Laars JV User Manual

Installation and Operation Instructions Document 1025W
Installation and Operation Instructions for
Mini-Therm II
Residential Gas-Fired Hydronic Boilers
Vent damper is optional in some provinces of Canada.
These instructions are to be stored in the packet provided on the boiler.
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water boiler installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed exactly , a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
H0071400W
Page 2
LAARS HEATING SYSTEMS
TABLE OF CONTENTS
SECTION 1. General Information
1A. Introduction...................................................3
1B. Warranty....................................................... 3
1C. Field Assembly.............................................3
1D. Flow Requirements ......................................4
1E. Boiler Placement ..........................................4
1F. Gas Supply and Piping .................................5
1G. Combustion Air Supply.................................6
1H. Venting ......................................................... 7
1H-1. Common Venting System............................. 8
1I. Water Piping of Boiler System...................... 8
1I-1. By-pass Piping ............................................. 8
1J. Chilled Water Systems ...............................10
1K. Electrical Wiring.......................................... 10
1L. Filling the System ....................................... 12
SECTION 2. Installation Instructions
2A-1. System Start-up.......................................... 14
2A-2. High Altitude Burner
Air Shutter Replacement ............................ 15
2A-3. Sequence of Operation ..............................16
2B. Water Temperature Setting ........................16
2C. Maintenance ............................................... 16
2D. Electrical Troubleshooting .......................... 17
SECTION 3.
Parts List .................................................... 21
Mini-Therm II Hydronic Boiler
Page 3
SECTION 1. General Information
WARNING
The JV hydronic boiler must be installed in accordance with the procedures detailed in this manual, or the Laars warranty will be voided. The installation must conform to the requirements of the local jurisdiction having authority, and, in the United States, to the latest edition of the National Fuel Gas Code, ANSI Z223.1. In Canada, the installation must conform with the latest edition of CAN/CGA­B149.1 OR .2 installation codes for gas burning appliances, and/or local codes. Any modifications to the boiler, its gas controls, gas orifices, wiring or draft diverter may void the warranty. If field conditions require modifications, consult the factory representative before initiating such modifications.
1A. Introduction
This manual provides information necessary for the installation, operation, and maintenance of Laars Model JV copper tube hydronic boilers. These boilers are available in two configurations; the JVT has a thermocouple/continuous burning pilot, and the JVS has an electronic intermittent ignition device (I.I.D.). Look for the model designation on the rating plate, which can be found on top of the boiler in the right rear corner. If the unit is part of a Mini-Combo II (model MC) Residential Gas-Fired Space/Water Heater, refer also to Document 8001, Mini-Combo II Installation and Operation Instructions.
The Laars automatic vent dampers are standard on all U.S. models. The Laars side wall power venters can be used on both JVS and JVT models. Special instructions for their installation are included in the vent damper and power venter package. Read them carefully before installation.
All application and installation procedures should be reviewed completely before proceeding with the installation. Consult the Laars factory, or local factory representative, with any problems or questions regarding this equipment. Experience has shown that most operating problems are caused by improper installation.
Some accessory items are shipped in separate packages. Verify receipt of all packages listed on the packing slip. Inspect everything for damage immediately upon delivery, and advise the carrier of any shortages or damage. Any such claims should be filed with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment whether visible or concealed.
1C. Field Assembly
1. Mini-Therm II boilers have built-in draft diverter
for natural draft operation.
2. Find the vent damper box which is located in the
boiler package (vent damper is optional in
Canada).
3. Install the vent damper directly to the top of the
draft diverter outlet with the damper operator
facing to the front of the boiler, and with the
flow direction arrow pointing upward. Use the
vent damper wire harness provided with the
boiler to connect the vent damper to the boiler.
The bracket end of the harness should be
connected to the vent damper actuator.
4. For Model JVS only: Install the metal plug
provided with the vent damper onto the damper
plate hole. Disregard the metal plug in case of
standing (continuous) pilot boilers. The damper
plate hole should never be blocked on all JVT
models.
Vent
Damper Vent Damper Harness
(optional in
Canada)
Draft Diverter
(built-in)
1B. Warranty
The Laars Model JV boilers are covered by a limited warranty. The owner should fill out the warranty registration card and return it to Laars.
All warranty claims must be made to an authorized Laars representative or directly to the factory. Claims must include the boiler serial number and model (this information can be found on the rating plate), installation date, and name of the installer. Shipping costs are not included in the warranty coverage.
Figure 1. Vent Damper Installation.
Page 4
LAARS HEATING SYSTEMS
5. The field assembly is now complete. The boiler is ready for water, gas and electrical connections and venting installation.
6. Do not modify the automatic vent damper device. It is very important that no other vents are closed. Provide at least six inches clearance between the automatic vent damper and combustible construction, and be sure to allow access for servicing the damper.
Caution
Do not force motor operation when operator is fastened to the damper by moving the damper blade, turning the shaft or by turning the position indicator.
Note: In Canada, the vent damper is optional.
1D. Flow Requirements
All high recovery, low volume water boilers
must have adequate flow for efficient operation. Pump selection is critical to this goal, and pumps should be selected to provide for system design water temperature rise. Table 1 details temperature rise and water flow (GPM) for the Mini-Therm boilers.
Damage from improper flow is not warranted.
Failure to insure proper water flow through the
heat exchanger of the boiler will void the Laars warranty. Flow can be verified by measuring the difference in water temperatures between the boiler inlet and outlet. For example: For a JV-100 installation, the inlet water temperature is 160°F (71°C), and the outlet temperature is 180°F (82°C). That means there is a 20° (-7°C) temperature rise through the boiler. According to Table 1, that would indicate a flow rate of 8 GPM (0.5L/S). Temperature rise must be measured with the longest (highest head) zone calling for heat alone.
Other factors to be considered before selecting a pump are pipe size, the number of fittings throughout the system, smoothness of the interior surface of the pipe, the quantity of water flowing through the pipe, whether a glycol solution is being used, and the total length of piping in the system. Table 2 can help in making that determination.
1E. Boiler Placement
The boiler must be placed to provide clearances on all sides for maintenance and inspection. There must also be minimum distances maintained from combustible surfaces.
At least 15" (381mm) access must be available in front of the boiler for burner removal. Consult local codes for clearances to hot water pipes and accessories.
If the boiler is to be installed in a garage, all burners and burner ignition devices must have a minimum 18" (457mm) clearance above the floor.
The Model JV-50 through JV-100 boilers can be installed in a closet, as long as the minimum clearances shown in Table 3 are observed. Special attention should be paid to clearances between the front of the boiler and the closet door when it is closed.
Consult the American National Standard Z21.13 for more information concerning closet installations. In Canada, refer to the latest edition of CAN/CGA­B149.1 and 2.
IMPORTANT: The boiler shall be installed on a floor of non-combustible construction with non­combustible flooring and surface finish and with no combustible materials against the underside, or on fire-resistant slabs or arches having no combustible materials against the underside unless listed for installation on a combustible floor.
All boilers must be installed on a non­combustible surface. That means a surface not capable of being ignited and burning, such as surfaces
8°C
15°F
Size
50 5.3
75 8.0 100 10.7 125 13.3 160 17.0 225 24.0
ft = Pressure drop (headloss) through the boilerin feet of water.
Flow Rate Headloss Flow Rate Headloss Flow Rate Headloss
gpm
l/s
0.3
0.5
0.7
0.8
1.1
1.5
ft
0.3
0.6
1.3
2.2
2.5
5.0
gpm = Water Flow in gallons per minute.
Note: Shaded area is the recommended flow and temperature rise.
m
0.1
0.2
0.4
0.7
0.8
1.5
gpm
4.0
6.0
8.0
10.0
12.8
18.0
Table 1. Temperature Rise °F °C.
11°C
20°F
l/s
0.3
0.4
0.5
0.6
0.8
1.1
m = Pressure drop (headloss) through the boiler in meters of water.
ft
0.2
0.3
0.7
1.3
1.8
3.1
l/s = Water flow in liters per second.
m
0.1
0.1
0.2
0.4
0.5
0.9
gpm
3.2
4.8
6.4
8.0
10.2
14.4
l/s
0.2
0.3
0.4
0.5
0.6
0.9
25°F
14°C
0.1
0.2
0.5
0.8
1.2
1.9
ft
m
0.0
0.1
0.2
0.2
0.4
0.6
Mini-Therm II Hydronic Boiler
Page 5
consisting entirely of a combination of steel, iron, brick, tile, concrete, slate, glass or plaster.
All boilers can be installed on a combustible floor if a non-combustible base assembly, available from Laars, is used. See the boiler rating plate for the appropriate base part number. Boilers must never be
installed on carpeting.
1/2" Pipe 3/4" Pipe 1" Pipe 1-1/4" Pipe
Size
Pump H.P. Pump H.P. Pump H.P. Pump H.P.
1/25 1/12 1/25 1/12 1/6 1/25 1/12 1/6 1/25 1/12 1/6 50 50 99 390 680 * * * * * * * 75 * 35 160 300 460 640 * * * * *
100 * * 77 150 260 330 620 * * * * 125 * * 27 80 140 170 360 600 * * * 160 * * * 25 72 57 160 330 190 480 * 225 * * * * * * * 110 * 69 330
*A circular and/or primary/secondary piping are required. Consult factory.
1. Chart is based on 30°F (-1°C) maximum temperature rise.
2. Calculations are based on Type L copper tubing with one
zone valve and eight elbows.
3. Typical circulating pumps: 1/25 HP=Taco 007, B&G LR-20 or
SLC-25, Grundfos UP15-42F, or equivalent. 1/ 12, Grundfos UP26-42F, or equivalent. 1/ HV, Grundfos UP43-75, or equivalent.
Table 2. Maximum Suggested Circuit Length in Feet.
Boiler Sizes 50-125 160-225 Clearances in Left side 6 Right side 6 Rear 6 Front 4 Flue 6 Top 23
mm 152 152 152 102 152 484
Table 3. Minimum Boiler Clearances
From Combustible Surfaces.
HP=B&G LR-
12
HP=B&G series
6
in
6 6 6 6 6
36
mm 152 152 152 152 152 914
As an alternative to the Laars non-combustible base plate, the National Fuel Code allows a boiler to be placed on other than a non-combustible surface when such an installation complies with the American Insurance Code. This code specifies the surface under the boiler be protected with hollow masonry no less than 4" (102mm) thick, covered with sheet metal at least 24 ga. in thickness. Such masonry must be laid with ends unsealed, and joints matched in such a way as to provide a free circulation of air from side to side through the masonry (see Figure 3).
12" Min. (305mm)
12" Min.
Hollow
Sheet Metal Cover
Sheet Metal Cover
Min. Thickness 24 Gauge
Min. Thickness 24
Galvanized
Gauge Galvanized
Hollow Concrete
Concrete
Block
Block
Figure 3. Typical Combustible Floor Installation.
1F. Gas Supply and Piping
Review the following instructions before proceeding with the installation.
1. Verify that the boiler is fitted for the proper
type of gas by checking the rating plate. Laars
boilers are normally equipped
to operate below a 2000 foot altitude. Boilers
equipped to operate at higher altitudes have
appropriate stickers or tags attached (next to the
rating plate).
2. Use the figures in Table 4 to provide adequate
gas piping from the gas meter to the boiler.
3. A trap (drip leg) must be provided ahead of the
gas controls (see Figure 4). A manual gas shutoff
valve must also be provided for service
convenience and safety. Check the local codes.
6 (152)
4*
(102)
6 (152)
Dimensions in inches (mm).
*6" for models JV160 to JV225.
6 (152)
Figure 2. Closet and Alcove Installation (see Table 3).
Distance
From Gas
Meter
0-50'
0-15m
50-100'
15-30m
100-200'
30-60m
Note: These figures are for Natural Gas (.65 Sp. Gr.), and are based on 1/2" water column pressure drop. Check supply pressure with a manometer, and local code requirements for variations. For LPG, reduce pipe diameter one size, but maintain a 1/2" minimum diameter. A 'normal' number of Tees and elbows have been taken into allowance.
50 75 100 125 160 225
1/2 3/4 3/4 3/4 1 1
3/4 3/4 3/4 1 1 1-1/4
3/4 1 1 1 1-1/4 1-1/4
Boiler Size
Pipe Size
Table 4. Gas Piping Sizes.
Page 6
LAARS HEATING SYSTEMS
4. Disconnect the boiler from the gas supply pipe before pressure testing the pipe for gas leaks. Provide gas supply pressure to the boiler as follows:
Inches Water Column Natural Gas Propane (LP)
Minimum 5.5 10
Maximum 9 14
NOTE: The boiler and all other gas appliances
sharing the boiler gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. Low gas pressure could be an indication of an undersize gas meter and/or obstructed gas supply line.
5. The correct burner manifold gas pressure is stamped on the rating plate. The regulator is pre­set at the factory, and normally requires no further adjustment.
6. Before operating the boiler, the complete gas supply system and all connections must be tested for leaks using a soap solution.
1G. Combustion Air Supply
The boiler location must provide sufficient
air supply for proper combustion, and ventilation of the surrounding area as outlined in the latest edition of ANSI standard Z223.1 or in Canada, CAN/CGA-B149.1 or .2, and any local codes that may be applicable.
In general, these requirements specify that boiler rooms which represent confined spaces should be provided with two permanent air supply openings; one within 12 inches (305mm) of the ceiling, the other within 12 inches (305mm) of the floor.
Outside Air Area*
Boiler Size
50 15
75 20 100 25 125 32 160 40 225 60
*Area indicated is for one of two openings; one at floor level and one at the ceiling, so the total net free area would be double the figures indicated. For special conditions, refer to NFPA54 ANSI Z223.1. In Canada refer to the National Standard CAN1-
B149.1 or .2 which differs from this table.
NOTE: Check with louver manufacturers for Net Free Area of louvers. Correct for screen resistance to the Net Free Area if a screen is installed. Check all local codes applicable to combustion air.
Outside Air
Sq. In.
Area in Sq. In.*
sq cm
97 129 161 206 258 387
Table 5. Minimum Recommended
Air Supply to Boiler Room.
Important
See gas line selection chart, Table 4 previous page, for gas line sizing. In all cases, pipe size is larger than inlet connection on heater. Run pipe size shown in chart and reduce at heater inlet.
Inside Air Area*
Inside Air
Sq. In.
Area in Sq. In.* (sq cm)
100 645 100 645 100 645 125 807 160 1032 225 1452
sq cm
Dimensions in inches (mm)
Dimensions
inches (mm)
Size A B C D E V
50 13-3/8
75 13-3/8 100 16-7/8 125 16-7/8 160 20-3/8 225 25-5/8
340 340 429 429 518 651
27-3/4 27-
3/4 705
28-3/4 28-3/4 28-3/4 31-1/2
705
730 730 730 800
23-5/8 24-1/8 24-1/8 23-5/8 23-5/8 23-1/4
600 613 613 600 600 591
21-3/4 21-3/4 22-3/4 22-3/4 22-3/4 23-3/4
552 552 578 578 578 629
26-1/2 27-1/2 27-1/2 27-1/2 27-1/2 27-1/2
673 699 699 699 699 699
Figure 4. Dimensional Information.
Water Gas Conn. Conn.
in. in.
4
102
5
127
5
127
6
152
6
152
7
178
1-1/4 1/ 2 1-1/4 1/ 2 1-1/4 1/ 2 1-1/4 1/ 2 1-1/4 1/ 2 1-1/4 *3/4*
*1/2 for propane
Mini-Therm II Hydronic Boiler
Page 7
Outside Air Supply: When combustion air is
supplied directly through an outside wall, each opening should have a minimum free area of one square inch per 4,000 BTU/h (1.2kW) input of the total input rating of all appliances in the enclosed area.
Inside Air Supply: When combustion is
supplied from inside the building, each opening should have a minimum free area of one square inch per 1,000 BTU/h (0.3kW) input of the total input rating of all appliances in the enclosed area. These openings should never be less than 100 square inches (645 sq. cm).
Note: In Canada, follow Canadian Standard,
CAN/CGA-B149.1, .2 or local codes.
Exhaust Fans or Vents: Any equipment which
exhausts air from the boiler room can deplete the combustion air supply or reverse the natural draft action of the venting system. This could cause flue products to accumulate in the boiler room. Additional air must be supplied to compensate for such exhaust.
The information in Table 5 is not applicable in installations where exhaust fans or blowers of any type are used. Such installations must be designed by qualified engineers.
If a blower or fan is used to supply air to the boiler room, the installer should make sure it does not create drafts which could cause nuisance shutdowns of the pilot. If a blower is necessary to provide adequate combustion air to the boiler, a suitable switch or equivalent must be wired into the boiler control circuit to prevent the boiler from firing unless the blower is operating.
The boiler must be completely isolated and protected from any source of corrosive chemical fumes such as those emitted by trichlorethylene, perchlorethylene, chlorine, etc.
1H. Venting
The draft diverter outlet is to be connected to an unobstructed vent pipe of the same or larger diameter, terminating outside the building. The vent pipe must have a listed vent cap, and extend at least two feet above any object within a ten foot radius. All connections should be made with rustproof sheet metal screws.
IMPORTANT NOTE: Do not use sheet metal screws at the snap lock joints of Type B gas vents.
Do not weld or fasten the vent pipe to the boiler draft diverter. The weight of the stack must not rest on the boiler. easily removable for normal boiler service and inspection.
elbows, reductions and restrictions. Horizontal runs should have at least a 1/4" rise per foot (20mm per meter) in the direction of flow. A vent connector shall be supported for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints.
conditioning or air supply fans. The fans can pick up exhaust flue products from the boiler and return them inside the building, creating a possible health hazard.
when used as a chimney (Type B or equivalent). In cold weather, uninsulated outside vents can chill the rising flue products, blocking the natural draft action of the venting system. This can create a health hazard by spilling flue products into the boiler room. Use engineered venting tables acceptable to the authority having jurisdiction to size the venting pipe or liner.
runs of the pipe which may cause excessive cooling and condensation.
The draft diverter and boiler top must be
Avoid horizontal runs of the vent pipe, and 90°
Avoid terminating boiler vents near air
Always use double-wall or insulated vent pipe
Avoid oversize vent piping or extremely long
Figure 5. Vent Pipe Sizing.
Rule of Thumb: The total length of the vent, including the connector and any offset, should not exceed 15 feet (4.6m) for every inch (25mm) of vent diameter (see Figure 5). Longer total lengths shown in venting tables are based on maximum capacity, not condensation factors.
Before connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions. When inspection reveals that an existing chimney is not safe for the intended application, it shall be rebuilt to conform to nationally recognized standards (see National Building Code or ANSI/NFPA 211), lined or relined with a suitable liner, or replaced with a vent or chimney suitable for the equipment to be attached.
Page 8
LAARS HEATING SYSTEMS
1H-1. Common Venting System
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused openings in the common
venting system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is
no blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe
condition.
3. Insofar as it is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to the
common venting system are located and other
spaces of the building. Turn on clothes dryers
and any appliance not connected to the common
venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust
thermostat so appliance will operate
continuously.
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use the
flame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance
remaining connected to the common venting
system properly vents when tested as outlined
above, return doors, windows, exhaust fans,
fireplace dampers and any other gas burning
appliance to their previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so the installation
conforms with the National Fuel Gas Code,
ANSI Z223.1. When resizing any portion of the
common venting system, the common venting
system should be resized to approach the
minimum size as determined using the
appropriate tables in Appendix G in the National
Fuel Gas Code, ANSI Z223.1.
1I. Water Piping of Boiler System
Figure 5 shows ‘typical’ plumbing installations. Be sure to provide unions and gate valves at the
boiler inlet and outlet so it can be isolated for service. Check local codes for specific plumbing requirements before beginning the installation.
An ASME pressure relief valve is supplied on all JV boilers, and is pre-set at 30 PSI. The valve outlet piping must discharge to a drain. Under no circumstances should the relief valve piping be a closed circuit.
A pressure reducing valve (automatic feed) must be used to maintain system at constant proper pressure (see Figure 6). Supply properly installed purge valves to eliminate air from each circuit.
A drain valve is supplied with the boiler, and can be found in the plastic bag shipped with each boiler. This valve is to be installed on the lower right side of the boiler, see Figure 4, and is used for draining the unit. To drain the boiler completely, open the drain
valve and remove the two drain plugs located on the lower left side of the boiler.
Be sure to include air vent devices located at the highest point in the system to eliminate trapped air, and an air elimination device near the outlet side of the JV boiler. Manual vent valves are recommended.
Hot water piping should be supported by suitable hangers or floor stands, NOT by the boiler. Due to expansion and contraction of copper pipe, consideration should be given to the type of hangers used. Rigid hangers could transmit noise through the system caused by the piping sliding in the hangers. It is recommended that padding be used when rigid hangers are installed.
Gas piping should also be supported by suitable hangers or floor stands, not the boiler.
A properly sized expansion tank must be included in the system. Laars offers an aircharged diaphragm-type expansion tank, with an automatic feed valve, which includes a pressure regulator set at 12 psig. The part numbers are:
Less Than 20 Gallons in System A0066800
20 to 45 Gallons in System A0066900
1I-1. By-pass Piping
The following information and suggestions are made on by-pass piping as it affects the temperature rise at the boiler. A boiler temperature rise must be taken on all JV boiler installations. If the temperature rise exceeds 30°F (-1°C), it is an indication that the boiler is not receiving adequate water flow. Check the pump for any obstruction, replace the pump with a larger size where necessary, or install a system by­pass as indicated in Figures 6 and 7.
On JV sizes 125, 160 and 225 with a multiple zone system, a by-pass is required to ensure proper flow in addition to properly sized circulator and piping system.
Loading...
+ 16 hidden pages