1.6INSTALLATION OF THE DISPENSER AND PUMP DECK ...............................................................4
1.7CONNECTION OF THE EQUIPMENT ..............................................................................................5
1.8START UP ..........................................................................................................................................5
1.9ADJUSTING WATER FLOW..............................................................................................................6
1.10 ADJUSTING WATER TO SYRUP RATIO (BRIX) ..............................................................................7
Cabinet23 inches x 23 inches (58.42 cm x 58.42 cm)
Rim25 inches x 25 inches (63.50 cm x 63.50 cm)
Height (without legs)19-1/2 inches (49.53 cm) above counter (to top
of valves)
23 inches (58.42 cm) below counter
WEIGHT
Shipping296 pounds(134.26 kg)
Empty253 pounds(114.75 kg)
Operating365 pounds(165.5 kg)
ICE BIN CAPACITY100 pounds(45.46 kg)
Pouring coffee, tea, and like substances into the drain can cause clogging.
WARNING!
1. INSTALLATION OF LANCER ICE COOLED DISPENSER
1.1RECEIVING
Each unit is tested under operating conditions and inspected before shipment. At the time of
shipment, the carrier accepts responsibility for the unit. Upon receiving the unit, carefully inspect the
carton for visible damage. If damage exists, have the carrier note the damage on the freight bill and
file a claim with carrier. Responsibility for damage to the unit lies with the carrier.
1.2UNPACKING
A. The ice cooled dispenser is shipped in a corrugated shipping carton. Remove the corrugated
shipping carton from the unit.
B. Remove the parts from the ice compartment.
C. Inspect the unit and parts for concealed damage. If damage exists, notify delivering carrier and
file a claim.
1.3SELECTING A COUNTER LOCATION
A. Select a counter location close to a properly grounded electrical outlet and a water supply that
meets the requirements specified in Section 1.4 below.
B. The counter location must be able to safely support a minimum of 365 pounds (165.5 kg) after
the counter cutout is made.
1.4WATER SUPPLY
A. Provide an adequate potable water supply The water supply line must be at least a 1/2 inches
(12.7 mm) pipe. Water pressure exceeding 50 PSI is regulated by a pressure regulator on the
pump deck. Water pressure below 40 PSI will require a booster pump.
B. Install a shut-off valve in the water line feeding the deck. If a separate water line is run for plain
water, ensure that it also has a shut-off valve.
3
P.N. 28-0720/05
Page 4
Use a filter in the water line to avoid damage to the dispenser.
WARNING!
C. The carbonator pump is equipped with a strainer on the inlet side. A water supply containing any
appreciable quantity of silt, fine sand, or other debris requires a filter ahead of the pump deck.
Clean the filter cartridge periodically, depending on the condition of the water. Failure to do so
may starve the pump of water, causing it to burn out, and voiding the warranty.
1.5ELECTRICAL SUPPLY
The dispenser must be properly electrically grounded to avoid serious
injury or fatal electrical shock. The power cord has a three-prong grounded
plug. If a three-hole grounded electrical outlet is not available, use an
approved method to ground the unit. Follow all local electrical codes when
making connections. Each dispenser must have a separate electrical circuit.
Do not use extension cords. Do not connect multiple electrical devices on
the same outlet.
ALWAYS disconnect power to the dispenser before attempting any internal
maintenance.
Only qualified personnel should service the internal components of the
dispenser. Avoid any contact with water when plugging in the dispenser.
A. Locate a standard 20 AMP, 110 VAC, 60 Hz single phase electrical power outlet with ground
connectors for the dispenser and pump deck.
1.6INSTALLATION OF THE DISPENSER AND PUMP DECK
AInspect the counter location where the dispenser will be installed. Verify that the counter is
strong enough to safely support a 365 pound (165.5 kg) load, after the counter cutout is made.
B. Verify that the unit will fit in the location. See below for the counter cutout dimensions.
NOTE: The unit can extend up to 23 inches (58.42 cm) below the counter, including the shipping
risers. It is recommended to keep the shipping risers attached to the dispenser. If the
dispenser ever requires removal, the shipping risers will protect the inlet tubes from being
damaged.
23 1/4"
23 1/4"
P.N. 28-0720/05
Counter Cutout for dispenser
4
Page 5
C. After the counter cutout is made, lower the dispenser into the counter.
NOTE: In order to ensure unit drainage and proper carbonation, it is necessary for the dispenser to
be level, front to back and side to side.
D. Position the pump deck under the counter within close proximity to the dispenser. The pump
deck must be on a level surface and have adequate electrical utilities available.
1.7CONNECTION OF THE EQUIPMENT
A. Position the CO
2 gas tank in the desired location. Assemble the high pressure regulator to the
CO2 gas tank and run the jumper line to the low pressure regulator.
B. Attach the CO2 gas line to the carbonator by attaching the line from the high pressure regulator
to the CO2 inlet. The setting of the high pressure CO2 gas regulator should be 75 PSI.
Do not turn on CO2at this time.
WARNING!
C. Position the syrup pumps in the desired location. Attach the CO
2 gas lines leading from the low
pressure regulator to these pumps.
D. Connect the syrup lines from the pumps to the appropriate inlets at the front of the unit. The
syrup inlets are identified at the bottom of the unit.
E. Connect the water inlet line to the pump. Complete the water line connection between the pump
and the water inlet to the carbonator at the bottom of the dispenser.
F. Provide a suitable drain in the plumbing system and attach the 3/4 inch (1.90 cm) diameter
schedule 40 PVC drains to it. The drip pan drainage outlet is located at the right rear of the unit.
The ice water drainage outlet is located at the right front of the unit.
G. Be sure to place the ice trap in the drain outlet inside the ice bin before filling with ice. This
device holds the ice away from the drain outlet, allowing the ice water to drain properly.
H. Plug in the transformer box to a standard 20 AMP, 110 VAC, single phase outlet. The unit will
internally convert the 110 VAC to 24 VAC.
1.8START UP
A. After all connections to water, CO
2 gas, electrical power, and syrup pumps are made, check for
leaks.
B. Be sure the Bag-In-Box contains syrup.
Do not operate the carbonator pump deck with the water supply turned off.
WARNING!
C. Turn on water. Open the pressure relief valve on the carbonator tank by flipping up the valve cap
lever, and hold it open until water flows from the relief valve. Close (flip down) the relief valve
and turn on the CO
2 gas.
D. To fill all lines with water, cycle the carbonator several times by operating the dispensing valves.
1. Ensure a good flow of plain water is established from each valve.
2. Turn on CO
at source and ensure that the HP regulator is set at 75 PSIG.
2
3. Operate valves until unit gases out.
4. Plug in carbonator pump motor. Pump Deck will automatically start.
5
P.N. 28-0720/05
Page 6
5. Activate carbonated water valves so that the carbonator pump cycles several times and a
good flow of carbonated water is established.
6. A low pressure gas regulator controls the flow of syrup to each dispensing valve. Connect
BIB connectors to BIB’s. Set LP regulator to 65 PSIG. Activate all valves to purge air from
the syrup lines.
NOTE: The unit will cycle on for 5.5 seconds, shut down, and immmediately start again and run
for additional 5.5 second intervals until the water level reaches the probe.
E. The dispenser bin should now be filled with ice cubes one inch below the level of the door
opening.
1.9ADJUSTING WATER FLOW
A. The water flow can be adjusted to either 1.25 ounces/second (37 ml/sec) or 2.5 ounces/second
(74 ml/sec) on all dispensing valves, using the following procedure.
NOTE: The unit should have ice on the cold plate for a least one hour before you attempt to brix the
o
valves. The drink temperature should be no higher than 40
F (4.4oC) when the ratio is set. This
is done after the unit has ice in the ice bin.
C. Slide the ID panel up until the flow controls are exposed (see below).
D. Remove the nozzle by twisting counterclockwise and pulling down.
E. Remove the diffuser by pulling down.
F. Install Lancer yellow syrup separator (PN 54-0031) in place of the nozzle.
G. Activate the dispensing valve to fill the separator syrup tube.
H. Hold a brix cup under the syrup separator and dispense water and syrup into the cup for four
seconds. Divide the number of ounces (ml) of water in the cup by four to determine the water
flow rate per second.
I. To obtain the proper flow, use a screwdriver to adjust the water flow control.
J. Repeat process for each valve.
FLOW CONTROL
SYRUP
DecreaseIncrease
SODA LEVER
(Optional)
CUP LEVER
I.D. PANEL
(Shown in
open position)
COVER SCREW
FLOW CONTROL
SYRUP
DecreaseIncrease
COVER
DATE OF
MANUFACTURE
SERIES NO.
NOZZLE
Valve Adjustments
P.N. 28-0720/05
6
Page 7
1.10 ADJUSTING WATER TO SYRUP RATIO (BRIX)
A. Hold the brix cup under the syrup separator and activate valve. Check ratio (brix).
B. To obtain the proper ratio, use screwdriver to adjust syrup flow control (see Figure 2).
C. Remove syrup separator.
D. Install diffuser and nozzle.
E. Slide ID panel DOWN.
F. Repeat process for each valve.
NOTE: When re-assembling valves with o-rings, ensure the o-ring is lubricated with an FDAapproved lubricant or water to prevent leakage or damage to the o-ring.
1.11 CONVERTER BLOCK
A. Set the converter block to provide either plain or carbonated water, depending on the product.
The alignment of the dot on the converter block signifies the active port (plain water or
carbonated water):
B. To remove the converter block, use a small screwdriver in the blind hole to pry the converter
block out. Applying pressure opposite the blind hole (dot side) will facilitate removing the
converter block:
7
P.N. 28-0720/05
Page 8
2. MVU OPERATION
2.1MVU PLUMBING DIAGRAM - MAKING CONNECTIONS TO THE MVU
A. Valves 1-3 and 6-8 are in the normal positions on the tower; however, the MVU is plumbed as
shown in the diagram below. Position A is syrup inlet #4 on the cold plate. Position D is syrup
inlet #5. Positions B, C, E, and F on the MVU connect in the positions shown on the illustration
of the Configurator block. These positions (B, C, E, F) are all ambient (bypass the cold plate).
2.2SYSTEM STARTUP
A. Turn on water and purge lines.
B. Turn on CO2 and gas out dispenser.
C. Plug in carbonator pump.
D. Cycle valves two times.
E. Turn on CO2 to BIB pumps.
F. Pour several drinks.
G. Prime for flavor shots.
H. Prime for beverages.
P.N. 28-0720/05
8
Page 9
2.3PROGRAM MULTI VALVE UNIT (MVU)
Set MVU Buttons as Carbonated, Non-Carbonated, or Flavor Shot Only.
The MVU can be programmed to serve soda or plain water beverages as well as a flavor shot from
each of the beverage positions on the valve.
To enter the programming mode on the MVU and assign water type to each individual brand
(Carbonated or Non-carb):
A. Press both A and C brand buttons at the
same time on the MVU panel for five
seconds.
1. The “Pour/Cancel” LED will illuminate. The
“SHOT” LED will blink one time.
2. Brands that are enabled for drinks will
have illuminated LED’s:
Lights on = non-carb
Lights flashing = carb
Lights off = no water (deactivated unless set
for shot)
B. Press a Brand button to change that
beverage from “water off” to “plain water
on”.
1. LED will illuminate and stay on for noncarb beverages.
C. Press the same brand button again to
switch from non-carb to carb.
1. Press the button one more time to turn the
water off for that valve (if position is used
for a flavor shot only).
D. Repeat this process for each brand.
9
P.N. 28-0720/05
Page 10
E. Press the Pour/Cancel button to lock the
changes in place and exit the
programming mode.
NOTE: The Program will save automatically
in 60 seconds if no additional changes are
made in that time frame; however, you can
exit any time within the 60 second window
by pressing Pour/Cancel. The changes
you’ve made will be saved.
2.4SET MVU FOR FLAVOR SHOTS
A. Press both A and C brand buttons (at the
same time) on the MVU panel for five
seconds to get into programming mode.
B. Press the “Shot” button.
1. The “Shot” button will illuminate.
2. Brands enabled for shots will be
illuminated.
C. Press the “Brand” button to turn the shot
mode for that brand on or off.
1. The shot mode is “ON” in the illustration.
P.N. 28-0720/05
10
Page 11
D. Press “Shot” again to return to “Drink Type
Selection”
E. Press the Pour/Cancel Button to lock the
changes in place and exit the
programming mode.
NOTE: The Program will save automatically
in 60 seconds if no additional changes are
made in that time frame; however, you can
exit any time within the 60 second window
by pressing Pour/Cancel. The changes
you’ve made will be saved.
11
P.N. 28-0720/05
Page 12
2.5FLOW RATE CHECK
The Dispenser’s water flow rate can be checked/calibrated using the on board computer as a
timer. To check/adjust flow rate:
A. Remove splashguard and module cover to expose flow controls and solenoids.
1. All active brands should have their shutoffs in the open position as illustrated below.
CW = Carbonated Water (sparkling)
PW = Plain Water (still)
P.N. 28-0720/05
B. Press the A and B buttons at the same
time for five seconds.
1. The Pour/Cancel button will illuminate and
the shot LED will blink 5 times.
12
Page 13
C. Remove outer nozzle and insert syrup
separator.
1. This is important to do during flow rate
check so you can determine if the
separator has been properly installed.
NOTE: Water will leak through to the syrup
chamber if not properly installed.
D. Place a ratio cup under the nozzle and
press a brand button.
1. The brand’s water module will open and
pour for four seconds.
NOTE: Only water will pour during the flow
rate check.
E. Check for 10 oz of water in the ratio cup.
1. If above or below 10 oz, adjust the water
flow control (shown on previous page)
and recheck.
2.6RATIO PROCESS
A. Remove outer nozzle and insert MVU separator if not done on previous step.
B. Prime separator by running the valve.
C. Press and fill the ratio cup to the appropriate levels.
D. Check/adjust ratio on each brand.
1. Use flow controls to adjust syrup.
13
P.N. 28-0720/05
Page 14
2.7PORTION CONTROL PROGRAMMING (MVU) (NO TOP-OFF)
A. Press the S and XL at the same time for
five seconds to enter the portion setting
mode.
1. The Pour/Cancel light will illuminate and
the shot light will blink two times.
Press the Brand button.
1. The selected brand’s LED will illuminate.
2. Multiple brands can be programmed at the same time to pour the same amounts for each
size during this step.
Do this by selecting several brand buttons; however, the first button selected will illuminate
and only its beverage will pour. The other brands selected will flash slowly.
3. If multi-brand programming, do not set carbonated drinks and non-carbonated drinks at the
same time because carbonated drinks will foam.
NOTE: The LED will blink twice and turn off if the brand has been programmed as a flavor shot
instead of a drink. You will need to reprogram the brand as a drink prior to setting the
portion.
C. Fill cup 1/3 full with ice and place it under
the nozzle, push and hold a drink “size”
button until the cup is full.
1. Once the pour is completed, the LED will
blink slowly to indicate that a new pour
duration has been programmed for that
key.
P.N. 28-0720/05
14
Page 15
D. Repeat this step for each of the other size
cups.
E. Select other brands and repeat these
steps for each of them.
F. Press the “Pour/Cancel” button to save
programming.
NOTE: The Program will save automatically
in 60 seconds if no additional changes are
made in that time frame; however, you can
exit any time within the 60 second window
by pressing Pour/Cancel. The changes
you’ve made will be saved.
2.8PORTION CONTROL PROGRAMMING WITH TOP-OFF (MVU)
A. Press the S, L, and Pour/Cancel buttons
at the same time for two seconds to enter
portion setting mode.
1.The Pour/Cancel light will illuminate and
the shot light will blink three times.
15
P.N. 28-0720/05
Page 16
B. Press the brand button.
1. The selected brand’s LED will illuminate.
2. Multiple brands can be programmed at the
same time to pour the same amounts for
each size during this step. Do this by
selecting several brand buttons;
however, the first button selected will
illuminate and only its beverage will pour.
The other brands selected will flash
slowly.
3. If multi-brand programming, do not set
carbonated drinks and non-carbonated
drinks at the same time because
carbonated drinks tend to pour faster.
C. Fill cup 1/3 full with ice.
D. Place cup under the nozzle, push and
hold a drink “size” button until the cup is
full.
1. Once the pour is completed, the LED will
blink fast to indicate Settle Time
programming mode.
2. If the duration is more than 40 seconds,
the dispense function is stopped and the
portion is not saved.
E. After beverage settles, press the Size button again to top off the drink.
1. If the settle time is more than fifteen seconds, the auto top-off times are cleared for all
selected flavors.
F. Repeat steps B-E for additional brands and cup sizes.
G. Press Pour/Cancel button to save the
portions and exit programming mode.
1. If no button is pressed in 60 seconds, the
system will exit program mode and save
the current programming.
P.N. 28-0720/05
2. The Pour/Cancel will blink until the
program is saved.
16
Page 17
2.9SHOT SIZE PROGRAMMING
Flavor shot portions can be adjusted using the MVU touchpad and a graduated cylinder. To adjust flavor
shots:
A. While in Portion Control Programming,
press the Shot button.
1. Pressing the Shot button again will exit
Shot Size Programming.
B. Press a “Brand” button. The brand button
will illuminate.
NOTE: If brand is not enabled for shot
mode, the LED light on that brand will blink
twice and turn off.
C. Place a graduated cylinder under the
nozzle.
D. Press and hold the XL portion button until
the portion size is achieved. Target is 30
ml (1 0z) of syrup for an XL portion for
most customers.
1. The XLRG LED will blink slowly to indicate
that a new shot duration has been
programmed.
NOTE: The other size buttons are
proportioned automatically based on the
amount poured in XL mode:
Small = 25% of XL portion
Medium = 50% of XL portion
Large = 75% of XL portion
E. Repeat steps B through D for each of the
other brands.
17
P.N. 28-0720/05
Page 18
F. Press Pour/Cancel to save the settings.
NOTE: The Program will save automatically in 60 seconds if no additional changes are made in
that time frame; however, you can exit any time within the 60 seconds window by pressing
Pour/Cancel. The changes you’ve made will be saved.
2.10 DISPENSER OPERATION
Crew Serve Beverage Dispensing
Flavor Shot Dispensing - Portion Control
A. Place cup under MVU nozzle.
B. Press the “Shot” button.
1. The “Shot” LCD will stay illuminated (active) for 10 seconds.
C. Select Brand Button.
1. Brand will stay illuminated for up to ten seconds.
2. Touch brand again to deactivate.
D. Select portion control size button to begin
dispensing flavor shot.
1. Press “Pour/Cancel” to stop dispense
B
mode.
C
Beverage Dispensing - Portion Controlled
A. Press the brand button.
1. Button stays active for 10 seconds or until
another brand is pressed.
B. Press a portion control size button.
1. Beverage will pour.
2. Press the Pour/Cancel to stop pour prior to
complete dispense.
D
A
A
B
P.N. 28-0720/05
18
Page 19
Beverages - Manual Dispense on Portion Control
A. Press the brand button.
1. Button stays active for ten seconds or until
another brand is pressed.
B. Press and hold the pour/cancel button.
1. The beverage continues to pour until the
button is released.
A
2. The selection will stay in memory for ten
seconds.
3. The valve can pour for a maximum of thirty
seconds.
2.11 FINAL ASSEMBLY
A. Reinstall the front cover plate.
B. Reinstall drip tray, splash plate and cup rest. System is ready for operation.
B
19
P.N. 28-0720/05
Page 20
3. RECOMMENDED SERVICE AND MAINTENANCE
3.1SCHEDULED
A. Daily – See Section 3.4 for daily cleaning.
BMonthly – See Section 3.5 for monthly cleaning.
C. Periodic Sanitizing - See sections 3.2 and 3.3 for sanitizing requirements.
D. As needed - Keep exterior surfaces of dispenser (including drip tray and cup rest) clean with a
damp, clean cloth.
3.2CLEANING AND SANITIZING SYSTEMS
A. General Information
(1) Lancer equipment (new or reconditioned) is shipped from the factory cleaned and sanitized
according to NSF guidelines. The operator of the equipment must provide
continuous maintenance as required by this manual and state and local health
department guidelines to maintain proper operation and sanitization.
NOTE: The cleaning and sanitizing procedures below pertain to the Lancer equipment identified
by this manual. If other equipment is being cleaned, follow the guidelines established for that
equipment.
(2) Cleaning and sanitizing should be accomplished only by trained personnel. Use sanitary
gloves during cleaning and sanitizing operations. Observe all safety precautions. Follow
instruction warnings on the cleaning product.
To avoid contamination, do not disconnect water lines when cleaning and
sanitizing syrup lines.
WARNING!
(3) Recommended Preparation of Cleaning Solutions.
(a) Cleaning solutions (for example, Ivory Liquid, Calgon, etc.) mixed with clean, potable
water at a temperature of 90 to 110 degrees Fahrenheit should be used to clean
equipment. The mixture ratio, using Ivory Liquid, is one ounce of cleanser to two gallons
of water. A minimum of four gallons of cleaning mixture should be prepared.
NOTE: Extended lengths of product lines may require that an additional volume of solution be
prepared.
(b) Any equivalent cleanser may be used as long as it provides a caustic-based,
non-perfumed, easily-rinsed mixture containing at least two percent sodium
hydroxide (NaOH).
(4) Recommended Preparation of Sanitizing Solutions.
(a) Sanitizing solutions should be prepared according to the manufacturer’s written
recommendations and safety guidelines. Follow manufacturer’s requirements so that
the solution provides 200 parts per million (PPM) chlorine at a temperature of 90
o
120
F. Prepare a minimum of four gallons of sanitizing solution.
NOTE: Extended lengths of product lines may require that an additional volume of solution be
prepared.
(b) Any sanitizing solution may be used as long as it is prepared according to the
manufacturer’s written recommendations and safety guidelines, and provides 200 parts
per million (PPM) chlorine.
o
F to
P.N. 28-0720/05
20
Page 21
3.3CLEANING AND SANITIZING BAG-IN-BOX (BIB) SYSTEMS
A. Disconnect syrup quick disconnect coupling from syrup packages and connect coupling to a bag
valve removed from an empty Bag-in-Box package.
B. Place end of syrup inlet line, with bag valve attached, in a clean container filled with clean,
potable, room-temperature water.
C. Place waste container under applicable dispensing valve. Activate valve until water is
dispensed. Flush and rinse line and fittings for a minimum of 60 seconds to remove all traces
of residual product.
NOTE: Extended lengths of product lines may require additional time for flushing and rinsing lines.
D. Prepare cleaning solution as described in Section 3.2 above. Place end of syrup inlet line in
container filled with cleaning solution.
E. Place waste container under applicable dispensing valve. Activate valve and draw cleaning
solution through lines for a minimum of sixty seconds. This will ensure line is flushed and filled
with cleaning solution. Allow line to stand for at least thirty minutes.
F. Place end of syrup inlet line in a clean container filled with clean, potable water at a
temperature of 90 to 110 degrees F.
G. Place waste container under applicable dispensing valve. Activate valve to flush and rinse line
and fittings for a minimum of sixty seconds to remove all traces of cleaning solution. Continue
rinsing until testing with phenolpthalein shows that the rinse water is free of residual detergent.
H. Prepare sanitizing solution as described in Section 3.2 above. Place end of syrup inlet line in
container filled with sanitizing solution which has been prepared.
I.Activate valve and draw sanitizing solution through line for a minimum of sixty seconds. This
will ensure line is flushed and filled with sanitizing solution. Allow line to stand for at least
fifteen minutes.
J. Remove bag valve from quick disconnect coupling and reconnect syrup inlet line to syrup
package. Ready unit for operation.
Flush sanitizing solution completely from syrup systems. Residual sanitizing
solution creates a health hazard.
WARNING!
K. Draw drinks and refill lines with end product to flush sanitizing solution from the dispenser.
NOTE: A fresh water rinse cannot follow sanitization of equipment. Purge only with the end use
product. This is an NSF requirement.
L. Test dispenser in the normal manner for proper operation. Taste dispensed product to ensure
there is no off-taste. If off-taste is found, flush syrup system again.
M. Repeat cleaning, rinsing, and sanitizing procedures for each valve circuit.
3.4VALVES
A. Valves may be cleaned and sanitized (see preparation in Section 3.2) in the same manner.
1. Remove cover and disconnect power so the valve will not be activated during the cleaning
procedure. Remove nozzle and diffuser. Wash these parts in cleaning solution, then
immerse them in a bath of sanitizing solution for 15 minutes.
2. Visually inspect around nozzle area for syrup residue. This area may be cleaned with warm
water and cloth or with the nozzle brush supplied. Wipe off dispensing lever.
3. Wearing sanitary gloves, remove, drain and air dry the nozzle and diffuser.
4. Wearing sanitary gloves, replace diffuser, twist nozzle in place.
5 Connect power and replace cover. Valve is ready for operation.
21
P.N. 28-0720/05
Page 22
3.5ICE BIN COMPARTMENT ON ALL ICE CHESTS
A. Clean and sanitize the ice bin compartment of the dispenser thoroughly at least once every
month. Use the following procedure:
B. Prepare cleaning solution and sanitizing solution described in Section 3.2.
C. Using the cleaning solution and a clean soft cloth, wash down the sides of the ice bin and the
surface of the aluminum casting.
D. Using clean, potable water, thoroughly rinse away the cleaning solution from the sides and
surface of the casting.
E. Using plastic sanitary gloves, soak a white cotton gauze cleaning rag in the sanitizing solution
and wipe all surfaces in the ice compartment.
NOTE: A fresh water rinse cannot follow sanitization of equipment. Purge only with the end-use
product. This is an NSF requirement.
F. Sanitizing of the ice compartment is complete. Refill with ice.
P.N. 28-0720/05
22
Page 23
4. TROUBLESHOOTING
TROUBLECAUSEREMEDY
4.1 No carbonation.A. Carbonator motor not running.
B. Absence of CO
2
gas.
C. Gas only from valves.
D. Carbonator tank air bound.
E. CO
gas pressure below 75
2
PSI.
F. Carbonator motor running
continuously.
A. Check power supply to see if
plugged in. Check if LED light is
blinking. If so, reset by
unplugging and re-plugging
power supply.
B. Replace with full tank of CO
gas.
C. Check for power failure.
Check fuses. Clean strainer on
pump.
D. Relieve gas pressure in tank
by flipping up relief valve until
water spurts out.
E. Reset high pressure CO
2
gas
regulator to 75 PSI. Change CO
tank if required.
F. Inspect check valve for
blockage. Check carbonator
control. Check carbonator pump
for efficiency.
2
2
G. Water pump not moving
water.
H. Ice on cold plate.
4.2 Noisy carbonator pump.A. Insufficient water supply or
water leak allowing air to be
pulled into pump.
B. Loose pump coupling.
4.3 Valves inoperable.A. Loss of power.
B. Faulty bin switch.
CONTINUED ON NEXT PAGE
G. Replace water pump if
necessary.
H. Fill bin with ice.
A. Provide adequate water
supply. Ensure strainer is clean.
B. Tighten set screw on pump
coupling.
A. Check power supply to see if
plugged in. Check transformer
circuit breaker. Check main
power circuit breaker, 110V.
Check keylock switch on side of
tower to ensure it is in the “ON”
position.
B. Ensure proper connection.
23
P.N. 28-0720/05
Page 24
TROUBLECAUSEREMEDY
4.4 LED blinking 4 blinks per
second.
4.5 LED blinking 1 blink per
second.
A. No water to pump.A. Ensure water supply is on,
carbonator pump motor is
connected, and probe is not
damaged. Reset by unplugging
and re-plugging power supply.
A. Short in probe.
B. Short in harness.
C. Crossed wires in harness or
probe plug.
A. Replace probe.
B. Replace harness.
C. Correct wiring (see CCNA
Bulletin Serv 256).
P.N. 28-0720/05
24
Page 25
NOTES
25
P.N. 28-0720/05
Page 26
5. ILLUSTRATIONS, PARTS LISTINGS, AND WIRING DIAGRAMS
5.1 SERIES 2300 DROP-IN
P.N. 28-0720/05
26
Page 27
5.1 SERIES 2300 DROP-IN - PARTS LIST
ITEM PART NO.DESCRIPTION
1 42-0100Tank Assy, High Performance
-30-9231Liner, Tank Wrapper, Back
2 30-10057Tank Wrapper
3 51-6225Rim Assy
4 30-9267Lid, Ice Bin
5 19-0353/02 LEV®, 4.5, Portion Control
6 05-2586Drip Tray
7 23-0797/02 Cup Rest
8 30-5424Splash Plate
9 04-1089Screw, 10 - 32 X 1.000 (for LEV® only)
10 04-1537Screw, 1/4-20 x .500
11 48-0776Foamed Manifold (5 Valve, 4-1)