Installation, Operation and Maintenance InstructionsDocument 2108C
Installation,
Operation and
Maintenance
Instructions for
9600 HWG
Condensing Water
Heater for Natural Gas
or Propane
ModelsHWG-M2-150
HWG-M2-175
HWG-M2-200
HWG-M2-250
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualified in hot water boiler installation and maintenance. Improper installation and/or operation could
create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death.
Improper installation and/or operation will void the warranty.
If the information in this manual is not
WARNING
followed exactly, a fire or explosion may
result causing property damage, personal
injury or loss of life.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from a
nearby phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call
the fire department.
Installation and service must be performed by a
qualified installer, service agency, or gas
supplier.
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion ou
pour éviter tout dommage matériel, toute
blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni
d’autres vapeurs ou liquides inflammables dans
le voisinage de cet appareil ou de tout autre
appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous
servir des téléphones dansle bâtiment où vous
vous trouvez.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualifié ou
par le fournisseur de gaz.
To the Installer: After installation these instructions
must be given to the owner or left on or near the
Water Heater.
To the User: This booklet contains important
information that will help you in maintaining and
operating this Water Heater. Please retain it for
future reference.
Warning: Should overheating occur or the gas
supply fail to shut off, turn off the manual gas
control valve to the appliance.
Important: This unit must be installed in
accordance with state and local codes by a qualified
installer!
9600 HWG Water Heater
p
Page 3
SECTION 1.
Introduction & Unpacking
1.1 Special Installation Considerations
BEFORE YOU BEGIN:
It is important for you to take a few minutes to
review this Installation and Operating Instructions
manual before you begin installation. This will make
installing and operating the unit easier and faster.
Direct vent-sealed combustion.
The 9600 HWG Water Heater does not and
should not take combustion air from inside the
building. All of the air is drawn in from the outdoors
through a 3-inch diameter plastic pipe. 3" PVC, ABS
or CPVC pipe is used for air intake and exhaust
venting. (PVC not permitted on HWG-M2-250
exhaust)
No chimney......flue......or draft inducer required.
Because this is a sealed combustion, forced draft unit,
it does not require, and must not be connected to a
chimney, existing venting system, or draft inducer.
CAUTION
Connection of this vent to a chimney, existing
venting system, or draft inducer will result in
poor and possibly dangerous operation.
The supplied vent terminations are designed to
be installed through the nearest outside wall (see
Sections 2C and 2D).
The 9600 HWG Water Heater is protected
against over pressurization. A 150 PSI pressure relief
valve is fitted to the unit. It is installed in the
dedicated fitting on the top of the water heater.
IMPORTANT: The inlet gas pressure to the
appliance must not exceed 13" WC.
A high quality circulator is built into the 9600
HWG Water Heater and will provide sufficient head
pressure and volume to circulate water to the storage
tank(s) (see Table 3).
All installations must be made in accordance
with the: 1) American National Standard Z223.1Latest Edition “National Fuel Gas Code” and with the
requirement of the local utility or other authorities
having jurisdiction, or; 2) Can-CGA B149 installation
code and / or local installation codes.
Such applicable requirements take precedence
over the general instructions contained herein.
All electrical wiring is to be done in accordance
with local codes, or in the absence of local codes,
with: 1) the National Electrical Code ANSI/NFPA
No. 70-latest Edition, or; 2) CSA standard C22.1
“Canadian Electrical Code - Pt 1. This appliance
must be electrically grounded in accordance with
these codes.
1.2 Materials Installer Must Provide
1.Total combined feet allowed for intake and exhaust
vent pipe per instructions. The following are acceptable materials for intake and exhaust vents:
Acceptable Intake Pipe Material
Models 150-200Model 250
3-inch or 4-inch PVC schedule
40 pipe per ASTM D-1785 std.
3-inch or 4-inch PVC DWV
pipe per ASTM D-2665 std.
3-inch or 4-inch ABS-DWV
pipe per ASTM D-2661 std. or
ASTM F-628 std.
3-inch or 4-inch CPVC
schedule 40 or 80 pipe per
ASTM F441 std.
3-inch or 4-inch AL29-4C
stainless steel complying with
UL std. 1738.
Acce
table Intake Pipe Material
Models 150-200Model 250
3-inch or 4-inch PVC schedule
40 pipe per ASTM D-1785 std.
3-inch or 4-inch PVC DWV
pipe per ASTM D-2665 std.
3-inch or 4-inch ABS-DWV
pipe per ASTM D-2661 std. or
ASTM F-628 std.
3-inch or 4-inch CPVC
schedule 40 or 80 pipe per
ASTM F441 std.
3-inch or 4-inch AL29-4C
stainless steel complying with
UL std. 1738.
2.Electrical connection to a 120VAC/15Amp
service.
3.Gas connection that will provide 250 cubic feet/
hour at 4 to 13 inch water gauge pressure.
4.Condensate drainage: a floor drain is preferred a condensate pump may be used.
5.Miscellaneous copper fittings and bronze valves
will be required to complete the piping system.
3-inch or 4-inch PVC schedule
40 pipe per ASTM D-1785 std.
3-inch or 4-inch PVC DWV
pipe per ASTM D-2665 std.
3-inch or 4-inch ABS-DWV
pipe per ASTM D-2661 std. or
ASTM F-628 std.
3-inch or 4-inch CPVC
schedule 40 or 80 pipe per
ASTM F441 std.
3-inch or 4-inch AL29-4C
stainless steel complying with
UL std. 1738.
3-inch or 4-inch CPVC
schedule 40 or 80 pipe per
ASTM F441 std.
3-inch or 4-inch AL29-4C
stainless steel complying with
UL std. 1738.
Page 4
LAARS Heating Systems
1.3 Unpacking
The 9600 HWG Water Heater is shipped in a
single carton with the following standard components
on top of the unit (see Figure 1).
1) Exhaust terminal
2) Intake terminal
3) Vent terminal backing plate (4)
4) Hubless coupling reducer
5) Hubless coupling (2)
Figure 1. Contents of shipping package.
1.Remove all packing and tie-down materials.
2.Check contents of the carton against items
shown above.
MinimumRecommended
ClearancesClearance for
FromAccessibility
Combustibleand Venting
Construction
BOTHAGACGA
Left Side1"6"48"
Right Side (Controls)1"12"24"
Top1"14"24"
Back1" 9"24"
Front1"24"48"
Vent0"
Table 1. Location clearances.
SECTION 2.
Locating and Clearances
2.1 Locating the 9600 HWG
The appliance should be located in an area
where leakage of any connections will not result in
damage to the area adjacent to the appliance or to
lower floors of the structure.
When such a location is not available, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance.
The unit is design certified by AGA / CGA for
installation on combustible flooring; in basements; in
closets, utility rooms or alcoves. It must not be
installed on carpeting.
The location for the unit should be chosen with
regard to the vent pipe lengths, external plumbing,
ventilation of operating components and accessibility
for service and cleaning.
If there is potential for snow accumulation in your
area, both the vent terminals should be installed at an
appropriate level above grade (see Figures 2 and 3).
The following dimensions and requirements
should be met when choosing the location for the unit
(see Table 1):
Figure 2. Suggested vent terminal installations.
2.2 Locating the Unit for Proper Venting
Distance from the Outside Wall or
Roof Termination
Intake Terminal isExhaust Terminal is
P/N 2400-102.P/N 2400-104.
Equivalent feet is determined by adding 10
linear feet for each 90° elbow and 5 linear feet for
each 45° elbow to be installed to the actual linear feet
of pipe required.
Example: 8' of pipe, 2 x 45° elbows and a 90°
elbow.
Equivalent Feet: 8' + (2 x 5') + (1 x 10') = 28.
9600 HWG Water Heater
Exhaust
Terminal
NOTE: If flue passes through a flat
roof with parapet walls exhaust terminal
level must be above the level of the wall.
If flue passes through a sloped or
peaked roof it is not necessary to locate
it to conform with location requirements
for conventional chimneys.
Typical Soil Pipe
Flashing Acceptable
Figure 3. Alternate vent terminal installations.
Roof terminals for air
intake
entry of rain water.
Intake
Terminal
must prevent
18"
Min.
Page 5
units, refer to Figure 4 for intake and exhaust
terminal locations.
2.4 Locating Unit for Proper Vent Height
The vent locations you select must permit direct
pipe runs to the terminal from the boiler. Since the
9600 HWG Water Heater is designed to drain any
water that collects in the vent, it is important that you
do not build any traps or low points into the vent
where water could collect and restrict the vent. It is
recommended that 1/4" per foot of vent be built into
the vent system to direct any water in the vent back
toward the boiler. Note that standard DWV elbows
have a built in allowance for the required 1/4" per foot
pitch.
If a 4" pipe size is used to permit longer vent
runs the installer must supply 4" hubless couplings (2)
and 3 x 4 bushings (2) to adapt to the unit fittings. 4"
inlet and exhaust screens are provided for installation
in contractor provided 4" coupling and elbow
terminations.
NOTE: It is required that a minimum separation
of 18" be maintained between the intake and exhaust
terminals and that both terminals be installed on the
same wall of the building. The intake terminal must
not be installed above the exhaust terminal since this
would tend to pull exhaust gases back into the intake
(see Figures 2 and 3).
2.3 Locating Vent Openings on Outside Wall
1.Exhaust terminal location.
The exhaust terminal fitting requires a 4" (10cm)
diameter hole through the outside wall. The
center line of this opening must be at least 18"
(46cm) above grade and at least 14" (35.6cm)
from any other building opening such as doors,
windows, etc.
Vent opening should be well away from
shrubbery or other obstructions that would block
or restrict the exhaust.
Whenever possible, locations under windows or
near doors should be avoided. Steaming at the
flue terminal is a normal occurrence. This should
be considered when deciding flue terminal
position.
2.Intake terminal location.
The intake terminal requires a separate 4"
(10cm) diameter hole to install the intake fitting.
The center line of the hole should be at least 16"
(41cm) above grade outdoors and 18" (46cm)
away from the exhaust outlet. The intake should
never be located above the exhaust terminal.
3.Intake and exhaust location for multiple unit
installation. For the installations of multiple
2.5 Locating Unit with Respect to Ventilation
While the 9600 HWG Water Heater requires no
indoor air for combustion, adequate airflow around
the unit must be provided for proper cooling of
electrical components.
EXHAUST
INTAKE
Figure 4. Multiple units minimum vent terminal
separation.
2.6 Locating Unit with Respect to
Storage Tanks
For the best results the 9600 HWG Water Heater
should be located within 10 feet of the storage tanks.
If the unit must be installed with longer piping
runs, then the larger diameter tubing must be used.
Calculate the necessary pipe size for your installation
(see Table 2).
SECTION 3.
Installation
3.1 Installing Vent Piping Terminal
The water heater is provided with intake and
exhaust terminals for use with 3" diameter plastic
pipe.
The installer is responsible for obtaining the vent
pipe and fittings. The maximum combined length of
the intake and exhaust pipe and maximum number of
elbows are determined by using the guidelines on Page
4.
Page 6
LAARS Heating Systems
The following steps are recommended for vent
installation:
1.Obtain the necessary 3" or 4" diameter plastic
piping and fittings as determined beforehand.
2.Position unit at previously selected location.
3.Unpack vent terminals and vent terminal backing
plates.
4.Cut holes in outside wall for vent terminals in
the previously selected locations.
5.Mount the vent terminals’ backing plates.
6.Fit all of the vent pipes together without
cementing. Make sure that there are no water
traps and that any pitch is inclined back towards
the boiler.
7.Make sure that the flexible vent connections at
the unit fit properly.
8.Begin cementing the intake and exhaust pipes,
start at the vent terminals and work back towards
the appliance. Note that the intake terminal is a
90 degree elbow fitting that is designed to face
down.
9.Support both intake and exhaust pipes with
hangers.
DO NOT RELY ON 9600 HWG TO SUPPORT
PIPES.
Horizontal runs must be supported adjacent to
each fitting and at 5ft. intervals between fittings.
ABS pipe must be supported at 3ft. intervals.
10.Tighten the flexible couplings to connect the
water heater to the vent pipes.
3.2 Connecting Gas to the 9600 HWG
Water Heater
1.The water heater requires gas at an inlet gas
pressure of at least 4" WC and no greater than
13" WC. Check with your local gas utility or
supplier for availability of these delivery
pressures.
2.Referring to TABLE 2, size supply piping to
keep flow capacity to the unit above 250 cubic
feet per hour (CFH) per unit installed.
3.Run gas supply line in accordance with all
applicable codes.
4.Locate and install manual shutoff valves in
accordance with state and local requirements.
5.Install drip leg and ground joint union
(see Figure 5).
6.All threaded joints should be coated with piping
compound resistant to action of liquefied
petroleum gas.
7.The 9600 HWG unit and its individual shutoff
valve must be disconnected from the gas supply
Additional length to be added for each tee or bend:
1.7'2.2'2.7'
Table 2. Gas supply piping.
piping during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.45kpa).
It must be isolated from the gas supply system
by closing its individual manual shutoff valve
during any pressure testing of the gas supply
piping system at test pressures equal to or less
than 1/2 PSIG (3.45kpa).
Failure to do so will possibly result in damage to
the gas control system.
8.The 9600 HWG Water Heater and its gas
connections must be leak tested before placing
the unit in operation.
9.Purge all air from gas lines.
3.3 Connecting Water System Piping,
Fittings & Accessories
Installing tank & piping
The 9600 HWG can be used with several
different types of readily available storage tanks. A
bronze circulating pump is built into the appliance.
The pump draws water from the storage tank and
pumps the water through the heater and back into
the tank.
Position the storage tank(s).
At the previously selected locations, position the
storage tank(s). Use Table 3 to determine the pipe size
necessary to provide adequate flow between the 9600
HWG and the tank(s).
Hot water outlet piping, fittings, and accessories.
1.Begin piping to the tank from the hot water
outlet at the top of the 9600 HWG cabinet.
2.Pipe the outlet from the relief valve (located on
top of the unit) such that any discharge from the
relief valve will be conducted to a suitable place
for disposal when relief occurs. Do not reduce
line size or install any valves in this line. The
line must be installed to allow complete drainage
of both the valve and the line.
3.Install a shut off valve in the piping between the
thermometer fitting and the tank.
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.