Lennox Hearth LBV-3824MP-H User Manual

Page 1
INSTALLATION INSTRUCTIONS
B-VENT ELITE® SERIES
B-VENTED GAS APPLIANCES P/N 504,137M REV. L 03/2007
This appliance may be installed in an aftermar­ket permanently located, manufactured home (USA only) or mobile home, where not prohib­ited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING: IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO­SION MAY RESULT CAUSING PROPERTY DAM­AGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors or liquids in the vicin­ity of this or any other appliance.
FOR YOUR SAFETY: What to do if you smell gas:
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• DO NOT use any phone in your building.
Follow your gas suppliers instructions.
• If your gas supplier cannot be reached, call the fire department.
MODELS
Millivolt Models Electronic Models
LBV-3824MN LBV-3824EN LBV-3824MP LBV-3824EP LBV-3824MN-H LBV-3824EN-H LBV-3824MP-H LBV-3824EP-H LBV-4324MN LBV-4324EN LBV-4324MP LBV-4324EP LBV-4324MN-H LBV-4324EN-H LBV-4324MP-H LBV-4324EP-H
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE POUR RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE BLESSURE OU LA MORT.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser d'essence ni d'autre vaperurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une odeur de gaz:
• Ne pas tenter d'allumer d'appareil.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones se trouvant dans le batiment où vous vous trouvez.
• Evacuez la piéce, le bâtiment ou la zone.
• Appeflez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service dos incendies.
OTL Report No. 116-F-18-05
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
L'installation et service doit être exécuté par un qualifié installer, agence de service ou le fournisseur de gaz.
1
Page 2
TABLE OF CONTENTS
PACKAGING
GENERAL INFORMATION
Packaging........................................ page 2
Introduction..................................... page 2
General Information......................... page 2
Location .......................................... page 3
Appliance Specifications.................. page 4
Clearances ....................................... page 4
Gas Vent Rule.................................. page 4
Framing Specifications .................... page 5
Assembly Steps............................... page 5
Installation....................................... page 6
Vent System Installation.................. page 7
Field Wiring ..................................... page 7
Connecting Gas Line........................ page 8
Outside Air Kit Installation ............... page 8
Log and Rockwool Installation ........ page 9
Appliance Operation ........................ page 10
Manual Limit Switch........................ page 10
Millivolt Appliance Checkout............ page 11
Electronic Appliance Checkout......... page 11
Adjustments .................................... page 11
Finishing Requirements................... page 12
Cold Climate Insulation.................... page 12
Installation Accessories................... page 12
Gas Conversion Kits.................. page 13
This installation manual will help you obtain a safe, efficient, dependable installation for your appliance and vent system.
Please read and understand these instructions before beginning your
installation.
2
The assembled vented gas fireplace is pack­aged with:
1 -one cartoned log set located in firebox
area.
2 - one bag of glowing embers (rockwool)
located in the bottom compartment.
3 - one envelope containing the literature
package which consists of the homeowner's manual, installation instructions, and war­ranty; envelope is located in the control area.
4 - one B-Vent Connector taped to the top of
the unit.
INTRODUCTION
The millivolt appliances are designed to oper­ate on either natural or propane gas. A millivolt gas control valve with piezo ignition system provides safe, efficient operation.
The electronic appliances are designed to op­erate on either natural or propane gas. An electronic intermittent pilot system provides safe, efficient operation. External electrical power is required to operate these units.
These appliances comply with National Safety Standards and are tested and listed by Omni­Test Laboratories (Report No. 116-F-18-5) to ANSI Z21.50b-2002 (in Canada, CSA-2.22b-
2002), and CAN/CGA-2.17-M91 in both USA and Canada, as vented gas fireplaces.
Installation must conform to local codes. In the absence of local codes, installation must comply with the current National Fuel Gas Code, ANSI Z223.1 (NFPA 54). (In Canada, the current CAN/CGA B149 installation code.) Elec­trical wiring must comply with local codes. In the absence of local codes, installation must be in accordance with the National Electrical Code, NFPA 70 - (latest edition). (In Canada, the current CSA C22.1 Canadian Electric Code.)
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
WARNING: IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL. FOR ASSISTANCE OR ADDI­TIONAL INFORMATION CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Note: Installation and repair should be per­formed by a qualified service person. The appli­ance should be inspected annually by a quali­fied professional service technician. More fre­quent inspections and cleanings may be re­quired due to excessive lint from carpeting, bedding material, etc. It is imperative that the control compartment, burners and circulating air passage ways of the appliance be kept clean.
S'assurer que le brùleur et le compartiment des commandes sont propres. Voir les instruc­tions d'installation et d'utilisation qui accompagnent l'apareil.
Provide adequate clearances around air open­ings and adequate accessibility clearance for service and proper operation. Never obstruct the front openings of the appliance.
WARNING: THESE FIREPLACES ARE VENTED DECORATIVE GAS APPLIANCES. DO NOT BURN WOOD OR OTHER MATE­RIAL IN THESE APPLIANCES.
These appliances are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the performance of this system and may be dan­gerous.
Input of appliances are 45,000 and 50,000 BTU/ HR for LBV-3824 and LBV-4324 respectively.
Gas Orifice Size
Type Elevation
LBV-3824
LBV-4324
Nominal operating pressures for the manifold side of the gas control system are; 3.5 inches water column (0.87 kPa) for natural gas mod­els and 10 inches water column (2.49 kPa) for propane gas models.
Do not use these appliances if any part has been under water. Immediately call a qualified, pro­fessional service technician to inspect the ap­pliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas se servir de cet appareil s'il a été plongé dans l'eau, complètement ou en partie. Appeler un technicien qualifié pour inspecter l'appareil et remplacer toute partie du système de contrôle et toute commande qui ont été plongés dans l'lau.
Natural
0.125 in.
#30
Propane
#48
#47
0 - 4500' (0 - 1370 m)
0 - 4500' (0 - 1370 m)
Page 3
This appliance may be installed in an after­market permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not con­vertible for use with other gases, unless a certified kit is used.
Cet appareil peut être installé dans un maison préfabriquée (É.-U. seulement) ou mobile déjà installée à demeure si les réglements locaux le permettent. Cet appareil doit être utilisé uniquement avec les types de gaz indiqués sur la plaque signalétique. Ne pas l'utiliser avec d'autres gaz sauf si un kit de conversion certifié est installé.
Millivolt appliances may be fitted at time of manufacture with either a Honeywell millivolt gas control valve or as SIT millivolt gas control valve. Both valves have been tested with and approved for use with these appliances and are listed accordingly.
Test gage connections are provided on the front of the millivolt gas control valves (identified OUT for the manifold side and IN for inlet pressure side for both SIT and Honeywell equipped appli­ances. A ¹⁄₈" NPT test gage connection is pro­vided on the electronic gas control valve adja­cent to the outlet to the main burner.
Minimum inlet gas pressure to the appliance is
5.0 inches water column (1.24 kPa) for natural gas and 11 inches water column (2.74 kPa) for propane for the purpose of input adjustment.
Maximum inlet gas supply pressure to the appliance is 10.5 inches water column (2.61kPa) for natural gas and 13.0 inches water column (3.23 kPa) for propane.
The appliance must be isolated from the gas supply piping system (by closing its individual manual shut-off valve) during any pressure testing of the gas supply piping system at test pressures equal to or less than ¹⁄₂ psig (3.5) kPa).
The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at pressures in excess of ¹⁄₂ psig (3.5 kPa).
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
Do not place clothing or other materials on or near this appliance.
WARNING: FAILURE TO COMPLY WITH THE INSTALLATION AND OPERATING IN­STRUCTIONS PROVIDED IN THIS DOCU­MENT WILL RESULT IN AN IMPROP­ERLY INSTALLED AND OPERATING AP­PLIANCE, VOIDING ITS WARRANTY. ANY CHANGE TO THIS APPLIANCE AND/OR ITS OPERATING CONTROLS IS DANGER­OUS. IMPROPER INSTALLATION OR USE OF THIS APPLIANCE CAN CAUSE SERI­OUS INJURY OR DEATH FORM FIRE, BURNS, EXPLOSION OR CARBON MON­OXIDE POISONING.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air immedi­ately. Turn off the gas supply to the appliance and have it serviced by a qualified profes­sional, as it may not be operating correctly.
WARNING: B-VENT APPLIANCES ARE NOT DESIGNED TO OPERATE IN NEGATIVELY PRESSURED ENVIRONMENTS (PRESSURE WITHIN THE HOME IS LESS THAN PRES­SURES OUTSIDE). SIGNIFICANT NEGA­TIVELY PRESSURED ENVIRONMENTS CAUSED BY WEATHER, HOME DESIGN, OR OTHER DEVICES MAY IMPACT THE OPERATION OF THESE APPLIANCES. NEGATIVE PRESSURES MAY RESULT IN POOR FLAME APPEARANCE, SOOTING, DAMAGE TO PROPERTY AND/OR SEVERE PERSONAL INJURY. DO NOT OPERATE THESE APPLIANCES IN NEGATIVELY PRES­SURED ENVIRONMENTS.
WARNING: CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES. USE CAUTION AROUND THE APPLIANCE TO AVOID BURNS OR CLOTHING IGNITION. YOUNG CHILDREN SHOULD BE CARE­FULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
WARNING: DO NOT PLACE CLOTHING OR OTHER FLAMMABLE MATERIALS ON OR NEAR THIS APPLIANCE.
AVERTISSEMENT: SURVEILLER LES ENFANTS. GARDER LES VÊTEMENTS, LES MEUBLES, L'ESSENCE OU AUTRES LIQUIDES À VAPEUR INFLAMMABLES LIN DE L'APPAREIL.
WARNING: THIS APPLIANCE MAY ONLY BE FITTED WITH DOORS CERTIFIED FOR USE WITH THE APPLIANCE.
AVERTISSEMENT: POUR UTILISATION UNIQUEMENT AVEC LES PORTES EN VERRE CERTIFIÊES AVEC L'APPAREIL.
These appliances are equipped with an inte­gral combustion air door and actuator arm. Combustion air kits are optional and must be installed before removing the securing screw allowing the movement of the combustion air actuator arm (see Step 7 on page 8).
LOCATION
Typical Locations
Figure 1
In selecting the location, the aesthetic and func­tional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important. Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies. Consideration should be given to traf­fic ways, furniture, draperies, etc., due to el­evated surface temperatures. The location should also be free of electrical, plumbing or other heating/air conditioning ducting.
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materi­als. However, if installed on combustible mate­rials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bottom surface must be used.
These appliances may be used for bedroom installations in the United States and are listed accordingly. These units may not be installed
in bedrooms in Canada.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3
Page 4
APPLIANCE SPECIFICATIONS
CLEARANCES
15 ¹⁄₂"
Combustion Air Inlet
3 ¹⁄₂"
11 ¹⁄₂"
8"
7 ¹⁄₄"
11"
24 ⁵⁄₈"
49 ³⁄₄"
12 ⁷⁄₁₆"
3824 - 38"
4324 - 43 ¹⁄₂"
3824 - 48"
4324 - 52 ³⁄₄"
Front View
Gas Line Access
3824 - 5"
4324 - 4 ³⁄₈"
6 ¹⁄₂"
10 ¹⁄₂"
3 ¹⁄₄"
44 ¹⁄₈"
44 ¹⁄₈"
49 ³⁄₄"
Minimum clearance to combustibles for the ap­pliance is as follows: sides and back - ¹⁄₂" (13 mm), floor - 0" (0 mm), adjacent wall - 0" (0 mm), ceiling - 37 ¹⁄₂" (953 mm).
Venting
Gas Vent Rule – Gas vent caps are not permit-
ted within 8 feet (2.4 mm) of a vertical wall or similar obstruction. Gas vent caps that are located 8' or more from a portion of a building which extends at an angle greater than 45° upward from the horizontal may terminate in accordance with that in no case shall any discharge opening on the cap be less than 2' (610 mm) horizontally from the roof surface (National Fuel Gas Code ANSI Z223.1 (NFPA 54) 7.6.2) (CAN/CGA B149).
Figure 3
Table 1 (Figure 3)
Roof Pitch is X/12
Minimum Height from Roof to Lowest Discharge Opening
, provided
X
12
4
Figure 2
Electrical Outlet
Left Side View
25 ⁵⁄₈"
9 ³⁄₄"
Junction
Box
3824 - 26 ⁵⁄₁₆" 4324 - 31 ¹⁄₁₆"
8"
B-Vent
3824 - 48"
4324 - 52 ³⁄₄"
Top View
25 ⁵⁄₈"
Gas Line Access
Right Side View
25 ⁵⁄₈"
3824 - ⁵⁄₈" 4324 - ¹⁄₂"
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Minimum Height
from Roof to Lowest
Roof Slope
Discharge Opening
Feet Meters
Flat to 6/12 1' 0" 0.3 Over 7/12 to 9/12 2' 0" 0.6 Over 10/12 to 12/12 4' 0" 1.2 Over 13/12 to 16/12 6' 0" 1.8 Over 17/12 to 21/12 8' 0" 2.4
Note: Venting terminals shall not be recessed into a wall or siding.
Table 1
Page 5
FRAMING SPECIFICATIONS
B
A
Fireplace Framing
Figure 4
FOAK Combustion Air Kit
Figure 5
Optional Locations
FOAK Combustion Air Kit
J
Rough Framing Face
(Unfinished Shown)
Figure 6
Inside Chase
Back Wall of Chase/Enclosure
Including Finising Materials
C
A
Back Wall of Chase/Enclosure
Including Finishing Materials
FATO Adapter (Optional)
Outside Chase
HH
(Unfinished Shown)
C
A
Header
if any
Framing Face
G
Rough
if any
G
Back Wall of Chase/Enclosure
FOAK-4 Combustion Air Kit
Including Finishing Materials
K
D
C A
E
Corner Installation
if any
(Unfinished Shown)
Figure 7
Framing Dimensions
Fireplace Opening Width
3824
A
B
C
D
E
F
G
H
J
K
48 ¹⁄₈"
(1222 mm)
50"
(1270 mm)
26 ¹⁄₄"
(667 mm)
13 ¹⁄₈"
(334 mm)
77 ¹⁄₄"
(1962 mm)
38 ⁵⁄₈"
(981 mm)
25 ⁵⁄₈"
(650 mm)
4"
(102 mm)
11"
(279 mm)
54 ⁵⁄₈"
(1388 mm)
(1343 mm)
(1270 mm)
(2083 mm)
(1041 mm)
(1473 mm)
Note: All framing dimensions calcu­lated for 1/2" dry wall at the appliance face. If sheathing the chase or finish­ing with other thickness materials, cal­culations will need to be made.
Framing Face
4324
52 ⁷⁄₈"
50"
31"
(787 mm)
15 ¹⁄₂"
(394 mm)
82"
41"
25 ⁵⁄₈"
(650 mm)
4"
(102 mm)
11"
(279 mm)
58"
G
Rough
ASSEMBLY STEPS
The typical sequence of installation follows, however, each installation is unique resulting in variations to those described.
1. Construct the appliance framing.
F
2. Route gas supply line to appliance location.
3. Position the appliance.
4. Install the vent system and exterior termina-
tion.
5. Field wire and install operating control switch.
6. Make connection to gas supply.
7. Install (optional) outside Air Kit.
8. Install the logs and rockwool.
9. Checkout appliance operation.
10. Adjust burner to ensure proper flame ap-
pearance.
PRE-INSTALLATION NOTES
The fireplace may be installed directly on a combustible floor or raised on a platform of an appropriate height. Do not place fireplace on carpeting, vinyl or other soft floor coverings. It may, however, be placed on flat wood, ply­wood, particle board or other hard surfaces. Be sure fireplace rests on a solid continuous floor or platform with appropriate framing for sup­port and so that no cold air can enter the room from under the fireplace.
The fireplace may be positioned and then the framing built around it, or the framing may be constructed and the fireplace positioned into the opening.
Usually, no special floor support is needed for the fireplace, however, to be certain:
1. Estimate the total weight of the fireplace system and surround materials such as brick, stone, etc., to be installed.
2. Measure the square footage of the floor space to be occupied by the system, surrounds and hearth extensions.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3. Note the floor construction, i.e. 2 x 6s, 2 x 8s or 2 x 10s, single or double joists, type and thickness of floor boards.
5
Page 6
4. Use this information and consult your local building code to determine if you need addi­tional support.
If you plan to raise the fireplace and hearth extension, build the platform assembly then position fireplace and hearth extension on top. Secure the platform to the floor to prevent possible shifting.
INSTALLING THE FIREPLACE
Step 1. Construct the Appliance Framing -
Frame appliance enclosure as illustrated in
Figures 4 through 7 on page 5
Note: The framed depth, 25 a framed wall, must always be measured from a finished surface. If a wall covering such as drywall is to be attached to the rear wall, then the 25
⁵⁄₈
"
(650 mm) must be measured from the drywall surface. It is important that this dimension be exact.
.
⁵⁄₈
"
(650 mm) from
An external regulator must be used on all propane (L.P.G.) heaters to reduce the supply tank pressure to 13" w.c. (maximum). Any copper tubing used to supply propane (L.P.G.) from the tank must be internally tinned.
IMPORTANT: HOLD GAS VALVE SECURELY TO PREVENT MOVEMENT WHEN CONNECT­ING TO INLET GAS LINE
WARNING: CONNECTING DIRECTLY TO AN UNREGULATED PROPANE (L.P.G.) TANK MAY CAUSE AN EXPLOSION.
All appliances are equipped with a gas flex line and shutoff valve attached directly to the gas control valve. To quickly and easily complete the gas line routing, use the gas flex line kit.
Step 3. Position the Appliance - Slide the fireplace into prepared framing or position fire­place in its final position and frame later.
IMPORTANT: UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS
FIGURE 2 )
BE REMOVED OR MODIFIED, NOR
(refer to
MAY YOU NOTCH THE HEADER TO FIT AROUND OR BE INSTALLED LOWER THAN THE SPACERS. THE HEADER MAY BE IN DI­RECT CONTACT WITH THE TOP SPACERS BUT MAY NOT BE SUPPORTED BY THEM.
Fireplace should be secured to side framing members using the full length ¹⁄₂ inch nailing flanges that are integral to the appliance at each side. Use 8d nails
(Figure 9 )
8d Nail
.
If the appliance is to be elevated above floor level, a solid continuous platform must be constructed.
The header may rest on the top metal spacers, but must not be notched to fit around them.
Consult all local codes. Step 2. Route Gas Supply Line - Route gas
line
(Figure 8 )
using techniques and materials prescribed by local and/or national codes. It is recommended that a gas line of ¹⁄₂" or greater diameter be used to allow full gas volume to the fireplace. Undue pressure loss will occur if the pipe is too small. The appliance, as set up at the factory, is best suited for use with a gas line routed from the left side. The gas line may however be alternately routed from the right side.
When rigid pipe is used, an ANSI approved manual shut-off valve and union must be in­stalled upstream of the fireplace.
Ensure that a sediment trap is installed in the existing gas line, if not, install a sediment trap upstream to prevent moisture and contami­nants from passing through trap to the appli­ance controls and burners. Failure to do so could prevent the appliance from operating reliably.
LEFT SIDE
7 ¹⁄₄"
(184 mm)
3 ¹⁄₂"
(79 mm)
RIGHT
SIDE
10 ¹⁄₂"
(269 mm)
3 ¹⁄₂"
(79 mm)
Figure 8
Refer to fireplace drawings and specifications on
pages 4 and 5
for framing dimensions and details. Framing header may be positioned directly on the fireplace top spacers.
Figure 9
Fireplace may be anchored to floor. Bend down four (4) anchor tabs located at the base of the fireplace and secure to the floor by nailing with
(Figure 10 ).
8d nails
Anchor Tab
Figure 10 Note: The nailing tabs and the area directly
behind the nailing tabs are exempt from the clearances described on the fireplace clearance label.
6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 7
Step 4. Install the Vent System & Exterior Termination -
A - Connect the factory-supplied B-Vent con-
nector (found taped to the top of the unit) as shown in
Figure 11
. Press it into the lanced protrusions internal to the flue outlet collar as far as the horizontal rolled seam located on the lower part of the connector, and secure with four sheetmetal screws (# 8 or larger).
B - Slip an 8" (203 mm) B-Vent system over the B-Vent connector and secure with four sheetmetal screws (# 8 or larger), and install the remainder of the B-Vent to the outside. Minimum overall height of the vent system and appliance must be 12' (3.66 m) vertical (no offset) or 17' (5.18 m) when an offset up to 45 degrees from the vertical is used. The lower part of the offset must not begin less than 3' (0.914 m) above the top of the fireplace
(see Figure 12 )
.
Maximum overall height of the vent system and appliance should not exceed 40 feet (12.19m).
8
Type B-Vent
Securing
Screws
Factory-Supplied B-Vent Connector
Securing
Screws
Lanced Flue
Outlet Collar
Figure 11
Install the B-vent system in accordance with the vent manufacturer's instructions.
CAUTION: THIS APPLIANCE CANNOT BE VENTED HORIZONTALLY.
Note: Refer to the vent manufacturers instal-
lation instructions for variations of venting techniques. If common venting of several units is contemplated, it should be discussed with an architect and the local Building Depart­ment.
12 ft.
Minimum
Figure 12
Step 5. Field Wiring – Refer to Section A for
millivolt appliances and Section B for electronic appliances.
A. Millivolt Wiring Units may be fitted at the factory with either a Honeywell millivolt gas control valve or an SIT millivolt gas control valve. Both valves have been tested with and approved for use with these appliances and are listed accordingly. Refer to wiring of Honeywell systems and
Figure 13
Figure 14
for
for
wiring of SIT systems. The gas valve has been set in place and has been
pre-wired at the factory. No additional wiring is required unless the optional wall switch or op­tional remote control kit is to be installed. Locate the optional wall switch or optional remote con­trol in the desired location and connect the millivolt wire
(see Figures 13 and 14 ).
CAUTION: DO NOT CONNECT THE WALL SWITCH TO A 120V POWER SUPPLY.
Honeywell Millivolt Wiring Diagram
If any of the original wire as supplied must be replaced, it must be replaced with Type A WM 200°C – 18 GA. wire.
BK
WT
*
TH
BK
TH
TPTH
TP
TH
TP
TP
Thermopile
* For Wall Switch Attachment Only.
Limit
Switch
Damper
Switch
BK
BK
Figure 13
45 degrees
max.
17 ft.
Minimum
3 ft.
Minimum
to Offset
SIT Millivolt Wiring Diagram
If any of the original wire as supplied must be replaced, it must be replaced with Type AWM 200°C – 18 GA. wire.
Damper Switch
BK
BK
Limit Switch
BK
* For Wall Switch Attachment Only.
Thermopile
BK
*
WHT
TP
TP
Figure 14 Note: Optional wall switch not supplied. If the
optional wall switch is not installed, the ends of the 18' coiled wire must be connected with a wire nut (not supplied) for the appliance to operate.
B. Electronic Wiring The electronic appli- ance must be connected to the main power supply. To install, route a 3-wire 120V 60Hz power supply to the appliance junction box and ground. Locate and install a low voltage (24V) wall switch (not supplied) in the desired location. Connect the low voltage wire to this
(see Figure 15 on Page 8 ).
switch
IMPORTANT: Ground lead must be connected to the green screw located on the outlet box.
Figure 18 on page 9
See
. Failure to do so will result in a potential safety hazard. The ap­pliance must be electrically grounded in accordance with local codes or, in the ab­sence of local codes, the National Electrical Code, ANSI/NFPA 70-(latest edition). (In Canada, the current CSA C22-1 Canadian Electrical Code.)
TH
TH
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
7
Page 8
Electronic Wiring Diagram (Honeywell)
(Optional ON/OFF Switch Wiring)
1. If any of the original wire as supplied must be replaced,
1. it must be replaced with Type AWM 200°C – 18 GA. wire.
2. 120V, 60Hz – Less than 3 amps.
BK
BK
R
Gas Valve
CONTROL
BL
OPT FAN
Tab Intact
Green Ground Screw
WT
OPTIONAL
ON/OFF
SWITCH OR
WALL SWITCH
Factory Wired
IGNITER
BK
W
Neutral Side of Receptacle
BL
PILOT
ASSEMBLY
Green
B
R
BK
DAMPER
SWITCH
White
Black
G
Ta b
Broken Red Hot
Side of Receptacle
BK
Transf. 120 V.
24 V
LIMIT
SWITCH
G
r
-
lartueN
120 VAC - Black
Junction Box
Optional
Accessory
Switch
BK
Field Wired
Figure 15
1. Route a 3-wire 120V 60Hz power supply line
to the appliance junction box wires and ground
(Figures 15 ).
2. After wiring is complete, replace the appli-
ance junction box cover and secure with the hex head screws previously removed.
Step 6. Connecting Gas Line Make gas line connections. All codes require a shut-off valve mounted in the supply line.
on page 9
illustrates two methods for con-
Figure 18
necting the gas supply. The flex-line method utilizing the gas flex line provided with the appliance is acceptable in the U.S., how­ever, Canadian requirements vary depend­ing on locality. Installation must be in com­pliance with local codes.
The gas control valve is located in the lower control compartment. To access the valve remove the refractory access panel and set aside
(Figure 16 ).
The millivolt control valve has a ³⁄₈" (10 mm) NPT thread inlet port. The electronic control valve has a ¹⁄₂" (13 mm) NPT thread inlet port and is fitted with a ¹⁄₂" x ³⁄₈" (13 mm
neerG-dnuo
x 10 mm) NPT fitting. Plan connections not
e
tihW
utilizing the ³⁄₈" NPT open end of the gas flex line shutoff, accordingly.
SIT Valve Shown
Refractory Access Panel
Figure 16
Secure all joints tightly using appropriate tools and sealing compounds (ensure pro­pane resistant compounds are used in propane applications).
Turn on gas supply and test for gas leaks, using a gas leak test solution (also referred to as bubble leak solution).
Note: Using a soapy water solution (50% dish soap, 50% water) is an effective leak test solution but it is not recommended, because the soap residue that is left on the pipes/ fittings can result in corrosion over time. Never
use an open flame to check for leaks. A. Light the appliance (refer to the lighting
instructions label in the control compartment or in the Homeowner's Care and Operation Instructions).
C. When the gas lines are tested and leak free, be sure to rinse off the leak testing solution.
D. When the gas lines are tested and leak free, observe the individual tongues of flame on the burner. Make sure all ports are open and producing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.
Step 7. Outside Air Kits Optional combustion (outside make-up air) kits, Model FOAK-4 or FAOK-4LD, may be used with these appliances. Refer to the installation instructions packaged with the air kits for specific installation informa­tion. If used, the outside air kit must be installed before the fireplace is framed and enclosed in the finished wall.
Outside air drawn into the fireplace supplies air to the fire for combustion. Only one combus­tion air duct on the left side of the fireplace is necessary if installed.
If additional length of duct is necessary, pur­chase locally available U.L. Class 0 or Class 1 metallic ducting. The duct may extend up to 50' (15.24 m) in any direction.
Note: When installing the air duct vertically, DO NOT terminate the duct closer than 3' below the
chimney top.
There is one hand operated shut-off valve lo­cated in the left side of the fireplace opening behind the screen. To open, pull the handle out. The combustion air damper should be fully open when the fireplace is in use and fully closed when the fireplace is not in operation to prevent outside air from entering your home.
B. Brush all joints and connections with the gas leak test solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob to the OFF posi­tion. Either tighten or refasten the leaking connection and retest as described above.
8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 9
Note: Supply wires may be alternatively connected to the outlet using the screw terminals, however the black supply wire must be wired to a terminal that is opposite (across the outlet) the point where the white supply wire is connected.
CAUTION: NEVER LOCATE INLET WHERE IT CAN BE BLOCKED BY SHRUBS, SNOW DRIFTS, ETC. NEVER LOCATE INLET IN GA­RAGE OR ANY AREA WHERE THERE IS AN­OTHER FUEL BURNING APPLIANCE OR PROD­UCTS EMITTING COMBUSTIBLE GASES SUCH AS PAINT, GASOLINE, ETC. IN COLD CLI­MATES, IT IS RECOMMENDED THE COMBUS­TION AIR DUCT BE INSULATED.
120 Vac 60 Hz
Figure 17
¹₂" x ³₈" Flare Shut-Off Valve
Ground Wire Connection
White (Supply)
Black (Supply)
Gas Flex Line (provided)
Bipolar Terminal Screw
Gas Valve (Millivolt or Electronic)
Outside combustion air ducting may be run upwards or vertically through framing and ceil­ing joists, with the hood installed through an outside wall and 3' (1 m) below the termination. Ducting may also be run downward through floor joists and under the home to a ventilated crawlspace not considered part of the living area of the home.
After installing the outside air kit, remove the cover from the shut off lever in the left side of the firebox opening.
Note: Do not terminate combustion air kit in attic space under any circumstances.
After completing the installation of the optional combustion air vent system the actuator arm must be put in service and tested to ensure proper operation before completing any enclo­sure around the firebox. Failure to do so may result in extensive and costly rework.
Operate the actuator through several cycles including the closed position. Ensuring proper operation and freedom of movement. Return the actuator arm to the closed position.
Gas Stub
Figure 18
³₈" Flex Tubing
(may be required in some areas, consult local codes.)
Note: ¹₂" NPT At Inlet Of Gas Valve For Electronic Models.
Alternate Hard Piping
³₈" Close Nipple
³₈" Shut-Off Valve
¹₂" x ³₈" Reducer
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
³₈" Union
³₈" Nipple
³₈" NPT Flare Fitting
(Remove Before Hard Piping)
Step 8. Installing Logs and Rockwool – The
logs are packaged within the firebox. The bag of rockwool is in the lower control compartment. Remove the rockwool from the packaging and tear into dime size pieces (see Homeowners Care and Operation Instructions). Do not use more than is necessary.
9
Page 10
Typical Log Set (Refer to Owners Manual for Details)
Piezo Ignitor
Piezo Ignitor
SIT Valve
Subsequent lightings of the appliance will not require such purging. Inspect the pilot flame (remove logs, if necessary, handling carefully).
MANUALLY-RESET BLOCKED FLUE SAFETY SWITCH
This appliance is equipped with a manually­reset blocked flue safety switch. Refer to
Figure 21
for its location. If during appliance operation, the flame goes out (independently of the burner on/off wall switch), it may be due to the operation of this safety limit switch. First allow the appliance to cool. Then reset the safety switch by pushing the red reset button.
Figure 19
Refer to the Homeowners Care and Operation Instructions for detailed log description and placement instructions. Log set shown in this document
(Figure 19)
is typical, installation of
all sets are similar.
APPLIANCE OPERATION
Honeywell Valve
Figure 20
When first lighting the appliance, it will take a few minutes for the line to purge itself of air. Once purging is complete, the pilot and burner will light and operate as indicated in the in­struction manual.
Figure 21
Detail A
Reset
Button
This reset button is located on the back of the limit switch, between the wire terminals (
Detail A of Figure 21
).
see
The appliance should then relight and remain lit. If this does not occur, turn off the appli-
ance and call a qualified service technician.
Wire Terminals
Step 9. Checking the System – With gas line
installed run initial system checkout before closing up the front of the unit. Follow the pilot lighting instructions provided in the Homeowner's Care and Operation Instructions. For piezo ignitor location see
Figure 20
volt appliances only).
Note: Instructions are also found on the pull out lighting instructions label attached to the gas control valve.
10
(milli-
Lintel Extension
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Manual Reset Limit Switch
Right Side Refractory Panel
Page 11
Millivolt Appliance Checkout
The pilot flame should be steady, not lifting or floating. Flame should be blue in color with traces of orange at the outer edge.
The top ³⁄₈" (9 mm) at the pilot generator (thermopile) should be engulfed in the pilot flame. The flame should project 1" (25 mm) beyond the hood at all three ports
Hood
Ignitor Rod
(Figure 22 ).
³⁄₈" Min (9 mm)
Step 10. Adjustments – The following para-
graphs address adjustment concerns and pro­cedures.
Flame Appearance and Sooting
Proper flame appearance is a matter of taste. Generally most people prefer the warm glow of a yellow to orange flame. Appliances operated with air shutter openings that are too large, or with long vertical vent runs, will exhibit flames that are blue and transparent. These weak, blue and transparent flames are termed anemic.
If the air shutter opening is too small sooting may develop. Sooting is indicated by black puffs developing at the tips of very long orange flames. Sooting results in black deposits form­ing on the logs, appliance inside surfaces and on exterior surfaces adjacent to the vent termi­nation. Sooting is caused by incomplete com­bustion in the flames and a lack of combustion air entering the air shutter opening.
Adjustment
To adjust the flame, position the air shutter to the nominal setting
(Figure 24 ).
Allow the burner to operate for at least 30 minutes. Observe the flame continuously. If it appears weak or sooty as previously described, adjust the air shutter open or closed until desired effect is achieved.
Note: If the flame still appears anemic with the air shutter closed all the way (usually a result of lengthy vertical venting runs), turn off the appli­ance, turn off the gas supply, wait for the parts to cool and access the air shutter. The shutter is prevented from actually closing by a tab that is bent over into the opening. Remove this obstruction by bending back. Reassemble and restart the appliance and after 24 minutes reobserve the flame. Adjust the air shutter as described.
Pilot Nozzels
Figure 22
Replace logs if removed for pilot inspection. To light the burner; rotate the gas valve control
knob counterclockwise to the “ON” position (ON will be to the left hand side of the valve). Turn ON the remote wall switch.
Electronic Appliance Checkout
To light the burner, turn ON the optional remote wall switch and turn the gas control switch to the “ON” position. Ensure the ignitor lights the pilot. The pilot flame should engulf the flame rod as shown in
Proper Flame Adjustment
Figure 23.
3/8 To 1/2 Inch
(9 mm to 13 mm)
Ground Electrode
Flame Rod
To achieve a warm yellow to orange flame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
No smoke or soot should be present. Reposi­tion the log set if the flames impinge on any of them.
If sooting conditions exist, the air shutter opening on the main burner can be adjusted. Normally, the more offsets in the vent system, the greater the need for the air shutter to be opened further.
WARNING: AIR SHUTTER ADJUSTMENT SHOULD ONLY BE PERFORMED BY A QUALIFIED PROFESSIONAL SERVICE TECHNICIAN.
Orifice
Air Shutter
Adjusting Set Screw
Burner Tube
Models Shutter Setting
LBV-3824
LBV-4324
Gas
Type
Natural 1/16" (1.59 mm)
Propane 3/16" (4.76 mm)
Natural Closed
Propane 1/4" (6.35 mm)
Factory Air
Inches (mm)
Figure 24
When satisfied that the appliance operates prop­erly, proceed to finish the installation. Leave the control knob/lever in “ON” position and turn the remote switch “OFF.” Replace the refractory access panel.
Figure 23
Hot Surface Igniter
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
11
Page 12
Finished Wall
INSTALLATION ACCESSORIES
The following accessory items are available for use in the installation of this appliance.
12"
Max.
Combustible Mantel and Trim
12"
Min.
Figure 25
Typical Installation
FINISHING REQUIREMENTS Wall Details and Combustible Mantels
Complete finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thick­ness of the finished wall
Figures 25 and 26
shelf projecting a maximum of 12" (305 mm) from the wall, and which must be installed a minimum distance of 12" (305mm) from the top of the firebox opening. No other mantel length/height combinations are allowable for this fireplace.
(Figure 25 )
. Both
show a combustible mantel
Header
Spacer
Non-combustible Wall Covering
Fireplace Opening
Max. Projection 12" (305 mm)
Combustible Mantel
0" Clearance to Combustible Side Wall
12" Min. (305 mm)
60"
(1524 mm)
Min. to Ceiling
Outside Air Kits Models FOAK-4 and FOAK-4LD
Outside Air kits are available with duct (FOAK-4) and without duct (FOAK-4LD) for use if outside combustion air is re­quired or desired. If model FOAK-4LD is used it must be used in conjunction with locally purchased, non-combustible Class 1 or Class 0 flexible duct.
Outside Combustion Air Kits (with duct) 81L87 FOAK-4 (without duct) 81L88 FOAK-4LD
Wall Switch Kit FWSK
A hearth extension is not required with this appliance. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation re­quirements.
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the appliance front face.
Figure 26
COLD CLIMATE INSULATION
If you live in a cold climate, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level.
Wall Switch Kit 85L87 FWSK
12
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 13
Gas Conversion Kits
WARNING: THIS CONVERSION KIT SHALL BE IN­STALLED BY A QUALIFIED SERVICE AGENCY IN AC­CORDANCE WITH THE MANUFACTURER'S INSTRUC­TIONS AND ALL APPLICABLE CODES AND REQUIRE­MENTS OF THE AUTHORIZED AGENCY HAVING JU­RISDICTION. IF THE INFORMATION IN THESE IN­STRUCTIONS ARE NOT FOLLOWED EXACTLY, A FIRE, EXPLOSION OR PRODUCTION OF CARBON MONOX­IDE MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. THE INSTAL­LATION IS NOT PROPER AND COMPLETE UNTIL THE OPERATION OF THE CONVERTED APPLIANCE IS CHECKED AS SPECIFIED IN THE OWNER INSTRUC­TIONS SUPPLIED WITH THE KIT.
In Canada
THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN1-B149.1 AND .2 INSTALLATION CODE.
sledoMepyTtinU.oNgolataC
4283-VBL tlovillim27M77 4234-VBL tlovillim5651H
AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION SERA INSTALLÉ PAR UNE AGENCE QUALIFIÉE DE SERVICE CONFORMÉMENT AUX INSTRUCTIONS DU FABRICANT ET TOUTES EXIGENCES ET CODES APPLICABLES DE L'AUTORISÉS AVOIR LA JURIDICTION. SI L'INFORMATION DANS CETTE INSTRUCTION N'EST PAS SUIVIE EXACTEMENT, UN FEU, EXPLOSION OU PRODUCTION DE PROTOXYDE DE CARBONE PEUT RÉSULTER LE DOMMAGES CAUSER DE PROPRIÉTÉ, PERTE OU BLESSURE PERSONNELLE DE VIE. L'AGENCE QUALIFIÉE DE SERVICE EST ESPONSABLE DE L'INSTALLATION PROPRE DE CET ÉQUIPMENT. L'INSTALLATION N'EST PAS PROPRE ET COMPLÉTE JUSQU'À L'OPÉRATION DE L'APPAREIL CONVERTI EST CHÉQUE SUIVANT LES CRITÈRES ÉTABLIS DANS LES INSTRUCTIONS DE PROPRIÉTAIRE PROVISIONNÉES AVEC L'ÉQUIPEMENT.
-smetsySTIStlovilliM noisrevnoCsaGenaporPoTlarutaN
stiK
sledoMepyTtinU.oNgolataC
4283-VBL tlovillim37M77 4234-VBL tlovillim6651H
stiK
-smetsySTIStlovilliM noisrevnoCsaGlarutaNotenaporP
LA CONVERSION DEVRA ÊTRE EFFECTUÉE CONFORMÉMENT AUX RECOMMANDATIONS DES AUTORITÉS PROVINCIALES AYANT JURIDICTION ET CONFORMÉMENT AUX EXIGENCES DU CODE D'INSTALLATION CAN1­B149.1 ET.2.
Gas conversion kits are available to adapt your appliance from the use of one type of gas to the use of another. These kits contain all the nec­essary components needed to complete the task including labeling that must be affixed to ensure safe operation.
Kit part numbers are listed here and the steps that follow detail the conversion procedure.
sledoMepyTtinU.oNgolataC
4283-VBL tlovillim47M77 4234-VBL tlovillim35L57 4283-VBL cinortcele7651H 4234-VBL cinortcele55L57
-smetsySllewyenoH stiKnoisrevnoCsaGenaporPoTlarutaN
sledoMepyTtinU.oNgolataC
4283-VBL tlovillim57M77 4234-VBL tlovillim45L57 4283-VBL cinortcele8651H 4234-VBL cinortcele65L57
-smetsySllewyenoH stiKnoisrevnoCsaGlarutaNotenaporP
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
13
Page 14
Pilot Orifice
Step 1. Turn off the gas supply to the appli-
ance. Remove the front glass door (if used) from the appliance. Access the control com­partment.
Step 2. Carefully remove the logs. Exercise care as not to break the logs.
Step 5. Honeywell Systems - See
Figure 28
and the instructions provided with the kit. Re­move the black thread-protecting cap. Remove the conversion flip cap by turning it counter­clockwise. Invert the flip cap so that the letters associated with the desired gas type are posi­tioned closest to the valve body.
Step 3. Locate the screws securing the burner (tray) to the appliance. Remove the burner and retain the securing screws.
Millivolt Appliances Step 4. SIT Systems - Refer to
Figure 27
and the instructions provided with the kit. Using a Torx T20, remove and discard the three pres­sure regulator mounting screws. Remove the pressure regulator, spring, poppet, diaphragm and bushing. Discard all removed compo- nents. Ensure the rubber gasket installed on the back of the replacement pressure regulator is properly positioned and install the new pres­sure regulator using the new screws supplied with the kit. Tighten screws to 25 In. lb. torque.
Pressure Regulator
Remove These Components
Figure 27
NG is for natural gas and LP is for propane. Tighten the flip cap by turning it clockwise. Replace the black thread-protecting cap.
Flip Cap Thread
Protector
Figure 28
Step 6. All Millivolt Systems – Attach ma-
nometer to the manifold side pressure test fitting and verify manifold pressure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.
Step 7. See
Figure 29
and remove the pilot hood assembly to access the hexed pilot ori­fice. Remove and replace the orifice with the one provided with the kit.
Figure 29
Electronic Appliances Step 8. Honeywell Electronic Valves - See
Figure 31
and the instructions provided with the kit. Remove the slotted cap screw, o-ring, pressure-regulating adjusting screw and spring. Retain all parts for possible later use. Install new components from the kit. Black cap and red spring for propane gas units. Silver cap and stainless steel spring fro natural gas units. Before installing the cap, attach manometer to the manifold side pressure test fitting and adjust screw until pressure reads
3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.
14
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 15
Pilot Assembly
All Models Step 9. Unscrew the orifice from the manifold
and replace it with the one provided with the kit
.
See the following table for orifice sizes for
natural and propane models.
Figure 32
illus-
trates the orifice.
Pilot Orifice
Flare Nut
Figure 30
CONTROL
I
G N I
T E
Manifold Pressure Test Port
Slotted Cap
Figure 31
Ignitor Assembly
Note: If the ignitor assembly is damaged, a replacement kit is available,
order Catalog Number 87L54.
OFFION
Inlet Pressure Test Port
Exercise extreme care to prevent damage to or breakage of the ignitor assembly.
I S P
Remove the screw securing the pilot assembly to its mounting bracket. Back off the flare nut at the end of the pilot gas line to free the pilot assembly from the gas line. Remove the pilot orifice and replace it with the one provided with the conversion kit. Reinstall the pilot assembly by reversing the steps detailed here.
When reinstalling the ignitor assembly, use extreme care to prevent damage and break­age. Do not apply any leverage to the ignitor
Adjusting Screw
Spring
assembly while restoring the retainer clip to its original position.
Retaining Clip
LBV
Series
Orifice Size
Natural
Propane
3824 0.125 in. #48 4324 #30 #47
Figure 32
Step 10. Reassemble all removed compo-
nents by reversing the procedures outlined in the preceding steps. Use pipe joint compound or Teflon tape on all pipe fittings before install­ing (ensure propane resistant compounds are used in propane applications, do not use pipe joint compounds on flare fittings).
Step 11. Attach the conversion label provided in the conversion kit to the rating plate on the appliance.
Step 12. Turn on gas supply and test for gas leaks. (See
step 6 on page 8
.)
Refer to
Figure 30
and replace the pilot orifice as follows: Remove the ignitor assembly retainer clip, and carefully remove the ignitor assembly.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
15
Page 16
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2001 by Lennox Hearth Products
P/N 504,137M REV. L 03/2007
16
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
1110 West Taft Avenue Orange, CA 92865
Loading...