Laars JV User Manual

Page 1
Installation and Operation Instructions Document 1025W
Installation and Operation Instructions for
Mini-Therm II
Residential Gas-Fired Hydronic Boilers
Vent damper is optional in some provinces of Canada.
These instructions are to be stored in the packet provided on the boiler.
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water boiler installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed exactly , a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
H0071400W
Page 2
Page 2
LAARS HEATING SYSTEMS
TABLE OF CONTENTS
SECTION 1. General Information
1A. Introduction...................................................3
1B. Warranty....................................................... 3
1C. Field Assembly.............................................3
1D. Flow Requirements ......................................4
1E. Boiler Placement ..........................................4
1F. Gas Supply and Piping .................................5
1G. Combustion Air Supply.................................6
1H. Venting ......................................................... 7
1H-1. Common Venting System............................. 8
1I. Water Piping of Boiler System...................... 8
1I-1. By-pass Piping ............................................. 8
1J. Chilled Water Systems ...............................10
1K. Electrical Wiring.......................................... 10
1L. Filling the System ....................................... 12
SECTION 2. Installation Instructions
2A-1. System Start-up.......................................... 14
2A-2. High Altitude Burner
Air Shutter Replacement ............................ 15
2A-3. Sequence of Operation ..............................16
2B. Water Temperature Setting ........................16
2C. Maintenance ............................................... 16
2D. Electrical Troubleshooting .......................... 17
SECTION 3.
Parts List .................................................... 21
Page 3
Mini-Therm II Hydronic Boiler
Page 3
SECTION 1. General Information
WARNING
The JV hydronic boiler must be installed in accordance with the procedures detailed in this manual, or the Laars warranty will be voided. The installation must conform to the requirements of the local jurisdiction having authority, and, in the United States, to the latest edition of the National Fuel Gas Code, ANSI Z223.1. In Canada, the installation must conform with the latest edition of CAN/CGA­B149.1 OR .2 installation codes for gas burning appliances, and/or local codes. Any modifications to the boiler, its gas controls, gas orifices, wiring or draft diverter may void the warranty. If field conditions require modifications, consult the factory representative before initiating such modifications.
1A. Introduction
This manual provides information necessary for the installation, operation, and maintenance of Laars Model JV copper tube hydronic boilers. These boilers are available in two configurations; the JVT has a thermocouple/continuous burning pilot, and the JVS has an electronic intermittent ignition device (I.I.D.). Look for the model designation on the rating plate, which can be found on top of the boiler in the right rear corner. If the unit is part of a Mini-Combo II (model MC) Residential Gas-Fired Space/Water Heater, refer also to Document 8001, Mini-Combo II Installation and Operation Instructions.
The Laars automatic vent dampers are standard on all U.S. models. The Laars side wall power venters can be used on both JVS and JVT models. Special instructions for their installation are included in the vent damper and power venter package. Read them carefully before installation.
All application and installation procedures should be reviewed completely before proceeding with the installation. Consult the Laars factory, or local factory representative, with any problems or questions regarding this equipment. Experience has shown that most operating problems are caused by improper installation.
Some accessory items are shipped in separate packages. Verify receipt of all packages listed on the packing slip. Inspect everything for damage immediately upon delivery, and advise the carrier of any shortages or damage. Any such claims should be filed with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment whether visible or concealed.
1C. Field Assembly
1. Mini-Therm II boilers have built-in draft diverter
for natural draft operation.
2. Find the vent damper box which is located in the
boiler package (vent damper is optional in
Canada).
3. Install the vent damper directly to the top of the
draft diverter outlet with the damper operator
facing to the front of the boiler, and with the
flow direction arrow pointing upward. Use the
vent damper wire harness provided with the
boiler to connect the vent damper to the boiler.
The bracket end of the harness should be
connected to the vent damper actuator.
4. For Model JVS only: Install the metal plug
provided with the vent damper onto the damper
plate hole. Disregard the metal plug in case of
standing (continuous) pilot boilers. The damper
plate hole should never be blocked on all JVT
models.
Vent
Damper Vent Damper Harness
(optional in
Canada)
Draft Diverter
(built-in)
1B. Warranty
The Laars Model JV boilers are covered by a limited warranty. The owner should fill out the warranty registration card and return it to Laars.
All warranty claims must be made to an authorized Laars representative or directly to the factory. Claims must include the boiler serial number and model (this information can be found on the rating plate), installation date, and name of the installer. Shipping costs are not included in the warranty coverage.
Figure 1. Vent Damper Installation.
Page 4
Page 4
LAARS HEATING SYSTEMS
5. The field assembly is now complete. The boiler is ready for water, gas and electrical connections and venting installation.
6. Do not modify the automatic vent damper device. It is very important that no other vents are closed. Provide at least six inches clearance between the automatic vent damper and combustible construction, and be sure to allow access for servicing the damper.
Caution
Do not force motor operation when operator is fastened to the damper by moving the damper blade, turning the shaft or by turning the position indicator.
Note: In Canada, the vent damper is optional.
1D. Flow Requirements
All high recovery, low volume water boilers
must have adequate flow for efficient operation. Pump selection is critical to this goal, and pumps should be selected to provide for system design water temperature rise. Table 1 details temperature rise and water flow (GPM) for the Mini-Therm boilers.
Damage from improper flow is not warranted.
Failure to insure proper water flow through the
heat exchanger of the boiler will void the Laars warranty. Flow can be verified by measuring the difference in water temperatures between the boiler inlet and outlet. For example: For a JV-100 installation, the inlet water temperature is 160°F (71°C), and the outlet temperature is 180°F (82°C). That means there is a 20° (-7°C) temperature rise through the boiler. According to Table 1, that would indicate a flow rate of 8 GPM (0.5L/S). Temperature rise must be measured with the longest (highest head) zone calling for heat alone.
Other factors to be considered before selecting a pump are pipe size, the number of fittings throughout the system, smoothness of the interior surface of the pipe, the quantity of water flowing through the pipe, whether a glycol solution is being used, and the total length of piping in the system. Table 2 can help in making that determination.
1E. Boiler Placement
The boiler must be placed to provide clearances on all sides for maintenance and inspection. There must also be minimum distances maintained from combustible surfaces.
At least 15" (381mm) access must be available in front of the boiler for burner removal. Consult local codes for clearances to hot water pipes and accessories.
If the boiler is to be installed in a garage, all burners and burner ignition devices must have a minimum 18" (457mm) clearance above the floor.
The Model JV-50 through JV-100 boilers can be installed in a closet, as long as the minimum clearances shown in Table 3 are observed. Special attention should be paid to clearances between the front of the boiler and the closet door when it is closed.
Consult the American National Standard Z21.13 for more information concerning closet installations. In Canada, refer to the latest edition of CAN/CGA­B149.1 and 2.
IMPORTANT: The boiler shall be installed on a floor of non-combustible construction with non­combustible flooring and surface finish and with no combustible materials against the underside, or on fire-resistant slabs or arches having no combustible materials against the underside unless listed for installation on a combustible floor.
All boilers must be installed on a non­combustible surface. That means a surface not capable of being ignited and burning, such as surfaces
8°C
15°F
Size
50 5.3
75 8.0 100 10.7 125 13.3 160 17.0 225 24.0
ft = Pressure drop (headloss) through the boilerin feet of water.
Flow Rate Headloss Flow Rate Headloss Flow Rate Headloss
gpm
l/s
0.3
0.5
0.7
0.8
1.1
1.5
ft
0.3
0.6
1.3
2.2
2.5
5.0
gpm = Water Flow in gallons per minute.
Note: Shaded area is the recommended flow and temperature rise.
m
0.1
0.2
0.4
0.7
0.8
1.5
gpm
4.0
6.0
8.0
10.0
12.8
18.0
Table 1. Temperature Rise °F °C.
11°C
20°F
l/s
0.3
0.4
0.5
0.6
0.8
1.1
m = Pressure drop (headloss) through the boiler in meters of water.
ft
0.2
0.3
0.7
1.3
1.8
3.1
l/s = Water flow in liters per second.
m
0.1
0.1
0.2
0.4
0.5
0.9
gpm
3.2
4.8
6.4
8.0
10.2
14.4
l/s
0.2
0.3
0.4
0.5
0.6
0.9
25°F
14°C
0.1
0.2
0.5
0.8
1.2
1.9
ft
m
0.0
0.1
0.2
0.2
0.4
0.6
Page 5
Mini-Therm II Hydronic Boiler
Page 5
consisting entirely of a combination of steel, iron, brick, tile, concrete, slate, glass or plaster.
All boilers can be installed on a combustible floor if a non-combustible base assembly, available from Laars, is used. See the boiler rating plate for the appropriate base part number. Boilers must never be
installed on carpeting.
1/2" Pipe 3/4" Pipe 1" Pipe 1-1/4" Pipe
Size
Pump H.P. Pump H.P. Pump H.P. Pump H.P.
1/25 1/12 1/25 1/12 1/6 1/25 1/12 1/6 1/25 1/12 1/6 50 50 99 390 680 * * * * * * * 75 * 35 160 300 460 640 * * * * *
100 * * 77 150 260 330 620 * * * * 125 * * 27 80 140 170 360 600 * * * 160 * * * 25 72 57 160 330 190 480 * 225 * * * * * * * 110 * 69 330
*A circular and/or primary/secondary piping are required. Consult factory.
1. Chart is based on 30°F (-1°C) maximum temperature rise.
2. Calculations are based on Type L copper tubing with one
zone valve and eight elbows.
3. Typical circulating pumps: 1/25 HP=Taco 007, B&G LR-20 or
SLC-25, Grundfos UP15-42F, or equivalent. 1/ 12, Grundfos UP26-42F, or equivalent. 1/ HV, Grundfos UP43-75, or equivalent.
Table 2. Maximum Suggested Circuit Length in Feet.
Boiler Sizes 50-125 160-225 Clearances in Left side 6 Right side 6 Rear 6 Front 4 Flue 6 Top 23
mm 152 152 152 102 152 484
Table 3. Minimum Boiler Clearances
From Combustible Surfaces.
HP=B&G LR-
12
HP=B&G series
6
in
6 6 6 6 6
36
mm 152 152 152 152 152 914
As an alternative to the Laars non-combustible base plate, the National Fuel Code allows a boiler to be placed on other than a non-combustible surface when such an installation complies with the American Insurance Code. This code specifies the surface under the boiler be protected with hollow masonry no less than 4" (102mm) thick, covered with sheet metal at least 24 ga. in thickness. Such masonry must be laid with ends unsealed, and joints matched in such a way as to provide a free circulation of air from side to side through the masonry (see Figure 3).
12" Min. (305mm)
12" Min.
Hollow
Sheet Metal Cover
Sheet Metal Cover
Min. Thickness 24 Gauge
Min. Thickness 24
Galvanized
Gauge Galvanized
Hollow Concrete
Concrete
Block
Block
Figure 3. Typical Combustible Floor Installation.
1F. Gas Supply and Piping
Review the following instructions before proceeding with the installation.
1. Verify that the boiler is fitted for the proper
type of gas by checking the rating plate. Laars
boilers are normally equipped
to operate below a 2000 foot altitude. Boilers
equipped to operate at higher altitudes have
appropriate stickers or tags attached (next to the
rating plate).
2. Use the figures in Table 4 to provide adequate
gas piping from the gas meter to the boiler.
3. A trap (drip leg) must be provided ahead of the
gas controls (see Figure 4). A manual gas shutoff
valve must also be provided for service
convenience and safety. Check the local codes.
6 (152)
4*
(102)
6 (152)
Dimensions in inches (mm).
*6" for models JV160 to JV225.
6 (152)
Figure 2. Closet and Alcove Installation (see Table 3).
Distance
From Gas
Meter
0-50'
0-15m
50-100'
15-30m
100-200'
30-60m
Note: These figures are for Natural Gas (.65 Sp. Gr.), and are based on 1/2" water column pressure drop. Check supply pressure with a manometer, and local code requirements for variations. For LPG, reduce pipe diameter one size, but maintain a 1/2" minimum diameter. A 'normal' number of Tees and elbows have been taken into allowance.
50 75 100 125 160 225
1/2 3/4 3/4 3/4 1 1
3/4 3/4 3/4 1 1 1-1/4
3/4 1 1 1 1-1/4 1-1/4
Boiler Size
Pipe Size
Table 4. Gas Piping Sizes.
Page 6
Page 6
LAARS HEATING SYSTEMS
4. Disconnect the boiler from the gas supply pipe before pressure testing the pipe for gas leaks. Provide gas supply pressure to the boiler as follows:
Inches Water Column Natural Gas Propane (LP)
Minimum 5.5 10
Maximum 9 14
NOTE: The boiler and all other gas appliances
sharing the boiler gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. Low gas pressure could be an indication of an undersize gas meter and/or obstructed gas supply line.
5. The correct burner manifold gas pressure is stamped on the rating plate. The regulator is pre­set at the factory, and normally requires no further adjustment.
6. Before operating the boiler, the complete gas supply system and all connections must be tested for leaks using a soap solution.
1G. Combustion Air Supply
The boiler location must provide sufficient
air supply for proper combustion, and ventilation of the surrounding area as outlined in the latest edition of ANSI standard Z223.1 or in Canada, CAN/CGA-B149.1 or .2, and any local codes that may be applicable.
In general, these requirements specify that boiler rooms which represent confined spaces should be provided with two permanent air supply openings; one within 12 inches (305mm) of the ceiling, the other within 12 inches (305mm) of the floor.
Outside Air Area*
Boiler Size
50 15
75 20 100 25 125 32 160 40 225 60
*Area indicated is for one of two openings; one at floor level and one at the ceiling, so the total net free area would be double the figures indicated. For special conditions, refer to NFPA54 ANSI Z223.1. In Canada refer to the National Standard CAN1-
B149.1 or .2 which differs from this table.
NOTE: Check with louver manufacturers for Net Free Area of louvers. Correct for screen resistance to the Net Free Area if a screen is installed. Check all local codes applicable to combustion air.
Outside Air
Sq. In.
Area in Sq. In.*
sq cm
97 129 161 206 258 387
Table 5. Minimum Recommended
Air Supply to Boiler Room.
Important
See gas line selection chart, Table 4 previous page, for gas line sizing. In all cases, pipe size is larger than inlet connection on heater. Run pipe size shown in chart and reduce at heater inlet.
Inside Air Area*
Inside Air
Sq. In.
Area in Sq. In.* (sq cm)
100 645 100 645 100 645 125 807 160 1032 225 1452
sq cm
Dimensions in inches (mm)
Dimensions
inches (mm)
Size A B C D E V
50 13-3/8
75 13-3/8 100 16-7/8 125 16-7/8 160 20-3/8 225 25-5/8
340 340 429 429 518 651
27-3/4 27-
3/4 705
28-3/4 28-3/4 28-3/4 31-1/2
705
730 730 730 800
23-5/8 24-1/8 24-1/8 23-5/8 23-5/8 23-1/4
600 613 613 600 600 591
21-3/4 21-3/4 22-3/4 22-3/4 22-3/4 23-3/4
552 552 578 578 578 629
26-1/2 27-1/2 27-1/2 27-1/2 27-1/2 27-1/2
673 699 699 699 699 699
Figure 4. Dimensional Information.
Water Gas Conn. Conn.
in. in.
4
102
5
127
5
127
6
152
6
152
7
178
1-1/4 1/ 2 1-1/4 1/ 2 1-1/4 1/ 2 1-1/4 1/ 2 1-1/4 1/ 2 1-1/4 *3/4*
*1/2 for propane
Page 7
Mini-Therm II Hydronic Boiler
Page 7
Outside Air Supply: When combustion air is
supplied directly through an outside wall, each opening should have a minimum free area of one square inch per 4,000 BTU/h (1.2kW) input of the total input rating of all appliances in the enclosed area.
Inside Air Supply: When combustion is
supplied from inside the building, each opening should have a minimum free area of one square inch per 1,000 BTU/h (0.3kW) input of the total input rating of all appliances in the enclosed area. These openings should never be less than 100 square inches (645 sq. cm).
Note: In Canada, follow Canadian Standard,
CAN/CGA-B149.1, .2 or local codes.
Exhaust Fans or Vents: Any equipment which
exhausts air from the boiler room can deplete the combustion air supply or reverse the natural draft action of the venting system. This could cause flue products to accumulate in the boiler room. Additional air must be supplied to compensate for such exhaust.
The information in Table 5 is not applicable in installations where exhaust fans or blowers of any type are used. Such installations must be designed by qualified engineers.
If a blower or fan is used to supply air to the boiler room, the installer should make sure it does not create drafts which could cause nuisance shutdowns of the pilot. If a blower is necessary to provide adequate combustion air to the boiler, a suitable switch or equivalent must be wired into the boiler control circuit to prevent the boiler from firing unless the blower is operating.
The boiler must be completely isolated and protected from any source of corrosive chemical fumes such as those emitted by trichlorethylene, perchlorethylene, chlorine, etc.
1H. Venting
The draft diverter outlet is to be connected to an unobstructed vent pipe of the same or larger diameter, terminating outside the building. The vent pipe must have a listed vent cap, and extend at least two feet above any object within a ten foot radius. All connections should be made with rustproof sheet metal screws.
IMPORTANT NOTE: Do not use sheet metal screws at the snap lock joints of Type B gas vents.
Do not weld or fasten the vent pipe to the boiler draft diverter. The weight of the stack must not rest on the boiler. easily removable for normal boiler service and inspection.
elbows, reductions and restrictions. Horizontal runs should have at least a 1/4" rise per foot (20mm per meter) in the direction of flow. A vent connector shall be supported for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints.
conditioning or air supply fans. The fans can pick up exhaust flue products from the boiler and return them inside the building, creating a possible health hazard.
when used as a chimney (Type B or equivalent). In cold weather, uninsulated outside vents can chill the rising flue products, blocking the natural draft action of the venting system. This can create a health hazard by spilling flue products into the boiler room. Use engineered venting tables acceptable to the authority having jurisdiction to size the venting pipe or liner.
runs of the pipe which may cause excessive cooling and condensation.
The draft diverter and boiler top must be
Avoid horizontal runs of the vent pipe, and 90°
Avoid terminating boiler vents near air
Always use double-wall or insulated vent pipe
Avoid oversize vent piping or extremely long
Figure 5. Vent Pipe Sizing.
Rule of Thumb: The total length of the vent, including the connector and any offset, should not exceed 15 feet (4.6m) for every inch (25mm) of vent diameter (see Figure 5). Longer total lengths shown in venting tables are based on maximum capacity, not condensation factors.
Before connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions. When inspection reveals that an existing chimney is not safe for the intended application, it shall be rebuilt to conform to nationally recognized standards (see National Building Code or ANSI/NFPA 211), lined or relined with a suitable liner, or replaced with a vent or chimney suitable for the equipment to be attached.
Page 8
Page 8
LAARS HEATING SYSTEMS
1H-1. Common Venting System
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused openings in the common
venting system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is
no blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe
condition.
3. Insofar as it is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to the
common venting system are located and other
spaces of the building. Turn on clothes dryers
and any appliance not connected to the common
venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust
thermostat so appliance will operate
continuously.
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use the
flame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance
remaining connected to the common venting
system properly vents when tested as outlined
above, return doors, windows, exhaust fans,
fireplace dampers and any other gas burning
appliance to their previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so the installation
conforms with the National Fuel Gas Code,
ANSI Z223.1. When resizing any portion of the
common venting system, the common venting
system should be resized to approach the
minimum size as determined using the
appropriate tables in Appendix G in the National
Fuel Gas Code, ANSI Z223.1.
1I. Water Piping of Boiler System
Figure 5 shows ‘typical’ plumbing installations. Be sure to provide unions and gate valves at the
boiler inlet and outlet so it can be isolated for service. Check local codes for specific plumbing requirements before beginning the installation.
An ASME pressure relief valve is supplied on all JV boilers, and is pre-set at 30 PSI. The valve outlet piping must discharge to a drain. Under no circumstances should the relief valve piping be a closed circuit.
A pressure reducing valve (automatic feed) must be used to maintain system at constant proper pressure (see Figure 6). Supply properly installed purge valves to eliminate air from each circuit.
A drain valve is supplied with the boiler, and can be found in the plastic bag shipped with each boiler. This valve is to be installed on the lower right side of the boiler, see Figure 4, and is used for draining the unit. To drain the boiler completely, open the drain
valve and remove the two drain plugs located on the lower left side of the boiler.
Be sure to include air vent devices located at the highest point in the system to eliminate trapped air, and an air elimination device near the outlet side of the JV boiler. Manual vent valves are recommended.
Hot water piping should be supported by suitable hangers or floor stands, NOT by the boiler. Due to expansion and contraction of copper pipe, consideration should be given to the type of hangers used. Rigid hangers could transmit noise through the system caused by the piping sliding in the hangers. It is recommended that padding be used when rigid hangers are installed.
Gas piping should also be supported by suitable hangers or floor stands, not the boiler.
A properly sized expansion tank must be included in the system. Laars offers an aircharged diaphragm-type expansion tank, with an automatic feed valve, which includes a pressure regulator set at 12 psig. The part numbers are:
Less Than 20 Gallons in System A0066800
20 to 45 Gallons in System A0066900
1I-1. By-pass Piping
The following information and suggestions are made on by-pass piping as it affects the temperature rise at the boiler. A boiler temperature rise must be taken on all JV boiler installations. If the temperature rise exceeds 30°F (-1°C), it is an indication that the boiler is not receiving adequate water flow. Check the pump for any obstruction, replace the pump with a larger size where necessary, or install a system by­pass as indicated in Figures 6 and 7.
On JV sizes 125, 160 and 225 with a multiple zone system, a by-pass is required to ensure proper flow in addition to properly sized circulator and piping system.
Page 9
Mini-Therm II Hydronic Boiler
Air Cushion Type Expansion Tank
Purge System
Bypass Valve (Ball Valve)
Optional Feed Water Inlet
Bypass Valve (Ball Valve)
Page 9
Optional
Pump
Location
Flo Checks
(installed at proper places)
Multi-Zone Pump System
JV
Boiler
JV
Boiler
Bypass Valves
Zone Pump
Air Scoop
Feed Water Inlet
Single Circuit System
Zone Pumps
(must be sized properly)
Flo Checks
Feed Water
Air Scoop
Inlet
Multi-Zone Valve System
Flo Checks
(installed at proper places)
Boiler Pump
Primary Secondary Multi-Zone Pump System
JV
Boiler
JV
Boiler
12"
12"
(305mm)
max
max
Air Scoop
Zone Pump
Air Scoop
Zone Pumps
(must be sized properly)
Flo Checks
Feed Water Inlet
Feed Water Inlet
Primary/Secondary Multi-Zone Valve System Low Temperature Installation
KEY:
PUMP CHECK VALVE VALVE ZONE VALVE UNION
Figure 6. Typical Plumbing Installations.
Zone Pump
12"
12"
(305mm)
max
JV
Boiler
max
Feed Water Inlet
Air Scoop
Boiler Pump
Primary/Secondary Multi-Zone Valve System
AUTO AIR BLEEDER
Page 10
Page 10
LAARS HEATING SYSTEMS
Note: On JV sizes 160 and 225 a primary/
secondary piping system is recommended. In this system, a circulator is dedicated to pumping the boiler only. This circulator should be sized for the boiler head loss and flow rate.
The two above piping configurations can also apply to JV sizes 50, 75 and 100, especially in multi­zone installations, but flow rates may be obtained without a by-pass.
All precautions must be taken by the installer to insure that a maximum temperature rise through the boiler does not exceed 30°F (-1°C). The temperature rise on boilers installed in multi-zone systems using zone valves must be taken when the zone of the longest length and/or the zone of the highest head loss is open.
Please note that a 1¼" diameter by-pass with balancing ball valve must be installed if a return water temperature of below 110°F (43°C) is expected under operating conditions (see Figure 7).
1J. Chilled Water Systems
If the boiler is installed in conjunction with refrigeration systems, it shall be installed so that the chilled medium is piped in parallel with the heating boiler with appropriate valves to prevent the chilled medium from entering the heating boiler.
When boiler piping is connected to heating coils, which are in close proximity to refrigerated air circulation, there must be flow control valves or other
From
System
Balancing Ball Valves
To
System
automatic methods to prevent gravity circulation of the boiler water during the cooling cycle.
1K. Electrical Wiring
Follow these instructions to make the necessary
initial electrical connections.
1. Remove the two screws attaching the front cover of the control box.
2. There are four wires coiled in the area on the right side of the control box, supplied with wire nuts: 2 black wires twisted together, a white wire and a brown wire (see Figure 8).
3. Follow the schematics in Figure 9. Remove the wire nut from the two black wires, and connect the hot lead from a 115V power supply to both wires. Secure the three wires with the wire nut. The white, neutral wire should be joined to the other neutral lead coming from the 115V power supply, and the neutral lead coming from the pump. The brown wire attaches to the hot side of the pump.
4. Attach the leads from the wall thermostat to the R and W terminals on the terminal strip, located on the left side of the control box.
5. When using a Laars or field supplied power venter, the proving switch must be connected in series with the hi-limit. See wiring diagrams, Document 1077. See Figure 1 for vent damper connections.
6. Check the boiler wiring and pump for correct voltage, frequency and phase. If the pump circuit is other than 115V, be sure there is an appropriate transformer or relay installed. The pump relay is suitable for pumps of ¾ HP or less.
7. For systems with multiple zone pumps or valves, see Figure 10.
Transformer BLK
In (Return)
Left Side View
A full size by-pass must be installed.
Figure 7. By-pass Piping. Figure 8. Field Wiring Connections.
Out
(Supply)
Drip
Leg
BRN WHT
Pump Relay
BLK - Hot WHT - Neutral
WHT - Neutral BRN - Hot On = Call for heat
115V Field Wiring 115V Factory Wiring
Power Supply 115V AC 60 Hz
To Pump 115V AC 3/4 H.P. Max
Page 11
Mini-Therm II Hydronic Boiler
Page 11
Figure 9a. Wiring Diagram, Spark Ignition System (JVS).
A means of disconnecting the electrical supply must be provided within sight of the boiler. The pump and boiler must be wired as shown to insure that the pump is running whenever the boiler is firing.
WARNING
The boiler must be electrically grounded in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the latest edition of the National Electrical Code, ANSI/NFPA 70, in the U.S. and with latest edition of CSA C22.1 Canadian Electrical Code, Part 1, in Canada. Do not rely on the gas or water piping to ground the metal parts of the boiler. Plastic pipe or dielectric unions may isolate the boiler electrically. Service and maintenance personnel who work on or around the boiler may be standing on wet floors and could be electrocuted by an ungrounded boiler.
Hi-Limit Switch: Factory setting is 190°F (88°C). This setting is correct for normal operations, and should only be changed by an authorized service technician. Under no circumstances should the setting exceed 220°F (104°C).
Flow Switch: If the system includes a flow switch, it should be wired in series with the high-limit
Figure 9b. Schematic, Spark Ignition System (JVS).
Page 12
Page 12
LAARS HEATING SYSTEMS
Figure 9c. Wiring Diagram, Standing Pilot System (JVT).
switch. The boiler will not fire unless the pump is running and the flow switch is closed.
Field installed safety devices and operating controllers, such as a valve end switch, draft switches, relays, timers, and outdoor temperature reset devices, can be connected to the boiler through the wall thermostat circuit. Do not exceed a draw of 30VA on the transformer secondary.
Heat Anticipator: For single zone installations, the wall thermostat heat anticipator should be set at
1.0 amperes. For multi-zone installations, have a qualified electrical technician make the necessary measurements to properly set the thermostats.
1L. Filling the System
It is crucial to the efficient operation of the system that all air be removed from the circuit. For this reason, an air scoop and vent should be located close to the boiler outlet, and there should be a minimum distance between cold water feed and system purge valve.
1. When the system has been completely installed,
close all air vents and open the makeup water
valve. Allow the circuit to fill slowly.
2. If a make-up water pump is employed, adjust the
pressure to provide a minimum of 12 psi
(82.7kPa) at the highest point in the circuit. If a
Figure 9d. Schematic, Standing Pilot System (JVT).
Page 13
Mini-Therm II Hydronic Boiler
Page 13
Wiring with Taco Zone Valves
Wiring with Honeywell Zone Valves
Wiring with Multiple Zone Pumps
Figure 10. Multiple Zone Wiring.
For primary/secondary pumping: Connect to "W" in lieu of "A." Boiler relay is used for boiler pump and connection to "W" will energize boiler pump when any zone is calling for heat.
Page 14
Page 14
LAARS HEATING SYSTEMS
pressure regulator is also installed in the line,
adjust it to the same pressure.
3. Close all gate valves. Purge one circuit at a time
as follows:
a. Open one circuit drain valve and let water
drain out for at least 5 minutes. Be certain there are no air bubbles visible in the water stream before closing the drain valve.
b. Repeat this procedure for each circuit.
4. Open all gate valves after all circuits have been
purged.
5. Run the system circulating pump for a minimum
of 30 minutes with the boiler shut off.
6. Open all strainers in the system, and check for
debris.
7. Recheck all air vents as described in Step 3 above.
8. Some expansion tanks require visual inspection
of liquid level. If necessary, inspect the liquid
level in the expansion tank. With the system
full of water, and under normal operating
pressure, to ensure proper water level in the
expansion tank.
9. Start up boiler according to the procedures
described in Section 2 and operate the system,
including the pump, boiler, and radiation units,
for one hour.
10. Recheck the water level in the expansion tank,
if necessary. If it exceeds ½ of the volume of
the tank, open the tank drain and reduce the
water level.
11. Shut down the entire system, and vent all
radiation units and high points in the system.
12. Close the water makeup valve and check the strainer
in the pressure reducing valve for sediment or
debris. Reopen the water makeup valve.
13. Verify system pressure with the boiler pressure
gauge before beginning regular operation.
Sizes
50-225
50-225
Firing
System
Spark
Ignition
Standing
Pilot
Table 6. Gas Valve Selection.
Type of
Gas
JVS
Natural or
Propane
JVT
Natural or
Propane
Valve
Number
VR8304H Honeywell
VR8300H Honeywell
Manufacturer
SECTION 2 Operation and Maintenance
2A-1. System Start-Up
WARNING
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
1. Verify that the pump system is operating properly:
a. Shut off the manual gas valve located
outside the boiler.
b. Raise the wall thermostat high enough to
call for heat.
c. The pump should come on immediately. If
it doesn't, test the electrical circuits.
2. Pilot Lighting:
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
a. The JVS boilers do not require manual
lighting. The pilot is controlled by the automatic ignition system.
b. The JVT boilers do require manual pilot
lighting. For access to the pilot burner, remove the louvered airbox cover by loosening the two thumb screws.
c. Different models of the JV boiler utilize
various gas valves. Although the gas valves may have different control knobs, they are all similar in operation. The JVS gas valve has a two-position knob, ON and OFF. The JVT valve has a three-position knob, ON, OFF and PILOT, some models come with extra push-button (see Figure 11).
14. Within 3 days of start-up, recheck and bleed all air vents and the expansion tank using these instructions.
VR8304 VR8300
Figure 11. Gas Valves.
Page 15
Mini-Therm II Hydronic Boiler
Page 15
3. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
All Models:
1. Shut off electrical power to the boiler.
2. Turn the gas valve knob clockwise to OFF. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
3. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow 2A-1.3 in “What to do if you smell gas”. If you don't smell gas, go to the next step.
JVS Models:
4. Turn gas valve knob counterclockwise to ON.
5. Restore power to the boiler, and set the thermostat to the desired temperature. The pilot will automatically ignite when there is a call for heat.
JVT Models: (Continuous Pilot)
4. Remove louvered burner cover by loosening the two thumb screws to access the pilot burner.
5. Remove the control box cover to fully access the gas valve.
6. Find pilot - follow metal tube from gas control. The pilot is on the right hand side of the first burner.
7. Turn knob on gas control counterclockwise to PILOT.
8. Push in control knob or push-button all the way and hold in. Immediately light the pilot with a match using the match holder. Continue to hold the control knob in for about one (1) minute after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 2 through 8.
a. If the knob does not pop up when released,
stop and immediately call your service technician or gas supplier.
b. If the pilot will not stay lit after several
tries, turn the gas control knob to OFF and call your service technician or gas supplier.
9. Replace the louvered airbox cover and tighten the two thumb screws securely.
10. Turn gas control knob counterclockwise to ON.
11. Replace control box cover.
12. Restore power to the boiler and adjust the thermostat high enough to call for heat to verify the boiler is operating properly.
13. Set the thermostat to the desired temperature.
2A-2. High Altitude Burner
Air Shutter Replacement
DANGER
This procedure must be followed exactly and must be performed by a qualified installer or warranty may be voided.
DANGER
Read and understand this entire procedure prior to proceeding. Improper adjustment of high altitude shutters may result in a fire, explosion, and/or high levels of toxic gases which may cause property damage, personal injury, or loss of life.
1. STOP! Read the safety information above.
2. Perform System Start-Up in accordance with Section 2A of this manual.
3. Remove burner cover by loosening two (2) thumbscrews.
4. Observe flame pattern on all burners. If the flame on any burner is pulsing, unstable or lifting continue with this procedure. Otherwise skip to step 10.
5. On all burners exhibiting an abnormal flame, loosen but do not remove the air shutter locking screw using a 5/16 inch wrench (see Figure 12).
LOCKING SCREW
(5/16" HEAD)
AIR SHUTTER
BURNER
Figure 12. Air Shutter Adjustment.
Page 16
Page 16
LAARS HEATING SYSTEMS
6. On each affected burner, slowly close the air shutter until a normal flame is observed then re­tighten its associated locking screw.
7. Turn the boiler off.
8. Perform System Start-Up in accordance with Section 2A of this manual.
9. Observe flame pattern on all burners. If the flame on any burner is pulsing, unstable or lifting then repeat steps 5 and 6 until all burners are exhibiting a normal flame.
10. Re-install the burner cover and tighten it in place.
2A-3. Sequence of Operation
1. Wall thermostat calls for heat.
2. The damper activator rotates damper blade to open position. Indicator light comes on.
3. Pump relay will turn on the circulating pump.
4. If water temperature is below the limit setting on the spark ignition models will light the pilot and check the flame existence.
5. After pilot is proven to be lit, the main gas valve will open, the main burners will ignite and continue until either the hi-limit or wall thermostat opens.
6. When the wall thermostat is satisfied, the burners will shut off. The pump relay will turn off the pump, and the damper will close. When the room temperature falls below the wall thermostat setting, the cycle will repeat.
Note: When equipped with pump delay option,
the pump will run for short time after the burners turn off and the damper closes.
2B. Water Temperature Setting
In Canada, for models equipped with modulating
gas valves, in addition to the main gas valve. These controls are factory set at "5" which is satisfactory for most installations. Lower settings may be appropriate for radiant floor systems, or when heating requirements are low. To change the factory setting simply adjust the red knob on the valve to the desired water temperature according to Table 7 (temperatures are approximate).
2C. Maintenance
1. Lubricate the water circulating pump per the instructions on the pump.
2. If a strainer is employed in a pressure reducing valve or the piping, clean it every six months.
3. At start-up, and periodically thereafter, the burner flame should be observed. If the flame has the appearance of 'sooting' tips, check for debris near the orifices and call the service technician.
4. Inspect the venting system for obstruction, leakage or corrosion at least once a year.
5. Keep the boiler area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
6. Be sure that all combustion air and ventilation openings are unobstructed.
7. Upon completion of the installation, inspect the external surfaces of the heat exchanger for fouling based on the following schedule:
24 hours 7 days 30 days 90 days Once every six months thereafter.
8. If the boiler is not going to be used for long periods of time in locations where freezing occurs, it should be completely drained of all water. To accomplish this, there is a drain valve on the right side of the boiler which can be opened. This will drain the right side of the boiler. There are two plugs located on the left side of the heater which must be removed to drain that side. Both sides must be drained.
9. The gas and electric controls on the boiler are engineered for long life and dependable operation, but the safety of the equipment depends on their proper functioning. It is strongly recommended that the basic items listed below be inspected by a qualified service technician every year.
a. Water temperature controls b. Pilot safety system. c. Automatic gas valves. d. Flow sensing safety devices. e. Vent dampers and power venters.
Dial
Number
Temp. °F 120 135 150 165 180 195 210 225 240
Temp. °C 49 57 66 74 82 91 99 107 116
1 2 3 4 5 6 7 8 9
Table 7. Water Temperature Settings.
Figure 13. 1) JVS Pilot; 2) JVH Pilot;
3) Main Burner Flame Pattern; 4) JVT Pilot.
Page 17
Mini-Therm II Hydronic Boiler
Page 17
10. Low water cutoffs should be inspected and flushed periodically.
Note: The Warranty does not cover damage
caused by lack of required maintenance, lack of water flow, or improper operating practices.
Fouling on the external surfaces of the heat
exchanger is caused by incomplete combustion, and is a sign of venting and/or combustion air problems. The heat exchanger can be inspected by using a flashlight and placing a mirror under the burners. An alternate method is to remove the venting and top panel to inspect the exchanger from above. The vent system should be inspected at the same time. If cleaning is required:
a. Shut off all power to the boiler. b. Remove the draft hood, venting top, flue
collector, and heat exchanger baffles.
c. Remove the burners by lifting them off the
orifices and pulling them out of the boiler.
d. Use a hand-operated spray bottle filled with
water, and a wire brush to clean soot and loose scale from the underside of the heat exchanger. DO NOT USE COMPRESSED AIR, HIGH PRESSURE WATER OR A GARDEN HOSE.
e. Clean any fallen debris from the bottom of the unit. f. Check to make sure the burner ports and pilot
assembly are free of debris before returning the burners to their original position.
g. Reassemble the boiler in reverse order, making
sure to replace the heat exchanger baffles.
2D. Electrical Troubleshooting
1. Remove the control box cover on the front of the boiler.
2. Verify that 115V is reaching the boiler by testing across the black wire on the pump relay and the white wire on the transformer.
3. Verify 24V transformer output by placing the meter leads on the yellow and red wires. If 24V is not evident, replace the transformer. Perform the following series of tests with one meter lead attached to the yellow wire on the transformer.
4. Place the second lead on the "W" connection on the terminal board. Turn the wall thermostat high enough to call for heat. If the meter fails to register 24V, the thermostat or its circuit may be defective.
5. Make sure thermostat is set high enough to call for heat. Place second lead on the "A" connec­tion on the terminal board. If voltage is evident, skip to step 6. If no voltage, test the circuit between the red wire on the transformer and terminal 4 on the pump relay; from terminal 6 on
the pump relay and the "A" connection on the terminal board; and from the purple wire termi­nal on the pump relay to the "W" connection on the terminal board. If no output is found, the connections or the pump relay could be defective.
6. Place the second lead on the orange wire termi­nal on the hi-limit switch. If no voltage across the switch, check for defective hi-limit, open circuit due to excessive water temperature, or a low temperature setting.
7. Place the second lead on the orange wire termi­nal on the blocked vent safety switch. If voltage is present, the vent damper is open. If voltage isn't present, connections or the vent damper could be defective.
8. Verify the voltage across the blocked vent and roll-out safety switches.
9. On JVT boilers, test for voltage at the "TH" terminal on the gas valve. If none is found, follow steps 1 through 8.
10. If it is determined that there is voltage to the gas valve, the pilot is lit and the thermocouple is properly positioned, and the thermostat is set high enough to call for heat, the gas valve or the pilot thermocouple may be defective
11. There are two tests necessary to make sure the problem is not in the pilot thermocouple. The first test can be performed by unscrewing the compression fitting on the gas valve, and placing one millivoltmeter lead on the center post of the tube and the other lead on the copper tubing. If the meter shows a reading of approximately 30 millivolts, proceed to the second test. If it doesn't, replace the pilot thermocouple. The second test requires the use of a Millivolt Read­ing Adapter to test the thermocouple under load. Once again, remove the pilot thermocouple compression fitting from the gas valve. Replace it with a Millivolt Reading Adapter, and screw the thermocouple fitting into the end of the adapter. Attach one lead from the millivoltmeter to either side of the adapter and the other lead to ground. Light the pilot and set the wall thermo­stat high enough to call for heat. With the boiler firing, take a millivolt reading. It should be in the 15 millivolt range. If it isn't, replace the pilot thermocouple.
Caution
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Page 18
Page 18
# Symptom Cause Remedy
LAARS HEATING SYSTEMS
1. Pump not A.No power A.Check circuit breakers and power source.
operating B . Pump defective B.Replace.
C.Incorrectly wired C.Recheck wiring diagrams.
2. Pilot outage A. Inlet gas pressure too low A. Consult gas utility company. Inlet gas pressure to boiler
should be 5.5" to 10.0" water column on natural gas. 11.0" to
B.Inlet gas pressure too high causing
an unstable blowing pilot B.Pressure should be regulated within limits shown above. C.Weak or defective thermocouple C.Replace thermocouple. D.Damaged pilot or thermocouple D.Replace. E.Dirty pilot E.Blow dust or lint out of pilot. F. Plugged or undersized pilot orifice F. Clean or replace pilot orifice.
14.0" on propane gas.
3. Flame roll-out A.Blocked flue A.Remove blockage.
on start-up B.Pilot out of position (delayed ignition) B.Correct pilot position.
C.Blocked heat exchanger or flue C.Clean and correct as necessary. D.Refractory tile out of place D.Correct or replace tile as necessary. E.Altered draft diverter E.Install factory-provided draft diverter.
4. Spillage at A.Cold chimney A.Allow boiler to operate 5 minutes to create draft action.
draft hood B.Vent pipe pitches down to chimney B. Reinstall vent pipe to pitch up from boiler to chimney.
C.Blocked chimney C.Remove blockage. D.Draft hood altered D.Install factory-provided draft diverter. E.Pre-fabricated chimney with incorrect cap E.Install U.L. listed vent cap.
5. Flame has A.Low primary air A.Correct manifold pressure according to rating plate. Correct
lazy yellow tip orifice size if necessary (see parts list). Clean burner ports if
dirty.
6. Not enough heat A.Inadequate gas supply A.Gas meter too small. Gas line from meter to boiler too small.
B.Low manifold gas pressure B. Gas pressure on boiler manifold, with Modusnap valve wide
C.Boiler size inadequate C.Replace with boiler of higher input.
open. Should be adjusted to 4.0"W.C. natural gas, 9.0"W.C. propane.
7. Pump noisy A.Air in volute A.Bleed air from volute. Check pump alignment.
B.Worn coupling or bearings B.Replace worn parts.
8. Boiler pounding A. Too low water flow through boiler A. Check temperature rise between inlet and outlet boiler piping.
or knocking 15°F to 25°F temperature rise is recommended. If temperature
rise is over 25°F, increase pipe size or pump capacity or locate obstruction. Check for stuck closed zone valves. Check for zone pumps not operating. Check for closed valve in system.
9. Boiler condensing A. Low water temperature A.Flue product moisture will condense at the start-up until the
boiler water temperature reaches the normal operating conditions.
10. Pump cavitates A.Defective fill valves or pressure regulator A. Replace.
or low water B.Oversized expansion tank B.Replace. pressure at boiler C.Expansion tank piped incorrectly C.Repipe expansion tank to suction size of pump. gauge or bubbles in system at high temperature
11. Pressure relief A.Water-logged expansion tank A.Drain
valve opens
2
/3 of the water from the expansion tank.
12. Pilot is lit but main A.Gas valve not at "on" position A.Turn knob to "on" position.
burners will not B.Boiler off on hi-limit control B. Check for low water flow or hi-limit setting. come on C.Boiler incorrectly wired C.On single or multiple zone systems with zone valves, room
D.Boiler off on blocked vent switch D.Remedy as in symptom #4. Reset the manual reset switch. E.Boiler off on flame roll-out switch E.Remedy as in symptom #3. Reset the manual reset switch. F. Broken wire in thermostat circuit
or defective thermostat F. Check continuity through thermostat circuit with wires
thermostat should be wired to R & W terminals. For multiple zone systems with zone pumps, thermostats for extra zones should be wired to R & A terminals.
disconnected from R & W.
13. Boiler short cycles A.Heat anticipator in room thermostat
set too low A.Increase setting (1.0 is usually satisfactory). B.Low water flow through boiler B.Increase size of pump or increase piping size. C.Hi-limit switch may be set too low C.Increase setting to at least 20°F over outlet water temperature.
Table 8. Troubleshooting Analysis.
Page 19
Mini-Therm II Hydronic Boiler
Troubleshooting Honeywell S8600
Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light.
Start
Turn off gas supply.
Turn thermostat
(controller) to call for
heat.
Power to module
(24V nominal).
YES
Spark across igniter/
sensor gap.
Intermittent Pilot System
To reset, interrupt power to heater
Note: Before troubleshooting, familiarize yourself with the start-up and checkout procedure.
Check line voltage power, low voltage transformer, hi- limit switch,
NO
NO
thermostat (controller) and wiring.
Pull ignition lead and check spark at module. Spark okay?
YES
Page 19
YES
Turn gas supply on.
Pilot burner lights?
YES
Spark stops when pilot
is lit?
YES
Main burner lights?
YES
NO
NO
NO
• Check ignition cable ground wiring, ceramic insulator and gap, and correct.
• Check boot of the ignition cable for signs of melting or buckling. Take protective action to shield cable and boot from excessive temperatures.
• Check that all manual gas valves are open, supply tubing and pressures are good, and pilot burner orifice is not blocked.
• Check electrical connections between module and pilot operator on gas control.
• Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay, replace gas valve; if not, replace module.
Note: If S8600H goes into lockout, reset system. Lockout is used on L.P.G. models.
• Check continuity of ignition cable and ground wire.
• Clean flame rod.
• Check electrical connections between flame rod and module.
• Check for cracked ceramic flame rod insulator.
• Check that pilot flame covers flame rod and is steady and blue.
• Adjust pilot flame.
• If problem persists, replace module.
• Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.
• Check electrical connections between module and gas valve. If okay, replace gas valve.
System runs until call for
heat ends?
YES
Call for heat ends.
System shuts off?
YES
Troubleshooting ends
NO
NO
Note: If S8600H goes into lockout, reset system.
• Check continuity of ignition cable and ground wire. Note: If ground is poor or erratic, shutdowns may occur occasionally even
though operation is normal at the time of checkout.
• Check that pilot flame covers flame rod and is steady and blue.
• If checks are okay, replace module.
• Check for proper thermostat (controller) operation.
• Remove MV lead at module; if valve closes, recheck temperature controller and wiring; if not, replace gas valve.
Repeat procedure until trouble-free operation is obtained.
Page 20
Page 20
LAARS HEATING SYSTEMS
Glossary of Terms
Air Vent
Another device used to purge air from the Circuit. Should be located at the highest point in the Circuit.
Branch
The section(s) of supply and return piping, including the heat distribution units (see below), connected directly to the trunk. Also referred to as a "zone."
By-pass
A section of pipe (including an adjustable valve) that diverts part of the water flow from undersized piping to the boiler. Adjusted to maintain minimum flow requirement (GPM) through the boiler.
Circuit
Entire water circulation piping, beginning and ending at the boiler (Series Loop System).
Expansion Tank (Compression Tank)
Installed in the circuit to accommodate excess water produced by heat expansion.
Heat Distribution Units
Transfers heat from the water supplied by the boiler to the area to be heated through the use of baseboard, convector, radiator, finned tube. Also known as "radiation."
Isolation Valve
Used to isolate the boiler from the circuit. It minimizes the amount of water drained from the system.
Primary-Secondary Piping
Two or more interconnecting circulating loops, each with its own pump. Primary=System Circuit; Secondary=Boiler Circuit.
Reverse-return Piping
Balanced, equal flow (first in, last out) piping. Utilized with multiple boilers and/or radiation. Applied with single system pumps, or primary-secondary pumps.
Side Wall Power Venter
This Laars accessory allows the boiler exhaust to be routed horizontally through an adjoining outside wall, rather than gravity venting with a chimney or stack when local codes allow.
System Purge Valve
A device used to purge air from the circuit. Should be located as close as possible to the cold water feed, but not immediately after the cold water feed.
Trunk
The section of piping which connects the boiler return and supply with the branch(es). Also known as a "main" or "header." Should be same size as boiler inlet/outlet connections.
Vent Damper (optional in Canada) Standard on JV boilers. This energy-saving device prevents heated air from exiting the open vent when the boiler is not operating.
Zone Pump
Circulators installed in branch piping that divert hot water coming from the boiler into various areas (zones) of a building.
Zone Valve
Diverts hot water from the boiler into various areas (zones) of a building.
Page 21
Mini-Therm II Hydronic Boiler
Page 21
SECTION 3. Parts List and Ordering Information
Part Number
Description Model, Size JVS-50 JVT-50 JVS-75 JVT-75 JVS-100 JVT-100 JVS-125 JVT-125
Pilot Gas System
Pilot Assembly (Nat.) W0030600 W0040900 W0030600 W0040900 W0030600 W0040900 W0030600 W0040900 Pilot Assembly (LP) W0039600 W0040901 W0039600 W0040901 W0039600 W0040901 W0039600 W0040901 Thermocouple - W0036500 - W0036500 - W0036500 - W0036500
Main Gas System
Burner W/Pilot Bracket L0056500 L0056500 L0056500 L0056500 L0056500 L0056500 L0056500 L0056500 Burner, Main L0052500 L0052500 L0052500 L0052500 L0052500 L0052500 L0052500 L0052500 Burner/Air Shutter (LP) L0055900 L0055900 L0055900 L0055900 L0055900 L0055900 L0055900 L0055900 Gas Valve, HW., VR8304 (Nat.) V2002200 - V2002200 - V2002200 - V2002200 ­Gas Valve, RS (Nat.) - R0017500 - R0017500 - R0017500 - R0017500 Gas Valve, HW., VR8300 (LP) - V2002100 - V2002100 - V2002100 - V2002100 Gas Valve, HW., VR8304 (LP) V0073600 - V0073600 - V0073600 - V0073600 ­Gas Orifice (Nat.) L0032200 L0032200 L0032200 L0032200 L0032200 L0032200 L0032200 L0032200 Gas Orifice (LP) L0032900 L0032900 L0032900 L0032900 L0032900 L0032900 L0032900 L0032900 Gas Manifold L0052601 L0052601 L0052602 L0052602 L0052603 L0052603 L0052604 L0052604
Electrical System
Relay, DPNO E0088400 E0088400 E0088400 E0088400 E0088400 E0088400 E0088400 E0088400 Transformer 115/24V (40VA) E0086100 E0086100 E0086100 E0086100 E0086100 E0086100 E0086100 E0086100 Ignition Control (S8600F) Nat. E0094001 - E0094001 - E0094001 - E0094001 ­Limit Switch E0098700 E0098700 E0098700 E0098700 E0098700 E0098700 E0098700 E0098700 Control Panel Wiring Harness 20406501 20406501 20406501 20406501 20406501 20406501 20406501 20406501 Power Venter Jumper 20036700 20036700 20036700 20036700 20036700 20036700 20036700 20036700 Terminal Strip E0098500 E0098500 E0098500 E0098500 E0098500 E0098500 E0098500 E0098500 Hi-Tension Lead 10449514 - 10449514 - 10449514 - 10449514 ­Blocked Vent SafetySwitch* E0121000 E0121000 E0121000 E0121000 E0121000 E0121000 E0121000 E0121000 Roll-out Safety Switch E2103200 E2103200 E2103200 E2103200 E2103200 E2103200 E2103200 E2103200 Fuse, 2 amp E2043600 E2043600 E2043600 E2043600 E2043600 E2043600 E2043600 E2043600
Water System
Heat Exchanger 20036601 20036601 20036602 20036602 20036603 20036603 20036604 20036604 Temperature/Pressure Gauge A0000100 A0000100 A0000100 A0000100 A0000100 A0000100 A0000100 A0000100 Pressure Relief Valve, 30PSI A0069000 A0069000 A0069000 A0069000 A0069000 A0069000 A0069000 A0069000 Well, Immersion E2058300 E2058300 E2058300 E2058300 E2058300 E2058300 E2058300 E2058300 Drain Valve 1/2" NPT P0066600 P0066600 P0066600 P0066600 P0066600 P0066600 P0066600 P0066600
Jacket and Fire Box Components
Draft Diverter 20034801 20034801 20034802 20034802 20034803 20034803 20034804 20034804 Rear Panel 20099801 20099801 20099802 20099802 20099803 20099803 20099804 20099804 Side Panel (L&R) 10467900 10467900 10467900 10467900 10467900 10467900 10467900 10467900 Front Panel 10484701 10484701 10484702 10484702 10484703 10484703 104884704 10484704 Top 20099401 20099401 20099402 20099402 20099403 20099403 20099404 20099404 Gap Closure 20099501 20099501 20099502 20099502 20099503 20099503 20099504 20099504 Flue Collector 20034901 20034901 20034902 20034902 20034903 20034903 20034904 20034904 Access Panel HX, (L&R) 10535900 10535900 10535901 10535901 10535900 10535900 10535901 10535901 Base, Control Box 10469200 10469200 10469200 10469200 10469200 10469200 10469200 10469200 Cover, Control Box 10469400 10469400 10469400 10469400 10469400 10469400 10469400 10469400 Burner Cover 10500601 10500601 10500601 10500601 10500602 10500602 10500602 10500602 Heat Exchanger Baffle 10485301 10485301 10485302 10485302 10485303 10485303 10485304 10485304 Tile Cover 10469501 10469501 10469502 10469502 10469503 10469503 10469503 10469504 Refractory, Front T0022001 T0022001 T0022002 T0022002 T0022003 T0021803 T0022004 T0022004 Refractory, Rear T0021701 T0021701 T0021702 T0021702 T0021703 T0021703 T0021704 T0021704 Insulation, Fiberglass T0027300 T0027300 T0027300 T0027300 T0002000 T0027300 T0027300 T0027300 Base Assembly 10467101 10467101 10467012 10467102 10467103 10467103 10467104 10467104 Combustible Base (optional) 10466701 10466701 10466701 10466701 10466702 10466702 10466702 10466702
Vent Damper Components
Automatic Vent Damper Assy., Penn Q35* E2071501 E2071501 E2071502 E2071502 E2071502 E2071502 E2071503 E2071503 Damper Connection Harness* E0099100 E0099100 E0099100 E0099100 E0099100 E0099100 E0099100 E0099100
* Optional in Canada.
Page 22
Page 22
Part Number
Description Model, Size JVS-160 JVT-160 JVS-225 JVT-225
Pilot Gas System
Pilot Assembly (Nat.) W0030600 W0040900 W0030600 W0040900 Pilot Assembly (LP) W0039600 W0040901 W0039600 W0040901 Thermocouple - W0036500 - W0036500
Main Gas System
Burner W/Pilot Bracket L0056500 L0056500 L0056500 L0056500 Burner, Main L0052500 L0052500 L0052500 L0052500 Burner/Air Shutter (LP) L0055900 L0055900 L0055900 L0055900 Gas Valve, HW., VR8304H (Nat.) V2002200 - V2002200 ­Gas Valve, RS (Nat.) - R0017500 - R0017500 Gas Valve, HW., VR8300H (LP) - V2002100 - V2002100 Gas Valve, HW., VR8304H (LP) V0073600 - V0073600 ­Modulating Valve, HWV 5155A 1/2" x 1/2" (Canada) V0051100 V0051100 V0051100 V0051100 Modulating Valve, HWV 5155A 1" x 1" (Canada) - - V0045100† V0045100† Gas Orifice (Nat.) L0050700 L0050700 L0050700 L0050700 Gas Orifice (LP) L0032900 L0032900 L0032900 L0032900 Gas Manifold L0052606 L0052606 L0052607 L0052607
Electrical System
Relay, DPNO E0088400 E0088400 E0088400 E0088400 Transformer 115/24V (40VA) E0086100 E0086100 E0086100 E0086100 Ignition Control (HW S8600F) NAT. E0094001 - E0094001 ­Ignition Control (S8610M) LP. E2102800 - E2102800 ­Limit Switch E0098700 E0098700 E0098700 E0098700 Control Panel Wiring Harness 20406501 20406501 20406501 20406501 Power Venter Jumper 20036700 20036700 20036700 20036700 Terminal Strip E0098500 E0098500 E0098500 E0098500 Hi-Tension Lead 10449515 - 10449516 ­Blocked Vent Switch* E0121000 E0121000 E0121000 E0121000 Roll-out Safety Switch E2103200 E2103200 E2103200 E2103200 Fuse, 2 amp. E2043600 E2043600 E2043600 E2043600
Water System
Heat Exchanger 20036605 20036605 20036606 20036606 Temperature/Pressure Gauge A0000100 A0000100 A0000001 A0000100 Pressure Relief Valve, 30PSI A0069000 A0069000 A0069000 A0069000 Well, Immersion E2058300 E2058300 E2058300 E2058300 Drain Valve 1/2" NPT P0066600 P0066600 P0066600 P0066600
Jacket and Fire Box Components
Draft Diverter 20034805 20034805 20034806 20034806 Rear Panel 20099805 20099805 20099806 20099806 Side Panel (L&R) 10467900 10467900 10467900 10467900 Front Panel 10501605 10501605 10501606 10501606 Top 20099405 20099405 20099406 20099406 Gap Closure 20099504 20099504 20099506 20099506 Flue Collector 20034905 20034905 20034906 20034906 Access Panel HX (L&R) 10535901 10535901 10535901 10535901 Base, Control Box 10469200 10469200 10469200 10469200 Cover, Control Box 10469400 10469400 10469400 10469400 Burner Cover 10494105 10494105 10494106 10494106 Heat Exchanger Baffle 10485305 10485305 10485306 10485306 Tile Cover 10469505 10469505 10469506 10469506 Refractory, Front T0022605 T0022605 T0022606 T0022606 Refractory, Rear T0021705 T0021705 T0021706 T0021706 Insulation, Fiberglass T0027300 T0027300 T0027300 T0027300 Base Assembly 10467105 10467105 10467106 10467106 Combustible Base (Optional) 10466703 10466703 10466704 10466704
Vent Damper Components
Automatic Vent Damper Assy. (Penn Q35)* E2071503 E2071503 E2071504 E2071504 Damper Connection Harness* E0099101 E0099101 E0099101 E0099101
*Optional in Canada
LAARS HEATING SYSTEMS
TO OBTAIN OR ORDER PARTS: Check with your nearest Laars dealer or distributor. They have many of the commonly needed parts in stock. If your dealer cannot supply you, contact the Service Department at Laars. See address and telephone information on back page of this document.
Page 23
Mini-Therm II Hydronic Boiler
Page 23
Figure 13. Parts Identification.
Figure 13 - Parts Identification
Page 24
H0071400W
Waterpik Technologies, Inc. 6000 Condor Drive, Moorpark, CA 93021 • 805.529.2000 • FAX 805.529.5934 20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • F AX 603.335.3355 480 S. Service Road West, Oakville, Ontario, Canada L6K 2H4 • 905.844.8233 • FAX 905.844.2635
www.laars.com
Litho in U.S.A. © Laars Heating Systems 0011 Document 1025W
Loading...