
Refer to section 3.2.3
(Modbus, CANopen, etc)
• SMV models <15HP (11kW) require optional
communication module (refer to the network
module documentation).
• Must also set one of the TB-13 inputs to 9
(Network Enable); see P121...P124
terminal strip and local keypad using one of the
TB-13 inputs. See note below.
terminal strip and optional remote keypad using
one of the TB-13 inputs. See Note below
terminal strip and local keypad using the CTRL
button.
NOTE: P100 Selection 6 is applicable to SMV 15HP
(11kW) and higher models only.
• An F.AL fault will occur if the Assertion Level switch (ALsw) position does not match
the P120 setting and P100 is set to a value other than 0.
Standard Reference
P101
Source
00 Keypad (Local or Remote)Selects the default speed or torque reference
• P103 cannot be set below Minimum Frequency (P102)
• To set P103 above 120 Hz:
- Scroll up to 120 Hz; display shows HiFr (flashing).
- Release s button and wait one second.
WARNING!
Consult motor/machine manufacturer before operating above rated frequency. Overspeeding the motor/machine may cause
damage to equipment and injury to personnel!
Acceleration Time 120.0 0.0 {s} 3600• P104 = time of frequency change from 0 Hz to
P104
Deceleration Time 120.0 0.0 {s} 3600
P105
EXAMPLE: IF P103 = 120 Hz, P104 = 20.0 s and P167 (base frequency) = 60 Hz; then the rate of frequency change from 0
Hz to 120 Hz = 40.0 s
S-Ramp Integration
P106
Time
(1)
Line Voltage Selection1*0 Low (120, 200, 400, 480VAC)* The default setting is 1 for all drives except
p107
- Press s button again to continue increasing P103.
0.0 0.0 {s} 50.0• P106 = 0.0: Linear accel/decel ramp
1 High (120, 240, 480, 600VAC)
Motor Overload100 30 {%} 100P108 = motor current rating x 100
p108
NOTE
Do not set above rated motor current as listed on the motor dataplate. The motor thermal
overload function of the SMV is UL approved as a motor protection device. Cycling power after
an overload fault could result in significantly reducing the motor life.
Motor Overload Type00 Speed Compensation
P109
references
•Whenusing an analog speed
reference, also see P160, P161
P167 (base frequency)
• P105 = time of frequency change from P167
to 0 Hz
• For S-ramp accel/decel, adjust P106
• P106 > 0.0: Adjusts S-ramp curve for smoother
ramp
when using “Reset to 50Hz default settings”
(Parameter P199, selection 4) with 480V
models. In this case, the default setting is 0.
SMV output rating
Example: if motor = 3amps and SMV = 4amps,
then P108 = 75%
IMPORTANT
Ir
60%
0
1 No Speed Compensation
Example: Motor is cooled by forced
ventilation as apposed to shaft mounted,
self cooling fans.
(1) Any changes to this parameter will not take effect until the drive is stopped.
28Lenze SMVector 13465100 EDBSV01 EN v18
V0108
Page 31
Commissioning
CodePossible Settings
No.NameDefault Selection
Start Method00 Normal
P110
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to personnel! Automatic starting/restarting should
only be used on equipment that is inaccessible to personnel.
Stop Method00 CoastDrive’s output will shut off immediately upon a stop
P111
Rotation00 Forward OnlyIf PID mode is enabled, reverse direction is disabled
P112
1 Start on Power-upDrive will automatically start when power is
2 Start with DC BrakeWhen start command is applied, drive will apply
3 Auto RestartDrive will automatically restart after faults, or when
4 Auto Restart with DC BrakeCombines settings 2 and 3
5 Flying Start/Restart - Type 1• Drive will automatically restart after faults, or
6 Flying Start/Restart - Type 1
7 Flying Start /Restart - Type 2
for 2-pole motors requiring a flying
restart
8 Flying Start/Restart - Type 2
for 2-pole motors requiring a flying
restart
NOTE
• P110 = 0, 2: Start command must be applied at least 2 seconds after power-up; F.UF
fault will occur if start command is applied too soon.
• P110 = 1, 3…6: For automatic start/restart, the start source must be the terminal strip
and the start command must be present.
• P110 = 2, 4…6: If P175=999.9, dc braking will be applied for 15s.
• P110 = 3…6: Drive will attempt 5 restarts; if all restart attempts fail, drive displays LC
(fault lockout) and requires manual reset.
• P110 = 5, 6: If drive cannot catch the spinning motor, drive will trip into F.rF fault.
• P110 = 5, 6: If drive trips into F.OF fault, try P110 = 7 or 8.
1 Coast with DC BrakeThe drive’s output will shut off and then the DC
2 RampThe drive will ramp the motor to a stop according
3 Ramp with DC BrakeThe drive will ramp the motor to 0 Hz and then
1 Forward and Reverse
applied.
DC braking according to P174, P175 prior to
starting the motor
power is applied.
when power is applied.
• After 3 failed attempts, drive will Auto Restart
with DC brake.
• P110 = 5, 7: Performs speed search, starting
at Max Frequency (P103)
• P110 = 6, 8: Performs speed search, starting
at the last output frequency prior to faulting
or power loss
• If P111 = 0, a flying START is performed when
a start command is applied.
• P110 = 7,8: Utilizes P280/281 to set Max
Current Level and Decel Time for restart
command, allowing the motor to coast to a stop
Brake will activate (refer to P174, P175)
to P105 or P126.
the DC Brake will activate (refer to P174, P175)
(except for Jog).
IMPORTANT
Lenze SMVector 13465100 EDBSV01 EN v18 29
Page 32
Commissioning
CodePossible Settings
No.NameDefault Selection
Auto/Manual Control00 Terminal Strip ControlThe reference is dictated by the settings and state
P113
P115
MOP Speed
Initialization at
Power-Up
1 Auto/Manual (CTRL button select)Allows the reference to be switched between auto
2 Manual Control OnlyReference is dictated by P101 regardless of any
NOTE
P113 is applicable to SMV 15HP (11kW) and higher models only.
00 Set to last MOP speed at power up Output frequency at power-up = last MOP speed
1 Set to 0.0Hz at power upOutput frequency at power-up = 0Hz
2 Set to Preset #3 (P133) at power up Output frequency at power-up = P133
of the TB-13x terminals. If no AUTO reference has
been setup on the terminal strip then reference
control is dictated by P101.
and manual using the CTRL pushbutton on the
drive keypad. If the CTRL pushbutton has selected
AUTO reference but no AUTO reference has been
setup on the terminal strip, then reference control
is dictated by P101.
AUTO source that may be selected by the TB-13x
terminals.
IMPORTANT
30 Lenze SMVector 13465100 EDBSV01 EN v18
Page 33
Commissioning
4.5.2 I/O Setup Parameters
CodePossible Settings
No.NameDefault Selection
Assertion Level21 LowP120 and the Assertion Level switch must both
p120
TB-13A Digital Input
P121
TB-13B Digital Input
p122
(Priority > TB13A)
Same as TB13A except:
3 = Preset #2
23 = Seq Seg, #2
TB-13C Digital Input
p123
(Priority > TB13B, A)
Same as TB13A except:
3 = Preset #3
23 = Seq Seg, #4
p124
TB-13D* Digital Input
(Priority > TB13C, B, A)
Same as TB13A except:
3 = Preset #4
23 = Seq Seg, #8
NOTE: P124 is
applicable to SMV
15HP (11kW) and
higher models only
2 High
00 NoneDisables input
1 AUTO Reference: 0-10 VDCFor frequency mode, see P160...P161,
2 AUTO Reference: 4-20 mA
3 AUTO Reference: Preset #1
* 13D: 3 = Reserved
4 AUTO Reference: MOP Up• Normally open: Close input to increase or
5 AUTO Reference: MOP Down
6 AUTO Reference: Keypad
7 AUTO Reference: Network
8 Control SelectUse when P100 = 4, 5 to switch between terminal
9 Network EnableRequired to start the drive through the network.
10 Reverse RotationOpen = Forward Closed = Reverse
11 Start Forward
12 Start Reverse
13 Run Forward
14 Run Reverse
15 Jog ForwardJog Forward speed = P134
16 Jog ReverseJog Reverse speed = P135
17 Accel/Decel #2Refer to P125, P126
18 DC BrakeRefer to P174; close input to override P175
19 Auxiliary Ramp to StopNormally closed: Opening input will ramp drive
20 Clear FaultClose to reset fault
21 External Fault F.EF
22 Inverse External Fault F.EF
23 AUTO Ref: Sequence Segment #1Works in Speed Mode only
24 Start Sequence
25 Step SequenceTransition from non-asserted to asserted state
26 Suspend Sequence
match the desired assertion level unless P100,
P121…P124 are all set to 0. Otherwise an F.AL
fault will occur.
For PID mode, see P204…P205,
For vector torque mode, see P330
For frequency mode see P131...P137,
For PID mode, see P231…P233,
For torque mode see, P331…P333
decrease speed, PID or torque setpoint.
• MOP Up is not active while in STOP
strip control and local or remote keypad control.
Refer to Note for typical circuit
Refer to Note for typical circuit
Active even if P112 = 0
to STOP according to P127, even if P111 is set
to Coast (0 or 1).
Normally closed circuit; open to trip
Normally open circuit; close to trip
WARNING
Jog overrides all STOP commands! To stop the drive while in Jog mode, the Jog input must be deactivated or a
fault condition induced.
WARNING
If the input defined to “Start Sequence” is opened during a sequence, the drive will exit sequencer mode and will run
at the specified standard or alternate speed source (dependent on drive configuration).
IMPORTANT
Lenze SMVector 13465100 EDBSV01 EN v18 31
Page 34
Commissioning
REV
RUN
REVSTOP
CodePossible Settings
No.NameDefault Selection
NOTE
• When input is activated, settings 1...7 override P101
• When TB-13A...TB-13D are configured for Auto References other than MOP, TB-13D overrides TB-13C, TB-13C overrides
TB-13B and TB-13B overrides TB-13A. Any other Auto Reference will have priority over MOP.
• Settings 10...14 are only valid in Terminal Strip mode (P100 = 1, 4, 5, 6)
• If Start/Run/Jog Forward and Start/Run/Jog Reverse are both activated, drive will STOP
• If Jog input is activated while drive is running, the drive will enter Jog mode; when Jog input is deactivated, drive will STOP
• An F.AL fault will occur if the Assertion Level switch (ALsw) position does not match the P120 setting and any of the digital
inputs (P121...P124) are set to a value other than 0.
• An F.IL fault will occur under the following conditions:
- TB-13A...TB-13D settings are duplicated (each setting, except 0, 3 and 23, can only be used once)
- One input is set to “MOP Up” and another is not set to “MOP Down”, or vice-versa.
- One input is set to 10 and another input is set to 11…14.
- One input is set to 11 or 12 and another input is set for 13 or 14.
• Typical control circuits are shown below:
- If any input is set to 10, 12 or 14, P112 must be set to 1 for Reverse action to function.
Run / Stop
with Direction
P121 = 10
STOP
13 A
FWD
20.0 0.0 {s} 3600• Selected using TB-13A...TB-13D (P121...
0.0 0.0 {Hz} 1000If Actual Frequency < P129 Use Accel/decel time
14
Acceleration Time 220.0 0.0 {s} 3600• Selected using TB-13A...TB-13D (P121...
P125
Deceleration Time 220.0 0.0 {s} 3600
P126
Deceleration Time
p127
for Auxiliary Ramp
to Stop
Automatic Accel/
p129
Decel rate switch
threshold
Preset Speed #10.0 0.0 {Hz} 500
p131
Preset Speed #20.0 0.0 {Hz} 500
p132
Preset Speed #30.0 0.0 {Hz} 500
p133
Preset Speed #40.0 0.0 {Hz} 500
p134
Preset Speed #50.0 0.0 {Hz} 500
p135
Preset Speed #60.0 0.0 {Hz} 500
p136
Preset Speed #70.0 0.0 {Hz} 500
p137
Preset Speed #80.0 0.0 {Hz} 500
p138
Start Forward /
Start Reverse
P121 = 11, P122 = 12
13 A13B
14
FWD
P124 = 17)
• For S-ramp accel/decel, adjust P106
P124 = 19).
• For S-ramp accel/decel, adjust P106
• Once executed, this ramp time has priority over
P105 and P126.
#2 (P125/P126)
If Actual Frequency > P129 Use Accel/decel time
#1 (P104/P105)
PRESET
4 (alternate) ------X
8 (alternate) --X--X
8 (alternate----XX
• Speed setting is used by P158
• 13D available on 15HP (11kW) & higher drives.
IMPORTANT
Run Forward /
Run Reverse
P121 = 13, P122 = 14
14
SPEED
1X------
13 A13B
RUN
FWD
RUN
REV
13A 13B 13C 13D
2--X---3----X-4XX----
5X--X-6--XX-7XXX--
32Lenze SMVector 13465100 EDBSV01 EN v18
Page 35
Commissioning
CodePossible Settings
No.NameDefault Selection
Relay Output
p140
TB-16, 17
TB-14 Output00...23 (same as P140)
p142
00 NoneDisables the output
1 RunEnergizes when the drive is running
2 ReverseEnergizes when reverse rotation is active
3 FaultDe-energizes when the drive trips, or power is
4 Inverse FaultEnergizes when the drive trips
5 Fault LockoutP110 = 3...6: De-energizes if all restart attempts
6 At SpeedEnergizes when output frequency = commanded
7 Above Preset Speed #6Energizes when output frequency > P136
8 Current LimitEnergizes when motor current = P171
9 Follower Loss (4-20 mA)Energizes when 4-20 mA signal is < P164
10 Loss of LoadEnergizes when motor load drops below P145;
11 Local Keypad Control Active
12 Terminal Strip Control Active
13 Remote Keypad Control Active
14 Network Control Active
15 Standard Reference ActiveEnergizes when P101 reference is active
16 Auto Reference ActiveEnergizes when Auto Reference is activated using
17 Sleep Mode ActiveRefer to P240...P242
18 PID Feedback < Min. AlarmEnergizes when PID feedback signal < P214
19 Inverse PID Feedback < Min. Alarm De-energizes when PID feedback signal < P214
20 PID Feedback > Max AlarmEnergizes when PID feedback signal > P215
21 Inverse PID Feedback > Max Alarm De-energizes when PID feedback signal > P215
22 PID Feedback within
Min/Max Alarm range
23 PID Feedback outside
Min/Max Alarm range
24 Reserved
25 Network ControlledSMV models < 15HP (11kW) require an optional
26 Loss of 0-10V InputEnergizes when 0-10V signal is < P158
27 Sequencer ControlledState set in individual sequencer segments
28 Sequencer Active
29 Sequencer Suspended
30 Sequence DoneEnd Sequence
31 Output Frequency = 0.0HzOutput inactive
24 Dynamic BrakingFor use with Dynamic Braking option
25...31 (same as P140)
IMPORTANT
removed
fail
frequency
Refer to P146 also
Energizes when the selected source is active for
start control
TB-13 input; refer to P121...P124
Energizes when PID feedback signal is within the
Min/Max Alarm range; refer to P214, P215
Energizes when PID feedback signal is outside the
Min/Max Alarm range; refer to P214, P215
communication module (refer to the network
module documentation).
Lenze SMVector 13465100 EDBSV01 EN v18 33
Page 36
Commissioning
CodePossible Settings
No.NameDefault Selection
Digital Output
P144
Inversion
NOTE
Inverting P140 or P142 when the parameter is set to NONE (0) will result in the output being
energized continuously.
NOTE
For SMVector drives rated at 0.33 to 10 HP (0.25 to 7.5 kW), P144 is only available with
TB-30 Output00 None2-10 VDC signal can be converted to 4-20 mA with
p150
Add Analog Input to
p151
TB-30 Output
TB-30 Scaling:
p152
Frequency
TB-30 Scaling: Load200 10 {%} 500If P150 = 3 or 4, sets the Load (as a percent of
p153
TB-30 Scaling:
p154
Torque
TB-30 Scaling:
p155
Power (kW)
software versions 3.0 and higher (refer to P501).
00 {%} 200P140, P142 = 10: Output will energize if motor
1 0-10 VDC Output Frequency
2 2-10 VDC Output Frequency
3 0-10 VDC Load
4 2-10 VDC Load
5 0-10 VDC Torque
6 2-10 VDC Torque
7 0-10 VDC Power (kW)
8 2-10 VDC Power (kW)
9 Network ControlledSMV models < 15HP (11kW) require an optional
10 Sequencer ControlledValue set in individual sequencer segments
0
P151
60.0 3.0 {Hz} 2000If P150 = 1 or 2, sets the frequency at which output
100 10 {%} 1000If P150 = 5 or 6, sets the Torque (as a percent of
1.0 0.1 {kW} 200.0If P150 = 7 or 8, sets the power at which output
Invert
P144
P142
0NONO
1NOYES
2YESNO
3YESYES
Add TB-25
Add TB-5
(4-20mA)
0NONO
1NOYES
2YESNO
3YESYES
(0-10VDC)
Invert
P140
Used to invert the selections for P140 (Relay Output)
and P142 (TB-14 Output).
EXAMPLE: When P140 = 6 (AT SPEED), the relay is
energized when output frequency = commanded
frequency. IF P144=1 or 3, then P140 is inverted
(INVERSE AT SPEED) and the relay is energized
when the output frequency does not equal the
command frequency.
load falls below the P145 value longer than the
P146 time
communication module (refer to the network
module documentation).
This parameter adds the analog input signal(s) to
the TB-30 Output signal. EXAMPLE: If a drive is
running at 60Hz with P150 set to 1 (0-10VDC Freq)
and P152 set to 240.0Hz, the output at TB-30 would
be 2.5VDC. If there is a 2.0VDC signal going into
TB-5 and P151 is set to 1 (ADD TB-5), the output
at TB-30 would become 4.5VDC.
equals 10 VDC
drive current rating) at which output equals 10 VDC.
00 No ActionSelects the reaction to a loss of the 0-10V signal
1 If TB5 < P158 - Trip Fault F.FAU
2 If TB5 < P158 - Run Preset #8
3 If TB5 < P158 - Run Preset Seg. #16
4 If TB5 > P158 - Trip Fault F.FAU
5 If TB5 > P158 - Run Preset #8
6 If TB5 > P158 - Run Preset Seg. #16
0.0 -10.0 {VDC} 10.0 Negative input voltage is not currently supported.
0.0 0 {VDC} 10.0Not active if [-10 to +10 VDC] option is selected.
0.0 -999.0 {Hz} 1000
Commissioning
at TB5
500ms is the minimum time above/below
Monitoring Level (P158) before triggering the
drive to trip or run at a preset speed.
For P157 = 3 or 6, the accel/decel time is set
in P786.
NOTE: P157 has priority over P163 and TB-13
presets/auto references (P121-P124)
f
P161
IMPORTANT
P161
Speed at Maximum
Signal
60.0 -999.0 {Hz} 1000
P160
(4mA)
ref
0V
10V
(20mA)
V0111
NOTE
• P160 sets the output frequency at 0% analog input
• P161 sets the output frequency at 100% analog input
• P160 or P161 < 0.0 Hz: For scaling purposes only; does not indicate opposite direction!
Analog Input Filter0.01 0.00 {s} 10.00• Adjusts the filter on the analog inputs (TB-5
p162
TB-25 (4-20mA)
P163
Analog Input
Monitoring Action
• P160 > P161: Drive will react inversely to analog input signal
and TB-25) to reduce the effect of signal noise
• The P162 delay time will affect the response
00 No Action• Selects the reaction to a loss of the 4-20 mA
1 If TB25 < P164 - Trip Fault F.FoL
2 If TB25 < P164 - Run Preset #7
3 If TB25 < P164 - Run Preset Seg. #15
4 If TB25 > P164 - Trip Fault F.FoL
5 If TB25 > P164 - Run Preset #7
6 If TB25 > P164 - Run Preset Seg. #15
time of diagnostic parameters (P520-P523).
signal at TB-25.
• Signal is considered lost if it falls below the
value set in P164
• Digital outputs can also indicate a loss of 4-20
mA signal; see P140, P142
• For P163 = 3 or 6, the accel/decel time is
set in P781.
NOTE: P163 has priority over TB-13 presets/auto
references (P121-P124)
Lenze SMVector 13465100 EDBSV01 EN v18 35
Page 38
Commissioning
CodePossible Settings
No.NameDefault Selection
TB-25 (4-20mA)
P164
Analog Input
Monitoring Level
Base Voltage15 {V} 1000Valid for V/Hz mode only.
P165
Carrier FrequencySee
P166
(1)
Base Frequency60.0 10.0 {Hz} 1500
p167
Fixed Boost0.0 {%} 40.0
p168
Accel Boost0.00.0 {%} 20.0Accel Boost is only active during acceleration
p169
Slip Compensation0.00.0 {%} 40.0Increase P170 until the motor speed no longer
P170
(1)
Current LimitMax I 30 {%} Max I• When the limit is reached, the drive displays
p171
Current Limit
P172
Reduction
Decel Override Time2.0 0.0 {s} 60.0Maximum time before drive trips into HF fault.
P173
DC Brake Voltage0.0 0.0 {%} 50.0Setting is a percent of the nominal DC bus voltage.
P174
2.0 0.0 {mA} 20.0
0 4 kHz• As carrier frequency is increased, motor noise
Notes
1 6 kHz
2 8 kHz
3 10 kHz
NOTE
• P167 = rated motor frequency for standard applications
• P165, P168 = default setting depends on drive rating
00 Current Limit Reduction Active -
Normal response
1 Current Limit Reduction Active - Fast
response
2 Current Limit Reduction Disabled -
Normal response
3 Current Limit Reduction Disabled -
Fast response
Set voltage for bus compensation in V/Hz mode
is decreased
• Observe derating in section 2.3
• Automatic shift to 4 kHz at 120% load
• NEMA 4X (IP65) Models: Default = 0 (4kHz)
• NEMA 1 (IP31) Models: Default = 1 (6kHz)
changes between no load and full load conditions.
CL(Current Limit), and either the acceleration
time increases or the output frequency
decreases.
• Digital outputs can also indicate when the limit
is reached; see P140, P142.
• Refer to section 2.3 for the maximum output
current Max I (%)
In field weakening, the Current Limit is inversely
proportional to the speed.
IMPORTANT
V0112
(1) Any changes to this parameter will not take effect until the drive is stopped.
36Lenze SMVector 13465100 EDBSV01 EN v18
Page 39
Commissioning
CodePossible Settings
No.NameDefault Selection
DC Brake Time0.0 0.0 {s} 999.9
p175
Keypad Setpoint
p176
Single Press
Increment
(2)
Speed Units00 HzSelect the UNITS LED that will be illuminated when
p177
Display Frequency
p178
Multiplier
Run Screen Display00 {Parameter Number} 599• 0 = Normal Run Screen, this display depends
p179
Oscillation Damping
p180
Control
Skip frequency 10.00.0 {Hz} 500• Drive will not run in the defined skip range;
p181
Skip frequency 20.00.0 {Hz} 500
p182
Skip frequency
p184
bandwidth
Voltage Midpoint
p185
V/Hz characteristic
(2)
Frequency Midpoint
p187
V/Hz characteristic
(3)
Integrated Dynamic
p189
Brake
NOTE: CONFIRM MOTOR SUITABILITY FOR USE WITH DC BRAKING
DC Brake voltage (P174) is applied for the time specified by P175 with the following exceptions:
• If P111=1, 3 and P175=999.9 the brake voltage will be applied continuously until a run
or fault condition occurs.
• If P110=2, 4…6 and P175=999.9, brake voltage will be applied for 15s
• If P121…P124=18 and the corresponding TB-13 input is CLOSED, brake voltage will be
applied until the TB-13 input is OPENED or a fault condition occurs.
0.1 0.1 100.0Used for run screen setpoint editing only.
1 RPM
2 %
3 /UNITS
4 NONE
0.00 0.00 650.00• Allows frequency display to be scaled
EXAMPLE
If P178 = 29.17 and actual frequency = 60 Hz, then Drive displays 1750 (rpm)
00 800 = Damping disabled
0.0 0.0 {Hz} 10.0
NOTE
Bandwidth (Hz) = fs (Hz) + P184 (Hz) fs = P181 or P182
EXAMPLE: P181 = 18 Hz and P184 = 4 Hz; skip range is from 18 to 22 Hz
00.0 {V} P165Valid only when P300 = 0 or 2.
0.0 0.0 {Hz} P167Valid only when P300 = 0 or 2.
0 Disabled
1 Enabled
If P176 >0.1 then scrolling of keypad setpoint
is enabled.
the drive is running in speed control mode. For this
parameter to be used, P178 must be set to a value
other than 0. IF P178 is set to 0, the Hz LED will
be illuminated regardless of the value set in P177.
• P178 = 0.00: Scaling disabled
• P178 > 0.00: Display = Actual Frequency
X P178
on mode of operation. Refer to section 4.2.
• Other selections choose a diagnostic parameter
to display (P501…P599).
• Parameters P560 - P564 are selectable if
the sequencer is enabled (P700 is not 0).
P560-P564 are not visible until P700 is
enabled.
Compensation for resonances within drive
used to skip over frequencies that cause
mechanical vibration
• P181 and P182 define the start of the skip
ranges
• P184 > 0 defines the bandwidth of both ranges.
Use with P187 to define midpoint on V/Hz curve.
Use with P185 to define midpoint on V/Hz curve.
IMPORTANT
(2) Parameter applicable to SMV models 15HP (11kW) and higher.
(3) Parameter applicable to SMV models 40HP (30kW) and higher.
Lenze SMVector 13465100 EDBSV01 EN v18 37
Page 40
Commissioning
CodePossible Settings
No.NameDefault Selection
Motor Braking0 Disabled
p190
1 Braking with BUS threshold
2 Braking always on with deceleration
3 Braking with bus regulator
4 Special
Flux brake OFF.
When drive is in deceleration and V
the rated V
As long as drive is in deceleration, the flux brake will be ON.
When drive is in deceleration and V
of the rated V
the bus voltage. Determined by the value in P191, the speed
increment = slip speed * P191(%) / 37.
(Consult factory before using)
IMPORTANT
> V
bus
bus
> V
deceleration freeze
deceleration freeze
), the flux brake will be turned ON.
bus
), the motor speed will be increased to reduce
bus
(114% of
(114%
WARNING
Flux braking can cause heat in the motor. To avoid damage to the motor, use a PTC to
Motor Brake Level00 {%} 75
p191
Motor Braking
p192
Deceleration
Reduction Level
Password00000 9999• Must enter password to access parameters
P194
Clear Fault History00 No Action
P197
protect the motor. If the flux brake is used too frequently, the drive will trip fault “F_PF”.
(flux
braking
disabled)
0.0 0 P167
(base freq)
Raising the value of P191 reduces the
drive deceleration rate during flux braking.
Active when P190 > 0 and drive is in deceleration
mode. Use to reduce deceleration time on high
inertia loads.
NOTE: Over usage of P190 can cause frequent
‘overload’ trips “F.PF”
Not active for P300 = 5 (Torque mode)
Active when P190 > 0 and P192 > 0.0, Drive is
in deceleration mode. Use to reduce deceleration
time on high inertia loads.
NOTE: Usage of P192 can cause the drive to
decelerate faster than settings in P105/P127.
Not active for P300 = 5 (Torque mode)
• P194 = 0000: Disables password
1 Clear Fault History
Program Selection0 Operate from User settings
p199
1 Operate from OEM settingsRefer to Notes 1, 2 and 3
2 Reset to OEM default settingsRefer to Note 1
3 Reset to 60 Hz default settings• Refer to Note 4
4 Reset to 50 Hz default settings
• Parameters are reset to the defaults listed in
this manual.
• For P199=4, the following exceptions apply:
- P103, P152, P161, P167 = 50.0 Hz
- P165 = 400V (400/480V drives only)
- P304 = 50 Hz
- P305 = 1450 RPM
- P107 = 0 (480 V drives only)
5 TranslateRefer to Note 5
WARNING!
Modification of P199 can affect drive functionality! STOP and EXTERNAL FAULT circuitry may
be disabled! Check P100 and P121...P124
NOTE 1
If the EPM does not contain valid OEM settings, a flashing GF will be displayed when P199
is set to 1 or 2.
NOTE 2
When P199 is set to 1, the drive operates from the OEM settings stored in the EPM Module
and no other parameters can be changed (GE will be displayed if attempted).
NOTE 3
Auto Calibration is not possible when operating from OEM Settings.
NOTES 4 and 5 - on next page.
38 Lenze SMVector 13465100 EDBSV01 EN v18
Page 41
Commissioning
CodePossible Settings
No.NameDefault Selection
Program SelectionNOTE 4
p199
Resetting to 50 and 60 Hz default settings will set the Assertion Level (P120) to “2” (High).
P120 may need to be reset for the digital input devices being used. An F.AL fault may occur
if P120 and the Assertion switch are not set identically.
NOTE 5
If an EPM that contains data from a previous compatible software version is installed:
• The drive will operate according to the previous data, but parameters cannot be changed
(cE will be displayed if attempted)
• To update the EPM to the current software version, set P199 = 5. The parameters can now
be changed but the EPM is incompatible with previous software revisions.
IMPORTANT
4.5.4 PID Parameters
CodePossible Settings
No.NameDefault Selection
PID Mode00 Disabled• Normal-acting: As feedback increases, motor
P200
1 Normal-acting
2 Reverse-acting
3 Normal-acting, Bi-directional
4 Reverse-acting, Bi-directional
NOTE
To activate PID mode, one of the TB-13 inputs (P121...P124) must be used to select the
Auto Reference that matches the desired PID setpoint reference. If the selected PID setpoint
reference uses the same analog signal as the PID feedback (P201), an F.IL fault will occur.
Example: The desired PID setpoint reference is the keypad (p and q). Set TB-13x = 6
(Auto Reference: Keypad):
• TB-13x = closed: PID mode is active
• TB-13x = open: PID mode is disabled and the drive speed will be controlled by the
PID Feedback Source00 4-20 mA (TB-25)Must be set to match the PID feedback signal
1 Enter SLEEP if Feedback >P243For time longer than P241 or same as Sel 0
2 Enter SLEEP if Feedback <P243For time longer than P241 or same as Sel 0
00 Coast to Stop
1 Ramp to Stop
2 Stop with P111 settings
0.0 P204 P205Active only when P247 = 1 or 2
00 Recovery if Speed Setpoint > P240
or if PID feedback differs from setpoint
by more than P242
1 Recovery only if Feedback < P246
2 Recovery only if Feedback > P246
• Increase P207 until system becomes unstable,
then decrease P207 by 10-15%
• Next, increase P208 until feedback matches
setpoint
• If required, increase P209 to compensate for
sudden changes in feedback
or vice versa.
• Used to smooth the transition from one PID
setpoint to another, such as when using the
Preset PID Setpoints (P231...P233)
output frequency = 0.0 Hz; drive display = SLP
• P240 = 0.0: Sleep mode is disabled.
• P200 = 0…2: Drive will start again when speed
max
command is above P240
• P242 > 0.0: Drive will restart when the PID
feedback differs from the setpoint by more
than the value of P242 or when the PID loop
requires a speed above P240.
IMPORTANT
(2) Parameter applicable to SMV models 15HP (11kW) and higher.
40Lenze SMVector 13465100 EDBSV01 EN v18
Page 43
Commissioning
Time
CodePossible Settings
No.NameDefault Selection
Auto Rinse in Sleep
P250
Mode
Time Delay between
P251
Auto Rinses
Auto Rinse Speed0.0-500.0 {Hz} 500.0If P112 = 1, negative sign = reverse direction
P252
Auto Rinse Time0.0 0.0 {sec} 6553.5Does not include time to decel back to speed
P253
Current Level: Flying
P280
Restart Type 2
Decel Time: Flying
P281
Restart Type 2
00 DisabledActivated in sleep mode only.
1 Enabled
Sleep Recovery cancels Auto Rinse
30.0 0.0 {min} 6553.5Time delay reset by re/entering sleep mode
Auto Pump Rinse Setup:
P250=1 (Enabled)
P251=# minutes between each
PumpRinse
P252=Hz speed of Pump Rinse
P253=# seconds Pump Rinse duration
70.0 0.0 {%} P171Maximum current during Type 2 flying restart
3.0 0.0 {sec} 3600.0Deceleration rate used during Type 2 flying
between each
Output Frequency
operation
restart operation
Delay Time
Pump Rinse
P251
IMPORTANT
P104/
P125
Pump Rinse Speed
Pump Rinse Time
P253
4.5.5 Vector Parameters
CodePossible Settings
No.NameDefault Selection
(1)
Drive Mode00 Constant V/HzConstant torque V/Hz control for general applications
P300
(1)
Motor Rated Voltage0 {V} 600
P302
(1)
Motor Rated Current0.1 {A} 500.0
P303
1 Variable V/HzVariable torque V/Hz control for centrifugal pump
2 Enhanced Constant V/HzFor single or multiple motor applications that require
3 Enhanced Variable V/Hz
5 Vector TorqueFor single-motor applications requiring torque control
NOTE
To configure the drive for either Vector mode or Enhanced V/Hz mode:
• P300 = 4, 5:
- Set P302...P306 according to motor nameplate
- Set P399 = 1 or 2 (if option 1 failed or in case of non-standard motor)
- Make sure motor is cold (20° - 25° C) and apply a Start command
- Display will indicate CAL for about 40 seconds
- Once the calibration is complete, the display will indicate Stop; apply another Start
command to actually start the motor
- If an attempt is made to start the drive in Vector or Enhanced V/Hz mode before
performing the Motor Calibration, the drive will display F.n1d and will not operate
• P300 = 2, 3: Same as above but only need to set P302…P304
and fan applications
better performance than settings 0 or 1, but cannot
use Vector mode, due to:
• Missing required motor data
• Vector mode causing unstable motor operation
starting torque and speed regulation
independent of speed
• Default setting = drive rating
• Set to motor nameplate data
IMPORTANT
P252
P105/
P126
(1) Any changes to this parameter will not take effect until the drive is stopped.
Lenze SMVector 13465100 EDBSV01 EN v18 41
Page 44
Commissioning
CodePossible Settings
No.NameDefault Selection
(1)
Motor Rated
p304
Frequency
(1)
Motor Rated Speed1750 300 {RPM} 65000
P305
(1)
Motor Cosine Phi0.80 0.40 0.99
P306
(1)
Motor Stator
P310
Resistance
(1)
Motor Stator
p311
Inductance
Dead Time
P315
Compensation Factor
Torque Limit100 0 {%} 400When P300 = 5, sets the maximum output torque.
P330
Preset Torque
P331
Setpoint #1
Preset Torque
P332
Setpoint #2
Preset Torque
P333
Setpoint #3
(2)
Preset Torque
P334
Setpoint #4
(1)
Current Loop P Gain0.25 0.00 16.0Changing these settings can adversely affect
P340
(1)
Current Loop I Gain6512 {ms} 9990
P341
(1)
Speed Loop Adjust0.0 0.0 {%} 20.0
P342
Slip Compensation
P343
Response Filter
Motor Auto-
P399
calibration
600 {Hz} 1000
Set to motor nameplate data
NOTE If motor cosine phi is not known, use one of the following formulas:
cos phi = motor Watts / (motor efficiency X P302 X P303 X 1.732)
cos phi = cos [ sin-1 (magnetizing current / motor current) ]
Fault History Counter 0 255Number of sequential occurrences of a fault.
P552
Display Range (READ ONLY)IMPORTANT
• Format: n.xxx where: n = 1..8,
1 is the newest fault; xxx = fault message (w/o the F.)
• Refer to section 5.3
does not match the drive model it is plugged into.
Refer to section 2.3.
0 {Hz} 500.0
0 {Hz} 500.0 Command speed if (Auto: Network) is selected as the speed
source
Indicates terminal status using segments of the LED display.
(Refer to section 4.5.7.1)
display. (Refer to section 4.5.7.2)
• Format: n.xxx where: n = 1..8,
1 is the newest fault; xxx = fault message (w/o the F.)
• Refer to section 5.3
The “hhhh” screen is displayed after hours exceed 999.
For example: 3 external faults occur over a period of time
with no other errors occurring. Then P552 will indicate 3,
P550 will indicate the error EF and P551 will indicate the
time of the first fault occurrence.
44Lenze SMVector 13465100 EDBSV01 EN v18
Page 47
Commissioning
Current Limit Diagnostic
* Input 13D available on 15-60HP (11-45kW) models only
LED
Additional I/O Module only
Code
No.Name
Sequencer: Currently
p560
Active Segment
Sequencer: Time
p561
since Start of Active
Segment
Sequencer: Time
p562
Remaining in Active
Segment
Sequencer: Number
p563
of cycles since start
Sequencer: Number
p564
of cycles remaining
Display Range (READ ONLY)IMPORTANT
0 17
0.0 {P708} 6553.5
0 {P708} 65535
0.0 {P708} 6553.5
0 {P708} 65535
0 65535
0 65535
NOTE: Parameters P560-P564 are visible only when P700 > 0 (i.e. the sequencer is enabled)
4.5.7.1 Terminal & Protection Status Display
Parameter P530 allows monitoring of the control terminal
points and common drive conditions:
An illuminated LED segment indicates:
• the protective circuit is active (LED 1)
• the Logic Assertion Switch is set to High (+)
• input terminal is asserted (LED 2)
• output terminal is energized (LED 4)
• the Charge Relay is not a terminal, this segment will
be illuminated when the Charge Relay is energized
(LED 4).
Parameter P531 allows monitoring of the keypad
pushbuttons:
An illuminated LED segment indicates when the button is
depressed.
LED 1 and LED 2 are used to indicate pushbutton presses on
a remote keypad that is attached to the drive. LED 3 and LED
4 indicate button presses on the local drive keypad.
1 Controller Inhibit
2 Quick Stop
3 Trip Fault, F.nF1
Read-Only: 0 - 9999Valid network messages received
NOTE: When the number of messages exceeds 9999, the counter resets and resumes
counting from 0.
communications.
If the onboard communications are disabled,
the user will not have access to any of the other
P6xx parameters.
IMPORTANT
46 Lenze SMVector 13465100 EDBSV01 EN v18
Page 49
Commissioning
4.5.9 Sequencer Parameters
The P700 Sequencer parameters are listed herein. Refer to section 4.5.7 for P56x Sequencer Diagnostic Parameters.
The sequencer function consists of 16 step segments, each individual step segment can have its own ramp time, time
spent in individual segment and output frequency entered. The sequencer has 3 different modes to control how the
drive moves through each individual step segment: Timer Transition, Step Sequence or Timer and Step Sequence.
P700= 1 (Timer Transition)
Starting at the segment number entered in the “Start Segment” parameter, the drive will automatically move through
each of the segments. The time spent in each segment is determined by the values set in the individual “Time in
Current Step” parameters.
P700= 2 (Step Sequence)
Starting at the segment number entered in the “Start Segment” parameter the sequencer will only move to the next
segment when a rising edge is applied to the highest priority digital input which is programmed to “Step Sequence”
selection “24”.
P700= 3 (Timer Transition or Step Sequence)
Starting at the segment number entered in the “Start Segment” parameter, the drive will automatically move through
each of the segments. The time spent in each segment is determined by the values set in the individual “Time in
Current Step” parameters, however if a rising edge is applied to the highest priority digital input which is programmed
to “Step Sequence” selection “24” it will force the sequencer to step into the next segment.
NOTE: A value of ”0” in the “Time in current step” parameter (ex: P712), will result in the segment being skipped.
CodePossible Settings
No.NameDefault Selection
Sequencer Mode00 DisabledIf P700 = 0 and no reference (P121, P101)
p700
P701
P702
P703
P704
P706
P707
(2)
Sequencer: TB13A
Trigger Segment
Sequencer: TB13B
Trigger Segment
Sequencer: TB13C
Trigger Segment
Sequencer: TB13D
Trigger Segment
Sequencer: Action
after Stop/Start
transition or Fault
Restart
Sequencer: Number
of cycles
1 Enabled: transition on timer only
2 Enabled: transition on rising edge (P121,
122, 123 = 25 step sequence)
3 Enabled: transition on timer or rising
edge
11 - 16
TB13A = lowest priority
11 - 16
TB13B: higher priority than TB13A
11 - 16
TB13C: higher priority thanTB13B, A
11 - 16
TB13D: higher priority than TB13C, B, A
00 Restart at beginning of sequencePointed by TB13x
1 Restart at beginning of current seg
2 Start at beginning of prior segment
3 Start at beginning of next segment
11 655351 = single scan; 65535 = continuous loop
points to any of the sequence segments,
then P701-P799 will not be displayed on the
local keypad.
Asserting TB13A with selection #24 (Start
Sequence), starts the sequence operation from
the segment specified in this parameter.
Asserting TB13B with selection #24 (Start
Sequence), starts the sequence operation from
the segment specified in this parameter.
Asserting TB13C with selection #24 (Start
Sequence), starts the sequence operation from
the segment specified in this parameter.
Asserting TB13D with selection #24 (Start
Sequence), starts the sequence operation from
the segment specified in this parameter.
IMPORTANT
(2) Parameter applicable to SMV models 15HP (11kW) and higher.
Lenze SMVector 13465100 EDBSV01 EN v18 47
Page 50
Commissioning
CodePossible Settings
No.NameDefault Selection
P708
Sequencer: Time
units/scaling
00 0.1 {sec} 6553.5Setup units/scaling for all sequencer time
1 1 {sec} 65535
2 1 {min} 65535
NOTE:
P708 rescales the following sequencer related parameters:
- Segment Times in current step: P712, P717, P722, P727, P732, P737, P742, P747,
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
0.00 0.00 {VDC} 10.00TB30 configuration parameter must be set to
0 0 0 0 1 1 1 1
0 0 0 0 1 1 1 1
0 0 0 0 1 1 1 1
IMPORTANT
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
accept this value: P150 = 10
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
accept this value: P150 = 10
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
0.00 0.00 {VDC} 10.00TB30 configuration parameter must be set to
0 0 0 0 1 1 1 1
0 0 0 0 1 1 1 1
0 0 0 0 1 1 1 1
IMPORTANT
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
accept this value: P150 = 10
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
accept this value: P150 = 10
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
0.00 0.00 {VDC} 10.00TB30 configuration parameter must be set to
0 0 0 0 1 1 1 1
0 0 0 0 1 1 1 1
0 0 0 0 1 1 1 1
IMPORTANT
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
accept this value: P150 = 10
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must
be set to accept data from the sequencer:
P140, P142, P441 = 27
accept this value: P150 = 10
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
0.00 0.00 {VDC} 10.00TB30 configuration parameter must be set to
0 0 0 0 1 1 1 1
0 0 0 0 1 1 1 1
0 0 0 0 1 1 1 1
IMPORTANT
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
accept this value: P150 = 10
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
accept this value: P150 = 10
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
0 0 0 0 1 1 1 1
0 0 0 0 1 1 1 1
0 0 0 0 1 1 1 1
IMPORTANT
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
accept this value: P150 = 10
direction
Scaling/units depend on P708
Skip segment if time = 0
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
accept this value: P150 = 10
direction
Scaling/units depend on P708
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
Lenze SMVector 13465100 EDBSV01 EN v18 53
Page 56
Commissioning
CodePossible Settings
No.NameDefault Selection
P794
P795
End Segment: TB30
Analog Output
Value
End Segment:
Drive Action
0.00 0.00 {VDC} 10.00TB30 configuration parameter must be set to
00 Keep RunningRecovery: Toggling the START SEQUENCE will
1 Stop (based on P111)
2 Coast to Stop
3 Quick Stop (per P127)
4 Coast with DC Brake
5 Ramp with DC Brake
WARNING!
If P795 = 0 then toggling the start sequence input will also restart the sequencer cycle but
in the interim where TB13X is open the drive will ramp to the standard or specified alternate
speed source depending on the drive configuration.
WARNING
If the input defined to “Start Sequence” is opened during a sequence, the drive will exit sequencer mode
and will run at the specified standard or alternate speed source (dependent on drive configuration).
IMPORTANT
accept this value: P150 = 10
start the cycle from ‘end segment Stop’ or ‘end
segment DC Brake’.
54Lenze SMVector 13465100 EDBSV01 EN v18
Page 57
4.5.9.1 Sequencer Flow Diagram Left
Sequencer Flow Diagram
Digital Input priority:
TB-13A -Lowest
TB-13B
TB-13C
Drive Stop/Start Control
Start from
Local Keypad
Start from
Terminal Strip
TB-13D - Highest
(2)
P100
0
1
2
Start from
Remote Keypad
(1)
Start from Network
(SMV communications
module)
(1)
Refer to relevant communications module user guide for starting from a
communications network, RS485 etc..
(2)
Refer to P100 description in the SMV Operating instructions for further
combinations of start sources.
(3)
TB-13D available on SMV models rated 15HP (11kW) or greater.
3
If none of the digital inputs (TB-13A,B,C or D) are asserted
but a start signal is given from the Start/Stop source (P100)
then the drive will run at the output frequency value governed by
the frequency reference source (P101).
> Selections shown as default values
P700
Notes
(3)
Sequencer
mode
disabled
0
1
2
3
WARNING
Commissioning
“Start Segment” number selection
TB-13A
P12124 P122
3
2
TB-13B
P123
24
TB-13C
24
P124
TB-13D
24
Start
Segment
P701
Start
Segment
P702
Start
Segment
P703
Start
Segment
P704
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
WARNING
If the input defined to “Start Sequence” is opened during a sequence, the drive will exit sequencer
mode and will run at the specified standard or alternate speed source (dependent on drive
configuration).
Lenze SMVector 13465100 EDBSV01 EN v18 55
Page 58
Commissioning
4.5.9.2 Sequencer Flow Diagram Right
Action after Stop/Start (P100) transition/digital input (if setup for
sequencer mode) transition or restart after trip.
P706
Action
Restart at beginning of sequence (pointed by TB13x)
0
Restart at beginning of current segment
1
2
Start at beginning of prior segment
3
Start at beginning of next segment
1
2
3
P
P712
P710
7
P
1
1
P720
7
1
6
P715
21
P7
P722
P717
SUSPEND SEQUENCE
Asserting input will suspend
sequencer in the currently active
segment, and when un-asserted
sequencer will continue to complete
the time remaining in the segment
TB-13x
P121/2/3/4
26
Suspend Sequencer
5
P7
P732
P730
1
3
6
P
7
3
6
P735
P737
7
P
P742
7
4
P740
1
8
P
7
4
6
P747
P745
9
P7
5
P752
P750
1
10
P
7
5
6
P755
P757
4
P7
2
6
P725
P727
Number of repeat Cycles P707
Ramp with DC Brake (See P174/P175)
Coast with DC Brake (See P174/P175)
Quick Stop (based on P128)
Keep running (based on P790)
(4)
The end segment is entered once the highest number segment with a non-zero value in the
“time in current segment” (P712/P711 etc..) parameter has completed and the number of
repeat cycles P707 has completed.
> A value of “0” in the segment time (P712 etc.) will result in the segment being skipped.
> Segment time and Accel/Decel (P712/P711 etc.) scaling is seconds as default.
> The sequencer will start from the segment pointed to by the digital input with the highest priority.
Notes
12
11
P
P760
7
6
1
6
6
7
P765
P
P767
P762
Coast to Stop
1
Stop (based on P111)
14
2
3
5
4
3
2
1
0
3
2
0
2
0
P
7
7
6
P775
P777
Segment
15
7
P
P782
No
(4)
End
13
P770
1
77
P
P772
3
> Selections shown as default values.
16
P780
P
1
8
Number of
cycles set
in P707
completed
Yes
P791
P792
P795
7
8
6
P787
P785
?
P790
56 Lenze SMVector 13465100 EDBSV01 EN v18
Page 59
4.5.9.3 Sequencer Status
Commissioning
Internal 0-10V reference
P150 = 10
Segment 1 active
Segment 2 active
Segment 3 active
Segment 4 active
Segment 5 active
Segment 6 active
Segment 7 active
Segment 8 active
Segment 9 active
Segment 10 active
Segment 11 active
Segment 12 active
Segment 13 active
Segment 14 active
Segment 15 active
Segment 16 active
End Segment active
End
Segment Delay
P792
Output Voltage
P714
Output Voltage
P719
Output Voltage
P724
Output Voltage
P729
Output Voltage
P734
Output Voltage
P739
Output Voltage
P744
Output Voltage
P749
Output Voltage
P754
Output Voltage
P759
Output Voltage
P764
Output Voltage
P769
Output Voltage
P774
Output Voltage
P779
Output Voltage
P784
Output Voltage
P789
Output Voltage
P794
TB30
NOTE
On the “End Segment”, the output voltage is not present until after the end segment delay P792
has expired. On the other segments the output voltage is present on entry to the segment. The
same is true for the digital outputs.
(1) The drive can only be restarted if the error message has been reset.
Drive ID warningThe Drive ID (P502) stored on the EPM
bf
Motor Auto-calibration activeRefer to P300, P399Motor Auto-calibration is being performed
CAL
An EPM that contains valid data from
cE
a previous software version has been
installed
Current Limit (P171) reachedMotor overload• Increase P171
CL
Decel OverrideThe drive has stopped decelerating
deC
ErrorInvalid data was entered, or an invalid
Err
Fast Current LimitOverloadVerify drive/motor are proper size for
FCL
Flying Restart Attempt after FaultP110 = 5,6
fst
OEM Settings Operation warningAn attempt was made to change
GE
OEM Defaults data warningAn attempt was made to use (or reset to)
GF
Fault LockoutThe drive attempted 5 restarts after a
LC
PID Deceleration StatusPID setpoint has finished its ramp but
PdeC
PID Mode ActiveDrive has been put into PID Mode.Refer to P200
PID
Sleep Mode is activeRefer to P240...P242
SLP
Start PendingThe drive has tripped into a fault and
SP
PID Mode disabled.Drive has been taken out of PID Mode.
spd
Output frequency = 0 Hz
stoP
(outputs U, V, W inhibited)
• activation of digital input
(P121...P124 = 18)
• automatically (P110 = 2, 4...6)
• automatically (P111 = 1, 3)
does not match the drive model.
An attempt was made to change
parameter settings
to avoid tripping into HF fault, due to
excessive motor regen (2 sec max).
command was attempted
parameter settings while the drive is
operating in OEM Settings mode.
the OEM default settings (P199 = 1 or 2)
using an EPM without valid OEM data.
fault but all attempts were unsuccessful
(P110 = 3...6)
the drive is still decelerating to a stop.
will automatically restart (P110 = 3...6)
Refer to P200.
Stop has been commanded from the
keypad, terminal strip, or network
Deactivate DC-injection brake
• deactivate digital input
• automatically after P175 time has
expired
• Verify motor data (P302…P306) and
perform Auto Calibration.
• Set drive mode (P300) to 0 or 1
• Reset the drive (P199 to 3 or 4) and
reprogram.
Parameter settings can only be changed after
the EPM data is converted to the current
version (P199 = 5)
• Verify drive/motor are proper size for
application
If drive trips into HF fault:
• Increase P105, P126
• Install Dynamic Braking option
application
In OEM Settings mode (P199 = 1), making
changes to parameters is not permitted.
Install an EPM containing valid OEM Defaults
data
• Drive requires manual reset
• Check Fault History (P500) and correct
fault condition
To disable Auto-Restart, set P110 = 0...2
Apply Start command (Start Control source
depends on P100)
(1) The drive can only be restarted if the error message has been reset.
58Lenze SMVector 13465100 EDBSV01 EN v18
Page 61
Troubleshooting and Diagnostics
5.2 Drive Configuration Messages
When the Mode button is pressed and held, the drive’s display will provide a 4-digit code that indicates how the
drive is configured. If the drive is in a Stop state when this is done, the display will also indicate which control source
commanded the drive to Stop (the two displays will alternate every second).
Configuration Display
Format = x.y.zz
Format = x.StPL.stp = Stop command came from Local Keypad
5.3 Fault Messages
The messages below show how they will appear on the display when the drive trips. When looking at the Fault History
(P500), the F_ will not appear in the fault message.
High Temperature faultDrive is too hot inside• Reduce drive load
f.AF
Assertion Level fault• Assertion Level switch is changed
f.AL
Personality faultDrive Hardware
f.bf
Control faultAn EPM has been installed that is either
f.CF
Incompatible EPM faultAn EPM has been installed that contains
f.cF
Forced Translation faultAn EPM from an old drive put in new drive
f.cFT
x = Control Source:
L = Local Keypad
t = Terminal Strip
r = Remote Keypad
n = Network
y = Mode:
S = Speed mode
P = PID mode
t = Torque mode
C = Sequencer mode
zz = Reference:
CP = Keypad p q
EU = 0-10 VDC (TB-5)
E1 = 4-20 mA (TB-25)
JG = Jog
nt = Network
OP = MOP
P1...P7 = Preset 1...7
t.stp = Stop command came from Terminal Strip
r.stp = Stop command came from Remote Keypad
n.stp = Stop command came from Network
FaultCauseRemedy
• Improve cooling
during operation
• P120 is changed during operation
• P100 or P121...P124 are set to a value
other than 0 and P120 does not match
the Assertion Level Switch.
blank or corrupted
data from an incompatible parameter
version
causes drive to trip F_cFT fault.
• Make sure the Assertion Level switch and
P120 are both set for the type of input
devices being used, prior to setting P100 or
P121...P124.
Refer to 3.2.3 and P120.
• Cycle Power
• Power down and install EPM with valid data
• Reset the drive back to defaults (P199 = 3, 4)
and then re-program
• If problem persists, contact factory technical
support
Press [M] (mode button) twice to reset
(1)
Lenze SMVector 13465100 EDBSV01 EN v18 59
Page 62
Troubleshooting and Diagnostics
FaultCauseRemedy
Dynamic Braking faultDynamic braking resistors are overheating • Increase active decel time
f.dbF
External fault• P121…P124 = 21 and that digital input
f.EF
EPM faultEPM missing or defectivePower down and replace EPM
f.F1
Internal faultsContact factory technical support
f.F2
…
has been opened.
• P121…P124 = 22 and that digital input
has been closed.
(P105, P126, P127).
• Check mains voltage and P107
• Correct the external fault condition
• Make sure digital input is set properly for NC
or NO circuit
f.F12
Control Configuration Fault The drive is setup for REMOTE KEYPAD
f.Fnr
TB25 (4-20 mA signal)
f.FoL
Threshold fault
OEM Defaults data faultDrive is powered up with P199 =1 and
f.GF
High DC Bus Voltage fault Mains voltage is too highCheck mains voltage and P107
Low DC Bus Voltage fault Mains voltage too lowCheck mains voltage
f.LF
No Motor ID faultAn attempt was made to start the drive
f.n1d
Module communication
f.ntF
fault
Network FaultsRefer to the module documentation. for
f.nF1
…
f.nF9
control (P100=2 or 5) but is not setup to
communicate with a remote keypad
The drive is setup for NETWORK ONLY
control (P100=3) but is not setup for
network communications
4-20 mA signal (at TB-25) drops below the
value set in P164.
OEM settings in the EPM are not valid.
Decel time is too short, or too much regen
from motor
More than one digital input set for the same
function
Only one digital input configured for MOP
function (Up, Down)
PID mode is entered with setpoint
reference and feedback source set to the
same analog signal
One of the digital inputs (P121…P124) is
set to 10 and another is set to 11…14.
One of the digital inputs (P121…P124)
is set to 11 or 12 and another is set to
13 or 14.
PID enabled in Vector Torque mode (P200
= 1 or 2 and P300 = 5)
in Vector or Enhanced V/Hz mode prior to
performing the Motor Auto-calibration
Communication failure between drive and
Network Module.
Causes and Remedies.
Set P400 = 1, or P600 = 1
Set P400 or P600 to a valid network
communications protocol selection
• Check signal/signal wire
• Refer to parameters P163 and P164.
Install an EPM containing valid OEM Defaults
data or change P199 to 0.
Increase active decel time (P105, P126, P127)
or install Dynamic Braking option
Each setting can only be used once (except
settings 0 and 3)
One input must be set to MOP Up, another must
be set to MOP Down
Change PID setpoint reference (P121…P124) or
feedback source (P201).
Reconfigure digital inputs
PID cannot be used in Vector Torque mode
Refer to parameters P300…P399 for Drive Mode
setup and calibration.
Check module connections
(1)
60 Lenze SMVector 13465100 EDBSV01 EN v18
Page 63
Troubleshooting and Diagnostics
FaultCauseRemedy
Output fault:
f.OF
Transistor fault
Output fault: Ground fault Grounded motor phaseCheck motor and motor cable
f.OF1
Motor Overload faultExcessive motor load for too long• Verify proper setting of P108
f.PF
Flying Restart faultController was unable to synchronize with
f.rF
Single-Phase faultA mains phase has been lostCheck mains voltage
f.SF
Start faultStart command was present when power
f.UF
TB5 (0-10V signal)
f.FAU
Threshold fault
Output short circuitCheck motor/motor cable
Acceleration time too shortIncrease P104, P125
Severe motor overload, due to:
• Mechanical problem
• Drive/motor too small for application
Boost values too highDecrease P168, P169
Excessive capacitive charging current of
the motor cable
Failed output transistorContact factory technical support
Excessive capacitive charging current of
the motor cable
the motor during restart attempt; (P110
= 5 or 6)
was applied (P110 = 0 or 2).
0-10V signal (at TB5) drops below the value
set in P158.
• Check machine / system
• Verify drive/motor are proper size for
application
• Use shorter motor cables with lower charging
current
• Use low capacitance motor cables
• Install reactor between motor and drive.
Use shorter motor cables with lower charging
current
• Verify drive and motor are proper size for
application
Check motor / load
• Must wait at least 2 seconds after power-up
to apply Start command
• Consider alternate starting method (P110).
• Check signal/signal wire
• Refer to parameters P157 and P158
(1) The drive can only be restarted if the error message has been reset.
(1)
Lenze SMVector 13465100 EDBSV01 EN v18 61
Page 64
Appendix
Appendix A
A.1 Permissable Cable Lengths
The table herein lists the permissable cable lengths for use with an SMV inverter with an internal EMC filter.
NOTE
This table is intended as a reference guideline only; application results may vary. The values in this
table are based on testing with commonly available low-capacitance shielded cable and commonly
available AC induction motors. Testing is conducted at worst case speeds and loads.
Maximum Permissible Cable Lengths (Meters) for SMV Model with Internal EMC Filters
MainsModel4 kHz Carrier
ESV251GG2SFG3812351033530N/A
ESV371GG2SFG3812351033530N/A
ESV751GG2SFG3812351033530N/A
(2/PE)
ESV112GG2SFG3812351033530N/A
240 V, 1-phase
ESV152GG2SFG3812351033530N/A
ESV222GG2SFG3812351033530N/A
ESV371GG4TFG30425220N/A10N/A
ESV751GG4TFG30425220N/A10N/A
ESV112GG4TFG30425220N/A10N/A
ESV152GG4TFG30425220N/A10N/A
ESV222GG4TFG30425220N/A10N/A
(3/PE)
ESV302GG4TFG30425220N/A10N/A
400/480 V,3-phase
ESV402GG4TFG545483422N/AN/A
ESV552GG4TFG545483422N/AN/A
ESV752GG4TFG545483422N/AN/A
(P166 = 0)
Class A Class B Class A Class B Class A Class B Class A Class B
6 kHz Carrier
(P166 = 1)
8 kHz Carrier
(P166 = 2)
10 kHz Carrier
(P166 = 3)
NOTE: The “GG” and “G” symbols are place holders in the Model part number that contain different information depending on
the specific configuration of the model. Refer to the SMV Type Number Designation table in section 2.2 for more information.
62Lenze SMVector 13465100 EDBSV01 EN v18
Page 65
Page 66
Lenze SMVector 13465100 EDBSV01 EN v18
Lenze Americas Corporation
630 Douglas Street
Uxbridge, MA 01569
USA
800 217-9100
508 278-7873
marketing@lenzeamericas.com
www.Lenze.com
Service
Lenze AC Tech Corporation
630 Douglas Street
Uxbridge, MA 01569
USA
508 278-9100
508 278-6620
repair@lenzeamericas.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.