Lennox Hearth LSM45EN-PV, LSM40EN-PV User Manual

INSTALLATION INSTRUCTIONS
AVERTISSEMENT : Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incindie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
WARNING /AVERTISSEMENT/AVISO
• HOT GLASS WILL CAUSE BURNS.
• DO NOT TOUCH GLASS UNTIL COOLED.
• NEVER ALLOW CHILDREN TO TOUCH GLASS.
• UNE SURFACE VITRÉE CHAUDE PEUT CAUSER DES BRÛLURES.
• LAISSER REFROIDIR LA SURFACE VITRÉE AVANT D'Y TOUCHER.
• NE PERMETTEZ JAMAIS À UN ENFANT DE TOUCHER LA SURFACE VITRÉE.
• EL VIDRIO CALIENTE CAUSARÁ QUEMADURAS.
• USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE.
• LOS NIÑOS DEBEN NUNCA TOCAR EL VIDRIO.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
Montebello® Power Vent Direct-Vent Gas Fireplaces
P/N 506023-09 Rev. C 06/2011
This manual is one of a set of two supporting this product. Refer to P/N
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 506223-29.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.
506025-02
for Care and Operation Instructions.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l'appareil. CONSOMMATEUR : Conservez cette notice pour consultation ultérieure.
MODELS
LSM40EN-PV LSM45EN-PV
Portland
US
OTL Report No. 116-F-22-5
ELECTRONIC:
TM
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
TABLE OF CONTENTS
Packaging .........................................Page 2
Introduction ......................................Page 2
General Information ..........................Page 2
Massachusetts and New York
Requirements ................................ Page 4
Cold Climate Insulation .....................Page 5
Manufactured Home Requirements ..Page 5
Location ............................................Page 5
Vent Termination Clearances ............Page 6
Minimum Clearances to Combustibles Page 8
Detailed Installation Steps .................Page 9
Typical Installation Sequence ...........Page 9
Step 1. Framing ...............................Page 9
Fireplace and Framing Specifications Page 10
Step 2. Routing Gas Line ................Page 11
Proper Sizing of Gas Line .................. Page 11
Step 3. Install the Vent System .......Page 12
General Vent Information ..................Page 12
Power Vent Components...................Page 12
Vent Section Length Chart ................Page 13
Vertical (Offset) Installation...............Page 13
Vent Instructions A through G...........Page 14
Vent Figures ......................................Page 15
Horizontal Termination System .........Page 16
Installing Power Vent Termination ....Page 16
Step 4. Field Wiring .........................Page 18
Step 5. Removing Glass Door
Frame Assembly ...........................Page 20
Step 6. Connecting Gas Line ...........Page 21
Step 7 Install Firebox Liner ............Page 21
Step 8. Verifying Appliance
Operation ......................................Page 21
Step 9. Installing Logs ...................Page 22
Step 10. Installing Glass Door ..........Page 24
Step 11. Burner Adjustments ............Page 24
Finishing Requirements ....................Page 26
Step 12. Attaching Safety-in-
Operation Warnings .................
Installation Accessories ....................Page 28
Gas Conversion Kits .................. Page 29
Please read and understand these instructions before beginning your
installation.
Page 27
PACKAGING
The assembled vented gas replace is pack­aged with:
BOX 1 - Fireplace:
Envelope (in rebox) containing Care and
Operation Instructions, Installation Instruc- tions, safety-in-operation warning labels,
and warranty.
Bag of glowing embers and volcanic stone
Pull screen
Door modesty shield
Adaptor with probe assembly
BOX 2 - Power Vent Components:
(1) power vent termination
(1) termination adaptor
(1) horizontal restop assembly
(1) vacuum hose
(1) 11/32" hose clamp
(1) strain relief
(1) bushing
(4) insulated 1/4" male terminals
(2) #10 ring terminals
REQUIRED (order separately):
One of the following brick liner kits: a. Brick Liner Kit, Rustic b. Brick Liner Kit, Herringbone c. Brick Liner Kit, Old Cottage d. Brick Liner Kit, Black. e. Brick Liner Kit, Red Rustic f. Brick Liner Kit, Red Herringbone
• One of the following log sets:
a. Birch Log set b. Oak Log set
INTRODUCTION
These Electronic appliances are designed to operate on natural gas or propane and have an electronic intermittent pilot ignition system.
External 120 Volt AC electrical power is is
required to operate these units.
These vented gas fireplaces are sealed com-
bustion gas replaces designed for residential
applications.
Use Only These Approved Vent Components
- These fireplaces are designed, tested and listed for operation and installation with, the following (4-1/2" inner and 7-1/2" outer) vent components only:
Secure Vent™ Direct-Vent System Compo-
nents manufactured by Security Chimneys
International.
These approved vent system components are
labeled for identication. Do NOT use any other
manufacturer’s vent components with these appliances.
GENERAL INFORMATION
WARNING
Young children should be care­fully supervised when they are in the same room as the appli­ance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la sur­face chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habi­tent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécu­rité; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Les enfants et les adultes devraient être infor­més des dangers que posent les températures de surface élevées et se tenir à distance afin d’éviter des brûlures ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
2
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
WARNING
Improper installation, adjust­ment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
WARNING
Failure to comply with these installation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appli­ance and/or its operating controls is dangerous.
WARNING
Clothing or other flammable material should not be placed on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
WARNING
Any safety screen or guard removed for servicing the appli­ance must be replaced prior to operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
WARNING
Improper installation or use of this appliance can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
Note: Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
Remarque : L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspec­tion par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les comparti­ments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres.
Do not use these appliances if any part has been under water. Immediately call a qualified, professional service technician to inspect the appliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas utiliser cet appareil s’il a été plongé, même partiellement, dans l’eau. Ap­peler un technicien qualifié pour inspecter l’appareil et remplacer toute partie du système de commande et toute commande qui a été plongée dans l’eau.
Only trim kit(s) supplied by the manufacturer shall be used in the installation of this ap­pliance.
Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
These appliances comply with National Safety
Standards and are tested and listed by OMNI­Test Laboratories, Inc. (Report No. 116-F-22-5) to ANSI Z21.50b in the USA, as vented gas
fireplaces.
These electronic appliances are listed by OMNI-Test Laboratories for installation in bedrooms and mobile homes.
Misc. Codes / Standards -
The Installation must conform to local codes.
In the absence of local codes, installation must
comply with the current National Fuel Gas Code, ANSI Z223.1.
The appliance, when installed, must be elec­trically grounded in accordance with local
codes or, in the absence of local codes, with
the National Electrical Code, ANSI/NFPA 70 ­latest edition.
Provide adequate clearances around air open-
ings and adequate accessibility clearance for service and proper operation. Never obstruct
the front openings of the appliance.
These appliances are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the performance of this system and may be dangerous.
These electronic appliances are manually controlled and feature an electronic intermittent
pilot ignition system. External electrical power
is required to operate these units.
These electronic models come standard with a manually-modulated gas valve; flame appear-
ance and heat output can be controlled at the gas valve. The BTU Input for these appliances
is shown in Table 1.
Input (BTU/HR) - All Models
Model No. Input (BTU/Hr)
Natural Gas
LSM40EN-PV 32,500 to 42,000 LSM45EN-PV 32,500 to 42,000
Propane Gas (if field converted)
LSM40EN-PV field-
converted to propane
LSM45EN-PV field-
converted to propane
Table 1
30,000 to 40,500
30,000 to 40,500
3
HI
LO
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Gas Pressure - All Models
Tables 2 and 3 show the appliances' inlet and manifold gas pressure requirements:
Inlet Gas Supply Pressure
(all models)
Fuel # Minimum Maximum
Natural Gas
Propane
5.5" WC
(1.37 kPa)
11.0" WC
(2.74 kPa)
10.5" WC
(2.61 kPa)
13.0" WC
(3.23 kPa)
Table 2
Manifold Gas Supply Pressure
(all models)
Fuel # Low High
Natural
Gas
Propane
(Lo) 2.2" WC
(.55 kPa)
(Lo) 6.3" WC
(1.57 kPa)
(Hi) 3.5" WC
(.87 kPa)
(Hi) 10.0" WC
(2.49 kPa)
Table 3
Test gauge connections are provided on the front of the gas control valve (identified IN for
the inlet and OUT for the manifold side). Refer
to Figure 1.
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step down regulators to reduce the pressure to safe levels.
These appliances must be isolated from the gas supply piping system (by closing their individual manual shut-off valve) during any
pressure testing of the gas supply piping system at test pressures equal to or less
than 1/2 psig (3.5 kPa).
These appliances and their individual shut-off
valves must be disconnected from the gas
supply piping system during any pressure testing of that system at pressures greater
than 1/2 psig (3.5 kPa).
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
PURGE CYCLE This is a power vented fireplace that requires household electrical power to operate. It will not operate during a power failure. When the fireplace is turned off, the exhaust blower will continue to operate for approximately one to two minutes after shutdown to expel the exhaust gases from the venting system.
Orifice Sizes - Sea Level To High Altitude (All Models)
These appliances are tested and approved for installation at elevations of 0-2000 feet (0-610
meters) above sea level, using the standard burner orice sizes (marked with an "*" in Table
4). For elevations above 2000 feet, contact your
gas supplier or qualified service technician.
Deration - At higher elevations, the amount
of BTU fuel value delivered must be reduced by either:
• Using gas that has been derated by the gas
company.
• Changing the burner orice to a smaller size as regulated by the local authorities having jurisdiction and by the (USA) National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition or, in Canada, the CAN/CSA-B149.1
codes - latest edition.
Install the appliance according to the regulations
of the local authorities having jurisdiction and,
in the USA, the National Fuel Gas Code NFPA
54 / ANSI Z223.1 - latest edition.
NOTE: Flame appearance will diminish 4% per thousand feet.
Burner Orifice Size
Elevation 0-2000 ft. (0-610m)
Model Natural Gas Propane Gas
.073" (#49)
H7936
.073" (#49)
H7936
LSM40-PV
LSM45-PV
Table 4
.125" (1/8") *
H7924
.125" (1/8") *
H7924
* Standard size installed at factory
•Part/Cat.Number
Gas Valve Diagrams
See Figure 1 for gas valve diagram.
Gas Supply Inlet
Inlet Pressure Gauge Port
Manifold Pressure Gauge Port
Gas Outlet to Burner
Hi / Lo Variable Flame Height Adjustment
Pilot Adjustment Screw
Figure 1 - SIT Electronic Gas Valve
REQUIREMENTS FOR THE COMMON­WEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with Massachusetts Rules and Regulations 248 C.M.R.
• Installation and repair must be done by a plumber or gas tter licensed in the Com­monwealth of Massachusetts.
• The exible gas line connector used shall not exceed 36 inches (92 centimeters) in
length.
• The individual manual shut-off must be a
T-handle type valve.
Massachusetts Horizontal Vent Requirements In the Commonwealth of Massachusetts, hori-
zontal terminations installed less than seven (7) feet above the finished grade must comply with the following additional requirements:
• A hard wired carbon monoxide detector with an alarm and battery back-up must be
installed on the floor level where the gas
replace is installed. The carbon monoxide detector must comply with NFPA 720, be ANSI/UL 2034 listed and be ISA certied.
• A metal or plastic identication plate must be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade and be directly in line with
the horizontal termination. The sign must
read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
NEW YORK CITY, NEW YORK (MEA)
4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Installation of these fireplaces are approved
for installation in New York City in the US state of New York.
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks
around your appliance with noncombustible
material and wherever cold air could enter the room. It is especially important to insulate
outside chase cavity between studs and under oor on which appliance rests, if oor is above
ground level. Gas line holes and other open-
ings should be caulked or stuffed with unfaced berglass insulation.
If the replace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can be placed underneath
to prevent cold transfer to the fireplace and into the room. It also helps to sheetrock inside
surfaces and tape for maximum air tightness
and caulk firestops.
MANUFACTURED HOME REQUIREMENTS
This appliance may be installed in an aftermarket
permanently located, manufactured home and
must be installed in accordance with the manu­facturer's instructions and the Manufactured
Home Construction and Safety Standard, Title
24 CFR, Part 3280, in the United States.
Cet appareil peut être installé cómme du matéri-
el d'origine dans une maison préfabriquée (É.U. seulement) ou mobile et doit être installé selon les instructions du fabricant et conformément à la norme Manufactured Home Constructions and Safety, Title 24 CFR, Part 3200 aux Unis.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is
not convertible for use with other gases, unless
a certified kit is used.
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil ne peut être converti à d'autres gaz, sauf si une trousse de conversion est utilisée.
CAUTION: Ensure that the cross mem­bers are not cut or weakened during installation. The structural integrity of the manufactured home floor, wall, and ceiling / roof must be maintained.
CAUTION: This appliance must be grounded to the chassis of the manu­factured home in accordance with local codes or in the absence of local codes, with the National Electrical Code ANSI / NFPA 70 - latest edition.
Cross Corner
Application
Room Divider
Application
Recessed
Application
Island
Application
Fireplace
Flat
Application
Application
Flat on Wall
Horizontal Termination
Figure 2 - Typical Installation
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to
the exterior and access to the fuel supply are
also important.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies (Figure 2).
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures (Figure 2).
The location should also be free of electrical, plumbing or other heating/air conditioning
ducting.
Note: When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit.
Drywall
Top of Fireplace
Opening
Non-Combustible
Be aware that this is a heat producing ap­pliance. Objects placed above the unit are exposed to elevated temperatures.
Do not insulate the space between the appli­ance and the area above it.
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located
on or near conventional construction materials.
However, if installed on combustible materials,
such as carpeting, vinyl tile, etc., a metal or
wood barrier covering the entire bottom surface must be used.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
5
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
VENT TERMINATION CLEARANCES
These instructions should be used as a guide­line and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA.
Horizontal Vent Termination Clearances
The horizontal vent termination must have
a minimum of 3" (76 mm) clearance to any overhead combustible projection of 2-1/2" (64 mm) or less (see Figure 3). For projections exceeding 2-1/2" (64 mm), see Figure 4. For
additional vent location restrictions refer to Figure 4 on Page 7.
Combustible Projection
2-1/2 inches or less in length
Greater than 2-1/2 inches in length
Ventilated or
Unventilated Soffit
See Figure 19 on Page 17 for the re­cess allowances, into exterior walls, of the power vent terminations.
Combustible Projection
24"
(610mm)
Side Elevation View
Power Vent Termination
Combustible
Figure 3 - Horizontal Vent Termination Clearances
3"
(76mm)
18"
(457mm)
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS
NOTE: Local Codes Or Regulations May Require Different Clearances.
NOTE: Location Of The Vent Termination Must Not Interfere With Access To The Electrical Service.
H
3 ft.
X
l
A
3 ft.
M
I
V
K
Exterior Wall
Horizontal
Termination
B
V
L
= Air Supply Inlet
X
* See Item D in the Text Below.
24"
*18”
Inside Corner
Center Line
of Termination
36"
18
DETAIL D
F
V
Ventilated Soffit
V
Fixed
Closed
Window
V
C
A
= Vent Terminal
V
Inside
Corner Detail
G
V
A
= 9" in U.S.
l
A
B
C
C
C
Operable
V
Window
B
B
= Area where Terminal is NOT permitted
B
l
A
J
E
D
V
X
Minimum Clearances US Installation **
A = Clearance above grade, veranda, porch, deck or balcony. 12 inches (30 cm) ** B = Clearance to window or door that may be opened. 6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW),
9 in. (23 cm) for appliances > 10,000 BTU/hr (3kW) and < 50,000 BTU/hr (15kW), 12 inches (30 cm) for appliances > 50,000 BTU/hr (15kW)*
C = Clearance to permanently closed window 9 inches (229 mm) recommended to prevent window condensation
D = Vertical clearance to ventilated soft located above the terminal within a horizontal
distance of 36 in. (91.4cm) from the center line of the terminal
E = Clearance to unventilated soffit 24 inches (61.0 cm) F = Clearance to outside corner 5 inches (12.7 cm) G = Clearance to inside corner 24 inches (61.0 cm)
H = Clearance to each inside of center line extended above meter / regulator assembly 3 feet (91 cm) within a height of 15 feet above the meter / regulator assembly ** I = Clearance to service regulator vent outlet 3 feet (91 cm) **
J = Clearance to non-mechanical air supply inlet to building or the combustion air inlet to
any other appliance
K = Clearance to mechanical air supply inlet 3 feet (91 cm) above, if within 10 feet (3 m) horizontally** L = Clearance above paved sidewalk or paved driveway located on public property 7 feet (2.13 m) ‡ M = Clearance under veranda, porch, deck or balcony 18 in. (46.0 cm) ** ‡ ** In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Codes - Latest Edition. ‡ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. *‡ Only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the oor.
24 inches (61.0 cm)
6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 9 in. (23 cm) for appliances > 10,000 BTU/hr (3kW) and < 50,000 BTU/hr (15kW), 12 inches (30 cm) for ap­pliances > 50,000 BTU/hr (15kW)*
Figure 4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7
5 (127)
8-1/4
(209)
14
(356)
12 (305)
19
(483)
2
(51)
4
(102)
6
(152)
8
(203)
10
(254)
12
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
MINIMUM CLEARANCES TO COMBUSTIBLES
Appliance And Vent Clearances
The appliance is approved with zero clearance to combustible materials
on all sides (as detailed in Table 5), with the following exception: When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit. In addition, when the unit is recessed, the side walls surrounding
the unit must not extend beyond the front edge of the unit (see Figure 2 on Page 5).
APPLIANCE MINIMUM CLEARANCES* Inches (millimeters)
Sides 1/2 (13), 0 (0) Spacers **
Top Spacers 0 (0)
Floor 0 (0) Back 1/2 (13), 0 (0) Spacers
Bottom of Appliance To Ceiling 69 (1743)
Vent 3 (76)
Top* / 1 (25.4) Sides & Bottom
SERVICE CLEARANCES Feet (meters)
Front 3 feet (0.9 meters)
Table 5
*Note: 3 in. (75 mm) above any horizontal/inclined vent component.
**Note: See Page 9, Step 1 for clearance requirements to the nailing flange located at each side of the unit and any screw heads adjacent to it.
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on
or near conventional construction materials. However, if installed on
combustible materials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bottom surface must be used.
Wall Finishes / Surrounds / Mantels
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the appliance face. See Figure 6 and Figure 43 on Page 26.
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with these exceptions: they must not cover any portion of the removable glass panel.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (see Figure 5). Mantels constructed of non- combustible materials may be installed at any height above the appliance
opening.
Mantel Depth
17 (432)
15 (381)
13 (330)
11 (279)
Distance from top of appliance to bottom of mantel
inches (millimeters)
Header
9 (229)
Top of Appliance
7 (178)
Fireplace
(side view)
Figure 5 - Minimum Mantel Clearances
At 14" minimum side wall clearance, a combustible wall can project to any length.
At 8-1/4" side wall clearance, a com­bustible wall can project 12"
o
45
Protected wall shown in white
Top View of
Fireplace
Combustible Materials Allowed In Shaded Area “Safe Zone”
Combustible Walls shown in dark gray
Combustible materials may project beyond one side of the fireplace opening as long as they are kept within the shaded areas illustrated here.
Inches (millimeters)
17 (432)
Figure 6 - Minimum Distance to Unprotected Side Wall
NOTE: We recommend the use of high temperature paint (rated 175° F
or higher) on the underside of the mantel.
8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifi­cally approved with this appliance may result in property damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
DETAILED INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre-wired. Remove
the shipping carton, exposing the front glass
door. Using a Phillips screwdriver, unfasten two
(2) screws located at the top of the glass frame
(see Figure 39 on Page 24). Tilt the top of the glass frame away from the unit. Lift it carefully
off the bottom door track and set the door aside,
protecting it from inadvertent damage.
Step 3. (Page 12) Install the vent system and
exterior termination.
Step 4. (Page 18) Field Wiring Connect 120 VAC electrical power to
the appliance receptacle.
Step 5. (Page 20) Remove glass door assem-
bly.
Step 6. (Page 21) Make connection to gas
supply.
Step 7. (Page 21) Install rebox liner kit. Step 8. (Page 21) Verifying appliance opera-
tion.
Step 9. (Page 22) Install logs, volcanic stone
and glowing embers.
Step 10. (Page 24) Install glass door assembly. Step 11. (Page 24) Adjust burner to ensure
proper flame appearance.
Step 12. (Page 27) Attach Safety in Operation
Warnings.
Step 1. FRAMING
Frame these appliances as illustrated in Figure 8 on Page 10, unless the appliance is to be
installed in a corner. See Figure 9 on Page 11 for corner framing installations. All framing details must allow for a minimum clearance
to combustible framing members as shown in
Table 5 on Page 8.
If the appliance is to be elevated above oor level, a solid continuous platform must be constructed below the appliance.
Use Top Flange For 1/2” Thick Drywall
Front Of Fireplace
Use Center Flange For Flush Mount
Use Bottom Flange For 5/8” Thick Drywall
Left Side Front Corner of Fireplace Shown
(Right Side Requirements the Same)
Unit Being Secured By Its Nailing Flanges
To The Framing
Note: The nailing flanges, combustible members and screw heads located in areas directly adjacent to the nailing flanges, are EXEMPT from the 1/2” clearance to combustible requirements for the firebox outer wrapper. Combustible framing may be in direct contact with the nailing flanges and may be located closer than 1/2” from screw heads and the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions specified in the framing details of this manual.
Unit Being Secured by Its Nailing
Flanges to the Framing
Figure 7
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation is outlined
below. However, each installation is unique and may result in variations to the steps described.
See the page numbers references in the follow-
ing steps for detailed procedures.
Step 1. (Page 9) Construct the appliance
framing. Position the appliance within the framing and secure with nailing
brackets.
Step 2. (Page 11) Route gas supply line to
the right side.
Headers may be in direct contact with the appliance top spacers but must not be sup­ported by them or notched to t around them. All construction above the appliance must be
self-supporting, DO NOT use the appliance for structural support.
The replace should be secured to the side framing members using the unit's nailing anges - one top and bottom on each side of
the fireplace front (see Figure 7). Use 8d nails or their equivalent.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
9
E
A
B
D
Top View
Front View
5-3/32 (129)
Right Side View
14-1/8
8-1/2” (216)
5-1/4” (133)
(359)
26-15/32
(672)
C
25-29/32
(658)
25-1/2
(648)
7
2-1/2 (64)
(178)
19-5/8
(498)
Gas Inlet
(This
Side
Only)
Electrical
Inlet
8-3/8 (213)
F
G
H
J
8” / 11”
Vent / Intake
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
A
B
C
VENT FRAMING
-
TOP VENT WITH 2 FEET VERTICAL VENT AND ONE 90° ELBOW
Framing should be constructed
of 2x4 or larger lumber.
Inches (mm)
(641)
25-1/4
1/2 A
10-1/2 (267)
7
(178)
5¹⁄₈
(130)
12-1/8
(308)
FIREPLACE AND FRAMING SPECIFICATIONS
Framing Dimensions
Model No. A B C *
LSM40-PV
LSM45-PV
* C = Adaptor Plus 4 Feet Vertical Vent (Min.) and 90° Elbow
in. 50-3/4 43 139-1/8
mm 1289 1092 3534
in. 56-7/8 48 144-1/8
mm 1445 1219 3661
Adaptor Plus 4 Feet Vertical Vent (Min.) and 90° Elbow
10
Figure 8
Model
LSM40-PV
LSM45-PV
No.
in. 50-5/8 37-1/4 42-7/8 25-5/16 34 37-5/8 33-3/32 29-9/32 34-3/4
mm 1286 946 1089 643 864 956 840 744 883
in. 56-11/16 42-1/4 47-7/8 28-3/8 40-1/8 43-5/8 38-3/32 34-1/2 40-59/64
mm 1440 1073 1216 721 1019 1108 968 876 1039
A B C D E F G H J
Fireplace Dimensions
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Vent Size
Co-axial DV
Vent Size
Diagrams, illustrations and photographs are not to scale – consult installation instructions. Product designs, materi­als, dimensions, specifications, colors and prices are subject to change or discontinuance without notice.
4-1/2" Inner 7-1/2" Outer
Notes
C
Back wall of chase/enclosure
(including any finishing materials)
D
A
B
Right Side Front Corner Of Fireplace Framing
6-1/4”
(159 mm)
19-5/8”
(498 mm)
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Model No. A B C D
LSM40-PV
LSM45-PV
in. 50-5/8 83-5/8 59-1/8 41-7/8
mm 1286 2124 1502 1064
in. 56-3/4 89-7/8 63-1/2 44-7/8
mm 1441 2283 1613 1140
Figure 9 - Corner Framing with Power Vent Termination
Step 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line along the inside
of the right side framing as shown in Figure
10. Gas lines must be routed, constructed and
made of materials that are in strict accordance with local codes and regulations.
All appliances are factory-equipped with a
exible gas line connector and 1/2 inch shutoff
valve. (See Step 6 on Page 21).
The incoming gas line should be piped into the
valve compartment and connected in one of the two methods as shown in Figure 29 on Page 21.
Figure 10
Proper Sizing of Gas Line
Properly size and route the gas supply line from the supply regulator to the area where the
appliance is to be installed per requirements
outlined in the National Fuel Gas Code, NFPA
54 - latest edition (USA).
Never use galvanized or plastic pipe. Refer to Table 6 for proper sizing of the gas sup-
ply line, if black iron pipe is being used. Gas lines must be routed, constructed and made
of materials that are in strict accordance with local codes and regulations. We recommend
that a qualied individual such as a plumber or gas tter be hired to correctly size and route
the gas supply line to the appliance. Installing a gas supply line from the fuel supply to the appliance involves numerous considerations of materials, protection, sizing, locations, controls, pressure, sediment, and more. Certainly no one unfamiliar and unqualified should attempt sizing or installing gas piping.
Schedule 40
Black Iron Pipe
Inside Diameter (Inches)
Schedule 40 Pipe
Length (feet)
0-10 1/2 3/8
10-40 1/2 1/2
40-100 1/2 1/2
100-150 3/4 1/2 150-200 3/4 1/2
Natural
Gas
Propane
Gas
Table 6
Notes:
• All appliances are factory-equipped with a exible gas line connector and 1/2 inch
shutoff valve (see Figure 29 on Page 21).
• See Massachusetts Requirements on Page 4 for additional requirements for installations
in the state of Massachusetts in the USA.
• The gas supply line should Not be connected
to the appliance until Step 6 (Page 21).
• A pipe joint compound rated for gas should be used on the threaded joints. Ensure propane
resistant compounds are used in propane applications. Be very careful that the pipe
compound does not get inside the pipe.
• It is recommended to install a sediment trap in the supply line as close as possible
to the appliance (see Figure 29 on Page 2). Appliances using Propane should have a
sediment trap at the base of the tank.
• Check with local building ofcial for local code requirements (i.e. are below grade penetrations of the gas line allowed?, etc).
IMPORTANT: If propane is used, be aware that if tank size is too small (i.e. under 100-lbs, if this is the only gas appliance in the dwelling. Ref. NPFA 58), there may be loss of pressure, resulting in insufficient fuel delivery (which can result in sooting, severe delayed ignition or other malfunctions). Any damage resulting from an improper installation, such as this, is not covered under the limited warranty.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
11
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Step 3. INSTALL THE VENT SYSTEM
General Information
These instructions should be used as a guide­line and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA.
These fireplaces are designed, tested and listed for operation and installation with, and only with, Secure Vent™ (SV4.5) Direct­Vent System Components, manufactured by Security Chimneys International. These ap­proved vent system components are labeled for identification. DO NOT use any other manufacturer's vent components with these appliances.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d'installation locaux et aux exigences du foumisseunde gaz.
Use only approved venting components. See Approved Vent Components on Page 2.
Power Vent Components
Locate the replace as per the instructions in this manual. Make the following modications to add the components used with the Power Vent Kits. This kit can only be used in conjunction with “Direct-Vent” series electronic versions of Lennox™ Fireplaces. This installation must conform with local codes or, in the absence of local codes, with the Natural Fuel Gas Code, ANSI Z223.1/NFPA 54.
CAUTION: This Power Vent Kit cannot be used with Millivolt appliances. Use kit only with the Electronically controlled fireplaces listed for its use as shown in this document.
POWER VENT COMPONENTS
Item No. Part
Number 1 604187-01 2 601970-01 Vacuum Hose 1
3 601451-01 Termination Assembly 1 4 74L61 SV Termination Adaptor (SV4.5RCH) 1 5 102010-01 Strain Relief - 3/8” 1 6 H2246 Firestop Assembly (Horizontal) 1 7 102022-01 8 P-8-7102 Snap Bushing 1
Adaptor Assembly With Probe 1
Hose Clamp - 11/32” 2
Description Qty.
These fireplaces must be vented directly to the outside.
The vent system may not service multiple
appliances, and must never be connected to a ue serving a solid fuel burning appliance. The vent pipe is tested to be run inside an enclosed wall (such as a chase). There is no requirement
for inspection openings in the enclosing wall at
any of the joints in the vent pipe.
Venting System
With the appliance secured in framing, de-
termine vent routing and identify the exterior
termination location. The following sections describe horizontal (exterior wall) vent applica­tions. A list of approved venting components
is shown on Page 28.
9 Ring Terminal - #10 2
10 Insulated 1/4” Male Terminal 4
1
2
5
7
4
6
8
8
9
3
12
Figure 11 - Power Kit Components
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
6 21 42 63 84
T OOOOO TTTTT AAAAA LLLLL
QQQQQ TTTTT YYYYY
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
5.4 573.0 1 0 0 0 0 1
9 57.0 2 0 0 0 0 2
5.01 578.0 0 1 0 0 0 1
51 52.1 1 1 0 0 0 2
5.22 578.1 0 0 1 0 0 1
5.13 526.2 0 3 0 0 0 3
5.43 578.2 0 0 0 1 0 1
5.73 521.3 1 1 1 0 0 3
5.34 526.3 0 2 1 0 0 3
54 57.3 0 0 2 0 0 2
5.64 578.3 0 0 0 0 1 1
15 52.4 1 0 0 0 1 2
5.55 526.4 0 1 2 0 0 3
75 57.4 0 0 1 1 0 2
5.76 526.5 0 0 3 0 0 3
96 57
.5 0 0 0 2 0 2
5.37 521.6 1 0 0 2 0 3
5.97 526.6 0 1 0 2 0 3
18 57.6 0 0 0 1 1 2
5.19 526.7 0 0 2 0 1 3
39 57.7 0 0 0 0 2 2
5.79 521.8 1 0 0 0 2 3
5.301 526.8 0 0 0 3 0 3 801 9 1 0 0 3 0 4
711 57.9 1 0 5 0 0 6
5.811 578.9 1 1 0 3 0 5
621 5.01 0 0 1 3 0 4
5.031 578.01 1 0 1 3 0 5
531 52.11 0 0 6 0 0 6
5.931 526.11 0 0 0 0 3 3
5.241 578.11 1 0 0 4 0 5
441 21 1 0 0 0 3 4
5.451 578.21 1 1 0 0 3 5
5.061 573.31 0 2 0 0 3 5
5.271 573.41 0 0 0 5 0 5
771 57.41 1 0 0 5 0 6
681 5.51 0 0 0 0 4 4
5.691 573.61 0 1 0 0 4 5
702 52.71 0 0 0 6 0 6
5.112 526.71 1 0 0 6 0 7
5.712 521.81 0 1 0 6 0 7
5.922 521.91 0 0 1 6 0 7
5.23
2 573.91 0 0 0 0 5 5
5.142 521.02 0 0 0 7 0 7
642 5.02 1 0 0 7 0 8
252 12 0 1 0 7 0 8
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
6 21 42 63 84
T OOOOO TTTTT AAAAA LLLLL
QQQQQ TTTTT YYYYY
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
5.4 573.0 1 0 0 0 0 1
9 57.0 2 0 0 0 0 2
5.01 578.0 0 1 0 0 0 1
51 52.1 1 1 0 0 0 2
5.22 578.1 0 0 1 0 0 1
5.13 526.2 0 3 0 0 0 3
5.43 578.2 0 0 0 1 0 1
5.73 521.3 1 1 1 0 0 3
5.34 526.3 0 2 1 0 0 3
54 57.3 0 0 2 0 0 2
5.64 578.3 0 0 0 0 1 1
15 52.4 1 0 0 0 1 2
5.55 526.4 0 1 2 0 0 3
75 57.4 0 0 1 1 0 2
5.76 526.5 0 0 3 0 0 3
96 57
.5 0 0 0 2 0 2
5.37 521.6 1 0 0 2 0 3
5.97 526.6 0 1 0 2 0 3
18 57.6 0 0 0 1 1 2
5.19 526.7 0 0 2 0 1 3
39 57.7 0 0 0 0 2 2
5.79 521.8 1 0 0 0 2 3
5.301 526.8 0 0 0 3 0 3 801 9 1 0 0 3 0 4
711 57.9 1 0 5 0 0 6
5.811 578.9 1 1 0 3 0 5
621 5.01 0 0 1 3 0 4
5.031 578.01 1 0 1 3 0 5
531 52.11 0 0 6 0 0 6
5.931 526.11 0 0 0 0 3 3
5.241 578.11 1 0 0 4 0 5
441 21 1 0 0 0 3 4
5.451 578.21 1 1 0 0 3 5
5.061 573.31 0 2 0 0 3 5
5.271 573.41 0 0 0 5 0 5
771 57.41 1 0 0 5 0 6
681 5.51 0 0 0 0 4 4
5.691 573.61 0 1 0 0 4 5
702 52.71 0 0 0 6 0 6
5.112 526.71 1 0 0 6 0 7
5.712 521.81 0 1 0 6 0 7
5.922 521.91 0 0 1 6 0 7
5.23
2 573.91 0 0 0 0 5 5
5.142 521.02 0 0 0 7 0 7
642 5.02 1 0 0 7 0 8
252 12 0 1 0 7 0 8
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
6 21 42 63 84
T O T A L
Q T Y
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
672 32 0 0 0 8 0 8
972 52.32 0 0 0 0 6 6
5.082 573.32 1 0 0 8 0 9
5.982 521.42 0 1 0 0 6 7
5.103 521.52 0 0 1 0 6 7
5.013 578.52 0 0 0 9 0 9
5.523 521.72 0 0 0 0 7 7
033 5.72 1 0 0 0 7 8
543 57.82 0 0 0 01 0 01
5.943 521.92 1 0 0 01 0 11
273 13 0 0 0 0 8 8
5.973 526.13 0 0 0 11 0 11
5.814 578.43 0 0 0 0 9 9
564 57.83 0 0 0 0 01 01
5.574 526.93 0 1 0 0 01 11
084 04 1 1 0 0 01 11
294 14 1 0 1 0 01 21
5.994 526.14 0 0 0 1 01 11
405 24 1 0 0 1 01 21
5.115 526.24 0 0 0 0 11 11
5.025 573.34 0 2 0 1 11 41
135 52.44 0 2 2 0 11 51
5.835 578.44 1 0 0 2 11 41
945 57.54 1 0 2 1 11 51
855 5.64 0 0 0 0 21 21
5.265 578.64 1 0 0 0 21 31
5.865 573.74 0 1 0 0 21 31
375 57.74 1 1 0 0 21 41
5.085 573.84 0 0 1 0 21 31
5.985 521.94 0 1 2 2 01 51
5.595 526.94 1 1 1 0 21 51
5.406 573.05 0 0 0 0 31 31
516 52.15 0 1 0 0 31 41
5.526 521.25 0 2 0 0 31 51
5.136 526.25 1 0 1 0 31 51
5.736 521.35 0 1 1 0 31 51
156 52.45 0 0 0 0 41 41
5.556 526.45 1 0 0 0 41 51
276 65 0 2 0 0 41 61
876 5.65 1 0 1 0 41 61
5.886 573.75 1 1 1 0 41 71
5.796 521.85 0 0 0 0 51 51
207 5.85 1 0 0 0 51 61
5.217 573.95 1 1 0 0 51 71
027 06 0 0 1 0 51 61
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
6 21 42 63 84
T O T A L
Q T Y
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
672 32 0 0 0 8 0 8
972 52.32 0 0 0 0 6 6
5.082 573.32 1 0 0 8 0 9
5.982 521.42 0 1 0 0 6 7
5.103 521.52 0 0 1 0 6 7
5.013 578.52 0 0 0 9 0 9
5.523 521.72 0 0 0 0 7 7
033 5.72 1 0 0 0 7 8
543 57.82 0 0 0 01 0 01
5.943 521.92 1 0 0 01 0 11
273 13 0 0 0 0 8 8
5.973 526.13 0 0 0 11 0 11
5.814 578.43 0 0 0 0 9 9
564 57.83 0 0 0 0 01 01
5.574 526.93 0 1 0 0 01 11
084 04 1 1 0 0 01 11
294 14 1 0 1 0 01 21
5.994 526.14 0 0 0 1 01 11
405 24 1 0 0 1 01 21
5.115 526.24 0 0 0 0 11 11
5.025 573.34 0 2 0 1 11 41
135 52.44 0 2 2 0 11 51
5.835 578.44 1 0 0 2 11 41
945 57.54 1 0 2 1 11 51
855 5.64 0 0 0 0 21 21
5.265 578.64 1 0 0 0 21 31
5.865 573.74 0 1 0 0 21 31
375 57.74 1 1 0 0 21 41
5.085 573.84 0 0 1 0 21 31
5.985 521.94 0 1 2 2 01 51
5.595 526.94 1 1 1 0 21 51
5.406 573.05 0 0 0 0 31 31
516 52.15 0 1 0 0 31 41
5.526 521.25 0 2 0 0 31 51
5.136 526.25 1 0 1 0 31 51
5.736 521.35 0 1 1 0 31 51
156 52.45 0 0 0 0 41 41
5.556 526.45 1 0 0 0 41 51
276 65 0 2 0 0 41 61
876 5.65 1 0 1 0 41 61
5.886 573.75 1 1 1 0 41 71
5.796 521.85 0 0 0 0 51 51
207 5.85 1 0 0 0 51 61
5.217 573.95 1 1 0 0 51 71
027 06 0 0 1 0 51 61
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
VENT SECTION LENGTHS
Determine the number of straight vent sections required. 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46­1/2" (1181 mm) net section lengths are available.
Refer to the Vent Section Length Chart.
Vertical (Offset) Installation
Analyze the vent routing and determine the
quantities of vent sections and number of elbows required. Refer to Figures 16 and 17
on Page 15 showing vent run requirements to aid in selecting the type of vertical installation
desired. Vent sections are available in net lengths of 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm). Refer to the Vent Section Length Chart for an aid in selecting length combinations. Elbows are available in 90° and 45° congura-
tions. Refer to Figure 15 on Page 14 for the
SV4.5 E45 and SV4.5 E90 elbow dimensional
specifications.
Where required, a telescopic vent section
(SV4.5LA) may be used to provide the installer
with an option in installing in tight and confined
spaces or where the vent run made up of xed length pieces develops a joint in a undesirable location, or will not build up to the required length. The SV4.5LA Telescopic Vent Section has an effective length of from 1-1/2" (38 mm) to 6-3/4" (171 mm). The SV4.5LA is tted with
a dimpled end (identical to a normal vent section
component) and a plain end with 3 pilot holes.
Slip the dimpled end over the locking channel
end of a standard SV4.5 vent component the
required distance and secure with three screws.
Maintain a minimum 1" (25 mm) clearance to combustible materials for all vertical ele­ments. Clearances for all horizontal elements are 3" (76 mm) on top, 1" (25 mm) on sides and 1" (25 mm) on the bottom.
Table 7
Effective Vent Length
Model Effective Length
SV4.5L6 4-1/2" SV4.5L12 10-1/2" SV4.5L24 22-1/2" SV4.5L36 34-1/2" SV4.5L48 46-1/2"
Note: Convert inches into metric equivalent measurement, as follows:
Millimeters (mm) = Inches x 25.4 Centimeters (cm) = Inches x 2.54 Meters (M) = Inches x .0254
13
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7-5/8”
(194 mm)
4-13/16
(122 mm)
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
A. Frame ceiling opening - Use a plumb line from the ceiling above the appliance to locate
center of the vertical run. Cut and/or frame an
opening, 10-1/2" x 10-1/2" (267 mm x 267 mm) inside dimensions, about this center mark
(Figure 12).
10-1/2" Min.
(267 mm)
Plumb Bob
Ceiling Framing
Figure 12
B. Attach adaptor (with probe) to appliance collar. Secure Vent™ SV4.5 direct-vent
system components are unitized concentric pipe components featuring positive twist lock connections (see Figure 13).
All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the adaptor fits over the appliance collar to create the positive twist lock connection.
Align the dimple (four places) of the upper vent section with the opening of the locking incline channel on the lower vent section or appliance collar. Twist vent component clock­wise to engage and seal until arrow
Arrow
Adaptor on Appliance Collar or Vent Section
and dimple align.
Dimple
Locking Incline Channel
Connected Vent Sections
Figure 13
To attach a vent component to the adaptor on appliance collar, align the dimpled end over the
adaptor collar, adjusting the radial alignment
until the four locking dimples are aligned with the inlet of the four inclined channels on the collar (refer to Figure 13). Push the vent component against the collar until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels.
14
10-1/2" Min.
(267 mm)
Arrow
The unitized design of the Secure Vent com-
ponents will engage and seal both the inner
and outer pipe without the need for sealant or
screws. If desired a #6 x 1/2" screw may be used at the joint, but it is not required as the
pipe will securely lock when twisted. C. Attach vent components to each other - Other
vent sections may be added to the previously
installed section in accordance with the require­ments shown in Figures 16 and 17 on Page 15.
To add another vent component to a length of vent run, align the dimpled end over the inclined channel end of the previously installed section,
adjusting the radial alignment until the four
locking dimples are aligned with the inlets of the four incline channels of the previous section.
Push the vent component against the previ­ous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels. This seating
position is indicated by the alignment of the arrow and dimple as shown in Figure 13.
D. Install firestop/spacer at ceiling - When
using Secure Vent, use SV4.5VF restop/spacer at ceiling joists. If there is living space above the ceiling level, the restop/spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the restop/ spacer must be installed on the top side of the joist. Route the vent sections through the framed
opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner. Remember to maintain 1" (25 mm)
clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections. Attic insulation shield (H3907) may be used to obtain the required clearances indicated here. See installation accessories on Page 28. The gap between the vent pipe and a vertical firestop can be sealed with non-combustible caulking.
E. Support the vertical vent run sections -
Blocking
Support Straps (Plumber's tape)
8 feet (2.4 m)
Maximum
1/2 inch (13 mm) minimum clearance to combustibles
Figure 14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Note - Proper venting support is very important. The weight of the vent must not be supported by the fireplace in any degree.
Support the vertical portion of the venting
system every 8 feet (2.4 m) above the replace vent outlet. One method of support is by utiliz-
ing field provided support straps (conventional
plumber's tape). Secure the plumber's tape to the framing members with nails or screws. Strap
the tape around the vent, securing the ends of the tape to the framing. If desired, sheet metal
screws #6 x 1/2" length may be used to secure
the support straps to the vent pipe.
F. Change vent direction to horizontal/inclined run - At transition from or to a horizontal/in-
clined run, install the SV4.5 E45 and SV4.5 E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis
of their initial collar section to align with the
required direction of the next vent run element.
Twist elbow sections in a clockwise direction only so as to avoid the possibility of unlocking any of the previously connected vent sections (see Figures 13 and 15).
8-1/8"
(206 mm)
Swivel Joint
(360° swivel)
SV4.5E45
45° Elbow)
Swivel Joint
(360° swivel)
SV4.5E90
90° Elbow)
Figure 15
G. Continue installation of horizontal/inclined sections - Continue with the installation of the
straight vent sections in horizontal/inclined run
as described in Step C. Install support straps every 3' (914 mm) along horizontal/inclined vent runs using conventional plumber’s tape (see
Page 15, Figure 16). It is very important that the horizontal/inclined run be maintained in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4" per foot (20 mm per meter) horizontal, in a direction away from the fireplace. The rise per
foot run ratios that are smaller are acceptable all
the way down to at or near level. Use a carpen­ter’s level to measure from a constant surface
and adjust the support straps as necessary.
It is important to maintain the required clear­ances to combustibles: 1" (25 mm) at all sides for all vertical runs; and 3" (76 mm) at the top, 1" (25 mm) at sides, and 1" (25 mm) at the bottom for all horizontal/inclined runs.
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
VENT FIGURES
Notes:
• SecureVent™ components (rigid vent pipe and terminal) are shown in the Figures.
• Two 45 degree elbows may be used in place of one 90 degree elbow.
• SV4.5VF (Secure Vent) firestop/spacer must be used anytime vent pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent)
firestop/spacer must be used anytime vent pipe passes through a combustible wall.
• It is very important that the horizontal/inclined run be maintained in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4" per foot (20 mm per meter) horizontal, in a direction away from the fireplace. The rise per foot run ratios that are smaller
are acceptable all the way down to at or near level.
Power Vent Termination
Exterior Wall
SV4.5L 6 / 12 / 24 / 36 / 48
Vent Sections
Horizontal / Inclined Run
Figure 16 - Typical Power Vent Routing
Firestop / Spacer
Maximum Horizontal
Venting 110 Feet.
Up to 6 Elbows
Floor
Support Brackets
Ceiling
Probe Adaptor (required)
Building Support Framing
SV4.5E90 Elbow
Vertical Rise
66 Feet Max.
4 Feet Min.
Fireplace
Minimum Vent Run
Horizontal
10 Feet
Probe Adaptor
(required)
Exterior Wall
Power Vent Termination
POWER VENT VENTING CHART
Maximum Number Of Elbows - 6
Maximum Feet Of Run
Minimum Horizontal Run B 10 feet
Minimum Vertical Run A
Maximum Vertical Rise A
A + B 110 feet
Adaptor Plus 4 Feet Vertical
Vent (Min.) and 90° Elbow
MINIMUM CLEARANCES TO COMBUSTIBLES
Vertical Vent Pipe 1.0 in. (25.4 mm)
Horizontal Vent Pipe
Top - 3.0 in. (76.2 mm)
Sides - 1.0 in. (25.4 mm)
Bottom - 1.0 in. (25.4 mm)
Figure 17
A
66 feet
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
(See Chart)
B
Probe Adaptor
(Required)
15
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
HORIZONTAL (OUTSIDE WALL) TERMINATION SYSTEM
See Figures 16 and 17 on Page 15 illustrating the various horizontal venting configurations
that are possible for use with these appliances. The table in Figure 17 on Page 15 shows each system’s minimum and maximum vertical and horizontal length values that can be used to
design and install the vent components in a variety of applications.
The horizontal vent system terminates through
an outside wall. Building Codes limit or prohibit
terminating in specific areas. Refer to Figure 4 on Page 7 for location guidelines.
Secure Vent™ SV4.5 direct-vent system com- ponents are unitized concentric pipe compo­nents featuring positive twist lock connection, (refer to Figure 13 on Page 14). All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the appliance collar to create the positive twist lock connection.
A. Plan the vent run - Analyze the vent routing and determine the
types and quantities of sections required
4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm) net section lengths are available. Make allowances for elbows as indicated in
Figure 15 on Page 14.
Maintain a minimum 1" (25 mm) clearance
to combustibles on the vertical sections. Clearances for the horizontal runs are; 3" (76 mm) on top, 1" (25 mm) on sides, and 1" (25 mm) at the bottom.
B. Frame exterior wall opening -
Locate the center of the vent outlet on the
exterior wall according to the dimensions
shown in Figure 8 on Page 10.
Cut and/or frame an opening, 10-1/2" x 12-
1/8" (267 mm x 308 mm) inside dimensions, about this center.
C. Frame ceiling opening - If the vertical route is
to penetrate a ceiling, use plumb line to locate the center above the appliance. Cut and/or frame an opening, 10-1/2" x 10-1/2"(267 mm x 267 mm) inside dimensions, about
this center (refer to Figure 12 on Page 14).
D. Attach vent components to appliance - To
attach a vent component to the appliance collar, align the dimpled end over the collar,
adjusting the radial alignment until the four
locking dimples are aligned with the inlets of the four incline channels on the collar (refer to Figure 13 on Page 14).
Push the vent component against the collar
until it fully engages, then twist the compo­nent clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure Vent components will
engage and seal both the inner and outer pipe
elements with the same procedure. Sealant and securing screws are not required.
E. Attach vent components to each other -
Other vent sections may be added to the
previously installed section in accordance
with the requirements of the vent tables.
To add another vent component to a length of vent run, align the dimpled end of the component over the inclined channel end of
the previously installed section, adjusting the
radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section. Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels. This seating
position is indicated by the alignment of the arrow and dimple as shown in Figure 13 on Page 14.
F. Install firestop/spacer at ceiling -
When using Secure Vent, use SV4.5VF re-
stop/spacer at ceiling joists. If there is living space above the ceiling level, the restop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceil­ing, the restop/ spacer must be installed on the top side of the joist. Route the vent
sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1" (25 mm) clear-
ance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.
G. Support the vertical run sections -
On the vertical run, support the venting
system every 8 feet (2.4m) above the re­place vent outlet with field provided support straps (Plumber's tape). Attach the straps to the vent pipe and secure to the framing
members with nails or screws.
H.Change vent direction - At transition from
or to a horizontal/inclined run, install the
SV4.5E45 and SV4.5E90 elbows in the same
manner as the straight vent sections. The
elbows feature a twist section to allow them to be routed about the center axis of their
initial collar section to align with the required
direction of the next vent run element. Twist elbow sections in a clockwise direction only so as to avoid the possibility of unlocking any of the previously connected vent sec­tions (see Figure 13 on Page 14).
I. Continue installation of horizontal/inclined
sections - Continue with the installation
of the straight vent sections in horizontal/
inclined run as described in Step E. Install support straps every 3 feet (1914 mm)
along horizontal/inclined vent runs using
conventional plumber’s tape.
See Figure 16 on Page 15. It is very im-
portant that the horizontal/inclined run be maintained in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4" per foot (20 mm per meter) horizontal, in a direction away from the fireplace. The rise per foot run ratios that
are smaller are acceptable all the way down
to at or near level. Use a carpenter’s level to
measure from a constant surface and adjust
the support straps as necessary.
Installing Power Vent Termination
J. Assemble vent run to exterior wall - If not
previously measured, locate the center of
the vent on the exterior wall. Prepare an opening as described in this manual. As­semble the vent system to a point where
the terminus of the last section is within 8 inches of the outside wall surface where
the power vent is to be mounted (refer to
Figure 19 on Page 17).
If the terminus of the last section is not
within this distance, use the telescopic vent section SV4.5LA, as the last vent section. For wall thicknesses greater than that shown in Figure 19 (Page 17), refer to Table 8 (Page 17) for the additional vent­ing components needed (in addition to the
termination and adaptor) for a particular
range of wall thicknesses.
K. Attach termination adaptor - Attach the
adaptor (adaptor - SV4.5RCH - provided with the power vent kit) to the vent section telescoping vent section, or elbow, as shown
in Figures 18 and 19 (Page 17) in the same
manner as any SV4.5 vent component.
16
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
L. Install Firestop/Spacer at exterior wall -
Install SV4.5HF Firestop/Spacer, provided
with the power vent kit, over the opening at the exterior side of the framing, long side up, with the 3 inch spacer clearance at the top as shown in Figure 18, and nail into place.
(The Firestop/Spacer may also be installed
over the opening at the interior side of the
framing).
M. Install the Power Vent termination - For
the last step, from outside the exterior wall,
slide the collars of the termination onto the adaptor (the outer inside the outer and the
inner outside the inner) until the termina­tion seats against the exterior wall surface to which it will be attached. Orient the
housing of the termination with the arrow pointed upwards. Secure the termination
to the exterior wall. The termination must not be recessed into the exterior wall or siding by more that the 1-1/4” (32 mm) as
shown in Figure 19.
The Power Vent termination has been designed to perform in a wide range of weather conditions. Our terminations meet or exceed industry standards.
When selecting the location of your ter­mination, do not place the termination where water from eaves and adjoining roof lines may create a heavy flow of cascading water onto the terminations. If the termination must be placed where the possibility of cascading water exists, it is the responsibility of the builder to direct the water away from the termination cap by using gutters or other means.
Take care to carefully follow the Installation Instructions for the termination, including the use of silicone caulking where required.
Firestop/Spacer (SV4.5HF) shown
on the exterior side of the wall. It
may also be installed on the
interior side.
7"
5-1/8"
(130 mm)
(178)
12-1/8"
(308 mm)
Adapter
SV4.5RCH
6 to 48 inch Vent Section,
Telescopic vent section,
10-1/2"
(267 mm)
Note: Centerline of Vent Piping is
NOT the Same as the Centerline of
the Frame Opening.
See Figure 8 on Page 10 for Minimum Distance to Base of Appliance
Base of Appliance
Figure 18 - Installing Power Vent Horizontal Termination
*Use silicone caulking to seal the top and sides of the termination, up to the underlayment, stucco, or masonry wall surface.
*Caulk
*Caulk
Stucco
Siding
**For thicknesses greater than 9-1/4”, see Table 8
Interior Surface of
Finished Wall
Maximum Extent of Vent Run Sections Relative to Exterior Surface of Framing
Last Vent Section.
Use Telescopic Vent
Section (SV4.5LA),
If Necessary
Power Vent
Termination
Adapter
SV4.5RCH
Power Vent
Termination
3"
(76 mm)
1"
(25.4 mm)
Maximum wall thickness
9-1/4 in.(235 mm)**
Exterior Surface of Siding
Exterior Surface of
Framing
6 in. to 9-1/4 in.
(152 to 235 mm)**
Power Vent
Termination
1-1/4" Maximum Re cess of the Sq uare Termination into Exterior Fi ni sh in g M ateria l
See Table 8 as an aid in venting component selection for a particular range of exterior wall thicknesses.
IMPORTANT: The vent termination is hot while in operation and for a period of time following the use of the fireplace. Young children should be carefully supervised when they are in the same area as a hot termination.
Venting Connection and Exterior Wall Recessing
of the Power Vent Horizontal Termination
Figure 19
Venting Components Required for Various Exterior
Wall Thicknesses, When Using The Power Vent Termination
Vent Components Required Exterior Wall Thickness - inches (mm)
Termination Kit Only 6 to 9-1/4 (152 to 235) Termination Kit and 6 In. Vent Section
(SV4.5L6) Termination Kit and 12 in. Vent Section
(SV4.5L12) Termination Kit and Telescopic Section
(SV4.5L12)
10-3/4 to 14 (273 to 356)
16-3/4 to 20 (426 to 508)
11-3/4 to 20 (299 to 508)
Table 8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
17
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Step 4. FIELD WIRING
CAUTION: Label all wires prior to disconnection when servic­ing controls. Wiring errors can cause improper and dangerous operation.
ATTENTION: Au moment de l'entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de cáblage peu-vent entraîner un fonctionnement inadéquat et dangereux.
Verify proper operation after servicing.
S'assurer que l'appareil fonctionne adé-quatement une fois l'entretien terminé.
CAUTION: Ground supply lead must be connected to the wire attached to the green ground screw located on the outlet box. See Figures 26 and 27 on Page 20. Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70-latest edition.
Route Wiring
NOTE: Electrical wiring must be performed by a qualified electrician.
• Install the strain relief in the hole provided on the right side of replace
for the electrical wiring (refer to Figure 20). Standard Instruction (For use when access to the termination is dif-
cult because of height or other reasons).
• Locate a locally procured electrical junction box within reach of the
termination wiring pigtail (refer to Figure 22 on Page 19) and route
the pigtail to the junction box as the termination is installed.
• Route 14 gauge AWG grounded Romex wiring (not provided) from the replace to the just installed junction box close to the termina­tion. Ensure the wiring is safety plated to prevent damage by framing
nails and finish drywall screws. Route the wire into the lower control
compartment and cut to length before installing the terminals. Install provided wiring hardware on the ends of the Romex wire.
• Refer to Figure 24 on Page 19 and install the electrical hardware on the ends of the Romex wiring. Male terminals on the Black and
White wires, and ring terminals on the ground wire.
• Using standard electrical practices and the terminals provided, con­nect the three wires of the Romex cable to the termination pigtail within the Electrical junction box. Ensure ground.
• The replace end of the Romex will be addressed in Connecting The
Power Vent To The Fireplace Control System.
Probe (1 *)
Hose Clamp (7 *)
Vacuum Hose (2 *)
Adaptor Assembly
* See Figure 11 on Page 12
Figure 21A - Vacuum Hose Connection To Probe
Vacuum Hose
Pressure Switch
18
Strain Relief
14 Gage Grounded Romex
Vacuum Hose
Snap Bushing
Wall Switch Harness
Figure 20
Pressure switch is located behind the panel on the right side of firebox
Right Side
of Fireplace
Firebox
Vacuum Hose
Junction Box
Pressure Switch
Figure 21B - Vacuum Hose Connection To Pressure Switch
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Wiring - Fireplace (See Figures 26 and 27 on Page 20)
Note: These electronic appliances must be connected to the main power
supply. The gas valve is set in place and pre-wired at the factory.
1. Route a 3-wire 120Vac 60Hz 1ph power supply to the appliance junc-
tion box.
2. Remove the electrical inlet cover plate from the side of the unit by remov-
ing the plate's securing screws (see Figure 8 on Page 10).
3. Remove the cover plate's knockout and then feed the power supply wire
through the knockout opening and into the unit junction box.
4. Connect the black power supply wire to the power outlet's red pigtail lead and the white power supply wire to the common terminal of the outlet as shown in Figures 26 and 27 on Page 20.
5. Connect the ground supply wire to the pigtail lead attached to outlet's green ground screw.
6. Appliance-mounted ON/OFF burner control switch (rocker switch) is
factory installed. Optional wall-mounted switch, or one of the optional
remote control kits may also be used.
7. If wall-mounted ON/OFF control is to be used, mount it in a convenient
location on a wall near the fireplace.
8. If an optional control is to be used, wire it in the low voltage circuit (see
Figure 26 on Page 20).
Note: The supplied 15 feet of 2 conductor wire has one end of each
conductor connected in parallel with the appliance mounted ON/OFF burner control switch and the other end of each conductor placed on top of the unit.
CAUTION: Do Not connect the optional wall switch to a 120V power supply.
• Refer to Figure 26 and install the electrical hardware on the fireplace end of the Romex wiring. Male terminals (#10) on the Black and White wires, and ring terminals (#9) on the ground wire. The termination end of the Romex will be connected to the termination with wire nuts (not provided).
• Refer to Figure 25 to connect the three wires of the Romex cable to the termination. Ensure the ground ring terminal is grounded beneath a structural screw as shown. Attach the junction box cover to the
termination with the screw previously removed.
• The replace end of the Romex will be addressed in Connecting The Power Vent To The Fireplace Control System.
Black and White
Romex
Ground Wire
10
9
Figure 23 - Romex
9. If an optional control switch is installed, turn the appliance-mounted
ON/OFF burner control switch to the OFF position.
10.After the wiring is complete, replace the cover plate.
Wiring - Power Vent Termination
Alternate Instructions (For use when access to the termination is easy
and a secondary electrical junction box installation is not desired).
• Remove the junction box cover from the termination by removing the
attaching screw (refer to Figure 22).
• Loosen the strain relief on the termination shown in Figure 22. Pull the pigtail in and shorten it to t within the junction box cover.
• Route 14 gauge AWG grounded Romex wiring (not provided) from replace to the J-Box at the termination. Ensure the wiring is safety plated to prevent damage by framing nails and nish drywall screws.
Route the wire into the lower control compartment and cut to length
before installing the terminals. Install provided wiring hardware on the replace end of the Romex wire.
Strain Relief
Romex Wire
Figure 24 - Back Of Termination
Pigtail Wires Cut
Off And Shortened
Ground Romex To The Termination
Pigtail
Junction Box Cover
Figure 22 - Bottom Of Termination
Attaching Screw
Figure 25 - Junction Box Cover Removed
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Strain Relief Holding Romex
Wire Nuts
19
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
J-BOX/RECEPTIACLE
WIRING
120V, 60HZ, 1PH
Factory Wired
Field Wired
Junction Box
Tab Intact
Tab Intact
n e e r G - d n u o r G
e t i h W - l a r
t u e N
120 VAC - Black
Green Ground Screw
White
Green
Neutral Side of Receptacle
Hot Side of Receptacle
Black
Pilot Burner Igniter-Sensor Assembly
Connector
Blue (20)
Ground
Green (12)
Purple (9)
Electronic Ignition
Control Board
White (6)
EV2 EV1
White (20)
Orange (20)
Black (20)
Green LED
Gas Valve
Item 45 Wire #2
Junction Box
Black
White
White (6)
Appliance Mounted
On/Off Switch
Wall-Mounted On/Off Switch (optional)
120 VAC
Transformer
120 V.
24 V.
Item 32 Wire #3
Black
White Ground
Black (16)
Pressure
Red
Switch
Red
Black
Black
Field Installed
Exhaust Blower Control Module
N/A
Item 63
Exhaust
Blower
Blower
(Field Installed)
To Igniter Module
20
Figure 26 - Electronic Wiring Diagram
Figure 27- J-BOX WIRING
Step 5. REMOVING GLASS DOOR ASSEMBLY
WARNING
Handle this glass with extreme care! Glass is susceptible to damage – Do not scratch or handle roughly while reinstall­ing the glass door frame.
Do not attempt to substitute the materials used on this door, or replace cracked or broken glass with any materials other than those provided by the appliance manufacturer.
The glass door of this appli­ance must only be replaced as a complete unit as provided by the manufacturer. Do not attempt to replace broken, cracked or chipped glass separately.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Refer to Figure 39 on Page 24 and remove the front glass door assembly as follows:
To remove the firescreens, lift up the center of
the rod to disengage it from the center bracket, bend down at center, hold left side with hand until it disengages from left side, being careful
not to scratch paint. Slowly remove the rod from the right side.
Using a Phillips screwdriver, unfasten two (2)
screws located at the top of the glass frame.
Tilt the glass frame at the top away from the
unit. Lift it carefully off the bottom door track
and set the door aside, protecting it from inad­vertent damage.
Gas Valve
3/8" NPT x
Flare Fitting
3/8" Flex Tubing
3/8" Nipple
3/8" Union
3/8" Close Nipple
3/8" Shut-off Valve
1/2" x 3/8"
Reducer
Gas
Stub
1/2" x 3/8" Flare
Shut-off Valve
Gas Solid Line Connector
Gas Flex Line Connector
*Sediment Trap
3"
Min
ELECTRONIC
Flame
Sensor
Hood
Igniter Rod
Pilot Nozzels
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Step 6. CONNECTING GAS LINE
All codes require a shut-off valve mounted in the supply line. The orientation of the shut-off valve should face the front. Figure 29 il­lustrates two methods for connecting the gas supply. A Sediment Trap is recommended to
prevent moisture and debris in gas line from
damaging the valve.
The ex-line method is acceptable in the U.S.A
where local codes permit. Installation must be in compliance with local codes. These appli-
ances are equipped with a gas ex-line for use
in connecting the unit to the gas line.
See Figure 29 for ex-line description. The ex-
line is rated for both natural and propane gas.
A manual shut off valve is also provided with
the ex-line. The gas control valve is located
on the right side of the unit.
When using solid gas line connector, access
the valve by removing the front door assembly
on the valve access side and the access plate (refer to Figure 28).
The electronic control valve has a 3/8" (10 mm)
NPT thread gas supply inlet.
Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resistant compounds are used in propane applications).
Turn on gas supply and test for gas leaks using a
gas leak test solution (also referred to as bubble leak solution).
Note: Using a soapy water solution is an
effective leak test solution but it is not recom­mended, because the soap residue that is left on the pipes/fittings can result in corrosion over time.
A. Light the appliance (refer to the lighting
instructions label in control compartment
or in the Care and Operation instructions
manual).
B. Brush all joints and connections with the
gas leak test solution to check for leaks.
If bubbles are formed, or gas odor is detected,
turn the gas control knob (off/pilot/on) to the
“OFF” position. Either tighten or refasten the
leaking connection, then retest as described above.
C. When the gas lines are tested and leak free
be sure to rinse off the leak testing solution.
D. Re-install the access plate, making certain
the gasket has not been damaged.
Step 7. INSTALL FIREBOX LINER KIT
Install the rebox liner kit per the instructions provided in kit (ref form # 750182M).
Note: The gas supply line must be installed in accor­dance with building codes by a qualified installer approved and/or licensed as required by the locality. In the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter.
Bring the shutoff valve on the end of the ex-line
over to the hard pipe and tighten with wrenches
from above through the rebox opening.
Right Side
Modesty Panel
Access Plate
Extension Knob
ON/OFF Switch
Hi-Lo
Gas Valve
Figure 28
TEST ALL CONNECTIONS FOR GAS LEAKS (FACTORY AND FIELD):
WARNING
Never use an open flame to check for leaks.
Figure 29 - GAS CONNECTION
Step 8. VERIFYING APPLIANCE OPERA­TION
Turn on burner then observe the individual tongues of ame on the burner. Make sure
all ports are open and producing flame evenly
across the burner. If any ports are blocked, or partially blocked, clean out the ports.
With gas line installed run initial system check-
out before closing up the front of the unit.
Follow the pilot lighting instructions provided.
Note: Lighting Instructions are also found on the literature tag tied to the bracket above the gas valve. To access the tag, reach into the right side opening.
When first lighting the appliance, it will take a few minutes for the line to purge itself of air. Once purging is complete, the pilot and
burner will light and operate as indicated in the instruction manual. Subsequent lighting
of the appliance will not require such purging. Inspect the pilot flame (remove logs, if neces-
sary, handling carefully).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Electronic Appliance Checkout
To light the burner, turn ‘ON’ the optional remote
wall switch or turn the appliance mounted ON/ OFF switch to the “ON” position. Ensure the igniter lights the pilot. The pilot flame should engulf the flame sensor as shown in Figure 30.
Figure 30
21
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Step 9. INSTALL VOLCANIC STONE, GLOWING EMBERS AND LOGS
WARNING
• DO NOT attempt to install the logs until the
appliance installation has been completed, the gas line connected and tested for leaks and the initial burner operation has been checked out. The size and position of the log set was engi-
neered to give the appliance a safe, reliable and attractive flame pattern. Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combus­tion, sooting, and poor flame quality. Logs get very hot and will remain hot up to one
hour after gas supply is turned off. Handle only when logs are cool. Turn off all electricity to the appliance before you install grate, volcanic stone, embers and logs. This appliance is not designed to burn wood.
Any attempt to do so could cause irreparable damage to the appliance and prove hazardous to your safety. If logs are not installed according to the log
installation instructions, flame impingement and improper combustion could occur and result in soot and/or excessive production of carbon monoxide (CO), a colorless, odorless, toxic gas.
REFERENCE - Firebox Accessories / Parts
Cat. No. Model Description
88L53 FGE Bag of Glowing Embers 80L42 FDVS Bag of Volcanic Stone
Figure 31
For Propane Gas Only, Do Not Place Embers On Main Ports
Step 1. Install the ceramic panels per the instructions provided in kit
(reference form #750182M).
Step 2. Place the volcanic stone around the burner as shown in Figure
33.
Step 3. Separate the glowing embers (rockwool) into pieces about the
size of a quarter (see Figure 31). Keep the pieces uffed, not matted. Distribute these pieces over the burner as shown in
Figure 32. Do not use more than necessary. When properly
positioned, the Glowing Embers will cover approximately 75% of the burner on natural gas. For propane gas, do not place embers on main ports.
Note: Excessive use of embers may result in sooting or poor flame. This appliance is provided with enough Glowing Embers for several applications, do not feel compelled to use all that is in a new bag. For best glowing effect, replace the ember material annually. Replacement Glowing Embers are available (Catalog Number 88L53).
Step 4. Position the individual logs as shown in Figures 34 through 38.
Logs should be placed in the order shown. Place logs 2 and 3 against the pins on the grate, NOT over them.
Proper log and twig placement is critical to encourage outstand-
ing flame appearance and prevent sooting. When positioned
properly as shown, twigs will be positioned between ame
peaks and will not impinge any flames. Positioning is the same for all colors of log sets.
Glowing Embers (Rockwool)
Figure 32
Volcanic Stone
Figure 33 - (LSM45-PV Shown)
22
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
LSM40-PV and LSM45-PV Log Placement
2
6
Figure 34
3
7
5
1
Log Number Description
1 Log, Center
2 Log, Rear
3 Log, Center/Left 4 Log, Center/Right
5 Log, Rear/Top
6 Log, Front/Left
7 Log, Front/Center
2
4
Figure 36
Align Groove At The Bottom Of Log (2) Over The Grate And Push It Towards The Rear.
3
4
Figure 35
1
Align Two Holes At Bottom Of Log (1) Over The Pins On The Gas Burner.
Engage Logs (3 & 4) With The Grate Pins And Align Groves At The Bottom Of The Logs Over The Grate.
Figure 37
6 5
Engage Log (6) With The Grate Pin And Align Groove At The Bottom Of The Log Over The Grate.
Align Hole At Bottom Of Log (5) Over The Pin On Log (2).
Engage Log (7) With The Pin On Log (4).
Figure 38
7
2
4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
23
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Glass Door Latch (2)
Glass Door Assembly
Firebox Floor
Top Flange Glass Door Frame Assembly
Screws
Step 10. INSTALLATION AND REMOVAL OF GLASS DOOR
When reinstalling the glass
door, the door latch screws must be securely tightened to prevent the glass door from falling out, which could potentially cause damage and possible injury.
Do not attempt to substitute the
materials used on this door, or replace cracked or broken glass.
Handle this glass with extreme
care! Glass is susceptible to damage – Do not scratch or handle roughly while reinstall­ing the glass door frame.
The glass door of this appli-
ance must only be replaced as a complete unit as provided by the manufacturer. Do not attempt to replace broken, cracked or chipped glass sepa­rately.
Do not attempt to touch the
front enclosure glass with your hands while the fireplace is in use.
Do not operate appliance with the glass front removed, cracked or broken.
AVERTISSEMENT
Ne pas utiliser l'appareil si le panneau frontal en verre n'est pas en place, est craqué ou brisé.
WARNING
WARNING
Only doors certified with the appliance shall be used.
Seules des portes certifiées pour cet appareil doivent être utilisées.
CAUTION: DO NOT abuse glass door by striking or slamming shut.
Retrieve the glass door. Visually inspect the
gasket on the backside of the frame. Gasket surface must be clean, free of irregularities
and seated firmly.
Position the door in front of the rebox opening
with the top of the door held away from the fireplace (Figure 39). Lower the bottom of the
door assembly on the bottom door track and
set on padded surface. Pivot the door up after
engaging and centering in the base channel.
Using a Phillips screwdriver, fasten the door
frame to the door latch with the two (2) screws.
The latch should pull forward to engage the door frame.
Install the door modesty shield on top flange
glass door as follows: grab the door modesty shield with both hands, with the open hem
going down and engage it with the upper lip
of the glass door frame by pushing it all the way down. Make sure the installed shield is
firmly in place.
With the firescreen hanging on the screen rod,
insert the right side of the rod into the existing hole on the right modesty panel. Bend down
the rod at the center and drop the left end into
the slot on the left modesty panel, being careful
not to scratch the paint.
Figure 39 ­INSTALLING THE GLASS DOOR
Step 11. BURNER ADJUSTMENTS
Flame Appearance and sooting
Proper flame appearance is a flame which is
blue at the base and becomes yellowish-orange in the body of the ame.
When the appliance is first lit, the entire flame
may be blue and will gradually turn yellowish-
orange during the first 15 minutes of operation. After 15 minutes of operation, if the flame is
blue, or if the ame is orange with evidence of sooting (black tip), the air shutter opening may need to be adjusted.
If the air shutter opening is closed too far, sooting may develop. Sooting is indicated
by black puffs developing at the tips of very long orange ames. Sooting results in black
deposits forming on the logs, appliance inside
surfaces and on exterior surfaces adjacent to
the vent termination.
Sooting is caused by incomplete combustion in the ames and lack of combustion air enter-
ing the air shutter opening. To achieve a warm
yellowish-orange ame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, rst check
the log set positioning to ensure that the flames are not impinging on any of the logs. If the log set is properly positioned and a
sooting condition still exists, then the air shutter opening should be increased.
• The more offsets in the vent system, the larger the air shutter opening will need to be.
• An appliance operated with the air shutter
opened too far, may have flames that appear
blue and transparent. These weak, blue and
transparent flames are termed anemic.
• Units converted for use with Propane gas may exhibit ames which candle or appear stringy. If this is present and persists, adjust
the air shutter to a more closed position, then operate the appliance for a few more minutes to ensure that the flame normalizes and the flames do not appear sooty.
The following chart is provided to aid you in
achieving the correct air shutter adjustment
for your installation.
Air Shutter Adjustment Guidelines:
Amount of
Primary Air
If air shutter is closed too far
If air shutter is open too far
Flame
Color
Flame will be orange
Flame will be blue
Air Shutter
Adjustment
Air shutter gap should be increased
Air shutter gap should be decreased
24
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Burner Air Shutter Adjustment Procedure
WARNING
Air shutter adjustment should only be performed by a quali­fied professional service technician.
Ensure that the front glass
door assembly is in place and sealed After adjustment.
CAUTIONS
Main Burner Factory Air Shutter
Opening Setting - Inches (millimeter)
Model Natural
LSM40-PV
LSM45-PV
1/8 (3.18) 1/4 (6.35) 1/8 (3.18) 1/4 (6.35)
Gas
Propane
Gas
Burner
Air Shutter Opening
Venturi
Orifice
Gas Valve
Soot will be produced if the
air shutter is closed too much. Any damage due to carboning resulting from improperly setting the air shutter is not covered under the warranty.
To adjust the ame, rotate the air shutter toward the back or toward the front of the replace.
Position the air shutter to the factory setting as
shown in the table in Figure 40. Allow the burner to operate for at least 15 minutes. Observe the
flame continuously. If it appears weak or sooty
as previously described, adjust the air shutter
until the flame appearance is as desired.
Use the extension knob (refer to Figure 28 on Page 21), to adjust the flame height as
desired, by sliding the knob over the variable flame adjustment knob located on the front of the valve. Replace the extension knob back to the hanger after the adjustment.
Units converted for use with propane gas may
exhibit a ame pattern that may candle or ap­pear stringy. If this is problematic or persists as the appliance is continually operated, adjust the air shutter open as described in the previous
paragraphs. Operate the appliance for a period of time as the effect diminishes, ensuring that the appliance does not develop sooty flames. When satisfied that the appliance operates properly, proceed to finish the installation.
Figure 40
(Birch Logs Shown) LSM40-PV
Figure 41 - Burner Flame Appearance
(Rustic Oak Logs Shown) LSM45-PV
Venturi
Leave the control knob in the ON position and
the remote switch OFF.
Note: See Figures 41 and 42 for proper burner flame appearance.
Figure 42 - Burner Flame Appearance
25
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Glass Door
Assembly
Fireplace
Finish Combustible Or Non-Combustible Material
Bottom Of Fireplace
1/8 Inch Minimum
Door Track
Finish Combustible Or Non-Combustible Material
Front Face Of Fireplace
Floor Panel
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
FINISHING REQUIREMENTS Wall Details
Complete finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thickness of the finished wall (Figure 43).
3" Min.
(76 mm)*
Combustible Finished Wall Materials
Header (2x4’s)
Combustible materials are allowed above this point on the face of the appliance.
8-3/8" Min.
(213 mm)
The gray shaded area must be non-combustible or Dura Rock
1" (25.4mm) Minimum
Top of
Appliance
Spacers
Adaptor Plus 4
Feet Vertical
Vent (Min.)
& 90° Elbow
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with the exceptions.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (see Figure 5 on Page 8). Mantels constructed of non-combustible materials may be installed at any height above the
appliance opening.
Combustible materials may project beyond the side of the replace
opening as long as it is kept within the shaded area illustrated in Figure 6 on Page 8.
Top of Door Frame
Fireplace (right side)
* Insulation is NOT ALLOWED in the clearance zones around vent compo-
nents. Keep this area free from combustible materials.
Figure 43
A hearth extension is not required with this appliance. If a hearth extension is used, there are two methods of installation. One, the nish combustible or non-combustible material could be ended by butting up against the
front face of the fireplace and the floor panel (refer to Figure 44).
Two, the nish combustible or non-combustible material could be ended below the replace (refer to Figure 45). Remove the floor panel as shown in Figure 44 by removing the screws on the right side of the panel and sliding the left side away from the tab. Discard the screws and oor panel.
It is critical that there is at least a 1/8" gap between the bottom of the door track and the surface of the finish material.
Figure 44
Figure 45
26
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Step 12. ATTACHING SAFETY-IN-OPERATION WARNINGS It is the installers responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this appliance.
ATTACHING SAFETY-IN-OPERATION WARNINGS
It is required that the safety instruction labels furnished with the replace be afxed to the op-
eration and control point of the fireplace. A safety
instruction label must be afxed to the wall switch
plate where the fireplace is turned on and off (See Figure A) or wall thermostat (See Figure B) and if used on the remote control handheld transmitter (Figure C). To properly complete the installation of
this replace, locate the multi-lingual adhesive labels
provided with the Care and Operation Instructions and proceed as follows:
1. Locate the wall switch or wall thermostat that controls the fireplace (verify the switch operates
the replace by turning it on and off). Clean the
wall switch plate or wall thermostat thoroughly
to remove any dust and oils. Afx the label to
the surface of the plate of the wall switch that controls the fireplace (Figure A) or the wall thermostat (Figure B). Choose the language
primarily spoken in the home. If unknown, afx the English language label.
2. If a remote control is used to control the fireplace, locate the transmitter and clean it thoroughly
to remove any dust and oils. Afx the label to
the surface of handheld transmitter (Figure C). Choose the language primarily spoken in the
home. If unknown, afx the English language label.
3. If you are unable to locate the labels, please call Lennox Hearth Products or your nearest Lennox
Hearth Products dealer to receive additional
safety instruction labels free of charge.
Cat. No. H8024 Replacement Label Kit
LENNOX HEARTH PRODUCTS 1-800-9-LENNOX
Note: English is red text on clear label. French and Spanish are white text on black label.
APPOSITION DES MISES EN GARDE RELATIVES À LA SÉCURITÉ D’UTILISATION
Il est impératif que les étiquettes de sécurité fournies avec le foyer soient collées à côté des dispositifs de contrôle du foyer. Une étiquette de sécurité doit être collée sur la plaque de l’interrupteur contrôlant l’allumage du foyer (voir Figure A) ou sur le thermostat mural (voir Figure B) et, le cas échéant, sur le boîtier de la télécommande (Figure C). Pour achever l’instal- lation correcte de ce foyer, procédez comme suit avec les étiquettes adhésives en langues étrangères fournies avec les instructions d’utilisation et d’entretien :
1. Repérez l’interrupteur ou le thermostat mural qui contrôle le foyer (vérifiez que l’interrupteur contrôle le fonctionnement du foyer en le faisant
basculer de Marche à Arrêt, et vice-versa). Nettoyez
soigneusement la plaque murale de l’interrupteur ou le thermostat mural pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur la surface de la plaque de l’interrupteur mural qui contrôle le foyer (Figure A) ou du thermostat mural (Figure B). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
2. Si une télécommande est utilisée pour contrôler le foyer, nettoyez la soigneusement pour éliminer la poussière et les traces de graisse ou d’huile.
Collez l’étiquette sur le boîtier de la télé-
commande (Figure C). Choisissez la langue qui est principalement parlée dans la résidence du proprié­taire. En cas de doute, collez l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez
appeler Lennox Hearth Products ou votre distribu­teur Lennox Hearth Products local pour recevoir
gratuitement des étiquettes supplémentaires.
Étiquettes de remplacement, n° cat. H8024
LENNOX HEARTH PRODUCTS 1-800-9-LENNOX
Remarque : Le texte anglais est rouge sur un support transparent. Le texte français et espagnol est blanc sur un support noir.
COLOCACIÓN DE ADVERTENCIAS DE SEGURIDAD EN OPERACIÓN
Se requiere que las etiquetas de instrucciones de seguridad incluidas con la chimenea se coloquen en
el punto de operación y control de la misma. Se debe
colocar una etiqueta de instrucciones de seguridad en la placa del interruptor de pared desde el cual se enciende y se apaga la chimenea (ver la Figura A) o en el termostato de pared (ver la Figura B) y en el transmisor de control remoto (Figura C) si se usa. Para completar correctamente la instalación de esta chimenea, encuentre las etiquetas adhesivas multilingües incluidas con las instrucciones de cuidado y operación y haga lo siguiente:
1. Identifique el interruptor o el termostato de pared que controla la chimenea (verifique que el interruptor
opera la chimenea encendiéndola y apagándola). Limpie bien la placa del interruptor o el termostato
de pared para quitar el polvo y aceite. Pegue la etiqueta en la superficie de la placa del interruptor que controla la chimenea (Figura A) o en el termostato de pared (Figura B). Seleccione el idioma que
más se habla en la casa. Si no sabe cuál es, use la
etiqueta en inglés.
2. Si se usa un control remoto para controlar la
chimenea, encuentre el transmisor y límpielo bien
para quitar el polvo y aceite. Pegue la etiqueta en la superficie del transmisor (Figura C). Seleccione
el idioma que más se habla en la casa. Si no sabe
cuál es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas, sírvase llamar a
Lennox Hearth Products o al distribuidor de Lennox Hearth Products más cercano para recibir etiquetas
de instrucciones de seguridad adicionales gratuitas.
Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS 1-800-9-LENNOX
Nota: La etiqueta en inglés es transparente con texto rojo. Las etiquetas en francés y español son negras con texto blanco.
SAFETY LABEL
DIAGRAMS
DIAGRAMMES DES ÉTIQUETTES
DE SÉCURITÉ
Figure A Figure B Figure C
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
DIAGRAMAS DE ETIQUETAS
DE SEGURIDAD
27
S
e
a
l
a
n
t
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
INSTALLATION ACCESSORIES
Listed Secure Vent™ Components
Cat. No. Model No. Description
77L70 SV4.5L6
77L71 SV4.5L12
77L72 SV4.5L24
77L73 SV4.5L36
77L74 SV4.5L48
77L75 SV4.5LA
77L76 SV4.5E45
77L77 SV4.5E90
H2246 SV4.5HF
H2247 SV4.5VF
The following flashings come packaged with a storm collar:
H5816
SV4.5-TWSK Through Wall Shield
750,247M
6 inch (152mm) Vent Section
12 inch (305mm) Vent Section
24 inch (610mm) Vent Section
36 inch (914mm) Vent Section
48 inch (1219mm) Vent Section
Telescopic Section
45 Degree Elbow
90 Degree Elbow
Firestop/Spacer ­Horizontal (3 - 1 - 1 spacing) 10 pack
Firestop/Spacer ­Vertical (1 - 1 - 1 spacing) 10 pack
Kit (used to shield the direct-vent pipe from blown insulation) Ref. instr. # 750,247M
Listed Secure Vent / Secure Flex™ Components
Cat. No. Model No. Description
Attic Insulation Shield
H3907 SV4.5RSA
H7748 FVK36
10K81 SFMP Mill-Pac, Black, High
89L40 SFMP-12 Mill-Pac, Black, High
91L66 SF-GC4-6 Gear Clamp 4.5 in. (114
91L67 SF-GC7-6 Gear Clamp 7.5 in.
(adjustable 12” to 22”)
36" Flex Vent Kit
Note: Flex attaches to ap­pliance collar at one end and to rigid venting at the other end.
Temperature Sealant
Temperature Sealant ­Bulk 12 pack
mm) for flex (6 pieces)
(190.5 mm) for flex (6 pieces)
28
96K93 SV4.5SU
96K92 SV4.5SP
Support Strap
Support Plate
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Burner Assembly
Gas Valve Assembly
Orifice
GAS CONVERSION KITS
WARNING
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instruction is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manu­facturer’s instructions supplied with the kit.The qualified service agency performing this installation assumes responsibility for this conversion.
AVERTISSEMENT
Cette trousse de conversion doit être installée par un technicien agréé, selon les instructions du fabricant et selon toutes les exigences et tous les codes pertinents de l’autorité compétente. Assurez-vous de bien suivre les instructions dans cette notice pour réduire au minimum le risque d’incendie, d’explosion ou la production de monoxyde de carbone pouvant causer des dommages matériels, des blessures ou la mort. Le tecnicien agréé est responsable de l’installation de cette trousse. L’installation n’est pas adéquate ni complète tant que le bon fonctionnement de l’appareil converti n’a pas été vérifié selon les instructions du fabricant fournies avec la trousse. Le fournisseur de service qualifié ayant réalisé l'installation assume les responsabilités liées à la conversion.
Gas conversion kits are available to adapt your appliance from the use of one type of gas to the use of another. These kits contain all the necessary components needed to complete the task including labeling that must be affixed to ensure safe operation.
Kit part numbers are listed here and the following steps detail the conversion proce­dure. Refer to the instructions provided with the conversion kit when performing any gas conversion.
Electronic SIT Systems
Natural Gas To Propane Gas
Conversion Kit (Electronic) Model No. Cat. No. LSM40-PV H7934 LSM45-PV H7934
INSTALLATION INSTRUCTIONS
Step 1. TURN OFF THE GAS SUPPLY TO THE APPLIANCE and disconnect power supply at the circuit breaker. Ensure appliance is cold.
CAUTION THE GAS SUPPLY SHALL BE SHUT OFF PRIOR TO DISCONNECTING THE ELECTRICAL POWER, BEFORE PROCEEDING WITH THE CONVERSION.
ATTENTION. AVANT D’EFFECTUER LA CONVERSION, COUPEZ D’ABORD L’ALIMENTATION EN GAZ, ENSUITE, COUPEZ L’ALIMENTATION ÉLECTRIQUE.
Step 2. Remove the front glass door/frame
and the access plate from the appliance. See Figure 39.
Step 3. Carefully remove the logs and the grate
assembly. Exercise care so as not to break the logs.
Step 4. Refer to Figure 46. Remove the burner
assembly with attached venturi tube.
Figure 46
Step 5. Refer to Figure 47 on Page 30 and the instructions provided with the kit. Using a Torx T20 (with 1/4” shank and center hole), remove and discard the three pressure regulator mounting screws. Remove the pressure regu-
lator, spring, poppet, diaphragm and bushing.
Discard all removed components.
Ensure the rubber gasket installed on the back of
the replacement pressure regulator is properly positioned and install the new pressure regula­tor using the new screws supplied with the kit.
Tighten screws to 25 In. lb. torque.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
29
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Pressure
Regulator
Remove These Components
LO
HI
Pressure
Regulator
SIT Electronic Gas Valve
Figure 47
Step 6. Refer to Figure 48 and remove the
pilot hood assembly to access the hexed pilot
orifice. Remove and replace the orifice with the one provided with the kit.
Pilot Orifice
SIT Electronic Pilot
Pilot Orifice
Electronic Pilot Assembly
Figure 48
Step 7. (Refer to Figure 46 on Page 29 and Figure 49)
VERIFY THE PROPER ORIFICE SIZE BE­FORE INSTALLING IT.
A. Remove the orifice from the manifold and
replace it with the one provided in the kit. See
the following table for orice sizes for natural
and propane models. Figure 49 illustrates
the orice. Use pipe joint compound or Teon tape on all pipe ttings before install-
ing (ensure propane resistant compounds are used in propane applications, do not
use pipe joint compounds on are ttings).
B. Retrieve the burner and slide the venturi tube
over the orice. Set the burner assembly
into its position and secure it.
C. Reinstall the grate assembly.
Burner Orifice Size
Elevation 0-2000 ft. (0-610m)
Model Natural Gas Propane Gas
LSM40-PV
LSM45-PV
Table 9
.125" (1/8") *
H7924
.125" (1/8") *
H7924
* Standard size installed at factory
•Part/Cat.Number
.073" (#49)
H7936
.073" (#49)
H7936
Figure 49
Step 8. Reassemble the remaining components by reversing the procedures outlined in the
preceding steps.
Step 9. Attach the conversion label provided
in the conversion kit to the rating plate on the appliance.
Step 10. Turn on gas supply and test for gas leaks. See Test All Connections For Gas Leaks on Page 21.
Step 11. Attach manometer to the manifold side pressure test fitting and verify manifold pressure reads 3.5 inches water column (0.87
kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.
ALWAYS TEST PRESSURES WITH THE VALVE REGULATOR CONTROL AT THE HIGHEST SETTING.
30
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTES
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
31
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design,
materials, specifications, and prices, and also to discontinue colors, styles, and products.
Consult your local distributor for replace code information.
Printed in U.S.A. © 2009 Lennox Hearth Products
P/N 506023-09 Rev. C 06/2011
32
1508ElmHillPike,Suite108•Nashville,TN37210
Loading...