© Copyright 2017 LBC Bakery Equipment, Inc. 8 Rev E 1/2017
1: Gas Connections
CAUTION: Gas supply connections and any
pipe joint compound must be resistant to the
action of propane gases.
The LMO-G is an indirect gas fired oven
consisting of a heat exchanger that consists of
15 (fifteen) in-shot burners and tubes totaling
90,000 BTU/HR.
Verify that the gas supply matched the type
listed on the data label. If the incoming
pressure exceeds ½ psig (3.45kPa) 14” W.C.
install a pressure regulator before the oven’s
gas valve.
Codes require installation of a gas shutoff
valve in the gas line ahead of the oven. The
gas supply line must be at least the equivalent
of ¾” iron pipe. Corrugated lines should not
be used.
Connect the gas supply line to the ¾” NPT
incoming gas connection located at the rear of
the oven. Ensure that the pipes are free and
clear of any dirt or obstruction. If the oven is
supplied with a flexible gas line, secure it to
the oven and wall per the manufacturers
instructions.
Verify that the line pressure before the gas
valves stays between 5” and 14” W.C. for
natural gas or 11” and 14” for W.C. for
propane gas – both with and without the
burner firing.
For conversion to Propane Gas or to
Natural Gas:
1. Shut off the gas supply to the oven.
Remove the bottom burner cover and the
side access cover.
2. Disconnect the gas line at the top of the
gas valve. Remove the four extended
nuts at the bottom of the turner
assembly. Lower the burner out of the
oven.
3. Remove the 15 orifices and replace with
the orifices listed on the burner/heat
exchanger parts list in this manual. Use
approved Teflon tape to seal the orifices.
4. Replace the burner. Reconnect the gas
line, replace the covers. Check for leaks.
5. Operate the burner. Adjust the gas
pressure to the correct pressure listed in
the burner/heat exchanger parts list in
this manual.
6. Apply proper labeling to indicate the
correct gas and pressure on the data plate
and at the gas connection point.
2: Ventilation
Ventilation requirements vary with each
installation and must comply with applicable
portions of the National Fire Protection
Association Standard 96 as well as any and
all State and local codes.
Exhaust Fan Interlock
A connection point (5 AMPS Max.) is provided
for indirect vent (Exhaust Hood) or optional
direct vent (Draft Hood). It is located in the
electrical connection box at the right rear
side of the oven. Consult local codes for vent
interlock requirements.
Indirect Vent (Installed under an
exhaust hood) – Standard installation
configuration.
Locate the oven under an exhaust hood with
adequate overhangs and exhaust rates to
completely capture the byproducts of
combustion discharged from the flue. From
the termination of the flue to the filters of the
hood venting system a clearance of 18” must
be maintained. The exhaust hood fan can be
directly interlocked to the oven (consult the
wiring diagram for terminal location*).
Direct Vent (Draft Hood) – Optional
configuration
Move the oven into position and attached the
customer supplied exhaust ducting and draft
diverter.
Verify that the air is being drawn into the
bottom of the draft diverter while the burner
is firing, using a draft gauge or smoke test.
Using a draft gauge, verify that a draft of
between 0.03” – 0.11” W.C. is maintained at
a point 6” above the draft diverter’s upper
collar. Any exhaust fan or draft inducer used
to maintain system suction must be operating
when the oven is turned on. (See exhaust fan
interlock.)