Lennox Hearth MPB3530CNM-B User Manual

INSTALLATION INSTRUCTIONS
MPB B-Vent Gas Fireplaces
P/N 506015-05 Rev. NC 07/2012
This manual is one of a set of two supporting this product. Refer to P/N 506017-04 for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 506223-45.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l’appareil. CONSOMMATEUR : Conservez cette notice pour consultation ultérieure.
WARNING
/
AVERTISSEMENT
MODELS
OTL Report No. 116-F-36d-5
Please read and understand these instructions
MILLIVOLT: ELECTRONIC:
MPB35CPM MPB40CNM MPB45CNM
Portland
US
before starting installation.
MPB33CNE MPB35CNE
/
AVISO
MPB40CNE MPB45CNE
s(/4',!337),,#!53%  "52.3
s$/./44/5#(',!33  5.4),#//,%$
s.%6%2!,,/7#(),$2%.  4/4/5#(',!33
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
$ONOTSTOREORUSEGASOLINEOROTHERFLAMMABLE
vapors and liquids in the vicinity of this or any other appliance.
7(!44/$/)&9/53-%,,'!3  s$ONOTTry to light any appliance.  s$ONOTTOUCHANYELECTRICALSWITCHDONOTUSEANY
phone in your building.
 s)MMEDIATELYCALLYOURGASSUPPLIERFROMA
neighbor’SPHONE&OLLOWTHEGASSUPPLIER’s instructions.
 s)FYOUCANNOTREACHYOURGASSUPPLIERCALLTHEFIRE
department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
s5.%352&!#%6)42»%#(!5$%  0%54#!53%2$%3"2Ä,52%3
s,!)33%22%&2/)$)2,!352&!#%  6)42»%!6!.4$g94/5#(%2
s.%0%2-%44%:*!-!)3Ã5.%.&!.4  $%4/5#(%2,!352&!#%6)42»%
AVERTISSEMENT : Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incindie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
15%&!)2%3)6/533%.4%:5.%/$%52$%'!:  s.EPASTENTERDALLUMERDAPPAREIL  s.ETOUCHEZÜAUCANINTERRUPTEUr. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
 s!PPELEZIMM£DIATEMENTVOTREFOURNISSEURDEGAZDEPUIS
un voisin. Suivez les instructions du fournisseur.
 s3IVOUSNEPOUVEZREJOINDRELEFOURNISSEURDEGAZ
appelez le service des incindies.
- ,’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
s%,6)$2)/#!,)%.4%  #!53!2¬15%-!$52!3
s534%$$%"%.5.#!  4/#!2%,6)$2)/#!,)%.4%
s,/3.)¶/3$%"%..5.#!  4/#!2%,6)$2)/
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
TABLE OF CONTENTS
Packaging .................................................... 2
Introduction ................................................. 2
General Information ..................................... 2
Requirements for the
Commonwealth of Massachusetts ............ 4
Cold Climate Insulation ................................ 4
Manufactured Housing ................................. 4
Location ........................................................5
Vent Termination Clearances ....................... 5
Appliance and Vent Clearances .................... 6
Pre-Installation Steps ................................... 7
Typical Installation Sequence ...................... 7
Detailed Installation Steps ............................ 7
Step 1. Framing ............................................ 7
Framing Specifi cations ................................ 8
Fireplace Specifi cations .............................. 9
Step 2. Routing Gas Line ............................. 9
Step 3. Installing Vent System ................... 10
Step 4. Field Wiring ................................... 11
Step 5. Wiring Optional
Forced Air Blower Kit .................... 12
Step 6. Connecting Gas Line ..................... 12
Step 7. Installing Optional Outside Air Kit ..13
Step 8. Verifying Appliance Operation ........... 14
Step 9. Installing Volcanic Stone, Glowing
Embers, and Logs ........................ 14
Step 10. Removing and
Installing the Glass Door ............. 19
Step 11. Burner Adjustments ..................... 19
Step 12. Testing Vent Operation ..................21
Step 13. Hood Installation .......................... 21
Step 14. Finishing Requirements ............... 21
Step 15. Attaching Safety-in-Operation
Warnings ............................ 22
Gas Conversion Kits ......................... 23
PACKAGING
The assembled vented gas fi replace is packaged with:
• (1 set) Logs (packaged in a carton inside the fi rebox).
• (1 bag) Volcanic Stone (included in the fi rebox or bottom compartment).
• (1 bag) Glowing Embers (in bottom compartment).
• Literature Kit (envelope in bottom com­partment containing Care and Operation Instructions, Installation Instructions, Safety-In-Operation Warning Labels, Warranty).
• (1) Hood (behind the top louver assembly).
INTRODUCTION
The Millivolt appliances have a millivolt gas control valve with piezo ignition system. If any optional accessories that will require electrical power are to be installed, the electrical power must be provided at the time of appliance installation.
The Electronic appliances are designed to operate on natural or propane gas. An electronic intermittent pilot ignition system provides safe, effi cient operation. External electrical power is required to operate these units. In the event of a power outage, four (4) "AA" batteries (in battery holder) provide backup power for appliance operation (excluding [optional] blower).
APPROVED VENT COMPONENTS
These vented gas fi replaces are designed for residential applications. They must be installed with approved Type-B, double wall vent pipe systems and a listed vent termination routed to the outside atmosphere. Use only the proper size listed below.
REQUIRED PIPE DIAMETER: MPB33 series: Requires 4 in. (102 mm) MPB35 series: Requires 5 in. (127 mm) MPB40 series: Requires 5 in. (127 mm) MPB45 series: Requires 6 in. (152 mm)
GENERAL INFORMATION
WARNING
Young children should be care­fully supervised when they are in the same room as the appli­ance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fi replace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la sur­face chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habi­tent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécu­rité; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
WARNING
B-Vent appliances are not designed to operate in negatively pressured environments (pres­sure within the home is less than pressures outside). Signifi cant negatively pressured environ­ments caused by weather, home design, or other devices may
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Les enfants et les adultes devraient être informés des dangers que posent les températures de surface élevées et se tenir à distance afi n d’éviter des brûlures ou que leurs vêtements ne s’enfl amment.
impact the operation of these appliances. Negative pres­sures may result in poor fl ame appearance, sooting, damage to property and/or severe personal injury. Do not operate these appliances in negatively pres-
2
sured environments.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WAR­RANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
WARNING
Improper installation, adjust­ment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
WARNING
Failure to comply with these in­stallation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appli­ance and/or its operating controls is dangerous.
WARNING
Clothing or other flammable material should not be placed on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de vêtements ni d’autres matières infl ammables sur l’appareil ni à proximité.
WARNING
Any safety screen or guard re­moved for servicing the appli­ance must be replaced prior to operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
WARNING
Improper installation or use of this appliance can cause serious injury or death from fi re, burns, explosion or carbon monoxide poisoning.
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifi cally approved with this appliance may result in property damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifi quement approuvées avec cet appareil sont utilisées.
Note: Installation and repair should be done by a qualifi ed service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
Remarque: L’installation et la réparation devrait être confi ées à un technicien qualifi é. L’appareil devrait faire l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres.
Do not use these appliances if any part has been under water. Immediately call a qualifi ed, professional service technician to inspect the appliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas utiliser cet appareil s’il a été plongé, même partiellement, dans l’eau. Appeler un technicien qualifi é pour inspecter l’appareil et remplacer toute partie du système de commande et toute commande qui a été plongée dans l’eau.
Only trim kit(s) supplied by the manufacturer shall be used in the installation of this appliance.
Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
These appliances comply with National Safety Standards and are tested and listed by OMNI-Test Laboratories, Inc. (Report No. 116-F-36d-5) to ANSI Z21.50b-2009 (in Canada, CSA 2.22b-2009), and CAN/CGA-
2.17-M91 (R2009) in both USA and Canada, as vented gas fi replaces.
Both millivolt and electronic versions of these appliances may be used in bedrooms only when the room is an "uncon ned space" as de ned by the National Fuel Gas Code. Use in bedrooms may not be allowed by your local building codes. You should obtain prior approval from the Authority having jurisdiction prior to installation.
MISC. CODES / STANDARDS
The Installation must conform to local codes or, in the absence of local codes, with the National
Fuel Gas Code, ANSI Z223.1 / NFPA 54—latest edition (In Canada, the current CAN/CGA-B149.1
installation code).The appliance, when installed, must be electrically grounded and wired in accordance with local codes or, in the absence of local codes, with the National Electrical Code,
ANSI/NFPA 70—latest edition, or the Canadian Electrical Code, CSA C22.1—latest edition.
Provide adequate clearances around air openings and adequate accessibility clearance for service and proper operation. Never obstruct the front or back openings of the appliance.
These appliances are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the performance of this system and may be dangerous.
These  replaces are designed as decorative appliances and are not intended for use as area heaters. They must not be equipped with wall thermostats or remote controls with thermostat functions.
OUTSIDE COMBUSTION AIR HOOK UP
These appliances are equipped with an integral combustion air door and actuator arm. Combustion air kits are optional. Install as shown in Step 7 on Page 13.
These appliances must not be connected to a chimney or fl ue serving a separate solid fuel burning appliance.
Both millivolt and electronic systems can be operated during a power outage, and feature manually operated hi-low fl ame control. The BTU Input for these appliances is shown in
Table 1.
Natural Gas Propane Gas
Model Input Rate
MPB33 13,500 to
MPB35 16,000 to
MPB40 24,000 to
MPB45 24,750 to
Table 1: BTU Input Ratings
(BTU/HR)
17,500
20,000
30,000
31,000
Input Rate
BTU/HR)
13,500 to
17,500
16,500 to
20,000
22,300 to
28,000
23,000 to
29,000
3
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
it
GAS PRESSURE—ALL MODELS
Tables 2 and 3 show the appliances' inlet and manifold gas pressure requirements:
Fuel # Minimum Maximum
Natural Gas
Propane
4.5 in. WC (1.12 kPa)
11.0 in. WC (2.74 kPa)
10.5 in. WC (2.61 kPa)
13.0 in. WC (3.23 kPa)
Table 2: Inlet Gas Supply Pressure
Fuel # Low High
Natural Gas
Propane
1.6 in. WC (0.40 kPa)
6.3 in. WC (1.57 kPa)
3.5 in. WC (0.87 kPa)
10.0 in. WC (2.49 kPa)
Table 3: Manifold Gas Supply Pressure
Test gauge connections are provided on the front of the millivolt and electronic gas control valve (identifi ed IN for the inlet and OUT for the manifold side). The control valves have a 3/8 in. (10 mm) NPT thread inlet and outlet side of the valve (refer to Figures 1 and 2).
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step down regulators to reduce the pressure to safe levels.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less
than 1/2 psi (3.5 kPa).
ORIFICE SIZES—SEA LEVEL TO HIGH ALTITUDE (ALL MODELS)
These appliances are tested and approved for installation at elevations of 0–4500 ft (0–1372 m) above sea level using the standard burner orifi ce sizes (marked with an "*" in Table 4). For elevations above 4500 ft, contact your gas supplier or qualifi ed service technician.
Deration—At higher elevations, the amount of BTU fuel value delivered must be reduced by either:
• Using gas that has been derated by the gas company.
• Changing the burner orifi ce to a smaller size as regulated by the local authorities having jurisdiction and by the (USA) National Fuel Gas Code NFPA 54—latest edition / ANSI Z223.1 or, in Canada, the CAN/CGA-B149.1 codes—latest edition.
4
Install the appliance according to the regulations of the local authorities having jurisdiction and, in the USA, the National Fuel Gas Code NFPA 54—latest edition / ANSI Z223.1 or, in Canada, the CAN/CGA-B149.1 latest edition.
Flame breadth, height and width will diminish 4% for every 1,000 feet of altitude. Gas Valve
Diagrams
. See Figure 1 for millivolt models
and Figure 2 For electronic models. In Canada - CAN/CGA-2.17-M91 (R2009)
(high altitude): THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE, IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER, PROVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/CGA-B149.1 OR CAN/CGA-B149.2 INSTALLATION CODES.
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
These fi replaces are approved for installation in the US state of Massachusetts if the following additional requirements are met:
• Install this appliance in accordance with Massachusetts Rules and Regulations 248 C.M.R.
Main Gas Control Knob
OFF/PILOT/ON
N
O
T
O
L
I
P
O
F
F
OUT
IN
Manifold Pressure Tap
Inlet Pressure Tap
Figure 1: SIT Millivolt Gas Valve
(from DFC Wire Harness)
Inlet (IN) Test Port
Manifold (OUT) Test Port
Orange Wire
(from DFC Wire
Harness)
Main Gas Inlet
3/8 in. NPT
Figure 2: SIT Electronic Gas Valve
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Pilot Adjustment
I
P
W
O
L
H
I
HI/LO Variable Flame Height Adjustment
Green Wire
Screw
T
O
L
H TPT
HT P
T
Model
Series
MPB33
MPB35
MPB40
MPB45
* Standard size installed at factory
• Part /Cat. Number
Nat.Gas
drill size (inches)
#47 (.0785") *
99K74 •
#44 (.086") *
60J80 •
#38 (.102") *
99K76 •
#36 (.104") *
24M10 •
Propane
drill size (inches)
(.048")*
99K78 •
#55 (.052") *
19L52 •
(.0625") *
21L01 •
#52 (.0635") *
37G00 •
Table 4: Burner Orifi ce Sizes
Elevation 0-4500 feet (0-1372 meters)
• Installation and repair must be done by a plumber or gas fi tter licensed in the Commonwealth of Massachusetts.
• The fl exible gas line connector used shall not exceed 36 in. (92 cm) in length.
• The individual manual shut-off must be a T-handle type valve.
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under fl oor on which appliance rests, if fl oor is above ground level. Gas line holes and other openings should be caulked or stuffed with unfaced fi berglass insulation.
If the fi replace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can be placed underneath to prevent conduction of cold transferring to the fi replace and into the room. It also helps to sheetrock inside surfaces and tape for maximum air tightness and caulk fi restops.
MANUFACTURED HOUSING
B-Vent Fireplaces are not approved for use in OEM or aftermarket manufactured housing built to HUD standards.
Hi/Lo Flame Control Knob
Yellow Ground Wire (from DFC Wire Harness)
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies (Figure 3).
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures (Figure 3).
The location should also be free of electrical, plumbing or other heating/air conditioning ducting.
Be aware that this is a heat producing appliance. Objects placed above the unit are exposed to elevated temperatures.
Do not insulate the space between the appliance and the area above it (see
Figure 9 on Page 8). The appliance must be mounted on a
fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile or other combustible material other than wood fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
Vertical Venting
Shown with Outside Air Kit installed (model FOAK-4 or
FOAK-4LD)
When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit.
Figure 3: Typical Installations
Offset
Venting
VENT TERMINATION CLEARANCES
Gas Vent Rule - Gas vent caps are not permitted within 8 feet (2.4 mm) of a vertical wall or similar obstruction. Gas vent caps that are located 8' or more from a portion of a building which extends at an angle greater than 45° upward from the horizontal may terminate in accordance with Figure 4, provided that in no case shall any discharge opening on the cap be less than 2' (610 mm) horizontally from the roof surface (National Fuel Gas Code ANSI Z223.1 (NFPA 54) Gas Vent Termination) (CAN/CGA B149.1).
MULTIPLE TERMINATIONS
These appliances may vent adjacent to and at the same level with any other gas appliances (including direct-vent appliances) provided that there is at least 2 ft. (0.6m) between the proximal edges of the vent caps. These appliances may be vented adjacent to a chimney vent servicing a solid fuel fi replace provided the B-vent cap is at least 2 ft. (0.6m) away from the nearest point of the chimney opening.
X
12
Roof Pitch is X/12
Minimum Height from Roof to Lowest Discharge Opening
1“ (25 mm) Minimum
Termination Heights For Vents
Above Flat Or Sloped Roofs
Ref. NFPA 54 / ANSI Z223.1
Roof Pitch Feet Meters
Flat to 6/12 1.0 0.3 6/12 to 7/12 1.25 0.38 7/12 to 8/12 1.5 0.46 8/12 to 9/12 2.0 0.61 9/12 to 10/12 2.5 0.76 10/12 to 11/12 3.25 0.99 11/12 to 12/12 4.0 1.22 12/12 to 14/12 5.0 1.52 14/12 to 16/12 6.0 1.83 16/12 to 18/12 7.0 2.13 18/12 to 20/12 7.5 2.29 20/12 to 21/12 8.0 2.44
Figure 4: Vertical Vent Termination Clearances
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
5
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
12 (305) MANTEL
10 (254) MANTEL
8 (203) MANTEL
6 (152) MANTEL
4 (102) MANTEL
4
(102)
12
(305)
10
(254)
2 (51) MANTEL
TOP OF APPLIANCE
6
(152)
NOTE - Hood shown as positioned in louvered front model. The hood position in the flush faced front model is lower than shown.
8
(203)
MANTEL CLEARANCES
Inches (mm)
APPLIANCE AND VENT CLEARANCES
MINIMUM CLEARANCES TO COMBUSTIBLES
The appliance is approved with zero clearance to combustible materials on all sides (as detailed in Table 5), with the following exception: When the unit is
installed with one side fl ush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit. In addition, when the unit is recessed,
the side walls surrounding the unit must not extend beyond the front edge of the unit (see Figure 3).
Back
Sides
Top Spacers
Floor
Bottom of Appliance To Ceiling
Vent
SERVICE CLEARANCES Feet (meters)
Front
1/2 (13) 1/2 (13)
0 (0) 0 (0)
64 (1626)
1 (25.4)
3 ft. (0.9 m)
Table5:Minimum Clearances
[inches (millimeters)]
HEARTH EXTENSION
A hearth extension is not required with this appliance. If a hearth extension is used, do not block the control compartment panel. Any hearth extension used is for appearance only and does not have to conform to any requirements for thermal protection.
WALL FINISHES / SURROUNDS / MANTELS
Note: Combustible wall fi nish materials and/ or surround materials must not be allowed to encroach the area defi ned by the appliance front face (black sheet metal). Never allow
combustible materials to be positioned in front of or overlapping the appliance face (see Figure 35 on Page 21).
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance face with these exceptions: they must not cover any portion of the removable glass panel, louvers, or control compartment.
Figure 5: Minimum Mantel Clearances
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (See Figure 5). Mantels constructed of non-combustible materials may be installed at any height above the appliance opening; however, do not allow anything to hang below the fi replace hood.
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifi ­cally approved with this appliance may result in property damage or personal injury.
0” Clearance to Combustible Side Wall
Ceiling
64 in.
(1626 mm)
Bottom of Fireplace
Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above the appliance.
NOTE: We recommend the use of high tem­perature paint (rated 175 °F, or higher) on the underside of the mantel.
AVERTISSEMENT
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifi quement approuvées avec cet appareil sont utilisées.
6
Figure 6: Clearance References
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
Anchor Ta b
PRE-INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre-wired.
Before installing the appliance, follow these steps:
1. Remove the shipping carton.
2. Remove the shipping pad, exposing
the front glass door.
3. Open the spring latch securing
the glass door (under the fi rebox fl oor). Remove the door by tilting it outward at the bottom and lifting it up. Set the door aside, taking care to protect it from inadvertent damage. See Removing the Glass Enclosure Panel on Page 19.
4. Remove the log set from the fi rebox.
Handle logs carefully to prevent breakage.
5. Remove the embers and
volcanic stone from the control compartment.
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation is outlined below; however, each installation is unique and may result in variations to the steps described. See the pages referenced in the following steps for detailed procedures.
Step 1. FRAMING (Page 7): Construct the appliance framing. Position the appliance within the framing and secure with nailing nailing fl anges and fl oor anchor tabs.
Bend out the appropriate nailing fl anges for the drywall/fi nish material to be used. Nailing fl anges are provided for fl ush framing, 1/2 in. and 5/8 in. framing depths (see Figure 10).
Step 2. ROUTING GAS LINE (Page 9): Route gas supply line to appliance location.
Step 3. INSTALLING VENT SYSTEM (Page 10): Install the vent system and exterior termination.
Step 4. FIELD WIRING (Page 11).
a. Millivolt Appliances—Install the operating
control switch (not factory provided). If installing the optional forced air circulating blower, bring in electrical service line.
b. Electronic Appliances—Field wire and install operating control switch.
Step 5. WIRING—OPTIONAL FORCED AIR BLOWER KIT (Page 12).
Step 6. CONNECTING GAS LINE (Page 12):
Make connection to gas supply.
Step 7. INSTALLING OPTIONAL OUTSIDE AIR KIT (Page 13)
Step 8. VERIFYING APPLIANCE OPERATION
(Page 14).
Step 9. INSTALLING VOLCANIC STONE, GLOWING EMBERS, AND LOGS (Page 14).
Step 10. REMOVING AND INSTALLING THE GLASS DOOR (Page 19).
Step 11. BURNER ADJUSTMENTS (Page 19):
Adjust burner primary air shutter to achieve proper fl ame appearance.
Step 12. TESTING VENT OPERATION
(Page 21)
Vent operation test and (safety limit) switch operation.
Step 13. HOOD INSTALLATION (Page 21). Step 14. FINISHING REQUIREMENTS (Page 21) Step 15. ATTACHING SAFETY-IN-
OPERATION WARNINGS (Page 21).
DETAILED INSTALLATION STEPS STEP 1. FRAMING
Frame the appliance as illustrated in Figure 9 on Page 8. All framing details must allow for a minimum clearance to combustible framing members as shown in the table on Page 8.
If the appliance is to be elevated above fl oor level, a solid continuous platform must be constructed below the appliance.
Note: The framed depth, 16 in. (406 mm) from a framed wall, must always be measured from a fi nished surface. If a wall covering such as drywall is to be attached to the rear wall, then the 16 in. (406 mm) must be measured from the drywall surface. It is important that this dimension be exact.
Headers may be in direct contact with the appliance top standoff spacers, but must
not be supported by them or notched to fi t around them. All construction above the appliance must be self-supporting. DO NOT use the appliance for structural support.
Secure the fi replace to the side framing members using the unit’s nailing fl anges — one top and bottom on each side of the fi replace front (See Figure 7). Use 8d nails or their equivalent.
FLOOR NAILING TABS
Fireplace may be anchored to fl oor. Bend down two anchor tabs (one on each side) located at the base of the fi replace and secure to the fl oor by nailing with 8d nails or equivalent (see Figure 8).
Side
Framing
Left Side Front Corner of Fireplace Shown
(Right Side Requirements the Same)
Note: The nailing flanges, combustible members and screw heads located in areas directly adjacent to the nailing flanges, are EXEMPT from the 1/2” clearance to combustible requirements for the firebox outer wrapper. in
direct contact with the nailing flanges and may be located closer than 1/2” from screw heads and the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions specified in the framing details of this manual.
Combustible framing may be
Unit Nailing Flange
(No clearance to
combustible
framing is required)
Figure 7: Unit Secured to Framing by Nailing Flange
Figure 8: Floor Anchor Tabs
Note: Some units only have one anchor tab
on each side.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
. o N l e d o M
A
t i n U
e z i S
A
g n i m a r F
e z i S
BCD E FGHJ K
. n i5 38 / 1 -5 34 / 1 -5 34 / 1 -9 18 / 5 - 9 17 52 / 1 -4 / 3 - 8 26 14 6 1 / 9 - 68 / 5 - 0 4
m m2 9 85 9 85 9 83 8 48 9 40 6 4 10 3 76 0 42 0 17 6 12 3 0 1
. n i8/
1 - 0 44 / 1 - 0 44 / 1 - 0 44 28 / 5 - 4 26 1 / 3 1 - 1 66 1 / 1 - 0 36 14 6 1 / 9 - 62 3 / 1 1 - 3 4
m m9 1 0 12 2 0 12 2 0 10 1 65 2 60 7 5 19 7 76 0 42 0 17 6 11 0 1 1
. n i8 / 1 - 0 44 / 1 - 5 44 / 1 - 0 44 28 / 5 - 9 28 / 3
- 6 66 1 / 3 - 3 36 14 6 1 / 9 - 66 1 / 5 1 - 6 4
m m6 4 1 19 4 1 12 2 0 10 1 62 5 76 8 6 13 4 86 0 42 0 17 6 12 9 1 1
MPB33
MPB35
MPB40
MPB45
in.
mm
845
842
33-1/4
845
33-1/4
546
21-1/2
286
11-1/4
1232
48-1/2
616
24-1/4
330
13
102
4
103
4-1/16
872
34-5/16
33-1/8
12-3/4
14-11/16
17-3/16
437
373
324
1146
45-1/8
24-7/8
29-7/8
34-7/8
886
759
632
30-11/16
7-1/16
7-1/16
7-1/16
179
179
179
Back Wall of Chase/Enclosure
*Optional FOAK
Outside
Air Kit
Including Finishing Materials
C
if any
B
Fireplace Framing
K
Corner Installation
Header
A
Back Wall of Chase/Enclosure
Including Finishing Materials
D
C
A E
if any
G
Rough
Framing Face
(Unfinished Shown)
J
A
Rough Framing Face
(Unfinished Shown)
Outside Chase
Back Wall of Chase/Enclosure Including Finishing Materials
C
F
HH
A
Inside Chase
if any
G
G
Rough
Framing Face
(Unfinished Shown)
8
All framing dimensions calculated for 1/2" dry wall at the appliance face. If sheathing the chase or finishing with other thickness materials, calculations will need to be made.
* Outside air kit - FOAK (without adaptor). See Figure 22 on Page 16.
Figure 9: Framing Specifi cations
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
ELECTRICAL INLET
(See Also
Right Side View )
5-1/2
OUTSIDE AIR
SHUTTER
GAS INLET
(See Also
Right Side View
ELECTRICAL
INLET
(Optional)
)
(140)
9-3/8 (238)
8-15/16
(227)
Left Side View
. o N l e d o MA BC DE F G
MPB33
MPB35
MPB40
MPB45
in. mm
. n i538 / 1 -8 / 1 - 2 39 12 / 1 - 9 25 38 / 1 -8 / - 6 1 / 7 - 25 8-3/4 m m29 86 1 83 8 49 4 72 9 82 3 66 1 37 2 1 222 . n i8/ 1 - 0 48 / 1 - 7 34 22 / 1 - 4 38 / 1 - 0 48 / 7 - 9 21 6 1 / 5 m m9 1 0 13 4 90 1 66 7 89 1 0 19 5 79 7 37 2 1 . n i8 / 1 - 0 48 / 1 - 7 34 22 / 1 - 9 38 / 1 - 5 48 / 7 - 4 36 1 / 7 - 7 16 8-3/4 m m6 4 1 13 4 90 1 63 0 0 16 4 1 16 8 83 4 42 5 1 222
Figure 10: Fireplace Specifi cations
FRAMING
STANDOFFS
(Top, Sides,
and Rear)
G
A
3
1-3/8
(76)
7-3/8 (187)
(35)
33-1/8
841 432
765 841
17 30-1/8
27-1/2
F
H
T op View
E
D
Front View
699
C
33-1/8
21-1/2
546
24-7/8
621
J
NOTE - Hood shown
3 (76)
GAS INLET (Either Side and bottom )
OPTIONAL ELECTRICAL
INLET KNOCKOU T
REQUIRING A FIELD
PROVIDED JUNCTION
B
BOX (Either Side)
10-3/4
12-7/16
1 - 45 8-3/4
Flue Outlet For B-V ent Connection
ELECTRICAL INLET
as positioned
in louvered
front model.
1 ³⁄ ₈ (35)
3 (76)
2-3/4 x 2 (70 x 51) COVER PLA TE with KNOCKOUT)
K
1/2 (13)
5-1/2 (140)
9-3/8
(238)
2
(53)
Right Side View
K
J
H
4
6-1/2
102 273
165
13
330
16
406
16
2
22
406
16
406
STEP 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line as shown in Figure 11. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations. The appliance, as set up at the factory, is best suited for use with a gas line routed from the left side. The gas line may however be alternately routed from the right side. All appliances are factory-equipped with a fl exible gas line connector and 1/2 inch shutoff valve. (See Step 6 on Page 12).
Pipe Coupling
(Recommended)
6-1/2"
(152 mm)
3"
(76 mm)
Figure 11: Route Gas Line
Also see Figure 12.
PROPER SIZING OF GAS LINE
Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code, ANSI Z223.1 (NFPA 54)—latest edition (USA) or CAN/CGA-B149.1—latest edition (Canada).
Never use galvanized or plastic pipe. Refer to Table 6 for proper sizing of the gas supply line, if black iron pipe is being used. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations. We recommend that a qualifi ed individual such as a plumber or gas fi tter be hired to correctly size and route the gas supply line to the appliance. Installing a gas supply line from the fuel supply to the appliance involves numerous considerations of materials, protection, sizing, locations, controls, pressure, sediment, and more. Certainly no one unfamiliar and unqualifi ed should attempt sizing or installing gas piping.
Notes:
• All appliances are factory-equipped with a fl exible gas line connector and 1/2 inch shutoff valve (see Figure 46 on Page 25).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Schedule 40 Pipe
Length (feet)
Natural
Gas
Propane
Gas
0–10 1/2 in. 3/8 in.
10–40 1/2 in. 1/2 in.
40–100 1/2 in. 1/2 in. 100–150 3/4 in. 1/2 in. 150–200 3/4 in. 1/2 in.
Table 6: Schedule 40 Black Iron Pipe— Inside Diameter
• See Massachusetts Requirements on Page 4 for additional requirements for
installations in the state of Massachusetts in the USA.
• The gas supply line SHOULD NOT be connected to the appliance until Step 6 on Page 12).
• A pipe joint compound rated for gas should be used on the threaded joints.
Ensure propane resistant compounds are used in propane applications. Be very
careful that the pipe compound does not get inside the pipe.
• It is recommended to install a sediment trap in the supply line as close as possible to the appliance.
• Check with local building offi cial for local code requirements.
9
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
IMPORTANT: If propane is used, be aware that if tank size is too small (i.e. under 100 lbs, if this is the only gas appliance in the dwelling. Ref. NPFA 58), there may be loss of pressure, resulting in insuffi cient fuel delivery (which can result in sooting, severe delayed ignition or other malfunctions). Any damage resulting from an improper installation, such as this, is not covered under the limited warranty.
STEP 3. INSTALLING VENT SYSTEM
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/ CGA-B149.1 in Canada.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d'installa tion locaux et aux exigences du foumisseunde gaz.
Type B-Vent - 4 in. (102 mm) for MPB33 Models, 5 in. (127 mm) for MPB35 / 40 Models or 6 in. (152 mm) for MPB45 Models
Securing Screws
Flue Outlet Collar
Figure 12: Initial B-Vent Installation
USE ONLY APPROVED B-VENT DIAMETER
MPB33, MPB35, MPB40 and MPB45 series fi replaces must be vertically vented using listed type-B, double-walled vent pipe with the proper diameter as listed below and a listed vent termination.
Required Pipe Diameter: MPB33 series: Requires 4 in. (102 mm)
MPB35 series: Requires 5 in. (127 mm) MPB40 series: Requires 5 in. (127 mm) MPB45 series: Requires 6 in. (152 mm)
CAUTION
This appliance cannot be vented horizontally.
Refer to the vent manufacturers installation instructions for variations of venting techniques. If common venting of several units is contem­plated, it should be discussed with an architect and the local Building Department.
Do not place insulation materials within 1 in. of the gas vent system.
Use only approved venting components. (see Approved Vent Components on Page 2.)
These fi replaces must be vented vertically to the outside.
Slip the fi rst section of B-Vent over the fi replace fl ue outlet and secure with sheet metal screws (# 8 or larger), then install the remainder of the B-Vent vertically to the outside. Minimum overall height of the vent system and appliance must be 10' (2.54 m) vertical with no offset, or 12' (3.7 m) when an offset up to 45 degrees from the vertical is used; or 15' (4.6 m) when an offset is greater than 45 degrees and up to 60 degrees (see Figure 13).
The offset may start at the fi replace fl ue collar. The maximum overall height of the vent system and appliance should not exceed 40 feet.
Install the B-vent system in accordance with the vent manufacturer's instructions.
Vertical
Installations
10 ft.
Minimum
Back View
Of Appliance
The maximum overall height of the vent system and appliance should not exceed 40 feet.
Figure 13: Vent System Installation
Installations
*12 ft. Min.
**15 ft. Min.
Back View
Of Appliance
*with an offset up to 45 degrees ** with an offset greater than 45
degrees and up to 60 degrees
Offset
10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
T
STEP 4. FIELD WIRING
CAUTION
The ground supply lead must be connected to the wire attached to the green ground screw located on the outlet box (see wiring diagrams). Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accor­dance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/ NFPA 70
latest edition (in
Canada, the current CSA C22.1 Canadian Electrical Code).
CAUTION: Label all wires prior to discon­nection when servicing controls. Wiring errors can cause improper and dangerous operation.
ATTENTION: Au moment de l’entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de cáblage peuvent entraîner un fonc­tionnement inadéquat et dangereux.
Verify proper operation after servicing.
S’assurer que l’appareil fonctionne adé­quatement une fois l'entretien terminé.
Refer to Section A for millivolt appliances and Section B for electronic appliances. The gas valve is set in place and pre-wired at the factory on both models.
JUNCTION BOX
120V AC
B
W
G
OPTIONAL
REMOTE RECEIVER
ON/OFF SWITCH
WALL SWITCH
WIRING COLOR CODE
B = BLACK BR = BROWN GY = GRAY PU = PURPLE R = RED
P/N 580491-01
HOT
NEUTRAL
GROUND
SAFETY LIMIT SWITCH
B-VENT MODELS ONLY
BL = BLUE G = GREEN O = ORANGE W = WHITE Y = YELLOW
SCHEMATIC REPRESENTATION ONLY
Figure 16: Wiring Diagram—Electronic Gas Valves
R
BATTERY HOLDER
AC/DC POWER ADAPTOR
Y G
O
B
B
CAUTION: ENSURE THAT WIRES ARE POSI­TIONED AWAY FROM HOT SURFACES AND SHARP EDGES.
If any of the original wire as supplied must be replaced, it must be replaced with Type AWM105 ° C – 18 GA. wire.
BK
H C T I W
S T
I M I L
BK
Thermopile
BK
AB
*OPTIONAL ON/OFF SWITCH,
WALL SWITCH, OR REMOTE
CONTROL RECEIVER
*TWIST WIRES “ A ” AND “ B ” TOGETHER TO OPERATE UNIT SOLELY BY MANIPULATING THE GAS VALVE CONTROL KNOB; OR CONNECT WIRES TO OPTIONAL ON/OFF SWITCH OR WALL
SWITCH OR REMOTE CONTROL RECEIVER TO OPERATE UNI
Schematic Representation Only
WT
T P
T
T
H
P
T H
Figure 14: SIT Milivolt Wiring Diagram
See Figure 10 on Page 10 for Optional Electrical Inlet Knockout Location.
* Field-Provided Junction Box and Duplex Receptacle
* Narrow (2-1/8 Inch Wide) J-Box Required
Figure 15: Optional J-Box/Outlet Box (Left Side Shown)
ELECTRONIC PILOT ASSEMBLY
IGNITER ROD
FLAME SENSOR
B
B
Y G
O
W BL
G
CPI SWITCH OFF (O) = INTERMITTENT PILOT MODE ON (-) = STANDING PILOT MODE
PILOT SENSOR CABLE
PROFLAME DFC BOARD
DFC WIRE HARNESS
PROFLAME VALVE
W
R
PILOT TUBE
SPARK WIRE CABLE
PILOT GROUND WIRE
R
BL
HOOD
Y
B
R
B
A. Millivolt Wiring (see Figure 14)
Millivolt units are not provided with any factory-installed controls; therefore, one of the optional control switches is required to operate the unit (ON/OFF Wall Switch, Unit-Mountable ON/OFF Switch*, Remote Control). See the fi replace Care and Operation Instructions for details.
[*If using a Unit-Mountable ON/OFF Rocker Switch with an optional Style View Door, mount the Rocker Switch on the door instead of the unit.]
1. If installing an ON/OFF wall switch or
receiver, mount it in a convenient location on a wall near the f replace.
2. Wire the control switch within the millivolt
control circuit using the 15 feet of 2 conductor wire supplied with the unit.
Note: The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the bottom compartment.
CAUTION
In millivolt systems, do not connect optional control switch to 120 v power supply.
B. Electronic Wiring (see Figure 16)
One of the following optional controls also may be used: ON/OFF Wall Switch, Remote Control (see fi replace Care and Operation Instructions for details.).
Note: Electronic models must be connected to the main power supply.
1. Route a 3-wire 120Vac 60Hz 1ph power
supply to the appliance junction box.
2. Remove the electrical inlet cover plate
from the side of the unit by removing the plate’s securing screws (see Figure 10 on
Page 9).
3. Remove the cover plate knockout; then
feed the power supply wire through the knockout opening and into the unit junction box.
4. See Figure 17. Connect the black power supply wire to the lower outlet’s red pigtail lead.
Connect the white power supply wire to
the outlet’s common terminal.
5. Connect the ground supply wire to the pigtail lead attached to the outlet’s green ground screw.
Note: Remote receiver should be located in the wall, or if installed in the control compartment, pulled all the way forward and completely to the left or right against the corner posts.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
11
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
6. If wall-mounted ON/OFF control is to be
used, mount it in a convenient location on a wall near the fi replace.
7. If an optional control is to be used, wire
it in the low voltage circuit as shown in
Figure 16.
Note: The supplied 15 feet of 2 conductor
wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the bottom compartment.
8. After the wiring is complete, replace the
cover plate.
WARNING
Electronic models of these appli­ances are equipped with a three­prong (grounding) plug utilized in connecting the electronic components to the junction box in the lower compartment. This grounding plug provides protec­tion against shock hazard and should be plugged directly into the properly grounded three­prong receptacle. DO NOT cut or remove the grounding prong from the plug.
STEP 5. WIRING OPTIONAL FORCED AIR BLOWER KIT
FBK-100, FBK-200, and FBK-250 Kits
(See Figure 17)
An electrical outlet box is provided for the installation of the FBK-100, FBK-200 and FBK-250 forced air blower kits. Electrical power must be provided to this box to operate these blowers. Install the blower kits according to the installation instructions provided with the kits.
Note: The tab connecting the two receptacles of the outlet box must be broken in the FBK-100 and FBK-200 blower kit applications (see Figure 17).
120V, 60HZ, 1PH
n
e
ti
e e
h
r
W
G
-
-
lar
dn
t
u
u
o
e
r
N
G
Black
White
Green
Plug blower into this receptacle
Blower
Ground
Figure 17: Junction Box Wiring
* Wall-mounted ON/ OFF Blower Switch or Variable Speed Control Switch.
120 VAC - Black
Junction Box
Tab Intact
Field Wired Factory Wired
Tab Broken
Red
Hot Side of Receptacle
Neutral Side of Receptacle
Green Ground Screw
STEP 6. CONNECTING GAS LINE
Make gas line connections. All codes require a shut-off valve mounted in the supply line. The orientation of the shut-off valve should face the front (see Figure 19). Figure 18 illustrates two methods for connecting the gas supply. The fl ex-line method is acceptable in the U.S.; however, Canadian requirements vary depending on locality. Installation must be in compliance with local codes.
A sediment trap is recommended in the gas piping within the home to prevent moisture and debris in the line from damaging the valve.
These appliances are equipped with a gas fl ex line for use (where permitted) in connecting the unit to the gas line. A gas fl ex line is provided to aid in attaching the direct vent appliance to the gas supply. The gas fl ex line can only be used where local codes permit. Refer to Figure 18 for fl ex line description. The fl ex line is rated for both natural and propane gas. A manual shut off valve is also provided with the fl ex line.
The gas control valve is located in the lower control compartment.
To access the valve, open the control compartment access panel. Actuate the spring loaded magnetic catches securing the panel. First, gently depress the upper right top corner of the panel until the magnet catch "pops" the door free. Then, gently pulling the panel forward, disengage the left magnet catch and allow the panel to swing down to open.
The control valves have a 3/8" (10 mm) NPT thread inlet and outlet side of the valve (refer to Figures X [Electronic] and Figure x [Millivolt] on Page X).
Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resistant compounds are used in propane applications). Optional: Seal around the gas line to prevent cold air leakage. Gas line holes and other openings can be caulked or stuffed with unfaced fi berglass insulation.
TEST ALL CONNECTIONS FOR GAS LEAKS (FACTORY AND FIELD)
WARNING
Never use an open fl ame to check for leaks.
Turn on gas supply and test for gas leaks, using a gas leak test solution (also referred to as bubble leak solution).
Note: Using a soapy water solution is an effective leak test solution but it is not recommended, because the soap residue that is left on the pipes/fi ttings can result in corrosion over time.
A. Light the appliance (refer to the
lighting instructions label in the control compartment or in the Care and Operation Instructions manual).
B. Brush all joints and connections with the
gas leak test solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob (off/pilot/on) to the “OFF” position (millivolt units), or turn the receiver, remote control or control switch to the “OFF” position (electronic units). Either tighten or refasten the leaking connection, then retest as described above.
C. When the gas lines are tested and
leak free, be sure to rinse off the leak testing solution.
12
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
Gas Stub
1/2" x 3/8" Flare
Shut-Off Valve
3/8" Flex Tubing
3/8" NPT x 3/8"
Flare Fitting
3/8" Nipple
3/8" Union
3/8" Close Nipple
3/8" Shut-Off Valve
1/2" x 3/8"
Reducer
Gas Valve
Optional Gas Flex Line Connector
Piezo
(Optional) Burner ON/OFF Switch
Main Gas Shut-Off Valve
Gas Valve
B-Vent Units Have
A Single Door Latch
Figure 18: Gas Connection
To open the outside air shutter, open the bottom control access panel, reach into the control compartment, and pull the outside air control lever all the way out. The outside air shutter should be fully open when the fi replace is in use and completely closed when the fi replace is not being used. Closing it when not in use will prevent outside cold air from entering the dwelling.
WARNING
DO NOT operate the outside air control lever with a fi re in the fi rebox unless a complete outside combustion air vent system has been installed with the appliance.
Outside Air Control Lever
Figure 19: Millivolt Gas Valve—Lower Control Compartment
STEP 7. INSTALLING OUTSIDE AIR KIT
Optional outside make-up air kits, Model FOAK-4 or FAOK-4LD (see Figure 21 on Page
14), may be used with these appliances. Refer to the installation instructions packaged with the air kits for specifi c installation information. If used, the outside air kit must be installed before the fi replace is framed and enclosed in the fi nished wall.
Outside air drawn into the fi replace supplies air to the fi re for combustion. Only one outside air duct is necessary, if installed. See Figure 3 on Page 5 for the location of the unit's outside air inlet.
If additional length of duct is necessary, purchase locally available U.L. Class 0 or Class 1 metallic ducting. The duct may extend up to 50' (15.24 m) in any direction.
Note: When installing the air duct vertically, DO NOT terminate the duct closer than 3' below the chimney top.
Outside supplemental combustion air ducting may be run upwards or vertically through framing and ceiling joists, with the hood installed through an outside wall and 3' (1 m) below the termination. Ducting may also be run downward through fl oor joists and under the home to a ventilated crawlspace not considered part of the living area of the home.
Note: Do not terminate an outside air kit in the attic space under any circumstances.
After completing the installation of the optional outside air vent system the outside air control lever must be put in service and tested to ensure proper operation before completing any enclosure around the fi rebox. Failure to do so may result in extensive and costly rework. Before the operation of the vent system can be tested, the lever securing screw must be removed (see Figure 20).
The hand operated outside air control lever is located on the left side of the fi replace opening (see Figure 20).
CAUTION
Never locate inlet where it can be blocked by shrubs, snow drifts, etc. Never locate inlet in garage or any area where there is another fuel burning appliance or products emitting combustible gases such as paint, gasoline, etc. In cold climates, it is recommended the outside air duct be insulated.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Outside Air Control Lever
Securing screw
Air Shutter in Closed Position
Outside Air Control Lever
Outside Air Control Lever
Securing Screw Removed
Air Shutter in Open Position
Figure 20: Outside Air Control Lever
Operate the actuator through several cycles including the closed position. Ensuring proper operation and freedom of movement. Return the actuator arm to the closed position.
13
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
Outside Combustion Air Kits
Cat. No. Model No. Description
81L87 FOAK-4 Combustion Air Kit (w/duct)
81L88 FOAK-4LD Combustion Air Kit (w/o duct)
Figure 21: Outside Combustion Air Kits
STEP 8. VERIFYING APPLIANCE OPERATION
With gas line installed, run initial system checkout before closing up the front of the unit. Follow the pilot lighting instructions provided in the Care and Operation Instructions. For piezo igniter location on millivolt appliances, (see Figure 19).
Note: Lighting Instructions are also found on the literature tag tied to the gas piping next to the gas valve. To access the tag, open the lower control
compartment door (see Figure 19). To open the control compartment access panel, actuate the spring loaded magnetic catches securing the panel. First, gently depress the upper right top corner of the panel until the magnet catch "pops" the door free. Then, gently pulling the panel forward, disengage the left magnet catch and allow the panel to swing down
to open. When fi rst lighting the appliance, it will
take a few minutes for the line to purge itself of air. Once purging is complete, the pilot and burner will light and operate as indicated in the instruction manual. Subsequent lighting of the appliance will not require such purging. Inspect the pilot fl ame (remove logs, if necessary, handling carefully).
MILLIVOLT APPLIANCE CHECKOUT
The pilot fl ame should be steady, not lifting or fl oating. Flame should be blue in color with traces of orange at the outer edge.
The top 3/8 in. (10 mm) at the pilot generator (thermopile) and the top 1/8 in. minimum (tip) of the quick drop out thermocouple should be engulfed in the pilot fl ame.
The fl ame should project 1 in. (25 mm) beyond the hood at all three ports (see Figure 22). Replace logs if removed for pilot inspection.
To light the burner; turn “ON” the remote wall switch and rotate the gas valve control knob counterclockwise to the “ON” position (“ON” will be at the top side of the valve).
Hood Igniter Rod
Thermocouple
3/8 in.
(9 mm)
Pilot Nozzels
Thermopile
Figure 22: Millivolt Pilot
ELECTRONIC APPLIANCE CHECKOUT
To light the burner, turn ‘ON’ the wall or remote control switch. Ensure the igniter lights the pilot. The pilot fl ame should engulf the fl ame rod as shown in Figure 23.
Igniter
Sensor
Flame Rod
(sensor)
Figure 23: Electronic Pilot
Min
Pilot Hood
STEP 9. INSTALLING VOLCANIC STONE, GLOWING EMBERS, AND LOGS
Locate the packaged carton of logs (which were located in the fi rebox). The decorative volcanic stone and glowing embers were packaged separately in plastic bags located in the control area of the fi replace.
DO NOT attempt to install the logs until the appliance installation has been completed, the gas line connected and tested for leaks, and the initial burner operation has been checked out.
Proper log placement is critical to encourage outstanding fl ame appearance and prevent sooting. When positioned properly as shown, logs will be positioned between fl ame peaks and will not impinge any fl ames.
Refer to Figure 26 for MPB33 Series appliances, Figure 27 for MPB35 Series appliances and Figure 28 for MPB40 and MPB45 Series appliances.
NOTE: Turn off all electricity to the appliance before you install volcanic stone, embers and logs.
WARNING
• DO NOT attempt to install the logs until the appliance installa­tion has been completed, the gas line connected and tested for leaks and the initial burner operation has been checked out.
The size and position of the log set was engineered to give the appli­ance a safe, reliable and attractive fl ame pattern. Any attempt to use a different log set in the fi replace will void the warranty and will result in incomplete combustion, sooting, and poor fl ame quality.
Logs get very hot and will remain hot up to one hour after gas supply is turned off. Handle only when logs are cool. Turn off all electricity to the appliance before you install grate, volcanic stone, embers and logs.
This appliance is not designed to burn wood. Any attempt to do so could cause irreparable damage to the appliance and prove hazardous to your safety.
If logs are not installed accord­ing to the log installation instruc­tions, fl ame impingement and improper combustion could occur and result in soot and/or excessive production of carbon monoxide (CO), a colorless, odorless, toxic gas.
14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
Step 1. Remove the appliance front door (see Removing the Glass Enclosure Panel on Page 19).
Step 2. Install decorative volcanic stone—Sprinkle the decorative volcanic
stone in a pleasing pattern. The volcanic stone should be placed directly on top of the firebox bottom, along the front and to the back at the right and left sides of the burner. Position any optional ceramic fiber liners before placing the stone. Logs should be positioned after the volcanic stone.
Note: This appliance is provided with enough glowing embers for several ap­plications, do not feel compelled to use all that is in a new bag. For best glowing effect, replace the ember material annually. Replacement glowing embers are available (Catalog Number 88L53).
Glowing Embers
Separate into Quarter
Size (separate) Pieces
Bag of Glowing
Embers (rockwool)
Glowing Embers
Figure 25: Glowing Embers Placement
Step 4. Placement of Logs—All top logs that rest on lower logs, do so over notches, indents or nubs. Proper log placement is critical to prevent sooting. Logs should be placed in the gaps between the flame peaks and should be positioned so they do not impinge the flames.
Step 5. Position the individual logs as shown in Figures 26, 27, and 28. Logs should be placed in the order shown. All logs that have notches to fi t over the grate tines should be positioned with these notches directly against the grate. Handle
logs carefully to prevent breakage.
Figure 24:
Step 3. Separate the glowing embers (rockwool) into pieces about the size of a quarter (see Figure 24). Keep the pieces fluffed up, not matted. Distribute these pieces over the front surface of the burner, as shown in Figure 25. Do not use more than is necessary. When properly positioned, the Glowing Embers will cover approximately 65% of the front burner and with no appreciable gaps or openings. Ensure that the main burner ports remain uncovered by the ember material.
REFERENCE
Cat. No. Model No. Description
88L53 FGE Bag of Glowing Embers 80L42 FDVS Bag of Decorative
Volcanic Stone
Table 7: Firebox Accessories/Parts
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
15
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
MPB33 LOG PLACEMENT
* Item
1
1
2 3 4
3
2
5 6
Description (stamped #)
Log, Rear (39-12) Log, Left (39-1) Log, Right (39-2) Log, Top Center (39-
13) Log, Top/Left (39-3) Log, Top/Right (39-4)
Catalog Number for the entire log set: 24M15
Position the individual logs as shown below. Logs should be
4
6
5
1
placed in the order shown. Position the rear log on the brackets at the rear of the firebox with the log's notches directly over the brackets. Position the right log (log no. 3) by inserting the pin from the rear log into the hole on its upper end. Place the left log and then the smaller left and right top logs. All logs that have notches to fit over the grate tines should be positioned with these notches directly against the grate. All top logs that rest on lower logs, do so over flattened mounting faces in the bottom logs.
Proper log and twig placement is critical to encourage outstanding flame appearance and prevent sooting.
4
3
2
5
6
16
Figure 26: Log Set 24M15 Placement
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
MPB35 LOG PLACEMENT
Log
1
3
2
Number Description (Stamped #)
1 Log, Rear (39-5) 2 Log, Left (39-1) 3 Log, Right (39-2) 4 Log, Top Center (39-6) 5 Log, Top/Left (39-3) 6 Log, Top/Right (39-4)
Catalog Number for the entire log set: H6197
4
5
6
Position the individual logs as shown below. Logs should be placed in the order shown. Position the rear log on the brackets at the rear of the fi rebox with the log's notches directly over the brackets. Position the right log (log no. 3) by inserting the pin from the rear log into the hole on its upper end. Place the left log and then the smaller left and right top logs. All logs that have notches to fi t over the grate tines should be positioned with these notches directly against the grate. All top logs that rest on lower logs, do so over fl attened mounting faces in the bottom logs.
Proper log and twig placement is critical to encourage outstanding fl ame appearance and prevent sooting.
1
4 3
2
Figure 27: Log Set H6197 Placement
5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6
17
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
MPB40 AND MPB45 LOG PLACEMENT
Log
1
2
3
Number Description (Stamped #)
1 Log, Center (39-8) 2 Log, Rear (138) 3 Log, Right (39-10) 4 Log, Left (39-9) 5 Log, Top/Left (39-11) 6 Log, Top/Right (39-11)
Catalog Number for the entire log set: 24M25
4
5
6
Position the individual logs as shown below. Logs should be placed in the order shown. Position the center log on the burner fi rst, then place the glowing embers as shown in Figure 52. Place the rear log, both the right and left, and then the smaller left and right top logs. All logs that have notches to fi t over the grate tines should be positioned with these notches directly against the grate. All top logs that rest on lower logs, do so over fl attened mounting faces in the bottom logs.
Proper log and twig placement is critical to encourage outstanding fl ame appearance and prevent sooting.
1
4
3
2
18
Figure 28: Log Set 24M25 Placement
5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
STEP 10. REMOVING AND INSTALLING THE GLASS DOOR
WARNING
Do not attempt to substitute the materials used on the door, or replace cracked or broken glass.
• Handle this glass with extreme care! Glass is susceptible to damage – Do not scratch or handle roughly while reinstalling the glass door frame.
• The glass door of this appliance must only be replaced as a complete unit as provided by the manufacturer. Do not attempt to replace broken, cracked or chipped glass separately.
Do not attempt to touch
the front enclosure glass with your hands while the fi replace is in use.
WARNING
Do not operate appliance with the glass front removed, cracked or broken.
AVERTISSEMENT
Ne pas utiliser l'appareil si le panneau frontal en verre n'est pas en place, est craqué ou brisé.
Only doors certifi ed with the appliance shall be used.
Seules des portes certifi ées pour cet appareil doivent être utilisées.
WARNING: DO NOT abuse glass door by striking or slamming shut.
Removing the Glass Enclosure Panel (see Figure 29)
Remove the top louver assembly. Open the lower control compartment door (see Figure 29 ) by pressing in simultaneously at the left and right top corners of the door (the door is hinged at the bottom).
Remove the bottom compartment door by sliding the hinge pin, located at the door’s left side, to the right until it disengages from the left corner post hole. Pull the door diagonally to the left, away from the fi replace.
Locate the latch at the top of the control compartment and disengage it from the door frame bottom vee-fl ange, pulling down on the handle to open it.
Installing the Glass Enclosure Panel (see Figure 29)
Retrieve the glass door. Visually inspect the gasket on the backside of the frame. Gasket surface must be clean, free of irregularities and seated fi rmly.
Position the door in front of the fi rebox opening with the bottom of the door held away from the fi replace (see Figure 29). Hook the top fl ange of the door frame over the top of the fi rebox frame.
Let the bottom of the door frame swing gently in towards the fi replace ensuring that the gasket seats evenly as the door frame draws shut. Fasten the latch located underneath the fi rebox fl oor to the door's vee-fl ange. Close the latch securely.
Top Flange on Glass Door
Glass Door
Latch
Bottom Vee-fl ange
Glass Door
NOTE: When installing the glass door, ensure the spacing on both sides are equal.
Figure 29: Installing or Removing Glass Door
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Firebox Floor
STEP 11. BURNER ADJUSTMENTS
Flame Appearance and Sooting
Proper fl ame appearance is a fl ame that is blue at the base and becomes yellowish­orange in the body of the fl ame.
When the appliance is fi rst lit, the entire fl ame may be blue and will gradually turn yellowish-orange during the fi rst 15 minutes of operation. If the fl ame remains blue, or if the fl ame is orange with evidence of sooting (black tip), the air shutter opening may need to be adjusted.
If the air shutter opening is closed too far, sooting may develop. Sooting is indicated by black puffs developing at the tips of very long orange fl ames. Sooting results in black deposits forming on the logs, appliance inside surfaces and on exterior surfaces adjacent to the vent termination.
Sooting is caused by incomplete combustion in the fl ames and lack of combustion air entering the air shutter opening. To achieve a warm yellowish-orange fl ame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, fi rst check the log set positioning to ensure that the fl ames are not impinging on any of the logs. If the log set is properly positioned and a sooting condition still exists, then the air shutter opening should be increased.
• The more offsets in the vent system, the larger the air shutter opening will need to be.
• An appliance operated with the air shutter opened too far, may have fl ames that appear blue and transparent. These weak, blue and transparent fl ames are termed anemic.
• Propane models may exhibit fl ames which candle or appear stringy. If this is present and persists, adjust the air shutter to a more closed position, then operate the appliance for a few more minutes to ensure that the fl ame normalizes and the fl ames do not appear sooty.
Note: The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation.
Air Shutter Adjustment Guidelines
Amount of
Primary Air
If air shutter is closed too far
If air shutter is open too far
Flame
Color
Flame will be orange
Flame will be blue
Air Shutter Adjustment
Air shutter gap should be increased
Air shutter gap should be decreased
19
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
WARNING
Air shutter adjustment should only be performed by a qualifi ed professional service technician.
Ensure the front glass panel
• is in place and sealed during adjustment.
CAUTION
Soot will be produced if the air shutter is closed too much. Any damage due to sooting, resulting from improperly setting the air shutter, is not covered under the warranty.
The air shutter door and nearby appliance surfaces are hot. Exercise caution to avoid injury while adjusting fl ame appearance.
1. Refer to Figures 30, 31, and 32 for
proper fl ame appearance. To adjust the fl ame, move the rod up and down (the adjustment rod is located in the lower control area). Position the air shutter to the factory setting as shown in Table 8.
2. Light appliance (follow lighting procedure
on lighting label in control compartment or in the Care and Operation Instructions).
3. Allow the burner to operate for at least
15 minutes while observing the fl ame continuously to ensure that the proper fl ame appearance has been achieved. If the following conditions are present, adjust accordingly.
• If fl ame appears weak or sooty, adjust the air shutter, incrementally, to a more open position until the proper fl ame appearance is achieved.
• If fl ame remains blue, adjust the air shutter, incrementally, to a more closed position until the proper fl ame appearance is achieved.
4. When satisfi ed that the burner fl ame appear-
ance is normal, reinstall the lower control compartment door, then proceed to fi nish the installation.
20
Figure 30: MPB33 MODEL
Figure 31: MPB35 MODEL
Figure 32: MPB40 AND MPB45 MODEL
Adjusting Set Screw
Adjustment Rod Up
(minimum air
Burner Tube
Air Shutter
Adjustment Rod Down
(fully open position)
Figure 33: Air Shutter
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
opening position)
Main Burner Factory Air Shutter
Opening Setting - Inches (millimeter)
Model Natural Gas Propane Gas
MPB33 Fully Closed 3/16" (4.76 mm) MPB35 Fully Closed 3/16" (4.76 mm) MPB40 Fully Closed 3/16" (4.76 mm) MPB45 Fully Closed 3/16" (4.76 mm)
Table 8: Air Shutter Opening Setting
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
STEP 12. TESTING VENT OPERATION
After appliance installation, perform this vent operation test to verify that proper venting conditions exist:
1. Place unit in its normally-operated
condition, that is, with the glass enclosure panel in place.
2. Close all doors and windows in the room.
Turn on all exhaust fans in the house.
3. Light the appliance.
4. Wait 15 minutes.
5. To check for venting action, start by
holding a smoke producing device below the glass enclosure panel. The smoke should be drawn into the control compartment. Continue the test by moving the smoke producing device along the entire length of below the glass door.
6. If the smoke is not drawn into the
control compartment, turn off the appliance and call a qualified service technician.
RESETTING THE SAFETY LIMIT SWITCH
This appliance is equipped with a manually resetable safety limit switch. Refer to Figure 34 for its location. If, during appliance operation, the flame goes out (independently of the burner on/off wall switch), it may be due to a blocked vent. If this condition occurs, the safety limit switch will activate, causing the fireplace burner to shut off. To reset this switch, first allow the appliance to cool, then remove the top louver panel. Reset the safety limit switch by pushing the red reset button, located between the wire terminals on the back of the switch (See Figure 34, Detail A).
The appliance should then relight and remain lit. Reinstall the top louver panel. If the appliance does not relight, turn off the appliance and call for a qualified service technician.
To replace the blocked flue safety limit switch
(see Figure 34, Details B & C).
This procedure should only be performed by a qualified service technician.
IMPORTANT - TURN ELECTRICAL POWER OFF BEFORE BEGINNING THIS PROCEDURE.
1. Lower the bottom control
compartment access panel. Remove the glass enclosure panel: open the latch (located in the center of the unit front opening, under the fi rebox fl oor) securing the glass enclosure panel. Remove the panel by tilting it outward at the bottom and lifting it up. Set the door aside protecting it from inadvertent damage (see Figure 29 on Page 19).
2. Remove the lintel securing screws
(3) and then remove the lintel. One of the lintel cabinet top holes is shown in Figure 34, Detail B.
3. Remove the scoop securing screws
(3) and then remove the scoop (see Figure 34, Detail B).
4. Remove the safety switch bracket
securing screws (2), and pull the switch/bracket assembly, with low voltage wires attached, through the side panel slot into the fi rebox (see Figure 34, Detail C).
5. Replace the switch.
6. Reinstall the switch/bracket
assembly.
7. Reinstall the scoop and lintel.
8. Reinstall the glass enclosure panel.
9. Raise the bottom control
compartment access panel.
10. The appliance should then relight
and remain lit. If this does not occur, check unit for a blocked fl ue condition.
Wire Terminals
Reset Button Cabinet
Corner Back Of
Limit Switch
Door Frame
Detail A
Lintel Securing Screw
Firebox Top
Detail B
Firebox Top
Detail C
Blocked Flue Safety Limit Switch Location, Inside
View of Firebox, Top/Right Side Intersection
Figure 34: Safety Limit Switch
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Hole in Cabinet Top
Scoop
Scoop Securing Screws
Lintel Securing-Screw
Hole in Cabinet Top
Limit Switch/Bracket
Securing Screws
Limit Switch
View Without Scoop
STEP 13. HOOD INSTALLATION
Refer to Figure 35. All models must have hoods installed prior to operating.
On louvered face units, slide the hood into the slots on the lower edge of the cabinet top above the louvered vent (see Figure 35).
STEP 14. FINISHING REQUIREMENTS Wall Details
Complete fi nished interior wall. To install the appliance facing fl ush with the fi nished wall, position framework to accommodate the thickness of the fi nished wall (see Figure 9
on Page 8).
See Page 4 for
Cold Climate Insulation and
Page 8 for Clearances.
Combustible
Finished Wall
Materials
Combustible material may touch top of appliance.
Combustible materials NOT allowed below this point on face of appliance.
Hood must be installed as shown.
Figure 35: Louver Face Models
This area must remain clear of combustible materials.
Min. 1 in. (25 mm)
Header Spacing Top Standoff
Top of Appliance
Louvers
Top of Door Frame
21
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
STEP 15. ATTACHING SAFETY-IN-OPERATION WARNINGS It is the installer’s responsibility to ensure these warnings are properly affi xed during installation. These warning labels are a
critical step in informing consumers of safe operation of this appliance.
ATTACHING SAFETY IN OPERATION WARN­INGS
It is required that the safety instruction labels fur­nished with the fireplace be affixed to the operation and control point of the fireplace. A safety instruction label must be affixed to the wall switch plate where the fireplace is turned on and off (See Figure A) and if used on the remote control handheld transmitter (Figure B). To properly complete the installation of this fireplace, locate the multi-lingual adhesive labels provided with the Care and Operation Instructions and proceed as follows:
1. Locate the wall switch that controls the fireplace
(verify the switch operates the fireplace by turn­ing it on and off). Clean the wall switch plate thoroughly to remove any dust and oils. Affix the label to the surface of the plate of the wall switch that controls the fireplace (Figure A). Choose the language primarily spoken in the home. If unknown, affix the English language label.
2. If a remote control is used to control the fireplace,
locate the transmitter and clean it thoroughly to remove any dust and oils. Affix the label to the surface of handheld transmitter (Figure B) . Choose the language primarily spoken in the home. If unknown, affix the English language label.
3. If you are unable to locate the labels, please call
Lennox Hearth Products or your nearest Lennox Hearth Products dealer to receive additional safety instruction labels free of charge.
Cat. No. H8024 Replacement Label Kit
LENNOX HEARTH PRODUCTS 1-800-655-2008
Note: English is red text on clear label. French and Spanish are white text on black label.
APPOSITION DES MISES EN GARDE RELATIVES À LA SÉCURITÉ D’UTILISATION
Il est impératif que les étiquettes de sécurité fournies avec le foyer soient collées à côté des dispositifs de contrôle du foyer. Une étiquette de sécurité doit être collée sur la plaque de l’interrupteur contrôlant l’allumage du foyer (voir Figure A) et, le cas échéant, sur le boîtier de la télécommande (Figure B). Pour achever l’installation correcte de ce foyer, procédez comme suit avec les étiquettes adhésives en langues étrangères fournies avec les instructions d’utilisation et d’entretien :
1. Repérez l’interrupteur qui contrôle le foyer (vérifiez que l’interrupteur contrôle le fonctionnement du foyer en le faisant basculer de Marche à Arrêt, et vice-versa). Nettoyez soigneusement la plaque murale de l’interrupteur pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur la surface de la plaque de l’interrupteur mural qui contrôle le foyer (Figure A). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
2. Si une télécommande est utilisée pour contrôler le foyer, nettoyez la soigneusement pour éliminer
Collez l’étiquette sur le boîtier de la télécommande (Figure B). Choisissez la langue qui est principale­ment parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez appeler Lennox Hearth Products ou votre distribu­teur Lennox Hearth Products local pour recevoir gratuitement des étiquettes supplémentaires.
Étiquettes de remplacement, n° cat. H8024
LENNOX HEARTH PRODUCTS 1-800-655-2008
Remarque : Le texte anglais est rouge sur un support transparent. Le texte français et espagnol est blanc sur un support noir.
COLOCACIÓN DE ADVERTENCIAS DE SEGURIDAD EN OPERACIÓN
Se requiere que las etiquetas de instrucciones de seguridad incluidas con la chimenea se coloquen en el punto de operación y control de la misma. Se debe colocar una etiqueta de instrucciones de seguridad en la placa del interruptor de pared desde el cual se enciende y se apaga la chimenea (ver la Figura A) y en el transmisor de control remoto (Figura B) si se usa. Para completar correctamente la instalación de esta chimenea, encuentre las etiquetas adhesivas multilingües incluidas con las instrucciones de cuidado y operación y haga lo siguiente:
1. Identifique el interruptor de pared que controla la chimenea (verifique que el interruptor opera la chimenea encendiéndola y apagándola). Limpie bien la placa del interruptor de pared para quitar el polvo y aceite. Pegue la etiqueta en la superficie de la placa del interruptor que controla la chimenea (Figura A). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
2. Si se usa un control remoto para controlar la chimenea, encuentre el transmisor y límpielo bien para quitar el polvo y aceite. Pegue la etiqueta en la superficie del transmisor (Figura B). Seleccione
.eliuh’d uo essiarg ed secart sel te erèissuop al
el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas, sírvase llamar a Lennox Hearth Products o al distribuidor de Lennox Hearth Products más cercano para recibir etiquetas de instrucciones de seguridad adicionales gratuitas.
Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS 1-800-655-2008
Nota: La etiqueta en inglés es transparente con texto rojo. Las etiquetas en francés y español son negras con texto blanco.
Illustrations are for example only. Your accessories may be different.
Les illustrations sont par exemple uniquement. Vos accessoires peuvent être différents.
Las ilustraciones son sólo ejemplos. Tu accesorios pueden ser diferentes.
22
SAFETY LABEL
DIAGRAMS
Figure A
DIAGRAMMES DES ÉTIQUETTES
DE SÉCURITÉ
Figure B
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
DIAGRAMAS DE ETIQUETAS
DE SEGURIDAD
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
GAS CONVERSION KITS
WARNING
This conversion kit shall be installed by a qualifi ed service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instruction is not followed exactly, a fi re, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualifi ed service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specifi ed in the manu­facturer’s instructions supplied with the kit.The qualifi ed service agency performing this installation assumes responsibility for this conversion.
AVERTISSEMENT
Cette trousse de conversion doit être installée par un technicien agréé, selon les instructions du fabricant et selon toutes les exigences et tous les codes pertinents de l’autorité compétente. Assurez-vous de bien suivre les instructions dans cette notice pour réduire au minimum le risque d’incendie, d’explosion ou la production de monoxyde de carbone pouvant causer des dommages matériels, des blessures ou la mort. Le tecnicien agréé est responsable de l’installation de cette trousse. L’installation n’est pas adéquate ni complète tant que le bon fonctionnement de l’appareil converti n’a pas été vérifi é selon les instructions du fabricant fournies avec la trousse. Le fournisseur de service qualifi é ayant réalisé l'installation assume les responsabilités liées à la conversion.
In Canada: THE CONVERSION SHALL BE CARRIED
OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/ CGA-B149.1 INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE EFFECTUÉE CONFORMÉMENT AUX RECOMMANDATIONS DES AUTORITÉS PROVINCIALES AYANT JURIDICTION ET CONFORMÉMENT AUX EXIGENCES DU CODE D'INSTALLATION CAN/ CGA-B149.1.
Gas conversion kits are available to adapt your appliance from the use of one type of gas to the use of another. These kits contain all the necessary components needed to complete the task including labeling that must be affi xed to ensure safe operation.
Kit part numbers are listed here and the following steps detail the conversion procedure. Refer to the instructions provided with the conversion kit when performing any gas conversion.
Table 9: Millivolt Conversion Kits
Millivolt SIT Systems
Natural Gas To Propane Gas
Conversion Kits
Models Catalog No.
MPB33 H2009 MPB35 H2011 MPB40 H2013 MPB45 H2015
Millivolt SIT Systems
Propane Gas to Natural Gas
Conversion Kits
Models Catalog No.
MPB33 H2010 MPB35 H2012 MPB40 H2014 MPB45 H2016
Electronic SIT Systems
Natural Gas To Propane Gas
Conversion Kits
Models Catalog No.
MPB33 H8632 MPB35 H8634 MPB40 H8636 MPB45 H8638
Electronic SIT Systems
Propane Gas To Natural Gas
Conversion Kits
Models Catalog No.
MPB33 H8631 MPB35 H8633 MPB40 H8635 MPB45 H8637
Table 10: Electronic Conversion Kits
INSTALLATION INSTRUCTIONS Step 1. TURN OFF THE GAS SUPPLY TO THE
APPLIANCE and disconnect power supply at the circuit breaker. Ensure appliance is cold.
CAUTION: THE GAS SUPPLY SHALL BE SHUT OFF PRIOR TO DISCONNECTING THE ELECTRICAL POWER, BEFORE PROCEEDING WITH THE CONVERSION.
ATTENTION: AVANT D’EFFECTUER LA CONVERSION, COUPEZ D’ABORD L’ALIMENTATION EN GAZ, ENSUITE, COUPEZ L’ALIMENTATION ÉLECTRIQUE.
Step 2. Open the lower control compartment
door (see Figure 19 on Page 13) by pushing on the right top corner of the door (the door is hinged at the bottom).
[Optional] Remove the control compartment door by sliding the hinge pin, located at the door’s left side, to the right until it disengages from the left corner post hole. Pull the control compartment door diagonally to the left, away from the fi replace.
Step 3. Remove the front glass door/frame from the appliance (see Page 19).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
23
LENNOX HEARTH PRODUCTS • MERIT PLUS® B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
Step 4. Carefully remove the logs. Exercise care so as not to break the logs.
Step 5. Refer to Figures 26, 27, or 28. A. Remove the grate and sub fl oor. B. Remove the two (2) screws securing the
burner assembly. C. Remove the burner assembly with
attached venturi tube.
MILLIVOLT AND ELECTRONIC IGNITION SYSTEM APPLIANCES
Step 6. SIT Systems—Refer to Figure 37
and the instructions provided with the SIT Regulator Conversion Kit. Using a Torx T20 driver to remove and discard the pressure regulator mounting screws (two screws for electronic models, three screws for millivolt models), pressure regulator tower, the diaphragm assembly (if applicable) and the spring. Discard all removed components.
Step 7. Install the new pressure regulator assembly using the supplied screws. Tighten the screws with a torque of 25 lb-in.
Pressure Regulator
Remove These Components
Millivolt Valve
Electronic Valve
Figure 37: Regulator Conversion
Step 8. Install the enclosed identifi cation label to the valve body where it can be easily seen.
Step 9. Refer to Figure 38. Remove the pilot hood assembly to access the hexed pilot orifi ce. Remove and replace the orifi ce with the one provided with the kit. Exercise extreme care to prevent damage to or breakage of the igniter assembly.
Pilot
Orifice
Figure 38: Millivolt Pilot
Step 10. Remove the burner orifi ce from the manifold and replace it with the one provided in the kit. See Table 11 for orifi ce sizes for natural and propane models. Figure 39 illustrates the orifi ce.
Figure 39: Orifi ce
Use pipe joint compound or Tefl on tape on all pipe fi ttings before installing (ensure propane resistant compounds are used in propane applications, do not use pipe joint compounds on fl are fi ttings).
Step 11. Retrieve the burner and hold the
venturi tube above the orifi ce. Set the burner assem bly into position and secure with the two screws previously removed.
Step 12. Reassemble the remaining components by reversing the procedures outlined in the Steps 1–5.
Step 13. Attach the conversion label provided in the conversion kit next to the rating plate on the appliance.
Step 14. Turn on gas supply and test for gas leaks (refer to Page 27).
Step 15. Reapply electrical power at the circuit breaker.
Step 16. Relight the main burner. The lighting instructions can be found on the lighting label in the control compartment or in the Care and Operation Manual provided with the appliance. Verify proper burner ignition and operation. See Burner Adjustments and Burner Flame Appearance on Page 19.
Step 17. Inspect the pilot system for proper fl ame. The pilot fl ame should engulf the fl ame sensor as shown in Figure 23 on Page 14.
Step 18. Using a manometer, test the inlet and manifold gas pressures (see Tables 3
and 4 on Page 4).
ALWAYS TEST PRESSURES WITH THE REGULATOR CONTROL VALVE AT THE HIGHEST SETTING.
Model
Series
MPB33
MPB35
MPB40
MPB45
Nat.Gas
drill size (inches)
#47 (.0785") *
99K74 •
#44 (.086") *
60J80 •
#38 (.102") *
99K76 •
#36 (.104") *
24M10 •
* Standard size installed at factory
• Part /Cat. Number
Propane
drill size (inches)
(.048")*
99K78 •
#55 (.052") *
19L52 •
(.0625") *
21L01 •
#52 (.0635") *
37G00 •
Table 11: Burner Orifi ce Sizes
Elevation 0–4500 ft ( 0–1372 m)
24
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifi cations, prices and also to discontinue colors, styles and products. Consult your local distributor for fi replace code information.
LENNOX®, the LENNOX design, DAVE LENNOX, the image of DAVE LENNOX and other related LENNOX marks are registered or common law trademarks of Lennox Industries Inc. and are used with permission.
Printed in U.S.A. © 2012 Lennox Hearth Products LLC
P/N 506015-05 Rev. NC 07/2012
26
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
Loading...