All rights reserved. No part of this manual may be reproduced or transmitted in any form without written permission from Lenze AC Tech Corporation. The information and technical data in this manual are subject to change
without notice. Lenze AC Tech Corporation makes no warranty of any kind with respect to this material, including, but not limited to, the implied warranties of it’s merchantability and fitness for a given purpose. Lenze AC
Tech Corporation assumes no responsibility for any errors that may appear in this manual.
All information given in this documentation has been carefully selected and tested for compliance with the hardware and software described. Nevertheless, discrepancies cannot be ruled out. We do not accept any responsibility nor liability for damages that may occur. Any necessary corrections will be implemented in subsequent
editions.
This document printed in the United States
Contents
About theseInstructions ....................................................................................................... 2
1 Safety Information .................................................................................................... 3
2 Technical Data ..........................................................................................................7
2.1 Standards and Application Conditions ...................................................................................7
2.2 SMV Type Number Designation .............................................................................................8
This documentation applies to the SMV frequency inverter and contains important technical data
regarding the installation, operation, and commissioning of the inverter.
These instructions are only valid for SMV frequency inverters with software revision 4.23 or
higher for version 4.23 software, the drive nameplate illustrated below would show “42” in the “F”
location.
Please read these instructions in their entirety before commissioning the drive.
C A B D E F
Type:
ESV751N04TXB
Id-No: 00000000
INPUT:
3~ (3/PE)
400/480 V
2.9/2.5 A
50-60 HZ
TYPE-4X INDOOR USE ONLY
OUTPUT:
3~ (3/PE)
0 - 400/460 V
2.4/2.1 A
0.75 KW/1HP
0 - 500 HZ
For detailed information
refer to instruction
Manual: SV01
000000000000000000
ESV751N04TXB000XX## ##
ABCDEF
CertificationsTypeInput RatingsOutput RatingsHardware VersionSoftware Version
Scope of deliveryImportant
• 1 SMV Inverter
with EPM installed (see Section 4.4)
• 1 Operating Instructions manual
After receipt of the delivery, check immediately whether the items delivered match
the accompanying papers. Lenze AC Tech does not accept any liability for deficiencies
claimed subsequently.
Claim:
• visible transport damage immediately to the forwarder.
• visible deficiencies /incompleteness immediately to your Lenze AC Tech representative
Related Documents
The documentation listed herein contains information relevant to the operation of the SMVector frequency inverter.
To obtain the latest documentation, visit the Technical Library at http://w ww.lenzeamericas.com.
ALSV01SMVector Additional I/O Module Installation and Operation Manual
DBV01SMVector Dynamic Braking
PTV01SMVector Potentiometer Install Instructions
RKV01SMVector ESVZXK1 Remote Keypad
RKVU01SMVector ESVZXH0 Remote Keypad (for NEMA 1 15-60HP (11-45kW) Drives)
2Lenze SMVector 13465100 EDBSV01 EN v18
Safety Information
1 Safety Information
General
Some parts of Lenze AC Tech controllers can be electrically live and some surfaces can be hot. Nonauthorized removal of the required cover, inappropriate use, and incorrect installation or operation
creates the risk of severe injury to personnel and/or damage to equipment.
All operations concerning transport, installation, and commissioning as well as maintenance must be
carried out by qualified, skilled personnel who are familiar with the installation, assembly, commissioning,
and operation of variable frequency drives and the application for which it is being used.
Installation
Ensure proper handling and avoid excessive mechanical stress. Do not bend any components and do not
change any insulation distances during transport, handling, installation or maintenance. Do not touch
any electronic components or contacts. This drive contains electrostatically sensitive components, which
can easily be damaged by inappropriate handling. Static control precautions must be adhered to during
installation, testing, servicing and repairing of this drive and associated options. Component damage
may result if proper procedures are not followed.
To ensure proper operation, do not install the drive where it is subjected to adverse environmental
conditions such as combustible, oily, or hazardous vapors; corrosive chemicals; excessive dust, moisture
or vibration; direct sunlight or extreme temperatures.
This drive has been tested by Underwriters Laboratory (UL) and is UL Listed in compliance with the
UL508C Safety Standard. This drive must be installed and configured in accordance with both national
and international standards. Local codes and regulations take precedence over recommendations
provided in this and other Lenze AC Tech documentation.
The SMVector drive is considered a component for integration into a machine or process. It is neither a
machine nor a device ready for use in accordance with European directives (reference machinery directive
and electromagnetic compatibility directive). It is the responsibility of the end user to ensure that the
machine meets the applicable standards.
Electrical Connection
When working on live drive controllers, applicable national safety regulations must be observed. The electrical
installation must be carried out according to the appropriate regulations (e.g. cable cross-sections, fuses,
protective earth [PE] connection). While this document does make recommendations in regards to these
items, national and local codes must be adhered to.
The documentation contains information about installation in compliance with EMC (shielding, grounding, filters
and cables). These notes must also be observed for CE-marked controllers. The manufacturer of the system
or machine is responsible for compliance with the required limit values demanded by EMC legislation.
Application
The drive must not be used as a safety device for machines where there is a risk of personal injury or material damage.
Emergency Stops, over-speed protection, acceleration and deceleration limits, etc must be made by other
devices to ensure operation under all conditions.
The drive does feature many protection devices that work to protect the drive and the driven equipment
by generating a fault and shutting the drive and motor down. Mains power variances can also result in
shutdown of the drive. When the fault condition disappears or is cleared, the drive can be configured to
automatically restart, it is the responsibility of the user, OEM and/or integrator to ensure that the drive is
configured for safe operation.
Lenze SMVector 13465100 EDBSV01 EN v18 3
Safety Information
Explosion Proof Applications
Explosion proof motors that are not rated for inverter use lose their certification when used for
variable speed. Due to the many areas of liability that may be encountered when dealing with these
applications, the following statement of policy applies:
Lenze AC Tech Corporation inverter products are sold with no warranty of fitness for a particular
purpose or warranty of suitability for use with explosion proof motors. Lenze AC Tech Corporation
accepts no responsibility for any direct, incidental or consequential loss, cost or damage that may
arise through the use of AC inverter products in these applications. The purchaser expressly agrees to
assume all risk of any loss, cost or damage that may arise from such application.
Operation
Systems including controllers must be equipped with additional monitoring and protection devices
according to the corresponding standards (e.g. technical equipment, regulations for prevention of
accidents, etc.). The controller may be adapted to your application as described in this documentation.
DANGER!
• After the controller has been disconnected from the supply voltage, live components and power connection
must not be touched immediately, since capacitors could be charged. Please observe the corresponding
notes on the controller.
• Close all protective covers and doors prior to and during operation.
• Do not cycle input power to the controller more than once every two minutes.
• For SMVector models that are equipped with a Disconnect Switch (11th character in model number is L or M),
the Disconnect Switch is intended as a motor service disconnect and does not provide branch circuit protection
to the inverter or motor. When servicing the motor, it is necessary to wait 3 minutes after turning this switch
to the off position before working on motor power wiring as the inverter stores electrical power. To service the
inverter, it is necessary to remove mains ahead of the drive and wait 3 minutes.
Safety Notifications
All safety information given in these Operating Instructions includes a visual icon, a bold signal word
and a description.
Signal Word! (characterizes the severity of the danger)
NOTE (describes the danger and informs on how to proceed)
Signal WordMeaningConsequences if ignored
Icon
DANGER!
WARNING!
WARNING!
Hot Surface
STOP!
NOTE
Warns of hazardous electrical voltage.Death or severe injuries.
Warns of potential, very hazardous
situations.
Warns of hot surface and risk of burns.
Labels may be on or inside the
equipment to alert people that surfaces
may reach dangerous temperatures.
Warns of potential damage to material
and equipment.
Designates a general, useful note.None. If observed, then using the control-
Risk of severe injury to personnel and/or
damage to equipment.
Risk of severe injury to personnel.
Damage to the controller/drive or its
environment.
ler/drive system is made easier.
4Lenze SMVector 13465100 EDBSV01 EN v18
Safety Information
Harmonics Notification in accordance with EN 61000-3-2, EN 61000-3-12:
Operation in public supply networks (Limitation of harmonic currents i.a.w. EN 61000-3-2,
Electromagnetic Compatibility (EMC) Limits). Limits for harmonic current emissions (equipment input
current up to 16A/phase).
DirectiveTotal Power
EN 61000-3-2
EN 61000-3-12
(1) For compliance with EMC regulations, the permissable cable lengths may change.
(2) The additional measures described only ensure that the controller meets the requirements of the EN 61000-3-2.
The machine/system manufacturer is responsible for the machine’s compliance with the regulations.
connected to Mains
(public supply)
< 0.5kWwith mains choke
0.5 ... 1kWwith active filter
> 1kWcomplies without additional measures
16 ... 75ampAdditional measures are required for compliance with the standard
Additional Measures Required for Compliance
Safety Information in accordance with EN 61800-5-1:
DANGER! - Risk of Electric Shock
Capacitors retain charge for approximately 180 seconds after power is removed. Disconnect
incoming power and wait at least 3 minutes before touching the drive.
DANGER! - Risque de choc électrique
Les condensateurs restent sous charge pendant environ 180 secondes après une coupure
de courant. Couper l’alimentation et patienter pendant au moins 3 minutes avant de toucher
l’entraînement.
WARNING!
• This product can cause a d.c. current in the PE conductor. Where a residual currentoperated (RCD) or monitoring (RCM) device is used for protection in case of direct or
indirect contact, only an RCD or RCM Type B is allowed on the supply side of this product.
• Leakage Current may exceed 3.5mA AC. The minimum size of the PE conductor shall
comply with local safety regulations for high leakage current equipment.
• In a domestic environment, this product may cause radio interference in which case
supplementary mitigation measures may be required.
(2)
Lenze SMVector 13465100 EDBSV01 EN v18 5
Safety Information
Safety Information in accordance with UL:
Note for UL approved system with integrated controllers: UL warnings are notes which apply to UL systems.
The documentation contains special information about UL.
•Integral solid state protection does not provide branch circuit protection. Branch circuit protection
must be provided in accordance with the National Electrical Code and any additional local codes. The
Warnings!
use of fuses or circuit breakers is the only approved means for branch circuit protection.
•When protected by CC and T Class Fuses, suitable for use on a circuit capable of delivering not
more than 200,000 rms symmetrical amperes, at the maximum voltage rating marked on the drive.
•Additionally suitable when protected by a circuit breaker having an interrupting rating not less than
200,000 rms symmetrical amperes, at the maximum voltage rating marked on the drive. (Excludes
ESV113xx2T, ESV153xx2T, ESV113xx4T, ESV153xx4T, ESV183xx4T, ESV223xx4T, ESV303xx4T,
ESV113xx6T, ESV153xx6T, ESV183xx6T, ESV223xx6T, and ESV303xx6T).
•Use minimum 75°C copper wire only, except for control circuits.
•For control circuits, use wiring suitable for NEC Class 1 circuits only.
•Torque Requirements (in accordance with UL) are listed in section 3.2.1,
Power Connections and in 3.2.3, Control terminals
•Shall be installed in a pollution degree 2 macro-environment.
•NEMA 1 (IP31) models shall be installed in a pollution degree 2 macro-environment.
•All models are suitable for installation in a compartment handling Conditioned Air (i.e., plenum rated).
WARNING!
The opening of branch-circuit protective device may be an indication that a fault has been interrupted. To reduce the risk of fire or electric shock, current carrying parts and other components
of the controller should be examined and replaced if damaged.
AVERTISSEMENT!
Le déclenchement du dispositif de protection du circuit de dérivation peut être dû à une coupure
qui résulte d’un courant de défaut. Pour limiter le risque d’incendie ou de choc électrique, examiner
les pièces porteuses de courant et les autres éléments du contrôleur et les remplacer s’ils sont
endommagés. En cas de grillage de l’élément traverse par le courant dans un relais de surcharge,
le relais tout entier doit être remplacé.
NOTE
Control and communications terminals provide reinforced insulation (i.e. considered SELV or PELV,
providing protection in case of direct contact) when the drive is connected to a power system rated
up to 300VAC between phase to ground (PE) and the applied voltage on Terminals 16 and 17 is less
than 150VAC between phase to ground. Otherwise, control and communications terminals provide
basic insulation.
6Lenze SMVector 13465100 EDBSV01 EN v18
Technical Data
2 Technical Data
2.1 Standards and Application Conditions
Conformity
Approvals
Input voltage phase imbalance
Supported Power Systems
Humidity
Temperature range
Installation height
Vibration resistance
Earth leakage current
Max Permissable Cable Length
Enclosure
Protection measures against
Compliance with EN 61000-3-2
Requirements
Compliance with EN 61000-3-12
Requirements
Operation in public supply networks (Limitation of harmonic currents i.a.w. EN 61000-3-2, Electromagnetic Compatibility
(EMC) Limits). Limits for harmonic current emissions (equipment input current up to 16A/phase).
(1) The stated cable lengths are permissible at default carrier frequencies (refer to parameter P166).
(2) The additional measures described only ensure that the controller meets the requirements of the EN 61000-3-2.
(2)
(2)
The machine/system manufacturer is responsible for the machine’s compliance with the regulations.
CELow Voltage (2006/95/EC) & EMC (2004/108/EC) Directives
NEMA 1 and NEMA 4X model enclosures are plenum rated in accordance with UL
508C and are suitable for installation in a compartment handling conditioned air.
Earth fault, phase loss, over voltage, under voltage, motor stalling, over temperature
motor overload (125% of FLA), short circuit (SCCR=200kA at rated voltage)
< 0.5kWwith mains choke
0.5 ... 1kWwith active filter
> 1kWwithout additional measures
16 ... 75ampAdditional measures required for compliance with EN 61000-3-12
without restrictions.
− For corner grounded 400/500V systems, operation is
possible but reinforced insulation to control circuits is
compromised.
Lenze SMVector 13465100 EDBSV01 EN v18 7
Technical Data
2.2 SMV Type Number Designation
The table herein describes the Type numbering designation for the SMVector Inverter models.
S = Single Phase Input only
Y = Single or Three Phase Input
T = Three Phase Input only
Input Line Filter
F = Integral EMC Filter
L = Integral EMC Filter and Integrated Disconnect Switch (NEMA 4X/IP65 Models only)
M = Integrated Disconnect Switch (NEMA 4X/IP65 Models only)
X = No EMC Filter/ No Disconnect Switch
Enclosure:
B = NEMA 1/IP31; Indoor only
C = NEMA 4X/IP65; Indoor only; Convection cooled
D = NEMA 4X/IP65; Indoor only; Fan cooled
E = NEMA 4X/IP65; Indoor/Outdoor; Convection cooled
F = NEMA 4X/IP65; Indoor/Outdoor; Fan cooled
NOTE
Prior to installation make sure the enclosure is suitable for the end-use environment
Variables that influence enclosure suitability include (but are not limited to) temperature, airborne
contaminates, chemical concentration, mechanical stress and duration of exposure (sunlight,
wind, precipitation).
152N02TXB
8 Lenze SMVector 13465100 EDBSV01 EN v18
Technical Data
2.3 Ratings
120V / 240VAC Models
Mains = 120V Single Phase (1/N/PE) (90...132V), 240V Single Phase (2/PE) (170...264V); 48...62Hz
Type
ESV251--1S--0.330.256.83.41.720024
ESV371--1S--0.50.379.24.62.42003232
ESV751--1S--10.7516.68.34.22005241
ESV112--1S--1.51.12010.06.02007474
NOTES:
Output Current: The Output Current Maximum (%) is a percentage of the Output Current Continuous Amps (In) rating
and is adjustable in parameter P171.
240VAC Models
Type
ESV251--2S--0.330.253.41.720020
ESV371--2S--0.50.375.12.420030
ESV751--2S--10.758.84.220042
ESV112--2S--1.51.112.06.020063
ESV152--2S--21.513.37.020073
ESV222--2S--32.217.19.620097
PowerMains CurrentOutput CurrentHeat Loss (Watts)
HpkW
120VA240VACont (In)AMax I%N1/IP31 N4X/IP65
No filter
Mains = 240V Single Phase (2/PE) (170...264V); 48...62Hz
PowerMains CurrentOutput CurrentHeat Loss (Watts)
HpkW
240V
A
Cont (In)AMax I%N1/IP31 N4X/IP65
No filter
N4X/IP65
W/ filter
N4X/IP65
W/ filter
240V Single Phase (2/PE) (170...264V), 240V Three Phase (3/PE) (170...264V); 48...62Hz
Type
ESV371--2Y--0.50.375.12.92.42002726
ESV751--2Y--10.758.85.04.22004138
ESV112--2Y--1.51.112.06.96.02006459
ESV152--2Y--21.513.38.17.02007569
ESV222--2Y--32.217.110.89.620010393
PowerMains CurrentOutput CurrentHeat Loss (Watts)
HpkW
1~ (2/PE)A3~ (3/PE)
A
Cont (In)AMax I%N1/IP31 N4X/IP65
No filter
N4X/IP65
W/ filter
240V Three Phase (3/PE) (170...264V); 48...62Hz
Type
PowerMains CurrentOutput CurrentHeat Loss (Watts)
HpkW
240V
A
Cont (In)AMax I%N1/IP31 N4X/IP65
No filter
N4X/IP65
W/ filter
Lenze SMVector 13465100 EDBSV01 EN v18 9
Technical Data
ESV112--2T--1.51.16.9620064
ESV152--2T--21.58.1720075
ESV222--2T--32.210.89.6200103
ESV402--2T--54.018.616.5200154139
ESV552--2T--7.55.52623200225167
ESV752--2T--107.53329200274242
ESV113--2T--15114842180485468
ESV153--2T--20155954180614591
NOTES:
Output Current: The Output Current Maximum (%) is a percentage of the Output Current Continuous Amps (In) rating
and is adjustable in parameter P171.
Output Current: The Output Current Maximum (%) is a percentage of the Output Current Continuous Amps (In) rating
and is adjustable in parameter P171.
For 400...480 VAC models, the output current maximum (%) in the 400V column is used when P107 = 0
For 400...480 VAC models, the output current maximum (%) in the 480V column is used when P107 = 1
PowerMains CurrentOutput CurrentHeat Loss (Watts)
HpkW
400VA480VACont (In)AMax I%N1/IP31 N4X/IP65
400V 480V 400V 480V
No filter
N4X/IP65
W/ filter
10 Lenze SMVector 13465100 EDBSV01 EN v18
Technical Data
600VAC Models
600V Three Phase (3/PE) (425...660V); 48...62Hz
Type
ESV751--6T--10.7521.72003731
ESV152--6T--21.53.22.72005143
ESV222--6T--32.24.43.92006857
ESV402--6T--546.86.120010167
ESV552--6T--7.55.510.29200148116
ESV752--6T--107.512.411200172152
ESV113--6T--151119.717180380356
ESV153--6T--20152522180463431
ESV183--6T--2518.53127180560519
ESV223--6T--30223632180640592
ESV303--6T--40304741180930
ESV373--6T--5037.559521801163
ESV453--6T--604571621801395
NOTES:
Output Current: The Output Current Maximum (%) is a percentage of the Output Current Continuous Amps (In) rating
and is adjustable in parameter P171.
PowerMains CurrentOutput CurrentHeat Loss (Watts)
HpkWA
Cont (In)AMax I%N1/IP31 N4X/IP65
No filter
STOP!
• For installations above 1000m a.m.s.l., derate In by 5% per 1000m, do not
exceed 4000m a.m.s.l.
• Operation above 40°C, derate In by 2.5% per °C, do not exceed 55°C.
N4X/IP65
W/ filter
Output Current (In) derating for Carrier Frequency (P166) for NEMA 1 (IP31) Models:
- If P166=2 (8 kHz), derate In to 92% of drive rating
- If P166=3 (10 kHz), derate In to 84% of drive rating
Output Current (In) derating for Carrier Frequency (P166) for NEMA 4X (IP65) Models:
- If P166=1 (6 kHz), derate In to 92% of drive rating
- If P166=2 (8 kHz), derate In to 84% of drive rating
- If P166=3 (10 kHz), derate In to 76% of drive rating
Lenze SMVector 13465100 EDBSV01 EN v18 11
Installation
b2
Mounting Screws
Q
N
Q
S
P1
3 Installation
3.1 Dimensions and Mounting
WARNING!
Drives must not be installed where subjected to adverse environmental conditions such as: combustible, oily, or
hazardous vapors; corrosive chemicals; excessive dust, moisture or vibration; direct sunlight or extreme temperatures.
_ = Last digit of part number: C = N4X Indoor (convection cooled) ~ = Last digit of part number: D = N4X Indoor (fan cooled)
E = N4X In/Outdoor (convection cooled) F = N4X In/Outdoor (fan cooled)
Severe damage to the drive can result if it is operated after a long period of storage or inactivity
without reforming the DC bus capacitors.
If input power has not been applied to the drive for a period of time exceeding three years (due to
storage, etc), the electrolytic DC bus capacitors within the drive can change internally, resulting
in excessive leakage current. This can result in premature failure of the capacitors if the drive is
operated after such a long period of inactivity or storage.
In order to reform the capacitors and prepare the drive for operation after a long period of inactivity,
apply input power to the drive for 8 hours prior to actually operating the motor.
3.2.1 Power Connections
STOP!
If the kVA rating of the AC supply transformer is greater than 10 times the input kVA
rating of the drive(s), an isolation transformer or 2-3% input line reactor must be added
to the line side of the drive(s).
DANGER! Hazard of electrical shock!
Circuit potentials up to 600 VAC are possible. Capacitors retain charge after power is
removed. Disconnect power and wait at least three minutes before servicing the drive.
STOP!
• Verify mains voltage before connecting to drive.
• Do not connect mains power to the output terminals (U,V,W)! Severe damage to the drive will result.
• Do not cycle mains power more than once every two minutes. Damage to the drive may result.
If the cable connection between the drive and the motor has an in-line contactor or
circuit breaker then the drive must be stopped prior to opening/closing the contacts.
Failure to do so may result in 0vercurrent trips and/or damage to the inverter.
PE L1 L2 N
PE L1 L2 L3
PE L1 L2
PE L1 N
M
PES
3~
PES = Protective Earth Shielding
WARNING!
Leakage current may exceed 3.5 mA AC. The minimum size of the protective
earth (PE) conductor shall comply with local safety regulations for high leakage
current equipment.
STOP!
In the case of a Spinning Motor:
To bring free-wheeling loads such as fans to a rest before starting the drive, use the DC injection
braking function. Starting a drive into a freewheeling motor creates a direct short-circuit and may
result in damage to the drive.
Confirm motor suitability for use with DC injection braking.
Consult parameter P110 for starting / restarting into spinning motors.
Lenze SMVector 13465100 EDBSV01 EN v18 17
Installation
backplate using saddle clamp
3.2.1.5 Installation Recommendations for EMC Compliance
For compliance with EN 61800-3 or other EMC standards, motor cables, line cables and control or communications
cables must be shielded with each shield/screen clamped to the drive chassis. This clamp is typically located at the
conduit mounting plate.
The EMC requirements apply to the final installation in its entirety, not to the individual components used. Because
every installation is different, the recommended installation should follow these guidelines as a minimum. Additional
equipment (such as ferrite core absorbers on power conductors) or alternative practices may be required to meet
conformance in some installations.
Motor cable should be low
capacitance (core/core <75pF/m,
core/shield <150pF/m). Filtered
drives can meet the class A limits
of EN 55011 and EN 61800-3
Category 2 with this type of motor
cable up to 10 meters.
NOTE: Refer to Appendix A for
recommended cable lengths. Any
external line filter should have its
External
Control
Circuits
Control and signal cabling
should be separated from
power cables by
a minimum of 300mm
360° shield termination to
chassis connected to the drive
chassis by mounting hardware
or with the shortest possible wire
or braid.
3.2.1.6 NEMA 4X (IP65) Input Terminal Block
For NEMA 4X (IP65) models with integrated EMC filter and/or integrated line disconnect, the input terminal block is
located on the right-hand side of the SMV inverter in the NEMA 4 X (IP65) enclosure. The single and three phase models
are illustrated herein. Refer to paragraph 3.2.3 Control Terminals for pin out information.
Enclosure / Backplate
From
Motor
From
AC Supply
Screened motor cable:
core/core <75pF/M
core/shield <150pF/M
1256
13A13B 13C 14 30 16 17
25 411
L1
PE
UVW
Single Phase (2/PE) 120/240 VAC models
(ESVxxxN01SMC) with integrated line
disconnect
L2
N
1256
13A13B13C 14 30 16 17
25 411
L1
PE
W
V
U
Single Phase (2/PE) 240 VAC models
with Filter and/or integrated line
disconnect
L2
1256
UVW
Three Phase (3/PE) models
with Filter and/or integrated line
disconnect
WARNING
Power remains present for up to 3 minutes on power input terminals (L1, L2 and L3) and output
terminals (U, V and W) even when the disconnect switch is in the OFF position. Remove input power
ahead of the drive and wait 3 minutes before removing the terminal cover.
18Lenze SMVector 13465100 EDBSV01 EN v18
25 411
PE
13A13B13C 14 30 16 17
L1
L2
L3
Loading...
+ 46 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.