LAARS LLS-1 Installation Manual

Operation Instructions Document 4188A
OUT OF
PRODUCTION
Operation Instructions for
Laars Logic System LLS-1
LCD Boiler Controller
To be used in conjunction with appropriate product Installation and Operation manual shipped with product.
WARNING
Improper adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer, service agency, gas supplier, or call factory Applications Engineer.
Page 2
LAARS HEATING SYSTEMS
TABLE OF CONTENTS
SECTION 1 General Information
1.1 Introduction .................................................... 3
1.2 Standard Operating Features ........................ 3
1.3 Inputs ............................................................. 3
1.4 Outputs .......................................................... 3
1.5 Indications / Displays ..................................... 3
SECTION 2 Operation
2.1 Sequence of Operation .................................. 4
SECTION 3 Field Installed Connections
...................................................................... 4
SECTION 4 Factory Installed Connections
...................................................................... 7
SECTION 5 Programmable Parameters
...................................................................... 7
OUT OF
SECTION 6 Programming
...................................................................... 9
SECTION 7 Troubleshooting
7.1 Display Fault Guide .................................... 14
7.2 Flow Fault Guide ......................................... 15
7.3 Blocked Vent Fault Guide ........................... 16
7.4 Flame Rollout Fault Guide .......................... 17
7.5 Low Gas Pressure Fault Guide ................... 18
7.6 High Gas Pressure Fault Guide .................. 19
7.7 Low Water Cut Off Fault Guide................... 20
7.8 Vent Damper Fault Guide ........................... 21
SECTION 8 Replacement Parts
8.1 Ordering Information................................... 22
8.2 Parts List .................................................... 22
PRODUCTION
Laars Logic System
Page 3
SECTION 1. General Information
1.1 Introduction
The Laars Logic System (LLS) is a solid state, commercial control capable of interfacing with your boiler or water heater to intelligently provide heat energy, diagnose problems and display boiler status via a liquid crystal display (LCD).
The LLS-1 allows you to customize your boilers operation to best suit the needs of your application, while providing you with useful information to increase efficiency and simplify servicing.
The control reads information from multiple inputs and controls multiple outputs with a total of seventeen display readings. All sensors are monitored in parallel for increased safety.
The control features a simple user interface that allows programming of many functions and parameters. All boiler / domestic water settings are accessible through this interface as well as alarm settings and gas valve staging. Pump options (such as freeze protection and pump exercise) can also be turned on or off. If the draft fan or power venter option is used, they too can be controlled through simple display windows.
1.2 Standard Operating Features
All safety devices and sensors are checked to be
working properly prior to starting boiler  Proven hot surface or spark ignition, pilot &
Optional outdoor air temperature reset for boiler
Alarm contacts for fault conditions  Domestic Hot Water (DHW) set-point with
Control primary boiler pump  Control DHW circulator (when Laars sensor is
Display supply water temperature  Display return water temperature and set point  Display outdoor air temperature (OAT sensor
Display DHW storage tank temperature & set-
Adjustable pump time delay  Adjustable manual reset outlet water temperature  Control boiler staging  2 amp fused relays for low voltage devices  30 amp fused relays for high voltage devices  Removable relay terminals for easy wiring  Easy to access, easy to read control box
PRODUCTION
main gas valves, flame proving, vent dampers,
power venting equipment, and combustion air
intake equipment
operating temperature
adjustable differential (when Laars sensor is used)
used)
optional)
point
locations
OUT OF
Back-lighting for all LCDs to make
programming easier in dark locations
Modes for set-up, normal operation,
programming & trouble-shooting
Components such as power venters, combustion
air intake systems, outdoor air sensors are field configurable
Continuous display of basic operating conditions
with easy to read symbols  Adjustable fan setting for pre and post purge timing  LCD will display and diagnose boiler
performance down to the component level  Redundant processors constantly monitor all
safety devices and control operation
1.3 Inputs
1. Tank Temperature Sensor (optional Laars sensor
for DHW)
2. Inlet Water Temperature Sensor
3. Outlet Water Temperature Sensor
4. Flame Sensor
5. Low Water Cut Off (Water Level)
6. Blocked Vent Switch
7. Water Flow Sensor (Flow Switch)
8. High Gas Pressure Sensor (may be optional)
9. Low Gas Pressure Sensor (may be optional)
10. Venturi Differential Pressure Switch
(MightyMax)
11. Burner Temperature Switch (Mighty Max)
12. Fusible Links (when boiler/heater is equipped)
13. Vent Damper Open (when boiler/heater is
equipped)
14. Draft Inducer Pressure Switch (when used)
15. Auxilliary Devices
1.4 Outputs
1. Boiler Pump
2. Igniter or Pilot Igniter Control
3. Pilot Gas Valve Control
4. Gas Valve Control
5. DHW Circulator (when used with Laars sensor)
6. Vent Damper (when used)
7. Alarm
8. Draft Inducer (when used)
1.5 Indications / Displays
Inlet Water Temperature  Outlet Water Temperature  Temperature Set Points for inlet water and DHW  Ignition Process Indicators  Low Water Cut Off Status (Water Level)  Vent Damper Status  Water Flow Status  Supply Gas Pressure Status (when ordered with
gas train)  Lockout Indication and Alarm  Main Gas Valve On/Off
Page 4
LAARS HEATING SYSTEMS
Main Gas Flame Status (if main burner flame
sensor is present)
Pump / Circulator Status for Boiler and DHW
Pumps  Fan Status  Boiler Staging Status  Service Required Indicators
SECTION 2. Operation
2.1 Sequence of Operation
1. The main power switch is ON.
2. Space heating or domestic hot water call for
heat signal is initiated.
3. The status of the water temperature at the boiler
inlet is verified.
4. The status of the water temperature at the boiler
outlet is verified.
5. Auxiliary terminals are checked to make sure the
circuit is closed.
6. Boiler pump is energized (if controlled by the
LLS).
7. Vent damper is opened (if installed)
8. Vent damper proving switch is verified.
9. Venting fans are energized (if installed).
10. Controller verifies that power venter proving
switch has been made.
11. Controller verifies that the high gas pressure
switch has not tripped if unit is equipped with
switch.
12. Proper minimum gas pressure is verified if the
unit has low gas pressure switch.
13. If used on the unit, rollout switch, blocked vent
switch and fusible links are checked.
14. Differential pressure switches to verify proper
air flow through units are checked (if the unit
has such devices).
15. Flow switch is checked.
16. Adequate water level is verified through Laars
Low water cutoff (if equipped).
17. Controller performs a pre-flame sense check.
18. Ignition system is energized.
19. Controller performs a post flame sense check.
20. The main gas valve assembly is activated as
prescribed.
21. The main burner is ignited.
22. Call for heat is satisfied.
23. Main gas valve assembly is deactivated.
24. The pump is allowed to operate for a preset time,
after which is stops (if pump delay is activated).
25. Venting fan is allowed to post purge, after which
is stops (if programmed).
26. Vent damper stays open if post purge is
activated, after which time it closes.
PRODUCTION
OUT OF
SECTION 3. Field Installed Connections
Connections that are made to the LLS controller are described in this section. Sensors, field-supplied switches, power venters, aquastats, etc. can be connected directly to the LLS control. This section describes the method of connection, as well as any important information regarding connections (see Figure 1). Many connections will require programming/setup of the controller.
The LLS-1 has several operating parameters that can be changed to ensure that the boiler operation best meets the needs for your application.
Laars controls boiler water temperature at inlet.
See Sections 5 and 6 for specifics about programming options.
Field Interlock - T1
The field interlock connection is commonly referred to as a T-T connection. This is for tank aquastats and heating thermostats / end switches. The boiler will not fire unless this connection is made.
WARNING
The Field Interlock connection is NOT for safety switches that are used to prevent the boiler from firing. For field-supplied safety switches, connect directly through the boiler wiring or through the auxillary switch connection on the LLS (J32). When components are wired through the Field Interlock, voltage to the main gas valves can be energized by the DHW (domestic hot water) sensor, if used. Contact the factory if you have any questions about how to connect safety switches to the boiler or the LLS.
Important Note About Tank Aquastats:
Standard tank aquastats must be connected to the Field Interlock (T1), not the DHW Tank Temp (T3). The aquastat will call for heat when the tank temperature drops, as in a standard water heater setup. DHW Tank Temp connection is for the Laars DHW Sensor only. Do not enable or program parameters for domestic water on the LLS when using a standard tank aquastat, or the controller will look for the Laars DHW Sensor.
Outside Air Temp - T2
Laars OAT (outside air temperature) Sensor is connected here when outdoor reset is used in a heating system. To ensure proper operation, only the Laars OAT sensor should be used with the LLS.
Laars Logic System
Page 5
OUT OF
PRODUCTION
Figure 1. Laars Logic System Connections.
DHW Tank Temp - T3
This connection is for a Laars DHW
(domestic hot water) Sensor only. (Standard tank
aquastats must be connected to T1, the Field Interlock connection on the controller.) The Laars DHW sensor is a thermistor, not a switch, and this connection reads resistance. Use of this sensor allows the user to program domestic water features that are not available when using a standard tank aquastat.
WARNING
If DHW sensor is used, additional components that are tied to the field interlock will NOT prevent the unit from firing when the DHW sensor calls for heat. For field-supplied safety switches that must keep the boiler from firing, connect directly through the boiler wiring or through the auxiliary switch connection on the LLS (J32).
Page 6
LAARS HEATING SYSTEMS
Water Level Sensor - J9
This connection is for a Laars Low Water
Cutoff only. (Other low water cutoff devices must be
connected to Aux SW - J32.) This connection is made at the factory on units that are ordered with the Low Water Cutoff option or other options that include a Low Water Cutoff and is made in the field when being added after the unit is on site.
Draft Pressure Switch - T4
When a draft fan is installed, a draft pressure switch must be connected to ensure that the fan is operating before the boiler is allowed to fire. Some boilers and water heaters have built-in fans, and this connection will be made to the units internal draft switch. Remove factory-installed jumper when connecting draft pressure switch.
Vent Damper Control - T5
Vent dampers for units that require them (Mighty Therm HH & PH, 175-250) are equipped with a harness that requires wiring to the LLS through the Vent Damper Control connection. See Figure 2. Remove factory installed jumper when connecting vent damper.
High & Low Gas Pressure Switches - T6
OUT OF
PRODUCTION
Figure 2. LLS Vent Damper Connection.
On pump-mounted units, this connection is made at the factory. To interlock a pump to the LLS for non-pump-mounted units, with the addition of Laars high voltage (110V) relay & wire harness, use this connection. One end of the wire harness connects to J20 and the other end connects to the relay. A separate 110V source is then connected through the relay to the pump. This connection will handle pumps as large as 1hP, 110V, single phase. The LLS can be programmed to post-purge the pump and monitor current draw through the relay.
DHW Pump Control - J19
This feature works with the Laars DHW sensor only. To interlock a domestic water pump
(the pump between the heater and the storage tank) to the LLS, with the addition of Laars high voltage (110V) relay, wire harness, and DHW sensor, use this connection. One end of the wire harness connects to J19 and the other end connects to the relay. The Laars DHW sensor must be connected to T3. A separate 110V source is then connected through the relay to the pump. This connection will handle pumps as large as 1hP, 110V, single phase. The LLS can be programmed to post-purge the pump and monitor current draw through the relay.
Aux Sw - J32
This connection is made at the factory if additional switches are ordered with the unit. If not, field-supplied safety switches can be connected here. Safety switches that must prevent the boiler from firing must be connected here, or in series with the boiler wiring, and NOT through the Field-Interlock connection.
When a heater is built with high and low gas pressure switches, this connection is made at the factory. When adding gas pressure switches in the field, wire them per Figure 3. Remove factory­installed jumper when connecting gas pressure switches.
Main Pump Control - J20
Figure 3. High and Low Gas Pressure Switch Connection.
Alarm Relay - J29
This is a normally open 24VAC relay connection, and is not a dry contact. With this alarm relay, the user will have a 24VAC source for building automation system alarms, bells, buzzers, or any other alarm device, 8VA maximum.
Draft Inducer Relay - J28
When a boiler or water heater has a built-in draft fan, this connection will be made at the factory. For field-supplied draft fans or power venters with the addition of Laars relay, the user can make a connection here which, upon a call for heat, will call the fan to operate. The LLS can be programmed to pre-purge and/or post-purge the fan. Important note: When this connection is used, a draft pressure switch must be installed at connection T4 to prove the fan is operating before the unit fires.
Vent Damper Relay - J27
Laars Logic System
Page 7
Mighty Therm Boilers, models HH and PH, 175 and 250, require that vent dampers be installed. The vent damper relay (supplied with the controller) is plugged into this connection, but no other connections are made to the relay. The function of the relay is to close connections internal to the control board.
ID Tag Port - J2
ID tag must NEVER be removed. Do not tamper with this connection at any time.
To LCD Panel - J4
An additional LCD (controller display) can be connected here and remote mounted up to 500 feet away from the LLS. This is for display only. Changes cannot be made, and the control cannot be reset from the remote display.
SECTION 4. Factory Installed Connections
The following connections are made at the factory, if required, and descriptions are provided here for informational purposes only. Some connection points are not functional on the LLS-1, and will not be used. Contact the factory before modifying any of these connections. The LLS-1 has several operating parameters that can be changed to ensure that the boiler operation best meets the needs for your application. See Section 5 and 6 for specifics about programming options.
Inlet Temp Sensor - J7
temperature sensor on the boiler/heater inlet.
Outlet Temp Sensor - J8
temperature sensor on the boiler/heater outlet.
PRODUCTION
This connection is made at the factory for the
This is the factory connection for the
OUT OF
Valve Gas 2 - J18
This connection is made at the factory to
control safety gas valve or stage.
Valve Gas 1 - J17
This connection is made at the factory to
control safety gas valve or stage.
Blocked Vent Sw - J13
This is the factory connection for a unit that is
equipped with a blocked vent switch.
Venturi Sw - J16
This is the factory connection for a unit that is
equipped with a venturi pressure switch.
Roll Out Sw - J14
This connection is made at the factory on units
that are equipped with roll-out switches.
Fuse Link - J15
This is the factory connection for a unit that is
built with a fusible link.
Gas Valve 3 Relay - J26
Not used on LLS-1
Gas Valve 4 Relay - J25
Not used on LLS-1
Gas Valve 5 Relay - J24
Not used on LLS-1
Gas Valve 6 Relay - J23
Not used on LLS-1
ID Tag Port - J2
ID tag must NEVER be removed. Do not
tamper with this connection at any time.
To LCD + Keyboard - J3
This connection is made at the factory, for the LLS display and keypad. Additional remote LCD panel must be connected to J4.
Water Level Sensor - J9
This connection is made at the factory on units that are ordered with the Low Water Cutoff option, or other options that include a Low Water Cutoff.
Water Flow Sensor - J10
This connection is made at the factory, for the water flow sensor (flow switch).
Tran Sec - J6
This is the factory connection for the units transformer.
Gas V-5 H-Volt - J22
Not used on LLS-1
Gas V-6 H-Volt - J21
Not used on LLS-1
SECTION 5. Programmable Parameters
See Section 6 For Programming Instructions
The LLS-1 has several operating parameters that can be changed to ensure that the boiler operation best meets the needs for your application. The following is a list of the programmable parameters, minimum and maximum values, and defaults. NOTE: Laars controls boiler water
temperature at inlet.
Page 8
LAARS HEATING SYSTEMS
Boiler Settings
Inlet Water Temperature
· 110°F min
· 220°F max
· 140°F default models HH/PH
· 110°F default models VW/PW
Operating Differential
· 2°F min
· 30°F max
· 15°F default models HH/PH
· 5°F default models VW/PW
Outlet Water Temperature
· 110°F min
· 240°F max
· 200°F default models HH/PH
· 180°F default models VW/PW
Low Return Water Temperature (for alarm)
· 40°F min
· 240°F max
· 80° default
Boiler Pump Settings
Boiler Pump Installed
· yes or no
· yes default for PH/PW
· no default for HH/VW
Run Constant, Auto
· auto default
· constant optional
Pump Extended Run Cycle (pump delay time)
· 0 minute min
· 10 minute max
· 5 minute default
Pump Exercise
· no default
· yes optional
Pump Exercise Frequency
· 1 day min
· 9 days max
· 7 days default
Freeze Protection
· on default
· off optional
Freeze Protection to operate at
· 33°F min
· 50°F max
· 35°F default
Domestic Hot Water (DHW) Settings
IMPORTANT NOTE: The DHW connection on the LLS is only for the Laars DHW sensor. Standard tank aquastats must be connected to the LLS field interlock. These Domestic Hot Water settings are only used if the Laars DHW sensor is controlling tank temperature.
PRODUCTION
OUT OF
DHW Operation
· off default
· on optional
DHW Setpoint Temperature
· 110°F min
· 190°F max
· 110°F default
Operating Differential
· 2°F min
· 30°F max
· 5°F default
Outdoor Reset Settings
(Not applicable to models VW & PW)
NOTE: Outdoor Reset is accomplished with Laars Outdoor Reset sensor. Other sensors may not be compatible with the LLS control logic. Outdoor Air Temperature Sensor Installed
· no default
· yes optional
Outdoor Reset
· off default
· on optional
Outdoor Reset Ratio (Boiler inlet temp set point governs high end of curve)
·min
·5 max
· default
Maximum permissible water temperature (will override reset curve)
· 150°F min
· 220°F max
· 190°F default
Minimum permissible water temperature (will override reset curve)
· 110°F min
· 150°F max
· 130°F default
Warm Weather Shutdown
· on default
· off optional
Warm Weather Shutdown Temp
· 40°F min
· 120°F max
· 60°F default
Alarm Settings
External Alarm
· on default
· off optional
Internal Alarm
· on default
· off optional
Loading...
+ 16 hidden pages