Legrand WC Cellular Raceway Systems Terrazzo Rings User Manual

1. Install duct, junction boxes, and accessories according
to the installation instructions provided with each unit. Level system.
2. The top cover of the junction box should be 1 1/4" [32mm] from the anticipated finished terrazzo floor level at this time.
3. Remove the round cover plate from the junction box (see Figure 1).
5. Place the round cover (removed from junction box in Step 3) into the outer brass ring. Line up screw holes in cover with holes in the square cover flange.
6. Place the inner brass ring into the outer ring, on top of the round cover replaced in Step 5. Line up the holes in the inner ring with the holes in the round cover.
7. Replace the original round cover hold-down screws (#10-24 flathead) with the brass screws (#10-24 fillister head) provided with the terrazzo unit.
8. Grease may be spread around the gap between the inner and outer rings and in the screw holes to prevent the ingress of any slurry from the terrazzo mixture.
9. Pour concrete to the desired level. The distance from the top of the concrete slab to the top of the terrazzo rings should be equal to the specified terrazzo thickness.
10. Pour the terrazzo mixture to the top of the brass terrazzo rings. Fill the inside of the inner ring with the terrazzo mixture.
11. After curing, grind surface of floor and terrazzo holder to desired level. Wipe off grease between rings.
Terrazzo Rings
Cat Nos. RTT4, RTT8, RTT13, and RTT20
INSTALLATION INSTRUCTIONS
Walker® electrical systems conform to and should be properly grounded in compliance with requirements of the current National Electrical Code or codes adminis­tered by local authorities.
All electrical products may present a possible shock or fire hazard if improperly installed or used. Walker elec­trical products may bear the mark as UL Listed and/or Classified and should be installed in conformance with current local and/or the National Electrical Code.
Figure 1
Figure 2
224JR Junction Box
RTT13 Shown
Inner Ring
Round Cover Plate (Removed from Junction Box in Step 3)
Outer Ring
Walker Systems, Inc. 1000 Innovation Drive, Williamstown, WV 26187
1 000 337 0800
© Copyright 2000 The Wiremold Company All Rights Reserved