Lab Gruppen D40-4L Operation Guide

Rev. 3.0.4
Item no. OM–DSERIES–LAKE
D SERIES
High–Power installation platform
Lake Variants:
D 200:4L D 120:4L
D 10:4L
Incorporating technologies from
Operation Manual
1. Important safety instructions
1. Important safety instructions
1. Important safety instructions
Before using the device, be sure to carefully read the Safety Instructions. Keep this document with the device at all times.
1. Read these instructions.
2. Keep these instructions
3. Heed all warnings.
4. Follow all instructions.
5. Do not use this apparatus near water.
6. Clean only with a dry cloth.
7. Do not block any ventilation openings. Install in accordance with the manufacturer’s instructions.
8. Do not install near any heat sources such as radiators, heat registers, stoves, or other apparatus (including ampliers) that produce heat.
9. Do not defeat the safety purpose of the polarized or grounding-type plug. A polarized plug has two blades with one wider than the other. A grounding-type plug has two blades and a third grounding prong. The wide blade or the third prong is provided for your safety. If the provided
plug does not t into your outlet, consult an electrician for
replacement of the obsolete outlet.
10. Protect the power cord from being walked on or pinched, particularly at plugs, convenience receptacles, and the point where they exit from the apparatus.
11. Only use attachments/accessories specied by the manufacturer.
12. Use only with a cart, stand, tripod, bracket, or table specied by the manufacturer, or sold with the apparatus. When a cart is used, use caution when moving the cart/apparatus combination to avoid injury from tip-over.
13. Unplug this apparatus during lightning storms or when unused for long periods of time.
14. Refer all servicing to qualied service personnel. Servicing is required when the apparatus has been damaged in any way, such as power-supply cord or plug is damaged, liquid has been spilled or objects have fallen into the apparatus, the apparatus has been exposed to rain or moisture, does not operate normally, or has been dropped.
15. Use the mains plug to disconnect the appartus from the mains.
16. WARNING: To reduce the risk of re or electric shock, do not expose this apparatus to rain or moisture.
17. Do not expose this equipment to dripping or splashing and
ensure that no objects lled with liquids, such as vases, are
placed on the equipment.
18. The mains plug of the power supply cord shall remain readily operable.
19. Do not connect the unit’s output to any other voltage source such as battery, mains source, or power supply, regardless of whether the unit is turned on or off.
20. Do not remove the top (or bottom) cover. Removal of the cover will expose hazardous voltages. There are no user serviceable parts inside and removal may void the warranty.
21. An experienced user shall always supervise this professional audio equipment, especially if inexperienced adults or minors are using the equipment.
22. The US National Differences clause 16.3 requires that
network cables must be ame rated VW-1.
2. Approvals
This equipment conforms to the requirements of the EMC Directive 2014/30/EU and the requirements of the Low Voltage Directive 2014/35/EU.
Standards applied: EMC Emission EN55103-1, E4 EMC Immunity EN55103-2, E5, with S/N below 1% at normal operation level. Electrical Safety EN60065, Class I
This equipment is tested and listed according to the U.S. safety standard ANSI/ UL 60065 and Canadian safety standard CSA C22.2 NO. 60065. Intertek made the tests and they are a Nationally Recognized Testing Laboratory
(NRTL).
3. Warnings
3.1. Explanation of warning symbols
The lightning bolt triangle is used to alert the user to the presence of un-insulated “dangerous voltages” within the unit’s chassis that may be
of sufcient magnitude to constitute a
risk of electric shock to humans.
The exclamation point triangle is used to alert the user to presence of important operating and service instructions in the literature accompanying the product.
3.2. Warnings
To prevent electric shock do not remove top or bottom covers. No user serviceable parts inside, refer servicing to
qualied service personnel.
Français: À prévenir le choc électrique n’enlevez pas les couvercles. Il n’y a pas des parties serviceable à l’intérieur, tous
reparations doit etre faire par personnel qualié seulment.
D SERIES Lake Operation Manual rev 3.0.4
2
3. Warnings
3. Warnings
To completely disconnect this equipment from the AC mains, disconnect the power supply cord plug from the AC receptacle. The mains plug of the power supply cord shall remain readily operable. Français: Pour démonter complètement l’équipement de l’alimentation générale, démonter le câble d’alimentation de son réceptacle. La prise d’alimentation restera aisément fonctionnelle.
To reduce risk of re or electric shock, do not expose this
apparatus to rain or moisture. Français: Pour réduire les risques d’incendie ou de choc électrique, n’exposez pas l’appareil à la pluie ou à l’humidité.
Do not expose this system/apparatus to dripping or splashing
and ensure that no objects lled with liquids, such as vases,
are placed on the apparatus. Français: N’exposez pas ce système/appareil au ruissellement ni aux éclaboussures et assurez-vous qu’aucun objet contenant du liquide tel qu’un vase n’est placé sur l’appareil.
This apparatus must be connected to a mains socket outlet with a protective earthing connection. Français: Cet appareil doit être raccordé à une prise secteur avec terre de protection.
The mains plug is used as a disconnect device and shall remain readily operable. Français: Lorsque la prise du réseau d’alimentation est utilisés comme dispositif de déconnexion, ce dispositif doit demeuré aisément accessible.
3.3. Caution
To reduce the risk of re or electric shock, do not remove screws. No user-serviceable parts inside. Refer servicing to qualied
service personnel. Français: Pour réduire le risque d’incendie ou de choc électrique, ne pas retirer les vis. Aucune pièce réparable par
l’utilisateur. Coner l’entretien àpersonnel qualié.
3.4. User responsibility
3.4.1. Mains connection grounding
Your amplier must be connected to a grounded socket outlet.
3.4.2. Speaker output hazard on amplifiers
Ampliers are capable of producing hazardous output
voltages. To avoid electrical shock, do not touch any exposed
speaker wiring while the amplier is operating. The external
wiring connected to the speaker terminals shall be installed
by a qualied person, or ready-made leads or cords of
appropriate capacity shall be used.
As the power output channels on ampliers produce high
voltage, do not connect or disconnect speaker cables when the mains power is on.
3.4.3. Radio interference
A sample of this product has been tested and complies with the limits for the European Electro Magnetic Compatibility
(EMC) directive. This equipment has also been tested and
found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference from electrical equipment. This product uses radio frequency energy and if not used or installed in accordance with these operating instructions, may cause interference to other equipment, such as radio receivers.
This Class A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment on and off, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the antenna.
Increase the separation between the equipment and
receiver.
Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.
Check if the affected unit complies with the EMC limits for immunity, (CE-labeled). If not, address the problem with
the manufacturer or supplier. All electrical products sold in the EC must be approved for immunity against electromagnetic elds, high voltage ashes, and radio interference.
• Consult the dealer or an experienced radio/TV technician for help.
3.4.4. Speaker damage
Amplier apparatus is very powerful and can be potentially
dangerous to both loudspeakers and humans alike. Many loudspeakers can be easily damaged or destroyed by overpowering them. Always check the speaker’s continuous
and peak power capabilities. Although the ampliers
attenuators can be used to reduce the overall gain, an increase of the input signal can result in full output power, which may cause damage to connected speakers.
3.4.5. Maintenance
For safe and reliable operation, the dust lters on both sides
of the front panel, behind the grilles, should be removed and
cleaned regularly to ensure maximum airow through the
device.
If the dust lters are not maintained there will be safety
risks; for example, high internal temperatures could ignite
the dust and start a re. There is also a risk that the unit will malfunction since it is dependent on constant airow from front to rear. If the dust lters are not clean and the unit
malfunctions, any resulting problems will not be covered by the warranty.
D SERIES Lake Operation Manual rev 3.0.4
3
4. Table of Contents
4. Table of Contents
4. Table of Contents
1. Important safety instructions 2
2. Approvals 2
3. Warnings 2
3.1. Explanation of warning symbols 2
3.2. Warnings 2
3.3. Caution 3
3.4. User responsibility 3
5. Introduction 6
5.1. Welcome 6
5.2. D Series: Two versions available 6
5.3. Feature summary 7
6. Installation 8
6.1. Unpacking 8
6.2. Mounting 9
6.3. Cooling and fan operation 10
6.4. Operating voltage 10
6.5. Grounding 11
7. Product overview 12
7.1. Front panel 12
7.2. Rear panel 13
14
14
8.2. Level Adjustments & Mute Points 14
9. Front panel interface 15
9.1. Frame status and control 15
9.2. Channel status and control 15
9.3. Frame select and ID 16
9.4. Additional front panel operations and indications 17
D SERIES Lake Operation Manual rev 3.0.4
4
4. Table of Contents
4. Table of Contents
10. Rear panel interface 18
11. Operation and performance 19
11.1. Operation precautions 19
11.2. Power output performance 19
21
11.4. Power Supply 28
11.5. Auto power down 29
11.6. LoadPilot Load Monitoring 30
12. Lake Processing and Lake Controller 33
12.1. Introduction 33
12.2. Modules and Frames 33
12.3. Lake LoadLibrary™ and Fingerprints 34
12.4. Loudspeaker Processor Overview 34
34
12.6. Frame and System Presets 34
35
13.1. Network setup 35
36
13.3. System setup 37
13.4. Additional Software Reference Material 40
14. Appendix 41
14.1. Faults and warnings 41
14.2. Current draw and thermal dissipation 43
14.3. Maintenance 49
50
16. Warranty and support 54
16.1. General 54
16.2. Technical assistance and service 54
D SERIES Lake Operation Manual rev 3.0.4
5
5. Introduction
5. Introduction
5. Introduction
5.1. Welcome
Thank you for choosing the Lab.gruppen D Series for your sound
offered by this product.
For fast installation and use of this product, your welcome package includes a printed copy of the D Series Quick Start Guide (QSG). It provides a brief introduction to the features and functionality of the D Series and it also contains the information required to safely install the product and place it in service. Please read through
recommended that you also review all other product documentation to ensure familiarity with the various
5.2. D Series: Two versions available
D Series is an advanced, high–power installation amplifier platform designed for demanding applications, primarily in performance venues. For the utmost flexibility in processing and networking, the D Series is available in two versions: the Lake version, with a full slate of Lake processing algorithms, Dante and AES67 audio networking; and the Tesira by Biamp version for full integration in a Tesira system and with Ethernet AVB audio transport. D-series Tesira versions are available in three output power levels, whereas the D-series lake versions are available in six output models. The six Lake power output models come in two form factors. Three high power models in a standard form factor and three lower powered models in a slimline, single rack unit, form factor.
This operation manual is for use with Lake processing versions only, and applies to models at all six output power levels. The models D 200:4L, D 120:4L, D 80:4L, D 40:4L, D 20:4L and D 10:4L will further on only
be referred to as D200, D120, D80, D40, D20 and D10.
D SERIES Lake Operation Manual rev 3.0.4
6
5. Introduction
5. Introduction
5.3. Feature summary
5.3.1. Features common to both D Series variants
Four channels with six levels of total available frame power output: 20000 W, 12000 W, 8000 W, 4000 W, 2000 W and 1000 W
• Rational Power Management (RPM)
• True exibility in allocating power output across each channel to match requirements, for more efcient
use of amplier inventory
• Any channel is capable of being signicantly scaled up to match power requirements.
Dedicated on–board surveillance and load monitoring for voice alarm applications
Advanced universal power supply
• Regulated Switch–Mode Power Supply (R.SMPS™) maintains stability through uctuations in mains voltage
• Best–in–class Power Factor Correction (PFC)
• Current Draw Modeling (CDM™) reduces peak mains draw
• Breaker Emulation Limiter (BEL™) responds to available mains distribution
• Under–Voltage Limiting (UVL™) allows continued operation through mains voltage drop
• CAFÉ (Conguring Ampliers For the Environment) software incorporates ESP™ (Equipment Specication Predictor) to assist in design, equipment specication and commissioning
Features controlled by on–board DSP
• Amplier gain is set in the digital domain and controlled via the Lake Controller software.
• ISVPL™ – The Inter–Sample Voltage Peak Limiter (ISVPL) tailors each channel’s power output to the
characteristics of the connected load
• Load Verication & Performance Monitoring – A comprehensive set of proprietary DSP–based tools
enables load verication and real–time performance monitoring
NOTE: The D200, D120 and D80 models have the possibility to bridge two power outputs to further increase scalability. This feature is not available on the D40, D20 and D10 models.
5.3.2. Features unique to Lake variant
Lake’s exclusive classic/linear–phase/FIR speaker processing platform with four throughputs
• Group control with Raised Cosine™ MESA EQ™ asymmetric lters
LimiterMax™ peak and RMS limiters
• Extensive loudspeaker preset database (Lake LoadLibrary™)
Comprehensive clocking management system with low latency sample rate conversion
Full support for Dante Controller
Multiple and redundant inputs with programmable failover
Four “Lake Class” analog inputs with Iso–Float™ ground isolation
• Two AES3 digital inputs (4 audio channels)
Eight dual–redundant Dante network audio inputs with AES67 support
Comprehensive 3rd party protocol for integration potential with third party matrix systems via purpose–
developed middleware
D SERIES Lake Operation Manual rev 3.0.4
7
6. Installation
6. Installation
5.3.3. Other Documentation
This Operation Manual is intended to serve as a guide and reference to the operation and maintenance of the D Series Lake hardware platform. Comprehensive information is given regarding installation, connection and operation of the front panel interface.
D Series Lake ampliers are designed for conguration and operation using the Lake Controller and CAFÉ software programs. This manual includes a brief tutorial on how to put an amplier into service using Lake Controller, and it
also includes an overview of some features that are implemented via CAFÉ.
For complete information on DSP conguration and operation using Lake Controller, please refer to the Lake
Controller Manual, available online at www.labgruppen.com/support.
For detailed information on conguration and operation of the power platform using CAFÉ, please refer to the guide
embedded in the software or to the CAFÉ Coach video series available on the Lab.gruppen YouTube channel or via a link on the Lab.gruppen web site.
6. Installation
6.1. Unpacking
Carefully open the shipping carton and check for any damage to the device or the supplied accessories. Every Lab.gruppen product is tested and inspected before leaving the factory and should arrive in perfect condition. If any damage is discovered, please notify the shipping company immediately. Only the consignee may initiate a claim with the carrier or their insurers for damage incurred during shipping. Save the carton and packing materials for the carrier’s inspection.
6.1.1. Included in the box
In addition to the D Series device, the shipping carton includes the following items:
D Series Lake Quick Start Guide
• AC mains lead (power cable) with Neutrik powerCON connector (D200, D120 and D80) or IEC connector
(D40, D20 and D10) and AC socket plug according to ordering selection
• Rear brackets for additional rear rack support (pair) along with associated mounting hardware
Connector kit including all needed connectors
• Front grille and dust lter assembly
NOTE: Depending on the model, the connector kit might include more connectors than applicable for the product you have. Select those connectors required for your unit and application.
Please keep the original carton and associated packaging to facilitate shipping of the device should the need arise.
D SERIES Lake Operation Manual rev 3.0.4
8
6. Installation
6. Installation
6.2. Mounting
D Series is made for mounting in 19 inch racks. Four screw holes are available for attachment of the amplier to
the racks front rack rail. This device has no top or bottom vents; therefore, units may be stacked directly on top of
one another. Sufcient space should be available at the rear to accommodate connectors and cables. In addition,
allowance must be made for cable or loom bends within a rack.
6.2.1. Rear Mounting
Two rear support brackets, along with associated mounting hardware, are included with the D Series device. It is strongly recommended that these are used wherever possible. Fit the brackets to the vertical rails at the rear of the
rack. The following diagrams show the tting options for xed and removable installation. The support brackets are reversible and may be tted to point either to the front or rear of the rack; the proper orientation depends on the
rack depth and position of the rear rack rails.
Figure 6.1: Rear support bracket with mounting hardware
Figure 6.2: Rear support bracket mounted for Figure 6.3: Rear support bracket mounted for
xed installation and bracket removable installation and bracket
pointing forward pointing towards rear
D SERIES Lake Operation Manual rev 3.0.4
9
6. Installation
6. Installation
6.2.2. Mounting front grille
The front grille is shipped on top of the amplier inside the box to protect it during shipping. The front grille adheres to the amplier with magnets. Hold the front grille with your ngers in each of the side cutouts and slide it gently into
place straight from the front.
6.3. Cooling and fan operation
D Series devices use a forced–air cooling system with airow from front to rear, allowing high continuous power levels without thermal problems. To facilitate maximum air ow, ensure that no objects such as rack doors or lids are placed at the front or rear of the rack. Never attempt to reverse the airow. Make sure an adequate air supply is provided in front of the D Series device, and that the rear of the device has sufcient space to allow
air to escape. It is recommended to keep the ambient temperature around the device as cool as possible. An
increased temperature can have a signicant negative impact on the expected lifetime on the components
inside the D Series device.
NOTE: Always ensure the dust lters behind the detachable front panel are clean to ensure maximum possible airow. The exterior front panel is held in place by powerful magnets but is easy to detach by using your ngers in the openings at the each side. To clean the foam lter, detach it from the exterior
front and gently use a vacuum cleaner or gently shake it. Remount with the opposite procedure. Never
operate the amplier without the dust lter installed.
NOTE: Fit solid blanks (not ventilation blanks) to unused rack spaces to ensure effective air circulation. Leaving
gaps in between items of equipment degrades the effectiveness of forced–air cooling.
If installing one or more D Series devices in a rack with other fan–cooled equipment, conrm that all other equipment also uses front–to–rear airow for cooling. If this precaution is not observed, there is a risk of overheating, as units with the reverse airow will be drawing in air which has already been heated by the
D Series devices.
The D Series device is equipped with a sophisticated temperature sensing system which protects it from any overheating which may occur as a result of inadequate ventilation.
6.4. Operating voltage
D Series has a universal power supply and its mains nominal and operating voltages are specied in the Technical Specications. D Series can be ordered with a variety of mains plugs. If the mains plug (AC plug) tted to the mains cable (AC cord) is not appropriate for your country it can be removed and a locally–sourced one tted instead. If you are not 100% condent of your competence to replace the mains plug (AC plug), the task should be carried out by qualied personnel.
NOTE: In–rush current is controlled and limited during the soft–start sequence. This enables multiple D Series Devices on the same AC mains circuit to be turned on simultaneously.
D SERIES Lake Operation Manual rev 3.0.4
10
6. Installation
6. Installation
6.4.1. Low voltage country considerations
Although the D Series has a wide range of operating mains voltage, some considerations can be applicable for
low voltage regions. D Series performs well throughout the specied nominal voltage range but has slightly better efciency at higher voltages. For regions with nominal voltage below 140 V, one could consider connecting the amplier in a three phase delta or two phase split-phase conguration, especially applicable for the bigger models, (D200, D120 and D80).
NOTE: Following connections applicable only for resulting voltage inside the ampliers nominal voltage
range.
Connecting the amplier in three phase delta conguration
In three–phase conguration where the phases are 120 degrees apart, one can connect three balanced loads in a delta conguration. The connection is made between the phases instead of between the neutral and a phase.
208V
120V
L1
Amp
L2
Amp
L1 L2
N N
Amp
120V
L3
120V
208V
Amp
Amp
Amp
208V
L3
3 phase Y 120V
3 phase delta 208V
Figure 6:4: Three phase delta conguration
Connecting the amplier in a split phase conguration
In two phase split–phase conguration there are two phases separated by 180 degrees. Connecting between the
phases gives double the line voltage.
100V 100V 200V
Amp
L1
Split phase 100V
Amp
L2N
L1 L2
Amp
N
Split phase 200V
Figure 6.5: Two phase split–phase conguration
6.5. Grounding
D Series must be grounded (earthed) with the safety ground pin to the mains distribution system. NEVER disconnect the earth (ground) pin on the mains cable (AC power cord). Use correctly-shielded balanced audio
input connections to minimize hum and interference.
D SERIES Lake Operation Manual rev 3.0.4
11
7. Product overview
7. Product overview
7. Product overview
7.1. Front panel
1
1
The front panel consists of an outer front with air intake and a centered user interface. The user interface has LEDs for monitoring and six recessed touch buttons for control.
1
Rack ears for 19 inch rack mount
2
Exterior front grille (also air intake and dust lter holder)
3
3
Touch and LED panel – See section 9.1 for further information.
D SERIES Lake Operation Manual rev 3.0.4
12
7. Product overview
7. Product overview
7.2. Rear panel
1
1 2
2
3
3 4
4
1
5
marked hot (+) and cold (-) terminal
2
Analog Inputs - Analog inputs are available on terminal block connectors with clearly marked hot (+), cold (-)
and ground terminals
5
3
AES3 Inputs - AES3 inputs are available on terminal block connectors with clearly marked hot (+), cold (-)
and ground terminals
4
RJ-45 Ethernet connectors for control, Dante and AES67 digital audio network
5
Mains connector - Detachable Neutrik powerCON (for D 200, D 120 and D 80) or locking IEC connector
D SERIES Lake Operation Manual rev 3.0.4
13
8. Signal flow, routing and mute points
7. Product overview
8. Signal flow, routing and mute points
8.1. Signal flow
device provides seven points in the signal chain where the signal level can be adjusted, muted or disconnected.
Module Data stored in Module FIles (Speaker Presets)
Frame Data stored in System Files and Frame Presets
Dante Receivers 1-8
Dante Receivers/AES/
Analog pass through to
Dante/AES67
INPUTS
AES 1-4
Analog 1-4
OUTPUTS
Dante 1-8
(no mutes)
Input
Routers
1-4
WITH
INPUT
MUTES
Input
Mixer A
Input
Mixer B
Input
Mixer C
Input
Mixer D
Lake Contour
Module A
Lake Contour
Module B
Lake Contour
Module C*
Lake Contour
Module D*
Attenuator
Phase Rev
Custom RPM
Attenuator
Phase Rev
Custom RPM
Attenuator
Output Routing
Phase Rev
Custom RPM
Attenuator
Phase Rev
Custom RPM
Mute
Mute
Mute
Mute
ISVPL
Auto RPM
ISVPL
Auto RPM
ISVPL
Auto RPM
ISVPL
Auto RPM
Amp Gain LoadSmart LoadPilot AMP
Amp Gain LoadSmart LoadPilot AMP
Amp Gain LoadSmart LoadPilot AMP
Amp Gain LoadSmart LoadPilot AMP
1 2 43 5
Figure 8.1: D Series Lake Signal Flow Diagram
1
The input section (inputs, input router and input mixer) allows for mixing capabilities as well as redundant and
prioritized inputs with automatic switch-over in case of signal failure
2
Up to four Lake Processing modules provide user EQ and loudspeaker processing, including LimiterMax limiting
3
The Output router allows free routing between module outputs and power output channels
4
Each power output channel provides individual channel processing, including ISVPL limiter, RPM and
load monitoring
5
8.2. Level Adjustments & Mute Points
the signal:
1 Input Router Stage Input selection and MUTE 2 Input Mixer Stage Router on /off connection to mixer and gain settings 3 Module Input Stage Mute and gain settings 4 Module Output Stage Mute and gain settings 5 Output Router Stage Output on /off routing connections 6 Attenuation Stage Power output channel mute and attenuation settings 7 Amp Gain Stage
NOTE: If the required audio signal is not passing correctly, verify the connection, mute and gain settings at all seven stages.
D SERIES Lake Operation Manual rev 3.0.4
14
9. Front panel interface
9. Front panel interface
9. Front panel interface
9.1. Frame status and control
1 2 5 6
43
NOTE: General status indication shown in Table 9.1. For detailed information on warning and fault indication, please refer to the Faults and Warnings table in Section 14.1.
1
FRAME LED – Provides status indication for a number functions affecting the amplier frame
2
TEMP LED – Provides status indication for internal temperatures sensed at multiple points, including power
supply, DSP and output channels
3
PSU LED – Provides status indication on functionality of Power Supply Unit and mains supply, including under–
and over–voltage, power supply faults, and unstable mains supply
4
POWER LED and TOUCH BUTTON – Provides power state indication and control. Press and hold button to
toggle the amplier between ON and STANDBY state. LED indication given in Table 9.1.
7
8
9
9.2. Channel status and control
5
LOAD LED – Provides load related status indication for monitoring functionality of LoadSmart and LoadPilot.
Warnings and faults indicate problems or anomalies detected in the connected loudspeakers and/or cabling
6
AMP LED – Provides amplier related status indication, including faults and warnings related to temperature,
over–current, clipping and very high frequency
7
SIGNAL LED – Provides signal related status indication, including no signal and input signal clipping
8
MUTE LED and TOUCH BUTTON – Provides mute status indication and control. The LED is indicating
both Lake mutes and power channel mute. A single touch on the mute button toggles the power channel mute between mute and unmuted states
9
SELECT LED and TOUCH BUTTON – for selection and indication control between computer software and unit
D SERIES Lake Operation Manual rev 3.0.4
15
9. Front panel interface
9. Front panel interface
OFF Green Amber Red
Frame
N/A Frame OK Frame warning Frame fault
Tem p
N/A Te mp OK Temp warning Temp fault
PSU
N/A PS U OK
Power supply/ Mains warning
Power supply/
Mains fault
Power
No mains power
Fixed:ON
Blinking: Turning ON
Button pressed.
Hold for transition
Fixed: STANDBY
Blinking: Turning to
STANDBY
Load
No LoadPilot active
LoadPilot active
and LoadOK
Load warning Load fault
Amp
N/A Power channel OK Power channel warning Power channel fault
Signal
Output below signal
present threshold (–60 dB)
Output above signal
present threshold (–60 dB) input clip (–2 dB) or limit/ fault active
Mute
Inactive channel in
bridge operation
Unmuted
Lake module is muting the signal chain at either input
router, module input or
module output
Power channel muted
Select
Frame not selected Frame selected Waiting for more touches N/A
Input signal approaching Input signal clip
Tabl e 9.1: LED/category chart
9.3. Frame select and ID
9
SELECT LED and TOUCH BUTTON – Selects mode and indicates control between computer software and
unit. A single touch on the button will select the unit in supported computer software views. Multiple consecutive touches will select the corresponding Lake module (one touch for module A, 2 for module B etc.). In the other direction, when selecting the unit in a supported computer software view, the LED will indicate the unit is selecte d with steady green illumination.
NOTE: The touch buttons use capacitive touch technology and might be sensitive to large temperature and humidity variations.
D SERIES Lake Operation Manual rev 3.0.4
16
9. Front panel interface
9. Front panel interface
9.4. Additional front panel operations and indications
9.4.1. Frame reset
A factory reset and soft reset can be performed from the front panel. A factory reset will restore all settings to original defaults, including network settings, frame presets and current settings. A soft reset reverts only the current settings to default. Network settings and frame presets are not changed with a soft reset.
6. Place the frame in standby mode.
7. Press and hold Select and channel 3 mute button. Then press the power button.
8. User interface will illuminate available options. Choose from the options below a. Press channel 1 mute button (red LED) to initiate the factory reset sequence. b. Press channel 2 mute button (amber LED) to initiate the soft reset sequence. c. To cancel, press channel 4 mute button (green LED).
9. Wait state indication is present while either reset is performed.
10. To complete the factory reset process, cycle the mains power by completely removing the power plug and reinserting it.
9.4.2. Wait indication
Wait indication is displayed when the frame is performing an operation. All LEDs except power are unlit and a circling amber light is displayed on channels 1 and 2.
9.4.3. Power cycle required indication
After an operation that requires a subsequent power cycle to complete, the power LED blinks alternately red and green. A Power cycle requires that the mains is completely removed from the device and not connected again
until the device has powered off.
9.4.4. Front panel lock
The front panel can be disabled from the Lake Controller. When the front panel is disabled, LEDs 4, 8 and 9 (all buttons on the lowest row) flash in amber when hitting any touch button.
D SERIES Lake Operation Manual rev 3.0.4
17
10. Rear panel interface
10. Rear panel interface
10. Rear panel interface
1
nnect loudspeaker
cables to the mating plug–in connectors observing polarity (including bridge mode option for D200, D120
and D80) as marked on the rear panel
2
Analog Inputs – Analog inputs are available on terminal block connectors with clearly marked hot (+), cold (–)
and ground terminals. The inputs are electronically balanced and feature Lake Iso–Float circuitry
3
AES3 Inputs – AES3 inputs are available on terminal block connectors with clearly marked hot (+), cold (–) and
ground terminals
4
RJ–45 Ethernet connectors
accept either mating etherCON connector or a standard RJ–45 connector.
1 2
2
3
for control, Dante and AES67 digital audio network. Neutrik etherCON connectors
3 4
5
4
1
5
Primary Network Connector – The primary connection provides integration into an Ethernet control network which may include other Lake Processors and the Lake Controller software. Network connection permits full control of all functions along with real–time metering from a remote position.
This device supports the Dante audio networking protocol, which allows transmission of multichannel, high–
definition digitial audio over the same Ethernet connection. AES67 audio flows are also supported.
Use the primary connector when using a star network topology, consisting of individual Cat–5e connections between the devices and an Ethernet switch. Alternatively this connection can be used to daisy chain directly to another Lake Processor. The daisy chain topology should not be used with Dante.
Additional information is also available in the Lake Network Co
NOTE: The Ethernet ports operate at the Ethernet data rate of up to 1 Gbps and allow straight or crossed network cables. LEDs above each port indicate network activity (ACT) and Gigabit network connections (Gbps). If Gbps LED is unlit, speed is 100 Mbps.
D SERIES Lake Operation Manual rev 3.0.4
18
11. Operation and performance
11. Operation and performance
Secondary Connector – The secondary network connector can be used to create a Dante dual–network topology by connecting all secondary network connectors to a separate Ethernet switch, ensuring full redundancy in the event of a network component failure. Alternatively, the secondary network connector can be used to daisy–chain multiple Lake devices (LM, PLM, PLM+ or D Series), if Dual Redundancy is Disabled from
the Lake Controller. When the device is in Dual Redundancy , it is possible to connect a Lake Controller to the Secondary Connector as long as the IP address on the computer is on the 172.31.x.x subnet.
If the device has dual redundancy enabled, any AES67 audio must be on the primary network (i.e. AES67 cannot be transmitted or received on the secondary connector).
ed via Lake Controller. See the Lake Controller Operation Manual for further details.
NOTE: When connecting multiple devices to an Ethernet network, care must be taken NOT to create a closed loop which causes network malfunction.
5
Mains connector – Detachable Neutrik powerCON (for D 200/120/80) or locking I EC c onnector (D 40/20/10).
For more information, please refer to Section 6.4.
11. Operation and performance
11.1. Operation precautions
Make sure that the Standby button on the unit’s f r ont panel is either unlit (OFF), or red ( STANDBY), before making any input or output connections. Ensure the AC voltage is within the range printed on the label adjacent to the AC mains connector. Ensure no input signal is present when powering on the unit to reduce the risk of any inadvertent bursts of high level audio.
11.2. Power output performance
The standard form factor D Series units (D200, D120 and D80) uses Lab.gruppen’s patented Class TD
purity of Class A/B designs. The slimline D Series units (D40, D20 and D10) uses a newly developed Class D:
perfectly under all load conditions and the output maintains it with very low nominal impedances. Reliability is very high, and there is no interference with nearby RF equipment.
D SERIES Lake Operation Manual rev 3.0.4
19
11. Operation and performance
11. Operation and performance
Load Impedance (ohms)
2 ohms
(per channel)
2.67 ohms
(per channel)
4 ohms
(per channel)
8 ohms
(per channel)
16 ohms
(per channel)
Hi-Z 70 V
(per channel)
Hi-Z 100 V
(per channel)
D 200:4L 4400 W 500 0 W 4400 W 2300 W 1150 W 3300 W 4700 W
D 120:4L 300 0 W 3000 W 3000 W 1900 W 950 W 3000 W 3000 W
D 80:4L 2000 W 2000 W 2000 W 1500 W 750 W 2000 W 2000 W
D 40:4L 800 W 1000 W 1000 W 1000 W 700 W 1000 W 1000 W
D 20:4L 500 W 500 W 500 W 500 W 425 W 500 W 250 W
D 10:4L 250 W 250 W 250 W 250 W 250 W 250 W 175 W
11.2.1. Symmetrical power
D Series models can deliver power as shown in Table 11.1 when all channels are driven equally.
Table 11.1: Symmetrical Load Power Ratings
11.2.2. Rational Power Management™
Rational Power Management™ (RPM) is a unique Lab.gruppen feature that allows for exible allocation of power
across channels of a D Series unit. Power that is not used by one output channel is free for use by another output
channel with greater demands. Unique to this series is that all models in the range have amplier channels that can produce higher outputs than the average 25% of the total power, see the Technical Specications for the maximum single channel power capacity. RPM automatically allocates power up to the total limits of the specic amplier
model and helps minimize unused power in the installation.
RMS voltage; and also the speaker’s AES power rating. By specifying the nominal impedance of the load, the RPM algorithms have all input data required to calculate resulting RPM settings. If the desired RPM settings results in a total power output higher
of delivering the
is performed with the ISVPL limiter algorithm. As default the R
the channels at a voltage (default voltage limitation) given in
in two modes.
er; peak and Via the CAFÉ Software, desired
reduction in dB. Once applied, the RPM functionality will ensure that all channels are capable
D SERIES Lake Operation Manual rev 3.0.4
20
11. Operation and performance
2000 W
11. Operation and performance
LOW
Figure 11.2: Amp channels power adjusted to match the loudspeaker requirements on a D 80:4
Auto RPM: The frame will automatically allocate power per output channel according to the ISVPL settings in the
speaker preset (per module output) in Lake Controller. Auto RPM assumes a nominal impedance of the Load and
applies an approximate power allocation. Auto RPM is default for D Series Lake.
MIDSUB
HIGH
Custom RPM: The CAFÉ software allows users to create an advanced custom power allocation scheme. Switching to Custom mode disables the Automatic mode. Additional information is available in documentation supplied with the CAFÉ software download.
Custom RPM using CAFÈ with ESP: CAFÉ (Conguring Ampliers For the Environment) is a dedicated software application for Windows and OSX that provides tools for system planning, specication and commissioning. CAFÉ incorporates the Equipment Specication Predictor (ESP), a software module that examines SPL and speaker requirements for a project and generates requirements for output power on an amplier and system level. ESP will generate a custom RPM conguration optimizing the power allocation within the frame. For more information on
CAFÉ and ESP, please consult the documentation supplied with the CAFÉ software download.
11.3. Amplifier and Load Protection Systems
The D Series is equipped with a comprehensive set of protection circuits. If operating conditions become
sufciently extreme that any of these circuits become active, indication is provided by amber or red LEDs on the front panel, and by text notications in the Lake Controller and CAFÉ software. Refer to Section 14.1 for more
information on warnings and faults.
D SERIES Lake Operation Manual rev 3.0.4
21
11. Operation and performance
11. Operation and performance
11.3.1. Inter–Sample Voltage Peak Limiter (ISVPL)
The ISVPL is a high quality voltage limiter that can deliver seamless limitation to any desired level. It ensures that the voltage at the output terminals never exceeds the dened threshold. It operates on these principles:
• The signal is delayed slightly to allow the ISVPL to look–ahead and reduce the gain before voltage in excess
of the threshold can appear at the output. This results in zero voltage overshoot at the output with a rounded limitation up to the threshold.
• The amplitude of the output signal between digital samples is predicted which permits the ISVPL to respond to
analog peaks that may occur at the digital to analog converter.
The release time of gain reduction is adaptive depending on the dynamics of the signal. It is possible to select
different ISVPL proles for limiting optimization for a specic frequency band and personal preference. The proles are divided into two categories, with one category optimized for low distortion and the other focusing on producing high sound pressure level (SPL). Within each category there are proles optimized for the different
frequency bands.
11.3.1.1. Low Distortion Profiles
• Universal – The universal prole is a soft limiter that can be used for all frequencies and is conservative in its
action upon VCL and CPL.
• Sub/LF – The Sub/LF prole is tuned for frequency bands below 600 Hz. It has longer attack and release times
and is less conservative when it comes to acting upon VCL and CPL.
11.3.1.2. High SPL Profiles
High SPL proles do not use the adaptive release time feature. High SPL proles optimized for high frequencies use less of the look–ahead delay peak–rounding feature; this feature is used most in the Sub prole and least the HF prole.
• Sub – The Sub prole is optimized for frequencies between 20 – 200 Hz
• LF – The LF prole is optimized for frequencies between 20 – 1200 Hz
• MF – The MF prole is optimized for frequencies between 300 – 6000 Hz
• HF – The HF prole is optimized for frequencies above 1 kHz
11.3.1.3. ISVPL Voltage Settings
The ISVPL threshold may be set at any level between 17.8 V and 600 V in the Lake Controller software. For further
details, please refer to the Lake Controller User Manual.
Lake–enabled amplier devices (D Series Lake, PLM+, PLM) that have a smaller peak output voltage capability still allow ISVPL speaker threshold settings up to 600 V. When a threshold is set above the current maximum capability of a power output channel, the actual ISVPL will automatically be set to the maximum ISVPL for that channel. Therefore, the ISVPL threshold can be set at the Module for the speaker’s maximum capability, and the Module le remains cross–compatible with all Lake–enabled amplier devices.
Table 11.3 shows the theoretical maximum output power based on only the load impedance and
the ISVPL setting. See the Technical Specications, or use CAFÉ, to nd the available power for a specic amplier and load.
D SERIES Lake Operation Manual rev 3.0.4
22
11. Operation and performance
Max. Sinewave Burst Power (Watts)
LLoad Impedance (ohms)
2 2.67 4 8 16
LISVPL SETTING (V peak)
194 4489 5993 4705 2352 1176
193 4489 5993 4656 2328 116 4
181 4489 5993 4095 2048 1024
167 4489 5223 3486 1743 872
153 4489 4384 2926 1463 732
121 3660 274 2 1830 915 458
101 2550 1910 1275 638 319
83 1722 1290 861 431 215
70 1225 918 613 306 153
56 784 587 392 196 98
47 552 414 276 13 8 69
38 361 270 181 9 0 45
17.8 79 59 40 20 10
Table 11.3: ISVPL–to–output examples
11. Operation and performance
11.3.2. Current Peak Limiter (CPL)
The output Current Peak Limiter (CPL) ensures that the power output section will not be damaged by forcing it to
deliver current levels at the outputs that exceed the maximum current ratings of the output transistors. The CPL
keeps the output transistors within their Safe Operating Area (SOA). The CPL is non–adjustable.
This condition indicates an attempt to draw excessive current at the output. The output is attenuated until the
output current falls below the maximum current rating. Limiting is performed by the ISVPL limiter in conjunction with the selected ISVPL prole.
CPL activity is shown by amber or red indication on Amp LED of the affected output channel and a corresponding text description in Lake Controller and CAFÉ software programs. Refer to Section 14.1 for more information on warnings and faults.
NOTE: If excessive current is indicated, check the output cables and examine the loudspeaker. If
impedance appears normal, you may rectify the condition by altering the ISVPL settings or lowering
input levels. CPL indication can be triggered by excessively low load impedance, possibly the result of too many loudspeaker cabinets connected in parallel.
11.3.3. Power Average Limiter (PAL)
The Power Average Limiter Active warning (PAL Active) will be displayed when the power supply is operating at the
maximum average input power allowed for the PSU design. When this warning is displayed, gain limiting is being
applied to the signal by a lowering of the ISVPL threshold.
D SERIES Lake Operation Manual rev 3.0.4
23
11. Operation and performance
11. Operation and performance
PAL activity is shown by PSU amber LED indication and a corresponding text description in Lake Controller and CAFÉ software programs. Refer to Section 14.1 for more information on warnings and faults.
11.3.4. Breaker Emulation Limiter (BEL™)
The BEL models the temperature in the external breaker and limits the mains current to prevent the breaker
be selected for Frame Replace support). The desired nominal current value can be set from 1 to 32 Arms. The resulting models the
allows current above the threshold to pass for a short time, leading to an increased modeled temperature. For the limiter to disengage, the current must reduce below the threshold to enable the breaker to cool down.
momentarily allows current above the threshold for a longer time, leading to an increased modeled temperature. ed current for the breaker to cool down.
is set above, or bellow, the model’s capabilities, the actual current is automatically adjusted into
:
predict the current consumption, with the exact speaker requirements, and propose a safeguarding
11.3.5. Under Voltage Limiter (UVL™)
The larger D Series devices (not D 20:4L and D 10:4L) are equipped with an under voltage limiter. W ith multiple, powerful devices on a mains distribution line, heavy current loads risk the reduction of voltage below that required for devices to function. The UVL reduces the mains current draw when voltage drops below 80 V. The amount of reduction applied increases as mains voltage drops towards 65 V; at 65 V the power supply is
automatically restarts.
11.3.6. Current Average Limiter (CAL™)
The Current Average Limiter (CAL) monitors the RMS current drawn from each power output channel to ensure that the power output stages are not overloaded. When activated, it regulates the current to a safe level to protect the channel. The CAL should not be activated in normal usage. If activated, this is shown by amber or red indication on the Amp LED of the affected output channel and a corresponding text description in Lake Controller and CAFÉ software programs. Refer to Section 14.1 for more information on warnings and faults
D SERIES Lake Operation Manual rev 3.0.4
24
11. Operation and performance
11. Operation and performance
NOTE: For Slimeline models, to optimize the CAL’s behavior when playing into a low impedance load, manually set the desired ISVPL to reflect the real peak voltage output to allow for a higher average current.
11.3.7. Voltage Clip Limiter (VCL)
If current draw from the unit’s power supply is too high, the PSU’s regulation capability may be exceeded and the internal voltage rails may drop and cause clipping. If this occurs, the VCL acts rapidly to prevent clipping on the subsequent peaks. Limiting is performed by the ISVPL limite Indication of this condition is shown on the output LEDs. Refer to Section 14.1 for more information on warnings and faults.
11.3.8. Temperature Protection
D Series devices are equipped with a sophisticated temperature sensing system that provides protection from overheating which may occur as a result of inadequate ventilation or excessive power output. Thermal measurements are made at several points within each power output channel along with measurements in
operate continuously, with the highest possible output, and prevent shutting down. If temperature in any area reaches a critical level, a warning is displayed. The warning is issued at approximately 80% of the maximum allowable temperature. If the temperature continues to increase, a limiter (ATL or PTL) is engaged that limits signal peaks to reduce further heat accumulation. Limiting is accomplished by gradual reduction of the ISVPL thresholds. In the extreme case where the limiter cannot reduce heat accumulation and temperature reaches a dangerous level, a fault is displayed and audio is muted.
Each power output channel, the power supply, and DSP area have separate indications. For all temperature faults, temperature monitoring will continue at 0.5 second intervals, with the output remaining muted. When the area has cooled below the dangerous threshold, the fault condition is cleared and audio is restored.
11.3.8.1. Power Output Channels
A power output channel temperature warning or fault is indicated by the Amp LED for that channel and the Temp LED for the frame.
A warning is indicated by a static amber LED
A fault is indicated with a static red LED
An event report is sent to the Lake Controller software for both the warning and the fault. If a temperature fault condition arises on a power channel, the output of that channel will be muted.
D SERIES Lake Operation Manual rev 3.0.4
25
11. Operation and performance
11. Operation and performance
channel Temperature Limiter (ATL) will engage at approximately 95% of the maximum allowable temperature. When ATL is engaged, it will try to reduce the power output to avoid that the amp channel goes into temp fault, i.e. muting. Limiting is removed when temperature falls below the ATL threshold.
11.3.8.2. Power Supply / DSP
A power supply (PSU) or DSP temperature warning or fault is indicated by the Temp LED.
A warning is indicated by static amber LEDs
Power supply Temperature Limit (PTL) is indicated by an amber LED
A fault is indicated with static red LEDs
If the power supply temperature keeps rising after reaching the temperature warning threshold, the Power supply Temperature Limiter (PTL) will engage at approximately 95% of the maximum allowable temperature. When PTL
i.e. muting of all channels. Limiting is removed when the temperature falls below the PTL threshold.
11.3.9. DC Protection
The DC protection is implemented, individually, on each power output to prevent damage to connected loudspeakers or any D Series components. DC present at the output will cause the unit’s power output module breaker to blow, causing a permanent hardware fault that prevents signal throughput. In this instance the channel’s Amp LED will illuminate red and a service channel fault will be registered in the Lake Controller and CAFÉ status views (D200, D120, D80 only). For the D40, D20 and D10, no audio will be heard from the outputs.
NOTE: A blown breaker in the power output module is not a user serviceable fault condition and the unit should be returned for repair.
11.3.10. VHF Protection
The D Series includes protection circuits that detect Very High Frequency (VHF) content in the input signal. The detection is amplitude–, frequency– and time–dependent. It is initiated from 10 kHz upwards and, if continuous VHF signals are detected above the threshold for more than the attack time, the output for a D200, D120 and
D80 will attenuate the gain until the signal is below the VHF threshold. When this is done, VHF Warning is displayed. If the signal is above the VHF threshold and the maximum of -12 dB of gain reduction is not enough to take the signal below the VHF threshold, the signal will mute after 15 seconds, and retest the signal after 6 seconds. Note that the D40, D20 and D10 will go directly to mute upon VHF detection. When continues
normal operation.
This protection system recognizes only continuous VHF signals at high levels that will not appear in speech or music. Any such content can therefore be considered as a fault condition. VHF protection is essential to avoid damage to HF drivers. VHF protection is dependent on a combination of output power level and frequency. Figure 11.4 shows a decreasing power threshold, from approximately 10 kHz upwards, which illustrates increasing sensitivity of the protection system with frequency. When continuous output power above the threshold line is detected, VHF protection becomes active.
D SERIES Lake Operation Manual rev 3.0.4
26
11. Operation and performance
11. Operation and performance
100
90
80
70
60
50
40
30
Voltage [Vrms]
20
10
0
0 5
Trigger voltage
10 15 20 25 30
Frequency [kHz]
Fig 11.4: VHF Protection Frequency Sensitivity
The attack time of the VHF protection circuitry also changes with frequency, becoming shorter at higher
frequencies. This is shown in Figure 11.5.
Full output voltage
1400
1200
1000
800
600
Time [ms]
400
20
200
0
0 5
10 15 20 25 30
Frequency [kHz]
Fig 11.5: VHF Protection Attack Time Variations
The VHF pr
solely to detect
continuous VHF content. HF content of normal music or speech signals at peak levels will be passed in full. Operation of the VHF protection circuits is indicated by the channel’s AMP LED that will illuminate yellow and display VHF Warning when the max of -12 dB of gain reduction is applied (only applicable for D200, D120 and D80) and light red for a VHF FAULT. Both of these will be registered in the Lake Controller and CAFÉ status views.
11.3.11. Short Circuit Protection
A low impedance or short circuit at the power output terminals is detected when the output current is high (Current
Peak Limiter is active) and, simultaneously, the peak output voltage is below a predetermined threshold. When this
situation occurs, the output stage is muted to protect it from damage.
Operation of the short circuit protection system is indicated by Amp channel LED showing steady red and a corresponding text description will register in Lake Controller and CAFÉ software programs. Refer to Section 14.1 for more information on warnings and faults.
D SERIES Lake Operation Manual rev 3.0.4
27
11. Operation and performance
11. Operation and performance
The presence of a short circuit (or low impedance) is re–tested every six seconds, and the output remains muted until the fault clears.
11.3.12. Power supply protection
The power supply is very advanced and has several internal control and monitoring functions. Should any of these fail, the power supply will shut down to prevent damage or limit severity of the failure. If the power supply shuts down audio will be muted. Power supply faults, or power supply needs service faults, are indicated by a red LED and associated error messages registered in Lake Controller and CAFÉ software programs.
In the extreme event of simultaneous low mains voltage supply and high power demand, the amount of incoming
condition is a power protect fault, indicated with a red LED and associated error messages registered in Lake Controller and CAFÉ software programs.
11.3.12.1. Mains anomaly protection
supply will then be forced to shut down. This
mains service.
Over–voltage – If the power supply detects mains voltage above 400 V peak or 270 V RMS, it will enter protective
associated error messages will register in Lake Controller and CAFÉ software programs.
Under–voltage – If the power supply detects mains voltage of less than 65 V, it will enter protective shut down mode. The amplifier will auto– restart if the condition clears. Will be indicated by a red LED and associated error messages will register in Lake Controller and CAFÉ software programs.
Mains instability – If the power supply detects protracted instability in the AC mains, it will enter protective shut down mode (D 200:4L, D 120:4L and D 80:4L only). The ampli Will be indicated by a red LED and associated error messages will register in Lake Controller and CAFÉ software programs.
Mains glitch – If the power supply detects a momentary mains glitch (missing cycles) at the AC inlet, a warning indication will be reported with a yellow LED and associated error messages will register in Lake Controller and CAFÉ software programs (D 200:4L, D 120:4L and D 80:4L only). The powers supply and product continue operation throughout a mains glitch.
11.4. Power Supply
The R.SMPS (Regulated Switch Mode Power Supply) is designed to keep supply voltage rails at optimum levels. Thus the R.SMPS can deliver full rail voltage to the output sta consistent transient response and a clean LF response.
D SERIES Lake Operation Manual rev 3.0.4
28
11. Operation and performance
11. Operation and performance
D Series features a universal power supply with power factor correction (PFC). The device can accept any mains voltage, from 65 V to 265 V, allowing it to function worldwide in many different congurations. The PFC reduces
current peaks on the lines and reduces the requirements placed on the mains distribution system. D Series units offer an unparalleled power factor extremely close to one.
11.4.1. Low Inrush Current
High power ampliers with inadequate inrush current limiting can draw considerable current from the mains at
turn–on, sometimes tripping a fast–acting mains breaker. The D Series, however, has very low inrush current to prevent tripping of breakers. Several units can, under normal conditions, be powered up simultaneously. If you do experience problems powering up multiple units simultaneously, they must either be turned on manually in an ordered manner, or sequenced remotely using the Lake Controller software’s Global Control feature. Alternatively, the capacity of the mains supply should be increased.
NOTE: If insufcient power is available to allow simultaneous power–up, then there is probably insufcient capacity for full power output during operation. It is recommended that additional capacity is
added to the mains power distribution system.
11.4.2. Adaptive rail control
The D Series slimline models have Adaptive rail control available in Performance (default) and Green mode. In Green mode, this feature further increase the slimline models green credentials by lowering the idle
consumption. This is achieved by lowering power supply’s supply voltage, to the
raised, to allow for full power outtake, as soon as the signal returns. This feature is user controlled via the Lake Controller, where it can be turned on or off.
11.5. Auto power down
The D Series models have been equipped with a Auto Power Down function. If Auto Power Down is enabled,
user-defined
audio passing and there is no user interaction via the Lake Controller, CAFÉ or 3rd party controllers.
When the
the frame will turn on again.
NOTE: There is no Auto Power On feature on the return of signal, the device will need to be actively turned on after entering the standby mode via the Auto Power Down feature. This can be done from the network via the Lake Controller or the 3rd party protocol or via the front panel button.
D SERIES Lake Operation Manual rev 3.0.4
29
11. Operation and performance
11. Operation and performance
11.6. LoadPilot Load Monitoring
11.6.1. Introduction
LoadPilot is a feature in D Series ampliers that can continually monitor the integrity of loudspeakers and cables
connected to the outputs to ensure that they are functioning properly and free from major anomalies or faults.
By implementing LoadPilot, systems incorporating D Series ampliers can be certied in compliance with voice
evacuation standards such as EN54–16 and NFPA72.
LoadPilot functions by automatically superimposing low–level pilot tones on the input signal (if any present) to the amplier. One tone is below the range of human hearing (approximately 10–20 Hz) and the other above (24 kHz),
so the activity of LoadPilot is inaudible regardless of whether the system is currently reproducing program content. High–resolution current sensing on the outputs can calculate the impedance of the load at the frequency of the tones. Hence a stable measurement of the impedance of the load can be obtained and potential anomalies or faults can be detected that would indicate impaired loudspeaker function or total inoperability due to failure of the loudspeaker or faults in connected wiring. The superimposition of pilot tones and analysis is interleaved across the
amplier’s output channels with a maximum total cycle time of around 20 seconds.
LoadPilot is implemented and congured in the CAFÉ software. Monitoring status and fault indication are displayed
on the front panel and both in CAFÉ and Lake Controller.
LoadPilot may be congured with the automatic calibration or through a manual advanced mode, depending on
monitoring requirements and characteristics of the connected loudspeaker loads.
11.6.2. Automatic calibration
11.6.2.1. Functional description
Automatic calibration is suitable for the following applications and requirements for error detection:
If one or two low–impedance loudspeakers are connected; if two in parallel is default, it will warn if one is missing.
• If there are one or two “spurs” with 70V loudspeakers connected; if two in parallel is default, it will warn if one is missing.
If there is a short circuit in the load.
• If there is an open circuit (all loudspeakers missing).
For passive 2– and 3–way loudspeakers, if one or two LF drivers are connected and working; if two in parallel
is default, it will warn if one is missing.
For some passive 2–way designs, if one HF driver is disconnected. (However, with some loudspeakers the HF impedance is dominated by a passive component i.e. crossover lter and the anomaly will not be detected.)
NOTE: LoadPilot is enabled only when the amplier is On. It does not function while the amplier is in
Standby.
D SERIES Lake Operation Manual rev 3.0.4
30
11. Operation and performance
11. Operation and performance
11.6.3. Manual configuration
11.6.3.1. Functional description
Manual conguration can be used in special cases where proper functioning requires setting of custom
measurement frequencies, custom measurement levels, custom warning thresholds, or combinations of the three.
Manual conguration addresses the following issues:
Speakers with non stable impedance – For the LoadPilot feature to function the load itself needs to have a stable impedance at the frequency of the tone. Resonances in the speaker or other non linear phenomenons can
make the impedance at a certain frequency unstable. Stability needs to be veried by examining the impedance response to make sure it is relatively at at the tone frequencies and by verifying LoadPilot readings when playing
signal through the speaker at the most extreme expected level. The frequency of the pilot tones can be changed within certain ranges and a tone can be disabled. If a frequency where the speaker is stable can not be found one tone can be disabled and LoadPilot relies solely on the remaining tone.
High noise levels – To obtain accurate impedance measurements, it is necessary to drive a current sufciently above the noise oor. However, it is important to keep the level low in order to prevent audible artifacts from cone travel. At very high impedances, the drive current may be insufcient. In the automatic mode, level is set around 60 mV which produces usable results for impedance up to 660 ohms.
Inductance in loudspeaker cables – Loudspeaker cable inductance at higher frequencies is very high relative to passive resistance, and the inductance increases linearly with length. Consequently, monitoring at the 24 kHz pilot tone frequency can be problematic with very long cables. The automatic mode will estimate cable impedance for 24 kHz and allow it to be used as long as it is less than 33% of total impedance presented by the load and as long as the total impedance is below about 440 ohms.
DC blocking capacitors in loudspeakers – Some loudspeakers incorporate a capacitor designed to block damaging voltages at very low frequencies. This may inhibit accurate measurements when using the 10 Hz pilot tone. In automatic mode, LoadPilot will disable the 10 Hz tone if total impedance is above about 440 ohms.
Constant voltage loudspeakers – Loudspeakers driven via transformers in 70V/100V solutions are more likely
to exhibit wide variations in measured impedance as music and/or pilot tones are reproduced by the system. Also, most constant voltage systems operate more than two loudspeakers in parallel. Therefore, in addition to manual
conguration of LoadPilot, additional step may be required. These include:
Insertion of a series capacitor in each loudspeaker to block the 10 Hz LF tone – This will defeat measuring the
loudspeakers with the LF tone, but will allow the LF tone to propagate through the entire cable run.
• Insertion of EOL (end–of–line) resistors – This enables LoadPilot to detect cable faults in a spur of the system.
• Insertion of EOL (end–of–line) inductor – This is not mandatory, but it will avoid the loss of level at mid and high
frequencies due to the EOL resistor.
NOTE: Manual conguration of LoadPilot is implemented in CAFÉ versions 1.1.0. and later. For detailed information on manual conguration of LoadPilot, please refer to the integrated guide in the software
program and to the CAFÉ Coach videos posted on the Lab.gruppen web site and on the Lab.gruppen channel on YouTube.
D SERIES Lake Operation Manual rev 3.0.4
31
11. Operation and performance
12. Lake Processing and Lake Controller
11.6.4. Indication
The LoadPilot feature constantly monitors the impedances at the two given pilot tone frequencies and compares to the measured thresholds. The following faults and warnings can be triggered.
Speaker shorted warning – Both tones below lower threshold. Corresponds to a distant short circuit that can either be in the cabling or in the speaker.
Speaker damaged warning – One of the tones is below or above thresholds. Corresponds to an unexpected impedance deviation of one of the tones, most likely a damage to the speaker.
Under speaker count warning – Both tones above upper threshold. Corresponds to an impedance increase across the impedance response and most likely a loss of speaker(s) in a parallel speaker connection.
corresponding to loss of the load.
Short circuit fault – LoadPilot analysis below short circuit threshold.
11.7. Audio over Ethernet
D Series Lake devices include Dante and AES67 digital audio networking as standard. Utilizing the latest advances in Ethernet technology, Dante offers simplified system configuration and extremely low latency while delivering very high quality uncompressed digital audio across the Lake network. The Zen™ automatic configura­tion feature enables plug-and-play setup without third-party DHCP or DNS servers. Dante is compatible with high-bandwidth networks, allowing large numbers of audio channels to be distributed alongside control and analyzer data.
AES67 is a new open standard making it possible connect more devices together and share audio.
The D Series Lake also have a feature to convert between AES67 and Dante, and can accordingly work as a bridge between the two different network protocols. It can input 8 channels of AES67 and transmit them out again as 8 Dante channels or vice versa and in any combination of Dante and AES67 channels.
The D Series Lake support 8 x 8 Inputs and Outputs on Dante/AES67. The networked audio channels' inputs are routed to the Dante receivers and are shared between both Dante and AES67. The total number of networked audio inputs available is 8 (Dante + AES67). On the output side, the device has 8 channels in total – and it is possible to configure the channel as Dante only (Unicast or Multicast) or have it as an AES67 flow as well. Up to 8 channels can be included in an AES67 transmit flow.
In order for the device to be able to input networked audio, “Dante” must be enabled in Lake Controller. See Lake Controller Operation Manual for further details.
11.7.1. Dante
D Series devices support dual redundant inputs and outputs on Dante, in either 48 or 96 kHz, with receive latency as low as 0.25 ms and up to 5 ms.
Dante devices and channels can be given “friendly” names, meaning audio can be routed without having to use or remember complex numbers.
Dante channels can be routed in both Dante Controller or in Lake Controller.
D SERIES Lake Operation Manual rev 3.0.4
32
12. Lake Processing and Lake Controller
11.7.2. AES67
When the device is in AES67 enable mode, the device is in 48 kHz only (also for Dante subscriptions/transmissions). The receiver latency for AES67 subscriptions is 2 ms. Transmission flows are Multicast only.
AES67 subscriptions can only be configured in Dante Controller. The AES67 transmitter must support the SAP (Session Announcement Protocol). This is one of four device discovery methods referenced in the AES67 standard. Check if the transmitting non-Dante AES67 device supports SAP. Otherwise Dante Controller cannot discover the audio flows coming from the device. Dante devices support SAP if their AES67 mode is enabled.
Multicast IP addresses must be in the range of 239.69.0.0 - 239.69.255.255. If dual redundancy is enabled on the device, the AES67 flow only works on the primary network. It is still possible to utilize Dante on primary and secondary networks at the same time, as an AES67 flow is present on the primary.
12. Lake Processing and Lake Controller
12. Lake Processing and Lake Controller
12.1. Introduction
D Series Lake integrates seamlessly into the Lake Processing environment, providing all features, functionality and connectivity associated with all Lake Processors. The internal Lake Processing, which includes programmable crossovers, EQ, dynamics and other functions, is fully controllable via Lake Controller software with a version number of v6.3 for D 200:4L, D 120:4L and D 80:4L, v6.5.0 for D 20:4L and D 10:4L and v6.5.1 for D 40:4L. All models are compatible with newer versions of the Lake Controller.
both available on www.labgruppen.com. Also, additional documentation is available from the Start Menu after software installation.
12.2. Modules and Frames
A Frame represents one physical Lake Processor device (e.g. a D 200:4L). A maximum of four Modules are contained within each Frame; these are referred to as Module A, B, C and D. The number of Modules shown in a
ed as a Classic Crossover (Bessel, Butterworth, Linkwitz–Riley), as a Linear Phase
Contour Classic 1 Way (CL1–Way) Output Modules, providing a total of four Module outputs that can be routed to any of the four power outputs, but default is one to one (input 1 -> output 1 etc.). Please refer to the Lake
Controller Operation Manual for further information.
D SERIES Lake Operation Manual rev 3.0.4
33
12. Lake Processing and Lake Controller
12. Lake Processing and Lake Controller
12.3. Lake LoadLibrary™ and Fingerprints
are available in the Lake LoadLibrary,
Additionally, Lake LoadLibrary loudspeaker types may also include data relating to the electrical characteristics of a
on the device. This data set is termed a Fingerprint. When a sp
as SpeakerPresets
12.4. Loudspeaker Processor Overview
The Lake Processing system within D Series Lake devices may be congured with up to four processing Modules
containing a total of up to twelve processing Module outputs that can be routed to any of the four power output
channels. Each set of processing elements is referred to as a Module and can be congured as crossovers, full bandwidth auxiliary outputs, or a combination of the two. The relationship between inputs and outputs is dened
via the Lake Controller.
The Lake Processing system provides two distinct categories of crossovers:
• Innite Impulse Response lters (IIR) such as the classic Bessel, Butterworth or Linkwitz–Riley types; these are available with slopes ranging from 6 dB/octave to 48 dB/octave.
• Finite Impulse Response lters (FIR) providing zero phase shift with steep transition slopes at the crossover frequencies. These are also referred to as Linear Phase Crossovers.
12.5. Module, System and Sub–System Configuration Files
See Figure 8.1 where Module data is highlighted
in Red and Frame data in Blue.
possible to store a Module File directly on the hardware device.
12.6. Frame and System Presets
The entire processor conguration can be stored as a Frame Preset on this hardware device. Presets can be recalled) via the Lake Controller software or Preset Manager utility; presets can be stored using the Lake Controller
software or Preset Manager utility. A maximum of 100 Frame Presets can be stored on this device. The data within
a Frame Preset encompasses the congurations of all Modules in the Frame, including levels, crossover, EQ, input
mixer, routing, and all other parameters. As Frame Presets are stored in the hardware device, recall is available without using a PC.
D SERIES Lake Operation Manual rev 3.0.4
34
13. System configuration tutorial
Using the System Presets function in the Lake Controller, entire system congurations can be stored and
recalled across a network of Lake devices, including D Series Lake, LM, PLM and PLM+ Series devices. This
enables fast retrieval and switching of entire system congurations as minimal data is being sent between the
Controller and Processors.
13. System configuration tutorial
This section will describe how to get started with associated software and set up a basic system for operation.
13.1. Network setup
13.1.1. Network connections/topology
Each frame has two network ports; a primary and a secondary. See the below diagram for a typical network topology using the primary ports.
13. System configuration tutorial
By default, the secondary ports are congured in dual redundancy mode to support a second redundant network. The alternate conguration for the two ports is a switch mode which allows daisy–chaining devices in a single
network. Daisy chain mode is not recommended for more than a few devices, and for not more than two if running Dante audio along with control data.
Computer
Switch
D Series Lake
D Series Lake
D Series Lake
D Series Lake
D Series Lake
D Series Lake
Wireless
Access Point
Switch
D Series Lake
D Series Lake
D Series Lake
D Series Lake
D Series Lake
D Series Lake
NOTE: If using Dante audio in the network, the audio trafc needs to be ltered from reaching the wireless links.
13.1.2. Network configuration
Frames are congured by default to obtain IP addresses automatically. The frame will assign itself an IP address in the link local range (169.254.1.0 through 169.254.254.255). If a computer is congured the same way
D SERIES Lake Operation Manual rev 3.0.4
35
13. System configuration tutorial
13. System configuration tutorial
(which should be default on modern operating systems), it will reside in the same subnet as the devices and
address in the 172.31.0.0 – 172.31.255.255.
13.2. Software installation and firmware update
13.2.1. Lake Controller software suite
1. The Lake controller software suite includes the Lake controller and accompanying utilities: Lake LoadLibrary, Dante discovery services and documentation. Download the Lake Controller installation from www.labgruppen.com.
2. Execute the installer and follow the on–screen instructions. This is a typical software installation where the default settings are acceptable for the vast majority of users.
13.2.2. CAFÉ software
1. The CAFÉ software is available as a separate installer on www.labgruppen.com.
2. Execute the installer and follow the on–screen instructions. This is a typical software installation where the default settings are acceptable for the vast majority of users.
13.2.3. Firmware update
The latest firmware for the product is included in the Lake controller installation. It is likely that firmware installed on the new product is older and requires updating. The firmware bundle includes all internal components (so no separate update for Dante etc. are needed).
1. Make sure all frames are powered on and connected through a wired network.
2.
3. Select the appropriate product range.
4. If more than one network adapter is enabled, a prompt will appear requiring selection of the adapter connected to the frames.
5. If prompted, allow the application access through the Firewall.
6.
7. Frames already up to date will not be selected.
8. Read warning message and tap OK.
9. Wait for all updates to be completed. A wait indication will display on the unit(s) during updating.
10.
a manual power cycle is required. (Note: A manual power cycle requires the mains plug to be completely
11. If internal updates are needed, these will be performed by the frame after the power cycle. A wait indication is displayed.
12. Tap Exit to close the update utility.
D SERIES Lake Operation Manual rev 3.0.4
36
13. System configuration tutorial
13. System configuration tutorial
13.3. System setup
This tutorial provides a step–by–step guide for conguration of a typical professional loudspeaker system and provides an overview of the basic features and operation of the frame. This tutorial describes how to congure 4–channel frame for use with a generic 3–way loudspeaker system (with separate HF, MF and LF drivers), plus
a separate subwoofer. It assumes that the system is fed with analog outputs from a mixing console with one fullrange main output and a separate sub feed.
1. Connect the loudspeakers to the four power output channels: a. Channel 1 – Low Frequency Driver b. Channel 2 – Mid Range Driver c. Channel 3 – High Frequency Driver d. Channel 4 – Subwoofer
2. Connect the main output of the mixing console to analog input 1 of the frame and the sub feed to input 2.
While conguring, it is a good practice to make sure the volume is turned down on the console.
3. Ensure the frame is powered on and is in its default state, and that the computer has established an active Ethernet connection.
4. On the Tablet PC, launch the Lake Controller software application. Select the appropriate network adapter if
more than one is enabled, and tap NO to the dialog asking whether to load the previous conguration.
5. Tap MODULES button on the menu bar at the bottom of the screen to access the Module Menu and scroll bar.
6. On the Module scroll bar, the frame is represented with a frame containing four discs. These are labeled A, B, C and D, each representing one of the four Lake processing modules.
7. Tap the frame to select it, then tap again in the MAIN area of the screen to place all modules of the frame in
the current system conguration. The Lake Controller uploads settings from the frame.
8. Tap the icon for Module A; its border will turn yellow to conrm selection and an LED on the front panel of the associated device will illuminate.
9. Tap the Module Store/Recall button on the Modules Menu; the menu will change to show additional options.
10. Double–tap the Default Modules folder, then double–tap the Contour Classic Crossovers folder. A set of loudspeaker symbols will be displayed.
11. Tap CL3way, and then tap the RECALL button. This congures the DSP for the Module A as a 3–way crossover for the 3 way speaker.
12. Tap Yes when asked to conrm that all data will be overwritten.
13. An Output conguration dialog will pop up to allow for routing of module outputs to power channels. Tap the orange number buttons in the matrix to un–route, freeing up a power channel. Tap a blue number button at the intersection of the appropriate module output and power channel, routing the module output to the power channel. Proceed until you have routing according to the picture below and tap the bottom right return button to exit the dialog.
D SERIES Lake Operation Manual rev 3.0.4
37
13. System configuration tutorial
13. System configuration tutorial
1
2
3
4
Bridge Bridge
14. The B module is already a CL1way as default and can be used to drive the sub.
15. Tap Store/Recall EXIT to return to the Modules Menu.
16. Ensuring Module A (or any other module that you want to control) is selected (yellow border), tap I/O Cong.
17. The right side of the I/O CONFIG screen displays a block diagram for the Modules. Tapping the different blue
blocks will access the conguration screens for Input mixer, Levels, Input EQ, Delay and Output EQ/Crossover respectively. The magnifying glass at the far right end accesses the output conguration. (NOTE: Tapping the blue return button (left arrow), or the EQ/Levels EXIT button in the menu bar returns to the I/O Cong screen from the various conguration screens.)
Input Mixer Conguration – Drag sliders and tap ON/OFF buttons to control input mixer settings.
D SERIES Lake Operation Manual rev 3.0.4
38
13. System configuration tutorial
13. System configuration tutorial
Levels Control – Drag sliders and tap mute buttons for module input and output channels.
Delay Control – Drag sliders to control input and output delay Crossover control – Select lters and drag on the bottom
Parametric EQ control – Select lter on the top squares
and adjust lter properties by dragging the controls. Sliders at the bottom control center frequency and Q (bandwidth). Gain is controlled in the main window area. Additional lters can be added by tapping the top lter objects and placing new lters on the main area.
frequency bar to adjust crossover frequency. Crossover types may be changed by selecting the Crossover Functions button.
18. Tap the Input Gain button in the block diagram and unmute the Module Input Mute. Tap EQ/Levels Exit to return to
IO Cong.
19. The left side of the IO cong screen holds frame conguration and summary for Clock conguration, Input conguration, Dante conguration, Breaker Emulation Limiter conguration and Analog Iso–Float & AES Termination conguration. All these congurations should be correct by default for this example.
20. From I/O cong, tap Amplier Events & Control and navigate to the Status tab. Unmute the power channels and slowly increase the volume on the appropriate feed from the mixing console. Audio should now be active at the
outputs and heard through the loudspeakers. Close the Amplier Events & Control dialog with the return button and return to the main area by tapping the I/O Cong EXIT button.
Amplier Events & Control, Status tab – Drag sliders to adjust power channel attenuation and tap mute buttons to control power channel mute. Metering and Status monitoring is available for each power channel.
D SERIES Lake Operation Manual rev 3.0.4
39
13. System configuration tutorial
13. System configuration tutorial
21. Repeat step 16 and 20 for the B module. On the Output EQ/Crossover, tap the Aux Output Functions button on the menu bar and then tap LPF Enable button. Drag the Low pass lter control object on the frequency slider just above the menu bar to an appropriate crossover frequency for the sub, e.g. 100 Hz.
22. Use the control options mentioned in 17 to tune your loudspeakers. For larger systems, modules can be
placed in groups (Groups menu from the MAIN page) for control of multiple units.
23. Some features like RPM can only be congured from within CAFÉ software. Return to AMPLIFIER EVENTS & CONTROL; from the main area hit MODULES button, select a module (e.g. Module A), tap I/O Cong, tap AMPLIFIER EVENTS & CONTROL, and navigate to the Control tab. The CAFÉ button (next to bottom) opens the CAFÉ application and imports and highlights the current amplier and its RPM view.
CAFÉ, RPM view – Enter power requirements and impedances for the channels to congure RPM.
13.4. Additional Software Reference Material
Additional information regarding conguration of Lake Controller for specic loudspeaker systems is available in the
Lake Controller Operation Manual, available for download in PDF format at www.labgruppen.com/support.
Additional information on conguration of CAFÉ software is available in an integrated guide in the software program
and in the CAFÉ Coach videos posted on the Lab.gruppen web site and on the Lab.gruppen channel on YouTube.
D SERIES Lake Operation Manual rev 3.0.4
40
14. Appendix
14. Appendix
Category/Type Name On screen text Description Action
FRAME
Warning
Lake Controller ofine CTRL OFFLINE
Frame unable to nd Lake controller
on the network
Check network cabling/
network if controller
expected on the network
Warning
AES / Dante clock slipping CLOCK SLIPPING
Frame not able to lock to incoming
AES stream or Dante clock slipping.
Check AES sender and
clock conguration or
Dante clock settings
Warning
Dante device na me conict NAME CONFLICT
Two or more devices on the network
with the same Dante name
Review Dante
conguration
Warning
Dante module not detected
DANTE NEEDS
SERVICE
Lake cannot detect a functioning
Dante module
Restart device; if not
cleared it needs service
to operate Dante
Warning
Dante module with
incompatible rmware
DANTE F W INVALID
Dante module not loaded
with correct FW
Retry updating the rmware
with LakeUpdate
Warning
Dante module disabled DANTE DISABLED
Dante module not communicated
correctly or other internal
conguration fault
Restart device; if not
cleared it needs service
Warning
Sense fault D SP SENS FLT:DSP
Voltage and current sensing on ampli er
output fault y. Audio continues but
protection might be compromised.
No load monitoring
Restart device; if not
cleared it needs service
Warning
A/D converter power
supply fault
A/D P SU FAULT
Voltage supply to the analog input
converters faulty
Restart device; if not
cleared it needs service for
analog input to work
Fault
Audio Fault AUDIO FAULT
Internal audio interface
not functioning
Restart device; if not
cleared it needs service
Fault
DICO communication fault DICO COMM FAULT
Communication fault between host
and amplier platform
Restart device; if not
cleared it needs service
TEMP
Warning
Temperature warning
power supply
TEMP WARN:PSU
Power supply temperature approaching critical levels
Improve cooling or reduce
output power to avoid
temperature becoming
critical
Warning
Temperature warning
DSP area
TEMP WARN:DSP
DSP area temperature approaching
critical levels
Improve cooling or reduce
output power to avoid
temperature becoming
critical
Warning
Power supply
Temperature Limit
PTL ACTIVE
Amplier is reducing output power
to avoid power supply temp
fault protection
Improve cooling or reduce
output power to avoid
limiting
Warning
Amp channel
Temperature Limit
ATL ACT IV E
Amplier channel is reducing output
power to avoid amplier channel
temp fault protection
Improve cooling or reduce
output power to avoid
limiting
Category/Type Name On screen text Description Action
Fault
Temperature fault
power supply
TE MP F LT: PS U
Power supply temperature reached
internal protection limit
Automatically restarts
when cooled down
Fault
Temperature fault
DSP area
TE MP F LT: DS P
DSP area re ached
critical temperature
Improve cooling or
reduce power
PSU
Warning
Under Voltage Limit UVL ACTIVE
The Under Volt age limiter is active a
the mains supply is approaching
the lower end of the devices
operational voltage. Output power
is decreased to ensure mains distribution does not collapse
Increase mains distribution
stiffness or reduce output
power to avoid limiting
Warning
Power Average Limit PAL AC TIV E
Amplier is reducing output power due
to average power or mains current
draw is above safe operating levels
Reduce output power
to avoid limiting
Warning
Breaker Emulation Limit BEL ACTIVE
Power supply is reducing mains current
draw to stay within B EL congured
nominal current and prole
Improve mains distribution
and update BEL
conguration or reduce
output power to avoid
limiting
Warning
Mains supply glitch MAINS GLITCH
Mains glitch (missing cycles) was
detected on the mains inlet
Check mains distribution/
connection
Fault
Need service NEED SERVICE:18 Power supply internal error
Restart device; if not
cleared it needs service
Fault
Mains voltage above
400 volt peak
MAINS>400 VPK
Power supply detects mains voltage above 40 0 volt peak. Protective shut
down, auto restart attempt
Check mains distribution/
connection
Fault
Mains voltage above
270 V
MAINS>270 V
Power supply detects mains voltage
above operation voltage. Protective
shut down, auto restart attempt
Check mains distribution/
connection
Fault
Mains voltage below
65 V
Mains<65 V
Power supply detects mains voltage
below operation voltage. Protective
shut down, auto restart attempt
Check mains distribution/
connection
Fault
Power supply fault PS U FA ULT Internal power supply fault
Check mains distribution/
connection. Restart
device; if not cleared
it needs service
Fault
Check mains CHECK MAINS
Power supply detects unstable
mains supply. Protective shut down,
auto restart attempt
Check mains distribution/
connection
Fault
Power supply power protect PSU POWER PROT
Too high output power for too low
mains supply voltage. Protective
shut down, auto restart attempt
Improve mains supply
voltage or reduce
output power
LOAD
Warning
Speaker short SPKR SHORT Both LoadPilot tones below thresholds Check load or calibration
Warning
Speaker damaged SPKR DAMAGED
One LoadPilot tone is above
or below threshold
Check load or calibration
14. Appendix
14.1. Faults and warnings
D SERIES Lake Operation Manual rev 3.0.4
41
14. Appendix
14. Appendix
Category/Type Name On screen text Description Action
Warni ng
Under speaker count UNDER SPKR CNT
Both LoadPilot tones above
thresholds or LoadSmart detected
fewer speakers than expected
Check load, cabling and
calibration
Warni ng
More speakers OVR SPKR COUNT
LoadSmart detected more speakers
than expected
Check load and
Warni ng
Uncertain about load UNCERTAIN LOAD LoadSmar t uncertain about load
Check load and
Fault
No load NO LOAD
At least one LoadPilot tone above
above thresholds
Check load or calibration
Fault
Wrong load WRONG LOAD
LoadSmart detected impedance
response output model
Check load and
Fault
Short circuit SHORT CIR CUIT
LoadPilot or full frequency analysis
below short threshold or hardware
short protection
Check load and cabling
AMP
Warni ng
channel
TEMP WARN
critical temperature
Improve cooling or reduce
output power to avoid
temperature becoming
critical
Fault
TE MP FAU LT
internal protection limit
Automatically unmutes
when cooled down
Warning
(D200, D120, D80 only)
VHF WARNINGVery high frequency warning
Amplifier channel gain
reduction due to VHF content
Check input signal
Fault
Service channel SERVICE CH.
Restart device; if not
cleared it needs service
Fault
Very high frequency fault VH F FAULT
Check input signal
Fault
Current average limiter CAL ACTIVE
above safe operating level
Reduce output power
to avoid limiting
Clip
Current clip CURRENT CLIP
current limit
Reduce output power
to avoid limiting
Clip
Voltage clip VOLTAGE CLIP
Reduce output power
to avoid limiting
Clip
Module clip MOD. CLIP Module output signal clipped
Review gain structure.
Module gain vs AmpGain
SIGNAL
Fault
No input source NO INPUT
Input router has no valid
input source
Review input router
settings/connections
Clip
Analog/AES input clip INPUT CLIP
The signal on the analog/AES input
is above inputs capability
Lower the signal on the
D SERIES Lake Operation Manual rev 3.0.4
42
14. Appendix
14. Appendix
D SERIES 10:4
Level Load
Rated p ower
per channel
Line Cu rrent Measure d Power (W ) Thermal Dissipation
(A) In Out Dissipated BTU/hr kCal/hr
Mains Voltage 10 0 VAC
Standby
0.1 7 0 7 24 6
Power On , Idling, Green Mode
0.5 45 0 45 15 3 38
Power On , Idling, Performanc e Mode
0.7 71 0 71 241 61
Pink Pseudo Noise
16 Ω / Ch. 250 x 4 2.3 229 125 104 355 89 8 Ω / Ch. 250 x 4 2.4 240 12 5 11 5 391 98 4 Ω / Ch. 250 x 4 2.6 254 125 129 439 111 2 Ω / Ch. 250 x 4 2.8 279 125 154 527 133 100 V / Ch. 175 x 4 1.8 179 88 92 3 13 79 70 V / Ch. 250 x 4 2.3 230 12 5 105 358 90
Mains Voltage 12 0 VAC
Standby
0.1 7 0 7 24 6
Power On , Idling, Green Mode
0.4 44 0 44 152 38
Power On , Idling, Performanc e Mode
0.6 70 0 70 238 60
Pink Pseudo Noise
16 Ω / Ch. 250 x 4 1.9 228 125 103 350 88 8 Ω / Ch. 250 x 4 2.0 238 125 113 386 97 4 Ω / Ch. 250 x 4 2.1 252 125 127 433 109 2 Ω / Ch. 250 x 4 2.3 277 125 152 519 131 100 V / Ch. 175 x 4 1.5 179 88 91 311 78 70 V / Ch. 250 x 4 1.9 229 125 103 353 89
Mains Voltage 2 08 VAC
Standby
0.1 7 0 7 24 6
Power On , Idling, Green Mode
0.3 42 0 42 142 36
Power On , Idling, Performanc e Mode
0.4 66 0 66 225 57
Pink Pseudo Noise
16 Ω / Ch. 250 x 4 1.1 221 125 96 328 83 8 Ω / Ch. 250 x 4 1.1 228 125 103 353 89 4 Ω / Ch. 250 x 4 1. 2 24 5 125 120 408 103 2 Ω / Ch. 250 x 4 1. 3 269 12 5 144 493 124 100 V / Ch. 175 x 4 0.9 174 88 86 294 74 70 V / Ch. 250 x 4 1.1 222 125 97 332 84
Mains Voltage 2 30 VAC
Standby
0.1 7 0 7 25 6
Power On , Idling, Green Mode
0.3 41 0 41 141 36
Power On , Idling, Performanc e Mode
0.3 65 0 65 222 56
Pink Pseudo Noise
16 Ω / Ch. 250 x 4 1.0 218 125 93 317 80 8 Ω / Ch. 250 x 4 1. 0 225 125 10 0 342 86 4 Ω / Ch. 250 x 4 1.1 238 125 113 387 97 2 Ω / Ch. 250 x 4 1. 2 263 125 138 472 119 100 V / Ch. 175 x 4 0.8 168 88 81 275 69 70 V / Ch.
250 x 4 1.0 216 125 91 311 78
14.2. Current draw and thermal dissipation
D SERIES Lake Operation Manual rev 3.0.4
43
14. Appendix
14. Appendix
D SERIES 20:4
Level Load
Rated p ower
per channel
Line Cu rrent Measure d Power (W ) Thermal Dissipation
(A) In Out Dissipated BTU/hr kCal/hr
Mains Voltage 10 0 VAC
Standby
0.2 7 0 7 24 6
Power On , Idling, Green Mode
0.5 46 0 46 15 7 39
Power On , Idling, Performanc e Mode
0.7 71 0 71 243 61
Pink Pseudo Noise
16 Ω / Ch. 425 x 4 2.9 348 213 136 463 117 8 Ω / Ch. 500 x 4 3.5 418 250 16 8 573 144 4 Ω / Ch. 500 x 4 3 .7 444 250 194 662 167 2 Ω / Ch. 500 x 4 4.1 492 250 242 825 208 100 V / Ch. 250 x 4 1.9 230 125 10 5 360 91 70 V / Ch. 500 x 4 3.5 410 250 16 0 546 13 8
Mains Voltage 12 0 VAC
Standby
0.1 7 0 7 23 6
Power On , Idling, Green Mode
0.4 45 0 45 15 5 39
Power On , Idling, Performanc e Mode
0.6 71 0 71 241 61
Pink Pseudo Noise
16 Ω / Ch. 425 x 4 2.9 346 213 134 457 115 8 Ω / Ch. 500 x 4 3.5 411 250 161 550 139 4 Ω / Ch. 500 x 4 3 .7 4 41 250 190 650 164 2 Ω / Ch. 500 x 4 4.1 487 250 237 810 204 100 V / Ch. 250 x 4 2.0 231 125 106 361 91 70 V / Ch. 500 x 4 3.4 408 250 158 540 136
Mains Voltage 2 08 VAC
Standby
0.1 7 0 7 24 6
Power On , Idling, Green Mode
0.3 43 0 43 147 37
Power On , Idling, Performanc e Mode
0.4 67 0 67 229 58
Pink Pseudo Noise
16 Ω / Ch. 425 x 4 1.5 336 213 124 422 10 6 8 Ω / Ch. 500 x 4 1. 8 398 250 14 8 506 127 4 Ω / Ch. 500 x 4 1. 9 426 250 176 600 151 2 Ω / Ch. 500 x 4 2.1 471 250 221 753 190 100 V / Ch. 250 x 4 1.0 224 12 5 99 339 85 70 V / Ch. 500 x 4 1.8 395 250 145 496 125
Mains Voltage 2 30 VAC
Standby
0.2 7 0 7 24 6
Power On , Idling, Green Mode
0.3 43 0 43 14 6 37
Power On , Idling, Performanc e Mode
0.4 67 0 67 227 57
Pink Pseudo Noise
16 Ω / Ch. 425 x 4 1.5 333 213 12 0 411 104 8 Ω / Ch. 500 x 4 1. 8 394 250 14 4 493 124 4 Ω / Ch. 500 x 4 1. 9 419 250 169 577 145 2 Ω / Ch. 500 x 4 2.1 467 250 217 741 187 100 V / Ch. 250 x 4 1.0 222 125 97 331 83 70 V / Ch.
500 x 4 1.8 392 250 142 484 122
D SERIES Lake Operation Manual rev 3.0.4
44
14. Appendix
14. Appendix
D SERIES 40:4
Level Load
Rated p ower
per channel
Line Cu rrent Measure d Power (W ) Thermal Dissipation
(A) In Out Dissipated BTU/hr kCal/hr
Mains Voltage 10 0 VAC
Standby
0.2 7 0 7 24 6
Power On , Idling, Green Mode
0.6 59 0 59 201 51
Power On , Idling, Performanc e Mode
0.8 78 0 78 267 67
Pink Pseudo Noise
16 Ω / Ch. 700 x 4 5.1 502 350 152 518 131 8 Ω / Ch. 1000 x 4 7. 2 709 500 209 714 180 4 Ω / Ch. 1000 x 4 7.6 754 500 254 868 219 2 Ω / Ch. 800 x 4 7.0 689 400 289 986 249 100 V / Ch. 1000 x 4 7.1 701 500 200 684 17 2 70 V / Ch. 1000 x 4 7.5 738 500 238 812 205
Mains Voltage 12 0 VAC
Standby
0.2 7 0 7 24 6
Power On , Idling, Green Mode
0.5 59 0 59 200 50
Power On , Idling, Performanc e Mode
0.7 77 0 77 263 66
Pink Pseudo Noise
16 Ω / Ch. 700 x 4 4.2 497 350 147 503 127 8 Ω / Ch. 1000 x 4 5.9 700 500 199 6 81 172 4 Ω / Ch. 1000 x 4 6.3 743 500 243 829 209 2 Ω / Ch. 800 x 4 5.7 679 400 279 953 240 100 V / Ch. 1000 x 4 5.8 690 500 190 648 163 70 V / Ch. 100 0 x 4 6.1 726 500 226 772 19 5
Mains Voltage 2 08 VAC
Standby
0.3 7 0 7 25 6
Power On , Idling, Green Mode
0.5 58 0 58 19 8 50
Power On , Idling, Performanc e Mode
0.5 77 0 77 263 66
Pink Pseudo Noise
16 Ω / Ch. 700 x 4 2.2 486 350 136 464 117 8 Ω / Ch. 1000 x 4 3.1 6 81 500 181 6 17 155 4 Ω / Ch. 1000 x 4 3.3 723 500 223 759 191 2 Ω / Ch. 800 x 4 3.0 662 400 261 892 225 100 V / Ch. 1000 x 4 3.0 673 500 173 589 148 70 V / Ch. 100 0 x 4 3.2 707 500 207 707 178
Mains Voltage 2 30 VAC
Standby
0.3 7 0 7 25 6
Power On , Idling, Green Mode
0.4 58 0 58 197 50
Power On , Idling, Performanc e Mode
0.5 77 0 77 263 66
Pink Pseudo Noise
16 Ω / Ch. 700 x 4 2.2 474 350 124 423 106 8 Ω / Ch. 1000 x 4 3.0 664 500 164 558 141 4 Ω / Ch. 1000 x 4 3.2 70 5 500 205 701 176 2 Ω / Ch. 800 x 4 3.0 649 400 249 850 214 100 V / Ch. 1000 x 4 3.0 659 500 159 544 137 70 V / Ch. 100 0 x 4 3.2 694 500 194 661 166
D SERIES Lake Operation Manual rev 3.0.4
45
14. Appendix
14. Appendix
D SERIES 80:4
Level Load
Rate d power
per channel
Line Cu rrent
Power Factor
Measured Power (W) Thermal Dissipation
(A) (%) In Out Dissip ated BTU/hr kCal/ hr
Mains Vo ltage 100 VAC, 3 0 A
Standby 0.3 43 11 0 11 36 9
Power on , Idling 2.1 99 20 4 0 204 696 175
Pink Ps eudo Noise
16 Ω / Ch. 75 0 10.1 99 981 375 6 07 2070 522
8 Ω / Ch. 15 00 15 .3 99 149 2 749 74 3 2534 639
4 Ω / Ch. 200 0 14. 9 99 150 2 652 850 2900 731
2.67 Ω / Ch. 20 00 15 .3 99 15 39 625 914 312 0 787
2 Ω / Ch. 200 0 15. 2 99 153 8 560 978 3337 8 41
LoadPilot Sine 20 k Hz
8 Ω / Ch. 2.2 98 211 0 2 11 720 181
M
ain s Voltage 12 0 VAC, 30 A
Standby 0. 3 35 11 0 11 37 9
Power on , Idling 1.8 98 202 0 202 689 174
Pink Ps eudo Noise
16 Ω / Ch. 75 0 8.0 99 95 4 375 579 1977 499
8 Ω / Ch. 15 00 12.6 99 1476 749 7 27 24 80 625
4 Ω / Ch. 200 0 14. 4 99 17 39 8 17 923 3148 794
2.67 Ω / Ch. 20 00 14 .7 99 178 0 766 1014 3461 873
2 Ω / Ch. 200 0 15. 2 99 183 9 739 11 01 3755 947
LoadPilot Sine 20 k Hz
8 Ω / Ch. 1.8 98 211 0 211 719 181
Mains Vo ltage 20 8 VAC, 17.3 A
Standby 0.3 17 11 0 11 39 10
Power on , Idling 1.1 91 197 0 197 673 170
Pink Ps eudo Noise
16 Ω / Ch. 75 0 4.6 99 927 375 552 188 4 475
8 Ω / Ch. 15 0
0 7.1 99 14 36 749 687 2345 5 91
4 Ω / Ch. 200 0 9.3 100 195 5 1000 955 3260 822
2.67 Ω / Ch. 20 00 9.8 100 2087 1003 1084 3698 933
2 Ω / Ch. 200 0 10. 3 10 0 2182 1001 1181 40 30 1016
LoadPilot Sine 20 k Hz
8 Ω / Ch. 1.1 92 204 0 20 4 695 175
Mains Vo ltage 23 0 VAC, 16 A
Standby 0.3 17 12 0 12 39 10
Power on , Idling 1.0 89 193 0 19 3 660 166
Pink Ps eudo Noise
16 Ω / Ch. 75 0 4.2 99 948 375 573 1957 493
8 Ω / Ch. 15 00 6.4 99 144 3 74 9 694 236 9 597
4 Ω / Ch. 200 0 8 .1 99 190 7 10 00 906 3092 78 0
2.67 Ω / Ch. 20 00 8 .7 10 0 2052 1003 1049 3580 903
2 Ω / Ch. 200 0 9.4 100 2200 1000 1201 4096 103 3
LoadPilot Sine 20 k Hz
8 Ω / Ch. 1.0 89 204 0 204 695 175
D SERIES Lake Operation Manual rev 3.0.4
46
14. Appendix
D SERIES 120:4
Level Load
Rate d power
per ch annel
Line Current
Power Factor
Measur ed Power (W) Thermal Dissipation
(A) (%) In Out Dissipated BTU/hr kCal/hr
Main s Voltage 100 VAC, 3 0 A
Standby 0. 3 43 12 0 12 40 10
Power on, I dling 2.3 98 219 0 219 74 9 18 9
Pink Ps eudo Noise
16 Ω / Ch. 950 10.8 99 10 59 475 584 1994 503
8 Ω / Ch. 19 00 19. 2 99 1868 949 919 313 6 791
4 Ω / Ch. 3000 24.6 99 2389 1200 11 89 4057 1023
2.67 Ω / Ch. 3 000 25 .7 99 25 51 1151 1400 4776 1204
2 Ω / Ch. 3000 25.8 99 2576 1113 14 63 49 92 125 9
LoadPilot Sine 20 kHz
8 Ω / Ch. 2.4 98 231
0 231 789 199
Main s Voltage 120 VAC, 3 0 A
Standby 0. 3 36 11 0 11 39 10
Power on, I dling 1.9 98 215 0 215 734 185
Pink Ps eudo Noise
16 Ω / Ch. 950 8.8 99 10 35 475 560 1910 482
8 Ω / Ch. 19 00 1 5.1 99 176 5 949 815 278 3 70 2
4 Ω / Ch. 3000 24.0 99 2817 15 02 1315 4487 1131
2.67 Ω / Ch. 3 000 24.5 99 28 94 14 37 1456 4969 12 53
2 Ω / Ch. 3000 2 5.1 99 2980 1361 1619 5524 13 93
LoadPilot Sine 20 kHz
8 Ω / Ch. 2.0 97 226 0 2 26 773 195
Main s Voltage 20 8 VAC, 17.3 A
Standby 0. 3 18 12 0 12 42 11
Power on, I dling 1.1 91 2 11 0 2 11 720 18 2
Pink Ps eudo Noise
16 Ω / Ch. 950 4.9 99 1
001 475 526 179 5 453
8 Ω / Ch. 19 00 8.7 99 176 6 949 816 2786 702
4 Ω / Ch. 3000 13. 3 99 2687 1501 1186 4046 10 20
2.67 Ω / Ch. 3 000 14 .0 99 28 47 150 0 1346 4594 115 8
2 Ω / Ch. 3000 14. 8 99 3046 1500 1546 5276 1330
LoadPilot Sine 20 kHz
8 Ω / Ch. 1.2 93 2 21 0 2 21 75 4 19 0
Mai ns Volta ge 230 VAC, 16 A
Standby 0. 3 18 13 0 13 43 11
Power on, I dling 1. 0 90 20 5 0 205 698 176
Pink Ps eudo Noise
16 Ω / Ch. 950 4 .7 99 100 3 475 529 1803 455
8 Ω / Ch. 19 00 7.7 99 173 4 949 784 2676 675
4 Ω / Ch. 3000 11 .4 99 256 2 15 01 1061 3620 913
2.67 Ω / Ch. 3 000 12 .8 99 2 873 14 99 1374 4688 11 82
2 Ω / Ch.
3000 13 .1 99 2993 15 00 14 93 5095 1285
LoadPilot Sine 20 kHz
8 Ω / Ch. 1.0 90 214 0 214 730 184
14. Appendix
D SERIES Lake Operation Manual rev 3.0.4
47
14. Appendix
14. Appendix
D SERIES 200:4
Level Load
Rated power
per ch annel
Line Current
Power Factor
Measur ed Power (W) Thermal Dissipation
(A) (%) In Out Dissipated BTU/hr kCal/hr
Main s Voltage 100 VAC, 3 0 A
Standby 0. 3 52 17 0 17 58 15
Power on, I dling 2.4 97 235 0 235 802 202
Pink Ps eudo Noise
16 Ω / Ch. 115 0 12 .1 99 11 92 588 604 2061 520
8 Ω / Ch. 2300 22.3 99 219 8 1174 102 4 3493 881
4 Ω / Ch. 4400 29. 2 99 2853 1478 1375 4691 118 3
2.67 Ω / Ch. 500 0 29.2 99 2862 13 99 14 63 4 991 1259
2 Ω / Ch. 4400 29 .1 99 2826 1355 1472 5022 126 6
LoadPilot Sine 20 kHz
8 Ω / Ch. 2
.5 97 236 0 236 807 203
Main s Voltage 120 VAC, 3 0 A
Standby 0. 3 48 17 0 17 58 15
Power on, I dling 2.0 97 227 0 227 775 195
Pink Ps eudo Noise
16 Ω / Ch. 115 0 12. 0 99 11 80 588 593 2023 510
8 Ω / Ch. 2300 18. 4 99 214 4 1174 970 33 10 835
4 Ω / Ch. 4400 3 0.0 99 3457 18 96 15 61 5326 1343
2.67 Ω / Ch. 500 0 29.5 99 3 439 175 2 16 87 5756 14 51
2 Ω / Ch. 4400 29. 9 99 3495 16 65 18 30 624 5 15 75
LoadPilot Sine 20 kHz
8 Ω / Ch. 2.0 97 232 0 232 790 199
Mai ns Volta ge 208 VAC, 17.3 A
Standby 0. 3 27 18 0 18 60 15
Power on, I dling 1. 2 92 222 0 222 757 191
Pink Ps eudo Noise
16 Ω /
Ch. 115 0 5.7 99 1151 588 564 1923 485
8 Ω / Ch. 2300 10. 2 99 2055 1174 881 3005 75 8
4 Ω / Ch. 4400 16 .2 99 3286 1948 1338 4565 1151
2.67 Ω / Ch. 500 0 15.6 99 3 171 1752 1419 4843 12 21
2 Ω / Ch. 4400 16.0 99 325 3 16 65 158 9 5420 13 67
LoadPilot Sine 20 kHz
8 Ω / Ch. 1.2 92 229 0 229 78 0 197
Mai ns Volta ge 230 VAC, 16 A
Standby 0. 3 23 18 0 18 61 15
Power on, I dling 1. 2 92 222 0 222 757 191
Pink Ps eudo Noise
16 Ω / Ch. 115 0 5.1 98 113 4 588 546 186 3 470
8 Ω / Ch. 2300 9.2 99 2053 117 4 879 2999 756
4 Ω / Ch. 4400 15.9 99 3529 2 109 14 20 4845 12 22
2.67 Ω / Ch. 500 0 16.0 99 356 4 193 5 163 0 5 561 14 02
2 Ω / Ch. 4400 16.0 99 3577 18 56 17 22 5 875 14 81
LoadPilot Sine 20 kHz
8 Ω / Ch. 1.1 90 228 0 228 777 196
14. Appendix
14.3. Maintenance
During normal operation a D Series device provides trouble–free service. If the front panel display requires cleaning, use a soft cloth only; do not use solvent cleaners.
The dust lters on both sides of the front panel, behind the grilles, should occasionally be removed and cleaned to ensure maximum airow through the device. Disconnect the unit from mains power prior to removing dust the lter, and ensure the dust lter is replaced prior to turning the unit back on.
In extreme cases it may be necessary to clean the inside of the device. This procedure should only be carried out
by qualied service personnel. Internal cleaning may be necessary if the device has had prolonged operation in an
extreme environment such as one where cracked oil smoke machines are in use. If the device is used in extreme conditions, it is recommended to have it serviced every three years as a preventative measure.
D SERIES Lake Operation Manual rev 3.0.4
48
14. Appendix
14. Appendix
14.3. Maintenance
During normal operation a D Series device provides trouble–free service. If the front panel display requires cleaning, use a soft cloth only; do not use solvent cleaners.
The dust lters on both sides of the front panel, behind the grilles, should occasionally be removed and cleaned to ensure maximum airow through the device. Disconnect the unit from mains power prior to removing dust the lter, and ensure the dust lter is replaced prior to turning the unit back on.
In extreme cases it may be necessary to clean the inside of the device. This procedure should only be carried out
by qualied service personnel. Internal cleaning may be necessary if the device has had prolonged operation in an
extreme environment such as one where cracked oil smoke machines are in use. If the device is used in extreme conditions, it is recommended to have it serviced every three years as a preventative measure.
D SERIES Lake Operation Manual rev 3.0.4
49
15. Technical Specifications
15. Technical Specifications
15. Technical Specifications
Genera l
Processi ng / Network Lake / Dante Lake / Dante Lake / Dante
Total burst p ower all cha nnels (sh are amon g channe ls with RPM) 2000 0 W 12000 W 80 00 W
Max. O utpu t Power (al l ch.’s dri ven)
2 ohms 4400 W 3000 W 2000 W
2.67 ohms 5000 W 3000 W 2000 W 4 ohms 4400 W 3000 W 2000 W 8 ohms 2300 W 1900 W 1500 W 16 ohms 1150 W 950 W 750 W Hi-Z 70 V 3300 W 3000 W 2000 W Hi-Z 100 V 4700 W 300 0 W 20 00 W
Max. O utpu t power br idged m ode (all c h.’s driv en)
4 ohms 8800 W 6000 W 4000 W 8 ohms 8800 W 6000 W 4000 W 16 ohms 4600 W 3800 W 3000 W
Max ou tput po wer sing le channel (al l models)
2 ohms 4400 W
2.67 ohms 5900 W 4 ohms 4600 W 8 ohms 2300 W 16 ohms 115 Hi-Z 70 V 3300 W Hi-Z 100 V 4700 W
Peak out put volta ge 194 V Max ou tput curr ent 67 A Ration al Power Man agemen t (RPM)
Protecti on feature s Cu rrent Aver age Limite r (CAL), Very High Freque ncy Protec tion (VHF), Direc t Current P rotection ( DC),
D 200 :4L D 120:4L D 80:4 L
4 4 4
1)
1)
1)
0 W
Share “total burst power” of the product freely among channels. Any channel can scale up to the “Max. output power si ngle chan nel”
194 V 175 V 155 V
Shor t Circuit Prote ction, Cur rent-Cli p Limiter, Volta ge Clip Limiter, Temperature pr otection
Inter Sa mple Voltage Peak Lim iter (ISVPL )
Pilot ton e generat ion and an alysis LoadPil ot Load imp edance a nalysis
Temperatu re control Regulate d fans and sh ow must go on lim itation ( ATL, PTL)
THD + N 20 Hz - 20 kH z for 1 W < 0.05 % THD + N at 1 kHz a nd 1 dB below c lippin g < 0.04 % Dynamic range > 114 dB Chann el separation (Cros stalk) at 1 k Hz > 70 dB Freque ncy respo nse (1 W into 8 ohm, 20 Hz - 20 kH z) +/- 0.05 dB Intern al sampl e rate / Data path Product propagatio n delay AES 9 6 kHz / anal og input 1.61 / 1.68 ms
Lake pr ocess ing
Loudsp eaker proce ssing Up to 4 modules of Clas sic/li near-phase/F IR crossover, EQ, delay, Limite rMax™ - peak a nd RMS limite rs System tuning Input re dundan cy / Matrix Automat ic 4 level input redun dancy / 4 input m ixers System i ntegration Compreh ensive 3rd party p rotocol ove r UDP Ether net
Dante Audio Ne twork
Dante I/O 8 x 8 (shared with AES67) Networ k topology / redund ancy F lexible topology / Sup ports d aisy-cha ined and D ual redu ndant net works Sampl e rates / tran sport 48, 96 kHz / U ni + Multic ast Networ k latency 0.25, 0.5, 1.0, 2.0, 5.0 ms
AES67 Audio Networ k
I/O 8 x 8 (shared with Dante) Network topol ogy / redundancy Flexible topology / Supports daisy-chained networks Sample rates / transport 4 8 kHz / Multicas t Network la tency 2 ms
Yes
D SERIES Lake Operation Manual rev 3.0.4
50
15. Technical Specifications
15. Technical Specifications
Analog inputs
Inputs 4 high quali ty inputs with I so-Floa t ground isolation Maximum inp ut / digital referen ce + 26 dBu / +21 dBu Sampling rate / reso lution 96 kHz / 24 bit Input impedance balanced / unbalanced 20 / 10 kO hm THD + N (ty pical at 1 k Hz unweighted) 0.00022 % THD + N (ty pical at 20 Hz and 20 kHz unwe ighted) 0.00033 %
AES Inputs
Inputs 2 AES inputs (4 audio cha nnels) Supported s ample ra tes / resolution 44.1, 48, 88.2, 96 , 176.4, 192 kHz / up to 24 bit Sample rate conversion THD + N 20 Hz - 20 k Hz unweig hted 0.00003 %
Rear panel interfa ce
Analo g inputs 4 x Terminal block c onnectors along input with +, – and ground AES inputs 2 x Terminal block connectors Output connectors
Ethernet ports Detachable mains cord Neutr ik PowerCo n rated at 250 V / 32 A
Front p anel user interface
System s tatus indication 3 x tri-color LE D. FRAME, TEM P, PSU for dev ice statu s indication Channel status indication 3 x tri-color L ED per chan nel. Statu s indication separ ated for cha nnel LOAD, AMP, SIGNAL s tatus Mute Per chan nel touch b utton for MUTE contro l and tri-c olor LED fo r indication Power Touch bu tton for ON /STANDBY control an d tri-color LED fo r power state in dication Select To uch button an d LED for bi-dire ctional device so ftware s elect functionalit y
Mains Power
Nominal voltage 100 – 240 V AC 50 – 60 Hz Operating voltage 70 – 265 V AC 45 – 66 Hz Mains wall plug
Power supply features
Soft st art / Inr ush power Yes / Ma x 8 A Power factor co rrection > 0.98 for main s power > 400 W Regulated switch mode power sup ply (R.SMP S) Yes Breaker Emulation Limiter (BEL) BEL max c urrent th reshold 32 A 25 A 15 A Power Average L imite r (PA L) Yes Under Volta ge Limiter (UVL) Yes Mains undervoltage and o vervoltag e protecti on and mains gl itch toler ance
Dimensions
Rack rai l to rear pan el W: 483 mm (19”), H: 88 mm (2 U), D: 424 mm (16”) Overall all depth front–rear support D: 463 mm
Weight Finish
Approvals
D 200 :4L D 12 0:4L D 80:4L
Can take u p to 16 mm 2 x EtherC on RJ45 100/1000 Base –T for the Lake Controller, Dante controller a nd/or DLM (3rd pa rty protocol)
Selectable on order CEE 7/7 “Schuko” 23 0 V / 16 A, NEMA L5–30 “Twistlock” 125 V / 30 A, NEMA 5–15P 125 V / 15 A (D 80:4 only), NEMA 5–20P 125 V / 20 A (D120:4 only), NEMA 6 –20P 250 V / 20 A, AS/NZS 3112 230 V / 15 A (Aus/Nz), BS 546 230 V / 16 A (India), C–3 0P 125V / 30A (Japan)
Yes
16.5 kg (36 lbs) 15.8 kg (35 l bs) 14.5 kg (32 lbs) Black painted stee l chassi s with grey pa inted stee l front with det achabl e grille
CE, ETL (A NSI/UL, C SA), PSE, RCM
2
(6 AWG) cable s
Not e 1): Lab.g ruppen bu rst power (1 kHz, 25 ms b urst power @ 150 BPM, 12 dB Cr est factor)
All specifications are subject to change without notice.
D SERIES Lake Operation Manual rev 3.0.4
51
15. Technical Specifications
15. Technical Specifications
Genera l
Proces sing / Net work Lake / Dante Lake / Dante Lake / Da nte
Total burst p ower all cha nnels (sh are among ch annels w ith RPM) 4000 W 2000 W 1000 W
Max. O utpu t Power (al l ch.’s driven)
2 ohms 800 W 50 0 W 250 W
2.67 ohms 1000 W 50 0 W 250 W 4 ohms 1000 W 500 W 250 W 8 ohms 1000 W 500 W 250 W 16 ohms 700 W 425 W 250 W Hi-Z 25 V 500 W 50 0 W 250 W Hi-Z 70 V 1000 W 500 W 25 0 W Hi-Z 100 V 1000 W 250 W 175 W
Max ou tput po wer single c hann el
2 ohms 850 W 8 50 W 850 W
2.67 ohms 1150 W 1150 W 1000 W 4 ohms 1750 W 1600 W 1000 W 8 ohms 1350 W 1100 W 1000 W 16 ohms 700 W 6 00 W 600 W Hi-Z 25 V 500 W 50 0 W 500 W Hi-Z 70 V 1450 W 1400 W 1000 W Hi-Z 100 V 2000 W 1000 W 70 0 W
Peak outpu t voltage 150 Vpk 142 Vpk 142 Vpk Max ou tput curr ent 30 Apk 30 Apk 30 Apk
Rational Po wer Manag ement (RPM)
Protecti on featur es
Inter Sa mple Voltage Peak Lim iter (ISVPL )
Pilot ton e generat ion and an alysis Yes Load imp edance a nalysis Yes Temperatu re control
D 40:4 L D 20:4L D 10:4 L
4 4 4
1)
1)
Share “ Total burst pow er” of the produc t freely among ch annels. Any chann el can sc ale up to the “single chann el max pow er”
145 Vpk 100 Vpk 65 Vpk Curre nt Average Limiter (CAL), Very High Fre quency Protection ( VHF), Direct Current Protection (DC), Shor t Circuit Protection, C urrent-C lip Limi ter, Voltage Cli p Limiter, Temperature protec tion
THD + N 20 Hz - 20 kH z for 1 W < 0.05 % THD + N at 1 kHz a nd 1 dB below c lippin g < 0.04 % Dynam ic range > 112 dB Chann el separation (Cros stalk) at 1 k Hz > 70 dB Freque ncy respo nse (1 W into 8 ohm, 20 H z - 20 kHz) +/- 0.05 dB Intern al sampl e rate / Data pat h Produc t propagation dela y AES 96 kHz / an alog input 1.61 / 1.68 ms
Lake pr ocess ing
Loudsp eaker proce ssing Up to 4 modules of Classic/ linear-ph ase/FIR c rossover, EQ, de lay, Limiter Max™ - peak an d RMS limi ters System tu ning Input re dundan cy / Matrix Automatic 4 leve l input re dundan cy / 4 input mi xers System i ntegration Comprehensive 3rd par ty protoc ol over UDP Ethernet
Dante Audio Ne twork
Dante I/O 8 x 8 (shared with AES67) Network topology / re dundan cy Flexible top ology / Supports Daisy-chained and Dual re dundant net works Sample rate s / transpor t 48, 96 kHz / Uni + Multicast Network latency 0. 25, 0.5, 1.0, 2.0, 5.0 ms
AES67 Audi o Network
I/O 8 x 8 (shared with Dante) Network topology / redundancy Flexible topology / Supports daisy-chained networks Sample rates / transport 48 kHz / Multicast Network lat ency 2 ms
Anal og inpu ts
Inputs 4 hig h qualit y inputs w ith Iso-F loat™ ground isolation Maxi mum input / digital refe rence + 26 dB u / +21 dBu Samplin g rate / resol ution 96 k Hz / 24 bit Input impedance balanc ed / unbal anced 20 / 10 kOhm THD + N (ty pical at 1 kHz unweigh ted) 0.00022 % THD + N (ty pical at 20 Hz and 20 kHz unweighted) 0.0 0033 %
D SERIES Lake Operation Manual rev 3.0.4
52
15. Technical Specifications
15. Technical Specifications
AES Inputs
Inputs 4 AES inputs Supported sample rate s / resolu tion 44.1, 48, 88.2, 96, 176.4, 192 kHz / up to 24 bit Sampl e rate conversion THD + N 20 Hz - 20 kHz unweig hted 0.00003 %
Back panel interface
Analog inputs 4 x Terminal block connectors an alog input with +, - and ground AES inputs 4 x Terminal block c onnectors a nalog input with +, - and ground
Output connectors
Ethernet ports 2 x EtherC on RJ45 Lake Controll er, Dante controller an d/or DLM (3rd p arty p rotocol) Detachable mains cord Detachable locking 3-pin IEC rate d at 250 V / 16 A
Front p anel user i nter face
System s tatus indication Channel s tatus indication 3 x tri- color LED pe r channe l. Status indi cation se parated fo r channe l LOAD, AMP, SIGNAL status Mute Per chan nel touch but ton for MUT E control a nd tri-color LED for indication Power Touch button for ON/STANDBY control an d tri-colo r LED for power state indication Select Touch bu tton and LE D for bi-directional device software select functionality
Mains Power
Nominal voltage 100 - 240 V AC 50 - 6 0 Hz Operating voltage 70 - 265 V AC 45 - 66 Hz Mains wall plug Selectable on order
Power supply features
Soft st art / Inr ush power Yes Power factor cor rection > 0.98 for main s power > 300 W Regulated switch mode power supply (R.SM PS) Yes Breaker Emulation Limiter (BEL) Yes BEL max c urrent th reshold 15 A 7 A 7 A Power Average L imite r (PA L) Yes Under Volta ge Limiter (UVL) Ye s Mains undervoltage and overvoltage protection and mains gli tch tolera nce
Dimensions
Rack rail to rear pan el W: 483 mm (19”), H: 44 mm (1 U), D: 425 mm (16.7”) Overall depth fro nt-rear su pport D: 463 m m
Weight
Finish
Approvals
D 40:4 L D 20 :4L D 10 :4L
to 8 mm2 (8.2 AWG) ca bles
3 x tri-color LED. FRAM E, TEMP, PSU for devic e status indication
CEE 7/7 “Schuko” 23 0 V / 16 A, NEMA 5-15 125 V / 15 A, BS1363-A 250 V / 13 A, IA16A3 250 V / 16 A, AU/NZ 250 V / 10 A, JP 125 V / 15 A, CPCS-CCC 250 V / 10 A
Yes
8.3 kg (18.3 lbs) 7.9 kg (17.3 lbs) 7.8 kg (17.1 lbs)
Black painted steel chassis with grey painted steel fr ont with detachabl e grille
CE, ETL (ANSI/UL , CSA), PSE, RCM, BIS, CCC
No No
Not e 1): Lab.g ruppen bu rst power (1 kHz, 25 ms b urst power @ 150 BPM, 12 dB Cr est factor)
All specifications are subject to change without notice.
D SERIES Lake Operation Manual rev 3.0.4
53
16. Warranty and support
16. Warranty and support
16. Warranty and support
16.1. General
This product is manufactured by Lab.gruppen, and it is warranted to be free from any defects caused by
components or factory workmanship, under normal use and service, for a period of ten (10) years from date of purchase from an authorized Lab.gruppen dealer. If the product fails to perform as specied during the warranty
period, Lab.gruppen will undertake to repair, or at its option, replace this product at no charge to its owner, provided the unit is returned undamaged, shipping prepaid, to an authorized service facility or to the factory. This warranty shall be null and void if the product is subjected to: repair work or alteration by a person other than those authorized by us; mechanical damage including shipping accidents; war, civil insurrection, misuse, abuse, operation with incorrect AC voltage; incorrect connections or accessories; operation with faulty associated equipment; or exposure to inclement weather conditions. Damage due to normal wear and tear is not covered by the warranty. Units on which the serial number has been removed or defaced will not be eligible for warranty service. Lab.gruppen shall not be responsible for any incidental or consequential damages. Lab.gruppen’s responsibility is limited to the product itself. Lab.gruppen takes no responsibility for any loss due to cancellation
of any events, or rent of replacement equipment or costs due to a third party’s or customer’s loss of prot, or any
other indirect cost or losses however incurred. Lab.gruppen reserves the right to make changes or improvements in design or manufacturing without assuming any obligation to change or improve products previously manufactured. This warranty is exclusive, and no other warranty is expressed or implied. This warranty does not affect the customer’s statutory rights.
International Warranties
Please contact your supplier or distributor for this information, as rights and disclaimers may vary from country to country.
16.2. Technical assistance and service
16.2.1. International service
If your Lab.gruppen product requires repair, contact your Lab.gruppen dealer or distributor, visit http://labgruppen.com/support or contact Lab.gruppen by phone or email to obtain details for the nearest authorized service center.
D SERIES Lake Operation Manual rev 3.0.4
54
16. Warranty and support
16.2.2. Factory service
16. Warranty and support
In the event a Lab.gruppen product requires factory service, you may contact Lab.gruppen’s service department for return instructions and a Return Authorization number.
Please note for product return:
1. Use the original packing.
2. Include a copy of the sales receipt, your name, return address, phone and fax number, email address and description of the defect.
3. Mark the Return Authorization number on the outside of the packing.
Ship the product prepaid to:
Music Tribe Brands Sweden AB Faktorvägen 1 SE-434 37 Kungsbacka Sweden Phone: +46 300 56 28 00
service@labgruppen.com www.labgruppen.com
D SERIES Lake Operation Manual rev 3.0.4
55
Notes
Notes
Notes
D SERIES Lake Operation Manual rev 3.0.4
56
Notes
Notes
Notes
D SERIES Lake Operation Manual rev 3.0.4
57
labgruppen.com
Lab.gruppen adopts a policy of continuous improvement and product specication is subject to change.
RPM, R.SMPS, PFC, CDM, BEL, UVL, CAFÉ, ESP, ISVPL, Iso–Float, Raised Cosine, MESA EQ, LimiterMax and
LoadLibrary are trademarks of Lab.gruppen AB. All other trademarks remain the property of their respective owners.
Copyright © 2018 Tribe Brands Innovation Sweden AB. All rights reserved.
Item no. OM–DSERIES–LAKE
Loading...