LAARS M4-LHS Installation Manual

Installation and Operation Manual
Modulating and Condensing /
Document 4232
M4-LHS
Non-condensing Boiler control
Hybrid Multi-Boiler Control
WARNING
FOR YOUR SAFETY: This product must be installed and serviced by
controls installation and maintenance. This manual is intended for
anyone who will install, operate or maintain the control system. Before
you begin installation and operation of this control, it is important that
you thoroughly review this manual. Improper installation and operation
could result in damage to equipment and possibly even personal
injury. Laars Controls are not intended for use as operation safety limit
controls. Another control, that is intended and certified as a high limit
control, must be in the water heater/boiler control circuit.
HTC# 059295-00 A
Contents
Hybrid Logic Overview
. . . . . . . . . . . . . . . . . . 3
Modulating Logic Overview. . . . . . . . . . . . . . . . 4
Outdoor Reset Concept . . . . . . . . . . . . . . . . . . 5
Control Layout . . . . . . . . . . . . . . . . . . . . . . . 6
Extension Layout . . . . . . . . . . . . . . . . . . . . . . 7
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Make Sure You Have the Right Control . . . . . . . . . 9
Installation . . . . . . . . . . . . . . . . . . . . . . . . . 10
Mounting the Enclosure. . . . . . . . . . . . . . . . . 10
Install the Sensors . . . . . . . . . . . . . . . . . . . . 11
System Sensor Installation . . . . . . . . . . . . . . . . 11
Outdoor Sensor Installation . . . . . . . . . . . . . . . . 11
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Wiring the Power . . . . . . . . . . . . . . . . . . . . . 12
Wiring the Sensors . . . . . . . . . . . . . . . . . . . . 12
Wiring the Shutdown, Tstat, or Setback . . . . . . . . . . 12
Wiring the Prove . . . . . . . . . . . . . . . . . . . . . 13
Wiring the Indirect Domestic Hot Water (DHW) Call . . . . 13
Wiring the System Output. . . . . . . . . . . . . . . . . 13
Wiring the Boilers. . . . . . . . . . . . . . . . . . . . . 14
Wiring Boiler Activation or On/Off Staging Boilers . . . . . 14
Wiring Multi-Stage Boilers . . . . . . . . . . . . . . . . 14
Wiring to Modulating Boilers . . . . . . . . . . . . . . . 14
Wiring the 4-20mA Modulating Boilers . . . . . . . . . . 14
Wiring Voltage Modulating Boilers. . . . . . . . . . . . . 14
Connecting to the Extensions and 4-20mA EMS Interface 15
Connecting to BACnet Interface Module . . . . . . . . . 16
Activate the Battery . . . . . . . . . . . . . . . . . . . 16
HYBRID Startup Menu . . . . . . . . . . . . . . . . . . 17
Modulating Startup Menu . . . . . . . . . . . . . . . . 18
Startup Settings. . . . . . . . . . . . . . . . . . . . . . 19
Program Change Switch Setting . . . . . . . . . . . . . 19
Startup Sequence . . . . . . . . . . . . . . . . . . . . 19
Boiler Type . . . . . . . . . . . . . . . . . . . . . . . . 19
Sensor Type . . . . . . . . . . . . . . . . . . . . . . . 19
EMS Input Mode . . . . . . . . . . . . . . . . . . . . . 19
EMS 4mA and 20mA Set Points. . . . . . . . . . . . . . 20
HYBRID Startup Settings . . . . . . . . . . . . . . . . 20
Switch Set Point . . . . . . . . . . . . . . . . . . . . . 20
Switch Differential . . . . . . . . . . . . . . . . . . . . 20
Switch Delay . . . . . . . . . . . . . . . . . . . . . . . 21
Heavy Load Sequence 2nd Group . . . . . . . . . . . . 21
Condensing and Non-Condensing Boiler Type . . . . . . 21
Condensing and Non-Condensing Boiler Number . . . . . 21
HYBRID Modulating Boiler Settings . . . . . . . . . . 22
Modulating Output Type . . . . . . . . . . . . . . . . . 22
Modulating Mode . . . . . . . . . . . . . . . . . . . . . 22
HYBRID Staging Boiler Settings . . . . . . . . . . . . 22
Staging Output Type . . . . . . . . . . . . . . . . . . . 22
Staging Mode . . . . . . . . . . . . . . . . . . . . . . 22
Modulating Boiler Settings . . . . . . . . . . . . . . . 23
Boiler Number . . . . . . . . . . . . . . . . . . . . . . 23
Modulating Output Type . . . . . . . . . . . . . . . . . 23
Modulating Mode . . . . . . . . . . . . . . . . . . . . . 23
Startup Settings (Continued) . . . . . . . . . . . . . . 24
Prove/Indirect Domestic Hot Water (DHW) Priority . . . . 24
Indirect Domestic Hot Water Set Point . . . . . . . . . . 24
Shutdown/Tstat/Setback Mode . . . . . . . . . . . . . . 24
Boost Mode . . . . . . . . . . . . . . . . . . . . . . . 25
Sensor Fault . . . . . . . . . . . . . . . . . . . . . . . 25
Setting the Control to Factory Defaults . . . . . . . . 25
BACnet MSTP Communication Menu. . . . . . . . . 26
BACnet Mode . . . . . . . . . . . . . . . . . . . . . . 26
BACnet Baud Rate . . . . . . . . . . . . . . . . . . . . 26
MS/TP Address. . . . . . . . . . . . . . . . . . . . . . 26
BACnet ID . . . . . . . . . . . . . . . . . . . . . . . . 26
Operating Settings . . . . . . . . . . . . . . . . . . . . 27
Program Change Switch Setting . . . . . . . . . . . . . 27
Season. . . . . . . . . . . . . . . . . . . . . . . . . . 27
Set Point . . . . . . . . . . . . . . . . . . . . . . . . . 27
Reset Ratio. . . . . . . . . . . . . . . . . . . . . . . . 27
Offset . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Outdoor Cutoff Temperature . . . . . . . . . . . . . . . 30
Minimum Water Temp . . . . . . . . . . . . . . . . . . 30
Maximum Water Temp . . . . . . . . . . . . . . . . . . 30
HYBRID Operating Menu . . . . . . . . . . . . . . . . 28
Modulating Operating Menu . . . . . . . . . . . . . . 29
System Settings . . . . . . . . . . . . . . . . . . . . . 31
Setback . . . . . . . . . . . . . . . . . . . . . . . . . 31
Purge Delay . . . . . . . . . . . . . . . . . . . . . . . 31
System Run-On . . . . . . . . . . . . . . . . . . . . . 31
Lead Boiler Rotation . . . . . . . . . . . . . . . . . . . 32
Standby Time. . . . . . . . . . . . . . . . . . . . . . . 32
Last Stage Hold . . . . . . . . . . . . . . . . . . . . . 32
Lead Stages . . . . . . . . . . . . . . . . . . . . . . . 32
Modulating Boiler Operating Settings . . . . . . . . . 33
Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Lag Delay . . . . . . . . . . . . . . . . . . . . . . . . 33
Soft-Off Delay . . . . . . . . . . . . . . . . . . . . . . 33
Staging Boiler Operating Settings . . . . . . . . . . . 34
Reaction Time . . . . . . . . . . . . . . . . . . . . . . 34
Minimum Runtime . . . . . . . . . . . . . . . . . . . . 34
Day - Night Schedule . . . . . . . . . . . . . . . . . . 36
Set Time . . . . . . . . . . . . . . . . . . . . . . . . . 36
Maintenance . . . . . . . . . . . . . . . . . . . . . . . 36
System & Outdoor Sensor Trim . . . . . . . . . . . . . . 36
Output Modulation Trim. . . . . . . . . . . . . . . . . . 37
Conguration . . . . . . . . . . . . . . . . . . . . . . . 37
Display . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Boiler Status . . . . . . . . . . . . . . . . . . . . . . . 38
Display Modulating Boiler Status . . . . . . . . . . . . . 38
Display Messages . . . . . . . . . . . . . . . . . . . . 38
Boiler Stage Menu . . . . . . . . . . . . . . . . . . . . 38
Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Ignition % . . . . . . . . . . . . . . . . . . . . . . . . 40
Modulation Start % . . . . . . . . . . . . . . . . . . . . 40
Copy Settings - Boiler A Only . . . . . . . . . . . . . . . 40
Troubleshooting . . . . . . . . . . . . . . . . . . . . . 41
Specications . . . . . . . . . . . . . . . . . . . . . . . 43
Hybrid - Outdoor Reset - BACnet Variable list . . . 44 Modulation - Outdoor Reset - BACnet Variable list 45
Modulation - Set Point - BACnet Variable list . . . . 46
BACnet PICS Statement. . . . . . . . . . . . . . . . . 47
Piping and Wiring Diagrams . . . . . . . . . . . . . . 48
Hybrid Piping Diagram . . . . . . . . . . . . . . . . . 48
Hybrid Wiring Diagram . . . . . . . . . . . . . . . . . 49
Modulating Piping Diagram. . . . . . . . . . . . . . . 50
Modulating Wiring Diagram. . . . . . . . . . . . . . . 51
HT# 059295-00 A
2
M4-LHS Installation and Operation Manual
HYBRID LOGIC OVERVIEW
In response to new advancement in condensing boiler design and size, many applications utilize multiple condensing boilers in addition to the non-condensing boilers. That triggered Laars's design of the M4-LHS. It is intended to manage the two groups of
When Hybrid is selected as the Boiler Type, the M4-LHS will select the lead group based on the Target temperature switching set point. See "Switch Set Point" on page 20. The Condensing group of boilers will be the Lead group when the System Temperature is below the System Target Switching Set Point. However, when the System Temperature rises above the Switching Set Point, the Non-Condensing boiler group will be the lead group and the Condensing Group will be the lag group.
Basically, the M4-LHS will allow the condensing group of boilers to operate as along as the System sensor is below the Switching Set Point. See"Switch Set Point" on page 20. During that period, if additional output boilers are needed, the M4-LHS may energize the Non-Condensing boilers to meet the load depending on the Heavy Load Sequence 2nd Group setting. See"Heavy Load Sequence 2nd Group" on page 21. When less output is required the M4-LHS will de-energize the lag group of boilers prior to de-energizing the lead group of boilers.
To eliminate any short-cycling due to rapid changes in the Target Temperature used in the switching, an adjustable Switching Delay has been incorporated. See"Switch Delay" on page 21.
Each of the condensing and non-condensing groups of boilers can be either modulating or staging. Modulating boilers can be of 4-20mA modulating signal or 0-10V modulating signal. See "Modulating Output Type" on page 23. Staging boilers can be On/Off, 2-Staeg, 3-Stage, or 4-Stage. See "Staging Output Type" on page 22.
For Hybrid settings, See "Boiler Type" on page 19. To set the Condensing and Non-Condensing boiler types See "HYBRID Modulating Boiler Settings" on page 22.
System Temp
140°F
120°F
100°F
SWITCH MODE = Target Temperature
SYSTEM
o
o
OD=
F SYS=
F
25
145
A
B
<<A>> B 100% 52%
C
NON­COND
NON­COND
NON­COND
CONDCOND
CONDCOND
NON­COND
D
RUNPROGRAM
B
C
A
S
D
WR
B
C
A
SY
P
/ VLT
CUR / VLT
CU
CUR / VLT
R
m
mAGND
V
mAGND
A
V
GND
LT
LT
L
N
-
-
­+
+
+
+
+
5
19
2
15
3
0
18
6
13
910
16
78
1
17
4
11
12
2
14
Target Switch Set Point
SYSTEM
A
B
C
D
RUNPROGRAM
C
A
B
A
D
WR
SYS
B
C
P
V
T
R
V
U
/
L
CUR
R / VLT
/
CU
C
AGND
mAGND
mAGND
VLT
VLT
m
LN
-
-
­+
+
+
+
5
13
9
15
3
19
20
18
6
78
16
10
4
17
11
12
14
1
2
Above the Switch Set Point
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
N
SHUTDOW
N
N
SIO
E
XTE
PROVE
OUTDOOR
SYSTEM
D
TS
TAT
/
/DHW
E
MODUL TE
MP
TEMP
CUR / VLT
K
A
E
C
TB
/S
AGND
A
V
V
LT
LT
m
m
-485
RS
TO
O
O
O
T
­+
+
+
+
2
9
30
28
31
32
26
25
23
22
24
27
21
Non-Condensing are the Lead Group Condensing are the Lag Group
= 120°F
o
o
OD=
F SYS=
F
25
145
<<A>> B 100% 52%
Below the Switch Set Point
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
OWN
S
HUTD
EXTENSION
VE
PRO
M
ST
OUTDOOR
S
E
Y
D
/TSTAT
/DHW
MODULE
T
TEMP
EMP
LT
CUR / VLT
/SETBACK
AGND
A
VLT
m
m
VLT
S
-485
R
O
O
O
O
T
T
­++
+
+
+
6
32
23
2
28
29
3031
25
21
22
24
27
Condensing are the Lead Group Non-Condensing are the Lag Group
M4-LHS Installation and Operation Manual
HT# 059295-00 A
3
MODULATING LOGIC OVERVIEW
The Modulation PID logic is capable of controlling multiple modulating current or voltage boilers. When heat is required, the control
PID activates the lead boiler and starts its purge. See "Purge Delay" on page 31. This is followed by the initiation of its modulation at
the Ignition %. See "Ignition %" on page 40. When additional heat is needed, the control starts to increase the lead boiler modulation
until the Modulation Start % has been reached. See "Modulation Start %" on page 40. Any additional heat requirement starts the lag
boiler purge. While the lag boiler is in purge, the lead boiler resumes its modulation until it reaches full re (100% modulation).
Additional heat requirements triggers the control to increase the lag boiler modulation.
When the M4-LHS PID requires reduced output, it will reduce the modulation of the lag boiler until it reaches its Ignition %. That shall be followed by the reduction of modulation of the lead boiler until it reaches 40% percent of the Modulation Start %. This shall trigger the control to turn off the lag boiler. The control will keep reducing the lead boiler modulation until it reaches its Ignition %. If the Last Stage Hold was activated, the control will hold the lead boiler at the Ignition % until the System Temperature exceeds the Target Set Point by the Last Stage hold setting. See "Last Stage Hold" on page 32.
For Modulating boilers, See "Boiler Type" on page 19. Also, See "HYBRID Modulating Boiler Settings" on page 22.
HT# 059295-00 A
4
M4-LHS Installation and Operation Manual
OUTDOOR RESET CONCEPT
Outdoor Temperature (in °F)
70 60
50
40 20
30 0 -10
10 -20
100
120
110
130
140
150
160
180
170
190
200
210
220
1:3 1:2 1:1.5
1:1.25
1:1
1.25:1
1.5:1
2:1
3:1 4:1
Water Temperature (in °F)
Reset Ratio Curves
Reset Ratio is Presented as
Outdoor Temp. : Water Temp. Ratio
1:4
The M4-LHS has multiple operating modes that satisfy most hydronic systems. It
changes the System Set Point based on outdoor temperature (Outdoor Reset). The
M4-LHS varies the temperature of the circulating heating water in response to changes in the outdoor temperature. The heating water temperature is controlled through the modulation or sequencing of the stages.
The M4-LHS also controls the system circulating pump with an adjustable Outdoor
Cutoff. When the outdoor temperature is above the Outdoor Cutoff, the pump is off and no heating water is circulated through the system. When the outdoor
temperature drops below the Outdoor Cutoff, the system pump relay is activated and the heating water circulates through the system. The temperature of the heating
water is controlled by the Reset Ratio, Water Offset, and changes with Outdoor
Temperature.
Reset Ratio/Outdoor Reset
When a building is being heated, heat escapes through the walls, doors, and windows
to the colder outside air. The colder the outside temperature, the more heat escapes. If you can input heat into the building at the same rate that it is lost out of the building, then the building temperatures will remain constant. The Reset Ratio is an adjustment that lets you achieve this equilibrium between heat input and heat loss.
The starting point for most systems is the 1.00 (OD):1.00 (SYS) (Outdoor Temperature : Heating Water Temperature) ratio. This means that for every degree
the outdoor temperature drops, the temperature of the heating water increases by one degree. The starting point of the curves is adjustable, but comes factory selected at 70°F Outdoor Temperature and 100°F Water Temperature. For example with
a 1.00 (OD):1.00 (SYS) ratio, if the outdoor temperature is 50°F, this means the
temperature has fallen 20° from the starting point of 70°F. Therefore, the heating water temperature shall increase 20° to 120°F.
Each building has different heat loss characteristics. A very well insulated building will not lose much heat to the outside air, and may need a Reset Ratio of 2.00
(OD):1.00 (SYS) (Outdoor:Water). This means the outdoor temperature would
have to drop 2° to increase the water temperature 1 degree. On the other hand, a
poorly insulated building with insufcient radiation may need a Reset Ratio of 1.00 (OD):2.00 (SYS). This means that for each degree the outdoor temperature dropped
the water temperature increases by 2°. The M4-LHS has a full range of Reset Ratios to match any buildings heat loss characteristics.
A heating curve that relies not only on Outdoor Temperature but also on the type of radiation improves heat comfort. The following are suggested initial settings for different types of radiation based on average building insulation and heat loss. The
contractor can ne tune these adjustments based on the specic building need.
Type of Radiation in Building Reset Ratio Offset
Radiators (Steel & Cast Iron) 1.00 (OD) : 1.00 (SYS) 0˚F
Baseboard (Finned copper tube& Cast Iron) 1.00 (OD) : 1.00 (SYS) 0˚F
Radiant (High Mass/Concrete) 4.00 (OD) : 1.00 (SYS) -10˚F
Radiant (Low Mass/Joists) 2.00 (OD) : 1.00 (SYS) -10˚F
Fan Coils & Air Handlers 1.00 (OD) : 1.00 (SYS) 20˚F
M4-LHS Installation and Operation Manual
With a 0° Offset, the Reset curves begin at 100° Water Temperature.
With a -20° Offset, the Reset curves begin at 80° Water Temperature.
With a +20° Offset, the Reset curves begin at 120° Water Temperature.
130
120
110
Water T emp erature
100
70 405060
Outdoor Temperature
110
100
90
Water Tem peratur e
80
70 405060
Outdoor Temperature
150
140
130
Water Tem per ature
120
90
100
70 405060
Outdoor Temperature
1:4 1:1
4:1
1:4
-20 Offset
1:4
1:1
4:1
1:1
+20 Offset
5
4:1
HT# 059295-00 A
CONTROL LAYOUT
Program Switch to restrict access to function changes. This switch is covered with Wiring Enclosure.
LED indicates the associated relay status.
OUTPUT RATINGS:
120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
USE COPPER WIRE, CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
CAUTION
: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
PWR
L
1
to de-energize the equipment before servicing.
SYS
N
2
3
4
A
B
C
D
5
6
7
8
9
10
11
12
The digital display shows the system status, set point, lead stage <in brackets>, and status of each stage. To view and adjust settings, press the appropriate buttons.
Buttons function is presented on
Bottom Row of display.
M4-LHS
SYSTEM
A
B
C
D
A
CUR / VLT
GND
13
B
CUR / VLT
mA
VLT
-
+
15
14
CUR / VLT
GND
mA
VLT
GND
-
+
-
+
+
16
18
19
17
HYBRID CONTROL
o
F
OD=35
<<A>> B 100% 50%
STAGE MENU
D
mA
mA
VLT
+
+
+
24
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
OUTDOOR
TEMP
T
O
25
26
RUNPROGRAM
C
CUR / VLT
mA
VLT
GND
-
+
+
20
23
21
22
SYS=145
SYSTEM
PROVE
TEMP
/DHW
T
O
28
29
27
O
30
o
F
SHUTDOWN
/TSTAT
/SETBACK
O
31
EXTENSION
MODULE
RS-485
120VAC Power
Four N.O. Boiler startup relay outputs. Each is wired in series with each boiler's limit circuit.
When connecting the control Outdoor Air
Sensor and System Sensor, no polarity is
observed. Prove terminals must be connected
for control to operate boilers.
System Output controls pumps, valves, or other system components.
Four modulation/staging outputs can be
4-20mA or Voltage. Go to Startup Menu
to determine the type of output for each stage.
Connect Extension panels to add
additional stages using a RJ11 cable(cable
provided with Extension) and RJ45-RJ11
Adaptor (Supplied with control) only or add
X-BAC BACnet Interface Module using RJ45
(cable provided with X-BAC Module)
PART NUMBER # CA009200
HT# 059295-00 A
6
M4-LHS Installation and Operation Manual
EXTENSION LAYOUT
Extension Selection Switch to determine Stage letters and LED colors. Ext-A Stages E - J and all LEDs are Green Ext-B Stages K - P and all LEDs are Red This switch is covered with the Wiring Enclosure.
LED indicates the associated relay status.
PWR
L N
1 2
C US
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
K M OL N P
E
3 4F5 6G7 8H9 10I11 12
FULL MODULATION SEQUENCING EXTENSION
E
G
I
Comm
J
11 12
M4Ext
K
M
O
L
F
N
H
J
P
Power
CAUTION:
More than one disconnect switch may be required to de-energize the equipment before servicing.
VLTmA
1514
CUR / VLT
GND
16
VLTmAGND
181716
Ext B
CUR / VLT
GND
19
VLTmAGND
212019
Ext A
K ML N
E F G H
CUR / VLT
GND
13
OUTPUT RATINGS:
120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
Risk of Electric Shock.
CUR / VLT
VLTmAGND
GND
242322
22
O P
I J
CUR / VLT
GND
25
VLTmA
2726
CUR / VLT
GND
28
EXTENSION
VLTmAGND
302916
MODULE
RS-485
120VAC Power
outputs. Each is wired in series with each boiler's limit circuit.
4-20mA or Voltage. Go to the control Startup
Menu to determine the type of output for each stage.
M4-LHS Installation and Operation Manual
Six N.O. Boiler startup relay
Six modulation/staging outputs can be
PART NUMBER # CA004400
Connect to any M4-LHS
and additional Extension panels to add
additional stages using a RJ11 cable only
(cable provided with M4Ext).
HT# 059295-00 A
7
FEATURES
Laars designed the M4-LHS with Hydronic building heating, using both condensing and non-condensing boilers, as the primary purpose. In addition, the M4-LHS is capable of controlling modulating and staging boilers. With this in mind, many of the M4-LHS features can be utilized to ease, enhance, and improve your system performance.
Condensing and Non-Condensing Boilers Can be Modulating or Multi-Stage.
The M4-LHS can operate both modulating and staging boilers. Just specify each of the Condensing and Non-Condensing boiler group type and the M4-LHS activates the groups based on an adjustable set of criteria.
PID Type Logic
The M4-LHS's control algorithms allow it to look at the rate of change in the system. If the system temperature is changing quickly, the M4-LHS reacts quickly to adjust the modulating stages’ output. If the system temperature changes slowly, the M4-LHS shall make slow and gradual output adjustments. Therefore, the M4-LHS adapts to specic system requirements and minimizes uctuations around the set point.
Controls 0-10 V or 4-20 mA modulating Burners
Whenever any of the Condensing or Non-Condensing group type is set to Modulating, the M4-LHS accurately controls the output from 0 to 100% of modulation for each of these different types of motors. Moreover, a single M4-LHS can control multiple modulating burners each with a different modulating signal.
Controls On/Off, 2-Stage, 3-Stage, or 4-Stage Burners
Whenever one of the Condensing or Non-Condensing group Type is set to Staging, the M4-LHS accurately sequences the stages using a PID logic.
Digital Display of all System Settings
The M4-LHS's alphanumeric digital display names each system parameter in simple English and shows its precise value. The easy to follow menu system allows users to quickly make changes to any system setting without having to learn any specialized codes or keyboard commands.
Automatic Rotation among Stages
Rotating the lead stage of each group promotes even wear. The M4-LHS has three modes of rotation: Manual, Last On, or Time. The Time rotates the lead stage every selected period from every hour to every 60 days.
Outdoor Reset or Set Point
The M4-LHS has a hydronic outdoor temperature reset function. This allows the M4-LHS to change the set point based on outdoor
temperature. Furthermore, additional settings have been added to ne tune this operation, like Offset, Minimum, and Maximum Water
Temperature and night setback schedule.
System Output
This output can be used to activate a system pump, combustion air damper, or perform any other function that is required when any stage is active. It energizes whenever the outdoor temperature is below the Outdoor Cutoff setting. A System Prove input checks the status of components activated by the System output before stages can be activated.
Normal or Parallel Modulation
The M4-LHS can stage modulating boilers as needed. In Normal Modulation, it increases the lead boiler modulation until it reaches its Modulation Start percent adjustment. Then, the M4-LHS starts the next boiler and so on. Moreover, the M4-LHS offers a parallel mode that can modulate several boilers together as a single large boiler. This mode is useful when used with condensing boilers as they
run more efcient at lower modulation. Thus, it is better to run several boilers at lower modulation than to run a single boiler at full re.
Add up to 16 Boiler Stages (Optional)
As a stand-alone, the M4-LHS is designed to control four stages. However, it has the capability of expanding its control to two extension panels each with six boiler stages. Thus, the M4-LHS can control a total of up to 16 boiler stages.
HT# 059295-00 A
8
M4-LHS Installation and Operation Manual
Setback or Day/Night Scheduling
Two Setback modes are available for the M4-LHS:
• The Day/Night Scheduling provides an adjustable time-based schedule for the Setback (only available when Shutdown or Tstat is selected as the Setback/Shutdown Startup option). See "Shutdown/Tstat/Setback Mode" on page 24.
• The Setback mode uses an external signal to switch the operation of the M4-LHS in and out of setback mode (only available when Setback is selected as the Setback/Shutdown Startup option).
Remote Set point (EMS 4-20mA)
By connecting the control to the optional 4-20mA EMS Interface (X-SIG), the control shall be capable of accepting a remote set point.
BACnet MS/TP Communication
An optional BACnet Interface Module (X-BAC) (CA009100) can be used to connect the control to a BACnet MSTP network for remote access.
MAKE SURE YOU HAVE THE RIGHT CONTROL
If you need the M4-LHS to do additional tasks that either are not listed or do not know how to congure them, contact your local Laars representative.
Setting an Initial Program will ease the conguration of the M4-LHS and will give the opportunity to utilize many of the energy saving features while giving comfortable heat when needed.
The program should consist of the following:
• Selecting the features that your system can utilize.
• Installation: Install the Control, switches and sensors. See"Installation" on page 10
• Setting the System Startup. See "Startup Settings" on page 19.
• Setting the System Operating Settings. See "Operating Settings" on page 27
• Setting the Stages. See "Modulating Boiler Operating Settings" on page 33. Also, see "Staging Boiler Operating Settings" on page 34
• Adjusting Reset Ratio and Water Offset (In Reset Mode Only). See "Reset Ratio" on page 27
M4-LHS Installation and Operation Manual
HT# 059295-00 A
9
INSTALLATION
Each of the M4-LHS or Extension consists of three primary enclosure components.
• TheEnclosureDisplayModule: contains the control electronic board, display, buttons, LEDs, and electric wiring terminals.
It has two screws to hold it to the base. A program conguration switch, used to adjust the control settings, is placed above the terminals. This switch is enclosed with the enclosure wiring cover for security. Wiring terminals are of the plug-in type to ease
installation and removal.
• TheEnclosureBase: contains the holes to mount and hold the control against the wall or any at surface. All other enclosure
components mount on the base. The bottom section of the Enclosure Base contains the wiring chamber with knockouts on the bottom to ease installation.
• TheEnclosureWiringCover: seals the wires from the external environment. It has two screws to hold it the base and a hole to secure a lock on the wiring enclosure. A plastic web that separates the wiring chamber into high and low volt sections has been provided.
MOUNTING THE ENCLOSURE
• Select a location near the equipment to be controlled.
• The surface should be at and sufciently wide and strong to hold the M4-LHS or the Extension.
• Keep the control away from extreme heat, cold, or humidity. Ambient operating temperature is from 20 to 120°F.
• Remove the Enclosure Wiring Cover from the control enclosure by removing the two bottom screws.
• Remove the Enclosure Display Module by removing the enclosure middle screws.
• Screw the Enclosure Base to the surface through the upper and lower mounting holes on the back of the enclosure.
• Replace the Enclosure Display Module and replace the enclosure middle screws.
• Do not replace the enclosure wiring cover until all wiring is done.
• When purchasing a padlock for the enclosure, the maximum shank diameter should not exceed ¼"
Enclosure Display Module
Enclosure Wiring Cover Enclosure Base
Hole for optional lock
Mounting Holes
Display Mounting Screws
Wiring Cover
Mounting Screws
HT# 059295-00 A
10
M4-LHS Installation and Operation Manual
INSTALL THE SENSORS
System
Strap-On
Sensor
Shield
Not connected
Plastic
Tie-Wraps
Around Pipe
Strap-On Sensor
Outdoor Sensor
System Sensor Installation
• Only use the System sensor (CA002500 or equivalent) provided with the unit.
• The sensor wires can be extended up to 500' using a shielded 2-conductor cable (Belden #8760 or equivalent). Do not ground the shield at the sensor but at the
panel using one of the terminals marked with an “O”.
• Do not run sensor wires in conduit with line voltage wiring.
• Install a 3/8"ID 1/2"NPT immersion well.
• If installing the system sensor on the supply, insert the sensor in a well with heat paste approximately 5' feet past the boiler loop outlet on the common supply
header but before any major takeoffs. The sensor must be located where it sees the output of all the boiler stages. If a boiler is piped so that the sensor does not see its output, the M4-LHS will not sequence the boilers correctly.
• The sensor can also be installed on the return to the boilers after all major returns
and before any boiler. However, when setting the reset ratio and the offset, the user must consider the temperature drop across the building loop.
WARNING
Use only the System and Outdoor Air sensors included with the control. Do
not use boiler sensors as it will cause operational problems.
Outdoor Sensor Installation
• Only use the Laars Outdoor Air Sensor group included with the unit (CA006500).
• Locate the sensor in the shade on the north side of the building. The sensor
should never be in direct sunlight.
• Be sure the location is away from doors, windows, exhaust fans, vents, or other
possible heat sources.
• The sensor should be mounted approximately 10' feet above ground level.
• Adhere the Outdoor Label provided to the back of the sensor base.
• Use the Enclosure Base bottom knockout for the conduit. Use the locknut to hold
the conduit and enclosure base together. Screw the cover to the base.
• If screws are used to afx the enclosure to the wall, make sure to seal around the
sensor and wall except from the bottom.
• The sensor wires can be extended up to 500' using shielded 2-conductor cable (#18/2). Do not ground the shield at the sensor but at the control using the
terminal marked with an “O”.
• Do not run sensor wires in conduit with line voltage wiring.
Immersion Heating System Sensor
Immersion Well
3/8" ID 1/2" NPT
Shield
Heating System
Sensor
Common Supply Pipe
Sensor Probe
ALERT
If the HSS can not sense the correct water
temperature, the M4-LHS will not provide
comfortable heat levels.
Seal around
sensor and wall
Outdoor Sensor snap-in location
Mounting
screws
location
Outdoor
drip-hole
Outdoor Label
on back of Sensor
Shield
not connected
ALERT
Determining the proper location of the Outdoor Sensor is very important. The M4-LHS will base
the heat on the outdoor temperature information it receives from this location. If the sensor is in the
sun, or covered with ice, its reading will be different from the actual Outdoor Temperature (OD).
M4-LHS Installation and Operation Manual
Conduit
HT# 059295-00 A
11
WIRING
SYSTEM
A
B
C
D
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7
8
9
10
11
12
13
15
14
17
16
18
20
19
21
24
23
29
25
27
26
28
32
30
31
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
+
mA
22
-
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLTBCUR / VLTCCUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE, CLASS 1 WIRE ONLY.
CAUTION
: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
/TSTAT
M4-LHS
HYBRID CONTROL
32
31
RS-485
O
EXTENSION
MODULE
SHUTDOWN
/SETBACK
/TSTAT
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
29
32
30
31
RS-485
O
O
EXTENSION
MODULE
PROVE
/DHW
SHUTDOWN
/SETBACK
/TSTAT
RS-485
EXTENSION
MODULE
• All wiring must enter the enclosure through the bottom knockouts.
• Class 1 voltage wiring must utilize a different knockout and conduit from any Class 2 voltage wiring.
Wiring the Power
(Terminals 1, 2)
• Bring the 120VAC 60Hz power wires through the bottom left knockout of the enclosure.
• Connect the hot line to terminal marked L.
• Connect the neutral line to the terminal marked N.
Laars recommends installing a surge suppressor on the power source to the M4-LHS.
WARNING
Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.
Laars recommends installing a surge suppressor on the power source to the M4-LHS.
Wiring the Sensors
WARNING
Connect the shield at the control terminal end and cut the shield wire at the sensor end.
To avoid operational problems, use only the System and Outdoor Air sensors included with the control.
System Sensor Wiring
(Terminals 27, 28)
• A M4-LHS must be connected to a System Temperature sensor (CA002500 or equivalent) located in the common header. The sensor must be inserted in a 3/8 ID well using heat paste.
• Temperature sensor wires can be extended up to 500’ by splicing its wires with a shielded 2-conductor cable (Belden #8760 or equivalent (#18/2)).
• Temperature sensors have no polarity. Connect the two wires from the sensor to the M4-LHS terminals marked
SYSTEM TEMP 27, 28.
• Connect the sensor shield to the circled terminal 28 with one of the sensor wires.
Outdoor Sensor Wiring
(Terminals 25, 26)
• The M4-LHS will vary the system Set Point based on outdoor temperature. In addition, the Outdoor Air Sensor group (CA006500) is used as an Outdoor Cutoff. The M4-LHS will disable all boilers when the outdoor temperature is above the adjustable Outdoor Cutoff temperature.
• For an outdoor sensor use the outdoor sensor provided.
• The sensor wires can be extended up to 500’ using shielded 2-conductor cable (Belden #8760 or equivalent (#18/2)).
• Temperature sensors have no polarity. Connect the wires from the outdoor sensor to the M4-LHS terminals marked
• Connect the shield to the circled terminal 26 with one of the sensor wires.
OUTDOOR TEMP - 25, 26.
Wiring the Shutdown, Tstat, or Setback
(Terminals 31, 32)
• The Shutdown will be available when selected as the Shutdown/Tstat/Setback mode from the Startup menu. See
• The Shutdown feature can be used whenever it is desirable to turn off the M4-LHS stage outputs from a remote
• The Tstat option, when selected from the Shutdown/Tstat/Setback startup menu, offer the capability of controlling
• The thermostat will send the M4-LHS a call for heat by shorting terminals 31 and 32.
"Shutdown/Tstat/Setback Mode" on page 24. This will provide the user with an adjustable Day/Night Schedule. See "Day - Night Schedule" on page 36.
location or another controller (i.e. EMS input).
the operation of the M4-LHS based on a thermostat input. This will provide the user with a adjustable Day/Night Schedule.
PWR
N
L
1
2
Line
Neutral
120VAC
Power Source
SYSTEM
TEMP
T
O
28
27
System Sensor
OUTDOOR
TEMP
T
O
25
26
Outdoor Sensor
SHUTDOWN
/TSTAT
/SETBACK
O
O
32
30
31
Shutdown,
T-Stat, or
Setback Signal
PROVE
/DHW
O
30
29
Sensor Shield
SYSTEM
TEMP
T
O
28
27
Sensor Shield
HT# 059295-00 A
12
M4-LHS Installation and Operation Manual
• When the Shutdown input is enabled by closing the dry contact, or when the Tstat input is disabled by opening the
RS-485
EXTENSION
MODULE
RS-485
EXTENSION
MODULE
SYSTEM
A
B
C
D
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
7
8
9
10
11
12
13
15
14
17
16
18
20
19
21
24
23
29
25
27
26
28
32
30
31
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
B
C
D
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
+
mA
22
-
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLTBCUR / VLTCCUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE, CLASS 1 WIRE ONLY.
CAUTION
: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
/TSTAT
M4-LHS
HYBRID CONTROL
dry-contact, all active modulating boilers will immediately modulate down to low for the Soft-Off period, then turn off. All staging boilers will turn off immediately.
• The System Output relay will remain active until the System Run-On Delay expires and then it will turn off.
• When Setback is selected in the Startup, a BMS/EMS or external clock can provide a Setback signal using these
input terminals. See "Shutdown/Tstat/Setback Mode" on page 24. No Day/Night Schedule will be available when Setback is selected from the Shutdown/Tstat/Setback mode in the Startup menu.
• Bring the two wires from the dry contact to the terminals marked SHUTDOWN/TSTAT/SETBACK- 31,32.
• The signal must be a dry contact only. No voltage can be placed across the SHUTDOWN/TSTAT/SETBACK
terminals.
Wiring the Prove
(Terminals 29, 30)
• The Prove feature checks system component operation and must be selected in the Startup Menu from the Prove/ DHW Sharing menu. See "Prove/Indirect Domestic Hot Water (DHW) Priority" on page 24.
• A typical use of this feature is to check for pump ow or combustion air damper status before ring any boiler.
• If the PROVE input is open on a call for heat, the M4-LHS enables only the System Output. All boiler outputs
will be off when the PROVE input is open.
• A factory-installed jumper provides the System Prove signal. Do not remove the jumper unless it is replaced with a System Prove signal or these terminals are to be used for DHW call input.
• Bring the two wires from the dry contact to the terminals marked PROVE - 29, 30.
• Prove Input terminals can accept a dry-contact signal only. No voltage can be placed across these terminals.
SHUTDOWN
PROVE
/DHW
O
O
30
29
Prove Signal
/TSTAT
/SETBACK
O
32
31
WARNING
The PROVE input cannot be used as a safety limit. All equipment must have its own
certified limit and safety controls as required by local codes. If Prove is selected in the
startup menu, no boiler stage will start unless Prove terminals are shorted. DO NOT remove
the PROVE jumper supplied unless replacing it with a Prove signal.
Wiring the Indirect Domestic Hot Water (DHW) Call
(Terminals 29, 30)
• DHW can be used to raise system Set Point to the DHW Set Point as well as manage the System Pump according to the DHW Priority setting. One of the DHW options must be selected from the Prove/DHW Sharing Startup menu. See "Prove/Indirect Domestic Hot Water (DHW) Priority" on page 24.
• Remove the existing jumper and wire an aquastat or a control to provide dry-contact closure to the DHW Call - 29,
30 terminals.
• DHW Call terminals can accept dry contact signals only. No voltage can be placed across these terminals.
Wiring the System Output
(Terminals 3, 4)
• The SYS output relay will energize and remain constantly energized whenever the outdoor temperature is below
the Outdoor Cutoff.
• When the outdoor temperature rises 2°F above the Outdoor Cutoff, the SYS output will remain energized for the
period set by the System Run-On then de-energize. See "System Run-On" on page 31.
• In addition, the System output will energize during summer DHW calls when DHW No Priority is selected. See "Prove/Indirect Domestic Hot Water (DHW) Priority" on page 24.
• The SYS output has one Normally Open (N.O.) relay contact rated for (1/8 HP).
• The N.O. contacts are dry contacts only. They do not source any voltage.
• Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.
PROVE
/DHW
O
O
30
29
28
Indirect
DHW Signal
SYS
3
4
L
N
System Pump
or Pump Starter
SHUTDOWN
/TSTAT
/SETBACK
O
32
31
A
5
6
M4-LHS Installation and Operation Manual
HT# 059295-00 A
13
Wiring the Boilers
SYSTEM
A
B
C
D
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
9
10
11
12
13
15
14
17
16
18
20
19
21
24
23
29
25
27
26
28
32
30
31
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
C
D
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
+
mA
22
-
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLTBCUR / VLTCCUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE, CLASS 1 WIRE ONLY.
CAUTION
: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
/TSTAT
M4-LHS
HYBRID CONTROL
SYSTEM
A
B
C
D
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
13
15
14
17
16
18
20
19
21
24
23
29
25
27
26
28
32
30
31
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
+
mA
22
-
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLTBCUR / VLTCCUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
CAUTION
: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
/TSTAT
M4-LHS
HYBRID CONTROL
SYSTEM
A
B
C
D
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
17
18
20
19
21
24
23
29
25
27
26
28
32
30
31
T
T
O
O
RS-485
+
+
mA
VLT
-
+
+
mA
GND
VLT
+
+
mA
22
-
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLTBCUR / VLTCCUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
/TSTAT
M4-LHS
HYBRID CONTROL
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
29
25
27
26
28
32
30
31
T
T
O
O
RS-485
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
PROVE
/DHW
SHUTDOWN
/SETBACK
/TSTAT
HYBRID CONTROL
• When wiring Condensing and Non-Condensing boilers make sure that the Condensing boilers use the rst
stages and the Non-Condensing boilers use the following stages. That is, if the installation had two Condensing Modulating boilers and two Non-Condensing Staging On/Off boilers, Stage A and B must be used by the Condensing boilers while Stage C and D must be used by the Non-Condensing boilers.
Wiring Boiler Activation or On/Off Staging Boilers
(A Terminals 5, 6), (B Terminals 7, 8), ...
• Each boiler output has a Normally Open (N.O.) dry-contact relay. They do not source any power.
• Wire the N.O. relay contacts in series with the unit’s limit circuit.
• Note that some modulating boilers may not require the use of these outputs.
A
SYS
5
3
4
Boiler
Boiler Enable
Output
B
678
Wiring Multi-Stage Boilers
(For Staging Boiler Types Only) See Page 19
• Each stage on a multi-stage boiler must use one of the N.O. relays.
• Note that on the display of the M4-LHS each multi-stage boiler will
OD=55oF SYS=142
<<AB>> CD HI LOW
consist of a multiple letters.
• Each stage output has one Normally Open (N.O.) relay contact that
does not source any power.
STAGE MENU
Multi-Stage Boiler
WARNING
Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.
Wiring to Modulating Boilers
The M4-LHS can modulate any combination of current or voltage boiler signals. See "Modulating Output Type" on page 23. Some modulating boilers may require the use of the stage output relays in addition to the modulating output.
WARNING
The Modulating Output Type must be set to match the boiler modulating
signal prior to wiring the boiler signal to avoid control or equipment damage.
Wiring the 4-20mA Modulating Boilers
(A Terminals 13, 14), (B Terminals 16, 17),...
• The M4-LHS can operate up to four 4-20 mA modulating motors.
• The Extension can operate up to six 4-20 mA modulating motors.
• The M4-LHS and the Extension sources excitation voltage for the
4-20mA signal.
• Wire the (-) from the boiler modulating motor to the (GND) terminal
on the M4-LHS. That is for boiler A, the modulating (GND) terminal will be 13.
• Wire the (+) from the boiler modulating motor to the (mA+) terminal
on the M4-LHS. That is for boiler A, the modulating (mA+) terminal will be 14.
OD=55oF SYS=142
<A> B 80% 50%
STAGE MENU
Modulating Boiler (Modulating
Boiler Type)
D
o
F
C
8
9
10
11
12
Low
High
2-Stage Boiler
o
F
A
CUR / VLT
mA
VLT
GND
-
+
+
15
13
14
4-20mA
-
Boiler 4-20mA
Modulation Output
Burner
Motor
+
GND
-
16
Wiring Voltage Modulating Boilers
(A Terminals 13, 15), (B Terminals 16, 18),...
• The M4-LHS can operate up to four 0-10V modulating motors.
• The Extension can operate up to six 0-10V modulating motors.
• Wire the (GND) from the boiler modulating motor to the (GND) terminal on the M4-LHS. For boiler D, the modulating (GND) terminal is be 22.
• Wire the (VLT+) from the boiler modulating motor to the (VLT+)terminal on the M4-LHS. For boiler D, the modulating (VLT+) terminal is be 23.
HT# 059295-00 A
14
M4-LHS Installation and Operation Manual
C
D
CUR / VLT
mA
mA
mA
VLT
VLT
GND
-
+
+
+
+
+
20
GND
23
21
24
22
Voltage
Burner
Motor
Boiler Voltage
Modulation Output
V+
Connecting to the Extensions and 4-20mA EMS Interface
SYSTEM
A
B
C
D
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
HYBRID CONTROL
RUNPROGRAM
ALERT
To set the Extension to a specific letter, remove the wiring cover and switch the Ext A/Ext B to the
desired letter. DO NOT set both extensions to the same letter to avoid errors.
• The M4-LHS is equipped with a RJ45 socket and a RJ45 to RJ11 Adaptor to connect to extension panels and X-SIG 4-20mA EMS
Interfaces. The Extension is equipped with two RJ11 sockets. It comes packaged with a RJ11 cable to connect to M4-LHS and an
additional Extension. Use the RJ45 to RJ11 Adaptor on the M4-LHS.
• The order in which the control, the extensions, and the interface are wired is not observed.
• Set each Extension to a different letter (EXT-A or EXT-B). The M4-LHS assigns the stage letters based on the extension letter
selected.
• Extension-A operates stages (E - J) and all the LEDs are Green. However, Extension-B operates stages (K - P) and all the LEDs
are Red. .
• Congure the Modulating and Sequencing Output Types after connecting the Extension panels to be able to congure their outputs.
See "Boiler Type" on page 19
• Use the 6-wire RJ11 cable supplied with the extension for proper operation.
M4-LHS
M4-LHS
SYSTEM
OUTPUT RATINGS:
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
FOR ALL CIRCUITS
INPUT RATINGS:
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
115VAC 60Hz , 30VA MAX
USE COPPER WIRE,
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
CLASS 1 WIRE ONLY.
ENCLOSED ENERGY
MANAGEMENT
EQUIPMENT
CAUTION: RISK OF ELECTRIC SHOCK
CAUTION: RISK OF ELECTRIC SHOCK
LISTED
More than one disconnect switch may be required
More than one disconnect switch may be required
99RA
to de-energize the equipment before servicing.
to de-energize the equipment before servicing.
D
C
B
A
SYS
PWR
SYS
PWR
L
N
L
N
3
1
2
3
1
2
D
C
B
A
5
8
6
7
9
10
4
11
12
5
6
7
9
8
10
4
11
12
SYSTEM
A
A
B
B
C
C
D
D
B
A
A
B
CUR / VLT
CUR / VLT
CUR / VLT
CUR / VLT
CUR / VLT
CUR / VLT
mA
VLT
mA
VLT
GND
GND
GND
mA
mA
VLT
GND
GND
GND
VLT
-
-
-
-
-
-
+
+
+
+
+
+
+
+
19
15
13
18
16
14
17
19
15
13
18
16
14
17
4-20 mA EMS
4-20mA INPUT
SignalGND
+
2
1
3
EMS/BMS Temperature Set PointInput
EMS/BMS Sources Excitation Voltage
CONDENSING AND NON-CONDENSING
Full Modulation Sequencing Control
o
F
SYS=145oF
OD=35
<<A>> B 100% 50%
STAGE MENU
DO NOT APPLY ANY VOLTAGE
DO NOT APPLY ANY VOLTAGE
RUNPROGRAM
RUNPROGRAM
20
20
C
D
D
C
CUR / VLT
CUR / VLT
mA
mA
VLT
mA
VLT
GND
VLT
mA
mA
mA
GND
VLT
-
-
+
+
+
+
+
+
+
+
+
+
23
22
24
21
23
21
22
24
RJ45 to RJ11
Adaptor
TO INPUT TERMINALS
TO INPUT TERMINALS
SYSTEM
OUTDOOR
SYSTEM
OUTDOOR
TEMP
TEMP
TEMP
TEMP
T
T
O
T
T
O
26
25
27
26
25
27
X SIG
RS485
EXTENSION
CONNECTORS
(-) (+)
O
O
28
28
PROVE
PROVE
/DHW
/DHW
O
O
30
29
30
29
RJ11
SHUTDOWN
SHUTDOWN /SETBACK
/SETBACK
31
31
M4-Extension A
M4-Ext
FULL MODULATION SEQUENCING EXTENSION
K
F
E
M
H
G
O
J
I
Power
Comm
EXTENSION
EXTENSION
/TSTAT
MODULE
MODULE
RS-485
O
RS-485
O
32
32
PWR
L N
1 2
K M OL N P
E
3 4F5 6G7 8H9 10I11 12
J
13114
Ext A
K ML N
E F G H
CUR / VLT
VLTmA
GND
1716
15
L
N
P
CAUTION:
More than one disconnect switch may be required to de-energize the equipment before servicing.
Ext B
CUR / VLT
CUR / VLT
GND
VLTmAGND
VLTmAGND
GND
21
201916
232219
18
OUTPUT RATINGS:
120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
Risk of Electric Shock.
O P
I J
CUR / VLT
CUR / VLT
VLTmAGND
VLTmA
GND
GND
262522
2928
27
24
CUR / VLT
GND
30
EXTENSION
MODULE
VLTmAGND
RS-485
323116
RJ11
Each Extension Panel or 4-20mA EMS
Interface comes with Connection Cable.
M4-Extension B
M4-Ext
PWR
L N
1 2
K M OL N P
E
3 4F5 6G7 8H9 10I11 12
FULL MODULATION SEQUENCING EXTENSION
K
F
E
M
H
G
O
J
I
Power
Comm
Ext A
K ML N
E F G H
J
CUR / VLT
VLTmA
GND
1716
15
13 14
L
N
P
CAUTION:
More than one disconnect switch may be required to de-energize the equipment before servicing.
Ext B
CUR / VLT
CUR / VLT
GND
VLTmAGND
VLTmAGND
GND
21
201916
232219
18
OUTPUT RATINGS:
120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
Risk of Electric Shock.
O P
I J
CUR / VLT
CUR / VLT
VLTmAGND
VLTmA
GND
GND
262522
2928
27
24
CUR / VLT
GND
30
EXTENSION
MODULE
VLTmAGND
RS-485
323116
RJ11
M4-LHS Installation and Operation Manual
HT# 059295-00 A
15
Connecting to BACnet Interface Module
• The M4-LHS can communicate to BACnet MSTP networks when used the X-BAC BACnet Interface Module (CA009100). The module must be purchased separately.
• The BACnet Interface Module comes with an RJ45 cable.
• Both the M4-LHS and the BACnet Interface Module are equipped with a RJ45 socket (RS485) to connect to communicate to each
other.
• The Interface BACnet Module must be wired to the BACnet MSTP network using the RS485 terminals A, GND, and B.
• If both an extension panel and the BACnet Interface Module are to be used, connect the RJ11 socket on the BACnet Interface
Module to the extension.
• Set the BACnet parameters. See "BACnet MSTP Communication Menu" on page 26.
X-BAC
BACnet Interface Module
PWR
L
N
1
2
OUTPUT RATINGS:
120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
USE COPPER WIRE, CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY MANAGEMENT EQUIPMENT
99RA
CAUTION
: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
SYS
A
B
C
5
3
6
4
7
8
9
10
11
D
12
M4-LHS
A
B
C
D
RUNPROGRAM
A
B
CUR / VLT
GND
-
13
14
C
CUR / VLT
CUR / VLT
mA
VLT
GND
mA
VLT
GND
mA
-
-
+
+
+
+
+
15
16
18
19
17
20
HYBRID CONTROL
D
CUR / VLT
VLT
GND
mA
mA
VLT
-
+
+
+
+
23
21
22
24
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
OUTDOOR
SYSTEM
PROVE
TEMP
TEMP
/DHW
T
O
T
O
O
25
26
28
29
27
30
SHUTDOWN
/TSTAT
/SETBACK
31
MSTP
A GND B
1 2 3
B (-)
A (+)
EXTENSION
MODULE
RS-485
O
32
Ground
To BACnet
MSTP
PRODUCT
COMM
RJ45 Cable
RS485
RJ45 RJ11
RJ45
RJ45 Communication Cable
Extension
M4Ext
PWR
L N
1 2
K M OL N P
E
3 4F5 6G7 8H9 10I11 12
FULL MODULATION SEQUENCING EXTENSION
K
E
M
G
O
I
Comm
J
13 14
L
F
N
H
J
P
Power
Ext A
K ML N
E F G H
CUR / VLT
CUR / VLT
VLTmA
GND
GND
1716
15
18
OUTPUT RATINGS:
120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
More than one disconnect switch may be required to de-energize the equipment before servicing.
Ext B
CUR / VLT
GND
VLTmAGND
21
201916
I J
CUR / VLT
CUR / VLT
VLTmAGND
VLTmAGND
GND
GND
232219
262522
27
24
O P
CUR / VLT
VLTmA
GND
2928
30
VLTmAGND
323116
RJ11
ACTIVATE THE BATTERY
• The battery enables to control to maintain the clock time.
• Unscrew and remove the Enclosure Display Module to reveal the back of the control CPU Board.
• Remove the plastic strap that covers the battery. The battery holder contacts should be touching the battery. The control has a coin Lithium battery (CR2032) that is used to
maintain the control's time during power outages. This battery can maintain the clock for up to a total of 100 days.
EXTENSION
MODULE
RS-485
RJ11 Extension Cable
Battery
ALERT
Do not install the battery unless you plan to keep the control continuously powered. If the
control has no power, the battery will lose its charge in 100 days.
HT# 059295-00 A
16
M4-LHS Installation and Operation Manual
HYBRID STARTUP MENU
-------- SETTINGS ----
Season Winter
System Target 140 <System Settings> <Maintenance> <System Startup>
BACK SELECT
-EMS 20ma SETPOINT-
220
F
o
[ ]
BACK SAVE
--- SWITCH DELAY ---
0.5Hour
[ ]
BACK SAVE
Page 21
HEAVY LOAD
-SEQUENCE #2 GROUP-
No
Yes
BACK SAVE
Page 22
CONDENSING
- MODULATING MODE -
Normal
Parallel
BACK SAVE
Page 21
NON-CONDENSING
---- BOILER TYPE ----
Modulating
Staging
BACK SAVE
NON-CONDENSING
-- BOILER NUMBER --
1
[ ]
BACK SAVE
Page 24
- SETBCK/SHUTDOWN -
Shutdown/Disable
Tstat/Enable Setback
BACK SAVE
Shutdown
Page 25
--- BOOST MODE ---
30 Minutes
Disable
BACK SAVE
M4-LHS Installation and Operation Manual
or Tstat
o
F
Page 20Page 21
Page 21
Page 24
Page 25
Setback
-- ARE YOU SURE? --
No
Yes
BACK SAVE
-EMS 4ma SETPOINT -
o
70
F
[ ]
BACK SAVE
--- SWITCH DIFF ---
o
10
F
[ ]
BACK SAVE
CONDENSING
---- BOILER TYPE ----
Modulating
Staging
BACK SAVE
CONDENSING
-- OUTPUT B TYPE --
4-20mA
0-10volt 0-5volt 2-10volt 1-5volt
BACK SAVE
NON-CONDENSING
-- OUTPUT C TYPE --
4-20mA
0-10volt 0-5volt 2-10volt 1-5volt
BACK SAVE
- DHW SETPOINT -
180
F
o
[ ]
BACK SAVE
--- SENSOR FAULT ---
All Off
All On
BACK SAVE
Page 19
--- BOILER TYPE ---
Modulation
Hybrid
Yes
BACK SAVE
Page 19Page 20
--- SENSOR TYPE ---
Reset oF
Reset
o
C
4-20mA EMS
4-20mA EMS
BACK SAVE
Reset
Page 20
- SWITCH SETPOINT -
o
150
[ ]
BACK SAVE
Page 21
CONDENSING
-- BOILER NUMBER --
2
[ ]
BACK SAVE
Page 23
-- OUTPUT A TYPE --
4-20mA
0-10volt 0-5volt 2-10volt 1-5volt
BACK SAVE
Page 22
- MODULATING MODE -
Normal
Parallel
BACK SAVE
Page 24
PROVE/DHW SHARING
Prove
DHW Priority DHW No Priority No Priority (Summer)
BACK SAVE
All DHW Options
Page 26
--- BACNET MODE ---
Disable
Enable
BACK SAVE
Modulating
CONDENSING
NON-CONDENSING
F
HT# 059295-00 A
17
MODULATING STARTUP MENU
Page 19
-------- SETTINGS ----
Season Winter
System Target 140
o
F <System Settings> <Maintenance> <System Startup>
BACK SELECT
Page 20
-EMS 4ma SETPOINT -
o
70
F
[ ]
BACK SAVE
-EMS 20ma SETPOINT-
220
F
o
[ ]
BACK SAVE
ALERT
To be able to change the M4-LHS
settings the Program/Run Switch must
be set to Program. The switch is located
under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover
can be secured using a lock.
-- ARE YOU SURE? --
No
Yes
Yes
BACK SAVE
- EMS INPUT MODE -
Disable
Enable
Enable
BACK SAVE
Disable
Page 23 Page 23
Set Point
-- BOILER NUMBER --
2
[ ]
BACK SAVE
Page 24
PROVE/DHW SHARING
Prove
DHW Priority DHW No Priority No Priority (Summer)
BACK SAVE
All DHW
Options
Page 24
- DHW SETPOINT -
180
[ ]
BACK SAVE
o
F
--- BOILER TYPE ---
Modulation
Hybrid
BACK SAVE
Page 19
-- SENSOR TYPE --
Reset oF
Reset
o
C Set Point oF Set Point oC
BACK SAVE
OUTPUT A TYPE --
4-20mA
0-10volt 0-5volt 2-10volt 1-5volt
BACK SAVE
Page 22
- MODULATING MODE -
Normal
Parallel
BACK SAVE
Page 25
- SETBCK/SHUTDOWN -
Shutdown/Disable
Tstat/Enable Setback
BACK SAVE
Shutdown
Setback
Page 25
--- SENSOR FAULT ---
All Off
All On
BACK SAVE
Page 26
Page 25
--- BOOST MODE ---
30 Minutes
Disable
BACK SAVE
or Tstat
--- BACNET MODE ---
Disable
Enable
BACK SAVE
HT# 059295-00 A
18
M4-LHS Installation and Operation Manual
STARTUP SETTINGS
SYSTEM
A
B
C
D
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
HYBRID CONTROL
Program Change Switch Setting
To be able to change the M4-LHS settings the Program/Run Switch must be set to Program.
The switch is located under the Enclosure Wiring Cover for security.
Startup Sequence
Button: MENU/<System Startup>
• When powered, the M4-LHS performs a self diagnostics-test.
• On the rst power up, the System Startup screen will appear after the initialization is complete. If it doesn’t, the M4-LHS has already been congured.
• The System Startup menu sets the main parameters that relate to the heating application.
These settings must be set by the installer.
Boiler Type
Modulation,Hybrid Default:Modulation
Button: MENU/<System Startup>/..../Boiler Type
• The same Laars control can operate modulating boilers or a combination of both types.
• The Modulation option will operate a variety of modulating boiler signals.
• The Hybrid option will sequence two groups of boilers, condensing and non-condensing. Each group could be of a different boiler type (Modulation or Staging). See "Hybrid Logic
Overview" on page 3. Each Multi-Stage boiler will use a single output relay for each stage.
• If BACnet is to be used, each of the Boiler Type modes will have a different set of BACnet
variables. See "Hybrid - Outdoor Reset - BACnet Variable list" on page 44.
Sensor Type
Reset°F,Reset°C,SetPoint°F,SetPoint°C,4-20mAEMS Default:Reset°F
(Set Point Options are Not Available with Hybrid Boiler Type)
Button: MENU/<System Startup>/..../Sensor Type
• If Reset °F is selected, all temperatures and settings will be displayed in degrees Fahrenheit
and the control will use Reset Ratios to adjust the system set point.
• If Reset °C is selected, all temperatures and settings will be displayed in degrees Celsius and
the control will use Reset Ratios to adjust the system set point.
• If Set Point °F is selected, all temperatures and settings will be displayed in degrees
Fahrenheit and the control will have an adjustable system set point.
• If Set Point °F is selected, all temperatures and settings will be displayed in degrees Celsius
and the control will have an adjustable system set point.
• The 4-20mA EMS option is only available to the Hybrid Boiler Type option. To use
4-20mA EMS with Modulating Boiler Type, select one of the Set Point options and the EMS Input Mode menu will follow to offer the 4-20mA EMS option.
• The use of the 4-20mA EMS option requires the purchase of the 4-20mA EMS Interface. It
gives the M4-LHS the capability of accepting a remote 4-20mA signal from a BMS or EMS system as the target set point.
• If BACnet is to be used, each of the Sensor Type modes will have a different set of BACnet
variables. See "Hybrid - Outdoor Reset - BACnet Variable list" on page 44.
EMS Input Mode
Disable,Enable Default:Disable
(Available after Set Point with Modulation Boiler Types)
Button: MENU/<System Startup>/..../Boiler Type/Sensor Type / EMS Input Mode
• It allows the M4-LHS to utilize the 4-20mA EMS Interface to accept a remote 4-20mA signal from a BMS or EMS system as the target set point.
-------- SETTINGS ----
Season Winter
System Target 140 <System Settings> <Maintenance> <Histories> <System Startup>
BACK SELECT
--- BOILER TYPE ---
Modulation
Hybrid
BACK SAVE
Modulating Options
-- SENSOR TYPE --
Reset oF
Reset Set Point oF Set Point oC
BACK SAVE
--- SENSOR TYPE ---
Reset oF
Reset 4-20mA EMS
BACK SAVE
- EMS INPUT MODE -
Disable
Enable
BACK SAVE
o
C
Hybrid Options
o
C
RUNPROGRAM
o
F
M4-LHS Installation and Operation Manual
HT# 059295-00 A
19
EMS 4mA and 20mA Set Points
SWITCH MODE = Target Temperature
4mA: can be set from 50°F/ 10°C to 200°F/93°C Default: 70°F/ 21°C 20mA: can be set from 70°F/ 21°C to 220°F/104°C Default: 220°F/ 104°C
Button: MENU/<System Startup>/..../Sensor Type / EMS Input Mode/EMS 4mA Set Point
With the use of the 4-20mA EMS Interface, the M4-LHS will be able to receive a 4-20mA signal as a set point from a BMS or an EMS system as the target set point.
The 4mA and 20mA Set Point menus will follow the selection of the 4-20mA EMS sensor type option or EMS input Mode.
There must be at least a 20°F differential between the 4mA and 20mA temperature settings.
Connect the 4-20mA EMS Control Interface to the M4-LHS RS485 connection.
Any signal below 2.4mA or above 21.6mA will start an EMS shutdown. The display will
indicate that by displaying the message "Shutdown by EMS ".
HYBRID STARTUP SETTINGS
See "Hybrid Logic Overview" on page 3.
System Temp
140°F
NON­COND
NON­COND
CONDCOND
SYSTEM
o
o
OD=
F SYS=
F
25
145
A
B
<<A>> B 100% 52%
C
D
A
B
A
B
D
SYS
PWR
C
L
T
R
/ V
T
C
U
C
CUR / VL
UR / VL
mAGND
D
mAGND
VL
VLT
GN
T
LN
-
-
­+
+
+
+
5
3
9
78
6
10
15
19
13
16
1
4
18
11
2
12
1
17
4
Above the Switch Set Point
DO NOT APPLY ANY VOLTAGE
RUNPROGRAM
TO INPUT TERMINALS
SHUTDOWN
IO
N
N
X
S
TE
E
OUTDOOR
SYSTEM
PROVE
D
C
/TSTAT
/DHW
D
E
UL
MO
TEMP
TEMP
LT
T
R / V
CU
/SETBACK
T
mAGND
mA
V
L
m
L
T
A
V
5
-
48
RS
O
T
O
T
O
O
­+
+
+
+
+
26
20
29
28
30
25
23
32
2
1
24
31
2
2
27
Non-Condensing are the Lead Group Condensing are the Lag Group
-EMS 4ma SETPOINT -
o
70
F
[ ]
BACK SAVE
-EMS 20ma SETPOINT-
220
F
o
[ ]
BACK SAVE
120°F
100°F
NON­COND
NON­COND
Target Switch Set Point
SYSTEM
o
o
OD=
F SYS=
F
25
145
A
B
<<A>> B 100% 52%
C
D
DO NOT APPLY ANY VOLTAGE
RUNPROGRAM
TO INPUT TERMINALS
TD
H
OWN
U
S
N
EXTENSIO M
ST
S
E
Y
OUTDOOR
VE
PR
O
C
A
B
D
R
D
SYS
C
A
PW
B
AT
/TS
T
HW
/
D
DU
LE
MO
MP
TE
TEMP
L
L
R / VL
T
T
C
C
T
UR / V
CUR / VLT
CUR / V
U
A
T
CK
/
B
SE
A
mAG
L
m
mAGND
mA
VLT
T
VLT
A
m
V
GND
VLT
ND
GND
RS-4
85
O
T
O
T
O
O
L
N
-
-
-
­+
+
+
+
+
+
+
+
+
5
3
1
6
10
13
18
5
26
2
19
20
16
28
789
29
25
30
4
23
1
31
2
3
2
11
12
24
21
17
2
14
27
= 120°F
Below the Switch Set Point
Condensing are the Lead Group Non-Condensing are the Lag Group
CONDCOND
Switch Set Point
From 0ºF/ -18ºC to 200ºF/ 94ºC Default: 150ºF/ 66ºC
Button: MENU/<System Startup>/..../Sensor Type/Switch Setpoint
It is the set point at which the M4-LHS will switch between the Condensing Boiler Group and Non-Condensing Boiler Group.
The Condensing Boiler group will be the lead group when the Target Temperature is below the Target Switch Set Point. However, the Non-Condensing Group will be the lead group when the Target Temperature is above the Target Switch Set Point.
Switch Differential
Adjustable from 5Fº / 3Cº to 20Fº / 11Cº Default: 10Fº / 6Cº
Button: MENU/<System Startup>/..../Switch Setpoint/Switch Diff
The Switch Differential controls the group switching. It allows the Calculated Target to
group over.
The default value is a good start to avoid oscillation between Condensing and Non­Condensing Boiler groups, particularly if no Switch Delay was set. See next setting.
- SWITCH SETPOINT -
150
F
o
[ ]
BACK SAVE
--- SWITCH DIFF ---
o
10
F [ ]
BACK SAVE
HT# 059295-00 A
20
M4-LHS Installation and Operation Manual
Switch Delay
Adjustablefrom0.0to12.0Hours Default:0.5hours
Button: MENU/<System Startup>/..../Switch Setpoint/Switch Diff/Switch Delay
• The Switch Delay is an additional layer of assurance used to reduce the intermittent change
of the lead group.
• To switch the lead group when the temperature is dropping, the sensor temperature must
remain below the Switch Set Point less the Switch Differential for the complete Switch Delay period before the switching of the lead group.
• I.e., if the Switch Set Point was set to 135ºF, and the Switch Differential was set to 5ºF, then the Target Temperature must drop below 130ºF for the complete Switch Delay for the lead
group to change from Condensing to Non-Condensing.
• To switch the lead group when the temperature is rising, the Target Temperature must rise
above the Switch Set Point for the complete Switch Delay before the switching of the lead group could take effect.
--- SWITCH DELAY ---
0.5Hour
[ ]
BACK SAVE
Heavy Load Sequence 2nd Group
Yes,No Default:No
Button: MENU/<System Startup>/..../Switch Delay/Heavy Load Seq#2 Group
• This option makes the second group of boilers act as a backup in heavy load conditions.
Thus, allowing them to start after all lead group boilers have run at their maximum capacity.
• If the system was designed to operate both groups of boilers in heavy load conditions, then
select Yes.
• Selecting No will only allow the lead group to operate. The secondary group will remain off
even if the system cannot reach the desired set point.
Condensing and Non-Condensing Boiler Type
Modulating,Staging Default:Modulating
Button: MENU/<System Startup>/..../Heavy Load Seq#2 Group/Condensing Boiler Type
• Select the appropriate boiler type from the list. Each of the types will be followed by a related additional conguration settings to adjust.
Condensing and Non-Condensing Boiler Number
Adjustablefrom1to15 Default:1
Button: MENU/<System Startup>/..../Condensing Boiler Type/ Condensing Boiler Number
• Select the number of condensing boilers. These boilers will occupy the rst letters of the
wiring stages on the M4-LHS starting with Stage-A.
• Then, select the number of non-condensing boilers later in the Startup menu. See "HYBRID
Startup Menu" on page 17.
• Note that, each Multi-Stage boiler requires the use of single output stage relay.
HEAVY LOAD
-SEQUENCE #2 GROUP-
No
Yes
BACK SAVE
CONDENSING
---- BOILER TYPE ----
Modulating
Staging
BACK SAVE
CONDENSING
-- BOILER NUMBER --
1
[ ]
BACK SAVE
M4-LHS Installation and Operation Manual
HT# 059295-00 A
21
HYBRID MODULATING BOILER SETTINGS
Modulating Output Type
4-20mA,0-10V,1-10V(Custom)Outputs Default:1-10vCustom
Button: MENU/<System Startup>/..../Condensing Boiler Number/Output A Type
• If either of the Condensing or Non-Condensing Boiler groups was set to Modulating as the
Boiler Type, the M4-LHS will offer the capability of controlling a variety of modulating
signals. Each boiler can be congured to have a different modulating signal.
• The modulating output for each boiler can be congured to 4-20mA operation (Current) or
any of the voltage options. Check the boiler to determine its signal requirements.
• When using the Extension, connect it to the M4-LHS prior to conguring the Output Type.
Otherwise, the M4-LHS might not recognize the Extension stages.
Modulating Mode
Normal,Parallel Default:Normal
Button: MENU/<System Startup>/..../Output A Type/Condensing Modulating Mode
• Some modulating boilers perform better at higher modulation. For these units, it is
advantageous to run one unit at high modulation than several units at lower modulation. If the units used are of this type, select Normal. This is the recommended setting for boilers with low turndown ratios.
• Most condensing boilers run more efciently at lower modulation. If it is more energy efcient to run several units at lower modulation than one at high. In this case select
Parallel. This is typically used on condensing boilers or boilers with high turndown ratios.
• For best Parallel performance, set the Modulation Start % to be equivalent to the lowest ring rate of the boiler multiplied by 2. That is, if the lowest ring of the boiler was 20%,
set your Modulation Start% to 40%. See "Modulation Start %" on page 40.
• Set the Lag Delay to 0 for better parallel performance. See "Lag Delay" on page 33.
CONDENSING
-- OUTPUT A TYPE --
4-20mA
0-10volt 0-5volt 2-10volt 1-5volt
BACK SAVE
WARNING
Make sure that boiler modulation
wiring matches the signal selected.
Warranty will not cover failed
components caused by improper
wiring. See "Wiring the Boilers" on
page 14.
CONDENSING
- MODULATING MODE -
Normal
Parallel
BACK SAVE
NON-CONDENSING
- MODULATING MODE -
Normal
Parallel
BACK SAVE
HYBRID STAGING BOILER SETTINGS
Staging Output Type
On/Off,2-Stage,3-Stage,4-StageOutputs Default:On/Off
Button: MENU/<System Startup>/..../Non-Condensing Output Type
• The M4-LHS can sequence multi-stage boiler starting with a single On/Off and up to a
4-stages. Just select the number of stages per boiler from this menu option.
• For each boiler stage a single output relay will be used. That is a 2-stage boiler will use two
of the control stages.
• The number selected applies to all sequencing boilers within that group whether it is
Condensing or Non-Condensing.
• The maximum number of stages the control can operate is 4. But with the addition of up to
two extensions, it can handle up to a total of 16 stages.
Staging Mode
Lo/Hi/Lo/Hi,Lo/Lo/Hi/Hi Default:Lo/Hi/Lo/Hi
Button: MENU/<System Startup>/..../Non-Condensing Output Type/Non-Cond Staging Mode
• During low load conditions, some boilers run more efcient when the lower stages are
energized alone than with the higher stages. For these types of boilers select Lo/Lo/Hi/Hi. Then, the M4-LHS will sequence the lower stages of all boilers set to Auto before sequencing the higher stages.
• For the rest of the boiler types, the Lo/Hi/Lo/Hi should allow the staging of the lower stage
of the lead boiler followed by the higher stage of the same boiler. Then when more stages
are needed, it will re the lower stage of the lag boiler followed by the higher stages
NON-CONDENSING
-- OUTPUT TYPE --
On/Off
2-Stage 3-Stage 4-Stage
BACK SAVE
NON-CONDENSING
- STAGING MODE -
LO/HI/LO/HI
LO/LO/HI/HI
BACK SAVE
HT# 059295-00 A
22
M4-LHS Installation and Operation Manual
MODULATING BOILER SETTINGS
Boiler Number
Adjustablefrom1to15 Default:1
Button: MENU/<System Startup>/Boiler Type/.../Boiler Number
• Select the number of modulating boilers.
Modulating Output Type
4-20mA,0-10V,1-10V(Custom)Outputs Default:1-10vCustom
Button: MENU/<System Startup>/..../Boiler Number/Output A Type
• The M4-LHS will offer the capability of controlling a variety of modulating signals. Each boiler can be congured to have a different modulating signal. Check the boiler to
determine its signal requirements.
• When using the Extension, connect it to the M4-LHS prior to conguring the Output Type. Otherwise, the M4-LHS might not recognize the Extension stages.
Modulating Mode
Normal,Parallel Default:Normal
Button: MENU/<System Startup>/..../Output A Type/Modulating Mode
• Some modulating boilers perform better at higher modulation. For these units, it is
advantageous to run one unit at high modulation than several units at lower modulation. If the units used are of this type, select Normal. This is the recommended setting for typical steel and cast iron boilers or boilers with low turndown ratios.
• There are many condensing boilers that run more efciently at lower modulation. If it is more energy efcient to run several units at lower modulation than one at high, select
Parallel. This is typically used on condensing boilers or boilers with high turndown ratios.
• For best Parallel performance, set the Modulation Start % to be equivalent to the lowest ring rate of the boiler multiplied by 2. That is, if the lowest ring of the boiler was 20%,
set your Modulation Start% to 40%. See "Modulation Start %" on page 40.
• Set the Lag Delay to 0 for better parallel performance. See "Lag Delay" on page 33.
WARNING
Make sure that boiler modulation
wiring matches the signal selected.
Warranty will not cover failed
components caused by improper
wiring. See "Wiring the Boilers" on
page 14.
-- BOILER NUMBER --
2
[ ]
BACK SAVE
OUTPUT A TYPE --
4-20mA
0-10volt 0-5volt 2-10volt 1-5volt
BACK SAVE
- MODULATING MODE -
Normal
Parallel
BACK SAVE
M4-LHS Installation and Operation Manual
HT# 059295-00 A
23
STARTUP SETTINGS (CONTINUED)
Prove/Indirect Domestic Hot Water (DHW) Priority
Prove,DHWPriority,DHWNoPriority,NoPriority(Summer) Default:Prove
Button: MENU/<System Startup>/..../Prove-DHW Sharing
• This setting determines the functionality of input terminals 29 and 30.
• When Prove is selected, the M4-LHS will not start any boiler unless the Prove terminals are
shorted/closed. However, it will allow the System relay to operate normally.
• There are three DHW Priority options. In all the options, a DHW call will raise the calculated water temperature to the DHW Set Point (See next setting).
• The Domestic Hot Water Priority option de-energizes the System relay during domestic hot water calls for a period of one hour. If after the priority period the DHW call did not expire,
the System relay will energize providing heat to the building and the temperature target will
remain at the DHW Set Point. After the DHW call ends, the set point will drop to satisfy the
reset ratio or set point.
• Domestic Hot Water No Priority option allows the System relay to remain energized during a domestic hot water call (aquastat call on terminals 29 and 30). However, in Summer,
Shutdown, No Tstat call for heat, or when the outdoor temperature is above Outdoor Cutoff,
a DHW call will energize the System relay. After the DHW call terminates, the System relay
will continue to run for the System Run-On period before turning off.
• Domestic Hot Water No Priority (Summer) behaves the same as the DHW No Priority.
The only difference is that in Summer, Shutdown, No Tstat call for heat, or when outdoor
temperature is above Outdoor Cutoff, a DHW call WILL NOT energize the System relay except for the Run-On delay after the DHW call ends.
Indirect Domestic Hot Water Set Point
(Available with any of the DHW Priority options)
Adjustablefrom140°F/60°Cto200°F/93°C Default:180°F/82°C
Button: MENU/<System Startup>/..../Prove-Setpoint
• On a DHW call, the M4-LHS will raise the target temperature to the DHW Set Point until the DHW call expires.
PROVE/DHW SHARING
Prove
DHW Priority DHW No Priority No Priority (Summer)
BACK SAVE
- DHW SETPOINT -
[ ]
BACK SAVE
180
o
F
Shutdown/Tstat/Setback Mode
ShutdownInput,TstateInput,SetbackInput Default:ShutdownInput
Button: MENU/<System Startup>/..../Setback\Shutdown
• This menu determines the functionality of terminals 31 and 32.
• The M4-LHS has two levels of heat, a Normal/Day and a Setback/Night. The Normal/Day
is good for when buildings are occupied and people are active. The Setback/Night holds a lower system temperature for night periods or when buildings are unoccupied.
• When Shutdown or Tstat is selected, the Day/Night Schedules will be available in the operating menu. See next settings. Terminals 31 and 32 will function as a Shutdown (Turn off boilers when shorted) or as a Tstat (Turn off boilers when opened). However, a call for indirect DHW will bring the boilers on.
• When Setback is selected, the External Signal option will switch the M4-LHS to Setback
mode when terminals 31 and 32 are shorted. This allows an external device or control to provide the setback signal. No scheduling or boost menu options will be available with Setback.
- SETBCK/SHUTDOWN -
Shutdown/Disable
Tstat/Enable Setback
BACK SAVE
HT# 059295-00 A
24
M4-LHS Installation and Operation Manual
Boost Mode
(Not Available in Setback Mode)
30Minutes,Disabled Default:Disable
Button: MENU/<System Startup>/..../Boost Mode
• The morning Boost is designed to return the building to comfortable ambient temperatures after the cooler Night (Setback) period. The control will accomplish this by running elevated water temperatures (will add Setback setting to calculated water temperature) for
30 minutes before the start of the Day schedule setting. That is, if the normal day set point
at a specic outdoor was 145˚F and the Setback setting was 20˚F, the boost will raise the system calculated temperature to 165˚F for 30 minutes before the start of the Day Schedule
setting.
• If no Boost is needed, then simply select Disabled from the Boost Menu.
• Boost is only available if Shutdown or Tstat is selected as an option. See previous setting.
--- BOOST MODE ---
30 Minutes
Disable BACK SAVE
Sensor Fault
AllOff,AllOn Default:AllOn
Button: MENU/<System Startup>/..../Sensor Fault
• The Sensor Fault will determine the operating status of all output stages that has their Mode
set to Auto when a sensor reads Short or Open.
• When All-Off is selected, the control will turn all boilers Off when the System sensor reads
Short or Open. However, when the Outdoor sensor reads Short or Open, the control will try
to maintain the Minimum Water Temperature.
• When All-On is selected and the Boiler Type was set to other than Hybrid, the control will
turn all boilers On to a 100% when the System sensor reads Short or Open and the outdoor temperature is below Outdoor Cutoff. However, when the Outdoor sensor reads Short or
Open, the control will try to maintain the Maximum Water Temperature.
• When All-On is selected and the Boiler Type was set to Hybrid, the control will turn all Non-Condensing boilers On to full re when the System sensor reads Short or Open and the
outdoor temperature is below Outdoor Cutoff. During that time all Condensing boilers will
turn Off. When the Outdoor sensor reads Short or Open, the control will try to maintain the Maximum Water Temperature.
and adjustments to match the new
SETTING THE CONTROL TO FACTORY DEFAULTS
To Reset the M4-LHS control to its original factory defaults, power down the control. Hold down the two right most buttons while powering the control back up until the TOTAL CLEAR STARTED screen appears. The Display will direct you to the Startup menu to program the control after the defaults are loaded.
--- SENSOR FAULT ---
All Off
All On BACK SAVE
ALERT
A good practice after performing
any Startup menu modification
is to check all operating settings
settings.
TOTAL CLEAR STARTED
Release buttons
and
Please Wait
NOTE: When resetting the control to original factory defaults all control settings will be
overwritten and will no longer exist.
ALERT
Do not turn off power to control until all Startup settings have been made. Otherwise, the next
power-up will be set to many Startup factory settings that may not fit your application.
M4-LHS Installation and Operation Manual
HT# 059295-00 A
25
BACNET MSTP COMMUNICATION MENU
-------- SETTINGS ----
Season Winter
System Target 140 <System Settings> <Maintenance> <System Startup>
BACK SELECT
---- BACNET ID ----
o
F
477000
[ ]
BACK SAVE
When using the M4-LHS in a BACnet MS/TP network, the use of BACnet Interface Module is required. In addition, each of the Boiler Type and Sensor Type Startup menu option will offer a different list of BACnet variables. See "Boiler Type" on page 19. See "Sensor Type" on page
19. Also, see "Hybrid - Outdoor Reset - BACnet Variable list" on page 44
-- ARE YOU SURE? --
No
Yes
BACK SAVE
----MS/TP ADDRESS----
64
[ ]
BACK SAVE
BACnet Mode
Enable,Disable Default:Disable
Button: MENU/<System Startup>/.... Sensor Fault/BACnet Mode
• This menu option enables or disables the BACnet MSTP capability. When enabled,
additional BACnet settings shall be available for further customizing.
• Note that if this option was enabled while no BACnet communication is present, the BAcnet error message will supersede other messages. See "Display Messages" on page 38.
--- BACNET MODE ---
Disable
Enable
BACK SAVE
- BACNET BAUDRATE -
9600
19200
38400
BACK SAVE
--- BACNET MODE ---
Disable
Enable
BACK SAVE
BACnet Baud Rate
9600,19200,38400 Default:19200
Button: MENU/<System Startup>/.... Sensor Fault/BACnet Mode/BACnet Baudrate
• For the control to communicate over a BAcnet MS/TP network, it must use the same Baud
rate as the rest of the network. The control offers three Baud Rates.
• If communication was not successful, the baud rate could be the cause. Check with the
network administrator for the network baud rate. Then match it on the control.
MS/TP Address
1to127 Default:64
Button: MENU/<System Startup>/.... /BACnet Mode/BACnet Baudrate/ MSTP Address
• Each device on the MS/TP network must have a unique address.
• This is the MS/TP address on a RS485 network. Its MS/TP range is 1 though 127.
• The MS/TP address must be provided by the Network Administrator.
BACnet ID
1to4,000,000 Default:477,000
Button: MENU/<System Startup>/.... / MSTP Address / BACnet ID
• The BACnet ID is a unique 32 bit number that identies the control within the BACnet
network. No two ID shall be the same even if dealing across networks.
• It must be provided by the BACnet Network Administrator.
- BACNET BAUDRATE -
9600
19200
38400
BACK SAVE
----MS/TP ADDRESS----
64
[ ]
BACK SAVE
---- BACNET ID ----
477000
[ ]
BACK SAVE
HT# 059295-00 A
26
M4-LHS Installation and Operation Manual
OPERATING SETTINGS
SYSTEM
A
B
C
D
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
HYBRID CONTROL
Outdoor Temperature
Water Temperature
70 405060
130
120
110
100
Outdoor Temperature
Water Tem perature
70 405060
110
100
90
80
Outdoor Temperature
Water Tem perature
70 405060
150
140
130
120
1:4
With a 0° Offset, the Reset curves begin at 100° Water Temperature.
With a -20° Offset, the Reset curves begin at 80° Water Temperature.
With a +20° Offset, the Reset curves begin at 120° Water Temperature.
1:4
1:4 1:1
1:1
1:1
4:1
4:1
4:1
90
100
+20 Offset
-20 Offset
Program Change Switch Setting
To be able to change the M4-LHS settings, the Program/Run Switch must be set to Program.
The switch is located under the Enclosure Wiring Cover for security.
Season
Winter,Summer Default:Winter
Button: MENU/Season
• The M4-LHS will turn all boiler relays off when it is in Summer setting. However, an indirect DHW call will bring boilers back on when needed. The Message Display Line will
display Summer to show the status.
• In Winter, the M4-LHS will activate the System relay whenever the Outdoor Temperature (OD) falls below the Outdoor Cutoff setting. The Message Display Line will not show any season information when in Winter.
• When the heating season is over, it is a good practice to switch the M4-LHS to Summer setting. This will allow the control to sequence the boilers on an indirect DHW call.
Set Point
Adjustable70ºF-250ºF Default:70ºF
(Not Available for Hybrid Boiler Types)
Button: MENU/Set Point
• The Set point is the temperature value the M4-LHS will use to control the system.
• The M4-LHS will increase, decrease or hold the modulation of the boilers to maintain the
system temperature around the Set point.
• The system can be expected to uctuate around the set point. The amount of uctuation
depends on the modulation settings and stage Settings.
• If the EMS Input Mode was Enabled, the Set Point will be set by the EMS system and will
be available to be read but not changed on the display. See "EMS Input Mode" on page 19.
Reset Ratio
Adjustable1.00ºOD:4.00ºSysto4.00ºOD:1.00ºSys Default:1.00ºOD:1.00ºSys
Button: MENU/System Target
• The Reset Ratio determines how the System water temperature (SYS) will vary with Outdoor Temperature (OD). With any of the ratios, the colder it becomes outside, the hotter the temperature of the system water. See "Outdoor Reset Concept" on page 5.
• With a 1.00 (OD):4.00 (SYS) ratio, the System water temperature (SYS) will increase
rapidly as the outside temperature falls, hitting the maximum of 240°F at 24°F outside
temperature. With a 4.00 (OD):1.00 (SYS) ratio, the System water temperature (SYS) will
increase slowly as the outside temperature falls. Even at -30°F, the system water will only
be 125°F, and at 24°F outside, the system water will be 112°F. Such a low Reset Ratio might be used with radiant oor heating applications.
• With most baseboard heating applications, a 1.00 (OD):1.00 (SYS) setting is a good place to start. With a 1.00 (OD):1.00 (SYS) ratio, for every degree the outside temperature falls, the
system water temperature is increased one degree.
• If required:AdjusttheRESETRATIOincoldweather. If the ambient building temperatures are too low in cold weather, move the ratio to a higher selection. That is,
if 1.00 (OD):1.00 (SYS) was initially selected, change the selection to 1.00 (OD):1.25 (SYS). If the building temperatures are too warm in cold weather, move the ratio to a lower selection. That is, if 1.00 (OD):1.00 (SYS) was initially selected, change the selection to
1.25 (OD):1.00 (SYS).
M4-LHS Installation and Operation Manual
RUNPROGRAM
----- SEASON -----
Winter
Summer
BACK SAVE
ALERT
DO NOT turn power off to the
M4-LHS when heating season
is over. If you do so, the battery
will run down and will have to
be replaced. Instead, switch to
Summer.
----- SET POINT -----
[ ]
BACK SAVE
-- SYSTEM TARGET --
1.00oOD = 4.00oSys
1.00oOD = 3.00oSys
1.00oOD = 2.00oSys
1.00oOD = 1.50oSys
1.00oOD = 1.25oSys
1.25
o
OD = 1.00oSys
o
OD = 1.00oSys
1.00
1.50oOD = 1.00oSys
2.00oOD = 1.00oSys
3.00oOD = 1.00oSys
4.00oOD = 1.00oSys
BACK SAVE
130
120
110
Water Temperature
100
70 405060
Reset Ratio
o
0
F
1:4 1:1
Warmer
Colder
Outdoor Temperature
4:1
27
HT# 059295-00 A
HYBRID OPERATING MENU
OD= 55oF SYS=143
o
<<A>> B 67% 22%
STAGE MENU
------- SETBACK -------
o
10
F
[ ]
BACK SAVE
--- PURGE DELAY ---
1.0 min
[ ]
BACK SAVE
-- SYSTEM RUN-ON --
10 min
[ ]
BACK SAVE
-- LEAD ROTATION --
Manual
Time
Last-On
BACK SAVE
-------- SETTINGS ----
Season Winter
F
System Target 140 <System Settings>
o
F
<Maintenance>
----- SEASON -----
Winter
Summer
BACK SAVE
<System Startup>
BACK SELECT
-- SYSTEM TARGET --
1.00oOD = 4.00oSys
1.00oOD = 3.00oSys
1.00oOD = 2.00oSys
1.00oOD = 1.50oSys
----- SETTINGS 1 ----
Setback 10oF
Purge Delay 1.0min System Run-On 10min Lead Rotation Time <More Settings>
BACK SELECT
1.00oOD = 1.25oSys
1.25
o
OD = 1.00oSys
o
OD = 1.00oSys
1.00
1.50oOD = 1.00oSys
2.00oOD = 1.00oSys
3.00oOD = 1.00oSys
4.00oOD = 1.00oSys
BACK SAVE
ALERT
To be able to change the M4-LHS
settings the Program/Run Switch must
be set to Program. The switch is located
under the Enclosure Wiring Cover for
security. The Enclosure Wiring Cover
can be secured using a lock.
------- OFFSET ------
o
+0
F
[ ]
BACK SAVE
- OUTDOOR CUTOFF -
o
65
F
[ ]
BACK ▼ SAVE
MINIMUM WATER TEMP
o
70
F
[ ]
BACK SAVE
-- STANDBY TIME --
10 min
[ ]
BACK SAVE
LAST STAGE HOLD
[ ]
BACK SAVE
--- LEAD STAGES ---
Cond Lead A
Non-Cond Lead C
BACK SAVE
HT# 059295-00 A
28
5
o
F
----- SETTINGS 2 ----
Standby Time 10min
Last Stg Hold 5
o
F <Lead Stages> <Staging Settings> <Mdlating Settings> <Day/Night Schdule>
BACK SELECT
DAY/NIGHT SCHEDULE
Set Time **:**
Day Schedule 6:00a Night Schedule 8:00p
BACK SAVE
MAXIMUM WATER TEMP
200
F
o
[ ]
BACK SAVE
- STAGE SETTINGS -
Reaction Time 2min
Minimum Runtime 2min
BACK SAVE
MODULATION SETTINGS
Gain +0
Lag Delay 0min Soft-Off Delay 45sec
BACK SAVE
M4-LHS Installation and Operation Manual
MODULATING OPERATING MENU
-------- SETTINGS ----
OD= 55oF SYS=143
o
<A> B 67% 22%
STAGE MENU
------- SETBACK -------
o
10
F
[ ]
BACK SAVE
F
Season Winter
System Target 140 <System Settings> <Maintenance> <System Startup>
BACK SELECT
----- SETTINGS 1 ----
Setback 10oF
Purge Delay 1.0min System Run-On 10min Lead Rotation Time <More Settings>
BACK SELECT
----- SEASON -----
Winter
o
F
Summer
BACK SAVE
Set Point
----- SET POINT -----
o
0
F [ ]
BACK SAVE
- OUTDOOR CUTOFF -
o
65
F
[ ]
BACK SAVE
--- PURGE DELAY ---
1.0 min
[ ]
BACK SAVE
-- SYSTEM RUN-ON --
settings the Program/Run Switch must
be set to Program. The switch is located
under the Enclosure Wiring Cover for
security. The Enclosure Wiring Cover
10 min
[ ]
BACK SAVE
-- LEAD ROTATION --
Manual
Time
Last-On
BACK SAVE
Last Stg Hold 5 <Lead Stages> <Mdlating Settings> <Day/Night Schdule>
-- STANDBY TIME --
BACK SELECT
10 min
[ ]
BACK SAVE
Day Schedule 6:00a Night Schedule 8:00p
LAST STAGE HOLD
o
5
F [ ]
BACK SAVE
--- LEAD STAGES ---
Cond Lead A
Non-Cond Lead C
BACK SAVE
M4-LHS Installation and Operation Manual
BACK SAVE
Lag Delay 0min Soft-Off Delay 45sec
BACK SAVE
ALERT
To be able to change the M4-LHS
can be secured using a lock.
----- SETTINGS 2 ----
Standby Time 10min
DAY/NIGHT SCHEDULE
Set Time **:**
MODULATION SETTINGS
Gain +0
o
F
Reset
- SYSTEM TARGET --
1.00oOD = 4.00oSys
1.00oOD = 3.00oSys
1.00oOD = 2.00oSys
1.00oOD = 1.50oSys
1.00oOD = 1.25oSys
1.25
o
OD = 1.00oSys
o
OD = 1.00oSys
1.00
1.50oOD = 1.00oSys
2.00oOD = 1.00oSys
3.00oOD = 1.00oSys
4.00oOD = 1.00oSys
BACK SAVE
------- OFFSET ------
o
+0
F [ ]
BACK SAVE
- OUTDOOR CUTOFF -
o
65
F [ ]
BACK SAVE
MINIMUM WATER TEMP
o
70
F [ ]
BACK SAVE
MAXIMUM WATER TEMP
200
F
o
[ ]
BACK SAVE
29
HT# 059295-00 A
Offset
Adjustablefrom50Fº/28Cºto-50Fº/-28Cº Default:0Fº/0Cº
Button: MENU/System Target/Offset
• The Offset adjust the starting points of the Reset Ratio curve. This means that, regardless of the Outdoor Temperature (OD) or the Reset Ratio that has been selected, when the
Offset setting is changed, that change is directly added to or subtracted from the calculated temperature. For example, if the Set Point was 130°F and the Offset was changed from 0F°
to 10F° (an increase of 10F°), then the Set Point temperature would increase to 140°F.
• The Offset setting does not change the ratio selection. What the Offset does is add or subtract a constant temperature value. See "Outdoor Reset Concept" on page 5.
• If required: AdjusttheWaterOffsetinmildweather. If the ambient building
temperatures are too warm in mild weather, decrease the offset. If the ambient building
temperatures are too cold in mild weather, increase the Water Offset.
• The rule of thumb for baseboard radiation is to change the offset 4°F for every 1°F you wish
to change the building temperature. In radiant heat applications, change the offset 1F° or 2F° for every 1F° you wish to change the building temperature.
Outdoor Cutoff Temperature
Adjustable:Off,from20ºF/70ºC-100ºF/38ºC,On Default:65ºF/18ºC
Button: MENU/System Target/Offset/Outdoor Cutoff
• The control will turn heating off if the outside temperature rises above the Outdoor Cutoff. This setting shall not affect any indirect DHW requirement.
• The Outdoor Cutoff screen will automatically appear after setting the Offset.
• When the outdoor temperature falls to the adjustable Outdoor Cutoff temperature, the
M4-LHS will operate the boilers to hold the calculated temperature.
• When the outdoor temperature rises to the Outdoor Cutoff plus a 2°F differential, the
M4-LHS will turn all boilers off. The System relay will remain energized for the Run-On delay then de-energize.
• The Outdoor Cutoff can be set from 20°F to 100°F. In addition, it can be set to ON or OFF. In the ON position, the System Relay will run regardless of the Outdoor Temperature (OD) and the burner stages will be active to hold the calculated water temperature. (Note: The
lowest water temperature the M4-LHS will circulate is 70°F. If the Outdoor Cutoff is turned
ON and the Season is set to Winter, the M4-LHS will circulate at least 70°F water even in the hottest of weather.) In the OFF position, the system pump will always be off and all
burner stages will be off.
------- OFFSET ------
o
+0
F
[ ]
BACK SAVE
Offset=10°F
Reset Ratio=1.5 : 1.0
180
170
160
150
140
130
120
Water Temperature (in °F)
110
100
Reset Ratio + 10F Offset
Min Target
70 60 50 40 2030 0 -1010 -20
Outdoor Temperature (in °F)
Max Target
Reset Ratio
Min Target=120°F
Max Target=170°F
Target Offset
- OUTDOOR CUTOFF -
[ ]
BACK SAVE
65
o
F
Minimum Water Temp
Adjustablefrom50ºF/10ºCto180ºF/82ºC HybridDefault:70ºF/21ºC   ModulationDefault:120ºF/49ºC
Button: MENU/System Target/Offset/Outdoor Cutoff/Minimum Water Temp
• The Minimum Water Temperature must be set to the boiler manufacturer’s specication.
The M4-LHS will calculate the Set Point based on the Outdoor Temperature (OD), the Reset Ratio, and the Offset value. The M4-LHS will control all boilers to hold either the Set Point
temperature, or the Minimum Water Temperature, whichever is higher.
• The Minimum Water Temperature must be at least 20°F lower than the Maximum Temperature (See next setting).
Maximum Water Temp
Adjustable70ºF/21ºC-220ºF/104ºC Default:200ºF/93ºC
Button: MENU/System Target/Offset/..../Maximum Water Temperature
• This is the highest temperature heating water the M4-LHS will circulate through the heating system.
• When using a radiation system, it should be set according to the tubing or oor manufacturer’s specication.
• The Maximum Temperature must be at least 20°F higher than the Minimum Temperature (See previous setting).
HT# 059295-00 A
30
M4-LHS Installation and Operation Manual
MINIMUM WATER TEMP
o
70
F
[ ]
BACK SAVE
MAXIMUM WATER TEMP
200
F
o
[ ]
BACK SAVE
SYSTEM SETTINGS
SYSTEM
A
B
C
D
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
HYBRID CONTROL
Button: MENU/<System Settings>
Settings 1 and Settings 2 menus provide access to adjusting and ne-tuning the system for
enhanced comfort and better fuel savings. The M4-LHS behaves differently based on the selected modes. See "Startup Settings" on page 19.
ALERT
To be able to change the M4-LHS settings the Program/Run Switch must be
set to Program. The switch is located under the Enclosure Wiring Cover for
security. The Enclosure Wiring Cover can be secured using a lock.
Setback
Adjustablefrom0F°/0C°to75F°/42C° Default:10F°/6C°
Button: MENU/<System Settings>/Setback
• The Setback feature can be used to provide the M4-LHS with a lower temperature Set Point
when less load is required.
• The lower Set Point will appear on the main display indicating this condition.
• For example, if the calculated temperature is 180°F and the Setback is 20°F, then when in
Setback or Night Schedule, the M4-LHS will hold a Set Point of 160°F = 180°F- 20°F. See "Day - Night Schedule" on page 36.
• A typical use for the Setback is to provide less system temperature to a building during
the Night Schedule or on the weekends when people are asleep or when the building is not occupied, but heat is still needed.
• The amount of Setback selected is subtracted from the Set Point when a Setback Input
Signal is received or the Night Time schedule setting started.
• If Setback is selected as the Shutdown/Tstat/Setback Mode (See "Shutdown/Tstat/Setback Mode" on page 24.), the Setback will not be activated unless a Short dry-contact signal is received on terminals (31 and 32).
• If Shutdown or Tstat is selected as the Shutdown/Tstat/Setback Mode (See "Shutdown/Tstat/ Setback Mode" on page 24.), the Setback will be activated only during the Night Schedule.
----- SETTINGS 1 ----
Setback 0oF
Purge Delay 1.0min System Run-On 0min Lead Rotation Time <More Settings>
BACK SELECT
----- SETTINGS 2 ----
Standby Time 10min
Last Stg Hold 0 <Lead Stages> <Staging Settings> <Mdlating Settings> <Day/Night Schdule>
BACK SELECT
------- SETBACK -------
[ ]
BACK SAVE
10
o
F
o
F
RUNPROGRAM
ALERT
When using Soft-Off and Last
Stage Hold, the last boiler stage will
not turn off until both parameters
have elapsed. In this case, Soft-Off
will start after the Last Stage Hold.
Purge Delay
Adjustablefrom0.0minto10.0min Default:1.0min
Button: MENU/<System Settings>/Purge Delay
• Many boilers go through a purge cycle before they are brought on line. When the M4-LHS
activates a boiler, it does not start to calculate its output until the Purge Delay is over. This allows the boiler to fully come online and begin producing.
• The Purge Delay helps prevent short cycling of any newly activated burner. Once the
burner is activated, it MUST run through the entire Purge Delay period.
• The minimum Purge Delay setting MUST be set to the time required by the boiler manufacturer. Time entry is in 0.1 of a minute (i.e. 1.5 minute will equal 90 seconds.)
• The Message Display Line will display Purge Delay and the remaining time.
System Run-On
Adjustablefrom0minto360min Default:10min
Button: MENU/<System Settings>/System run-On
• A common use for the System Run-On is to control a system pump in a heating system.
The extra time helps transfer the boiler residual heat to the heating system.
• The System relay will energize whenever the outdoor temperature is below the Outdoor Cutoff and the Shutdown is Open or the Tstat is closed. When the Outdoor Temperature
rises 2°F above the Outdoor Cutoff or the control is switched to Summer and after the last burner relay has de-energized, the System relay will remain energized for the System Run­On period.
M4-LHS Installation and Operation Manual
--- PURGE DELAY ---
1.0 min
[ ]
BACK SAVE
ALERT
Set Purge Delay as per boiler
manufacturer recommendation.
-- SYSTEM RUN-ON --
10 min
[ ]
BACK SAVE
HT# 059295-00 A
31
• The System Run-On time should be set based on the size and type of the boilers and
pumps used. In general, when setting the System Run-On consult the boiler and pump manufacturers for the best setting.
• When the System relay is in the Run-On period, the Message Display Line will indicate that
status and the remaining time.
Lead Boiler Rotation
AdjustableManual,Time(1hrto60Days),Last-On Default:Time(24Hours)
Button: MENU/<System Settings>/Lead Rotation
• The Lead Boiler is the rst boiler brought on when an output is needed.
• The Lead Boiler can be rotated automatically every specied time period, manually, or
based on Last-On. Time rotation is recommended.
• The Lead Group Lead Boiler is shown in bracket layers on the main display. The Lag Group lead Boiler is shown in a single bracket. See "Boiler Status" on page 38.
• Only boilers which are set to Auto Mode can be Lead. Therefore, not all the boilers may be
available when manually selecting a new Lead Boiler.
Standby Time
Adjustablefrom1minto60min Default:10min
Button: MENU/<System Settings>/<More Settings>/Standby Time
• Standby boilers are used for backup or extreme load conditions only. A Standby boiler can
never be a Lead Boiler.
• The Standby Time only applies to boilers set to Standby.
• A boiler can be set to be a Standby boiler using the Stage Menu. See "Mode" on page 39.
• A Standby boiler can only be activated after all the boilers in Auto Mode have run at 100%
modulation for the full Standby Time.
• The full Standby Time must always elapse regardless of what happens to the system
temperature. Therefore, shorter Standby Times will result in smoother set point operation in extreme conditions. On the other hand, longer Standby Times may prevent a Standby boiler
from ring if the other boilers can eventually meet the load, or if the load decreases.
-- LEAD ROTATION --
Manual
Time
Last-On
BACK SAVE
-- LEAD ROTATION --
24hrs
[ ]
BACK SAVE
-- STANDBY TIME --
10 min
[ ]
BACK SAVE
Last Stage Hold
Adjustablefrom0F°/0C°to30F°/17C° Default:5F°/3C°
Button: MENU/<System Settings>/<More Settings>/Last Stg Hold
• The Last Stage Hold prevents short cycling of the Lead Stage during low demand periods.
• In these conditions, the system might require less output than the lowest lead Stage. When
the M4-LHS brings on the Lead Stage, the Set Point is quickly exceeded, and the M4-LHS turns the Lead Stage off.
• To prolong the run time during this type of condition, use the Last Stage Hold setting to let
the system temperature exceed the Set Point by the number of degrees selected.
• For example, with a Set Point of 160°F and a Last Stage Hold setting of 10°F, the Lead Stage boiler will de-energize after the Set Point exceeds 170°F (160°F + 10°F).
• In many cases, it is better to overshoot slightly than to short cycle a boiler.
• When Soft-Off is set to other than 0 seconds, the Lead Boiler will need to remain at or
exceed the Last Stage Hold for the Soft-Off period before turning off.
Lead Stages
CondensingLead,Non-CondensingLead Default:1stboilerintheGroup
Button: MENU/<System Settings>/<More Settings>/Lead Stages
• In addition to having a lead group, each group of boilers, Condensing Group and
Non-Condensing Group, will have its own lead boiler that can be selected from this menu.
• After assigning the lead boiler for each group, the lead will rotate based on the Lead
Rotation option selected. See "Lead Boiler Rotation" on page 32.
• The Lead Group Lead Boiler can be identied by the two brackets <<A>>.
• The Lag Group Lead Boiler can be identied by the one bracket <C>.
LAST STAGE HOLD
[ ]
BACK SAVE
--- LEAD STAGES ---
Cond Lead A
Non-Cond Lead C
BACK SAVE
5
o
F
HT# 059295-00 A
32
M4-LHS Installation and Operation Manual
MODULATING BOILER OPERATING SETTINGS
Gain
Adjustablefrom-10to+10 Default:0
Button: MENU/<System Settings>/<More Settings>/<Modulating Settings>/Gain
• The Gain adjusts the aggressiveness of the modulating PID logic. It controls how much
modulation is changed when the system temperature is different from the Set Point.
• A Gain of 0 is a good starting point for all systems.
• If during normal load conditions, the system temperature tends to oscillate signicantly, decrease the Gain by two numbers (for example, from 0 to -2). Wait for at least 15 minutes
before evaluating how the change has affected the system.
• If during normal load conditions the system temperature tends to remain consistently below the Set Point (or consistently above the Set Point), increase the Gain by two numbers (for example, from 0 to 2). Wait for at least 15 minutes before evaluating how the change has
affected the system.
Lag Delay
Adjustablefrom0minto60min Default:0min
Button: MENU/<System Settings>/<More Settings>/<Modulating Settings>/Lag Delay
• The Lag Delay requires the lead stage to remain at 100% modulation for the full period of
the Lag Delay before the lag stage can be activated. For example, if the Lag Delay was set to 10 minutes, the Lead Stage must remain at 100% modulation for the full ten minutes before the lag stage could be activated. The Message Display Line will display Lag Delay and the remaining time.
• The Lag Delay is useful in installations where one unit should usually have enough output
to hold the load unless it fails or load conditions become extreme.
• The Lag Delay overrides the Modulation Start % selected for each stage. Regardless of
that setting, the previous stage must reach and stay at 100% before the lag stage can be activated.
• The full Lag Delay must elapse regardless of what happens to the system temperature.
Therefore, set the Lag Delay to 0 minutes to achieve smooth operation.
• Note that if Parallel was selected as the Modulation Mode (See "Modulating Logic Overview" on page 4), this value must be set to 0 minutes to avoid having the lead boiler going to 100% modulation prior to ring the lag boiler.
MODULATION SETTINGS
Gain +0
Lag Delay 0min Soft-Off Delay 45sec
BACK SAVE
------ GAIN ------
+0
[ ]
BACK SAVE
---- LAG DELAY ----
0 min
[ ]
BACK SAVE
Soft-Off Delay
Adjustablefrom0secto60sec Default:10sec
Button: MENU/<System Settings>/<More Settings>/<Modulating Settings>/Soft-Off Delay
• When a boiler is no longer needed, the Soft-Off keeps that boiler in Low Fire prior to
turning it off.
• The display will show a percent that is equal to the Ignition % for the stage in Soft-Off
delay. That number will blink for the Soft-Off delay period.
• If during the Soft-Off delay period the M4-LHS needed that stage to turn back on, the stage
will be released from the Soft-Off delay and resume normal operation.
• On a Shutdown initiation or Tstat termination any stage that was On will go into Soft-Off
delay before fully turning off.
ALERT
When using Soft-Off and Last Stage Hold, the last boiler will not turn off until both
parameters have elapsed. In this case, Soft-Off will start after the Last Stage Hold.
M4-LHS Installation and Operation Manual
-- SOFT-OFF DELAY --
10 sec
[ ]
BACK SAVE
HT# 059295-00 A
33
STAGING BOILER OPERATING SETTINGS
Reaction Time
Adjustablefrom1to10minutes Default:2minutes
Button: MENU/<System Settings>/<More Settings>/<Stage Settings>/Reaction Time
• It is the amount of time it takes a single stage to affect the system.
• After the control turns on a stage trying to meet the set point, it will not turn on another
stage until the Reaction Time has elapsed.
• To determine the optimum time, start with a hot system. Then, turn on a single stage and
calculate how long it takes until the system temperature begins to respond to that stage. That period should be set as the Reaction Time.
Minimum Runtime
Adjustablefrom1to60minutes Default:2minutes
Button: MENU/<System Settings>/<More Settings>/<Stage Settings>/Min Runtime
• This is the minimum amount of time any stage will run.
• For the lowest stage of a unit, the Minimum Runtime starts after the purge cycle.
• The Runtime does not apply to the last stage online. The Last Stage Hold applies in that
case.
• Initially, set the Minimum Runtime to half the Reaction Time.
• If the system tends to overshoot, reduce the Minimum Runtime. However, if boilers tend to
short cycle, increase the Minimum Runtime.
Avoiding Conicting Boiler Limits
The temperature limits set on the boilers MUST be set considerably higher than the M4-LHS's Set Point for the reasons detailed below.
• The M4-LHS sensor is located in a common header some distance from the boilers.
• As the temperature rises in the header and before reaching the sensor location, energy is
dissipated. Therefore, the temperature in the header could be lower than that registered by boiler sensors.
• In addition to the normal drop experienced between the boiler’s temperature and that
read by the M4-LHS sensor, the Last Stage Hold setting must be accounted for. The boiler
limit must be set above the Set Point PLUS the Last Stage Hold PLUS the normal drop
experienced in the piping.
• Using the previous example of a 10°F Last Stage Hold with a 160°F Set Point, the boilers’
limits must be set enough over 170°F to prevent the boilers’ internal limits being reached.
In this situation, the boiler high limit should be set higher than 180°F to prevent erratic
operation.
- STAGE SETTINGS -
Reaction Time 2min
Minimum Runtime 2min
BACK SAVE
-- REACTION TIME --
2 min
[ ]
BACK SAVE
- MINIMUM RUNTIME -
2 min
[ ]
BACK SAVE
WARNING
The temperature limits set on the
boilers must be higher than the M4-LHS Max Water Temp. Read the left section for details that will prevent erratic system operation.
HT# 059295-00 A
34
M4-LHS Installation and Operation Manual
Avoiding Conicting Boiler Limits
The temperature limits set on the boilers MUST be set considerably higher than the M4-LHS's Set Point for the reasons detailed below.
• The M4-LHS sensor is located in a common header some distance from the boilers.
• As the temperature rises in the header and before reaching the sensor location, energy is
dissipated. Therefore, the temperature in the header could be lower than that registered by boiler sensors.
• In addition to the normal drop experienced between the boiler’s temperature and that
read by the M4-LHS sensor, the Last Stage Hold setting must be accounted for. The boiler
limit must be set above the Set Point PLUS the Last Stage Hold PLUS the normal drop
experienced in the piping.
• Using the previous example of a 10°F Last Stage Hold with a 160°F Set Point, the boilers’
limits must be set enough over 170°F to prevent the boilers’ internal limits being reached.
In this situation, the boiler high limit should be set higher than 180°F to prevent erratic
operation.
WARNING
The temperature limits set on the
boilers must be higher than the M4-LHS Max Water Temp. Read the left section for details that will prevent erratic system operation.
M4-LHS Installation and Operation Manual
HT# 059295-00 A
35
DAY - NIGHT SCHEDULE
SYSTEM
A
B
C
D
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
HYBRID CONTROL
(Available when "Shutdown or Tstat" is selected from the Shutdown/Tstat/ Setback Startup menu option only)
Button: MENU/<System Settings>/<More Settings>/Day/Night Schedule
• The M4-LHS has two levels of heat. The Day (Normal) level is used when a building is
occupied and people are active.
• The Night (Setback) level is used when a building is not occupied, or when people are
sleeping. This setting reduces the calculated temperature by the Setback setting. See
"Setback" on page 31. If the Day calculated water temperature was 150˚F and the Setback was 20˚F, the Night Schedule will run at (150˚F - 20˚F) = 130˚F.
• If the Boost feature is being used, it uses the Day Schedule as the Boost ending point. See "Boost Mode" on page 25. That is, if the Day Schedule is set to start at 6:00AM, the Boost will start 30 minutes prior to the Day setting at 5:30AM. The M4-LHS will then raise the calculated water temperature by the Setback amount. Using the previous example, at 5:30AM the M4-LHS will raise the calculated water to 170˚F = (150˚F + 20˚F) until 6:00AM.
DAY/NIGHT SCHEDULE
Set Time **:**
Day Schedule 6:00a Night Schedule 8:00p
BACK SAVE
-- DAY SCHEDULE --
6:00 Am
BACK SAVE
Set Time
Button: MENU/<System Settings>/<More Settings>/Set Time
• Adjust the time by selecting Set Time from the menu and then scrolling through the hours
then select Save. If the hours are to be set to PM, scroll through the AM hours to reach the PM hours. Then, scroll through the minutes then select Save.
ALERT
Remember that the battery is the backup for the Time. If no power is supplied to the M4-LHS and
there was no battery or the battery had no power, time values will be lost and will need to be reset.
MAINTENANCE
Button: MENU/<Maintenance>
The Maintenance menu gives access to sensor and modulating output trimming. In addition,
you'll have access to view the Startup conguration settings.
ALERT
To be able to change the M4-LHS settings the Program/Run Switch must be
set to Program. The switch is located under the Enclosure Wiring Cover for
security. The Enclosure Wiring Cover can be secured using a lock.
System & Outdoor Sensor Trim
Adjustablefrom-5F°/-3C°to+5F°/+3C° Default:0°F
Button: MENU/<Maintenance>/System Trim Button: MENU/<Maintenance>/Outdoor Trim
• The Laars thermistor type sensors are very accurate, and normally require no calibration.
Sometimes it may be desirable to make small adjustments to the displayed value for either
the Outdoor Temperature (OD) or the System Temperature (SYS). The Trim setting is used
to adjust the displayed value.
• Do not use the Trim setting to make the Outdoor Temperature sensor match that reported
on the radio or TV. Outdoor Temperature can vary widely over a broadcast range. Only trim the outdoor sensor based on an accurate thermometer reading taken where the sensor is located.
----- SET TIME -----
7:35 Pm
BACK SAVE
----- MAINTENANCE ----
System Trim +0oF
Outdoor Trim 0 <Output Trim> <Configuration>
BACK SAVE
SYSTEM SENSOR TRIM
[ ]
BACK SAVE
OUTDOOR SENSOR TRIM
[ ]
BACK SAVE
+0
+0
o
F
o
F
o
F
RUNPROGRAM
HT# 059295-00 A
36
M4-LHS Installation and Operation Manual
Output Modulation Trim
(Available for modulating boilers only)
Adjustablefrom-1.0to+1.0 Default:0.0
Button: MENU/<Maintenance>/Output Trim
• Each of the modulating stages controlled has a separate Output Trim setting.
• Output Trim acts as an adjustment to a stage output percent to match the burner motor.
• After adjusting the Output Trim, test the operation to make sure the results match your
expectation.
ALERT
DO NOT use the Output Trim for a Stage unless it is absolutely necessary. Test
burner operation and modulation output matching after adjusting the Output Trim.
-- STAGE A TRIM ---
Output Trim +0.0
<Prev Stage> <Next Stage>
BACK SAVE
Conguration
Button: MENU/<Maintenance>/<Conguration>
• This menu option provides a consolidated view of the M4-LHS's Startup and Stage settings.
Outdoor and System Temperature
OD= 55oF SYS=143
Prepurge Delay 15 <<A>> B 67% 20%
STAGE MENU
o
F
Messages
Boilers and Their Status
}
Button Functions
Buttons
v1.00, ResetoF Outdoor, Non-HeavyLoad Switch:35F,5F,0.5Hr c:mod, 2,Normal nc:mod, 2,Normal Shutdown/Disable
BACK NEXT
PROVE Bst:30, All On 4-20, 4-20, BAC=Enable, 19200,2
BACK EXIT
DISPLAY
The M4-LHS display layout provides a variety of information that gives an immediate picture of the operation status. The display
shows two boilers at a time. When extensions are present, the two middle buttons (◄ ►) scroll the screen to view additional boilers.
Moreover, all the information displayed can be viewed in brightly or dimly lit rooms.
• The buttons' functionality changes based on the screen and menu level. The buttons' functionality is displayed on a dark
background on the screen bottom line.
• (◄ ►) Horizontal arrows are to scroll through the available stages.
• (▲ ▼) Vertical arrows are to scroll through the menu functions when in menus or to change settings when in a setting screen.
• The Top line displays the Outdoor and System sensor values.
• The second line displays all messages pertaining to the operation or status. See "Display Messages" on the next page.
• The third line will list the boiler stages. Additional stages can be scrolled to using the two middle buttons. The lead boiler letter
will be bracketed. See "Lead Boiler Rotation" on page 32. The lead boiler in the lead group will have two sets of brackets.
• The fourth line lists each boiler modulation or sequencing status. See "Boiler Status" on the next page.
M4-LHS Installation and Operation Manual
HT# 059295-00 A
37
BOILER STATUS
The M4-LHS boiler status gives immediate access to each boiler stages or modulation.
• --- Boiler is off due to no call for heat.
• <<A>> A is the lead boiler in the lead Hybrid group. See "Lead Stages" on page 32.
• <C> C is the lead boiler in the lag Hybrid group or the lead boiler in Modulating Boiler Type. See "Lead Stages" on page 32.
• C/E Extension panel is NOT communicating back to the M4-LHS. See "Connecting to the Extensions and 4-20mA EMS Interface" on page 15.
• mON All boiler stages are set to ON.
• mOFF All boiler stages are set to OFF.
Display Modulating Boiler Status
• 97% Boiler is modulating at the indicated percentage.
• m95% Boiler Stage Mode is set to Manual Modulation to the specied percent. See "Mode" on page 39.
• h50% Boiler is in post purge for 30 seconds.
DISPLAY MESSAGES
The M4-LHS display layout reserved the second line for message indications. The following is a list of the most common Message
Display Line information:
• Boost To 170˚F The Boost has started 30 minutes before the Day Schedule setting and the Boost temperature is 170˚F.
See "Boost Mode" on page 25.
• DHW Call (180˚F) There is an indirect DHW call. The M4-LHS will raise the system Set Point to the indicated temperature.
DHW increases calculated temperature to the DHW Set Point. See "Indirect Domestic Hot Water Set
Point" on page 24.
• Holding Until 150˚F The Lead boiler is in Last Stage Hold. This example shows that the lead stage will turn off when system
temperature reaches 150˚F. See "Last Stage Hold" on page 32.
• Interface Module Error There is no communication to the BACnet Module Interface while the BACnet Mode is set to Enable.
See "BACnet Mode" on page 26.
• Lag Delay: 123 The lead boiler is at 100% and the remaining purge time to start the lag boiler in seconds is 123. See "Lag
Delay" on page 33.
• Outdoor Cutoff The outdoor temperature is above the Outdoor Cutoff setting. No boilers will be active for heating. See
"Outdoor Cutoff Temperature" on page 30.
• Prove Failure After boilers have run for some time, Prove signal has ended. All boilers set to Auto or Standby will
de-energize. However, the System relay will remain energized. See "Prove/Indirect Domestic Hot Water (DHW) Priority" on page 24 and "Wiring the Prove" on page 13.
• Purge Delay: 23 A boiler is in purge cycle and the remaining purge time in seconds is 23. See "Purge Delay" on page 31.
• Setback to: 130˚F The Night Schedule or Setback input is active. Current Setback temperature is 130˚F. See "Setback"
on page 31. See "Day - Night Schedule" on page 36.
• Shutdown Active The Shutdown Terminals are Shorted. No boilers will be active. See "Shutdown/Tstat/Setback Mode" on
page 24. Also See "Wiring the Shutdown, Tstat, or Setback" on page 12.
• Summer The control is set to Summer. No heat is active. See "Season" on page 27.
• Switch in: 00:30 The switch from one group to the other will take place after 30 minutes. See "Switch Delay" on page 21.
• System Run-On: 46 The System relay is ON for the System Run-On Delay. This example shows that it will remain in System
Run-On for an additional 46 seconds before turning off. See "System Run-On" on page 31.
• Tstat Call The Tstat Terminals are Shorted. Boilers will be active. See "Shutdown/Tstat/Setback Mode" on page 24.
• Waiting for Prove The System relay is ON and the prove terminals are open before the lead boiler relay can energize. See
"Prove/Indirect Domestic Hot Water (DHW) Priority" on page 24.
BOILER STAGE MENU
HT# 059295-00 A
38
M4-LHS Installation and Operation Manual
Staging Modulation
SYSTEM
A
B
C
D
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
HYBRID CONTROL
STAGE A SETTINGS
Mode Auto
<Prev Stage> <Next Stage>
BACK ▼ SELECT
STAGE A MODE
Auto
Standby Manual Off On
BACK SAVE
OD= 55oF SYS=143
<<A>> B 67% 20%
STAGE MENU
STAGE A SETTINGS
Mode Auto
Ignition % 1% Mod Start % 80% <Prev Stage> <Next Stage> Copy Settings
BACK ▼ SELECT
o
F
STAGE A
- IGNITION POINT -
1%
[ ]
BACK SAVE
STAGE A
MODULATION START
75%
[ ]
BACK SAVE
Button: STAGE/
The Stage menu provides adjustment for each of the individually boiler operations.
• In most installations, all active boiler adjustments are the same, but each can be congured
differently if desired.
• If the boilers are not set up properly, the M4-LHS operation may appear to be erratic.
• When the STAGE button is depressed, the Boiler A settings menu will be shown.
• Make all the appropriate settings for Boiler A (See below).
• After completing all the settings for Boiler A (See below), you have the option of copying
these settings to all other modulating boilers. Everything but the Mode -- Auto/Standby/ Manual/Off/On -- will be copied.
• Then select the <Next Stage> option from the menu to reach the Boiler B settings
menu. Continue until all boilers have been set.
• If an Extension is connected to the M4-LHS and the stages have been set through the
Startup menu, then scrolling through stages using the <Next Stage> and <Prev Stage> menu options will scroll through the Extension stages as well.
ALERT
To change the M4-LHS settings, the Program/Run Switch must be set to
Program. The switch is located under the Enclosure Wiring Cover for security.
The Enclosure Wiring Cover can be secured using a lock.
Mode
Auto,Standby,Manual,Off,On Default:Auto
Button: STAGE/Mode
• The M4-LHS only controls the modulation of boilers set to Auto or (after a delay) those
set to Standby. None of the other settings is recommended for outputs connected to active boilers.
• Any stage without an active boiler or stage connected must be set to Off.
• The following list describes the MODE options:
Modulating Boiler Stage Menu
STAGE A SETTINGS
Mode Auto
Ignition % 1% Mod Start % 80% <Prev Stage> <Next Stage> Copy Settings
BACK ▼ SELECT
Sequencing Boiler Stage Menu
STAGE A SETTINGS
Mode Auto
<Prev Stage> <Next Stage>
BACK ▼ SELECT
RUNPROGRAM
STAGE A MODE
Auto
Standby Manual Off On
BACK SAVE
M4-LHS Installation and Operation Manual
HT# 059295-00 A
39
Auto The M4-LHS will control the boiler’s operation to maintain the desired Set Point. Only boilers set to Auto can be Lead
boilers.
Standby Standby boilers can only be activated when all boilers in Auto have been at 100% modulation or at High re for the full
Standby Time. Standby is generally used when you want a specic boiler to be available in extreme load conditions. Note
that a Standby boiler Cannot be a Lead boiler.
Manual Available For modulating boilers only. The Manual Mode should only be used when testing a boiler. Manual overrides the
Prove input. For modulating boilers, the exact percent of modulation for a boiler can be set with the Manual mode. Once
selected, the unit will immediately turn on and modulate to the selected percentage. See "Boiler Status" on page 38.
Off Any stage output not connected to a physical stage should be set to Off. The Off Mode can also be used to disable units
that are being serviced.
On This mode should only be used when testing a boiler. This mode overrides the PROVE input, Season setting, Shutdown or
Tstat status, and Sensor Fault status. Once set to On the boiler will immediately start ring at its highest rate.
Ignition %
(Modulating Boilers Only)
0-10VDCAdjustablefrom1%to50% Default:1% 1-10VDCCustomAdjustablefrom5%to70% Default:25%
Button: STAGE/Ignition %
• The Ignition % of a boiler is the lowest percent of modulation that boiler can achieve. That
is for the 4-20mA and 0-10VDC if the Ignition % was set to 20%, the 0-10VDC terminals will output 2VDC. The 4-20mA terminals will output 7.2mA.
• The 1-10V custom boiler types will use the Ignition % when the boiler is activated. In this
case, the Ignition % will be the level at which the control will output 1VDC.
• During the Soft-Off Delay, the boiler will remain at the Ignition % before turning Off.
- IGNITION POINT -
[ ]
BACK SAVE
Modulation Start %
(Modulating Boilers Only)
Adjustablefrom0%to100% Default:75%
Button: STAGE/Mod Start %
• The Modulation Start determines at what modulation percent the previous boiler (lead boiler) should be for the lag boiler to be activated.
• For example, if the Modulation Start for Boiler B is set to 50%, then when Boiler A reaches 75% modulation (50% Mod Start % + 25% Ignition % = 75%), Boiler B will be brought on.
• When modulation is decreasing, the lag unit will remain on at the Ignition % modulation until the previous boiler reaches 40% of
lag boiler's Modulation Start, or 2% above the Ignition Point, whichever is higher.
• Using the same example, as the load decreases, Boiler B will modulate down to its Ignition %. Boiler A will then modulate down to 30% (75% x 40%). Only then will Boiler B turn off.
• If the Lag Delay is set to anything other than 0, the lead boiler must reach 100% modulation before the lag boiler is activated.
However, the Modulation Start % should still be set correctly, because it will be valid when modulation is decreasing. "Lag Delay" on page 33
Laars suggests that when Parallel is selected as the Modulation Mode to set the Modulation percent equal to or slightly higher than double the Ignition %. This way, the lag boiler will only start if the load is large enough for two boilers to run at the lowest modulation. See "Modulating Logic Overview" on page 4.
[ ]
BACK SAVE
STAGE A
25%
STAGE A
MODULATION START
75%
Copy Settings - Boiler A Only
(Modulating Boilers Only)
Button: STAGE/Copy Settings
• If all the active modulating boilers are to be set to the same Ignition % and Modulation %,
they can be set for Boiler A and then copied to the other modulating boilers.
• It is still required to select the Mode for all other boilers as the Mode is NOT copied.
ALERT
The Mode MUST be set for each boiler. The Copy Settings command will not set the
Mode for the remaining boilers. Only Ignition % and Modulation Start % are copied.
HT# 059295-00 A
40
M4-LHS Installation and Operation Manual
-- COPY SETTINGS -­From Stage A to
all other stages
BACK COPY
TROUBLESHOOTING
SENSOR INPUTS
Display shows Sensor OPEN or SHORT
When the display shows sensor OPEN, short the control sensor input terminals. The display
should change to read SHORT. This indicates that the sensor wires are not continuous. If the display does not SHORT, the M4-LHS may be damaged.
When the display shows sensor SHORT, remove the wires from the sensor terminals. The
display should change to read OPEN. In this case, replace the sensor. Otherwise, if the display does not show OPEN, the M4-LHS may be damaged.
Display shows an Incorrect Temperature
Remove the wires from the sensor terminals. The display should change to read OPEN. If it
does not, the M4-LHS may be damaged. Take an ohm reading across the detached sensor wires. The ohm reading should correspond to the Temperature Sensor Chart. If it does not, the sensor may be damaged.
CONTROL OPERATION
No Heat
• Season- Make sure that the Season is set to Winter. See "Season" on page 27 and "Display Messages" on page 38.
• Prove- Even though, the system relay may be energized, the M4-LHS will not energize and
stage relays unless the Prove is shorted. See "Display Messages" on page 38 and "Wiring the
Prove" on page 13.
• Shutdown- The M4-LHS will deactivate stage outputs when the Shutdown terminals are
shorted. See "Display Messages" on page 38 and "Wiring the Shutdown, Tstat, or Setback" on
page 12.
• Tstat- The M4-LHS will deactivate stage outputs when the Tstat terminals are open. See
"Display Messages" on page 38 and "Wiring the Shutdown, Tstat, or Setback" on page 12.
• SensorFault- When the Sensor Fault is set to All Off in the startup menu, the System sensor fault (in all Sensor Type modes) or the Outdoor sensor fault (in Reset mode) will de-energize all stage relays. See "Display Messages" on page 38 and "Sensor Fault" on page 25.
• SystemorOutdoorSensor- If the System or Outdoor sensor reading was higher that the actual temperature, the M4-LHS might not bring any stage on. Check "Display shows an Incorrect Temperature" section.
• OutdoorCutoff- If the Outdoor cutoff was set too low, the building might be allowed to
cool more than is desired. A comfortable setting is between 60°F to 65°F. "Outdoor Cutoff
Temperature" on page 30
Too Much Heat
• IndirectDomesticHotWatercall- The M4-LHS will raise the temperature of the system to the
DHW Set Point on a DHW call, connected to terminals 29 and 30. Check to see if there is a call for DHW and the length of time it lasts.
• ResetRatioandOffset- If excessive heat occurs only in certain weather conditions, adjust the
Reset Ratio and Offset. See "Outdoor Reset Concept" on page 5. If excessive heat occurs year
round, reduce the Offset.
• BoilerModeSettings- The M4-LHS will only controls boilers their mode is set to Auto or Standby. Check if any boiler stage is set to Manual or On. See "Mode" on page 39.
• ControlSettings- The Last Stage Hold will allow only the Lead boiler to stay on for an additional number of degrees. If the setting is too high, and only the Lead boiler is on, the system can over heat. Reduce the Last Stage Hold setting. See"Last Stage Hold" on page 32.
Temperature Sensor Chart
TEMPERATURE
°F °C
OPEN 150000
-30 -34 117720
-20 -29 82823
-10 -23 59076
0 -18 42683
10 -12 31215
20 -7 23089
25 -4 19939
30 -1 17264
35 2 14985
40 4 13040
45 7 11374
50 10 9944
55 13 8714
60 16 7653
70 21 5941
80 27 4649
90 32 3667
100 38 2914
110 43 2332
120 49 1879
130 54 1524
140 60 1243
150 66 1021
160 71 842
170 77 699
180 82 583
190 88 489
200 93 412
210 99 349
220 104 297
230 110 253
240 116 217
250 121 187
SHORT 100
Value
(in Ohms)
M4-LHS Installation and Operation Manual
HT# 059295-00 A
41
Too Little Heat
• ResetRatioandOffset- If reduced heat occurs only in certain weather conditions, adjust the
Reset Ratio and Offset (See "Outdoor Reset Concept" on page 5). If reduced heat occurs year
round, increase the Offset.
• SetbackandDay/NightSchedule- If reduced heat occurs only during specic hours, check the
Day/Night Schedule and the Setback values. Then, reduce the Setback setting. See "Setback" on page 31.
• BoilerModeSettings- The M4-LHS will only control boilers their mode is set to Auto or Standby. Check if any boiler stage is set to Manual, Off, or Standby. See "Mode" on page 39.
Boilers are Short-Cycling
• LagDelay- Increase the Lag Delay only if modulating boilers tend to short-cycle.
• MinimumRuntime- Increase the Minimum Runtime only if staging boilers tend to short-cycle.
• LastStageHold- Increase the Last Stage Hold only if the lead boiler tends to short-cycle.
System is Overshooting or Undershooting
ModulatingBoilers
• Gain- If when using modulating boilers the system is overshooting reduce the Gain. See "Gain"
on page 33.
• Gain- If when using modulating boilers the system is undershooting increase the Gain.
StagingBoilers
• ReactionTime- If when using staging boilers the system is overshooting increase the Reaction
Time. As the stages will be turning on faster than they are affecting the system. If the system was undershooting for long periods, reduce the Reaction Time. See "Reaction Time" on page 34.
• MinimumRuntime- If when using staging boilers the system is overshooting reduce the Minimum Run Time. If the system was undershooting, increase the reaction time as it is turning off stages quicker than needed. See "Minimum Runtime" on page 34.
HT# 059295-00 A
42
M4-LHS Installation and Operation Manual
SPECIFICATIONS
VoltageInput: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 VAC 60 Hz
PowerConsumption: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 VA Max
OperatingTemperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20°F/-6°C to 130°F/54°C
OperatingHumidity: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20% to 80% non-condensing
Dimensions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11"W x 9" H x 3 ¾" D
Weight: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 pounds
M4-LHS SPECIFICATIONS
SwitchBetweenBoilerGroupsMode: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using Target Temperature
LeadStageRotation: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time ( 1 to 1440 Hours (60 days)), Manual, Last-On
PumpOutput: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 N.O. S.P.S.T
ModulatingBoilerModes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Auto, Manual, Standby, On, Off
StagingBoilerModes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auto, Standby, On, Off
StandbyTime: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 to 60 minutes
ModulatingOutputTypes: . . . . . . . . . . . . . . . . . . . Current (4-20mA) and Voltage (0-10V, 0-5V, 2-10V, and 1-5V)
SequencingOutputTypes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . On/Off, 2-Stage, 3-Stage, or 4-Stage
OutputRelayRatings: . . . . . . . . . . 1 Amp inductive (⅛ HP), 6 Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits
Add-OnExtensionPanels: . . . . . . . . . . . . . . . . . . . . . . . . up two Extension Panels using RS485 (RJ45 or RJ11)
IgnitionPoint%: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 to 50%
ModulationStartPoint%: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 to 100%
ModulationModes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Normal or Parallel
SequencingModes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Lo/Hi/Lo/Hi or Lo/lo/Hi/Hi
TemperatureDisplay: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fahrenheit or Celsius
Display: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Graphical Alphanumeric (up to 7 rows x 21 char. each)
LED: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 System Output relay, 4 Boiler Output relays
ControlSensorRanges:. . . . . . . . . . . . . . . . . . . . . Outdoor Temperature sensor - minus 35°F/-37°C to 250°F/121°C
Heating system sensor - minus 35°F/-37°C to 250°F/121°C
OutdoorCutoffRange: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20°F/-6°C to 100°F, ON and OFF
ResetRatioRange: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (1:4) to (4:1) (Outdoor : System Water)
OffsetAdjustment: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .minus -40°F°/-22°C° to plus 40°F°/22°C°
MinimumWaterTemperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50°F/10°C to 170°F/77°C
MaximumWaterTemperature:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90°F/32°C to 240°F/116°C
IndirectDomesticHotWater: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . with Priority or without Priority
PumpRun-On: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 to 360 minutes
PurgeDelay: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.0 to 10.0 minutes
LagDelay: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0 to 60 minutes
LastStageHold: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 to 30°F
Schedules: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Day and 1 Night (Setback) setting per day
NightSetback: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0°F°/0°C° to 75°F°/42°C°
PowerBackup: . . . . . . . . . Lithium coin battery, 100 days minimum 5 year replacement (Maintains Clock in power outages)
ExternalInputs: . . . . . . . . . . . . Shutdown, Tstat, and Setback Input, and Prove and DHW Call Input. (Dry Contacts Only)
Season: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Winter and Summer
EXTENSION SPECIFICATIONS
(EachExtensioncanaddupto(6)additionalboilerstages.AmaximumoftwoExtensionscanbeused.)
ExtensionNumbering: . . . . . . . . . . . .Toggle Switch A (Stages E - J, LEDs are Green) or B (Stages K - P, LEDs are Red)
BoilerOutputs: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (6) N.O. S.P.S.T.
ModulatingOutputTypes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (6) 4-20mA and 0-10V
OutputRelayRatings: . . . . . . . . . . 1 Amp inductive (⅛ HP), 6 Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits
ConnectiontoM4-LHSandanotherextension: . . Two RS485 connections using 6 wire RJ11 cable (Cable is provided)
M4-LHS Installation and Operation Manual
43
HT# 059295-00 A
1=SHUTDOWN,2=NO TSTAT CALL,3=PROVE FAILURE,4=
PURGE DLEAY,5=WAITING FOR PROVE,6=SENSOR FAULT,7=
LAG DELAY, 8=LAST STAGE HOLD,9=DHW CALL,10 = SYSTEM
RUNON,11=SUMMER,12=OUTDOOR CUTOFF,13=BOOST
MODE,14=SETBACK MODE,15 = NORMAL OPERATION
1 =1.00 OD = 4.00 Sys,2 =1.00 OD = 3.00 Sys,3 =1.00 OD = 2.00 Sys, 4
=1.00 OD = 1.50 Sys,5 =1.00 OD = 1.25 Sys,6 =1.00 OD = 1.00 Sys,,7
=1.25 OD = 1.00 Sys,8 =1.50 OD = 1.00 Sys,9 =2.00 OD = 1.00 Sys,10
=3.00 OD = 1.00 Sys,11 = 4.00 OD = 1.00 Sys
False True True = Energized, False = De-Engergized
RY0 - RY Max
Stages
BINARY-VALUE Read Only
2800 - Max
Stages
Hybrid Object ID Object Type Object Value Object Name Units Minimum Maximum Denition
HYBRID - OUTDOOR RESET - BACNET VARIABLE LIST
Model Device Object Read Only MODEL
Serial Number Device Object Read Only SNUMBER
Version Device Object Read Only VERSION
Operation Mode 100 MULTISTATE-VALUE Read Only OPMODE 1 3 1= Hybrid, 2 = Modulation Setpoint, 3 = Modulation Reset
Outdoor Temperature 200 ANALOG-VALUE Read Only ODTEMP Degree F 32000=OPEN,3201=SHORT
System Temperature 300 ANALOG-VALUE Read Only SYSSEN Degree F 32000=OPEN,3201=SHORT
Control Status 400 MULTISTATE-VALUE Read Only CSTAT 1 15
Season 500 MULTISTATE-VALUE Read/Write SEA 1 2 1= Winter, 2= Summer
Reset Ratio 600 MULTISTATE-VALUE Read/Write RR 1 11
Offset 700 ANALOG-VALUE Read/Write OFF Degree F -50 50 Integer Values Only (-1,0,1,2…)
Outdoor Cutoff 800 ANALOG-VALUE Read/Write CO Degree F 19 101 Integer Values Only (19,20,21…)
Min Water Temp 900 ANALOG-VALUE Read/Write MINW Degree F 50 180 Integer Values Only (50,51,52…)
Max Water Temp 1000 ANALOG-VALUE Read/Write MAXW Degree F 70 220 Integer Values Only (70,71,72…)
Setback 1100 ANALOG-VALUE Read/Write SB Degree F 0 75 Integer Values Only (0,1,2…)
Purge Delay 1200 ANALOG-VALUE Read/Write PDLY Minutes .1 10 .1 thru .9 after Integer Values Only (1,2…)
System Runon 1300 ANALOG-VALUE Read/Write RUNON Minutes 0 360 Integer Values Only (0,1,2…)
Rotation Time 1400 ANALOG-VALUE Read/Write RTTIME Hours 1 1440 Hours since last rotation Integer Values Only (1,2,3…)
Standby Time 1500 ANALOG-VALUE Read/Write STBYDLY Minutes 1 60 Integer Values Only (1,2,3…)
Last Stage Hold 1600 ANALOG-VALUE Read/Write LSTHOLD Degree F 0 30 Integer Values Only (0,1,2…)
Con Lead Stage 1700 MULTISTATE-VALUE Read/Write CLEAD 1 16 Represent the current lead boiler for the condensing group
Non-Con Lead Stage 1800 MULTISTATE-VALUE Read/Write NCLEAD 1 16 Represent the current lead boiler for the non-condensing group
Reaction Time 1900 ANALOG-VALUE Read/Write RETIME Minutes 1 10 Integer Values Only (1,2,3…)
Min Run Time 2000 ANALOG-VALUE Read/Write MINRUN Minutes 1 60 Integer Values Only (1,2,3…)
Gain 2100 MULTISTATE-VALUE Read/Write GAIN 1 10
Lag Delay 2200 ANALOG-VALUE Read/Write LAGDLY Minutes 0 60 Integer Values Only (0,1,2…)
Soft off 2300 ANALOG-VALUE Read/Write SOFF Seconds 0 60 Integer Values Only (0,1,2…)
Set Time 2400 ANALOG-VALUE Read/Write PTIME Minutes 1 1440 Time since midnight Integer Values Only (1,2,3…)
Day Schedule 2500 ANALOG-VALUE Read/Write DSCHED Minutes 1 1440 Time since midnight Integer Values Only (1,2,3…)
Night Schedule 2600 ANALOG-VALUE Read/Write NSCHED Minutes 1 1440 Time since midnight Integer Values Only (1,2,3…)
System Relay 2700 BINARY-VALUE Read Only SYSRLY False True True = Energized, False = De-Engergized
Output Relays
HT# 059295-00 A
44
M4-LHS Installation and Operation Manual
1=SHUTDOWN,2=NO TSTAT CALL,3=PROVE FAILURE,4=
PURGE DLEAY,5=WAITING FOR PROVE,6=SENSOR FAULT,7=
LAG DELAY, 8=LAST STAGE HOLD,9=DHW CALL,10 = SYSTEM
RUNON,11=SUMMER,12=OUTDOOR CUTOFF,13=BOOST
MODE,14=SETBACK MODE,15 = NORMAL OPERATION
1 =1.00 OD = 4.00 Sys,2 =1.00 OD = 3.00 Sys,3 =1.00 OD = 2.00 Sys, 4
=1.00 OD = 1.50 Sys,5 =1.00 OD = 1.25 Sys,6 =1.00 OD = 1.00 Sys,,7
=1.25 OD = 1.00 Sys,8 =1.50 OD = 1.00 Sys,9 =2.00 OD = 1.00 Sys,10
=3.00 OD = 1.00 Sys,11 = 4.00 OD = 1.00 Sys
False True True = Energized, False = De-Engergized
RY0 - RY Max
Stages
Hybrid Object ID Object Type Object Value Object Name Units Minimum Maximum Denition
MODULATION - OUTDOOR RESET - BACNET VARIABLE LIST
Model Device Object Read Only MODEL
Serial Number Device Object Read Only SNUMBER
Version Device Object Read Only VERSION
Operation Mode 100 MULTISTATE-VALUE Read Only OPMODE 1 3 1= Hybrid, 2 = Modulation Setpoint, 3 = Modulation Reset
Outdoor Temperature 200 ANALOG-VALUE Read Only ODTEMP Degree F 32000=OPEN,3201=SHORT
System Temperature 300 ANALOG-VALUE Read Only SYSSEN Degree F 32000=OPEN,3201=SHORT
Control Status 400 MULTISTATE-VALUE Read Only CSTAT 1 15
M4-LHS Installation and Operation Manual
Season 500 MULTISTATE-VALUE Read/Write SEA 1 2 1= Winter, 2= Summer
Reset Ratio 600 MULTISTATE-VALUE Read/Write RR 1 11
Offset 700 ANALOG-VALUE Read/Write OFF Degree F -50 50 Integer Values Only (-1,0,1,2…)
Outdoor Cutoff 800 ANALOG-VALUE Read/Write CO Degree F 19 101 Integer Values Only (19,20,21…)
Min Water Temp 900 ANALOG-VALUE Read/Write MINW Degree F 50 180 Integer Values Only (50,51,52…)
Max Water Temp 1000 ANALOG-VALUE Read/Write MAXW Degree F 70 220 Integer Values Only (70,71,72…)
Setback 1100 ANALOG-VALUE Read/Write SB Degree F 0 75 Integer Values Only (0,1,2…)
Purge Delay 1200 ANALOG-VALUE Read/Write PDLY Minutes .1 10 .1 thru .9 after Integer Values Only (1,2…)
System Runon 1300 ANALOG-VALUE Read/Write RUNON Minutes 0 360 Integer Values Only (0,1,2…)
Rotation Time 1400 ANALOG-VALUE Read/Write RTTIME Hours 1 1440 Hours since last rotation Integer Values Only (1,2,3…)
Standby Time 1500 ANALOG-VALUE Read/Write STBYDLY Minutes 1 60 Integer Values Only (1,2,3…)
Last Stage Hold 1600 ANALOG-VALUE Read/Write LSTHOLD Degree F 0 30 Integer Values Only (0,1,2…)
Gain 1700 MULTISTATE-VALUE Read/Write GAIN 1 10
Lag Delay 1800 ANALOG-VALUE Read/Write LAGDLY Minutes 0 60 Integer Values Only (0,1,2…)
Soft off 1900 ANALOG-VALUE Read/Write SOFF Seconds 0 60 Integer Values Only (0,1,2…)
Set Time 2000 ANALOG-VALUE Read/Write PTIME Minutes 1 1440 Time since midnight Integer Values Only (1,2,3…)
Day Schedule 2100 ANALOG-VALUE Read/Write DSCHED Minutes 1 1440 Time since midnight Integer Values Only (1,2,3…)
Night Schedule 2200 ANALOG-VALUE Read/Write NSCHED Minutes 1 1440 Time since midnight Integer Values Only (1,2,3…)
BINARY-VALUE Read Only
2400 - Max
Stages
System Relay 2300 BINARY-VALUE Read Only SYSRLY False True True = Energized, False = De-Engergized
Output Relays
HT# 059295-00 A
45
1=SHUTDOWN,2=NO TSTAT CALL,3=PROVE FAILURE,4=
PURGE DLEAY,5=WAITING FOR PROVE,6=SENSOR FAULT,7=
LAG DELAY, 8=LAST STAGE HOLD,9=DHW CALL,10 = SYSTEM
RUNON,11=SUMMER,12=OUTDOOR CUTOFF,13=BOOST
MODE,14=SETBACK MODE,15 = NORMAL OPERATION
False True True = Energized, False = De-Engergized
RY0 - RY Max
Stages
BINARY-VALUE Read Only
2100 - Max
Stages
Hybrid Object ID Object Type Object Value Object Name Units Minimum Maximum Denition
MODULATION - SET POINT - BACNET VARIABLE LIST
Model Device Object Read Only MODEL
Serial Number Device Object Read Only SNUMBER
Version Device Object Read Only VERSION
Operation Mode 100 MULTISTATE-VALUE Read Only OPMODE 1 3 1= Hybrid, 2 = Modulation Setpoint, 3 = Modulation Reset
Outdoor Temperature 200 ANALOG-VALUE Read Only ODTEMP Degree F 32000=OPEN,3201=SHORT
System Temperature 300 ANALOG-VALUE Read Only SYSSEN Degree F 32000=OPEN,3201=SHORT
Control Status 400 MULTISTATE-VALUE Read Only CSTAT 1 15
Season 500 MULTISTATE-VALUE Read/Write SEA 1 2 1= Winter, 2= Summer
Setpoint 600 ANALOG-VALUE Read/Write SETP Degree F 70 250 Integer Values Only (70,71,72…)
Outdoor Cutoff 700 ANALOG-VALUE Read/Write CO Degree F 19 101 Integer Values Only (19,20,21…)
Setback 800 ANALOG-VALUE Read/Write SB Degree F 0 75 Integer Values Only (0,1,2…)
Purge Delay 900 ANALOG-VALUE Read/Write PDLY Minutes .1 10 .1 thru .9 after Integer Values Only (1,2…)
System Runon 1000 ANALOG-VALUE Read/Write RUNON Minutes 0 360 Integer Values Only (0,1,2…)
Rotation Time 1100 ANALOG-VALUE Read/Write RTTIME Hours 1 1440 Hours since last rotation Integer Values Only (1,2,3…)
Standby Time 1200 ANALOG-VALUE Read/Write STBYDLY Minutes 1 60 Integer Values Only (1,2,3…)
Last Stage Hold 1300 ANALOG-VALUE Read/Write LSTHOLD Degree F 0 30 Integer Values Only (0,1,2…)
Gain 1400 MULTISTATE-VALUE Read/Write GAIN 1 10
Lag Delay 1500 ANALOG-VALUE Read/Write LAGDLY Minutes 0 60 Integer Values Only (0,1,2…)
Soft off 1600 ANALOG-VALUE Read/Write SOFF Seconds 0 60 Integer Values Only (0,1,2…)
Set Time 1700 ANALOG-VALUE Read/Write PTIME Minutes 1 1440 Time since midnight Integer Values Only (1,2,3…)
Day Schedule 1800 ANALOG-VALUE Read/Write DSCHED Minutes 1 1440 Time since midnight Integer Values Only (1,2,3…)
Night Schedule 1900 ANALOG-VALUE Read/Write NSCHED Minutes 1 1440 Time since midnight Integer Values Only (1,2,3…)
System Relay 2000 BINARY-VALUE Read Only SYSRLY False True True = Energized, False = De-Engergized
Output Relays
HT# 059295-00 A
46
M4-LHS Installation and Operation Manual
BACNET PICS STATEMENT
Product Model Number Protocol Revision Software Version Firmware Version
M4-LHS BACnet Control Varies 1.5 2.0 2.0
Vendor Vendor ID Address and Phone
Laars
Product Description
M4-LHS control for hot water heating applications. (see http://www.Laars.com for more information)
BACnet Standardized Device Prole (Annex L)
Product Device Prole
M4-LHS BACnet Control BACnet Application Specic Controller (B-ASC)
Supported BIBBs (Annex K)
Supported BIBBs BIBB Name
DS-RP-B Data Sharing-ReadProperty-B
DS-WP-B Data Sharing-WriteProperty-B
DM-DDB-B Device Management-Dynamic Device Binding-B
DM-DOB-B Device Management-Dynamic Object Binding-B
DM-DCC-B Device Management-DeviceCommunicationControl-B
Standard Object Types Supported
Object Type Creatable Deletable
Analog Value No No
Binary Value No No
Multi-State Value No No
Device No No
Data Link Layer Options (Annex J)
Product Data Link Options
M4-LHS BACnet Control BACnet MS/TP
Segmentation Capability
Segmentation Type Supported Window Size (MS/TP product limited to 1)
Able to transmit segmented messages No
Able to receive segmented messages No
Device Address Binding
Product Static Binding Supported
M4-LHS BACnet Control No
Character Sets
Product Character Sets supported
M4-LHS BACnet Control ANSI X3.4
Baud Rates: 9600, 19200, 38400
M4-LHS Installation and Operation Manual
HT# 059295-00 A
47
PIPING AND WIRING DIAGRAMS
HYBRID PIPING DIAGRAM
M4-LHS
HYBRID CONTROL
SYSTEM
A
B
Two Modulating Condensing Boilers and Two On/Off Non­Condensing Boilers
120VAC
B
A
SYS
PWR
L
N
5
3
7
8
6
4
1
2
C
D
DO NOT APPLY ANY VOLTAGE
RUNPROGRAM
TO INPUT TERMINALS
A
C
D
CUR / VLT
mA
GND
VLT
-
+
+
10
9
15
13
12
11
14
OUTDOOR
C
B
D
TEMP
CUR / VLT
CUR / VLT
CUR / VLT
ND
T
mA
mA
VLT
G
GND
mA
mA
VLT
VL
GND
T
-
-
-
+
+
+
+
+
+
+
25
23
20
26
18
16
19
24
22
17
21
Outdoor
Sensor
STARTUP SETTINGS
Boiler Type = Hybrid
SHUTDOWN
EXTENSION
STEM
VE
PRO
SY
/TSTAT
MODULE
W
TEMP
/DH
/SETBACK
485
RS-
O
O
O
O
T
29
32
28
30
31
27
Condensing Boiler Type = Modulating Condensing Boiler Number = 2 Condensing Modulating Mode = Parallel Non-Condensing Boiler Type = Staging Non-Condensing Output Type = On/Off Non-Condensing Boiler Number = 2
Boiler 1
Condensing
Modulating
Boiler 2
Condensing
Modulating
Boiler 3
Non-Condensing
On/Off
Boiler 4
Non-Condensing
On/Off
System
Sensor
Building Heating Loop
System:
The M4-LHS operates two modulating boilers and two On/Off Boilers. The boilers are piped in Reverse Return on the primary loop. The System output is controlling the System Pump.
Laars is aware that each installation is unique. Thus, Laars is not responsible for any installation related to any electrical or plumbing diagram generated by Laars . The provided illustrations are to demonstrate Laars ’s control operating concept only.
HT# 059295-00 A
48
M4-LHS Installation and Operation Manual
HYBRID WIRING DIAGRAM
M4-LHS
OUTPUT RATINGS:
120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
USE COPPER WIRE, CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
CAUTION
: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
SYSTEM
A
B
C
D
HYBRID CONTROL
Two 4-20mA Modulating Condensing Boilers and Two On/Off Non­Condensing Boilers
L
N
L N
System Pump
PWR
L
1
N
2
B
A
SYS
5
3
678
4
Boiler 1
Boiler 2
{
Modulating
Condensing
Group (Boiler 1 & 2)
OUTPUT RATINGS:
120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
USE COPPER WIRE, CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
D
C
9
10
11
12
Boiler 3
Boiler 4
{
4 - 20 mA
Staging
Modulating
Signal Outputs
Non-Condensing
Group (Boiler 3 & 4)
M4-LHS
CAUTION
: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
A
CUR / VLT
CUR / VLTBCUR / VLTCCUR / VLT
mA
mA
VLT
GND
GND
-
-
+
+
+
15
13
16
14
17
Boiler 1
SYSTEM
A
B
C
D
RUNPROGRAM
VLT
GND
-
+
19
18
Boiler 2
D
mA
mA
mA
VLT
VLT
GND
-
+
+
+
+
+
23
20
21
24
22
HYBRID CONTROL
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
OUTDOOR
TEMP
T
25
26
O
SYSTEM
TEMP
T
28
27
Shield
O
PROVE
/DHW
29
Shield
O
30
SHUTDOWN
/SETBACK
31
Prove Jumper
System Sensor
Outdoor Sensor
EXTENSION
/TSTAT
MODULE
RS-485
O
32
Do Not remove
STARTUP SETTINGS
Boiler Type = Hybrid Condensing Boiler Type = Modulating Condensing Boiler Number = 2 Condensing Output Type = 4-20ma Condensing Modulating Mode = Parallel Non-Condensing Boiler Type = Staging Non-Condensing Output Type = On/Off Non-Condensing Boiler Number = 2
Two Voltage Modulating Condensing Boilers and Two On/Off Non­Condensing Boilers
A
CUR / VLT
CUR / VLTBCUR / VLTCCUR / VLT
mA
VLT
GND
GND
-
-
+
+
15
13
16
14
Boiler 1
Voltage
Modulating
Signal Outputs
L
N
L N
System Pump
PWR
L
1
N
2
5
3
678
9
Boiler 1
Boiler 2
{
10
11
12
Boiler 3
{
Boiler 4
4
D
C
B
A
SYS
Staging
Modulating
Condensing
Non-Condensing
Group (Boiler 1 & 2)
Group (Boiler 3 & 4)
M4-LHS Installation and Operation Manual
mA
VLT
GND
+
+
19
18
17
Boiler 2
D
mA
mA
VLT
+
+
+
23
24
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
OUTDOOR
TEMP
T
25
26
SHUTDOWN
SYSTEM
PROVE
TEMP
/DHW
/SETBACK
T
O
O
O
30
29
31
28
27
EXTENSION
/TSTAT
MODULE
RS-485
O
32
RUNPROGRAM
mA
VLT
GND
-
-
+
+
20
21
22
STARTUP SETTINGS
Boiler Type = Hybrid
Shield
Shield
Prove Jumper
Do Not remove
Condensing Boiler Type = Modulating Condensing Boiler Number = 2 Condensing Output Type = Any voltage Condensing Modulating Mode = Parallel
System Sensor
Outdoor Sensor
Non-Condensing Boiler Type = Staging Non-Condensing Output Type = On/Off Non-Condensing Boiler Number = 2
HT# 059295-00 A
49
MODULATING PIPING DIAGRAM
Outdoor
Sensor
Four Modulating Boilers
120VAC
Boiler 1
Condensing
Modulating
C
B
A
SYS
PWR
L
N
5
6
3
789
4
1
2
Boiler 2
Condensing
Modulating
10
D
12
11
M4-LHS
SYSTEM
A
B
C
D
A
B
CUR / VLT
CUR / VLT
CUR / VLT
GND
mA
mA
VLT
GND
VLT
GND
-
-
-
+
+
+
+
15
13
18
16
19
14
17
RUNPROGRAM
C
GND
mA
VLT
+
+
20
22
21
HYBRID CONTROL
DO NOT APPLY ANY VOLTAGE
OUTDOOR
D
CUR / VLT
T
VL
mA
mA
-
+
+
+
23
24
TO INPUT TERMINALS
TEMP
T
O
25
26
SYSTEM
PROVE
/DHW
TEMP
T
O
O
29
30
28
27
DOWN
SHUT
EXTENSION
/TSTAT
MODULE
CK
BA
/SET
RS-485
O
32
31
Boiler 3
Condensing
Modulating
STARTUP SETTINGS
Boiler Type = Modulation Boiler Number = 4
Boiler 4
Condensing
Modulating
System
Sensor
Building Heating Loop
System:
The M4-LHS operates four modulating boilers. The boilers are piped in Reverse Return on the primary loop. The System output is controlling the System Pump.
Laars is aware that each installation is unique. Thus, Laars is not responsible for any installation related to any electrical or plumbing diagram generated by Laars . The provided illustrations are to demonstrate Laars's control operating concept only.
HT# 059295-00 A
50
M4-LHS Installation and Operation Manual
PIPING AND WIRING DIAGRAMS
HYBRID PIPING DIAGRAM
M4-LHS
HYBRID CONTROL
SYSTEM
A
B
Two Modulating Condensing Boilers and Two On/Off Non­Condensing Boilers
120VAC
B
A
SYS
PWR
L
N
5
3
8
6
7
4
1
2
C
D
DO NOT APPLY ANY VOLTAGE
RUNPROGRAM
TO INPUT TERMINALS
A
C
D
CUR / VLT
mA
VLT
GND
-
+
+
9
10
15
13
12
11
14
OUTDOOR
C
D
B
TEMP
CUR / VLT
CUR / VLT
CUR / VLT
GND
mA
mA
VLT
mA
mA
GND
VLT
VLT
GND
T
-
-
-
+
+
+
+
+
+
+
25
23
20
26
18
16
19
24
22
17
21
Outdoor
Sensor
STARTUP SETTINGS
Boiler Type = Hybrid
SHUTDOWN
EXTENSION
SYSTEM
PROVE
/TSTAT
MODULE
TEMP
/DHW
/SETBACK
RS-485
T
O
O
O
O
32
29
30
28
31
27
Condensing Boiler Type = Modulating Condensing Boiler Number = 2 Condensing Modulating Mode = Parallel Non-Condensing Boiler Type = Staging Non-Condensing Output Type = On/Off Non-Condensing Boiler Number = 2
Boiler 1
Condensing
Modulating
Boiler 2
Condensing
Modulating
Boiler 3
Non-Condensing
On/Off
Boiler 4
Non-Condensing
On/Off
System
Sensor
Building Heating Loop
System:
The M4-LHS operates two modulating boilers and two On/Off Boilers. The boilers are piped in Reverse Return on the primary loop. The System output is controlling the System Pump.
Laars is aware that each installation is unique. Thus, Laars is not responsible for any installation related to any electrical or plumbing diagram generated by Laars . The provided illustrations are to demonstrate Laars ’s control operating concept only.
HT# 059295-00 A
48
M4-LHS Installation and Operation Manual
HYBRID WIRING DIAGRAM
M4-LHS
OUTPUT RATINGS:
120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
USE COPPER WIRE, CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
CAUTION
: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
SYSTEM
A
B
C
D
HYBRID CONTROL
Two 4-20mA Modulating Condensing Boilers and Two On/Off Non­Condensing Boilers
L
N
L N
System Pump
PWR
L
1
N
2
B
A
SYS
5
3
678
4
Boiler 1
Boiler 2
{
Modulating
Condensing
Group (Boiler 1 & 2)
OUTPUT RATINGS:
120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
USE COPPER WIRE, CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
D
C
9
10
11
12
Boiler 3
Boiler 4
{
4 - 20 mA
Staging
Modulating
Signal Outputs
Non-Condensing
Group (Boiler 3 & 4)
M4-LHS
CAUTION
: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
A
CUR / VLT
CUR / VLTBCUR / VLTCCUR / VLT
mA
VLT
GND
GND
-
-
+
+
15
13
16
14
17
Boiler 1
SYSTEM
A
B
C
D
mA
VLT
GND
+
+
19
18
Boiler 2
RUNPROGRAM
D
mA
mA
mA
VLT
GND
-
-
+
+
+
+
23
20
21
22
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
SYSTEM
PROVE
OUTDOOR
TEMP
TEMP
VLT
+
24
/DHW
T
T
O
O
29
25
28
26
27
Shield
Shield
System Sensor
Outdoor Sensor
HYBRID CONTROL
SHUTDOWN
/TSTAT
/SETBACK
O
O
32
30
31
Prove Jumper
Do Not remove
EXTENSION
MODULE
RS-485
STARTUP SETTINGS
Boiler Type = Hybrid Condensing Boiler Type = Modulating Condensing Boiler Number = 2 Condensing Output Type = 4-20ma Condensing Modulating Mode = Parallel Non-Condensing Boiler Type = Staging Non-Condensing Output Type = On/Off Non-Condensing Boiler Number = 2
Two Voltage Modulating Condensing Boilers and Two On/Off Non­Condensing Boilers
A
CUR / VLT
CUR / VLTBCUR / VLTCCUR / VLT
mA
VLT
GND
GND
-
-
+
+
15
13
16
14
Boiler 1
Voltage
Modulating
Signal Outputs
L
N
L N
System Pump
PWR
L
1
N
2
5
3
678
9
Boiler 1
Boiler 2
{
10
11
12
Boiler 3
Boiler 4
{
4
D
C
B
A
SYS
Staging
Modulating
Condensing
Non-Condensing
Group (Boiler 1 & 2)
Group (Boiler 3 & 4)
M4-LHS Installation and Operation Manual
mA
VLT
+
+
18
17
Boiler 2
D
mA
mA
VLT
+
+
+
23
24
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
OUTDOOR
TEMP
T
25
26
SHUTDOWN
SYSTEM
PROVE
TEMP
/DHW
/SETBACK
T
O
O
O
30
29
31
28
27
EXTENSION
/TSTAT
MODULE
RS-485
O
32
RUNPROGRAM
mA
VLT
GND
GND
-
-
+
+
19
20
21
22
STARTUP SETTINGS
Boiler Type = Hybrid
Shield
Shield
Prove Jumper
Do Not remove
Condensing Boiler Type = Modulating Condensing Boiler Number = 2 Condensing Output Type = Any voltage Condensing Modulating Mode = Parallel
System Sensor
Outdoor Sensor
Non-Condensing Boiler Type = Staging Non-Condensing Output Type = On/Off Non-Condensing Boiler Number = 2
HT# 059295-00 A
49
MODULATING PIPING DIAGRAM
Outdoor
Sensor
Four Modulating Boilers
120VAC
Boiler 1
Condensing
Modulating
B
A
SYS
PWR
L
N
5
3
8
6
9
7
4
1
2
Boiler 2
Condensing
Modulating
C
10
D
12
11
M4-LHS
SYSTEM
A
B
C
D
A
B
CUR / VLT
CUR / VLT
CUR / VLT
GND
mA
mA
VLT
GND
VLT
GND
-
-
+
+
+
+
15
13
18
16
19
14
17
RUNPROGRAM
C
mA
VLT
-
+
+
20
21
HYBRID CONTROL
D
CUR / VLT
mA
mA
GND
VLT
-
+
+
+
23
24
22
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
SHUTDOWN
EXTENSION
SYSTEM
PROVE
OUTDOOR
/TSTAT
MODULE
TEMP
TEMP
/DHW
/SETBACK
RS-485
T
O
O
T
O
O
32
29
25
30
28
31
26
27
Boiler 3
Non-Condensing
On/Off
STARTUP SETTINGS
Boiler Type = Modulation Boiler Number = 4
Boiler 4
Non-Condensing
On/Off
System
Sensor
Building Heating Loop
System:
The M4-LHS operates four modulating boilers. The boilers are piped in Reverse Return on the primary loop. The System output is controlling the System Pump.
Laars is aware that each installation is unique. Thus, Laars is not responsible for any installation related to any electrical or plumbing diagram generated by Laars . The provided illustrations are to demonstrate Laars's control operating concept only.
HT# 059295-00 A
50
M4-LHS Installation and Operation Manual
MODULATING WIRING DIAGRAM
L
N
L N
System Pump
PWR
L
1
N
2
OUTPUT RATINGS:
120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
USE COPPER WIRE, CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
B
A
SYS
5
3
678
4
Boiler 1
Boiler 2
4 Modulating
M4-LHS
CAUTION
: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
D
C
9
10
11
12
Boiler 3
Boiler 4
boilers
Activation Signal
SYSTEM
A
B
C
D
A
CUR / VLT
CUR / VLTBCUR / VLTCCUR / VLT
mA
VLT
GND
GND
-
-
+
+
15
13
16
14
17
Boiler 1
4 - 20 mA
Modulating
Signal Outputs
mA
VLT
GND
+
+
19
18
Boiler 2
RUNPROGRAM
mA
-
+
20
Boiler 3
VLT
+
21
D
mA
mA
GND
-
23
22
+
+
Boiler 4
HYBRID CONTROL
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
SYSTEM
PROVE
OUTDOOR
TEMP
TEMP
VLT
+
24
/DHW
T
T
O
O
29
25
28
26
27
Shield
Shield
System Sensor
Outdoor Sensor
SHUTDOWN
/TSTAT
/SETBACK
O
O
32
30
31
Prove Jumper
Do Not remove
EXTENSION
MODULE
RS-485
Four 4-20mA
Modulating Boilers
STARTUP SETTINGS
Boiler Type = Modulation Output Type = 4-20ma Boiler Number = 4
M4-LHS
OUTPUT RATINGS:
120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
USE COPPER WIRE, CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
SYS
PWR
N
L
3
1
4
2
L
N
A
5
678
Boiler 1
B
Boiler 2
CAUTION
: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
D
C
9
10
11
12
Boiler 3
Boiler 4
L N
System Pump
boilers
4 Modulating
Activation Signal
M4-LHS Installation and Operation Manual
SYSTEM
A
B
C
D
A
CUR / VLT
CUR / VLTBCUR / VLTCCUR / VLT
mA
VLT
GND
GND
-
-
+
+
15
13
16
14
Boiler 1
Modulating
Signal Outputs
mA
VLT
GND
+
+
19
18
17
Boiler 2
Voltage
RUNPROGRAM
D
mA
mA
mA
VLT
GND
-
-
+
+
+
+
23
20
21
22
Boiler 3
Boiler 4
HYBRID CONTROL
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
SYSTEM
PROVE
OUTDOOR
TEMP
TEMP
VLT
+
24
/DHW
T
T
O
O
29
25
28
26
27
Shield
Shield
System Sensor
Outdoor Sensor
SHUTDOWN
/TSTAT
/SETBACK
O
O
32
30
31
Prove Jumper
Do Not remove
EXTENSION
MODULE
RS-485
Four Voltage
Modulating Boilers
STARTUP SETTINGS
Boiler Type = Modulation Output Type = Any Voltage
Option
Boiler Number = 4
HT# 059295-00 A
51
20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • FAX 603.335.3355 1355 Kuehner Drive, Simi Valley, CA 93063 • 800.900.9267 • FAX 800.559.1583 (Sales, Service) 1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • FAX 905.366.0130
www.laars.com Litho in U.S.A © Laars Heating Systems 0911 Document 4232
HTC# 059295-00 A
Loading...