LAARS VW-PW Installation Manual

Installation, Operation and Maintenance Instructions Document 2051F
Installation, Operation and Maintenance Instructions for
Mighty Therm
Volume Water Heaters
Model VW-PW Sizes 175-400
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water heater installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed exactly , a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
H0147500F
Page 2
LAARS Heating Systems
TABLE OF CONTENTS
SECTION 1. General Information
1.1 Introduction.................................................... 3
1.2 Warranty........................................................ 3
1.3 Technical Assistance..................................... 3
SECTION 2. Installation Instructions
2.1 General Information....................................... 4
2.2 Field Assembly ..............................................4
2.3 Site Location.................................................. 5
2.3.1 Installation Information...................................5
2.3.2 Outdoor Installation (U.S. only)...................... 5
2.3.3 Flooring - Typical Installation ......................... 6
2.4 Combustion and Ventilation Air Supply.......... 6
2.4.1 Outdoor Air Supply ........................................ 7
2.4.2 Indoor Air Supply ........................................... 7
2.4.3 Exhaust Fans or Vents .................................. 7
2.5 Venting of Combustion Products ................... 7
2.5.1 General Information....................................... 7
2.5.2 Replacement of Existing Heater .................... 8
2.6 Water Flow .................................................... 8
2.6.1 Reversible Water Connections ...................... 8
2.6.2 Water Chemistry.......................................... 11
2.6.3 Freeze Protection ........................................ 11
2.6.4 Water Hardness .......................................... 11
2.6.5 Pump Requirements.................................... 14
2.6.6 Pressure Buildup in Water System .............. 14
2.6.7 Pressure Relief Valve .................................. 14
2.6.8 Water Pressure ........................................... 14
2.6.9 Pump Installation ......................................... 14
2.6.10 Storage Tank Installation ............................. 15
2.6.11 Thermal Circulation of Hot Water in
Cold Water Supply Lines ............................. 15
2.7 Gas Supply and Piping ................................ 16
2.7.1 General Instructions..................................... 16
2.7.2 Special Precautions for Propane Gas.......... 16
2.8 Electrical Wiring........................................... 16
2.9 Combined Space Heating/Potable
Water Heating Systems............................... 17
2.9.1 Combined Space Heating............................ 17
SECTION 3. Operating Instructions
3.1 Normal Operating Sequence ....................... 17
3.2 Start-Up Procedure...................................... 17
3.3 Setting the Temperature Controls................ 20
3.3.1 Remote Water Heater Temperature
Control: ........................................................20
3.3.2 Internal Water Heater Temperature
Control: ........................................................20
3.4 Adjustment for Minimum Input Rate
(models with modulating gas valve)............. 21
3.5 Hi-Limit Switch Checkout............................. 22
3.6 Shut-Down Procedure ................................. 22
SECTION 4. Maintenance
4.1 General Instructions..................................... 22
4.2 Replacement of Gas Controls...................... 22
4.3 Heat Exchanger........................................... 24
4.3.1 Inspecting the Heat Exchanger.................... 24
4.3.2 Cleaning the Heat Exchanger ...................... 24
SECTION 5. Troubleshooting
5.1 Gas Pressure Tests..................................... 24
5.1.1 Checking the Main Line Gas Pressure ........ 24
5.1.2 Checking the Manifold
Regulated Gas Pressure ............................. 25
5.2 Electrical Troubleshooting ........................... 25
5.2.1 Heater Does Not Come On.......................... 25
5.2.2 Testing the Transformer .............................. 26
5.2.3 Testing the Electrical Power Supply............. 26
5.2.4 Testing the Manual Reset
Hi-Limit Switch............................................. 26
5.2.5 Testing the Flow Switch ...............................26
5.2.6 Testing the Fusible Link
(Flame roll-out switch) ................................. 26
5.2.7 Testing the Fuse.......................................... 27
5.2.8 Testing the Ignition Control
(for spark ignition)........................................ 27
5.2.9 Testing the Ignition Control
(for standing pilot)........................................ 28
5.2.10 Testing the High Voltage Ignition Lead ........ 28
5.2.11 Testing the Safety Shutoff
(for standing pilot)........................................ 28
5.2.12 Testing the Safety Shutoff
(for automatic pilot)...................................... 28
5.2.13 Testing the Igniter Electrode ........................ 28
5.2.14 Testing the Pilot Thermocouple
(for standing pilot)........................................ 29
5.2.15 Testing for Pilot burner
(for spark ignition)........................................ 29
5.2.16 Testing for Burner Ignition
(for standing pilot)........................................ 30
5.2.17 Heater Will Not Shut Off .............................. 30
5.2.18 On-Off Main Burner Cycling......................... 30
5.2.19 Testing the Terminal Strip/External
Controls ....................................................... 30
SECTION 6. Parts List
6.1 General Information..................................... 30
6.2 Parts List ..................................................... 30
Mighty Therm Volume Water Heaters
Page 3
SECTION 1. General Information
1.1 Introduction
This manual provides installation, operating, and maintenance instructions for Models VW and PW Volume Water Heaters, Sizes 175 through 400. Review all application and installation procedures completely before proceeding with the installation. Experience has shown that most operating problems are caused by improper installation.
The VW-PW heaters are offered in a basic configuration (see Figure 1). On PW heaters the pump is factory installed. On VW heaters the pump is field installed.
1.2 Warranty
The VW-PW heaters are sold with a limited factory warranty.
Make all warranty claims to an authorized Laars representative or directly to the factory. Claims must
include the heater serial number and model (this information can be found on the rating plate), installation date, and name of the installer. Shipping costs are not included in the warranty coverage.
Some accessory items are shipped in separate packages. Inspect everything for damage immediately upon delivery, and advise the transporter of any shortages or damage. Any such claims should be filed with the transporter. The transporter will not accept a claim from the shipper, Laars.
The warranty does not cover damage caused by improper installation, operation, or field modification.
1.3 T echnical Assist ance
Consult Laars or your local wholesaler with any questions or problems involving the specification, installation and operation of Laars equipment. An experienced technical support staff is ready to assist in assuring the proper performance and application of Laars products.
Dimensions shown in inches cm.
Gas Connection
Size Water C C V
Connect. U.S. Only (Indoor) Vent
Nat. Propane Size A B (Outdoor) Dia.
Size in. mm in. mm in. mm in. cm in. cm in. cm in. cm in. mm
175 250 325 400
Figure 1. General configuration.
3
/4 19
3
/4 19
3
/4 19
3
/4 19
Note: Dimensions may vary.
1
/2 13 11/2 38 18 46 261/2 67 141/16 36 23/2 60 6 152
1
/2 13 11/2 38 221/2 57 31 79 181/16 47 243/4 63 7 178
1
/2 13 11/2 38 263/4 68 353/4 91 193/16 49 257/8 66 8 203
1
/2 13 11/2 38 313/4 80 401/4 102 225/8 58 267/8 68 9 229
Page 4
LAARS Heating Systems
SECTION 2. Installation Instructions
2.1 General Information
WARNING
Follow local regulations with respect to installation of carbon monoxide (CO) detectors and manufacturer's maintenance schedule of the heater.
Install the VW-PW heaters in accordance with the procedures in this manual (or the Laars warranty may be voided), local codes and ordinances. In the absence of such codes, install the heaters in accordance with the latest edition of the National Fuel Gas Code, ANSI Z223.1. In Canada, the installation must be in accordance with CAN1-B149.1 or .2 and local codes. The authority having jurisdiction may require the installation conform to the Standard for Controls and Safety Devices for Automatically Fired Heaters, ANSI/ASME CSD-1. Any changes to the heater, gas controls, gas orifices, wiring or draft diverter may void the warranty. If field conditions require a change to any of the above, consult the factory.
All gas-fired products require correct installation to assure safe operation. The requirements for heaters include the following:
1. Field assembly of drafthood or vent cap (see
Section 2B).
2. Appropriate site location (clearances) and
flooring.
3. Sufficient combustion and ventilation air.
4. Adequate venting of combustion products.
5. Adequate water flow.
6. Properly sized gas meter and piping.
7. Proper electrical wiring.
This manual provides the information needed to meet these requirements. Review all application and installation procedures completely before continuing the installation.
number for the drafthood is on the heater rating plate. Follow this procedure to make the conversion:
a. Remove the top filler plate, stamped “HOT”, by
slipping a fine-blade screwdriver into the slot at the rear of the plate and gently prying it up (see Figure 2).
b. Remove the two screws attaching the adapter
plate to the top assembly and lift it out (see Figure 3).
c. Remove the vent cap or drafthood from its
package.
Figure 2. Top filler plate. Figure 3. Adapter plate.
Figure 4. Flue transition Figure 5. Vent cap with
ring. adapter plate
(outdoor).
2.2 Field Assembly
The VW-PW heater is shipped from the factory with the top assembly in the low-profile configuration for outdoor installations.
The VW-PW heater is design certified for indoor installation when equipped with a special drafthood, which must be installed without modification. The part
Figure 6. Drafthood with Figure 7. Drafthood switch
adapter plate receptacle. (indoor).
Mighty Therm Volume Water Heaters
d. Disengage the flue transition ring from the stack
extension and place it on top of the collector assembly as shown in Figure 4.
e. Slide the adapter plate over the bottom of the
stack extension as shown in Figure 5. Fit the stack extension down over the flue transition ring. Seat the adapter plate on the top assembly and secure it with two screws (see Figure 6).
f. Indoor models, size 175 and 250 only, require an
adapter cable (included with product). The cable connects the blocked vent safety switch (BVSS) on the bell of the external draft hood to the 6­position Molex plug on the side of the unit (see Figure 7). Refer to instruction sheet included with cable.
Closet Installation
(unacceptable)
A closet is any 4 sided enclosure which is less than 16* times the total volume of all the gas fired appliances within the enclosure.
Page 5
Room Installation
(acceptable)
A room is any enclosure which is at least 16* times greater than the total volume of all the gas fired appliances within the enclosure
2.3 Site Location
2.3.1 Installation Information
WARNING
Improper installation or maintenance can cause nausea or asphyxiation from carbon monoxide in flue gases which could result in severe injury, property damage, or death.
Avoid placing the heater in locations where it can be damaged by water or condensate leakage. If this is not possible, provide a suitable drain pan to catch and divert any leakage. The pan must not block natural flow of air around the heater.
Locate the heater to provide adequate clearance on all sides for inspection, service and to provide adequate air circulation for proper operation.
Locate the heater so the clearances from combustible surfaces shown in Table 1 and Figure 8 are met.
Indoors Outdoors
Clearance from: inch mm inch mm
Top 37 940 Unobstructed Water conn. side 12 305 Unobstructed Opposite side 6 152 6 152 Front Alcove Unobstructed Rear 6 152 6 152 Vent* 6 152 — Flooring Combustible Combustible
Service clearance = 36 inches (914mm) at front of heater, and 18 inches (457mm) at water connection side. *1" (25mm) if double wall vent is used.
Table 1. Minimum Boiler Clearances
from Combustible Surfaces.
Alcove Installation
(acceptable)
An alcove suitable for the installation of a heater is a restricted section of a room not separated from the room by a door or partition and which meets the minimum clearances specified in this manual.
* When the ceiling height exceeds 8 feet, you are only allowed to consider 8 feet when calculating the total volume of the enclosure.
Figure 8. Alcove installation.
Locate the heater on a waterproof floor with a floor drain and a 6 inch (152 mm) minimum curb on all four sides to protect the building if heater repairs are needed.
2.3.2 Outdoor Installation (U.S. Only)
Caution
Outdoor installations are not recommended in areas where the danger of snow blockage exists. VW-PW heaters can be installed in the standard low-profile, grate top configuration as received from the factory, or with an optional vent cap.
Locate the heater in an open, unroofed area. Do not locate the heater below or adjacent to any doors, windows, louvers, grills, etc., which connect in any way with an inhabited area of a building, even though the access might be through another structure such as a garage or utility room (see Figure 9 and Table 1). There must be a minimum of 4 feet (1.22 m) horizontally and vertically between the heater and any door, window, or gravity inlet to a building (see Figure 10).
If the heater is installed close to a structure, protect it from rain water runoff with rain gutters on the roof or other measures. Do not locate the heater near sprinkler systems that could spray water on it.
Page 6
LAARS Heating Systems
Concrete slab must extend out a minimum of 12 in. (305mm) on all sides.
LAARS
UNIT
(Side View)
Base For Combustible Floors
Roof - Wood and Steel Construction
Figure 9. Incorrect outdoor installation.
Figure 10. Outdoor location installation.
A void locations where wind deflection off nearby structures might cause wind loading and downdraft conditions. Where downdraft conditions exist, locate the heater at least 3 feet (0.91 m) from the structure.
Figure 11. Standard base for combustible floor.
Mounting Platform must extend out a minimum of 12 in. (305mm) on all sides.
LAARS
20 Gauge Galvanized Sheet Metal Cap
Roofing
Figure 12. Typical roof mounting.
Base For Combustible Floors
UNIT
(Side View)
Raised Mounting Platform (Wood)
Base Rail Flashing
Roof
2.3.3 Flooring - Typical Installation
Do not install the heater directly on carpeting without placing a non-combustible platform between the carpeting and the heater. If the heater is installed in a carpeted alcove, the entire floor of the alcove must be covered by a non-combustible panel. The panel must be strong enough to carry the total weight of the heater and all piping, pumps, and any other equipment attached to the heater. For rooftop installation, see Figure 11 through Figure 13.
2.4 Combustion and Ventilation
Air Supply
All indoor installations must have openings to outside air for combustion, ventilation and dilution of
LAARS
UNIT
(Side View)
Base For Combustible Floors
Flashing 4x4 Stringer Roof
Figure 13. Typical roof mounting with standard
combustible mount base.
Base Rail
20 Gauge Galvanized Sheet Metal Cap
Roofing
Mighty Therm Volume Water Heaters
Page 7
Required Net Free Opening Area
Directly from Outside
At Top At Bottom
Model in.
175 44 284 44 284 250 63 406 63 406 325 82 529 82 529 400 100 645 100 645
Note: For screens or louvers, add 50%.
Table 2. Air Openings to Outside.
Notes:
1. The drafthood must sit directly on top of the heater as shown and must not be altered in any manner.
2. An Underwriters' Laboratories listed vent cap is re­quired to eliminate downdraft and allow the heater to function properly.
3. Use approved roof fitting.
2
cm
2
in.
2
cm
Method 1:
T wo permanent openings, one commencing
within 12" (30 cm) of the top and one commencing
2
within 12" (30 cm) of the bottom of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors. When directly communicating with the outdoors directly, or through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4000 Btu/hr (550 square mm/ kW) of total input rating of all equipment in the enclosure. When communicating to the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2000 Btu/hr (1100 square mm/kW) of total input rating of all equipment in the enclosure.
Method 2:
One permanent opening, commencing within 12" (30 cm) of the top of the enclosure shall be permitted. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors, and shall have a minimum free area of 1 square inch per 3000 Btu/hr (734 square mm/kW) of the total input rating of all equipment located in the enclosure. This opening must not be less than the sum of the areas of all vent connectors in the confined space.
Other methods of introducing combustion and ventilation air are acceptable, providing they conform to the requirements in ANSI Z223.1, or applicable codes.
In Canada, Table 2 does not apply. Consult local building and safety codes or, in absence of such requirements, follow CAN/CGA B149.
NOTE: Check with louver manufacturers for net free area of louvers. If screens or louvers are installed, add 50 percent for each screen/louver to the net free area Check all local codes applicable to combustion air.
Figure 14. Indoor installation and venting.
flue gases from inside the building (see Figure 14 and Table 2 ). Laars does not recommend indoor installations that do not provide combustion air from outside the building.
In the United States, the most common requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2, which follow. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.
2.4.1 Outdoor Air Supply
When combustion air comes directly through an outside wall, each opening must have a minimum free area of at least one square inch for each 4,000 BTU/h input of the total input rating of all appliances in the enclosed area. (In Canada, refer to CGAB149.1 and .2.)
2.4.2 Indoor Air Supply
Confined and non-confined areas have different requirements for installation. Consult the latest edition of the National Gas Code for installation requirements.
2.4.3 Exhaust Fans or Vents
Any equipment which uses air or removes air from the heater room can use up the combustion air
Page 8
LAARS Heating Systems
supply or reverse the natural draft action of the venting system. This could cause flue products to build up in the heater room. More air must be supplied to make up for the decrease.
2.5 Venting of Combustion Products
2.5.1 General Information
When installed indoors, the drafthood must be connected to a venting system. The venting system must be installed by a qualified installer and in accordance with the latest edition of ANSI Z223.1. In Canada, the installation must be in accordance with CAN1-B149.1 or .2, and any local codes that apply.
The vent pipe must have a listed vent cap, and extend at least 2 feet (0.6 m) above any object within a 10 foot (3.0 m) radius.
NOTE: Do not use sheet metal screws at the snap lock joints of Type B double-wall gas vents.
Do not weld or bolt the vent pipe to the heater drafthood. The weight of the stack must not rest on the heater. The drafthood and heater top must be easily removable for normal heater service and inspection.
WARNING
Avoid ending heater vents near air conditioning or air supply fans. The fans can pick up exhaust flue products from the heater and return them inside the building, creating a possible health hazard.
Avoid horizontal runs of the vent pipe and 90 degree elbows, reductions, and restrictions. Horizontal runs should have at least a 1/4 inch (6.3 mm) rise per foot in the direction of flow. Support a vent connector for the design and weight of the material used to maintain clearances and physical damage and separate of joints.
Always use double-wall or insulated vent pipe (Type B or equivalent).
WARNING
In cold weather, uninsulated outside vents can chill the rising flue products, blocking the natural draft action of the venting system. This can create a health hazard by spilling flue products into the heater room.
Avoid oversize vent piping or extremely long runs of the pipe which may cause too much cooling and condensation of flue gasses.
When the installation of a power vent or draft fan in the venting system is necessary, qualified personnel
should design the installation following good engineering practices and all applicable codes. A suitable draft switch must be wired into the heater control circuit at the terminal designated Field Interlock to keep the heater from firing unless there is a positive draft.
2.5.2 Replacement of Existing Heater
When a heater is removed from a common venting system, the venting system may be too large for proper venting of the other appliances connected to it.
If replacing an existing heater with a VW or PW heater and the existing heater was connected to a common venting system, the common venting system must comply with ANSI Z223.1/National Fire Protection Association (NFPA) 54. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the tables in ANSI Z223.1/NFPA 54, Appendix G. In Canada, the common venting system should be resized so the installation will be in accordance with CAN/CGA B149.1 or .2.
2.6 Water Flow
2.6.1 Reversible Water Connections
NOTE: This procedure is not recommended for the PW pump-mounted models.
Laars ships the VW heater with the water connections on the right side. The VW heater can be installed with the water connections on either side. It could be necessary, or helpful, to switch the connections to the left side to improve access for installation service. Have a professional service technician perform this modification before installing the heater using the following procedures:
1. Remove the front cover.
2. If there is a vent cap or drafthood installed, they
must be removed before removing the grate top
assembly. On indoor installations (sizes 175-
250), the drafthood switch must be disconnected
at the left side of the heater.
3. If the unit is in the low-profile outdoor
configuration, remove the hex-head screws
(see Figure 15) and lift the grate top assembly
straight up.
4. Remove the screws that fastens the flue collector
holddown clamps and remove the clamps (see
Figure 16).
5. Remove the flue collector assembly by lifting it
out of the chassis.
6. Remove the screws that fastens the gap closures
and put them aside.
Mighty Therm Volume Water Heaters
Page 9
Figure 15. Heat exchanger reversal.
Figure 16. Flue collector Holddown Clamps.
Page 10
LAARS Heating Systems
7. Remove the three grommets.
8. Remove the drain valves and plug. There is one hex plug on the left side, near the rear of the jacket. The drain valves are located on the left side and right side of the heater (see Figure 9).
Figure 17. Sensory bulb locations.
Figure 18. Retaining clip removal.
Figure 19. Hole location, left side.
9. Remove the four screws that fastens the metal channels covering the capillary tube on the right side of the jacket, and lay the channels aside.
10. In the control compartment, find the manual reset high-limit switch box (see Figure 15) and loosen the screw on the top to remove the cover.
11. Loosen the screw that fastens the white wire and remove it from the terminal. Pull it out through the top of the case and separate the other white wire from the red wire coming from the fuse holder. Gently pull the two white wires out of the control compartment and coil them on top of the heat exchanger.
12. A temperature control sensing bulb is located in the front of the header on the inlet side and a manual reset hi-limit sensing bulb is located on the back side of the header on the outlet side (see Figure 17). Remove these sensing bulbs from the
header. The following steps for removal apply to all sensing bulbs:
a. If there is more than one capillary tube coming
out of the header, label the capillary tubes.
b. Loosen the screw on the capillary tube
retaining clip, then gently pry the clip apart until it comes free from the temperature control (see Figure 18).
c. Pull the sensing bulbs out of the temperature
control.
d. Gently pull the capillary tubes into the control
compartment.
e. Pull the temperature sensing bulb out of the
header, and temporarily route it to the front of the heater.
13. Use a pair of diagonal cutters to cut the plastic tie around the wire bundle in the control compartment.
14. On the terminal strip, disconnect the two brown wires from No. 5 and No. 6 terminals.
15. Remove the flow switch conduit retaining clip and the elbow leading into the jacket.
16. Reach inside the control compartment and release the retaining nut in the upper right corner. The nut should only be finger-tight.
17. When the conduit is pulled away from the jacket, pull the two brown wires out of the control compartment. Coil the conduit and wires on top of the heat exchanger.
18. Use a chassis punch to put two 7/8 inch (22 mm) holes in the front left side of the jacket (see Figure 19).
19. Remove the front and rear tile covers (see Figure 15).
Loading...
+ 22 hidden pages