Lennox Hearth LSM40ST-N, LSM40ST-P User Manual

INSTALLATION INSTRUCTIONS
WARNING /AVERTISSEMENT/AVISO
Montebello See-Through Direct-Vent Gas Fireplaces
P/N 506023-12 Rev. B 05/2011
This manual is one of a set of two supporting this product. Refer to P/N
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 506223-11.
506025-05
for Care and Operation Instructions.
MODELS
LSM40ST-N LSM40ST-P
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l’appareil. CONSOMMATEUR : Conservez cette notice pour
Intertek Report No.
100326523PRT-001
Look for the EnerGuide
Gas Fireplace Energy
Efficiency Rating in this manual.
Based on CSA P.4.1-02
consultation ultérieure.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.
TM
• HOT GLASS WILL CAUSE BURNS.
• DO NOT TOUCH GLASS UNTIL COOLED.
• NEVER ALLOW CHILDREN TO TOUCH GLASS.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
• UNE SURFACE VITRÉE CHAUDE PEUT CAUSER DES BRÛLURES.
• LAISSER REFROIDIR LA SURFACE VITRÉE AVANT D'Y TOUCHER.
• NE PERMETTEZ JAMAIS À UN ENFANT DE TOUCHER LA SURFACE VITRÉE.
AVERTISSEMENT : Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incindie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
• EL VIDRIO CALIENTE CAUSARÁ QUEMADURAS.
• USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE.
• LOS NIÑOS DEBEN NUNCA TOCAR EL VIDRIO.
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
TABLE OF CONTENTS
Packaging ................................................... 2
Introduction ................................................ 2
Approved Vent Components .................... 2
General Information .................................... 2
Misc. Codes/Standards ........................... 3
Inputs and Efficiencies ............................ 3
Gas Supply Pressure Requirements ........ 3
Gas Valve Diagram ................................. 4
Orifice Sizes ............................................ 4
Massachusetts / NYC Requirements ....... 4
Cold Climate Insulation ............................... 5
Manufactured Home Requirements ............ 5
Location ...................................................... 5
Vent Termination Clearances ...................... 6
Hearth Extensions (Optional) ...................... 8
Minimum Clearances to Combustibles ........ 9
Pre-Installation Steps .................................. 10
Typical Installation Sequence ..................... 10
Detailed Installation Steps:
Step 1. Framing .......................................... 10
Framing Specifications ............................. 11
Fireplace Dimensions ............................... 12
Step 2. Route Gas Line .............................. 13
Step 3. Install Vent System ........................ 14
General Information ................................. 14
Vent Restrictor Assembly/Installation ...... 14
Vent Termination (Vertical/Horizontal) ..... 14
Vertical (Roof) Termination ...................... 15
Vertical Termination with Straight
Vertical Venting ............................... 15
Straight Vent Section Lengths Table ... 15 Vertical Termination with Offset
Vertical Venting ............................... 16
Vertical Termination System Figures
and Tables ........................................ 18
Horizontal (Wall) Termination .................. 19
Horizontal Termination System
Figures and Tables ........................... 21
Step 4. Field Wiring .................................... 23
Step 5. Remove Glass Door ....................... 23
Step 6. Connecting Gas Line ...................... 24
Step 7. Install Firebox Liner Panels ............ 25
Step 8. Verify Appliance Operation ............. 25
Step 9. Install Volcanic Stone, Glowing
Embers, and Logs .................................... 26
Step 10. Install Glass Doors, Mesh Pull
Screens, and Modesty Panel ................... 29
Step 11. Burner Adjustments ..................... 30
Finishing Requirements .............................. 31
Step 12. Attaching Safety-in-Operation
Warnings ..................................... 33
Installation Accessories .............................. 34
Gas Conversion Kits .......................... 35
The assembled vented gas replace is pack­aged with the following items:
Fireplace Components:
(1) Literature Kit (in envelope in rebox;
contains Care and Operation Instruc­tions, Installation Instructions, safety-
in-operation warning labels, warranty)
(1) Remote Control Kit (in plastic bag in re-
box; contains remote control, receiver) (1) Log Set (1) Vent Restrictor Assembly (1) bag Glowing Embers (4) bags Volcanic Stone (1) Door Modesty Shield
Panel Kit (sold separately; REQUIRED for all
replace models) - one of the following kits:
Architectural Stone Ceramic Venetian Tile Ceramic Buff Herringbone Ceramic Buff Rustic Ceramic Black Rustic Ceramic Black Porcelain
Outdoor Installation Kit (sold separately;
REQUIRED for indoor/outdoor installations)
INTRODUCTION
The Montebello™ See-Through is a direct-vent, sealed combustion gas replace designed
for either indoor/indoor or indoor/outdoor residential applications (including screened
porches and lanais). See “Minimum Clearances to Combustibles” on Page 9.
NOTE: INDOOR/OUTDOOR INSTALLATIONS REQUIRE AN OUTDOOR INSTALLATION KIT
(SOLD SEPARATELY).
These appliances are designed to operate on natural or propane gas. The system is switch-
able between standing and intermittent pilot
modes.
External electrical power is required to oper­ate these units. If the system operates on line
voltage, four “AA” batteries (in receiver) can be used as a backup in case of a power outage.
Approved Vent Components
These fireplaces are designed, tested, and listed for operation and installation with the following vent components (8" inner and 11" outer) only:
• SecureVent
ponents manufactured by Security Chimneys
International.
These approved vent system components are
labeled for identication. Do NOT use any other
manufacturer’s vent components with these appliances.
SV8 direct-vent system com-
GENERAL INFORMATIONPACKAGING
WARNING
Young children should be care­fully supervised when they are in the same room as the appli­ance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la sur­face chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habi­tent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécu­rité; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Les enfants et les adultes devraient être infor-més des dangers que posent les températures de surface élevées et se tenir à distance afin d’éviter des brûlures ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
2
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional informa­tion consult a qualified installer, service agency or the gas supplier.
WARNING
Failure to comply with these installation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appliance and/or its operating controls is dangerous.
WARNING
Clothing or other flammable material should not be placed on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de vête­ments ni d’autres matières inflam­mables sur l’appareil ni à proximité.
WARNING
Any safety screen or guard removed for servicing the appli­ance must be replaced prior to operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
WARNING
Improper installation or use of this appliance can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
Note: Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
Remarque : L’installation et la répara­tion devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien profes­sionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres.
Do not use these appliances if any part has been under water. Immediately call a qualified, professional service technician to inspect the appliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas utiliser cet appareil s’il a été plongé, même partiellement, dans l’eau. Appeler un technicien qualifié pour inspecter l’appareil et remplacer toute partie du système de commande et toute commande qui a été plongée dans l’eau.
Only trim kit(s) supplied by the manufacturer shall be used in the installation of this ap­pliance.
Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
These appliances comply with National Safety
Standards and are tested and listed by Intertek (Report No. 100326523PRT-001) to ANSI Z21.88 (in Canada, CSA-2.33), and CAN/CGA-
2.17-M91 (CSA P4.1) in both USA and Canada,
as vented gas fireplace.
These appliances are listed by Intertek for installation in bedrooms, aftermarket mobile homes, and manufactured homes.
Misc. Codes/Standards
Installation must conform to local codes or, in
the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition (in Canada, the current CAN/CSA-B149.1
installation code). The appliance, when installed, must be electri-
cally grounded and wired in accordance with
local codes or, in the absence of local codes,
with the National Electrical Code, ANSI/NFPA 70 - latest edition, or the Canadian Electrical Code, CSA C22.1 - latest edition.
Provide adequate clearances around air open­ings and adequate accessibility clearance for service and proper operation. Never obstruct the front or back openings of the appliance.
These appliances are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the per­formance of this system and may be dangerous.
The system is switchable between standing
and intermittent pilot modes. External electri­cal power is required to operate these units.
If the system operates on line voltage, four “AA” batteries (in receiver) can be used as a backup
in case of a power outage.
These models come standard with a remotely modulated gas valve. The included transmitter remotely controls flame appearance and heat
output (manual gas valve adjustment is not possible).
Inputs and Efficiencies
Appliance BTU inputs are listed in Table 1A. Appliance efficiencies are listed in Table 1B.
INPUTS
Gas Type (Fireplace Model) Inputs (BTU/hr)
Natural Gas (LSM40ST-N) 40,000 to 60,000 Liquid Propane (LSM40ST-P) 43,500 to 56,000
Table 1A
EFFICIENCIES
Gas Type (Fireplace Model)
Natural Gas (LSM40ST-N) 68% 67% Liquid Propane (LSM40ST-P) 70% 67%
Table 1B
AFUE EnerGuide
Gas Fireplace Energy Efciency Rating
Based on CSA P.4.1-02
Gas Supply Pressure Requirements
Inlet and manifold gas supply pressure require­ments for these appliances are listed in Tables 2 and 3.
Inlet Gas Supply Pressure (all models)
Fuel # Minimum Maximum
Natural Gas
Propane
Table 2
Manifold Gas Supply Pressure (all models)
Fuel # Low High
Natural
Gas
Propane
Table 3
(Continued on next page)
5.0" WC
(1.24 kPa)
11.0" WC
(2.74 kPa)
(Lo) 1.6" WC
(0.4 kPa)
(Lo) 6.3" WC
(1.57 kPa)
10.5" WC
(2.61 kPa)
13.0" WC
(3.23 kPa)
(Hi) 3.5" WC
(0.87 kPa)
(Hi) 10.0" WC
(2.49 kPa)
3
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Gas Supply Pressure Requirements
(continued)
Test gauge connections are provided on the front of the electronic gas control valve (identi­fied IN for the inlet and OUT for the manifold
side). The control valves have a 3/8" (10 mm) NPT
thread inlet and outlet side of the valve. Refer to Figure 1.
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step-down regulators to reduce the pressure to safe levels.
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
These appliances must be isolated from the gas supply piping system (by closing their individual manual shut-off valve)
during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
These appliances and their individual
shut-off valves must be disconnected
from the gas supply piping system during any pressure testing of that system at pressures greater than 1/2 psig (3.5 kPa).
Orifice Sizes
Sea Level To High Altitude (All Models)
These appliances are tested and approved
for installation at elevations of 0– 4500 feet (0– 1372 meters) above sea level using the standard burner orice sizes (marked with an asterisk [*] in Table 4 ). For elevations above 4500 feet, contact your gas supplier or qualied
service technician.
Deration
At higher elevations, the amount of BTU fuel value delivered must be reduced by either:
• using gas that has been derated by the gas company; or
• changing the burner orice to a smaller size as regulated by the local authorities having jurisdiction and by the (USA) National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition or, in Canada, the CAN/CSA-B149.1
codes - latest edition.
Install the appliance according to the regulations
of the local authorities having jurisdiction and,
in the USA, the National Fuel Gas Code NFPA
54 / ANSI Z223.1 - latest edition or , in Canada, the CAN/CSA-B149.1- latest edition.
NOTE: Flame appearance will diminish 4% per thousand feet.
Burner Orifice Sizes
Elevation 0– 4500 feet (0–1372 meters)
Natural Gas
Drill size (inches)
#32 (0.116")*
H8002•
Standard size installed at factory.
Table 4
*
•Part/CatalogNumber.
Propane
Drill size (inches)
#52 (0.0635")*
H8003•
Requirements for the Commonwealth of Massachusetts
These fireplaces are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with Massachusetts Rules and Regulations 248 C.M.R.
• Installation and repair must be done by a plumber or gas tter licensed in the Com­monwealth of Massachusetts.
• The exible gas line connector used shall not exceed 36 inches (92 centimeters) in
length.
• The individual manual shut-off must be a
T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, hori­zontal terminations installed less than seven (7) feet above the finished grade must comply with the following additional requirements:
• A hard-wired carbon monoxide detector with an alarm and battery back-up must be
installed on the floor level where the gas
replace is installed. The carbon monoxide detector must comply with NFPA 720, be ANSI/UL 2034 listed and be ISA certied.
• A metal or plastic identication plate must be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade and be directly in line with
the horizontal termination. The sign must
read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
Line (In) Test Port
Orange Wire
(from DFC Wire
Harness)
Inlet 3/8" NPT
Figure 1: SIT Proflame Valve
4
(From DFC Wire
Manifold (Out)
Test Port
Green Wire
Harness)
Gas Valve Diagram
See valve diagram in Figure 1.
Connect GTMS Wire Harness
Pressure Regulator Tower
Outlet 3/8" NPT
Yellow Ground Wire (From DFC Wire Harness)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
New York City, New York (MEA)
Installation of these fireplaces is approved for
installation in New York City, NY.
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks
around the appliance with noncombustible
material and wherever cold air could enter the
room. If the oor is above ground level, it is
especially important to insulate outside chase
cavity between studs and under the oor on
which the appliance rests. Gas line holes and
other openings should be caulked or stuffed with unfaced berglass insulation.
If the replace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can be placed under-
neath to prevent cold transfer to the fireplace and into the room. It also helps to sheetrock inside surfaces and tape for maximum air tightness and caulk firestops.
Drywall
Outdoors
Indoors
(Top View)
MANUFACTURED HOME REQUIREMENTS
This appliance may be installed in an after­market, permanently located, manufactured
home and must be installed in accordance
with the manufacturer's instructions and the
Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the
United States, or the Standard for Installation
in Mobile Homes, CAN/CSA Z240 MH Series,
in Canada.
Cet appareil peut être installé cómme du matéri-el d'origine dans une maison
préfabriquée (É.U. seulement) ou mobile
et doit être installé selon les instructions
du fabricant et conformément à la norme Manufactured Home Constructions and Safety, Title 24 CFR, Part 3200 aux Unis ou à la norme Can/CSA-Z240 Série MM, Maisons mobiles au Canada.
This appliance is only for use with the type of gas indicated on the rating plate. This ap-
pliance is not convertible for use with other
gases, unless a certified kit is used.
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil ne peut être con-
verti à d'autres gaz, sauf si une trousse de
conversion est utilisée.
Top of Fireplace Opening
When unit is installed with one side flush with a wall, the wall on other side of unit must not extend beyond front edge of unit.
Figure 2: Typical Installation/Locations
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary
concerns; however, vent system routing to
the exterior and access to the fuel supply are also important.
CAUTION: Due to high temperatures, the ap­pliance should be located out of traffic and away from furniture and draperies (Figure 2).
AVERTISSEMENT : En raison des tem­pératures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures (Figure 2).
The location also should be free of electrical, plumbing, or other heating/air conditioning
ducting.
Be aware that this is a heat-producing ap­pliance. Objects placed above the unit are exposed to elevated temperatures.
Do not insulate the space between the appli­ance and the area above it.
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located
on or near conventional construction materials.
However, if installed on combustible materials, (such as carpeting or vinyl tile), a metal or wood barrier covering the entire bottom surface must be used.
CAUTION: Ensure that the cross members are not cut or weakened during installation. The structural integrity of the manufactured home floor, wall, and ceiling / roof must be maintained.
CAUTION: This appliance must be grounded to the chassis of the manufactured home in accordance with local codes or in the absence of local codes, with the National Electrical Code ANSI / NFPA 70 - latest edi­tion or the Canadian Electrical Code CSA C22.1 - latest edition.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
5
*H = MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING OF VENT
TERMINATION HEIGHTS FOR VENTS ABOVE
FLAT OR SLOPED ROOFS
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
VENT TERMINATION CLEARANCES
These instructions should be used as a guide­line and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the cur­rent standards of CAN/CSA-B149.1 in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations accord-
ing to the installation codes listed above. Also
see Figure 3A.
Terminate single vent caps relative to building
components as shown in Figure 3B.
12 in (305 mm) minimum
Horizontal Overhang
2 FT
2 FT MIN.
Vent
Termination
Storm Collar
Flashing
Concentric
Vent Pipe
*H = minimum height from roof to lowest discharge opening of vent.
MIN.
Lowest
Discharge
Opening
H*
1 inch (25.4 mm) Minimum Clearance to Combustibles
Vertical Wall
X
12
Roof Pitch is X/12
Figure 3B: Vertical Vent Termination Clearances
Vent/air intake termination clearances
above the high side of an angled roof are listed in the table below.
Termination Heights for Vents
Above Flat or Sloped Roofs
(Ref. NFPA 54 / ANSI Z223.1)
Roof Pitch *Feet *Meters
Flat to 6/12 1.0 0.3
6/12 to 7/12 1.25 0.38 7/12 to 8/12 1.5 0.46
8/12 to 9/12 2.0 0.61
9/12 to 10/12 2.5 0.76
10/12 to 11/12 3.25 0.99 11/12 to 12/12 4.0 1.22
12/12 to 14/12 5.0 1.52 14/12 to 16/12 6.0 1.83
16/12 to 18/12 7.0 2.13
18/12 to 20/12 7.5 2.29 20/12 to 21/12 8.0 2.44
Figure 3A : Multiple Terminations
Horizontal Vent Termination Clearances
The horizontal vent termination must have a minimum of 3 in (76 mm) clearance to any overhead combustible projection of 2-1/2 in (64 mm) or less (see Figure 4). For projections exceeding 2-1/2 in (64 mm), see Figure 4. For additional vent location restrictions refer to Figure 5 on Page 7.
Combustible
Projection
extending more
than 2.5 inches
Combustible Projection extending up to 2.5 inches
24 in
(610 mm)
Horizontal Termination Kit
Horizontal Vent Termination Clearances
For recess allowances of square horizontal termination into exterior walls, see Figure 30 on Page 20.
Figure 4
3 in
(76 mm)
Side Elevation View
Ventilated or Unventilated Soffit
6
V
X
V
= Vent terminal
= Air supply inlet
= Area terminal NOT permitted
= 9" U.S. (12" Canada)
A
G
X
V
= Vent terminal
= Air supply inlet
= Area terminal NOT permitted
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS
NOTE:
•Local codes or regulations may require
different clearances.
•Location of vent termination must NOT
interfere with access to electrical service.
= Vent terminal
V
= Area terminal NOT permitted
= Air supply inlet
X
= 9" U.S. (12" Canada)
D
Center Line of
Horizontal
Termination
36"
(91.4 cm)
Exterior Wall
D
36"
(91.4 cm)
Inside Corner
[DETAIL]
See Item “D” in table below.
Ventilated
Soffit
V
A
G
V
G
A
[DETAIL]
Inside Corner
H
B
V
F
L
V
Fixed Closed
Window
C
Operable
Window
B
X
V V
V
A
C
C
C
B B
B
J
M
V
I
MINIMUM CLEARANCES
Clearance Description US Installation Canadian Installation
A = Clearance above grade, veranda, porch,
deck, or balcony.
B = Clearance to window or door that may be
opened.
C = Clearance to permanently closed window. 9 in (229 mm) recommended to prevent window
D = Vertical clearance to ventilated soffit
located above the terminal within a horizontal distance of 36 in (91.4 cm)
from center line of terminal.
E = Clearance to unventilated soffit. 24 in (61 cm) 24 in (61 cm) F = Clearance to outside corner. 5 in (12.7 cm) 5 in (12.7 cm) G = Clearance to inside corner. 24 in (61 cm) 36 in (91.4 cm)
H = Clearance to each inside of center line
extended above meter/regulator assembly.
= Clearance to service regulator vent outlet. 3 ft (91.4 cm) 3 ft (91.4 cm)
I
J = Clearance to non-mechanical air supply
inlet to building or combustion air inlet to
any other appliance.
K = Clearance to mechanical air supply inlet. 3 ft (91.4 cm) above, if within 10 ft (3 m) horizontally. 6 ft (1.83 m) L = Clearance above paved sidewalk or paved
driveway located on public property.
M = Clearance under veranda, porch, deck, or
balcony.
In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Codes (latest editions). In accordance with the current CAN/CSA-B149.1 Installation Code (latest editions). A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single-family dwellings and serves both dwellings. Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
Figure 5
18 in (46 cm) 18 in (46 cm)
6 in (15.2 cm) for appliances < 10,000 BTU/hr (3kW); 9 in (23 cm) for appliances > 10,000 BTU/hr (3kW)
and < 50,000 BTU/hr (15kW);
12 in (30 cm) for appliances > 50,000 BTU/hr (15kW).
condensation.
24 in (61 cm) 24 in (61 cm)
3 ft (91.4 cm) within a height of 15 ft above the
meter/regulator assembly.
6 in (15.2 cm) for appliances < 10,000 BTU/hr (3kW); 9 in (23 cm) for appliances > 10,000 BTU/hr (3kW)
and < 50,000 BTU/hr (15kW);
12 in (30 cm) for appliances > 50,000 BTU/hr (15kW).
7 ft (2.13 m) 7 ft (2.13 m)
18 in (46.0 cm) 18 in (46.0 cm) 
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6 in (15.2 cm) for appliances < 10,000 BTU/hr (3kW); 12 in (30 cm) for appliances > 10,000 BTU/hr (3kW)
and < 100,000 BTU/hr (30kW);
36 in (91.4 cm) for appliances > 100,000 BTU/hr (30kW). 12 in (305 mm) recommended to prevent window
condensation.
3 ft (91.4 cm) within a height of 15 ft above the
meter/regulator assembly.
6 in (15.2 cm) for appliances < 10,000 BTU/hr (3kW); 12 in (30 cm) for appliances > 10,000 BTU/hr (3kW)
and < 100,000 BTU/hr (30kW);
36 in (91.4 cm) for appliances > 100,000 BTU/hr (30kW).
D E
V
X
K
7
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
HEARTH EXTENSIONS (OPTIONAL)
Note: Hearth extensions are not required with this appliance.
Optional Indoor Hearth Extension
Combustible indoor hearth material may only be installed at or below the base of the replace (see Figures 6 and 7).
Non-combustible indoor hearth material may be installed above the base of the replace and may butt against the front face of the replace (see
Figures 6 and 7).
Also note the following:
• Combustible material may project beyond the sides of the replace
opening, as long as it is within the shaded area shown in Figure 10 on Page 9.
• Vertical installation clearances to combustible mantels vary according
to the depth of the mantel (see Figure 9 on Page 9).
• Non-combustible mantels may be installed at any height above the
appliance opening.
Optional Outdoor Hearth Extension
All outdoor hearth material (combustible and non-combustible) must be installed a minimum of 6" (152 mm) below the base of the replace
(see Figure 7).
Also note the following:
• For vertical installation clearances to combustible outdoor mantels and
overhangs, see Page 32 and the instructions provided in the Outdoor
Installation Kit (required for all outdoor installations; see Page 34).
• Non-combustible outdoor mantels and overhangs may be installed at any height above the appliance opening.
Indoor
Side
Fireplace
(side view)
Outdoor
Side
Finish combustible material must be installed at or below base of fireplace.
Finish non-combustible material may butt against front face of fireplace.
Also see Figure 7.
Figure 6: Optional Indoor Hearth Extension
8
Floor Panel
Indoor hearth extension:
Front Face of Fireplace
Finish combustible material must be installed at or below base of fireplace.
Finish non-combustible material may be installed above base of fireplace and may butt against front face of fireplace.
Figure 7: Optional Indoor and Outdoor Hearth Extensions
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6" (152 mm)
minimum
Outdoor hearth extension:
All finish hearth material (combustible and non-combustible) must be at least 6" (152 mm) below base of fireplace.
7 (178)
2
(51)
4
(102)
6
(152)
8
(203)
10
(254)
12
(305)
9 (229)
13 (330)
17 (432)
15 (381)
11 (279)
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
MINIMUM CLEARANCES TO COMBUSTIBLES
Appliance and Vent Clearances
The appliance is approved with zero clearance to combustible materials on both sides (as detailed in Table 5), with the following exceptions:
When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit.
In addition, when the unit is recessed, the side walls surrounding the unit must not extend beyond the front edge of the unit (see Figure 2
on Page 5).
MINIMUM CLEARANCES TO COMBUSTIBLES
Back / Sides Top Spacers 0 in (0 mm) Floor 0 in (0 mm) Unit Bottom to Ceiling 72.0 in (1829 mm) Vertical Vent Pipe 1.0 in (25.4 mm) Horizontal Vent Pipe
0 in (0 mm) Spacers
Top: 4.0 in (102 mm) Sides: 1.0 in (25.4 mm) Bottom: 1.0 in (25.4 mm)
SERVICE CLEARANCES
Front 3 ft (0.9 m)
Table 5
Do NOT insulate space between appliance and area above it.
Combustible
Enclosure/Shelf
~
Min. 4"
~
(102 mm)
91.5" (2324 mm)
Indoor/Outdoor
90" (2287 mm)
minimum
Indoor/Outdoor
Min. 2 ft vertical vent section and one 90-degree elbow required
minimum
Top of Fireplace
2 x 4
Figure 8: Min. Height of Combustible Enclosure
Mantel Depth
IMPORTANT!
Min. clearance to
combustibles above any
horizontal vent component
is
4" (102 mm).
4" (102 mm) above any horizontal/inclined vent component.
See Step 1 ("FRAMING") on Page 10 for clearance requirements to
nailing flanges on each side of unit and any adjacent screw heads.
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materials; however, if installed on combustible materials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bottom surface must be used.
Min. Height of Combustible Enclosure
To provide for the lowest possible combustible enclosure (or shelf) surface, the venting should be routed in a way to minimize obstructions to the space above the appliance. Do not insulate the space between the appliance and the area above it (see Figure 8).
Wall Finishes / Surrounds / Mantels
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front faces (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the appliance face. See Pages 31 and 32.
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with these exceptions: they must not cover any portion of the removable glass panel.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (see Figure 9 ). Mantels constructed of non- combustible materials may be installed at any height above the appliance
opening.
Note: Use high-temperature paint (rated 175°F or higher) on the under­side of the mantel.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
to bottom of mantel
Distance from top of appliance
Inches
(millimeters)
Top of Appliance
Figure 9: Mantel Clearances
Minimum Distance to Unprotected Side Wall
At 14" minimum side wall clearance, a combustible wall can project to any length.
At 8-1/4" side wall clearance, a combustible wall can project 12" maximum.
Gray area is “safe zone”
14" (356 mm)
8.25" (209 mm)
(13 mm)
Figure 10: Side Wall Clearances
0.5"
45°
Protected wall shown in white
Top View of Fireplace
Combustible materials are allowed in gray “safe
5 in (127 mm)
zone” illustrated here. Combustible walls are
shown in black.
12 in
Protected wall is shown
(305 mm)
in white. Combustible material
17 in
may project beyond
(432 mm)
the side of the fireplace opening if it is within the gray "safe zone" illustrated here.
Side View
9
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
PRE-INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre-wired.
1. Remove the shipping carton, exposing the
front glass door on the control side.
2. Using a Phillips screwdriver, unfasten two
(2) screws located at the top of the glass
frame (see Figure 50 on Page 29). Tilt the top of the glass frame away from the unit.
Lift it carefully off the bottom door track
and set the door aside, protecting it from inadvertent damage.
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifi­cally approved with this appliance may result in property damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation is outlined
below.
Note: Each installation is unique and may result in variations to the steps described herein.
See the page numbers referenced in the fol­lowing steps for detailed procedures.
Step 1. FRAMING (Page 10): Construct
appliance framing. Position
appliance within framing; and secure with nailing brackets.
Step 2. ROUTE GAS LINE (Page 13):
Route gas supply line to right side (when viewed from control side of
appliance).
Step 3. INSTALL VENT SYSTEM (Page 14):
install vent system and exterior termination.
Step 4. FIELD WIRING (Page 23): Connect
120 Vac electrical power to the appliance receptacle.
Step 5. REMOVE GLASS DOOR ASSEMBLY
(Page 23).
Step 6. CONNECT GAS LINE (Page 24):
Make connection to gas supply.
Step 7. INSTALL FIREBOX LINER PANEL
KIT (Page 25).
Step 8. VERIFY APPLIANCE OPERATION
(Page 25).
Step 9. INSTALL VOLCANIC STONE,
GLOWING EMBERS, AND LOGS
(Page 26).
Step 10. INSTALL GLASS DOORS, MESH
PULL SCREENS, AND MODESTY PANEL (Page 29).
Step 11. BURNER ADJUSTMENTS (Page
30): Adjust burner air shutter to
ensure proper flame appearance.
FINISHING REQUIREMENTS (Page 31). Step 12. ATTACHING SAFETY-IN-
OPERATION WARNINGS (Page 33).
DETAILED INSTALLATION STEPS
Step 1. FRAMING
Frame these appliances as illustrated in Figure 12 on Page 11. All framing details must allow
for a minimum clearance to combustible fram­ing members as shown in Table 5 and Figures
8–10 on Page 9.
If the appliance is to be elevated above oor level, a solid continuous platform must be constructed below the appliance.
Headers may be in direct contact with the appliance top spacers but must not be sup­ported by them or notched to t around them. All construction above the appliance must be
self-supporting, DO NOT use the appliance for structural support.
Secure the fireplace to the side framing mem-
bers using the unit's nailing anges — one top and bottom on each side of the replace
front (see Figure 11). Use 8d nails or their equivalent.
Securing Unit to Framing by Nailing Flanges
Use Top Flange for 1/2” Thick Drywall
Front of Fireplace Use Center Flange
for Flush Mount
Use Bottom Flange for 5/8” Thick Drywall
Left Side Front Corner of Fireplace Shown
(Same requirements for right side)
Note: The nailing anges, combustible
members and screw heads in areas directly adjacent to the nailing anges are EXEMPT from the 1/2-inch clearance to combustible requirements for the rebox outer wrapper. Combustible framing may be in direct
contact with the nailing flanges and may
be located closer than 1/2 inch from screw heads and the rebox wrapper in areas adjacent to the nailing anges. Frame the
opening to the exact dimensions specified in the framing details in these Installation
Instructions.
Figure 11
10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
13
(330)
16
(406)
6-1/2 (165)
C
Inches
(millimeters)
1-1/2
(38)
D
A
B
E
~
D
B
13
(330)
16
(406)
6-1/2 (165)
C
Inches
(millimeters)
A
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
FRAMING SPECIFICATIONS
Framing should be constructions of 2x4 or larger lumber.
LSM40ST A
in 52-1/16 47-5/16 75-1/2 26-5/16 6
(mm) (1322) (1202) (1918) (668) (152)
B
C
D
E
Dimension B is from replace base to top framing member. Dimension C is from replace base to centerline of horizontal vent pipe.
Minimum vent framing: 2 ft vertical vent and one 90° elbow. For other venting configurations, see Step 3, INSTALL VENTING SYSTEM.
1/2-inch board for platform (shown in gray). Dimension E is a 6-inch clearance from replace base to outdoor
surface (e.g., deck, patio, lanai) that is required as a moisture barrier (not a combustible clearance) on outdoor side only.
Figure 12
INDOOR SIDE
Outdoor Surface (e.g., deck, patio, lanai)
OUTDOOR SIDE*
*For indoor/outdoor installations, the control side
of the fireplace must be installed on the indoor side.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
11
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
FIREPLACE DIMENSIONS
(shown with Outdoor Kit installed)
FIREPLACE COLLAR AND VENT SIZE
Fireplace Vent Collar and Vent Pipe (Coaxial DV) 8" Inner / 11" Outer
NOTE: All venting/termination systems (vertical and horizontal) require installation of the provided Vent Restrictor. See Page 14 for details.
inches
(millimeters)
27-7/16
(697)
3-15/32
(88)
26-3/16
(665)
inches
(millimeters)
13-3/32
(333)
inches
(millimeters)
12-5/16
(313)
25-9/32
(642)
5-13/32
(137)
Fireplace Vent Collar
8" Inner / 11" Outer
7-5/16
(186)
Top View
34-3/4
(883)
5-3/32
(130)
12
46-19/32
(1184)
19-17/32
Figure 13
(496)
7 (178)
Control Switch Wires Knock-Out
Left Side View
Gas Inlet
J-Box
29-19/32
(752)
Front View (opposite valve access side)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
41-1/2
(1054)
33-3/4
(857)
50-1/2
(1283)
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Step 2. ROUTE GAS LINE
NOTICE: For indoor/outdoor installations,
the CONTROL SIDE of the fireplace must be installed on the INDOOR side.
Route a 1/2" (13 mm) gas line along the inside
of the right side framing as shown in Figures 14 and 15. Gas lines must be routed, constructed
and made of materials that are in strict accor­dance with local codes and regulations.
All appliances are factory-equipped with a
exible gas line connector and 1/2-inch shutoff
valve (see Step 6 on Page 24).
The incoming gas line should be piped into
the valve compartment and connected in one of the two methods as shown in Figure 36 on Page 24.
Proper Sizing of Gas Line
Properly size and route the gas supply line from the supply regulator to the area where the
appliance is to be installed per requirements
outlined in the National Fuel Gas Code, NFPA
54 - latest edition (USA) or CAN/CSA-B149.1
- latest edition (Canada).
Never use galvanized or plastic pipe. Refer to Table 6 for proper sizing of the gas supply line,
if black iron pipe is being used. Gas lines must be routed, constructed and made of materials
that are in strict accordance with local codes and regulations.
IMPORTANT: It is critical that a licensed installer perform this step strictly per NFPA.
We recommend that a qualified, licensed
plumber or gas tter be hired to correctly size
and route the gas supply line to the appliance. Installing a gas supply line from the fuel supply to the appliance involves numerous consider­ations of materials, protection, sizing, loca­tions, controls, pressure, sediment, and more. Certainly no one unfamiliar and unqualified should attempt sizing or installing gas piping.
Notes:
• All appliances are factory-equipped with a exible gas line connector and 1/2-inch
shutoff valve (see Figure 36 on Page 24).
• See Massachusetts Requirements on Page 4 for additional requirements for installa-
tions in the state of Massachusetts in the
USA.
• The gas supply line should not be connected
to the appliance until Step 6 (Page 24).
• A pipe joint compound rated for gas should be used on the threaded joints. Ensure
propane-resistant compounds are used in propane applications. Be very careful that
the pipe compound does not get inside the pipe.
Sediment Trap: It is recommended to install a sediment trap in the supply line as close as
possible to the appliance (see Figure 36 on Page 24). Appliances using propane should
have a sediment trap at the base of the tank.
• Check with local building ofcial for local code requirements (such as whether below-
grade penetrations of the gas line allowed,
etc.).
7”
(178 mm)
Right Side Front Corner
(Valve Side) Of Fireplace Framing
Figure 14: INDOOR / INDOOR
1-1/2”
(38 mm)
7”
(178 mm)
Right Side Front Corner
(Valve Side) Of Fireplace Framing
19-1/2"
(495 mm)
19-1/2"
(495 mm)
Schedule 40, Black Iron Pipe
Inside Diameter (Inches)
Schedule 40 Pipe
Length (feet)
0-10 1/2 3/8
10-40 1/2 1/2
40-100 1/2 1/2
100-150 3/4 1/2 150-200 3/4 1/2
Natural
Gas
Table 6
Propane
Gas
IMPORTANT NOTE REGARDING
PROPANE INSTALLATIONS
Using a propane tank smaller than 100 lbs may create pressure loss and insufficient fuel delivery, which can cause sooting, severe delayed ignition, or other malfunctions (ref. NPFA 58).
Any damage as a result of insufficient tank size or other improper installation is NOT covered under the limited warranty.
Figure 15: INDOOR / OUTDOOR
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
13
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Step 3. INSTALL VENT SYSTEM
General Information
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to lo­cal codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/ CSA-B149.1 in Canada.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d'in­stalla tion locaux et aux exigences du foumisseunde gaz.
Use only approved venting components. See “Approved Vent Components” on Page 2.
These fireplaces must be vented
directly to the outside.
Vent Restrictor Kit
Vent Restrictor Assembly for Horizontal Termination Systems
For systems with horizontal termination, use only the vent restrictor base.
The vent system may not service multiple ap-
pliances and must never be connected to a ue serving a solid fuel burning appliance.
The vent pipe is tested to be run inside an enclosed wall (such as a chase). There is no
requirement for inspection openings in the en-
closing wall at any of the joints in the vent pipe.
Vent Restrictor Assembly and Installation
All vent systems require installation of a vent restrictor. A vent restrictor kit is provided with
the replace (packaged inside the rebox) and includes one base, two wings, and four screws (see Figure 16A).
1. Assemble the vent restrictor components
according to the type of termination and length of vent run, as shown in Figures 16B and 16C.
2. Install the vent restrictor in the appliance top flue outlet, as shown in Figure 16D. The
vent restrictor is held in place by friction only.
Vent Restrictor Assembly for Vertical Termination Systems
For systems with vertical termination, use the four provided
screws to attach the two wings to the base in the applicable position based on length of vertical run, as shown below.
Assembly for vertical termination with 6–10 ft vertical runs:
Note: When possible, install the vent
restrictor through the top of the appliance vent outlet BEFORE installing the vent system. (It is possible to install the vent restrictor from inside the firebox after vent system installation; however, doing so requires removing the firebox baffle.)
Vent Termination (Vertical or Horizontal)
With the appliance secured in framing, determine whether to terminate the venting
vertically (through the roof) or horizontally (through the wall).
• For Vertical (Roof) Termination Systems,
see Pages 15–18.
• For Horizontal (Wall) Termination Systems,
see Pages 19–22.
See Page 34 for a list of
approved venting components.
(1) Vent Restrictor Base
(2) Wings (4) Screws
Figure 16A Figure 16B
Vent Restrictor Installation
Applicable Vent Restrictor Assembly (per Figures 16B and 16C)
Inner Collar
~
~
Appliance Vent Outlet
Assembly for vertical termination with 11–40 ft vertical runs:
Assembly for vertical termination with 41–60 ft vertical runs:
14
Install applicable vent restrictor assembly (per Figures 16B and 16C)
into inner collar of appliance vent outlet.
Note: The vent restrictor is held in place by friction only.
Figure 16D
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 16C
HSTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
6 21 42 63 84
T O T A L
Q T Y
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
5.4 573.0 1 0 0 0 0 1
9 57.0 2 0 0 0 0 2
5.01 578.0 0 1 0 0 0 1
51 52.1 1 1 0 0 0 2
5.91 526.1 2 1 0 0
0
3
12 57.1 0 2 0 0 0 2
5.22 578.1 0 0 1 0 0 1
5.52 521.2 1 2 0 0 0 3
5.13 526.2 0 3 0 0 0 3
5.43 578.2 0 0 0 1 0 1
5.73 521.3 1 1 1 0 0 3
5.34 526.3 0 2 1 0 0 3
54 57.3 0 0 2 0 0 2
5.64 578.3 0 0 0 0 1 1
5.94 521.4 1 0 2 0 0 3
15 52.4 1 0 0 0 1 2
5.55 526.4 0 1 2 0 0 3
75 57.4 0 0 1 1 0 2
66 52.5 0 2 2 0 0 4
5.76 526.5 0 0 3 0 0 3
96 57.5 0 0 0 2 0 2
27 6 1 0 3 0 0 4
5.37 521.6 1 0 0 2 0 3
5.97 526.6 0 1 0 2 0 3
18 57.6 0 0 0 1 1 2
09 5.7 0 2 1 0 1 4
5.19 526.
7 0 0 2 0 1 3
39 57.7 0 0 0 0 2 2
69 8 1 0 1 2 0 4
5.79 521.8 1 0 0 0 2 3
201 5.8 2 0 0 0 2 4
5.301 526.8 0 0 0 3 0 3
801 9 1 0 0 3 0 4
411 5.9 0 2 0 0 2 4
711 57.9 1 0 5 0 0 6
5.811 578.9 1 1 0 3 0 5
621 5.01 0 0 1 3 0 4
5.031 578.01 1 0 1 3 0 5
531 52.11 0 0 6 0 0 6
831 5.11 0 0 0 4 0 4
5.931 526.11 0 0 0 0 3 3
5.241 578.11 1 0 0 4 0 5
noitceSlanimoN )sehcni(htgneL
6 21 42 63 84
T O T A L
Q T Y
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
441 21 1 0 0 0 3 4
051 5.21 0 1 0 0 3 4
5.451 578.21 1 1 0 0 3 5
5.061 573.31 0 2 0 0 3 5
5.271 573.41 0 0 0 5 0 5
771 57.41 1 0 0 5 0 6
381 52.51 0 1 0 5 0 6
681 5.51 0 0 0 0 4 4
5.091 578.51 1 0 0 0 4 5
5.691 573.61 0 1 0 0 4 5
5.502 521.71 0 1 1 5 0 7
702 52.71 0 0 0 6 0 6
5.112 526.71 1 0 0 6 0 7
5.712 521.81 0 1 0 6 0 7
5.922 521.91 0 0 1 6 0 7
5.232 573.91 0 0 0 0 5 5
732 57.91 1 0 0 0 5 6
5.142 521.02 0 0 0 7 0 7
642 5.02 1 0 0 7 0 8
252 12 0 1 0 7 0 8
462 22 0 0 1 7 0 8
672 32 0 0 0 8 0 8
972 52.32 0 0 0 0 6 6
5.082 573.32 1 0 0 8 0 9
5.382 526.32 1 0 0
0 6 7
5.982 521.42 0 1 0 0 6 7
5.103 521.52 0 0 1 0 6 7
5.013 578.52 0 0 0 9 0 9
513 5.62 1 0 0 9 0 01
5.523 521.72 0 0 0 0 7 7
033 5.72 1 0 0 0 7 8
633 82 0 1 0 0 7 8
543 57.82 0 0 0 01 0 01
5.943 521.92 1 0 0 01 0 11
273 13 0 0 0 0 8 8
5.673 573.13 1 0 0 0 8 9
5.973 526.13 0 0 0 11 0 11
5.814 578.43 0 0 0 0 9 9
324 52.53 1 0 0 0 9 01
564 57.83 0 0 0 0 01 01
HSTGNELNOITCESTNEV
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Vertical (Roof) Termination Systems
This section includes configurations for vertical
(roof) termination systems with either straight
vertical venting (see below and Page 18) and offset vertical venting (see Pages 16–18).
Secure Vent™ rigid vent pipe and termination
components are shown in the figures. The tables on Page 18 summarize each sys-
tem’s minimum and maximum vertical and horizontal length values.
For vertical (roof) termination, the minimum vent height above the roof and/or adjacent
walls is specified in ANSI Z223.1, latest edi-
tion (in Canada, the current CAN/CSA-B149.1 installation code) and by major building
codes. Always consult your local codes for specific requirements. A general guide to follow is the Gas Vent Rule (see Figure 3B
on Page 6).
Vertical Termination System with Straight Vertical Venting
Note: If not already done, install the pro­vided vent restrictor before proceeding (see Page 14).
Determine the number of straight vent sec­tions required. Available straight vent sec­tions (and their effective lengths) are listed in
Table 7, below. See Page 34 for all venting components.
Plan the vent lengths so a joint does not occur at the intersection of ceiling or roof joists. Refer to the “VENT SECTION LENGTHS
charts at right.
Vertical Termination System with Straight Vertical Venting
Termination
Max. 60 ft
(18 m)
Min. 6 ft
(1.8 m)
Figure 17
Flashing and Storm Collar
Min. 1 in (25 mm) Clearance to Combustibles
Firestop/Spacer
Secure Vent Vent Sections
(SV8L6, SV8L12, SV8L24, SV8L36, SV8L48)
Available Straight Vent Sections
Cat. No. Model No. Description Effective Length
H2250 SV8L6 6 in (152 mm) Vent Section 4.5 in (114 mm) H2251 SV8L12 12 in (305 mm) Vent Section 10.5 in (267 mm) H2252 SV8L24 24 in (610 mm) Vent Section 22.5 in (572 mm)
Metric
Conversion
Inches x 25.4 = mm. Inches x 2.54 = cm. Inches x 0.0254 = m.
H2253 SV8L36 36 in (914 mm) Vent Section 34.5 in (876 mm) H2254 SV8L48 48 in (1219 mm) Vent Section 46.5 in (1181 mm)
Table 7 See Page 34 for a list of all approved venting components.
15
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Min. 13 in
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Vertical Termination System with Offset Vertical Venting
Note: If not already done, install the pro­vided vent restrictor before proceeding (see Page 14).
Analyze the vent routing and determine the
quantities of vent sections and number of elbows required. Refer to Vertical Termination
System Figures and Tables on Page 18 to select the type of vertical installation desired.
Vent sections are available in net lengths of 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm). Refer to the Vent Section Length
Chart on Page 15 for an aid in selecting length
combinations. Elbows are available in 90° and 45° congurations. See Figure 21 on Page 17 for the SV8E45 and SV8E90 elbow dimensional
specifications. Where required, a telescopic vent section
(SV8LA) may be used to provide the installer
with an option in installing in tight and confined spaces or where the vent run made up of fixed
length pieces develops a joint in a undesirable location, or will not build up to the required
length. The SV8LA Telescopic Vent Section has
an effective length of from 1-1/2" (38 mm) to 6-3/4" (171 mm). The SV8LA is tted with a
dimpled end (identical to a normal vent section
component) and a plain end with 3 pilot holes.
Slip the dimpled end over the locking channel end of a standard SV8 vent component the required distance and secure with three screws.
Maintain a minimum 1" (25 mm) clearance to combustible materials for all vertical ele­ments. Clearances for all horizontal elements are 4" (102 mm) on top, 1" (25 mm) on sides and 1" (25 mm) on the bottom.
A. Frame ceiling opening.
Use a plumb line from the ceiling above the
appliance to locate center of the vertical run. Cut and/or frame an opening, 13" x 13" (330
mm x 330 mm) inside dimensions, about this center mark (Figure 18).
Roof Framing
Min. 13 in (330 mm)
Ceiling Framing
16
Plumb Bob
Figure 18
(330 mm)
B. Attach vent components to appliance. Secure Vent™ SV8 direct-vent system compo-
nents are unitized concentric pipe components featuring positive twist lock connections (see Figure 19).
All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent com­ponents fit over the appliance collar to create the positive twist-lock connection.
Align four dimples in upper vent section with inlets of four locking incline channels on lower vent section or appliance collar.
Twist upper vent section clockwise
Arrow
Lower Vent Section or Appliance Collar
until arrows and dimples align.
Dimple
Locking Incline Channel
Connected Vent
Sections
Arrow
Figure 19
To attach a vent component to the appliance collar, align the dimpled end over the collar,
adjusting the radial alignment until the four
locking dimples are aligned with the inlet of the four inclined channels on the collar (refer to Figure 19). Push the vent component against the collar until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels.
The unitized design of the Secure Vent com-
ponents will engage and seal both the inner
and outer pipe without the need for sealant or
screws. If desired, a #6 x 1/2" screw may be used at the joint, but it is not required, as the
pipe will securely lock when twisted.
C. Attach vent components to each other.
Other vent sections may be added to the pre­viously installed section in accordance with the requirements of the vertical vent figures
and tables.
To add another vent component to a length of vent run, align the dimpled end over the inclined channel end of the previously installed section,
adjusting the radial alignment until the four
locking dimples are aligned with the inlets of the four incline channels of the previous section.
Push the vent component against the previous section until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. This seating
position is indicated by the alignment of the arrow and dimple as shown in Figure 19.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
D. Install firestop/spacer at ceiling.
When using Secure Vent, use SV8BF restop/ spacer at ceiling joists. If there is living space above the ceiling level, the restop/spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the restop/spacer must be installed on the top side of the joist.
Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner. When running vertical chimney
sections, remember to maintain 1" (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation. Attic insulation shield (H3908) may be used to obtain the required clearances indicated here. See installation accessories on Page
34. The gap between the vent pipe and a vertical firestop can be sealed with non­combustible caulking.
E. Support vertical vent run sections.
Note: Proper venting support is very im­portant. The weight of the vent must not be supported by the fireplace in any degree.
Support the vertical portion of the venting
system every 8 feet (2.4 m) above the replace
vent outlet.
One method of support is conventional
plumber’s tape (not provided). Secure the plumber’s tape to the framing members with
nails or screws.
Loop the plumber’s tape around the vent,
securing the ends of the tape to the framing. If desired, use #6 x 1/2" sheet metal screws to secure the support straps to the vent pipe. See Figure 20.
Blocking
Support Straps
(Plumber’s Tape)
Max.
8 ft (2.4 m)
0 in (0 mm) minimum clearance to spacers
Figure 20
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
C
D
Storm Collar
Vertical Termination System with Offset Vertical Venting (continued)
F. Change vent direction to horizontal/ inclined run.
At any transition to or from a horizontal/
inclined run, install the elbows (SV8E45, SV8E90; see Figure 21) in the same manner
as the straight vent sections.
The elbows feature a twist section to allow them to be routed about the center axis of their
initial collar section, to align with the required direction of the next vent run element. Twist
elbow sections in a clockwise direction only, to avoid the possibility of unlocking any pre­viously connected vent section (see Figures
19 and 21).
6"
(153 mm)
360° Swivel Joint (SV8E45) 45° Elbow
360° Swivel Joint (SV8E90) 90° Elbow
10"
(254 mm)
H. Frame roof opening.
Identify location for vent at the roof. Cut and/ or frame opening per Roof Framing Chart (see
Figure 22).
Framing Dimensions for Roof
Pitch C D
0/12
6/12
12/12
13 in
(330 mm)
13 in
(330 mm)
13 in
(330 mm)
13 in
(330 mm)
15-1/2 in
(394 mm)
20-1/2 in
(541 mm)
Figure 22: Roof Framing
K. Install vertical termination.
The final step involves installation of the verti­cal termination. Extend the vent sections to the
height as shown in “Vertical Vent Termination Clearances” on Page 6.
The vertical termination (Figure 24) installs in the same manner as other Secure Vent™ sections. Align the termination over the end of
the previously installed section, adjusting the
radial alignment until the four locking dimples of the termination are aligned with the inlets of the four incline channels of the last vent section. Push the termination down until it fully engages, then twist the termination clockwise, running the dimples down and along the incline chan­nels until they seat at the end of the channels.
Figure 21
G. Continue installation of horizontal/ inclined sections.
Continue with installation of the straight vent sections in horizontal/inclined run as de-
scribed in Step C. Install support straps every 3 ft (914 mm) along horizontal/inclined vent runs using conventional plumber’s tape (see Page 19, Figure 28).
NOTICE: It is important to install
horizontal runs on a steady, (i.e., no “dips”), slightly positive incline of approximately 1/4 inch rise-per-foot (20 millimeters rise-per-meter) horizontal, in a direction away from the fireplace. (Slightly smaller rise-per-foot run ratios
are acceptable.) Use a carpenter’s level to measure from a constant surface, and
adjust support straps as necessary.
Note: It is important to maintain the required clearances to combustibles: 1" (25 mm) at all sides for all vertical runs; and 4" (102 mm) at the top, 1" (25 mm) at sides, and 1" (25 mm) at the bottom for all horizontal/ inclined runs.
I. Install roof flashing.
Extend the vent sections through the roof structure. Install the roof flashing over the vent section and position such that the vent
column rises vertically (use carpenters level)
(Figure 23 ). Nail along perimeter to secure
ashing or adjust roong to overlap the ash­ing edges at top and sides only and trim where
necessary. Seal the top and both sides of the
flashing with waterproof caulking.
J. Install storm collar.
Install the storm collar, supplied with the
ashing, over the vent/ashing joint (see
Figure 23). Loosen the storm collar screw. Slide collar down until it meets the top of the
ashing. Tighten the adjusting screw. Apply non-combustible caulking or mastic around the circumference of the joint to provide a
water tight seal.
Storm
Flashing
Collar
Figure 24
If the vent system extends more than 5 ft (1.5
m) above the roof ashing, stabilizers may be
necessary.
Additional screws may be used at section joints for added stability.
Guide wires may be attached to the joint for ad­ditional support on multiple joint congurations.
Figure 23
17
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
VERTICAL TERMINATION SYSTEM FIGURES AND TABLES
Secure Vent™ rigid vent pipe and termination
components are shown in the figures. Note: Two 45-degree elbows may be used
in place of one 90-degree elbow. If using 45-degree elbows, follow the same rise-to­run ratios as shown for 90-degree elbows.
NOTICE:
Secure Vent Vertical Firestop/Spacer
(SV8BF) must be used anywhere vent pipe passes through a combustible floor or ceiling. Secure Vent Horizontal Firestop/Spacer (SV8HF4) must be used anywhere vent pipe passes through a combustible wall.
It is important to install horizontal runs
on a steady, (i.e., no “dips”), slightly positive incline of approximately 1/4 inch rise-per-foot (20 millimeters rise-per-meter) horizontal, in a direc­tion away from the fireplace. (Slightly
smaller rise-per-foot run ratios are acceptable.) Use a carpenter’s level to measure from a constant surface, and
adjust support straps as necessary.
Vertical Termination System with Straight Vertical Venting
Vertical Termination System with Offset Vertical Venting using Two 90-Degree Elbows
H
Vertical Firestop/Spacer (SV8BF)
V
1
H max. V + V1 min.
feet (meters) feet (meters)
10 (3.1) 2.5 (0.762) 15 (4.65) 3.5 (1.06)
*
20 (6.2) 4.5 (1.37)
V + V1 + H = 40 ft (12.4 m) max. V + V1 = 11 ft (3.3 m) min.
Example: A 20-ft horizontal vent run (H + H1) would require 4.5 ft min. vertical vent (V + V1).
Figure 26
*Install the provided Vent Restrictor (see Page 14).
V
18
Ceiling
Firestop/Spacer
(SV8BF)
*
*Install the provided Vent Restrictor (see Page 14).
Figure 25
60 ft (18.3 m) max.
6 ft (1.83 m) min.
Vertical Termination System with Offset Vertical Venting using Three 90-Degree Elbows
Vertical
1
Firestop/Spacer (SV8BF)
H
Horizontal Firestop/Spacer (SV8HF4)
V
1
H
H + H1 max. V + V1 min.
feet (meters) feet (meters)
10 (3.1) 2.5 (0.762) 15 (4.65) 3.5 (1.06)
*
20 (6.2) 4.5 (1.37)
H + H1 = 20 ft (6.2 m) max. V + V1 = 11 ft (3.3 m) min. V + V1 + H + H1 = 40 ft (12.4 m) max.
Example: A 20-ft horizontal vent run (H + H
)
1
would require 4.5 ft min. vertical vent (V + V1).
Figure 27
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
*Install the provided Vent Restrictor (see Page 14).
V
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Horizontal (Wall) Termination Systems
This section includes configurations for hori­zontal venting systems with horizonal termina-
tion (terminates through an outside wall) (see Figures 31–33 on Pages 21–22).
The tables on Pages 21 and 22 summarize each
system’s minimum and maximum vertical and horizontal length values.
Note: Building codes limit or prohibit horizontal termination in specific areas. For location guidelines, see Figure 5 on Page 7.
Secure Vent™ pipe applications are shown in
the illustrations. Secure Vent SV8 direct-vent system components are unitized concentric pipe components featuring positive twist-lock connection (see Figure 19 on Page 16). The appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the appliance collar to create the positive twist-lock connection.
A. Plan the vent run. Analyze the vent routing and determine the
types and quantities of sections required. See Page 15 for a list of available straight vent sections and their effective lengths (Table 7), as well as “VENT SECTION LENGTHS” charts. See Page 34 for a list of all approved venting components.
Plan the vent lengths so that a joint does not
occur at the intersection of ceiling or roof joists. Make allowances for elbows as indi­cated in Figure 21 on Page 17.
Maintain a minimum 1" (25 mm) clearance to combustibles on the vertical sections. Clearances for horizontal runs are 4" (102 mm) on top, 1" (25 mm) on sides, and 1" (25 mm) at the bottom.
B. Frame exterior wall opening.
Locate the center of the vent outlet on the ex ter ior wal l ac cor ding to the di men ­sions shown in Figure 12 on Page 11.
Cut and/or frame an opening 16" x 13" (406 mm x 330 mm) inside dimensions, with 10" above center and 7" below center.
C. Frame ceiling opening. If the vertical route is to penetrate a ceiling,
use plumb line to locate the center above the
appliance. Cut and/or frame an opening, 13" x
13" (330 mm x 330 mm) inside dimensions, about this center (see Figure 18 on Page 16).
D. Attach vent components to appliance.
To attach a vent component to the appliance collar, align the dimpled end over the collar,
adjusting the radial alignment until the four
locking dimples are aligned with the inlets of the four incline channels on the collar (see
Figure 19 on Page 16).
Horizontal Termination System with Horizontal/Inclined Run
Elbow
Support
Brackets
Ceiling
Horizontal / Inclined Run
Vertical Firestop/ Spacer (SV8BF)
Min. 2 ft (610 mm) Vertical
Section and One 90° Elbow
Support the vertical portion of the venting system every 8 ft (2.4 m) above the fireplace vent outlet.
Support Bracket Spacing every 3 ft (914 mm)
Fireplace
SV8L6/12/24/36/48 Vent Sections
Building
Support
Framing
SV8E90
Vertical
Rise
Figure 28
Push the vent component against the collar until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure
Vent components will engage and seal both the
inner and outer pipe elements with the same procedure. Sealant and securing screws are not required.
E. Attach vent components to each other.
Other vent sections may be added to the previ­ously installed section in accordance with the
requirements of the vent tables. To add another
vent component to a length of vent run, align the dimpled end of the component over the inclined channel end of the previously installed
section, adjusting the radial alignment until the
four locking dimples are aligned with the inlets of the four incline channels of the previous section. Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels. This
seating position is indicated by the alignment of the arrow and dimple as shown in Figure
19 on Page 16.
F. Install firestop/spacer at ceiling.
When using Secure Vent, use SV8BF vertical restop/spacer at ceiling joists. If there is living space above the ceiling level, the restop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the restop/spacer must be installed on the top side of the joist. Route the vent sections through the
framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1" (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
G. Support the vertical run sections. See Step E on Page 16. On the vertical run, support the venting system
every 8 ft (2.4 m) above the replace vent outlet with eld provided support straps (Plumber's tape). Attach the straps to the vent pipe and secure to the framing members with nails or
screws (see Figure 20 on Page 16).
H. Change vent direction.
At transition from or to a horizontal/inclined
run, install the SV8E45 and SV8E90 elbows in
the same manner as the straight vent sections.
The elbows feature a twist section to allow them to be routed about the center axis of their initial
collar section to align with the required direc­tion of the next vent run element. Twist elbow
sections in a clockwise direction only so as to avoid the possibility of unlocking any of the previously connected vent sections (see
Figure 19 on Page 16).
I. Continue installation of horizontal/inclined sections.
Continue with the installation of the straight vent
sections in horizontal/inclined run as described
in Step E. Install support straps every 3 feet
(1914 mm) along horizontal/inclined vent runs using conventional plumber’s tape.
See Figure 28.
NOTICE: It is important to install hori­zontal runs on a steady, (i.e., no “dips”), slightly positive incline of approximately 1/4 inch rise-per-foot (20 millimeters rise-per-meter) horizontal, in a direction away from the fireplace. (Slightly smaller
rise-per-foot run ratios are acceptable.)
Use a carpenter’s level to measure from a
constant surface, and adjust support straps
as necessary.
Termination (SV8HTS4)
Exterior Wall
Termination (SV8HTS4)
19
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
It is important to maintain the required clear­ances to combustibles: 1" (25 mm) at all sides for all vertical runs; and 4" (102 mm) at the top, 1" (25 mm) at sides, and 1" (25 mm) at the bottom for all horizontal/inclined runs.
Use a carpenter’s level to measure from a
constant surface and adjust the support straps
as necessary.
J. Assemble vent run to exterior wall. If not previously measured, locate the center of
the vent at the exterior wall. Prepare an open-
ing as described in Step B (previous page). Assemble the vent system to point where the
terminus of the last section is within 5 in. (127
mm) to 8-1/2 in. (216 mm) inboard of the
exterior surface to which the termination is to
be attached, see Figure 30 (below) and Table 8 (Page 21).
If the terminus of the last section is not within this distance, use the telescopic vent section (SV8LA) as the last vent section. For wall thick­nesses greater than that shown in Figure 30, refer to Table 8 on Page 21. This table lists the additional venting components needed (in
addition to the termination and adaptor) for a
particular range of wall thicknesses.
K. Attach termination adaptor. Attach the adaptor (adaptor - SV8RCH - provided
with the termination) to the vent section or telescoping vent section), or elbow as shown in
Figure 29 in the same manner as any SV vent component (refer to Step E, previous page).
L. Install Firestop/Spacer at exterior wall. When using the square termination, install
Secure Vent™ Firestop/Spacer (SV8HF4) over the opening at the exterior side of the framing,
long side up, with the 4-inch spacer clearance
at the top as shown in Figure 29, and nail into place.
M. Install the Square Termination (SV8HTS4). For the last step, from outside the exterior
wall, slide the collars of the termination onto the adaptor (the outer over the outer and the
inner inside the inner) until the termination
seats against the exterior wall surface to which
it will be attached. Orient the housing of the
termination with the arrow pointed upwards. Secure the termination to the exterior wall. The
horizontal termination must not be recessed into the exterior wall or siding by more than the 1-1/4" (32 mm) as shown in Figure 30.
IMPORTANT: The vent termination is hot while in operation and for a period of time following the use of the fireplace. Young children should be carefully supervised when they are in the same area as a hot termination.
16 in
(406mm)
6-1/2 in
(165mm)
Adaptor
SV8RCH
6- to 48-inch Vent Section or Telescopic Vent Section
Firestop/Spacer (SV8HF4) shown on exterior side of wall
13 in
(330mm)
1 in (25mm)
Note: Centerline of vent piping is NOT the same as centerline of framed opening.
Base of Appliance
Square Termination (SV8HTS4)
4 in (102 mm)
1 in (25.4 mm)
Figure 29: Installing Square Horizontal Termination
Min. 5 in (127 mm) wall thickness
Max. 8-1/2 in (216 mm)
Siding
Interior surface of finished wall
Maximum extent of vent run
sections relative to exterior
surface of framing
Last vent section
(If necessary, use
telescopic vent
section SV8LA.)
wall thickness
Exterior Surface of Siding
Exterior Surface of Framing
5 to 8-1/2 in (127−216 mm)
~
Square Termination SV8HTS4
Stucco
_________
Adaptor
SV8RCH
For wall thicknesses greater than
8-1/2 in (216 mm), see Table 8.
Horizontal Square Termination SV8HTS4
Venting Connection and Exterior Wall Recessing
Figure 30
Horizontal terminations have been designed to perform in a wide range of weather condi­tions. Our terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, do not place the termina­tion where water from eaves and adjoining rooflines may create a heavy flow of cascad­ing water onto the termination cap. If the cap must be placed where the possibility of cascading water exists, it is the responsibility of the builder to direct the water away from the termination cap by using gutters or other means.
Take care to carefully follow these installation instructions for the termination, including the use of silicone caulking where required.
~
Square Termination SV8HTS4
Max. 1-1/4 in recess of square termination into exterior finishing material
20
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
See Table 8 as an aid in venting component selection for a particular range of exterior wall thicknesses.
Required Venting Components (based on Exterior Wall Thickness)
when using Horizontal Square Termination Kit (SV8HTS4)
Exterior Wall Thickness Required Components
5 to 8-1/2 in (127 to 216 mm) • Termination Kit
(SV8HTS4)
HORIZONTAL TERMINATION SYSTEM FIGURES/TABLES
Note:
Secure Vent™ rigid vent pipe and termination components are shown
in the figures.
• Two 45-degree elbows may be used in place of one 90-degree elbow. If using 45-degree elbows, follow the same rise-to-run ratios as shown for 90-degree elbows.
9-3/4 to 14 in (248 to 356 mm) • Termination Kit (SV8HTS4)
• 6-in Vent Section (SV8L6)
6-3/4 to 15-1/4 in (171 to 387 mm) • Termination Kit
(SV8HTS4)
• Telescopic Section (SV8LA)
11-1/4 to 19-3/4 in (286 to 502 mm) • Termination Kit (SV8HTS4)
• Telescopic Section (SV8LA)
• 6-in. Vent Section (SV8L6)
Table 8
NOTICE:
Secure Vent Vertical Firestop/Spacer (SV8BF) must be used
anywhere vent pipe passes through a combustible floor or ceiling. Secure Vent Horizontal Firestop/Spacer (SV8HF4) must be used anywhere vent pipe passes through a combustible wall.
It is important to install horizontal runs on a steady, (i.e., no
“dips”), slightly positive incline of approximately 1/4 inch rise­per-foot (20 millimeters rise-per-meter) horizontal, in a direction away from the fireplace. (Slightly smaller rise-per-foot run ratios
are acceptable.) Use a carpenter’s level to measure from a constant surface, and adjust support straps as necessary.
HORIZONTAL TERMINATION SYSTEM WITH HORIZONTAL/INCLINED RUN USING ONE 90-DEGREE ELBOW
(elbow connection not directly at appliance)
Note: The provided vent restrictor is required in all venting systems. See Page 14 for settings.
Table C
H Maximum
V Minimum
feet (meters) feet (meters)
3.5 (1.07) 2.5 (0.762)
6.5 (1.98) 3.5 (1.07)
8.5 (2.6) 4.5 (1.37)
10.5 (3.2) 5.5 (1.68)
12.5 (3.8) 6.5 (1.98)
14.5 (4.4) 7.5 (2.3)
16.5 (5.0) 8.5 (2.6)
18.5 (5.6) 9.5 (2.9) 20 (6.0) 10 (3.0)
V + H = 40 ft (12.4 m) max. H = 20 ft (6.2 m) max.
Example: 20 feet of horizontal vent run (H) requires a minimum 10 feet of vertical vent (V).
Square
Termination
(SV8HTS4)
shown
H
Horizontal Firestop/Spacer (SV8HF4)
Vertical Firestop/Spacer (SV8BF)
V
See Table 8 as an aid in selecting venting components for a particular range of exterior wall thicknesses.
Figure 31
21
V
H
H
1
V
1
Horizontal
Firestop/Spacer
(SV8HF4)
Vertical
Firestop/Spacer
(SV8BF)
Horizontal
Firestop/Spacer
(SV8HF4)
Vertical
Firestop/Spacer
(SV8BF)
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
HORIZONTAL VENT FIGURES/TABLES (continued)
HORIZONTAL TERMINATION SYSTEM WITH HORIZONTAL/INCLINED RUN USING TWO 90-DEGREE ELBOWS
(Elbow connection not directly at appliance)
Note: The provided vent restrictor is required in all venting systems. See Page 14 for settings.
Horizontal Firestop/Spacer
(SV8HF4)
H
H
1
Horizontal Firestop/Spacer
(SV8HF4)
Example: If 20 feet of (H+H1) horizontal vent run is needed, then 10 feet minimum of (V) vertical vent will be required.
Vertical
Firestop/Spacer
(SV8BF)
See Table 8 on Page 21 as an aid in selecting venting components for a particular range of exterior wall thicknesses.
H
+ H
feet (meters) feet (meters)
3.5 (1.07) 2.5 (0.762)
6.5 (1.98) 3.5 (1.07)
V
8.5 (2.6) 4.5 (1.37)
10.5 (3.2) 5.5 (1.68)
12.5 (3.8) 6.5 (1.98)
14.5 (4.4) 7.5 (2.3)
16.5 (5.0) 8.5 (2.6)
18.5 (5.6) 9.5 (2.9) 20 (6.0) 10 (3.0)
V + H + H1 = 40 ft (12.4 m) max.
H + H
1
Table D
max.
1
= 20 ft (6.2 m) max.
V min.
Figure 32: Horizontal Termination with Two 90-Degree Elbows
HORIZONTAL TERMINATION SYSTEM WITH HORIZONTAL/INCLINED RUN USING THREE 90-DEGREE ELBOWS
(Elbow connection not directly at appliance)
Note: The provided vent restrictor is required in all venting systems. See Page 14 for settings.
H V + V
V = 2.5 ft (0.762 m) min.
V + V
Table E
+ H1 = 20 ft (6.2 m) max.
+ H + H1 = 40 ft (12.4 m) max.
1
= 11 ft (3.35 m) min.
1
22
See Table 8 on Page 21 as an aid in selecting venting components for a particular range of exterior wall thicknesses.
Figure 33: Horizontal Termination with Three 90-Degree Elbows
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
BL = Blue
G = Green
Step 4. FIELD WIRING
CAUTION: Label all wires prior to discon­nection when servicing controls. Wiring errors can cause improper and dangerous operation.
ATTENTION: Au moment de l'entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de cáblage peu-vent entraîner un fonc­tionnement inadéquat et dangereux.
Verify proper operation after servicing.
S'assurer que l'appareil fonctionne adé­quatement une fois l'entretien terminé.
CAUTION
Ground supply lead must be connect­ed to the wire attached to the green ground screw located on the outlet box. See Figures 34 and 35. Failure to do so will result in a potential safety hazard. The appliance must be elec­trically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70-latest edition.
Electronic Wiring
(See Figures 34 and 35)
Note: The electronic appliance must be connected to the main power supply.
1. Route a 3-wire, 120 Vac, 60 Hz, 1ph power
supply to the appliance junction box.
2. Remove the electrical inlet cover plate from
the side of the unit by removing the plate's
securing screws (see Figure 13, Page 12).
3. Remove the cover plate’s knockout and then
feed the power supply wire through the
knockout opening and into the unit junction box.
4. Connect the black power supply wire to the power outlet’s red pigtail lead and the white
Tab Intact
Green Ground Screw
Green
Neutral Side of Receptacle
White
Tab Intact
Hot Side of Receptacle
power supply wire to the common terminal of the outlet as shown in Figures 34 and 35.
5. Connect the ground supply wire to the pig­tail lead attached to outlet's green ground screw.
6. Appliance-mounted ON/OFF burner control
switch (rocker switch) is factory installed.
7. After wiring is complete, replace the cover plate.
Step 5. REMOVE GLASS DOOR ASSEMBLY (ON CONTROL SIDE)
If not already done, remove the glass door
assembly on the control side of the replace (see Page 29).
Ground - Green Neutral - White
120 VAC - Black
Junction Box
Black
J-BOX / RECEPTACLE
WIRING
120V, 60HZ, 1PH
Field Wired
Factory Wired
Junction Box
120V AC
W
B
Hi-Temp Sleeve
Cable Harness 102661-01
Wiring Color Code
B = Black
BR = Brown
Figure 35: Junction Box Wiring
(See Figure 35 for detailed drawing of junction box / receptacle wiring.)
ELECTRONIC WIRING DIAGRAM FOR GRAVITY VENT FIREPLACES
B
BR
Y
O
Proflame Valve
Electronic Modulation
G
VENT UNITS
Hot
Neutral
Ground
G
Wall Receiver
GY = Gray O= Orange
AC/DC
Power Adaptor
GY
R
B
BR
O
Y
W
G
BL
PU
PU = Purple W = White
R = Red Y = Yellow
O
G
Y
THIS CONNECTOR NOT
USED ON GRAVITY
Pilot Tube
DFC Wire Harness 102662-01
Y
G
O
W
W
G
BL
PU
W
Unit Mounted Rocker Switch OFF (o) = Intermittent Pilot Mode ON (-) = Standing Pilot Mode
Electronic Pilot Assembly
Pilot Ground Wire
Igniter Rod
R
Y
B
Spark Wire Cable
Pilot Sensor Cable
Hood
Proflame DFC Board
Flame Sensor
Figure 34: Electronic Wiring Diagram for Montebello Gravity Vent Fireplaces
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
23
Gas Valve
3/8" NPT x
Flare Fitting
3/8" Flex Tubing
3/8" Nipple
3/8" Union
3/8" Close Nipple
3/8" Shut-off Valve
1/2" x 3/8"
Reducer
Gas
Stub
1/2" x 3/8" Flare
Shut-off Valve
Gas Solid Line Connector
Gas Flex Line Connector
*Sediment Trap
3"
Min
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Step 6. CONNECT GAS LINE
All codes require a shut-off valve mounted in the supply line. The orientation of the shut-off valve should face the front. Figure 36 illustrates two methods for connecting the gas supply. A Sedi­ment Trap is recommended to prevent moisture
and debris in gas line from damaging the valve. The ex-line method is acceptable in the U.S.A
where local codes permit; however, Canadian
requirements vary depending on local codes. See Figure 36 for flex-line description. The
ex-line is rated for both natural and propane
gas. A manual shut off valve is also provided with the flex-line.
The gas control valve is located on the right side of the unit.
When using solid gas line connector, access the
valve by removing the glass door assembly on
the control side (see Page 29) and the access plate (see Figure 37).
The electronic control valve has a 3/8" (10 mm)
NPT thread gas supply inlet.
Bring the shutoff valve on the end of the ex-line
over to the hard pipe and tighten with wrenches
from above through the rebox opening.
Secure all joints tightly using appropriate tools and sealing compounds (ensure propane­resistant compounds are used in propane applications). Seal around gas line to prevent cold air leakage. Use sealants approved by local codes for the application.
Test All Connections for Gas Leaks (Factory and Field)
WARNING
Never use an open flame to check for leaks.
Turn on gas supply and test for gas leaks using a
gas leak test solution (also referred to as bubble leak solution).
Note: Using a soapy water solution is an effec-
tive leak test solution but it is not recommended, because the soap residue that is left on the pipes/
fittings can result in corrosion over time.
A. Light the appliance. See the lighting instruc-
tions label in the replace control compart­ment or Care and Operation Instructions.
B. Brush all joints and connections with the gas
leak test solution to check for leaks. If bubbles
are formed, or gas odor is detected, turn the receiver or remote control to the OFF position.
Either tighten or refasten the leaking connection; then retest as described above.
C. When the gas lines are tested and leak-free,
be sure to rinse off the leak testing solution.
D. Reinstall the access plate, making certain the
gasket has not been damaged.
Right Side
Modesty Panel
Access Panel
Main Gas
Shut-Off Valve
Gas Valve
ON/OFF Switch*
Control Compartment Access
*ON/OFF Switch - Switches from intermittent
ignition to a standing pilot (a standing pilot
stays lit when replace is off).
Figure 37
24
Figure 36
GAS CONNECTION
Note: The gas supply line must be installed in accor­dance with building codes by a qualified installer approved and/or licensed as required by the locality. In the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Step 7. INSTALL FIREBOX LINER PANELS
Install the ceramic or porcelain rebox liner
panels per the instructions provided in the kit
(ref. document P/N 506019-21).
NOTICE: Liner panels must be
installed before operating fireplace.
Step 8. VERIFY APPLIANCE OPERATION
Turn on the burner, then observe the individual tongues of ame on the burner.
Make sure all ports are open and producing ame evenly across the burner.
If any ports are blocked (or partially blocked),
clean out the ports.
With the gas line installed, run initial system
checkout before closing up the front of the
unit. Follow the pilot lighting instructions pro­vided in the Care and Operation Instructions.
Note: Lighting instructions also can be found on the lighting label tied to the bracket above the gas valve. To access the tag, reach into the right side opening (see Figure 37 on Page 24).
When first lighting the appliance, it will take a few minutes for the line to purge itself of air.
Once purging is complete, the pilot and burner
will light and operate as indicated on Page 30.
Subsequent lighting of the appliance will not
require such purging.
Inspect the pilot flame (remove logs, if neces-
sary, handling carefully).
Appliance Checkout
To light the burner, refer to the lighting in­structions in the Care and Operation Instruc-
tions or the lighting label tied to the bracket above the gas valve (behind the right panel).
Make sure the igniter lights the pilot. The
pilot flame should engulf the flame sensor, as shown in Figure 38.
PILOT ASSEMBLY
Proper Pilot Flame Appearance
Igniter Rod
Pilot Hood
Flame Sensor
Pilot Nozzels
Figure 38
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
25
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Step 9. INSTALL VOLCANIC STONE, GLOWING EMBERS, AND LOGS
9-1. Remove mesh pull screens, modesty panel, and glass door as-
sembly from one side of replace. See Page 29.
9-2. Locate materials (log set, bag of glowing embers, and bags of
volcanic stone).
Note: LOGS ARE FRAGILE! Handle with care to prevent breakage.
9-3. Install volcanic stone. Place some of the volcanic stone on the
rebox oor around the grate (the entire bag of volcanic stone will NOT be used).
Note: Do NOT place volcanic stone on burner.
9-4. Prepare and install glowing embers.
Note: This appliance is provided with enough glowing ember material for several applications. Do NOT use the entire contents of a new bag at one time.
a) Separate some of the glowing ember material into pieces about
the size and thickness of a dime (see Figure 39). Keep the
pieces fluffed up, not matted.
IMPORTANT! Ember pieces must be
as SMALL and THIN as a dime.
b) Distribute the dime-sized pieces over the surface of the burner,
in the areas shown in Figures 40 and 41.
Note: To prevent flame impingement and soot, do not use
more ember material than necessary.
c) For best glowing effect, replace ember material annually.
Note: Use only catalog number H8312 Glowing Embers with this fireplace.
Bag of Glowing Embers
Separate glowing ember material into THIN, square, dime-sized pieces.
Figure 39: Preparation of Glowing Ember Material
B
A
C
Control Side
Figure 40: Placement of Glowing Ember Pieces
WARNING
DO NOT attempt to install the logs until the appli­ance installation has been completed, the gas line connected and tested for leaks, and the initial burner operation has been checked out.
Logs get very hot and will remain hot up to one hour
after gas supply is turned off. Handle only when logs are cool. Turn off all electricity to the appliance before you install volcanic stone, embers and logs.
The size and position of the log set was engineered
to give the appliance a safe, reliable and attractive flame pattern. Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combustion, sooting, and poor flame quality.
This appliance is not designed to burn wood. Any
attempt to do so could cause irreparable damage to the appliance and prove hazardous to your safety.
If logs are not installed according to the log installa-
tion instructions, flame impingement and improper combustion could occur and result in soot and/or excessive production of carbon monoxide (CO), a
26
colorless, odorless, toxic gas.
Place embers in circled areas.
Control Side
(top view of burner shown)
Place glowing ember material in circled areas ONLY.
Do NOT place glowing ember material over main flame gas ports.
To prevent flame impingement and soot, do not use more ember
material than necessary.
Figure 41: Placement of Glowing Ember Pieces
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
9-5. Install logs (reference Figure 42 and Table 9 ).
Note: Logs are FRAGILE! Handle with care to prevent breakage.
Left Rear Log
E
Left Front Log
Center Rear Log
Center Log
C
Right Rear Log
D
A
Right Front Log
F
Figure 42: Top View of Logs
LOG SET
Item* Description Item* Description
A B C
Log, Center Log, Right Rear Log, Left Front
D E F
Log, Top Right Log, Top Left Log, Top Front
*Item letters correspond to photos.
FIREBOX ACCESSORIES/PARTS
Cat. No. Model Description
H8312 PGE Bag of Glowing Embers 80L42 FDVS Bag of Volcanic Stone
Table 9
9-6. Place rectangular notches on underside of Center Log A (Figure
44) over Boss #1 and Boss #4 (Figure 43).
B
Pin
A
Landing
Figure 44
9-7. Place notch on underside of Right Rear Log B (Figure 45 ) over
Boss #2 (Figure 43).
Place opposite end of Right Rear Log B (Figure 45) on Landing for
Log B (see Figure 43).
Landing for Log D
(see Step 9-9 and Figure 47 on next page)
B
Boss #1 Boss #2
Boss #3 Landing for Log C
Landing for Log B
[CONTROL SIDE]
Figure 43: Burner Bosses and Landings
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Boss #4
Figure 45
9-8. See Figures 43 and 46. Place notch on underside of Left Front
Log C over Boss #3.
Place opposite end of Left Front Log C on Landing for Log C (see
Figure 43).
C
Figure 46
27
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
9-9. Place groove on underside of Top Right Log D over the grate as
shown in Figure 47.
The middle section of Log D will rest on the landing on Log B
(labeled as “Landing for Log D” in Figure 45).
Groove Location
D
B
Figure 47
9-10. See Figure 48. Place hole on underside of Top Left Log E over pin
on Center Log A.
9-11. See Figure 49. Place groove on underside of Top Front Log F over
the grate finger. Rest the other end of the log on the Landing on Center Log A.
A
Landing
Groove Location
F
Figure 49
Figure 48
[DETAIL]
E
A
Pin
A
28
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Step 10. INSTALL GLASS DOORS, MESH PULL SCREENS, AND MODESTY PANEL
WARNING
HOT GLASS WILL CAUSE BURNS.
DO NOT TOUCH GLASS UNTIL COOLED.
Install only when fireplace is OFF and
COLD
.
•Fireplace surfaces get EXTREMELY HOT!
•The glass on the front of the fireplace
reaches EXTREMELY HIGH temperatures and can cause severe burns if touched. Even after the gas is turned off, fireplace surfaces remain extremely hot.
CAUTION
RISK OF PERSONAL INJURY
OR PROPERTY DAMAGE.
Do NOT abuse glass doors by striking or slamming shut
Never operate fireplace with glass door assemblies removed.
These direct-vent appliances are designed
to operate only when both glass door assemblies are installed. Generally, the glass door assemblies should not be
removed, except when access to compo-
nents within the rebox is required.
Securely tighten door latch screws when
reinstalling glass door assemblies to prevent doors from falling out.
Handle glass door assemblies with extreme care. Replace damaged glass door assemblies with approved replace­ment assemblies only.
The door assemblies on this replace
contain ceramic glass. Handle with care to prevent damage. If the door frame
or glass on either assembly becomes
damaged, replace the entire glass door
assembly with a manufacturer-approved replacement assembly only. Do not attempt to substitute any materials used on door assemblies or replace cracked or broken glass with any other materials.
Installing Glass Doors, Mesh Pull Screens, and Modesty Panel
(see Figure 50)
Note: These instructions do NOT apply to the Outer Glass Door provided in the Out­door Kit (for indoor/outdoor installations).
1) Install one of the glass doors, as follows: a) Retrieve the glass door. Visually inspect
the gasket on the back of the frame. Gasket surface must be clean, free of
irregularities, and seated firmly.
b) Position the door in front of the rebox
opening, with the top of the door held away from the fireplace (see Figure 50).
c) Lower the bottom of the door assembly
onto the bottom door track, engaging and centering it in the base channel, and then
gently swing the door up.
d) Using a #3 Phillips screwdriver, fasten the
door frame to the door latches with the
two (2) latch screws. The latches should
pull forward to engage the door frame.
Note: Securely tighten latch screws when
reinstalling glass door assembly.
2) Install the modesty panel on the top ange
of the glass door, as follows:
a) Grasp the modesty panel with both hands
(with the open hem facing down).
b) Engage it with the top flange of the glass
door frame by pushing it all the way down. Make sure the installed modesty
panel is firmly in place.
3) Install the mesh pull screens, as follows: a) Retrieve the rod and two mesh pull
screens. If necessary, attach screens to rod.
b) Slowly insert the right end of the rod into
the hole in the right rod bracket.
c) Insert the left end of the rod into the slot
in the left rod bracket.
Removing Glass Doors, Mesh Pull Screens, and Modesty Panel
(see Figure 50)
1) Remove the mesh pull screens, as follows: a) Lift up the left end of the rod to disengage
it from the slot in the left rod bracket.
b) Slowly remove the right end of the rod
from the hole in the right rod bracket.
c) Set aside the rod and mesh pull screens
for later reinstallation.
2) Remove the modesty panel from the top
ange of the glass door by rmly pulling up on it with both hands until it is disengaged.
3) Remove one of the glass doors, as follows: a) See Figure 50. While holding the top of
the glass door frame in place, use a #3 Phillips screwdriver to remove the two
(2) screws securing the door frame to the two (2) door latches.
b) Carefully tilt the top of the glass door
frame away from the unit (as shown in
Figure 50), and then lift the door as­sembly up and out of the lower track.
c) Carefully place the glass door assembly
on a padded surface in a safe location to prevent damage.
Top Flange on Glass door assembly
Figure 50
Glass Door Latch (2)
Screws
Only doors certified with the appliance shall be used.
Seules des portes certifiées pour cet appareil doivent être utilisées.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
29
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Step 11. BURNER ADJUSTMENTS
Flame Appearance and Sooting
Proper ame appearance is a ame that is blue at the base and becomes yellowish-orange in the body of the ame. When the appliance is rst lit, the entire ame may be blue and will
gradually turn yellowish-orange during the first 30 minutes of operation. After 30 minutes of
operation, if the ame is blue, or if the ame is orange with evidence of sooting (black tip), the air shutter opening may need to be adjusted.
If the air shutter opening is closed too far, sooting may develop. Sooting is indicated
by black puffs developing at the tips of very long orange ames. Sooting results in black
deposits forming on the logs, appliance inside
surfaces and on exterior surfaces adjacent to
the vent termination.
Sooting is caused by incomplete combustion in the ames and lack of combustion air enter-
ing the air shutter opening. To achieve a warm
yellowish-orange ame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, rst check
the log set positioning to ensure that the flames are not impinging on any of the logs. If the log set is properly positioned and a sooting condition still exists, then the air
shutter opening should be increased.
• The more offsets in the vent system, the larger the air shutter opening will need to be.
• An appliance operated with the air shutter
opened too far, may have flames that appear
blue and transparent. These weak, blue and
transparent flames are termed anemic.
• Propane models may exhibit ames which
candle or appear stringy. If this is present
and persists, adjust the air shutter to a more
OPEN position, then operate the appliance for a few more minutes to ensure that the flame normalizes and the flames do not appear sooty.
The following chart is provided to aid you in
achieving the correct air shutter adjustment
for your installation.
Burner Air Shutter Adjustment
1. Light the appliance (follow lighting proce-
Procedure
WARNING
HOT GLASS WILL CAUSE BURNS.
DO NOT TOUCH GLASS UNTIL COOLED.
•Fireplace surfaces get EXTREMELY HOT!
•The glass on the front of the fireplace
reaches EXTREMELY HIGH temperatures and can cause severe burns if touched. Even after the gas is turned off, fireplace surfaces remain extremely hot.
CAUTION
RISK OF PERSONAL INJURY
OR PROPERTY DAMAGE.
Air shutter adjustment should only be performed by a qualified professional service technician.
Soot will be produced if the air shutter is closed too much. Any damage due to carboning resulting from improperly setting the air shutter is not covered under the warranty.
Volcanic Stone
Figure 51: Burner Flame Appearance — Control Side
2. Allow the burner to operate for at least 30
3. Adjust the air shutter using the lever on the
A minimum shutter setting is designed into
Note: See Figures 51 and 52 for proper burner flame appearance.
Adjustment Lever
dure in Care and Operation Instructions or
on lighting label in control compartment).
minutes while continuously observing the
flame to ensure that the proper flame ap-
pearance has been achieved (see Figures 51 and 52).
lower right side of the rebox (Figure 51).
For more OPEN air shutter, slide lever
to the RIGHT.
For more CLOSED air shutter, slide lever to the LEFT.
the venturi by four 1/16"-inch tabs.
• If the ame appears weak or sooty (as
described on the previous page), adjust
the air shutter until proper flame appear­ance is achieved.
• If ame stays lowered blue, incremen-
tally adjust the air shutter to a more
CLOSED position until proper flame appearance is achieved.
Air Shutter
30
Air Shutter Adjustment Guidelines:
Amount of
Primary Air
If air shutter is closed too far
If air shutter is open too far
Flame
Color
Flame will be orange
Flame will be blue
Air Shutter
Adjustment
Air shutter gap should be increased
Air shutter gap should be decreased
Volcanic Stone
Figure 52: Burner Flame Appearance — Opposite Control Side
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Min. 4 in*
Min. 4 in*
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
FINISHING REQUIREMENTS
Wall Details - INDOOR SIDE(S)
Complete the finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thickness of the finished wall (Figure 53).
INTERIOR WALL FINISHING EXTERIOR WALL FINISHING
(102 mm)
Wall Stud
Combustible
Finished Wall
Materials
Header
Combustible
materials are
allowed on face
of appliance
above this point
~
Min. 1 in*
(25 mm)
2 ft Vertical
Vent and 90° Elbow
IMPORTANT!
Min. clearance above any
horizontal vent component
is
4 in (102 mm).
Wall Details - OUTDOOR SIDE
Complete finished exterior wall per the instructions provided
in the Outdoor Installation Kit and the instructions provided
here. To install the appliance facing flush with the finished exterior wall, position framework to accommodate the thickness of the exterior finished wall (Figure 54).
(102 mm)
Wall Stud
~
Combustible Sheathing
Min. 1 in*
(25 mm)
2 ft Vertical
Vent and
90° Elbow
Header
Non-combustible sheathing required below this point.
Non-combustible
*Insulation is
NOT ALLOWED in clearance zones around vent components. Keep this area free from combustible materials.
Figure 53
Top of Appliance
Spacers
Top of Door Frame
FIREPLACE (side view)
Top of
Appliance
Top of Door Frame
Figure 54
See Page 4 for Cold Climate Insulation
and Page 9 for Clearances.
Spacers
FIREPLACE (side view)
Extend housewrap (building paper) to this point.
Note: Non-combustible sheathing and housewrap (building paper) should extend to U-channels on sides and bottom.
*Insulation is
NOT ALLOWED in clearance zones around vent components. Keep this area free from combustible materials.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
31
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Combustible Sheathing
Non-Combustible Board
A
B B
Non-Combustible Board
Combustible Sheathing
C
Non-Combustible Board
Sheathing Requirements
A B C*
12” (305 mm) 7” (178 mm) 6” (152 mm)
*Dimension “C” is clearance required from fireplace base to surface (e.g., deck, patio, lanai) as a moisture barrier (not a combustible clearance) on outdoor side only.
Overhang
B
A
Siding
A
A
Siding
Siding
Trim
C*
Exterior Minimum Clearances
Material A B C*
Vinyl 12” (305 mm) 35-1/2” (902 mm) 6” (305 mm)
Non-Vinyl 7” (178 mm) 35-1/2” (902 mm) 6” (305 mm)
*Dimension “C” is clearance required from fireplace base to surface (e.g., deck, patio, lanai) as a moisture barrier (not a combustible clearance) on outdoor side only.
Figure 55: Sheathing
Figure 56: Exterior Clearances
32
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Step 12. ATTACHING SAFETY-IN-OPERATION WARNINGS It is the installer’s responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this appliance.
ATTACHING SAFETY-IN-OPERATION WARNINGS
It is required that the set of safety instruction labels that have been furnished with the replace be afxed
to the operation and control points of the fireplace. A
safety instruction label must be afxed to the receiver
wall switch plate where the fireplace is turned on and off (See Figure A) and on the remote control handheld transmitter (See Figure B). To properly complete the installation of this fireplace, locate the
multi-lingual adhesive labels provided with the Care
and Operation Instructions and proceed as follows:
1. Locate the wall receiver that controls the fire­place (verify the switch operates the fireplace
by turning it on and off). Clean the wall receiver
plate thoroughly to remove any dust and oils.
Afx the label to the surface of the plate of the
wall receiver that controls the fireplace (Figure A). Choose the language primarily spoken in the
home. If unknown, affix the English language
label.
2. Locate the remote control transmitter and clean it thoroughly to remove any dust and
oils. Afx the label to the surface of handheld
transmitter (Figure B). Choose the language primarily spoken in the home. If unknown, affix
the English language label.
3. If you are unable to locate the labels, please
call Lennox Hearth Products or your nearest Lennox Hearth Products dealer to receive ad-
ditional safety instruction labels free of charge. Cat. No. H8024 Replacement Label Kit
LENNOX HEARTH PRODUCTS 1-800-9-LENNOX
Note: English is red text on clear label. French and Spanish are white text on black label.
APPOSITION DES MISES EN GARDE RELATIVES À LA SÉCURITÉ D’UTILISATION
Il est impératif que le jeu d’étiquettes de sécurité qui ont été fournies avec le foyer soient collées à côté des dispositifs de contrôle du foyer. Une étiquette de sécurité doit être collée sur la plaque du récepteur mural contrôlant l’allumage du
foyer (voir Figure A) et sur le boîtier de la télécommande (Figure B). Pour achever l’installation correcte de ce
foyer, procédez comme suit avec les étiquettes adhésives en langues étrangères fournies avec les instructions d’utilisation et d’entretien :
1. Repérez le récepteur mural qui contrôle le foyer (vérifiez que l’interrupteur contrôle le fonction ­nement du foyer en le faisant basculer de Marche à Arrêt, et vice-versa). Nettoyez soigneusement
la plaque du récepteur mural pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur
la surface de la plaque du récepteur mural qui contrôle
le foyer (Figure A). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
2. Repérez la télécommande et nettoyez-la soigneuse­ment pour éliminer la poussière et les traces
de graisse ou d’huile. Collez l’étiquette sur le boîtier
de la télécommande (Figure B). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez
appeler Lennox Hearth Products ou votre distribu-
teur Lennox Hearth Products local pour recevoir gratuitement des étiquettes supplémentaires.
Étiquettes de remplacement, n° cat. H8024
LENNOX HEARTH PRODUCTS 1-800-9-LENNOX
Remarque : Le texte anglais est rouge sur un support transparent. Le texte français et espagnol est blanc sur un support noir.
COLOCACIÓN DE ADVERTENCIAS DE SEGURIDAD EN OPERACIÓN
Se requiere que el juego de etiquetas de instrucciones de seguridad que se incluyeron con la chimenea se coloque en los puntos de operación y control de la
misma. Se debe colocar una etiqueta de instrucciones
de seguridad en la placa del interruptor de pared del receptor desde el cual se enciende y se apaga la chimenea (ver la Figura A) y en el transmisor de control remoto (ver la Figura B). Para completar correctamente la instalación de esta chimenea, encuentre las etiquetas adhesivas multilingües incluidas con las instrucciones de cuidado y operación y haga lo siguiente:
1. Identifique el receptor de pared que controla la chimenea (verifique que el interruptor opera la
chimenea encendiéndola y apagándola). Limpie bien la placa del receptor de pared para quitar el
polvo y aceite. Pegue la etiqueta en la superficie de la placa del receptor de pared que controla la chimenea (Figura A). Seleccione el idioma que
más se habla en la casa. Si no sabe cuál es, use
la etiqueta en inglés.
2. Identifique el transmisor de control remoto y
límpielo bien para quitar el polvo y aceite. Pegue
la etiqueta en la superficie del transmisor (Figura B). Seleccione el idioma que más se habla en la
casa. Si no sabe cuál es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas, sírvase
llamar a Lennox Hearth Products o al distribuidor
de Lennox Hearth Products más cercano para
recibir etiquetas de instrucciones de seguridad
adicionales gratuitas.
Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS 1-800-9-LENNOX
Nota: La etiqueta en inglés es transparente con texto rojo. Las etiquetas en francés y español son negras con texto blanco.
SAFETY LABEL
DIAGRAMS
DIAGRAMMES DES ÉTIQUETTES
DE SÉCURITÉ
On
Remote
Off
PRG
Figure A Figure B
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
DIAGRAMAS DE ETIQUETAS
DE SEGURIDAD
33
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
typ.
INSTALLATION ACCESSORIES
Listed Secure Vent™ Components
Cat.
No.
Model
No.
H8323 SV8HTS4 Horizontal Square
Termination with Firestop/Spacer (H8322) and Adaptor (H2267)
H2265 SV8VTR Vertical Termination
H2250 SV8L6 6 inch (152 mm)
Vent Section
H2251 SV8L12 12 inch (305 mm)
Vent Section
H2252 SV8L24 24 inch (610 mm)
Vent Section
H2253 SV8L36 36 inch (914 mm)
Vent Section
H2254 SV8L48 48 inch (1219 mm)
Vent Section H2255 SV8LA Telescopic Section H2256 SV8E45 45 Degree Elbow
Description
H2262 SV8SU Support Strap
H2263 SV8SP Support Plate
H3908 SV8ARSA Attic Insulation Shield
(adjustable 12” to 22”)
Open Top Shroud CTSO-46 for double terminations
C
2a
D
2b
A
Shroud: Open Top, Chase Top -
1 typ.
2a
2b
2b
2a
2a
B
Open Top Shrouds CTSO-33 and CTSO-44 for single terminations
C
E
D
A
Inches (millimeters)
Cat. No. Model A B C D *E
H1985 CTSO-33
H1987
CTSO-44
H1986 CTSO-46
37-5/8
(955)
48-5/8 (1235)
48-5/8 (1235)
37-5/8
(955)
48-5/8 (1235)
73 1/4
(1860)
(Open Top Shroud Termination Kit Instructions P/N 750193M)
7-1/2 (191)
7-1/2 (191)
7-1/2 (191)
24-1/2
24-1/2
24-1/2
typ.
2
B
(622)3 (76)
(622)3(76)
(622)3(76)
1
E
34
H2257 SV8E90 90 Degree Elbow
The following flashings come packaged with a storm collar
H3236 SV8F Flat Roof Flashing
H2258 SV8FA Adjustable Flashing,
1/12 to 7/12 H2259 SV8FB Adjustable Flashing,
7/12 to 12/12 H3237 SV8SC6 Storm Collar
(pkg of 6)
H8322 SV8HF4 Firestop/Spacer,
Horizontal
(4-1-1 spacing) H2261 SV8BF Firestop/Spacer,
Vertical
(1-1-1 spacing)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Arch Top Shroud CTSA-33
A
B
C
Shroud: Arch Top, Chase Top -
D
Inches (millimeters)
Cat. No. Model A B C D
H1988 CTSA-33
34
(864)
5
(127)
(Arch Top Shroud Kit Instructions P/N 750194M)
34
(864)
(864)
Outdoor Kits
H7940 LSM40STODK Outdoor Kit with
Light-tint Glass
H8061 LSM40ST-ODKT Outdoor Kit with
Dark-tint Glass
(Outdoor Kit Instructions P/N 506019-20)
34
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
GAS CONVERSION KITS
Gas conversion kits are available to adapt your
appliance from the use of one type of gas to another. These kits contain all the necessary components needed to complete the task, in-
cluding labeling that must be afxed to ensure
safe operation.
Kit part numbers are listed at right.
Refer to the instructions provided with the conversion kit when performing any gas conversion.
Gas Conversion Kits
Kit Model No. Kit Cat. No. Description
GCK-NP-LSM40ST H7951 Natural Gas to Liquid Propane Conversion Kit GCK-PN-LSM40ST H7952 Liquid Propane to Natural Gas Conversion Kit
Table 10
(Gas Conversion Kit Instructions P/N 506019-53)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
35
LENNOX HEARTH PRODUCTS • MONTEBELLO® SEE-THROUGH DIRECT-VENT GAS FIREPLACES (LSM40ST-N / LSM40ST-P) • INSTALLATION INSTRUCTIONS
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, and prices, and also to discontinue colors, styles, and products.
Consult your local distributor for replace code information.
Printed in U.S.A. © 2011 Lennox Hearth Products
P/N 506023-12 Rev. B 05/2011
36
1508ElmHillPike,Suite108•Nashville,TN37210
Loading...