Installation and Operation Instructions Document 1276C
Installation and
Operation Instructions for
®
MAGNATHERM
Modulating Boiler Water Heater
Model MGH2000 Model MGV2000
1,999 MBTU/h 1,999 MBTU/h
Model MGH2500 Model MGV2500
2,499 MBTU/h 2,499 MBTU/h
Model MGH3000 Model MGV3000
3,000 MBTU/h 3,000 MBTU/h
Model MGH3500 Model MGV3500
3,500 MBTU/h 3,500 MBTU/h
Model MGH4000 Model MGV4000
4,000 MBTU/h 4,000 MBTU/h
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualied in hot water boiler and heater installation and maintenance. Improper installation and/or operation
could create carbon monoxide gas in ue gases which could cause serious injury, property damage, or
death. Improper installation and/or operation will void the warranty.
WARNING
If the information in these instructions is
not followed exactly, a re or explosion
may result causing property damage,
personal injury or death.
Do not store or use gasoline or other
ammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from
a neighbor’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call
the re department.
Installation and service must be performed
by a qualied installer, service agency, or gas
supplier.
AVERTISSEMENT
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion ou
pour éviter tout dommage matériel, toute blessure
ou la mort.
Ne pas entreposer ni utiliser d’essence ou ni
d’autres vapeurs ou liquides inammables dans
le à proximité de cet appareil ou de tout autre
appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous servir
des téléphones dans le bâtiment où vous vous trovez.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions du
fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualié ou
par le fournisseur de gaz.
13.2.11 Control Panel Assembly ..............................100
ii
LAARS Heating Systems
MagnaTherm Boilers and Water Heaters
Section 1
GENERAL INFORMATION
1.1 Introduction
is manual includes information which will
help you to install, operate, and maintain the
Magnaerm 2000, 2500, 3000, 3500 and 4000
systems. Please read this manual completely before
proceeding with the installation. If you have any
questions regarding this equipment, please consult
the LAARS Heating Systems factory, or a local
factory representative. Many operating problems are
caused by improper installation.
1.2 Safety Notes
Page 1
Touch
Screen
DANGER
• Water temperature over 125°F (52°C) can cause
severe burns instantly or death from scalds.
Children, disabled and elderly are at highest risk of
•
being scalded.
See instruction manual before
•
setting temperature at
heating appliance.
•
Feel water before
bathing or showering.
If this appliance is used
•
to produce water that
could scald if too hot,
such as domestic hot water
use, adjust the outlet
control (limit) or use temperature limiting valves
to obtain a maximum water temperature of 125°F
(52°C).
WARNING
Fire or Explosion Hazard
Improper conguration can cause fuel buildup and
explosion. Improper user operation may result in
property loss, severe physical injury, or death.
Any changes to safety-related conguration
parameters must only be done by experienced and/
or licensed burner/boiler operators and mechanics.
If any odor of gas is detected, or if the gas burner
does not appear to be functioning in a normal
manner, close the main gas shuto valve. Do not
shut o the power switch. Contact your heating
contractor, gas company, or factory representative.
Open the
front panel
to access
the Touch
Screen
e Magnaerm Appliance is protected against
over-pressurization. A pressure relief valve is
included with each Magnaerm.
e inlet gas pressure to the appliance must not
exceed 13” W.C. (3.2 kPa).
All installations must be made in accordance with
1) American National Standard Z223.1/NFPA54Latest Edition “National Fuel Gas Code” or 2) CSA
B149.1 “Natural Gas and Propane Installation Code”
and with the requirement of the local utility or other
authorities having jurisdiction. Such applicable
requirements take precedence over the general
instructions contained herein.
WARNING
Carbon Monoxide Hazard
Improper adjustment of the burners may lead to
poor combustion quality, increasing the amount
of carbon monoxide produced. Excessive carbon
monoxide levels may lead to personal injury or
death.
Page 2
LAARS Heating Systems
Model Nomenclature
1 2 3 4 5 6 7 8 9 10 11 12 13
M G 1
SERIES
M G
USAGE
H -
HYDRONIC
V - VOLUME
WATER
SIZE
MBTU/h
2000
2500
3000
3500
4000
FUEL
N - NATURAL
P - PROPANE
COUNTRY
CODE
X - USA/CANADA
E - EXPORT
Not CSA approved
*
*
OPTIONS CODE
X -
STANDARD
J - CSD-1
ELEC SYSTEM
A - 110V, 1Ø
B - 220V, 1Ø
C - 208V, 3Ø
D - 480V, 3Ø
E - 600V, 3Ø
ASME
X - “H” STAMP (MGH)
W - “HLW” STAMP (MGV)
1.3ModelIdentication
Consult the rating plate on the unit. The following
information describes the model number structure.
Electrical shock can cause severe injury, death or
property damage. Disconnect the power supply
before beginning installation or changing the
wiring to prevent electrical shock or damage to the
equipment. It may be necessary to turn o more than
one power supply disconnect.
All electrical wiring is to be done in accordance with
local codes, or in the absence of local codes, with:
1) e National Electrical Code ANSI/NFPA No.
70 - latest Edition, or 2) CSA STD. C22.1 “Canadian
Electrical Code - Part 1.” is appliance must be
electrically grounded in accordance with these codes.
Altitude:
Gas input rating of the MagnaTherm shall be used for
elevations up to 2000 ft (600 m). The input rating at
elevations above 2000 ft (600 m) shall be reduced at
a rate of 4 percent for each 1000 ft (300 m) above sea
level before selecting the equipment size.
1.4 Warranty
LAARS Heating Systems MagnaTherm boilers are
covered by a limited warranty. The owner should
complete the warranty registration at
http://www.LAARS.com
ALL WARRANTY CLAIMS must be made by an
authorized LAARS Heating Systems representative.
Claims must include the serial number and model
(this information can be found on the rating plate).
All claims must also include the installation date and
name of the installer. Shipping costs are not included
in the warranty coverage.
WARNING
Magnaerm units must be installed in
accordance with the procedures detailed in this
manual, or the LAARS Heating Systems warranty
will be voided. e installation must conform to
the requirements of the local jurisdiction having
authority, and, in the United States, to the latest
edition of the National Fuel Gas Code, ANSI
Z223.1/NFPA54. In Canada, the installation
must conform to the latest edition of CSA
B149.1 Natural Gas and Propane Gas Installation
Code, and/or local codes. Where required by the
authority having jurisdiction, the installation
of Magnaerm boilers must conform to the
Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1.
Any modications to the boiler, its gas controls, or
wiring may void the warranty. If eld conditions
require modications, consult the factory
representative before initiating such modications.
REVISION
1 -FIRST
MagnaTherm Boilers and Water Heaters
1.5 Unit Overviews
The next 3 pages give a visual reference to
the basic component locations of the LAARS
MagnaTherm.
Page 3
Blower
Manual
gas valve
Touch Screen
Heat Exchanger
Power Pack
Model 2000
Perspective from front left corner.
Shown with front doors and left side
panels removed
Condensing Unit
Air Intake and
Filter
Water Outlet
Water Inlet
Vent
Condensate
Trap
Perspective from opposite corner.
Page 4
Blower
Manual
gas valve
Touch Screen
Heat Exchanger
LAARS Heating Systems
Power Pack
Condensing Unit
Air Intake and
Filter
Water Outlet
Water Inlet
Models 2500 and 3000
Vent
Condensate
Trap
MagnaTherm Boilers and Water Heaters
Page 5
Blower
Manual
gas valve
(hidden behind main
gas valve)
Touch Screen
Heat Exchanger
Condensing Unit
Power Pack
Models 3500 and 4000
Air Intake and
Filter
Water Outlet
Water Inlet
Vent
Condensate
Trap
Page 6
E
F
U
B
A
VIEW
REAR
N
Q
S
P
M
R
L
G
H
K
J
T
FRONT
VIEW
SIDE
VIEW
C
D
Condensate Trap
Contact
Factory
Oponal
Flanges,
Vent
Gas
6”x3.5”
Touchscreen
Display
Air Inlet
Pressure
Relief
Valve
Water
Outlet
‘Knock-
down’
Height
Water
Inlet
H
J
Gas
Air Inlet
Model 4000
The Model 4000 varies from other sizes in the locaon of it’s Air Inlet and Gas Supply.
The MagnaTherm is shipped in a single crate.
Remove all packing and tie-down materials.
Section 2
LOCA TING THE APPLIANCE
2.1 Locating the Appliance
The MagnaTherm may be installed indoors or
outdoors. If installing outdoors in a location that
may experience freezing temperatures, precautions
must be taken to prevent water in the heat exchanger
and condensate inside and outside of the boiler from
freezing. Damage due to freezing water or condensate
is not covered by the warranty .
Choose a location for the unit which allows clearances
on all sides for maintenance and inspection. See T able 1.
Always install the unit on a rm, level surface.
The unit should not be located in an area where
leakage of any connections will result in damage to
the area adjacent to the appliance, or to lower oors
of the structure.
When this type of location is not available, install
a suitable drain pan, adequately drained, under the
appliance.
The appliance is design-certied by CSA-
International for installation on combustible
ooring; in basements; in utility rooms or alcoves.
MagnaTherm boilers must never be installed on
carpeting. The location for the appliance should
be chosen with regard to the vent pipe lengths and
external plumbing.
The unit shall be installed such that the gas ignition
system components are protected from water (dripping,
spraying, rain, etc.) during operation and service
(circulator replacement, control replacement, etc.).
When vented vertically , the MagnaTherm must be
located as close as practical to the vertical section
of the vent. If the vent terminal and/or combustion
air terminal terminate through a wall, and there is
potential for snow accumulation in the local area, both
terminals should be installed at an appropriate level
above grade or the maximum expected snow line.
The dimensions and requirements that are shown in
Table 1 should be met when choosing the locations
for the appliance.
2.2 Correct Vent Distance from
Outside Wall or Roof Termination
The forced draft combustion air blower in the
appliance has sufcient power to vent properly when
the guidelines in Table 2are followed.
Note - When located on the same wall, the
MagnaTherm combustion air intake terminal must be
installed a minimum of 12” (30cm) below the exhaust
terminal. There must also be a minimum horizontal
distance from intake to the exhaust terminal
of 84” (213cm) See Figure 4
APPLIANCE SUGGESTED SERVICE ACCESS CLEARANCE
SURFACE INCHESCM
Front 2461
Left Side 820
Right Side 820
Back 2461
Top, 2000 1230
Top, 2500 & 3000 1538
Top, 4000 2461
APPLIANCE REQUIRED CLEARANCE TO COMBUSTIBLES
SURFACE INCHESCM
Front 18 45
Left Side 415
Right Side 415
Back 1115
Top 12.5
Vent 1 2.5
Table 1. Clearances
INTAKE / EXHAUST
MAX EQUIVALENT
SIZE DIAMETER FT. M
2000 & 2500 8” 10030
3000 & 3500 10” 100 30 4000 12” 100 30
Installations in the U.S. require exhaust vent pipe that is CPVC
complying with ANSI/ASTM D1785 F441, polypropylene
complying with ULC S636, or stainless steel complying with
UL1738. Installations in Canada require exhaust vent pipe that
is certied to ULC S636.
Intake (air) pipe must be PVC or CPVC that complies with
ANSI/ASTM D1785 F441, ABS that complies with ANSI/ASTM
D1527, stainless steel, or galvanized material.
To calculate max equivalent length, measure the linear feet of
the pipe, and add 5 feet (1.5 m) for each elbow used.
Table 2. Vent / Air Pipe Sizes
Page 8
(Place in section 3.1)
Screen for horizontal galvanized air pipeD2012101D2012101D2012102D2012103D2012103
Screen for horizontal PVC air pipeCA012001CA012001CA012002CA012003CA012003
Screen for horizontal polypropylene air pipeCA012201CA012201CA012202CA012203CA012203
Screen for vertical galvanized air pipeD2012201D2012201D2012202D2012203D2012203
Screen for vertical PVC air pipeCA012401CA012401CA012402CA012403CA012403
Screen for vertical polypropylene air pipeCA012601CA012601CA012602CA012603CA012603
Section 3
VENTING AND COMBUSTION AIR
3.1 Combustion Air
MagnaTherm boilers and water heaters must have
provisions for combustion and ventilation air in
accordance with the applicable requirements for
Combustion Air Supply and Ventilation in the
National Fuel Gas Code, ANSI Z223 1; or in Canada,
the Natural Gas and Propane Installation Code, CSA
B149.1. All applicable provisions of local building
codes must also be adhered to.
A MagnaTherms can take combustion air
from the space in which it is installed, or the
combustion air can be ducted directly to the unit.
Ventilation air must be provided in either case.
3.1.1 Combustion Air From Room
In the United States, the most common requirements
specify that the space shall communicate with the
outdoors in accordance with Method 1 or 2. (See the
following descriptions.) Where ducts are used, they
shall be of the same cross-sectional area as the free
area of the openings to which they connect.
Method 1: Two permanent openings, one
LAARS Heating Systems
commencing within 12” (300 mm) of the top and
one commencing within 12” (300 mm) of the
bottom, of the enclosure shall be provided. The
openings shall communicate directly, or by ducts,
with the outdoors or spaces that freely communicate
with the outdoors. When directly communicating
with the outdoors, or when communicating to the
outdoors through vertical ducts, each opening shall
have a minimum free area of 1 square inch per
4000 Btu/hr (550 square mm/kW) of total input
rating of all equipment in the enclosure. When
communicating to the outdoors through horizontal
ducts, each opening shall have a minimum free
area of not less than 1 square inch per 2000 Btu/
hr (1100 square mm/kW) of total input rating of all
equipment in the enclosure.
Method 2: One permanent opening, commencing
within 12” (300 mm) of the top of the enclosure,
shall be permitted. The opening shall directly
communicate with the outdoors or shall
communicate through a vertical or horizontal duct
to the outdoors or spaces that directly communicate
Table 3. Ducted Air Accessories
PVC, sch. 40ANSI/ASTM D1785 or D2665
CPVC, sch. 40ANSI/ASTM F441
Single wall galv. steel26 gauge
PolypropyleneULC S636 Class 2C
Table 4. Required Combustion Air Pipe Material
Model 2000Model 2500Model 3000Model 3500Model 4000
MaterialUnited StatesCanada
ABSANSI/ASTM D1527The air pipe material must be chosen based upon
the intended application of the boiler, and must
be installed according to the vent manufacturer’s
installation instructions.
MagnaTherm Boilers and Water Heaters
with the outdoors and shall have a minimum free
area of 1 square inch per 3000 Btu/hr (734 square
mm/kW) of the total input rating of all equipment
located in the enclosure. This opening must not be
less than the sum of the areas of all vent connectors
in the conned space.
Other methods of introducing combustion and
ventilation air are acceptable, providing they
conform to the requirements in the applicable codes
listed above.
In Canada, consult local building and safety codes
or, in absence of such requirements, follow CAN/
CSA B149.
3.1.2 Ducted Combustion Air
The combustion air can be taken through the wall, or
through the roof. LAARS offers accessories to use
with ducted air systems, as shown in Table 3.
See Table 4 to select the appropriate diameter air
pipe. When taken from the roof, a eld-supplied
rain cap or an elbow arrangement must be used to
prevent entry of rain water. (See Figure 6).
Use ABS, PVC, CPVC, polypropylene, stainless
steel, or galvanized pipe for the combustion air
intake. (See Table 4) The intake must be sized per
Table 2. Route the intake to the boiler as directly
as possible. Seal all joints. Provide adequate
hangers. The unit must not support the weight of
the combustion air intake pipe. The maximum
equivalent pipe length allowed is 100 feet (30 m).
Each elbow is considered to be 5 feet (1.5m)
Page 9
3.2 Venting
WARNING
Selection of improper vent materials for
installations that are installed in closets, or will be
operated in high ambient temperature levels, may
lead to property damage, personal injury, or death.
WARNING
Failure to use the appropriate vent material,
installation techniques, or glues and sealants
could lead to vent failure causing property
damage, personal injury or death.
WARNING
All venting must be installed according to this
manual and any other applicable local codes,
including but not limited to, ANSI Z223.1/NFPA 54,
CSA B149.1, CSAB149.2 and ULC S636. Failure
to follow this manual and applicable codes may
lead to property damage, severe injury, or death.
When using polypropylene or stainless steel
materials in horizontal duct congurations, a single
elbow must be installed on the end of the air inlet
to act as an outdoor terminal. In vertical duct
applications, two elbows must be installed on the
end of the inlet to act as a vent terminal. When
elbows are use as terminals, appropriate screens
must be installed to prevent blockage.
The elbow(s) required for termination are not
included in the kits sown in Table 3
The connection for the intake air pipe is on the back
panel.
In addition to air needed for combustion, air shall
also be supplied for ventilation, including air
required for comfort and proper working conditions
for personnel. Refer to the applicable codes.
Page 10
(Place in section 3.1)
Model 2000Model 2500Model 3000Model 3500Model 4000
Screen for horizontal galvanized air pipeD2012101D2012101D2012102D2012103D2012103
Screen for horizontal PVC air pipeCA012001CA012001CA012002CA012003CA012003
Screen for horizontal polypropylene air pipeCA012201CA012201CA012202CA012203CA012203
Screen for vertical galvanized air pipeD2012201D2012201D2012202D2012203D2012203
Screen for vertical PVC air pipeCA012401CA012401CA012402CA012403CA012403
Screen for vertical polypropylene air pipeCA012601CA012601CA012602CA012603CA012603
Table 3a - Ducted Air Accessories
(Place in section 3.2)
Model 2000Model 2500Model 3000Model 3500Model 4000
Horizontal vent terminal for stainless steelD2012001D2012001D2012002D2012003D2012003
Screen for horizontal CPVC ventCA012101CA012101CA012102CA012103CA012103
Screen for vertical stainless steel ventD2012301D2012301D2012302D2012303D2012303
Screen for vertical CPVC ventCA012501CA012501CA012502CA012503CA012503
LAARS Heating Systems
If the system temperatures are unknown at the
time of installation, class IIC or higher venting
material is recommended.
The MagnaTherm is a Category IV appliance and
may be installed with the standards listed on Table 6.
The unit’s vent can terminate through the roof, or
through an outside wall.
All installations must be done following the vent
supplier’s recommended installation techniques.
If these are not available, refer to the LAARS
recommendations for the material used.
For Category IV boilers, have horizontal runs
sloping upwards not less than 1/4 inch per foot
(21 mm/m) from the boiler to the vent terminal;
be installed so as to prevent accumulation of
condensate; and, where necessary, have means
provided for drainage of condensate.
Pour la catégorie IV, les chaudières ont horizontal
en pente vers le haut au moins 1/4 de pouce par pied
(21 mm/m) à partir de la chaudière pour l’évent
borne; être installé de façon à éviter l’accumulation
de condensats; et, le cas échéant, ont des moyens
prévus pour l’évacuation des condensats.
This will allow the condensate to run back to the
MagnaTherm to drain. Route the vent pipe to the
heater as directly as possible. Seal all joints. Provide
adequate hangers as required in the venting system
manufacturer’s Installation Instructions, or at least
every 4 feet.
The unit must not support the weight of the vent
pipe. The maximum equivalent pipe length allowed
is 100 feet (30m). Each elbow is considered to be 5
feet (1.5m). LAARS offers accessories to use with
horizontal and vertical exhaust vent systems, as
shown in Table 5
3.2.1 Common Venting
The MagnaTherm can be common vented, however,
the common venting must be a professionally
designed and approved system. MagnaTherm
units are never permitted to share a vent with any
Catagory 1 appliances.
3.2.3 Venting Requirements Unique to
Canada
MagnaTherm boilers and water heaters are Vent
Table 5. Vent Accessories
MaterialUnited StatesCanada
Stainless steelUL 1738Venting must be ULC S636 certied for use as
CPVC, sch 40ANSI/ASTM F441
Polypropylene
Pending APPROV AL
Table 6. Required Exhaust Vent Material
Installation Standards
venting material. The venting material class must
be chosen based upon the intended application
of the boiler, and must be installed according to
ULC S636 Class 2C
the maximum ue gas temperature and the vent
manufacturer’s instructions.
MagnaTherm Boilers and Water Heaters
Category IV appliances. Per the requirements of
CAN/CSA-B149.1, only BH vent systems can be
connected to these units and such vent systems,
either ULC S636 certied stainless steel or other
ULC S636 certied BH vent (eg. plastics) must
be installed per the vent manufacturer’s certied
installation instructions.
It is the responsibility of the appropriately licensed
technician installing this MagnaTherm to use
ULC S636 certied vent material consistent with
the requirements as described in the Venting and
Combustion Air section.
Class I venting systems are suitable for gas-red
appliances producing ue gas temperature of more
than 135°C, but not more than 245°C.
Class II venting systems are suitable for gas-red
appliances producing ue gas temperatures of 135°C
or less.
Page 11
Class II venting systems are further classied into
four temperature ratings as follows:
A Up to and including 65°C / 149°F
B Up to and including 90°C / 194°F
C Up to and including 110°C / 230°F and
D Up to and including 135°C / 275°F
Flue Gas Sampling Port It is also the responsibility of the installer to ensure
that a ue gas sampling port is installed in the vent
system. This ue gas sampling port must be installed
near the ue connection of the MagnaTherm: within
2 feet of the ue connection. There is no ue gas
sampling port internal to the MagnaTherm, so one
must be installed in the vent system external to the
MagnaTherm. A ue gas sampling port available as
a component of the ULC S636 certied vent system
is preferred. However, if one is not available with
the certied vent system, LAARS suggests using
a tee with the branch connection sized to allow for
insertion of a ue gas analyzer probe. The branch
connection must be resealable with a cap or other
means to ensure the vent system remains sealed.
(See Figure 2)
Consideration must be given to the placement
and orientation of the ue gas sampling port to
ensure that condensate is free to ow back into the
MagnaTherm and not collect anywhere in the vent
system - including in the ue gas sampling port.
Exhaust Vent Terminal An exhaust vent terminal must be installed. If an
Figure 2. Test Port
exhaust vent terminal is not available with the
certied vent system, LAARS suggests the use of
a coupler tting from the certied vent system into
which the vent terminal screen can be installed.
Be sure to install and terminate both vent and
combustion air pipes per the instructions in this
section.
3.3 Locating the Vent and Combustion
Air Terminals
3.3.1 Side Wall Vent Terminal
The appropriate LAARS side wall vent terminal
must be used. The terminal must be located in
accordance with ANSI Z223.1/NFPA 54 and
applicable local codes. In Canada, the installation
must be in accordance with CSA B149.1 or .2 and
local applicable codes.
Consider the following when installing the terminal:
1. Figure 4 shows the requirements for
mechanical vent terminal clearances for the
U.S. and Canada.
2. Vent terminals for condensing appliances or
appliances with condensing vents are not
permitted to terminate above a public walkway,
or over an area where condensate or vapor
could create a nuisance or hazard.
3. Locate the vent terminal so that vent gases
cannot be drawn into air conditioning system
inlets.
4. Locate the vent terminal so that vent gases
Page 12
U.S. Installations (see note 1) Canadian Installations (see note 2)
A= Clearance above grade, veranda, porch, 12 inches (30 cm) 12 inches (30 cm)
deck, or balcony See note 6 See note 6
B= Clearance to window or door that may be Direct vent only: 12 inches (30 cm); 36 inches (91 cm)
opened Other than Direct vent: 4 ft (1.2m) below or to
side of opening; 1 ft (30 cm) above opening
C= Clearance to permanently closed window See note 4 See note 5
D= Vertical clearance to ventilated soft located
above the terminal within a horizontal See note 4 See note 5
distance of 2 feet (61 cm) from the center
line of the terminal
E= Clearance to unventilated soft See note 4 See note 5
F= Clearance to outside corner See note 4 See note 5
G= Clearance to inside corner See note 4 See note 5
H= Clearance to each side of center line 3 feet (91 cm) within a height 15 feet
extended above meter/regulator assembly See note 4 above the meter/regulator assembly
I= Clearance to service regulator vent outlet See note 4 3 feet (91 cm)
J= Clearance to nonmechanical air supply Direct vent only: 36” (91cm)
inlet to building or the combustion air inlet Other than Direct vent: 4 ft (1.2m) below 36 inches (91 cm)to any other appliance or to side of opening; 1 ft (30 cm) above opening
K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m) 6 feet (1.83 m)
horizontally
L= Clearance above paved sidewalk or pavedVent termination not allowed in this location7 ft (2.1 m) driveway located on public propertyfor category IV appliances. See note 5
M= Clearance under veranda, porch, deck, See note 4 12 inches (30 cm)
or balcony See note 5
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CAN/CSA-B149 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
4. For clearances not specied in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the
requirements of the gas supplier.
5. For clearances not specied in CAN/CSA-B149, clearance is in accordance with local installation codes and the requirements of the
gas supplier.
6. IMPORTANT: All terminals must be placed so that they remain a minimum 12” above expected snow line. Local codes may have
more specic requirements, and must be consulted.
LAARS Heating Systems
Figure 3. Combustion Air and Vent Through Side Wall
*When vent terminal is less than 10 feet (3 m) horizontally
from a forced air inlet, the terminal must be at least 3 feet
(0.9 m) above the air inlet. (US only)
MagnaTherm Boilers and Water Heaters
84
IMPORTANT: All terminals must be placed so that they remain at least 12”
above the expected snow line. Local codes may have more specic
requirements, and must be consulted. Refer to the NFPA54 National Fuel Gas
Code and your local codes for all required clearances for venting.
Figure 5. Multiple Side-Wall Terminals, Air and
Vent
cannot enter the building through doors,
windows, gravity inlets or other openings.
Whenever possible, avoid locations under
windows or near doors.
5. Locate the vent terminal so that it cannot
be blocked by snow. The installer may
determine that a vent terminal must be
higher than the minimum shown in codes,
depending upon local conditions.
6. Locate the terminal so the vent exhaust does
not settle on building surfaces or other nearby
objects. Vent products may damage surfaces or
objects.
7. If the boiler or water heater uses ducted
combustion air from an intake terminal located
on the same wall, see See Figure 5 and Figure
4 for proper spacing and orientation.
Page 13
3.3.2 Side Wall Combustion Air Terminal
Consider the following when installing the terminal.
1. Do not locate the air inlet terminal near a
source of corrosive chemical fumes (e.g.,
cleaning uid, chlorine compounds, etc.).
2. Locate the terminal so that it will not be subject
to damage by accident or vandalism. It must be
at least 7 feet ( 2.1 m) above a public walkway.
3. Locate the combustion air terminal so that it
cannot be blocked by snow. The National Fuel
Gas Code requires that it be at least 12 inches
(30 cm) above grade, but the installer may
determine it should be higher, depending upon
local conditions.
4. If the MagnaTherm is side-wall vented to the
same wall, use Figure 4 to determine the proper
mounting locations.
5. Multiple vent kits should be installed such that
the horizontal distance between outlet group
and inlet group is 84” (213 cm). (See Figure 5)
6. The vent outlet must be at least 12” above the top
of the air inlet, and must be at least 84” (213 cm)
horizontally from the air inlet. (See Figure 5).
3.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the vent
must extend at least 3 feet (0.9 m) above the point
at which it penetrates the roof. It must extend at
least 2 feet (0.6 m) higher than any portion of a
building within a horizontal distance of 10 feet (3.0
m), and high enough above the roof line to prevent
blockage from snow . The vent terminal offered with
the MagnaTherm can be used in both vertical and
horizontal applications. When the combustion air is
taken from the roof, the combustion air must terminate
at least 12” (30 cm) below the vent terminal.
If the vent termination is located in an area exposed
to high winds, an optional PVC tee (the same
diameter as the vent pipe) may be used. The tee’d
vent termination offers greater protection from wind
related operating issues.
Figure 4. Minimum Venting Distance
12”
84”
213
Page 14
*
3.3.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a eld-
supplied rain cap or an elbow arrangement must be
used to prevent entry of rain water. The opening on
the end of the terminal must be at least 12” (30 cm)
above the point at which it penetrates the roof, and
high enough above the roof line to prevent blockage
from snow. When the vent terminates on the roof, the
combustion air must terminate at least 12” (30 cm)
below the vent terminal.
LAARS Heating Systems
*
*
*
In Canada, refer to CAN/CSAB199.1
*
*
3.3.5 Installations in the Commonwealth
of Massachusetts
In Massachusetts the following items are required
if the side-wall exhaust vent termination is less than
seven (7) feet above nished grade in the area of
the venting, including but not limited to decks and
porches. (From Massachusetts Rules and regulations
248 CMR 5.08.)
1. Installation of Carbon Monoxide Detectors
At the time of installation of the side wall vented
gas fueled appliance, the installing plumber or
gas-tter shall observe that a hard-wired carbon
monoxide detector with an alarm battery back-
up is installed on the oor level where the gas
appliance is to be installed. In addition, the
installing plumber or gastter shall observe
that a battery operated or hard-wired carbon
monoxide detector with an alarm is installed on
each additional level of the dwelling, building
or structure served by the side-wall horizontally
vented gas fueled equipment. It shall be the
responsibility of the property owner to secure
the services of qualied licensed professionals
for installation of hard-wired carbon monoxide
detectors.
a. In the event that the side-wall horizontally
vented gas fueled equipment is installed in a
crawl space or an attic, the hard-wired carbon
monoxide with alarm and battery back-up may
be installed on the next adjacent oor level.
b. In the event that the requirements of the
subdivision cannot be met at the time of
completion of installation, the owner shall have
a period of thirty (30) days to comply with the
above requirements, provided, however, that
during said thirty (30) day period, a battery
operated carbon monoxide detector with an
alarm be installed.
2. Approved Carbon Monoxide Detectors
Each carbon monoxide detector shall comply
with NFPA 720 and be ANSI/UL 2034 listed and
IAS certied.
*
Figure 6. Combustion Air and Vent Through Roof
3. Signage
A metal or plastic identication plate shall be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade directly in line with the exhaust
vent terminal for horizontally vented gas fueled
heating appliance or equipment. The sign shall
read, in print no less than one-half (1/2) inch in
size: “GAS VENT DIRECTLY BELOW, KEEP
CLEAR OF ALL OBSTRUCTIONS.”
4. InspectionThe state or local gas inspector of the side-
wall horizontally vented gas fueled appliance
shall not approve the installation unless, upon
inspection, the inspector observes carbon
monoxide detectors and signage installed in
accordance with the provisions of 248 CMR
5.08(2)(a) 1-4.
3.4 Common Vent Test
Note -This section does not describe a method
for common venting MagnaTherm’s. It describes
what must be done when a unit is removed from
a common vent system. MagnaTherm’s require
special vent systems and fans for common vent.
Contact the factory if you have questions about
common venting MagnaTherm’s.
MagnaTherm Boilers and Water Heaters
Page 15
When an existing boiler is removed from a common
venting system, the common venting system is likely
to be too large for proper venting of the appliances
remaining connected to it.
At the time of removal of an existing boiler,
the following steps shall be followed with each
appliance remaining connected to the common
venting system placed in operation, while the other
appliances remaining connected to the common
venting system are not in operation.
1. Seal any unused openings in the common
venting system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is
no blockage or restriction, leakage, corrosion or
other deciencies which could cause an unsafe
condition.
3. Insofar as is practical, close all building doors
and windows and all doors between the space
in which the appliances remaining connected
to the common venting system are located
and other spaces of the building. Turn on any
clothes dryers and any appliance not connected
to the common venting system. Turn on any
exhaust fans, such as range hoods and bathroom
exhausts, so they will operate at maximum
speed. Do not operate a summer exhaust fan.
Close replace dampers.
4. Place in operation the appliance being
inspected. Follow the lighting instructions.
Adjust thermostat so appliance will operate
continuously.
5. Test for spillage at the draft hood relief opening
after ve minutes of main burner operation. Use
the ame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance
remaining connected to the common venting
system properly vents when tested as outlined
above, return the doors, windows, exhaust fans,
replace dampers and any other gas burning
appliance to their previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so the installation
conforms with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 and/or CAN/CSA
B149.1, National Gas and Propane Installation
Code. When resizing any portion of the common
venting system, the common venting system
should be resized to approach the minimum
size as determined using the appropriate tables
in Appendix F in the National Fuel Gas Code,
ANSI Z223.1 NFPA 54 and/or CAN/CSA
B149.1, National Gas and Propane Installation
Code.
Au moment du retrait d’une chaudiére existante, les
mesures suivantes doivent être prises pour chaque
appareil toujurs raccordé au systéme d’évacuation
commun et qui fonctionne alors que d’autres
appareils toujours raccordés au système d’évacuation
ne fonctionnent pas:
1. Sceller toutes les ouvertures non utilisées du
système d’évacuation.
2. Inspecter de facon visuelle le système
d’évacuation pour déterminer la grosseur
et l’inclinaison horizontale qui conviennent
et s’assurer que le système est exempt
d’obstruction, d’étranglement, de fuite, de
corrosion et autres défaillances qui pourraient
présenter des risques.
3. Dans la mesure du possible, fermer toutes les
portes et les fenêtres du bâtiment et toutes les
portes entre l’espace où les appareils toujours
raccordés au système d’évacuation sont installés
et les autres espaces du bâtiment. Mettre en
march les sécheuses, tous les appareils non
raccordés au système d’évacuation commun
et tous les ventilateurs d’extraction comme
les hottes de cuisinière et les ventilateurs des
salles de bain. S’assurer que ces ventilateurs
fonctionnent à la vitesse maximale. Ne pas faire
fonctionner les ventilateurs d’été. Fermer les
registres des cheminées.
4. Mettre l’appareil inspecté en marche. Suivre les
instructions d’allumage. Régler le thermostat
de facon que l’appareil fonctionne de facon
continue.
5. Faire fonctionner le brûleur principal pendant 5
min ensuite, déterminer si le coup-tirage déborde
à l’ouverture de décharge. Utiliser la amme
d’une allumette ou d’ une chandelle ou la fumée
d’ une cigarette, d’un cigare ou d’une pipe.
6. Une fois qu’il a été détermineé, selon la méthode
indiquée ci-dessus, que chaque appareil raccordé
au système d’évacuation est mis à l’air libre
de facon adéquate. Remettre les portes et
les fenêtres, les vientilateurs, les registre de
cheminées et les appareils au gaz àleur position
originale.
7, Tout mauvais fonctionnement du système
d’évacuation commun devrait être corrigé
de facon que l’installation soit conforme au
National Fuel Gas Code, ANSI Z223.1/NFPA
54 et (ou) aux codes d’installation CAN/
CSA-B149.1. Si la grosseur d’une section du
système d’évacuation doit être modié pour
respecter les valeurs minimales des tableaux
pertinents de l’appendice F du National Fuel Gas
Code, ANSI Z223.1/NFPA 54 et (ou) aux codes
d’installation CAN/CSA-B149.1.
Page 16
(Place in section 3.1)
Model 2000Model 2500Model 3000Model 3500Model 4000
Screen for horizontal galvanized air pipeD2012101D2012101D2012102D2012103D2012103
Screen for horizontal PVC air pipeCA012001CA012001CA012002CA012003CA012003
Screen for horizontal polypropylene air pipeCA012201CA012201CA012202CA012203CA012203
Screen for vertical galvanized air pipeD2012201D2012201D2012202D2012203D2012203
Screen for vertical PVC air pipeCA012401CA012401CA012402CA012403CA012403
Screen for vertical polypropylene air pipeCA012601CA012601CA012602CA012603CA012603
Table 3a - Ducted Air Accessories
(Place in section 3.2)
Model 2000Model 2500Model 3000Model 3500Model 4000
Horizontal vent terminal for stainless steelD2012001D2012001D2012002D2012003D2012003
Screen for horizontal CPVC ventCA012101CA012101CA012102CA012103CA012103
Screen for vertical stainless steel ventD2012301D2012301D2012302D2012303D2012303
Screen for vertical CPVC ventCA012501CA012501CA012502CA012503CA012503
Table 3*- Vent Accessories
(Place in section 3.5)
Air intake screen for unit placed outdoorsCA011901CA011901CA011902CA0011903CA0011903
Vent terminal for unit placed outdoorsCA011801CA011801CA011802CA011803CA011803
Table 7. Air & Vent accessories for Units Placed Outdoors
Model 2000Model 2500Model 3000Model 3500Model 4000
LAARS Heating Systems
3.5 Outdoor Installation
If installing outdoors in a location that may experience
freezing temperatures, precautions must be taken to
prevent water in the heat exchanger and condensate
inside and outside of the boiler from freezing. Damage
due to freezing water or condensate is not covered by the
warranty.
For proper operation in outdoor installations,
the boiler must be equipped with the inlet air and
exhaust terminal kits listed in Table 7. Additional
instructions are supplied with the terminal kits.
WARNING
Do not use open ame to check for leaks. An
open ame could lead to explosion, which
could result in property damage, serious injury
or death.
Note - The MagnaTherm appliance and all
other gas appliances sharing the gas supply line
must be ring at maximum capacity to properly
measure the inlet supply pressure. The pressure
can be measured at the supply pressure port
on the gas valve. Low gas pressure could be an
indication of an undersized gas meter, undersized
gas supply lines and/or an obstructed gas supply
line. MagnaTherm units may be equipped with
low and high gas pressure switches that are
integrally vent limited. These types of devices do
not require venting to atmosphere.
Section 4
GAS SUPPLY AND PIPING
4.0 Gas Supply and Piping
Gas piping should be supported by suitable hangers
or oor stands, not the appliance. Installers should
refer to local building and safety codes or, in the
absence of such requirements, follow the National
Fuel Gas Code, ANSI Z223.1 NFPA and/or CSA
B149.1 installation codes.
Review the following instructions before proceeding
with the installation.
1. Verify that the appliance is tted for the
proper type of gas by checking the rating
plate. MagnaTherm appliances are normally
equipped to operate at elevations up to 2000
feet (610m).
However, the appliance will function properly
without the use of high altitude modication at
elevations up to 10,000 feet (3050 m).
2. The maximum inlet gas pressure must not
exceed 13” W.C. (3.2kPa). The minimum inlet
gas pressure is 4” W.C. (1.0kPa).
3. Table 8 and Table 9 offer some gas pipe sizing
information. Refer to the applicable gas code
for more detailed sizing information.
4. Run gas supply line in accordance with all
applicable codes.
5. Locate and install manual shutoff valves in
accordance with state and local requirements.
6. A sediment trap must be provided upstream of
the gas controls.
7. All threaded joints should be coated with
piping compound resistant to action of
liqueed petroleum gas.
8. The appliance and its individual shutoff valve
must be disconnected from the gas supply
piping during any pressure testing of that
system at test pressures in excess of 1/2 PSIG
(3.45kpa).
9. The unit must be isolated from the gas supply
system by closing its individual manual shutoff
valve during any pressure testing of the gas
supply piping system at test pressures equal to
or less than 1/2 PSIG (3.45kpa).
10. The appliance and its gas connection must be
leak tested before placing it in operation.
5.2 MagnaTherm Water Heater Flow and Head Requirements
***
*
*
*
*
Table 11. Water Heater Flow and Head Requirements
*
*
MagnaTherm Boilers and Water Heaters
Section 6 WATER CONNECTIONS
MGH BOILERS
6.1 MGH System Piping:
Hot Supply Connections
Note -This appliance must be installed in a closed
pressure system with a minimum of 12 psi (82.7
kPa) static pressure at the boiler.
Page 19
A boiler installed above radiation level, or as
required by the authority having jurisdiction,
must be provided with a low water cutoff device
either as a part of the boiler or at the time of boiler
installation.
6.3 MGH Freeze Protection
The hot water piping should be supported by
suitable hangers or oor stands. Do not support the
piping with this appliance. The hangers used should
allow for expansion and contraction of pipe. Rigid
hangers may transmit noise through the system
resulting from the piping sliding in the hangers. We
recommend that padding be used when rigid hangers
are installed. Maintain 1” (2.5 cm) clearance to
combustibles for all hot water pipes.
Pipe the discharge of the relief valve (full size) to a
drain or in a manner to prevent injury in the event of
pressure relief. Install an air purger, an air vent, an
expansion tank, a hydronic ow check valve in the
system supply loop, and any other devices required
by local codes. The minimum ll pressure must
be 12 psig (82.7 kPa). Install shutoff valves where
required by code.
Suggested piping diagrams are shown in Figure 7
through Figure 10. These diagrams are meant only as
guides. Components required by local codes must be
properly installed.
The MagnaTherm’s efciency is higher with
lower return water temperatures. Therefore, to
get the best low return temperature with multiple
boilers, pipe as shown in Figure 9 and Figure 10.
6.2 MGH Cold Water Make-Up
1. Connect the cold water supply to the inlet
connection of an automatic ll valve.
2. Install a suitable back ow preventer between
the automatic ll valve and the cold water
supply.
3. Install shut off valves where required.
In some installations, a hot water heating boiler is
connected to heating coils located in an air handling
appliance where the coils may be exposed to
refrigerated air circulation. In these cases, the boiler
piping system must be equipped with ow control
valves or other automatic means to prevent gravity
circulation of the boiler water during the cooling
cycle.
MagnaTherm units may be installed indoors or
outdoors. If installing outdoors in a location that
may experience freezing temperatures, precautions
must be taken to prevent water in the heat exchanger
and condensate inside and outside of the boiler from
freezing. Damage due to freezing water or condensate
is not covered by the warranty .
If installed indoors, and there is an event such as a
power outage, interruption of gas supply, failure of
system components, activation of safety devices,
etc., this may prevent a boiler from ring. Any time
a boiler is subjected to freezing conditions, and
the boiler is not able to re, and/or the water is
not able to circulate, there is a risk of freezing
in the boiler or in the pipes in the system. When
water freezes, it expands. This may result in bursting
of pipes, or damage to the boiler, and this could
result in leaking or ooding conditions.
Do not use automotive antifreeze. To help prevent
freezing, LAARS recommends the use of inhibited
glycol concentrations between 20% and 35% glycol.
Typically, this concentration will serve as burst
protection for temperatures down to approximately
-5°F (-20°C). If temperatures are expected to be
lower than -5°F (-20°C), glycol concentrations up
to 50% can be used. When concentrations greater
than 35% are used, water ow rates must be
increased to maintain a 20°F to 25°F temperature
rise through the boiler.
WARNING
Glycol must not be used in domestic hot
water applications. Refer to Section 7 for
instructions on freeze protection for MGV
units (domestic hot water).
Page 20
LAARS Heating Systems
Different glycol products may provide varying
degrees of protection. Glycol products must
be maintained properly in a heating system, or
they may become ineffective. Consult the glycol
specications, or the glycol manufacturer, for
information about specic products, maintenance
of solutions, and set up according to your particular
conditions.
The following manufacturers offer glycols,
inhibitors, and anti foamants that are suitable
for use in the MagnaTherm. Please refer to the
manufacturers instructions for proper selection and
application.
• Sentinel Performance Solutions Group
• Hercules Chemical Company
• Dow Chemical Company
The boiler control offers some assistance with freeze
protection, as long as the boiler is energized, and
able to re.
1. If the outlet sensor detects less than 45°F, the
control energizes the boiler pump.
2. If the outlet sensor detects less than 35°F, the
control will re at low rate.
3. Once in freeze protect mode, the boiler will
remain in that state until the outlet sensor detects
greater than 50°F.
The condensate drain must be installed to prevent
the accumulation of condensate. When a condensate
pump is not used, the tubing must continuously
slope downward toward the drain with no spiraling.
Consult local codes for the disposal method.
Caution
Condensate is mildly acidic (pH=5), and
may harm some oor drains and/or pipes,
particularly those that are metal. Ensure
that the drain, drainpipe, and anything that
will come in contact with the condensate
can withstand the acidity, or neutralize
the condensate before disposal. Damage
caused by failure to install a neutralizer
kit or to adequately treat condensate will
not be the manufacturer’s responsibility.
6.4 MGH Suggested Piping Schematics
Figure 7 through Figure 10 show suggested piping
congurations for MGH boilers. These diagrams
are only meant as guides. All components or piping
required by local code must be installed.
6.5 Condensate Drain Trap
A condensate drain trap is included with the
MagnaTherm and is designed to drain the boiler of
condensate. The vent condensate should be drained
through a drain tee located in the vent line. This will
help prevent excessive condensate from entering the
boiler condensate trap.
Connect a 3/4” PVC pipe between the drain
connection and a oor drain (or condensate pump if
a oor drain is not accessible).
MagnaTherm Boilers and Water Heaters
Space heating zone circuits
Space heating zone circuit
Page 21
Low temp. radiant zone
Air vent
Water feed
controls
4 pipe dia. max.
System pump
4 pipe dia. max.4 pipe dia. max.4 pipe dia. max.
Note This drawing is a schematic
representation of a piping style,
and is not intended to be used
as a working installation drawing.
Local code requirements
must be met.
Figure 7. Hydronic Piping — Single Boiler, Multiple Temperature Zones
Zoning with circulators
Page 22
Note This drawing is a schematic
representation of a piping style,
and is not intended to be used
as a working installation drawing.
Local code requirements
must be met.
LAARS Heating Systems
Air vent
Expansion tank
4 pipe dia. max.
Low temp. radiant zone
Water feed controls
Indirect DHW tank
Low temp. radiant zone
Anti-scald
mixing
valve
Domestic
hot water
out
Cold water
Figure 8. Hydronic Piping — Single Boiler with Low Temperature Zones and Indirect DHW Tank
Indirect tank directly off of boiler
MagnaTherm Boilers and Water Heaters
Page 23
Note This drawing is a schematic
representation of a piping style,
and is not intended to be used
as a working installation drawing.
Local code requirements
must be met.
Space heating zone circuit
Air vent
Water feed controls
Expansion tank
4 pipe dia. max.
Space heating
zone circuits
Low temp. radiant zone
4 pipe dia. max.4 pipe dia. max.
Common piping must be sized for the
combined water ow of all of the boilers.
Common piping must be sized for the
combined water ow of all the boilers.
Note This drawing is a schematic
representation of a piping style,
and is not intended to be used
as a working installation drawing.
Local code requirements
must be met.
4 pipe dia. max.4 pipe dia. max.
Note Indirect pump
must be sized
for boiler and
indirect
Indirect
DHW tank
Anti-scald
mixing valve
Domestic
hot water
out
Cold
water
Note In this piping arrangement,
the boiler pump must turn o
during DHW operation.
Figure 10. Hydronic Piping — Multiple Boilers, Indirect DHW Off of One Boiler
MagnaTherm Boilers and Water Heaters
Section 7 WATER CONNECTIONS
MGV UNITS
7.1 MGV Water Quality
MGV water heaters must be installed in water
conditions of 15 gpg hardness or less, with a pH
range of 6.5 to 9.5 pH. Values outside of this range
may reduce the life expectancy of the product.
Operating the MGV in water with higher hardness
levels will cause heat exchanger fouling, erosion,
or corrosion, leading to premature component
or system failure. Failure of this type will not be
warranted. If the water in use exceeds the conditions
recommended, water softeners or other devices
should be installed to improve water quality.
Page 25
7.2 MGV Suggested Piping Schematics
Figure 11 through Figure 13 show suggested piping
congurations for MGV boilers. These diagrams
are only meant as guides. All components or piping
required by local code must be installed.
7.3 MGV Piping Requirements
The water piping should be supported by suitable
hangers and oor stands. Do not support the piping
with this appliance. The hangers used should allow
for expansion and contraction of copper pipe. Rigid
hangers may transmit noise through the system
resulting from piping sliding in the hangers. We
recommend that padding be used when rigid hangers
are installed. Maintain 1” (2.5 cm) clearance to
combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size) to
the drain or in a manner to prevent injury in the
NOTE: This drawing shows
Location
of pump
TPRV
NOTES:
1. Locate MGV DHW sensor or remote aquastat well
in lower 1/3 of tank.
2. Back ow preventer may be required - check local codes.
3. Thermal expansion tank may be required - check local codes.
4. Caution: Pump sizing must be based upon water hardness at job site.
5. If the tank does not have a tapping for the cold water supply, the supply may be run
to the pipe between the tank and boiler inlet.
suggested piping conguration and
valving. Check with local codes and
ordinances for additional requirements.
1
Supply
Building
return
Expansion
tank
3
Cold
water
supply
2
Figure 11. DHW Piping - One Heater, One Vertical Tank
Page 26
LAARS Heating Systems
event of pressure relief. Install a diaphragm-type
expansion tank, ow check, and shutoff valves
where needed or as required by code.
The piping should be installed so that each pump
supplies ow only to the heater to which it is
attached.
7.4 MGV Cold Water Make-Up
The cold water make-up may be connected to the
tank as shown in Figure 11 through Figure 13.
If the tank does not have a tapping for the cold
water supply, the supply may be run to the pipe
between the tank and boiler inlet. Install back-ow
preventers and shut-offs where needed or required
by code.
2
Cold water
supply
7.5 MGV Freeze Protection
If installing outdoors in a location that may
experience freezing temperatures, precautions must
be taken to prevent water in the heat exchanger
and condensate inside and outside of the boiler
from freezing. Damage due to freezing water or
condensate is not covered by the warranty .
If installed indoors, and there is an event such as
a power outage, component failure or other issue
when freezing is likely, the heater and system
must be drained to avoid the risk of damage due
to freezing. Glycol must not be used in volume
water heating applications.
NOTES:
1. Locate the MGV DHW sensor or remote aquastat well
in lower 1/3 of tank.
2. Back ow preventer may be required - check local
codes.
3. Thermal expansion tank may be required check local codes.
4. Caution: Pump sizing must be based upon water
Building
return
hardness at job site.
5. If the tank does not have a tapping for the cold water
supply, the supply may be run to the pipe between the
tank and boiler inlet.
Pump
Supply
Expansion
tank
TPRV
1
Ball valve
(typical)
TPRV
1
Figure 12. DHW Piping - One Heater, Two Vertical Tanks
NOTE: This drawing shows
suggested piping conguration and
valving. Check with local codes and
ordinances for additional requirements.
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.