Legrand 861 User Manual

861 Series Outlet Boxes for Wood & Raised Floors
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 002 968R1 – Updated November 2005
Walker® electrical systems conform to and should be properly grounded in compliance with requirements of the current National Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire hazard if improperly installed or used. Walker electrical products may bear the mark as UL Listed and/or Classified and should be installed in conformance with current local and/or the National Electrical Code.
IMPORTANT: Please read all instructions
before beginning.
Products Covered: 861, 861QTC, 861AMDTC, 861AMDRTTC, & 861FFTC
Applications:
This unit is for wood floor and raised floor construction with:
• 3/4" [19.1mm] subflooring with carpet and padding or
• 3/4 [19.1mm] subflooring with 1/4" underlayment and tile or linoleum floor covering.
These requirements represent the minimum floor thickness to ensure enough cross section is available for the box to lock into the subflooring.
• Suitable for use in air handling spaces in accordance with sec. 300-22(C) of the National Electrical Code.
BOX INSTALLATION
1. Determine the floor box location. (Make sure the placement does not interfere with obstructions below such as floor joists, HVAC duct, light fixtures, etc.) Drill a hole through the flooring using a 4" [102mm] hole saw (4 1/16" [104mm] actual).
2. For a flush installation in hardwood or tile floors with the 895T or 896T series covers - cut a 4 5/16" [109mm] diam­eter, 1/8" [3.2mm] deep step in the final floor covering.
3. Pull the nonmetallic sheathed cable or armor clad cable up to and through the 4" [102mm] hole.
NOTE: For air handling spaces allowed for that
application. See NEC 300-22(C). For communications applications, type CMP communication plenum cable is required in raised floor plenums when wiring methods as described in NEC article 300-22(C) are not followed.
4. Remove the appropriate 1/2" [12.7mm] trade size knockout and attach a cable connector to accommodate the wiring system being used.
Attach the wiring system to the box. To access the wiring cavity, open the disposable cover cap and reseal after use to avoid debris entry.
5. Orient the box to the desired rotation and push into the hole. The box will not turn once installed so make sure the receptacle will be parallel or perpendicular with any adjacent walls.
6. Use the disposable cover as a template to trim around when installing carpet or tile.
NOTE:
Refer to carpet/tile cutout template when installing the following catalog numbers: 861QTC, 861CMDTC, 861CMDRTTC, 861FFTC.
7. When wiring the final activation, remove the disposable cover taking care not to push the box through the opening.
2
2. Attach trim flange to outlet box using (4) #6 x 3/8" flat head screws.
3. Align gasket over receptacle and press bead into flange.
4. Attach the slide cover with (2) #6 cover screws. Do not over tighten screws. Apply icon on receptacle slide if wired for isolated ground circuit. Push box into the hole until firmly seated against floor finish.
1. Wire and attach the quad receptacle to the outlet box using (2) #8 x 3/4" round head screws.
CAUTION: Receptacle mounting means not grounded. Grounding
wire connection required. For isolated ground wiring, connect ground leads to a separate isolated ground conductor. See NEC 250-146(d).
CAUTION:
Gasket must be set in place to provide scrub water seal.
CAUTION:
Do not operate tile stripper or resurfacing equipment over top of cover. This may result in damage to the finish of the product.
NOTE:
Place Orange triangle on devices that are wired for isolated ground. See NEC 250-146(D).
Gasket
Slide Cover
CONVENTIONAL WIRING SCHEMATIC ISOLATED GROUND WIRING SCHEMATIC
BLACK or HOT BLACK BLACK or HOT BLACK
From branch circuit from poke-thru receptacle From branch circuit from poke-thru receptacle
WHITE or NEUTRAL WHITE WHITE or NEUTRAL WHITE
From branch circuit from poke-thru receptacle From branch circuit from poke-thru receptacle
GREEN or GROUND GREEN ISOLATED GROUND GREEN
From branch circuit from poke-thru receptacle From branch circuit from poke-thru receptacle
System Ground
GREEN or GROUND
GREEN (jumper wire)
From branch circuit from poke-thru System Ground junction box
GREEN (jumper wire) from poke-thru junction box
WARNING: Ground wire from junction box must be connected to system ground.
QUAD RECEPTACLE COVER INSTALLATION: Cat No. 861QTC
2. Remove screw plugs and install flexible conduit fittings with conduit.
1. Attach conduit flange to the outlet box using (4) #6 x 1/2" pan head screws. Push the box into the hole until firmly seated against the floor finish.
NOTE: Keep screw plugs for future abandonment.
CAUTION:
Do not operate tile stripper or resurfacing equipment over top of cover. This may result in damage to the finish of the product.
FURNITURE FEED COVER INSTALLATION: Cat No. 861FFTC