Laars HWG-M2-150, HWG-M2-250, HWG-M2-175, HWG-M2-200 Installation, Operation And Maintenance Instructions

Installation, Operation and Maintenance Instructions Document 2108A
Installation, Operation and Maintenance Instructions for
9600 HWG
Condensing Water Heater for Natural Gas or Propane
Models HWG-M2-150
HWG-M2-175 HWG-M2-200 HWG-M2-250
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water heater installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flamable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS  Do not try to light any appliance.  Do not touch any electrical switch; do not use any phone in your building.  Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.  If you cannot reach your gas supplier, call the fire department .  Installation and service must be performed by a qualified installer, service agency or the
gas supplier.
10-427A
Page 2
LAARS HEATING SYSTEMS
TABLE OF CONTENTS
SECTION 1. Introduction and Unpacking
1A. Special Installation Considerations............... 3
1B. Checklist of Materials Installer
Must Provide ................................................ 3
1C. Unpacking .................................................... 3
SECTION 2. Locating and Clearances
2A. Locating the 9600 HWG ............................... 4
2B. Locating the Unit for Proper Venting
Distance from the Outside Wall or
Roof Termination .......................................... 4
2C. Locating Vent Openings on Outside Wall ..... 5
2D. Locating Unit for Proper Vent Height ............ 5
2E. Locating Unit with Respect to Ventilation ..... 5
2F. Locating Unit with Respect to
Storage Tanks .............................................. 5
SECTION 3. Installation
3A. Installing Vent Piping Terminal ..................... 5
3B. Connecting Gas to the 9600
HWG Water Heater ...................................... 6
3C. Connecting Water System Piping,
Fittings & Accessories .................................. 6
3D. Tank Temperature Control ........................... 7
3E. Condensate Drain Connection ..................... 7
3F. Electrical Connections .................................. 7
3G. Main Power .................................................. 7
3H. Temperature Control .................................... 7
SECTION 4. Start Up
4A. Filling the System ....................................... 10
4B. Operation Checklist .................................... 10
SECTION 5. Maintenance
5A. Owner Care and Maintenance ................... 11
5B. Routine De-Liming Procedure .................... 11
5C. Therostat Replacement .............................. 11
5D. Vent and Condensate Drain Inspection
(performed annually) .................................. 11
5E. Cleaning Combustion Chamber Coil
and/or Burner ............................................. 12
5F. Combined Water (potable) Heating and
Space Heating ............................................ 12
SECTION 6. Quick Reference Trouble Shooter
6A. Short Cycling .............................................. 13
6B. 9600 Overheats Quickly or
Knocks During Operation ........................... 13
6C. Delayed Ignition .......................................... 13
6D. Occasional Lockouts .................................. 13
S9301A Control Module ............................. 14
SECTION 7. Replacement Parts List
................................................................... 17
To the Installer: After installation these instructions must be given to the owner or left on or near the Water Heater.
To the User: This booklet contains important information that will help you in maintaining and operating this Water Heater. Please retain it for future reference.
Warning: Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance.
Important: This unit must be installed in accordance with state and local codes by a qualified installer!
9600 HWG Water Heater
Page 3
SECTION 1. Introduction & Unpacking
1A. Special Installation Considerations
BEFORE YOU BEGIN:
It is important for you to take a few minutes to review this Installation and Operating Instructions manual before you begin installation. This will make installing and operating the unit easier and faster.
Direct vent-sealed combustion.
The 9600 HWG Water Heater does not and should not take combustion air from inside the building. All of the air is drawn in from the outdoors through a 3-inch diameter plastic pipe. 3" PVC, ABS or CPVC pipe is used for air intake and exhaust venting. (PVC not permitted on HWG-M2-250 exhaust)
No chimney......flue......or draft inducer required.
Because this is a sealed combustion, forced draft unit, it does not require, and must not be connected to a
chimney, existing venting system, or draft inducer.
CAUTION
Connection of this vent to a chimney, existing venting system, or draft inducer will result in poor and possibly dangerous operation.
The supplied vent terminations are designed to be installed through the nearest outside wall (see Sections 2C and 2D).
The 9600 HWG Water Heater is protected against over pressurization. A 150 PSI pressure relief valve is fitted to the unit. It is installed in the dedicated fitting on the top of the water heater.
IMPORTANT: The inlet gas pressure to the appliance must not exceed 13" WC.
A high quality circulator is built into the 9600 HWG Water Heater and will provide sufficient head pressure and volume to circulate water to the storage tank(s) (see Table 3).
All installations must be made in accordance with the: 1) American National Standard Z223.1­Latest Edition National Fuel Gas Code and with the requirement of the local utility or other authorities having jurisdiction, or; 2) Can-CGA B149 installation code and / or local installation codes.
Such applicable requirements take precedence over the general instructions contained herein.
All electrical wiring is to be done in accordance with local codes, or in the absence of local codes, with: 1) the National Electrical Code ANSI/NFPA No. 70-latest Edition, or; 2) CSA standard C22.1 Canadian Electrical Code - Pt 1. This appliance must be electrically grounded in accordance with these codes.
1B. Checklist of Materials Installer
Must Provide
1. The following are acceptable materials for intake and exhaust vents: a) 3" or 4" PVC sched. 40 pipe per ASTM D-
1785 standard. (Not permitted on HWG­250 exhaust).
b) 3" or 4" PVC DWV pipe per ASTM D-
2665 standard. (Not permitted on HWG­250 exhaust).
c) 3" or 4" ABS-DWV pipe per ASTM D-
2661 or ASTM F-628 Standard.
d) 3" or 4" CPVC schedule 40 pipe per ASTM
F441 standard.
e) The solvent cement for pipe joints is to
comply with the following standards:
1). PVC pipe D2564 ABS pipe D2235 CPVC pipe F493
2). CSA listed solvent for a-d
2. Electrical connection to a 120VAC/15Amp service.
3. Gas connection that will provide 250 cubic feet/ hour at 4 to 13 inch water gauge pressure.
4. Condensate drainage: a floor drain is preferred ­a condensate pump may be used.
5. Miscellaneous copper fittings and bronze valves will be required to complete the piping system.
1C. Unpacking
The 9600 HWG Water Heater is shipped in a
single carton with the following standard components on top of the unit (see Figure 1).
1) Exhaust terminal
2) Intake terminal
3) Vent terminal backing plate (4)
4) Hubless coupling reducer
5) Hubless coupling (2)
Figure 1. Contents of shipping package.
1. Remove all packing and tie-down materials.
2. Check contents of the carton against items shown above.
Page 4
LAARS HEATING SYSTEMS
SECTION 2. Locating and Clearances
2A. Locating the 9600 HWG
The appliance should be located in an area where leakage of any connections will not result in damage to the area adjacent to the appliance or to lower floors of the structure.
When such a location is not available, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance.
The unit is design certified by AGA / CGA for installation on combustible flooring; in basements; in closets, utility rooms or alcoves. It must not be installed on carpeting.
The location for the unit should be chosen with regard to the vent pipe lengths, external plumbing, ventilation of operating components and accessibility for service and cleaning.
If there is potential for snow accumulation in your area, both the vent terminals should be installed at an appropriate level above grade (see Figures 2 and 3).
The following dimensions and requirements should be met when choosing the location for the unit (see Table 1):
Minimum Recommended
Clearances Clearance for
From Accessibility Combustible and Venting Construction
BOTH AGA CGA Left Side 1" 6" 48" Right Side (Controls) 1" 12" 24" Top 1" 14" 24" Back 1" 9" 24" Front 1" 24" 48" Vent 0"
Table 1. Location clearances.
2B. Locating the Unit for Proper Venting
Distance from the Outside Wall or Roof Termination
Intake Exhaust
Maximum run: Maximum run: 3" pipe size 3" pipe size 55 equivalent feet 55 equivalent feet
4" pipe size 4" pipe size 85 equivalent feet 85 equivalent feet
Minimum run: Minimum run: 11 equivalent feet 21½ equivalent feet
Intake Terminal is Exhaust Terminal is P/N 2400-102. P/N 2400-104.
Equivalent feet is determined by adding 10 linear feet for each 90° elbow and 5 linear feet for each 45° elbow to be installed to the actual linear feet of pipe required.
Example: 8' of pipe, 2 x 45° elbows and a 90° elbow.
Equivalent Feet: 8' + (2 x 5') + (1 x 10') = 28.
If a 4" pipe size is used to permit longer vent runs the installer must supply 4" hubless couplings (2) and 3 x 4 bushings (2) to adapt to the unit fittings. 4" inlet and exhaust screens are provided for installation in contractor provided 4" coupling and elbow terminations.
NOTE: It is required that a minimum separation of 18" be maintained between the intake and exhaust terminals and that both terminals be installed on the same wall of the building. The intake terminal must not be installed above the exhaust terminal since this would tend to pull exhaust gases back into the intake (see Figures 2 and 3).
Exhaust
6"
Inside of
Exterior
Wall
Figure 2. Suggested vent terminal installations.
24"
Min.
Grade Level
Intake
12" Min.
Exhaust
Terminal
Terminal
NOTE: If flue passes through a flat roof with parapet walls exhaust terminal level must be above the level of the wall.
If flue passes through a sloped or peaked roof it is not necessary to locate it to conform with location requirements for conventional chimneys.
Typical Soil Pipe
Flashing Acceptable
Figure 3. Alternate vent terminal installations.
Roof terminals for air intake must prevent entry of rain water.
Intake
18"
Min.
9600 HWG Water Heater
Page 5
2C. Locating Vent Openings on Outside Wall
1. Exhaust terminal location. The exhaust terminal fitting requires a 4" (10cm) diameter hole through the outside wall. The center line of this opening must be at least 16" (41cm) above grade and at least 14" (35.6cm) from any other building opening such as doors, windows, etc. Vent opening should be well away from shrubbery or other obstructions that would block or restrict the exhaust. Whenever possible, locations under windows or near doors should be avoided. Steaming at the flue terminal is a normal occurrence. This should be considered when deciding flue terminal position.
2. Intake terminal location. The intake terminal requires a separate 4" (10cm) diameter hole to install the intake fitting. The center line of the hole should be at least 16" (41cm) above grade outdoors and 18" (46cm) away from the exhaust outlet. The intake should never be located above the exhaust terminal.
3. Intake and exhaust location for multiple unit installation. For the installations of multiple units, refer to Figure 4 for intake and exhaust terminal locations.
2D. Locating Unit for Proper Vent Height
The vent locations you select must permit direct
pipe runs to the terminal from the boiler. Since the 9600 HWG Water Heater is designed to drain any water that collects in the vent, it is important that you do not build any traps or low points into the vent where water could collect and restrict the vent. It is recommended that 1/4" per foot of vent be built into the vent system to direct any water in the vent back toward the boiler. Note that standard DWV elbows have a built in allowance for the required 1/4" per foot pitch.
2E. Locating Unit with Respect to Ventilation
While the 9600 HWG Water Heater requires no
indoor air for combustion, adequate airflow around the unit must be provided for proper cooling of electrical components.
EXHAUST
INTAKE
Figure 4. Multiple units minimum vent terminal separation.
2F. Locating Unit with Respect to
Storage Tanks
For the best results the 9600 HWG Water Heater
should be located within 10 feet of the storage tanks.
If the unit must be installed with longer piping runs, then the larger diameter tubing must be used. Calculate the necessary pipe size for your installation (see Table 2).
SECTION 3. Installation
3A. Installing Vent Piping Terminal
The water heater is provided with intake and exhaust terminals for use with 3" diameter plastic pipe.
The installer is responsible for obtaining the vent pipe and fittings. The maximum combined length of the intake and exhaust pipe and maximum number of elbows are determined by using the guidelines on Page
4.
The following steps are recommended for vent installation:
1. Obtain the necessary 3" or 4" diameter plastic
piping and fittings as determined beforehand.
2. Position unit at previously selected location.
3. Unpack vent terminals and vent terminal backing
plates.
4. Cut holes in outside wall for vent terminals in the
previously selected locations.
5. Mount the vent terminals backing plates.
6. Fit all of the vent pipes together without
cementing. Make sure that there are no water
traps and that any pitch is inclined back towards
the boiler.
7. Make sure that the flexible vent connections at
the unit fit properly.
8. Begin cementing the intake and exhaust pipes,
start at the vent terminals and work back towards
the appliance. Note that the intake terminal is a
90 degree elbow fitting that is designed to face
down.
9. Support both intake and exhaust pipes with
hangers.
DO NOT RELY ON 9600 HWG TO SUPPORT
PIPES.
Horizontal runs must be supported adjacent to
each fitting and at 5ft. intervals between fittings.
ABS pipe must be supported at 3ft. intervals.
10. Tighten the flexible couplings to connect the
water heater to the vent pipes.
Page 6
LAARS HEATING SYSTEMS
3B. Connecting Gas to the 9600 HWG
Water Heater
1. The water heater requires gas at an inlet gas pressure of at least 4" WC and no greater than 13" WC. Check with your local gas utility or supplier for availability of these delivery pressures.
2. Referring to TABLE 2, size supply piping to keep flow capacity to the unit above 250 cubic feet per hour (CFH) per unit installed.
3. Run gas supply line in accordance with all applicable codes.
4. Locate and install manual shutoff valves in accordance with state and local requirements.
5. Install drip leg and ground joint union (see Figure 5).
6. All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas.
7. The 9600 HWG unit and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig (3.45kpa). It must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.45kpa).
Failure to do so will possibly result in damage to the gas control system.
8. The 9600 HWG Water Heater and its gas connections must be leak tested before placing the unit in operation.
9. Purge all air from gas lines.
Length Capacity of Pipe in MBTU/h
of (.6 Specific Gravity)
Pipe 3/4" 1" 1-1/4"
10' 278 520 1,050 20' 190 350 730 30' 152 285 590 40' 130 245 500 50' 115 215 440
75' 93 175 360 100' 79 150 305 150' 64 120 250
Additional length to be added for each tee or bend:
1.7' 2.2' 2.7'
Table 2. Gas supply piping.
3C. Connecting Water System Piping,
Fittings & Accessories
Installing tank & piping
The 9600 HWG can be used with several
different types of readily available storage tanks. A
bronze circulating pump is built into the appliance. The pump draws water from the storage tank and pumps the water through the heater and back into the tank.
Position the storage tank(s).
At the previously selected locations, position the storage tank(s). Use Table 3 to determine the pipe size necessary to provide adequate flow between the 9600 HWG and the tank(s).
Hot water outlet piping, fittings, and accessories.
1. Begin piping to the tank from the hot water
outlet at the top of the 9600 HWG cabinet.
2. Pipe the outlet from the relief valve (located on
top of the unit) such that any discharge from the
relief valve will be conducted to a suitable place
for disposal when relief occurs. Do not reduce
line size or install any valves in this line. The
line must be installed to allow complete drainage
of both the valve and the line.
3. Install a shut off valve in the piping between the
thermometer fitting and the tank.
Cold water supply piping, fittings and accessories.
1. Install a strainer between the 9600 HWG and the
system. For proper pipe size and distance
limitations, refer to Table 3.
2. Connect a drain valve and a shut off valve to the
9600 HWG cold inlet. On multiple units install a
check valve at each units cold water inlet.
3. Where check valves have been installed on cold
water inlet piping, check to be sure system has
an adequately sized expansion tank to allow
thermal expansion to occur.
Hot water supply piping.
Follow the manufacturers guidelines for completion of the hot water system connections.
Manual Main
Shut Off
Gas Supply
To
9600 HWG
Drip Leg
Cap
Figure 5. Gas supply piping.
Loading...
+ 14 hidden pages