BOX ACTIVATION:
1. After concrete has cured, saw off the remainder of the box with
a wood saw. Box height is to be cut 1/8" [3.2 mm] below the
final height of the carpet or tile floor covering. For 1/8" [3.2 mm]
thick tile, cut the box flush with the floor.
2. Pull wires to the box (see chart below for wiring capacity for
each cover). Re-insert the concrete cap to prevent damage to
the box until the cover is ready to be installed.
Box
Volume
CAUTION: Box must be cut square and parallel with the
floor surface.
BOX HEIGHT WIRING VOLUME WIRING VOLUME WIRING VOLUME WIRING VOLUME
(with Divider) (with Divider)
Inches [mm] Cu. Inches [ml] Cu. Inches [ml] Cu. Inches [ml] Cu. Inches [ml]
6 [152.0] 65.0 [1065.0] 45.0 [738.0] 27.9 [457.0] 47.9 [784.0]
5 1/2 [140.0] 58.0 [950.0] 39.3 [644.0] 22.2 [364.0] 40.9 [670.0]
5 [127.0] 51.0 [835.0] 33.6 [551.0] 16.5 [270.0] 33.9 [554.0]
4 1/2 [114.0] 44.0 [720.0] 27.9 [457.0] 10.8 [177.0] 26.9 [440.0]
4 [102.0] 37.0 [605.0] 22.2 [364.0]
3 1/2 [89.0] 30.0 [490.0] 16.5 [270.0]
3 [76.0] 23.0 [377.0] 10.8 [177.0]
To calculate the total box
volume, use displacement
of the largest uncut
section remaining
CAUTION: Do not use
in concrete
pours less than
4 1/2" [114mm].
CAUTION: Do not use
in concrete
pours less than
4 1/2" [114mm].
Single Service
895 & 896 Activations
Dual Service
895DCC Activation
Dual Service 881CTC,
881RC4ATC, 897CTC,
897CFFTC & 899CTC
Activations
Single Service
881CM2TC,
Activations
Volume Capacities For Ratchet-Pro PVC Floor Box