Legrand 880MPFC User Manual

Wiremold/ Legrand electrical systems conform to and should be properly grounded in compliance with requirements of the current National Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire hazard if improperly installed or used. Wiremold/ Legrand electrical products may bear the mark as UL Listed and/or Classified and should be installed in conformance with current local and/or the National Electrical Code.
Fire Classified Floor Boxes
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 007 421 – July 2008
NOTE: 880MPFC is a single gang offering. Can not gang Boxes
together and maintain Fire Classification.
IMPORTANT: Please read all instructions
before beginning.
Step 1 MEASURE AND LOCATE BOX.
Box must be located over deck valley directly above thickest region of concrete.
Step 2 PREASSEMBLY
Secure box to mounting plate with cable ties or wire. Loosely insert adapters and conduit elbows into box.
Mounting Plate
Reducer or Plug
Reducer
Offset displaced downward
Second PVC Elbow (Optional)
Cut ø 2" [51mm] Hole through Deck
Distance to outside edge of elbow
Step 3 CUT OPENINGS INTO DECK
Measure to the outside edge of the 1" trade size PVC elbow to the box centerline. Cut a 2" [51mm] tangent to this dimension. Repeat on opposite side if both PVC elbows are required.
2"
[51mm]
Step 4 ATTACH MOUNTING PLATE & GLUE
Secure mounting plate to deck by welding or screws. Glue elbow(s) and adapter(s) in place. Seal any unused hub with hub plug provided. Offset in mounting plate is positioned downward. Seal off any excessive gaps around elbows with duct tape.
1 1/4" to 1" Trade Size Hub Reducer
Secure to Deck with Screws or weld
1" Trade Size PVC Elbow
Seal opening end with Duct Tape
NOTE: Use only 1" trade size elbow supplied.
Step 5 SECURE CONCRETE
COVER & POUR
Insert body spacer and concrete cover in box. Do not remove intumescent pads. Pour concrete to requires height.
Concrete Cover
Body Spacer
Intumescent Pads – Do not Remove
Step 6 CUT BOX TO
REQUIRED HEIGHT
After concrete has cured, saw off the remainder of the box at floor level using a wood saw. If the final floor covering is a thick carpet, leave enough of the box protruding above the floor to compensate.
Step 7 CUT CARPET OR FLOOR
COVERING AROUND BOX
After upper section of box is removed, cut the carpet or floor covering as indicated.
5 3/8"
[137mm]
4 3/8"
[111mm]
Wiremold / Legrand
U.S. and International: 60 Woodlawn Street • West Hartford, CT 06110 1-800-621-0049 • FAX 860-232-2062 • Outside U.S.: 860-233-6251 Canada: 570 Applewood Crescent • Vaughan, Ontario L4K 4B4 1-800-723-5175 • FAX 905-738-9721
1 007 421 0708
© Copyright 2008 Wiremold / Legrand All Rights Reserved
Type 880MPFC outlet boxes for use with 1-, 11/2- or 2-hour rated unprotected reinforced concrete floors, floors employing unprotected steel floor units and concrete toppings (D900 Series Designs) or concrete floors with suspended ceilings. (Fire resistive designs with suspended ceilings should have provisions for accessibility in the ceiling area below the outlet boxes.)
The assembled outlet boxes will not reduce the ratings of the floor assembly when the thickness and type of concrete (required for specific ratings) are within the specified limits and the fittings are installed as specified.
1. Concrete – Minimum thickness of structural concrete topping of 3 1/4" [83mm] on steel deck. Unit weight of concrete to be 100 to 155 pcf.
2. Installation – Mounted on 2" or 3" [51mm or 76mm] deck. For use with up to (4) 12 AWG Type THHN power conductors or (48) 23 AWG tele/data conductors.
Outlet Boxes and Fittings Classified for Fire Resistance Wiremold/ Legrand (R8209)
Step 8 ACTIVATION
CAUTION: Wiring capacity is reduced by 9.0 cu.in. than stated by graduations
on box due to intumescent pads.
COVER PLATES
Adapter Carpet & Duplex Duplex GFCI Round
Tile Flange Dual Rectangular Rectangular Twist
Flip Lid Flip Lid Flip Lid Lock
Brass 817B 828R 828DPGFITC 828GFITC 828DLR
Aluminum 818TCAL 828R-TCAL 828DPGFITCAL 828GFITCAL 828DLRAL
Nonmetallic 880MPA
880MPFC
880MPFC: Complete activation following instructions provided with Adapter
(Cat. No. 880MPA), flange and cover plate. See list below for available options.