FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualied in hot water boiler and heater installation and maintenance. Improper installation and/or operation
could create carbon monoxide gas in ue gases which could cause serious injury, property damage, or
death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not
followed exactly, a re or explosion may
result causing property damage, personal
injury or loss of life.
Do not store or use gasoline or other
ammable vapors and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from a
nearby phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call
the re department.
Installation and service must be performed
by a qualied installer, service agency, or gas
supplier.
AVERTISSEMENT
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion
ou pour éviter tout dommage matériel, toute
blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ou ni
d’autres vapeurs ou liquides inammables dans
le à proximité de cet appareil ou de tout autre
appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE
GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous servir
des téléphones dans le bâtiment où vous vous
trovez.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualié
9.2 Final Check Lists ............................................ 79
SECTION 10 Parts
10.1 Parts Lists & Illustrations (models 080-140) ... 80
10.2 Parts Lists & Illustrations (model 199) ............ 86
Page 3
The FT Series Heating Only, Boiler
SECTION 1 Product Accessories
1.1 Introduction
This manual provides information necessary for the
installation, operation, and maintenance of the FT Series
Heating Only , Boiler. All application and installation
procedures must be read and reviewed completely before
proceeding with the installation. Consult the manufacturer
(see the back cover), or your local manufacturer’s
representative, with any problems or questions regarding
this equipment. Experience has shown that most operating
problems are caused by improper installation.
1.2 Included with the Unit
ItemDescriptionQty
Page 3
All installations must be made in accordance with
1) American National Standard Z223.1/NFPA54-Latest Edition
“National Fuel Gas Code” or
2) CSA B149.1 “Natural Gas and Propane Installation Code” and
with the requirement of the local utility or other authorities having
jurisdiction. Such applicable requirements take precedence over
the general instructions contained herein.
All electrical wiring is to be done in accordance with the local
codes, or in the absence of local codes, with: 1) The National
Electrical Code ANSI/NFPA No. 70-latest Edition, or 2) CSA
STD. C22.1 “Canadian Electrical Code - Part 1”. This appliance
must be electrically grounded in accordance with these codes.
Wall Mounted Boiler
FTHW (all sizes)
Installation Instructions and
User’s Manual
Condensate Hose
Wall Mount Bracket
2 types of Wall Anchors
1
1
1
FT1894
4
4
1
Pressure Relief Valve
(CH LINE 3/4
˝
30psi)
Model: CASH ACME F-82
Mesh Screens
3”
1
2
Page 4
Page 4
1.2 Included with the Appliance (continued)
ItemsDescriptionsQty
Propane Conversion Orice
80 / 100 / 120 / 140 MBH
O-Ring and Gasket Kit1
Outdoor Temperature Sensor
with anchors and screws
Auto Fill Valve and Backow Preventer Valves are NOT
included (Field Supplied).
199 MBH
1
SECTION 2 Product Characteristics
2.1 Model Nomenclature (model number)
The Model Nomenclature is shown on your Rating Plate and consists of a series of letters and numbers( Nomenclature ) that further identies the characteristics of your FT.
To remove the cover, unthread the 4 phillips head screws.
Keep the screws in a safe place for re-application of cover.
This is typical for all models of the FT.
NOName of Component
17
CH Pressure Gauge
18
‘CH’ Return Adapter
19
Condensate Trap
20
Condensate Adapter
21
CH Return Temperature Sensor
22
Condensate Air Pressure Switch
23
Terminal Block
24
Heat Exchanger
25
Ignition Transformer
26
Sight Glass
27
Burner Overheat Switch
28
Igniter
29
BLDC Fan (blower)
30
Exhaust Temperature Sensor
31
Air Pressure Sensor
32
Vent Pipe Collar
Page 11
The FT Series Heating Only, Boiler
2.4 Names of Components (continued)
Page 11
FTHW
120/140
Heating only boiler
NOName of Component
1
Air Vent (air eliminator)
2
Air Intake Collar
3
Air / Gas Mixing Pipe
4
Gas Inlet Pipe 2
5
Gas Valve
6
Exhaust Duct
7
Low Water Temperature Sensor
8
OP Sensor
9
Flame Detecting Sensor
10
Main PCB
11
Control Display
12
Manual ON/OFF Power Switch
13
Gas Inlet Pipe 1
14
‘CH’ Internal Pump
15
Gas Inlet Adapter
16
‘CH’ Supply Adapter
NOName of Component
17
CH Pressure Gauge
18
‘CH’ Return Adapter
19
Condensate Trap
20
Condensate Adapter
21
CH Return Temperature Sensor
22
Condensate Air Pressure Switch
23
Terminal Block
24
Heat Exchanger
25
Ignition Transformer
26
Sight Glass
27
Burner Overheat Switch
28
Igniter
29
BLDC Fan (blower)
30
Exhaust Temperature Sensor
31
Air Pressure Sensor
32
Vent Pipe Collar
Page 12
Page 12
2.4 Names of Components (continued)
FTHW
Heating only boiler
199
NOName of Component
1
Air Vent (air eliminator)
2
Air Intake Collar
3
Gas Valve
4
Gas Inlet Pipe 2
5
Air / Gas Mixing Pipe
6
Gas Inlet Pipe 1
7
Exhaust Duct
8
OP Sensor
9
Low Water Level Sensor
10
Main PCB
11
Flame Detecting Sensor
12
Control Display
13
Manual ON/OFF Power Switch
14
‘CH’ Internal Pump
15
Gas Inlet Adapter
16
‘CH’ Supply Adapter
NOName of Component
17
CH Pressure Gauge
18
‘CH’ Return Adapter
19
Condensate Trap
20
Condensate Adapter
21
CH Return Temperature Sensor
22
Condensate Air Pressure Switch
23
Terminal Block
24
Heat Exchanger
25
Ignition Transformer
26
Sight Glass
27
Burner Overheat Switch
28
Igniter
29
BLDC Fan (blower)
30
Exhaust Temperature Sensor
31
Air Pressure Sensor
32
Vent Pipe Collar
Page 13
The FT Series Heating Only, Boiler
Gas
Input
Air Intake
2.5 Product Flow Paths and Characteristics
Water in the heating pipe is used for space heating.
Combustion
Air
Page 13
Vent
CH SupplyCH Return
CH = Central Heat
Page 14
Page 14
SECTION 3 Safety Regulations
3.1 Safety Symbols
WARNING
To avoid product damage, personal injury, or even
possible death, carefully read, understand, and
follow all the instructions in the Installation and
Operation manual before installation, operation
and service the Boiler.
Manufacturer cannot anticipate every
circumstance that might involve a potential
hazard. Therefore, all possible incidents are not
included in our warnings. Proper installation,
operation, and service are your responsibility.
You must make sure that the operation and
settings of the Boiler are safe for you and for
others.
This manual provides Safety Symbols. When the
user fails to adhere to the following requirement,
it may cause death, serious injury, and substantial
property damage.
For safety symbols, ‘DANGER’, ‘WARNING’,
CAUTION’ are indicated and the denitions for these
terms are as follow:
DANGER
Indicates an imminently hazardous situation
which, if not avoided, will result in death or
serious injury. This signal word is limited to the
most extreme situations.
WARNING
Indicates a potentially hazardous situation
which, if not avoided, could result in death or
serious injury.
CAUTION
WARNING
FOR YOUR SAFETY READ BEFORE
OPERATING
If you do not follow these instructions exactly, a
re or explosion could result causing property
damage, personal injury or loss of life.
A. This appliance does not have a pilot. It
is equipped with an ignition device which
automatically lights the burner. Do not try to
light the burner by hand.
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next
to the oor because some gas is heavier than
air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
re department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not push in or turn by hand, don’t try to repair
it, call a qualied service technician. Force
or attempted repair may result in a re or
explosion.
D. Do not use this appliance if any part has
been under water. Immediately call a qualied
service technician to inspect the appliance and
to replace any part of the control system and
any gas control which has been under water.
Indicates a potentially hazardous situation
which, if not avoided, may result in minor or
moderate injury. It is also used to alert against
unsafe practices and hazards involving only
property damage.
WARNING
Cancer and Reproductive Harm.
www.P65WARNINGS.CA.GOV.
as required by the state of California Proposition 65.
This appliance must be installed in accordance with
local codes if any; if not, follow ANSI Z224.1/NFPA
54 or CAN/CSA B149.1, Natural Gas and Propane
Installation Code, as applicable.
This appliance is certied for use at altitudes up
to 4,500ft(1,370m) in accordance to the latest CSA/
CGA 2.17-M91 Gas-Fired Appliances for Use at
High Altitudes.
Page 15
The FT Series Heating Only, Boiler
DANGER
Vapors from ammable liquids will explode and
catch on re. These will cause death or severe
burns.
Do not use or store ammable products such as
gasoline, solvents or adhesives in the same room
or area near the appliance.
Keep ammable products
Far away from boiler
In approved containers
Tightly closed
Out of children’s reach
Vapors
Cannot be seen
are heavier than air
spread on the oor
Can spread from other rooms to the main burner
by air currents
Do not install the appliance where ammable
products will be stored.
Read and follow boiler warnings and instructions
thoroughly. If owner’s manual is missing, contact
the retailer or manufacturer.
This boiler must be installed by a qualied plumber,
a licensed gas tter, and/or a professional service
technician.
Improper installation and/or operation will cause a
potentially hazardous situation, such as serious injury
or death. Also, it will void the warranty.
• The National Fuel Gas Code NFPA 54 / ANSI Z224.1
• National Electric Code ANSI/NEPA 70
• All applicable local, state, national and provincial
codes, regulations and laws.
Proper care is your responsibility. Carefully read and
understand the Operating Information in this manual
before operating the Manufacturer Boiler.
Be aware of the location of the gas shut-off valve
and operation method. Close the gas shut-off valve
immediately if the appliance is subjected to re,
overheating, ood, physical damage, or any other
Page 15
damaging condition that might affect the operation
of the unit. Boiler must be checked by a qualied
technician before resuming operation.
DO NOT use this Boiler if any part has been under
water. Immediately call a qualied technician for
inspecting the Boiler and replacing any part of the
control system and gas control which have been
under water.
Do not power up the unit until the gas and water
supply valves are fully opened. Make sure that the
fresh air intake port and exhaust gas port are opened
and functional.
DO NOT attempt to install, repair, or service this
Boiler by yourself.
Do not change any part of the Boiler.
Contact a qualied technician if the Boiler needs
repair or maintenance.
Ask your gas supplier for a list of qualied service
providers.
DO NOT use spray paint, hair spray, or any other
ammable spray near Boiler or near the exterior fresh
air inlet port. DO NOT place any items in or around
the exterior exhaust gas outlet port and/or fresh air
inlet port. These could restrict or block the ow in or
out of the vent system.
“Caution: While repairing control, all wires are
labeled. You must connect the wires in accordance
with the instruction.
Wiring errors can cause improper and dangerous
operation.
“Verify proper operation after servicing operation”
This consists of the gas ignition system components
which are protected from water (dripping, spraying, rain,
etc.) during operation and service (circulator replacement,
condensate trap, control replacement, etc.).
After installing the heater, safety devices must be
tested.
This boiler is equipped with a blocked vent shutoff
system.
If the error code ‘41’ occurs, follow the instructions
below.
- First, turn off the manual gas valve.
- Make sure that there is no foreign object in the vent
passage or rodent screen.
- If you do not nd any problem, do the following.
- Turn off the error state by pressing the power button
of Control Display.
- If the error occurs repeatedly, call your service
technician or gas supplier.
Page 16
Page 16
3.2 Safety Precautions and Proper Use
Before Operation
1. Check the Gas Type (NG/LP)
When using or moving the unit for the rst time, check
if gas type matches with the gas type of the Boiler.
Check whether the gas type which is supplied is NG
(Natural Gas) or LP (Propane) and also check the
Boiler gas type.
The gas type is indicated on the rating plate on side of
the Boiler.
2. Check the Power (120V 60Hz)
Check that the appliance is connected properly.
3. Check the Cold Water
Inlet valve
Please keep the
appliance water
inlet valve open
at all times. The
appliance will not ignite
when insufcient water
or no water is in the
heating pipes. (valve:
always open position)
open
When in Operation
1. Caution for Gas leak
Frequently check for a gas leak at the gas connection
portion with soapy water.
Steps to take if you have a Gas leak.
1. Shut down the boiler as soon as gas fumes are
detected.
2. Close the intermediate gas valve.
3. Open windows for ventilation.
4. Call a qualied service technician for immediate
repair.
2. Caution for Ventilation
Make sure that there is sufcient inow and outow of air
ventilation while using the unit.
If the ventilation is improper, combustion quality may
deteriorate inside the appliance and cause shortened life
of the appliance.
3. Burn Warning
Be careful not to burn yourself on the ue or pipes. They
become extremely hot during operation.
CAUTION
4. Check the Gas Valve
Check that the manual gas shut-off valve
that supplies the FT is opened.
5. Check the area around the appliance and remove
any combustible or ammable materials. Remove
laundry or any other items that are on or near the
boiler or vent pipe.
Carbon monoxide poisoning
If vent pipe fumes enter the room, it could cause
poisoning by carbon monoxide gas. Check that the
vent pipes are properly connected. Open windows
for ventilation. Call a qualied service technician for
immediate repair.
Gas leakage test.
Gas supply line must be inspected regularly.
WARNING
Do not use the appliance for any other purpose other
than for residential hydronic heating.
Do not store combustibles or ammable material such as
gasoline near the appliance.
Do not store other items on or near this boiler.
Do not store combustible (ammable) materials such as
papers.
Do not hang clothes on the vent pipe. This may start a
re.
Do not shut off the Boiler.
When you leave home for a long time, do not shut off
Boiler. The Boiler has a freeze protection function. The
ceramic heater is installed inside of the heater’s internal
pipe to protect the heater from freezing.
Do not wipe the appliance or Control Display
with wet cloth. Electric shock may occur, or internal
parts may fail due to the exposure to moisture.
Do not disassemble the Boiler.
If repair is required, call your local qualied technician.
Page 17
The FT Series Heating Only, Boiler
18
46
3
8
3
8
24
60
12
30
SECTION 4 Installation
Page 17
NOTE: For Cascading Installations, please refer
to document 1349 ‘Cascading the FT Series
Boiler’, available online.
4.1 Location and Clearances
The FT must be mounted to a suitable wall by a
qualied heating contractor under the guidelines of a
boiler. The wall may be of concrete or wood. Suitable
fasteners for concrete or wood must be used. Failure to
wall mount this boiler using correct fasteners will affect
the performance and life expectancy of the boiler and
will void the warranty.
WARNING
Installations must comply with
• All the local, state, provincial, and national codes,
laws, regulations and ordinances.
• National Fuel Gas Code, ANSI Z223.1 – The latest
version.
• National Electrical Code.
• A National Standard of Canada CAN/CSA-B149.1
Check before placing the Boiler
• Always check the connected components which are
near to the heater. The components are below.
Water piping position / Venting adapter / Gas supply
piping / Electrical power / Condensate drain hose.
• Inspect area around Boiler. Remove any combustible
materials, gasoline and other ammable liquids.
Failure to keep Boiler area clear and free of
combustible materials, gasoline and other ammable
liquids and vapors can result in severe personal
injury, death or substantial property damage.
• The Boiler which has gas control system
components must be protected from any possible
danger during operation and service.
• If new Boiler replaces an existing appliance, check
and correct system problems, for example:
- Do not install if: System leaks causing oxygen
corrosion or heat exchanger cracks from hard water
deposits.
Provide clearances
• If the heater was installed in a narrow space
or corner, please ensure that there is sufcient
space for service and maintenance access. For
regular maintenance, gas and water lines must be
accessible.
The boiler must be installed on a wall that can bear its weight.
Minimum clearances to Combustibles.
For installation from
Non-Combustibles and Combustibles
Suggested Service
Clearance
TOP of appliance18 in (46 cm)18 in (46 cm)
BACK of appliance0 in (0 cm)0 in (0 cm)
FRONT of appliance24 in (60 cm)40 in (101 cm)
SIDE of appliance3 in (7 cm)8 in (20 cm)
BOTTOM of appliance12 in (30 cm)24 in (61 cm)
Table 1. Minimum Clearances
WARNING
CLEARANCES FOR SERVICE ACCESS
• If you do not provide the minimum clearances
shown, it might not be possible to service the
boiler without removing it from the space.
• Space must be provided with combustion /
ventilation air openings correctly sized for
all other appliances located in the same
space as the boiler. The boiler cover must be
securely fastened to prevent it from drawing
air from the boiler room. This is particularly
important if the boiler is in a room with other
appliances. Failure to comply with the above
warnings could result in substantial property
damage, severe personal injury, or death.
to Combustibles and for Service.
Page 18
Page 18
4.2 Wall Mount Bracket
4.2.2 The installation height and location
for your FT depends on your installation scenario. With all
clearances considered, and given adequate positioning for
air supply and venting, you will need to determine the best
position to mount the Wall Mount Bracket. The wall must
be concrete, wood, or plywood over studs, and must be
strong enough to hold the boiler!
• Start by familiarizing yourself to how the
included Wall Mount Bracket hooks underneath
the two Hangers that are attached to the back of
the boiler. The ‘hooks’ of the Wall Mount Bracket will
be 3” from the Top of the boiler once the boiler is hung.
• Position the Wall Mount Bracket at the location that it will go,
being sure that it is level, and then drill 4 holes (0.47”dia)
with a 1/2” drill bit, into the wall through the Bracket.
• If mounting to a concrete wall, then use the concrete
anchors. If onto wood or 5/8” (16 mm) plywood, then use
the wood screws. Do not hang the FT onto sheetrock unless
it is possible to fasten directly
into the structural studs. If the
included anchors do not suit
your installation, you must use
‘Field Supplied’ anchors that
are appropriate for the wall’s
construction.
Bolts (4)
Anchors
(4)
Wall Mount
Bracket
3" to Top
of Unit
*
Concrete,
Wood,
or 5/8" Plywood
Wall Mount
Bracket
Hangers (2)
(fastened to the back of unit)
4.2.1 Hang the Boiler
• Lift the boiler up, align the Hangers on the back
of the boiler with the hooks on the Wall Mount
Bracket, and hang the boiler onto the Wall Mount
Bracket. Do a visual inspection to make sure that
the boiler is hanging properly onto the hooks of
the Wall Mount Bracket.
• Fasten the bottom of the boiler to the wall using
2 suitable wall anchors (eld supplied).
Page 19
The FT Series Heating Only, Boiler
4.3 Combustion Air
Page 19
FT boilers must have provisions for combustion
and ventilation air in accordance with the applicable
requirements for Combustion Air Supply and Ventilation
in the National Fuel Gas Code, ANSI Z223 1; or in
Canada, the Natural Gas and Propane Installation Code,
CSA B149.1. All applicable provisions of local building
codes must also be adhered to.
A FT unit can take combustion air from the space
in which it is installed, or the combustion air can be
ducted directly to the unit. Ventilation air must be
provided in either case.
4.3.1 Combustion Air from Room
In the United States, the most common requirements
specify that the space shall communicate with the
outdoors in accordance with method 1 or 2, which follow.
Where ducts are used, they shall be of the same cross-
sectional area as the free area of the openings to which
they connect.
Method 1: Two permanent openings, one commencing
within 12” (300mm) of the top and one commencing
within 12” (300mm) of the bottom, of the enclosure
shall be provided. The openings shall communicate
directly, or by ducts, with the outdoors or spaces
that freely communicate with the outdoors. When
directly communicating with the outdoors, or when
communicating to the outdoors through vertical ducts,
each opening shall have a minimum free area of 1
square inch per 4000 Btu/hr (550 square mm/kW) of
total input rating of all equipment in the enclosure. When
communicating to the outdoors through horizontal ducts,
each opening shall have a minimum free area of not
less than 1 square inch per 2000 Btu/hr (1100 square
mm/kW) of total input rating of all equipment in the
enclosure.
Method 2: One permanent opening, commencing
within 12” (300mm) of the top of the enclosure, shall
be permitted. The opening shall directly communicate
with the outdoors or shall communicate through a
vertical or horizontal duct to the outdoors or spaces
that directly communicate with the outdoors and shall
have a minimum free area of 1 square inch per 3000
Btu/hr (734 square mm/kW) of the total input rating of
all equipment located in the enclosure. This opening
must not be less than the sum of the areas of all vent
connectors in the conned space.
Other methods of introducing combustion and
ventilation air are acceptable, providing they conform to
the requirements in the applicable codes listed above.
In Canada, consult local building and safety codes or, in
absence of such requirements, follow CAN/CGA B149.1
4.3.2 Ducted Combustion Air
The combustion air can be taken through the wall, or
through the roof. When taken from the wall, it must be
taken from out-of-doors by means of the Manufacturer
horizontal wall terminal. When taken from the roof, a
eld-supplied rain cap or an elbow arrangement must
be used to prevent entry of rain water.
Use ABS, PVC, CPVC, polypropylene, or galvanized
pipe for the combustion air intake. Route the intake
to the boiler as directly as possible. Seal all joints.
Provide adequate hangers. The unit must not support
the weight of the combustion air intake pipe. Maximum
linear pipe length allowed is shown in Table 5. Subtract
5 allowable linear ft. (1.5m) for every elbow used.
The connection for the intake air pipe is at the top of
the unit.
In addition to air needed for combustion, air shall also
be supplied for ventilation, including air required for
comfort and proper working conditions for personnel.
COMBUSTION AIR INSTALLATION STANDARDS
MATERIAL UNITED STATES CANADA
ABS ANSI/ASTM D1527
PVC, sch 40 ANSI/ASTM D1785 or D2665 Air pipe material must be chosen
CPVC, sch 40 ANSI/ASTM F441 CPVC, sch 40, ANSI/ASTM, Polypropylene
Polypropylene UL1738, ULC S636. based upon the intended application of the boiler.
Single wall galv. steel 26 gauge
Table 2. Required Combustion Air Pipe Material.
Page 20
Page 20
The instructions for the installation of the venting
system shall specify that the horizontal portions of
the venting system shall be supported to prevent
sagging; the methods of and intervals for support
shall be specied. These instructions shall also
specify that the venting system:
Category I, II and IV boilers must be installed so
that horizontal sections have a slope of at least ¼
inch per foot (21 mm/m) to prevent accumulation of
condensate; and
For Category II and IV boilers, where necessary,
have means provided for drainage of condensate.
NOTICE
CAUTION
The FT is standard as a Natural Gas Boiler and
must be converted if propane is the desired gas, unless
specically manufactured for propane.
Adequate drainage
• The appliance should be installed not to damage
the adjacent area. If such locations cannot be
avoided, it is recommended that a suitable drain
pan, adequately drained, be installed under the
appliance. The pan must not block combustion air
ow.
Les instructions d'installation du système
d'évacuation doivent préciser que les sections
horizontales doivent être supportées pour prévenir
le échissement. Les méthodes et les intervalles
de support doivent être spéciés. Les instructions
doivent aussi indiquer les renseignements suivants:
les chaudières de catégories I, II et IV doivent
présenter des tronçons horizontaux dont la pente
montante est d'au moins ¼ po par pied (21 mm/m)
entre la chaudière et l'évent; les chaudières de
catégories II et IV doivent être installées de façon à
empêcher l'accumulation de condensat;
et si nécessaire, les chaudières de catégories II et IV
doivent être pourvues de dispositifs d'évacuation du
condensat.
AVIS
Connecting the Water Supply
• To conserve water and energy, insulate all water
piping—especially the hot and recirculation water
lines. Never cover the drain or pressure relief valve.
Having a backow preventer in the cold water
supply line will prevent thermal expansion
backow. Contact the water supplier or local
plumbing inspector for information about how to
control this situation.
If overheating occurs or the gas supply fails to shut
off, turn off the manual gas valve.
This installation must conform with below section
• “Air for Combustion and Ventilation” of the
National Fuel Gas Code, ANSI Z224.1/NFPA 54,
or Sections 8.2, 8.3 or 8.4 of Natural Gas and
Propane Installation Code, CAN/CSA B149.1, or
applicable provisions of the local building codes.
Page 21
The FT Series Heating Only, Boiler
4.4 Venting, Exhaust
Page 21
DO NOT COMMON VENT FT UNITS.
never permitted to share a vent with
Category I appliances.
For Cascading Installations, please refer to
document 1349 ‘Cascading the FT Series Boiler’,
The ue temperature of the FT changes dramatically
with changes in operating water temperature.
Therefore, it is necessary to assess the application
of the boiler to determine the required certied vent
class. If the FT is installed in an application where
the ambient temperature is elevated, and/or installed
in a closet/alcove, CPVC, polypropylene, or stainless
steel material is required. If the system temperatures
are unknown at the time of installation, stainless,
polypropylene or CPVC material is recommended.
The FT is a Category IV appliance and may be installed
with PVC, CPVC or polypropylene that complies with
ULC-S636, ANSI/ASTM D1785 F441 (see Table 3) or
a stainless steel venting system that complies with UL
1738 Standard and ULC S636.
Failure to use the appropriate vent material, installation
techniques, glues/sealants could lead to vent failure
causing property damage, personal injury or death.
All venting must be installed according to this manual
and any other applicable local codes, including but not
limited to, ANSI Z224.1/NFPA 54, CAN/CSA B149.1
and ULC-S636. Failure to follow this manual and
applicable codes may lead to property damage, severe
injury, or death.
NOTICE
NOTICE
available online.
WARNING
WARNING
FT units are
NE PAS ÉVENT COMMUNE FT UNITÉS.
unités ne sont jamais autorisés à partager un
évent Catégorie I avec les appareils.
AVIS
FT
___________________________________________
Use of cellular core PVC (ASTM F891), cellular core
CPVC, or Radel® (polyphenolsulfone) in non-metallic
venting systems is prohibited and covering non-
metallic vent pipe and ttings with thermal insulation is
prohibited.
_________________________________________
INSTALLATIONS IN CANADA require the use of
venting material certied to ULCS636. All Gas
vents connected to the FT, plastic, stainless
steel or otherwise must be certied to this ULC
standard. Appropriate selection of vent material is
very important for proper performance and safe
operation of the FT.
The ue temperature of the FT changes
dramatically with changes in operating water
temperature. Therefore, it is necessary to assess
the application of the boiler to determine the
required certied vent class. If the FT is installed in
an application where the outlet water temperature
exceeds 145°F, and/or installed in a closet, class
IIB or higher vent material is required. If the
system temperatures are unknown at the time of
installation, class IIB or higher venting material is
recommended.
IN CANADA all venting used must meet the
following requirements:
1. ULC-S636 certied and marked
2. The rst 3 feet of venting must be accessible
for visual inspection.
3. All components used in the vent system must
WARNING
VENTING INSTALLATION STANDARDS
MATERIAL UNITED STATES CANADA
Stainless Steel UL 1738 Venting must be ULC-S636 certied for use as
PVC, sch 40 ANSI/ASTM D1785 venting material. The venting material must be chosen
CPVC, sch 40 ANSI/ASTM F441 based upon the intended application of the boiler.
Polypropylene UL1738 or ULC-S636
Table 3. Required Exhaust Vent Material.
Page 22
Page 22
4.4 Venting, Exhaust (continued)
be from a certied manufacturer.
4 . Vent system components must not be mixed
with alternate manufacturers certied
components and/or unlisted components.
5 . The venting must be installed according
to the vent manufacturers installation
instructions.
The unit’s vent can terminate through the roof, or
through an outside wall.
Vent pipe must pitch upward, toward the vent
terminal, not less than 1/4” per foot, so that
condensate will run back to the FT to drain. Route
vent pipe to the heater as directly as possible. Seal
all joints and provide adequate hangers as required
in the venting system manufacturer’s Installation
Instructions. Horizontal portions of the venting
system must be supported to prevent sagging and
may not have any low sections that could trap
condensate. The unit must not support the weight of
the vent pipe.
WARNING
Failure to vent this Boiler in accordance with
these instructions could cause a re, resulting
in severe property damage, personal injury or
death.
Do not interchange vent systems or materials
unless it is specied.
The use of thermal insulation covering pipe and
ttings is prohibited.
Do not apply an electric damper, draft hood or
vent damper with this Boiler.
Do not locate vent termination where exposed
to prevailing winds. Moisture and ice may fall
on surface around vent termination. To prevent
deterioration, surface must be in good repair
(sealed, painted, etc.).
4.5 General Location Guideline
1. Vent system installation must be in accordance
with Local codes or, in the absence of local codes,
the National Fuel Gas Code, ANSI Z224.1 /NFPA
54 and/or CSA B149.1, Natural Gas and Propane
Installation Code.
2. The Boiler is designed to be installed as a Direct
Vent (sealed combustion) type. The air for
combustion must be supplied directly from the
outside to the burner. Also, the ue gases must be
vented directly to the outdoors (through wall or roof).
3. Do not install venting system components on the
exterior of building except as specically required by
these instructions
- Vent terminals must be at least 1 foot from any door,
window, or gravity inlet into the building.
- Maintain the correct clearance and orientation
between the vent and air intake terminals.
The vent and air intake terminals must be at the
same height and their center lines must be spaced
apart 12˝ minimum.
- The bottom of the vent and air intake terminal must
be at least 12˝ above the normal snow line. In no
case should they be less than 12˝ above grade
level.
- Do not install the vent terminal directly over
windows or doors.
- Air intake terminal must not terminate in areas that
might contain combustion air contaminates, such
as near swimming pools.
- For sidewall venting, the minimum horizontal
distance between any adjacent individual Module
(Boiler) vent terminations is twelve (12) inches. It
is better to be far more than 12 inches for avoiding
frost damage to building surfaces where vent
terminations are placed.
- The minimum horizontal distance between any
adjacent individual module (boiler) roof vent
endpiece is one (1) foot.
Page 23
The FT Series Heating Only, Boiler
4.6 Locations for Vent Pipe Terminator
4.6.1 Direct Venting Clearances
Page 23
U.S. Installations (see note 1) Canadian Installations (see note 2)
A= Clearance above grade, veranda, porch, 12 inches (30 cm) 12 inches (30 cm) deck, or balcony See note 6 See note 6
B= Clearance to window or door that may be Direct vent only: 12 inches (30cm); 36 inches (91 cm)opened Other than Direct vent: 4 ft (1.2m) below or to NT 80 only - 12 inches (30 cm)
side of opening; 1 ft (30cm) above opening
C= Clearance to permanently closed window See note 4 See note 5
D= Vertical clearance to ventilated soft located
above the terminal within a horizontal See note 4 See note 5distance of 2 feet (61cm) from the center
line of the terminal
E= Clearance to unventilated soft See note 4 See note 5
F= Clearance to outside corner See note 4 See note 5
G= Clearance to inside corner See note 4 See note 5
H= Clearance to each side of center line 3 feet (91 cm) within a height 15 feet
extended above meter/regulator assembly See note 4 above the meter/regulator assembly
I= Clearance to service regulator vent outlet See note 4 3 feet (91 cm)
J= Clearance to nonmechanical air supply Direct vent only: 12” (30cm) 80-285; 36” (91cm)
inlet to building or the combustion air inlet 399-850. Other than Direct vent: 4 ft (1.2m) below 36 inches (91 cm)to any other appliance or to side of opening; 1 ft (30cm) above opening NT 80 only - 12 inches (30 cm)
K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m) 6 feet (1.83 m)
horizontally
L= Clearance above paved sidewalk or pavedVent termination not allowed in this location 7 ft (2.1 m) driveway located on public propertyfor category IV appliances. See note 5
M= Clearance under veranda, porch, deck, See note 4 12 inches (30 cm) (see note 3)
or balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CAN/CSA-B149.1 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
4. For clearances not specied in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of the gas supplier.
5. For clearances not specied in CAN/CSA-B149, clearance is in accordance with local installation codes and the requirements of the gas supplier.
6. IMPORTANT: Terminal must be placed such that it remains a minimum 12” above expected snow line. Local codes may have more
specic requirements, and must be consulted.
Table 4. Direct Vent Clearances
Page 24
Page 24
4.6.2 Venting Requirements in the
Commonwealth of Massachusetts
In Massachusetts the following items are required if
the side-wall exhaust vent termination is less than
seven (7) feet above nished grade in the area
of the venting, including but not limited to decks
and porches. From Massachusetts Rules and
regulations 248 CMR 5.08
1. Installation of Carbon Monoxide Detectors
At the time of installation of the side wall
vented gas fueled appliance, the installing plumber
or gastter shall observe that a hard-wired carbon
monoxide detector with an alarm battery back-up is
installed on the oor level where the gas appliance
is to be installed. In addition, the installing plumber
or gastter shall observe that a battery operated or
hard-wired carbon monoxide detector with an alarm
is installed on each additional level of the dwelling,
building or structure served by the side-wall
horizontally vented gas fueled equipment. It shall
be the responsibility of the property owner to secure
the services of qualied licensed professionals
for installation of hard-wired carbon monoxide
detectors.
a. In the event that the side-wall horizontally
vented gas fueled equipment is installed in a crawl
space or an attic, the hard-wired carbon monoxide
with alarm and battery back-up may be installed on
the next adjacent oor level.
b. In the event that the requirements of the
subdivision cannot be met at the time of completion
of installation, the owner shall have a period of thirty
(30) days to comply with the above requirements,
provided, however, that during said thirty (30) day
period, a battery operated carbon monoxide detector
with an alarm be installed.
2. Approved Carbon Monoxide Detectors
Each carbon monoxide detector shall comply
with NFPA 720 and be ANSI/UL 2034 listed and IAS
certied.
3. Signage. A metal or plastic identication plate
shall be permanently mounted to the exterior of
the building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent
terminal for horizontally vented gas fueled heating
appliance or equipment. The sign shall read, in
print no less than one-half (1/2) inch in size: “GAS
VENT DIRECTLY BELOW, KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4. Inspection The state or local gas inspector of
the side-wall horizontally vented gas fueled appliance
shall not approve the installation unless, upon
inspection, the inspector observes carbon monoxide
detectors and signage installed in accordance with the
provisions of 248 CMR 5.08(2)(a) 1-4.
Page 25
The FT Series Heating Only, Boiler
Page 25
DO NOT COMMON VENT FT UNITS.
NOTICE
FT units
are never permitted to share a vent with
Category I appliances.
Common Vent Test
NOTE: This section does not describe a method for
common venting FT units. It describes what must
be done when an existing unit is removed from a
common vent system.
At the time of removal of an existing boiler, the following steps
shall be followed with each appliance remaining connected to
the common venting system placed in operation, while the other
appliances remaining connected to the common venting system
are not in operation.
1. Seal any Not Used openings in the common venting system.
2. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other deciencies which
could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows
and all doors between the space in which the appliances
remaining connected to the common venting system are
located and other spaces of the building. Turn on clothes
dryers and any appliance not connected to the common
venting system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they will operate at
maximum speed.
4. Place in operation the appliance being inspected. Follow the
lighting instructions. Adjust thermostat so the appliance will
operate continuously.
5. Operate the main burner for 5 minutes then, determine if the
cut-draw overows to the discharge opening. Use the ame
of a match or a candle or the smoke of a cigarette, a cigar or
a pipe
6. Once it has been determined, according to the method
indicated above, that each device connected to the drainage
system is placed in the open air in an adequate manner.
Install the doors and windows, fans, the registers of chimneys
and gas appliances to their original position
7. Any malfunction of the venting system should be corrected so
that the installation conforms to the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 and (or) the installation codes CAN/
CSA-B149.1. If the size of a section of the evacuation system
must be changed, the system should be modied to comply
with the minimum values of the relevant tables of appendix F
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and
(or) the installation codes CAN/CSA-B149.1
NOTICE
NE PAS ÉVENT COMMUNE FT UNITÉS.
AVIS
FT unités
ne sont jamais autorisés à partager un évent
Catégorie I avec les appareils.
Au moment du retrait d'une chaudière existante, les mesures
suivantes doivent être prises pour chaque appareil toujours raccordé
au système d'évacuation commun et qui fonctionne alors que
d'autres appareils toujours raccordés au système d'évacuation ne
fonctionnent pas:
1. Sceller toutes les ouvertures non utilisées du système
d'évacuation.
2. Inspecter de façon visuelle le système d'évacuation pour
déterminer la grosseur et l'inclinaison horizontale qui conviennent
et s'assurer que le système est exempt d'obstruction,
d'étranglement, de fuite, de corrosion et autres défaillances qui
pourraient présenter des risques.
3. Dans la mesure du possible, fermer toutes les portes et les
fenêtres du bâtiment et toutes les portes entre l'espace où les
appareils toujours raccordés au système d'évacuation sont
installés et les autres espaces du bâtiment. Mettre en marche
les sécheuses, tous les appareils non raccordés au système
d'évacuation commun et tous les ventilateurs d'extraction comme
les hottes de cuisinière et les ventilateurs des salles de bain.
S'assurer que ces ventilateurs fonctionnent à la vitesse maximale.
Ne pas faire fonctionner les ventilateurs d'été. Fermer les registres
des cheminées.
4. Mettre l'appareil inspecté en marche. Suivre les instructions
d'allumage. Régler le thermostat de façon que l'appareil fonctionne
de façon continue.
5. Faire fonctionner le brûleur principal pendant 5 min ensuite,
déterminer si le coupe-tirage déborde à l'ouverture de décharge.
Utiliser la amme d'une allumette ou d'une chandelle ou la fumée
d'une cigarette, d'un cigare ou d'une pipe.
6. Une fois qu'il a été déterminé, selon la méthode indiquée ci-
dessus, que chaque appareil raccordé au système d'évacuation
est mis à l'air libre de façon adéquate. Remettre les portes et
les fenêtres, les ventilateurs, les registres de cheminées et les
appareils au gaz à leur position originale.
7. Tout mauvais fonctionnement du système d'évacuation commun
devrait être corrigé de façon que l'installation soit conforme au
National Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou) aux codes
d'installation CAN/CSA-B149.1. Si la grosseur d'une section
du système d'évacuation doit être modiée, le système devrait
être modié pour respecter les valeurs minimales des tableaux
pertinents de l'appendice F du National Fuel Gas Code, ANSI
Z223.1/NFPA 54 et (ou) les codes d'installation CAN/CSA-B149.1
AVIS
Page 26
Page 26
4.7 Air Supply and Vent Connections
4.7.1 Vent / Air Pipe Lengths
Boiler model
FTHW (all sizes)
Table 5. Maximum Vent / Air Pipe Lengths for either 3” or 2 “ Pipes
NOTE: For each elbow, reduce the maximum allowable length
• 5 feet (1.5M) for each 3-inch 90-degree elbow
• 2.5 feet (0.75M) for each 3-inch 45-degree elbow
• 8 feet (2.4M) for each 2-inch 90-degree elbow
• 4 feet (1.2M) for each 2-inch 45-degree elbow
• Max 6 elbows for 3” vent, Max 4 elbows for 2” vent
NOTE: The FT is factory set to operate
using 3” piping for Intake and Vent. For
3” Pipe vent, the default setting for DIP
4 is ON. If your installation is using a 2”
vent pipe, DIP Switch 4 must be in the
OFF position.
Refer to Section 4:18
3˝ Combustion Air / Vent Pipe2˝ Combustion Air / Vent Pipe
Max
100´ (30M)
50´
Propane models are limited to 25
*
equivalent feet of 2” vent
WARNING
• Use of cellular core CPVC, or Radel (polyphenolsulfone)
in venting systems is prohibited.
• Covering non-metallic vent pipe and ttings with thermal
insulation is prohibited.
• Do not obstruct the ow of combustion and ventilated air.
Max
(15M*)
*
4.7.2 Direct Venting
The FT boiler can use 3˝ or 2˝ diameter exhaust
and 3˝ or 2˝ diameter intake air ducts. To ensure the
draw of air directly from and exhaust of air directly
to the outside of the building, create an airtight seal
from the boiler collar to the vent termination.
(For installations in Canada) eld-supplied plastic
vent piping must comply with CAN/CSA B149.1
(latest edition) and be certied by the Standard
For Type BH Gas Venting Systems, ULC-S636.
Components of this listed system must not be
interchanged with other vent systems or unlisted
pipes or ttings. All plastic components and
specied primers and glues of the certied vent
system must be from a single system manufacturer
and must not be intermixed with another system
manufacturer’s parts.
Tightening — Boiler Collar (Socket) to Vent
Pipe & Inlet Pipe
- Clean and dry your selected PVC, CPVC vent
pipe and Manufacturer Boiler collar (socket).
- You can select to the size of vent pipe(2˝ & 3˝),
according to the installation conditions.
- Push the pipe into the collar (socket) until it
touches the bottom of the socket tting.
- For 2” installations, install a eld supplied 3” to
2” adaptor. Adaptor must be installed in vertical
section of piping only.
3” pipe
2” pipe connected, using an adapter
3” to 2”
adapter
is NOT
included.
Page 27
The FT Series Heating Only, Boiler
4.7.3 Indoor Combustion Air
Read and Follow Sections 4.3 Guidelines First.
1. Insert the termination end cap into the intake air duct.
2. Provide two openings to allow for circulation of
combustion air as specied by ANSI Z224.1/NFPA 54.
In Canada refer to CAN/CSA B-149.1
NOTE: The FT needs fresh air for safe operation and must
be installed so there are provisions for adequate
combustion and ventilation air.
ModelFTHW80FTHW100FTHW120FTHW140FTHW199
Maximum Input (BTU/H)80,000 100,000 120,000 140,000 199,000
Page 27
Indoor make up air is provided,
a minimum free area of 1 in2
per 1,000 BTU/H
2
80 in
13 1/4˝
(W) x 13 1/4˝ (H)
2
100 in
13 1/4˝
(W) x 13 1/4˝ (H)
2
120 in
13 1/4˝
(W) x 13 1/4˝ (H)
2
140 in
13 1/4˝
(W) x 13 1/4˝ (H)
2
199 in
13 1/4˝
(W) x 13 1/4˝ (H)
Table 6. Adequate Free Area
4.8 Vent / Air Pipe Termination
All Terminations:
• After connecting terminals, install vent screens on both the vent and air inlet.
Two 3” vent screens are included with each unit. Additional replacement screens are available for purchase.
• Direct Vent - Vertical Terminations
with Sloped Roof
Vent Screens
are required
Page 28
Page 28
SIDE VIEW
FRONT VIEW
Exhaust Screen
12” MIN
1” MIN
Exhaust
Combustion
Intake
Air Intake Screen
Exterior Wall
NOTE: Must be 12”
Minimum distance
above highest
anticipated snow level
or grade, whichever is
greater (TYP).
NOTE: The Exhaust must
be equal to or above the
Combustion Intake while at
a Minimum of 12” apart.
12” MIN
Apart
Exhaust
90o Elbow
Exhaust
Screen
Exhaust
Exhaust
12” MIN
1” MIN
Sill
Combustion
Intake
Combustion
Intake
SIDE VIEWFRONT VIEW
Exterior Wall
NOTE: Must be 12”
Minimum distance
above highest
anticipated snow level
or grade, whichever is
greater (TYP).
12” MIN
12”
MIN
Exhaust Screen
Exhaust
12” MIN
12” MIN
1” MIN
Sill
Combustion
Intake
Combustion
Intake
SIDE VIEWFRONT VIEW
Air Intake Screen
90o Elbow
Exterior Wall
12”
NOTE: Must be 12”
Minimum distance
above highest
anticipated snow level
or grade, whichever is
greater (TYP).
Exhaust
MIN
Horizontal Vent Termination
• Direct Vent - Sidewall Termination
A
4.8 Vent / Air Pipe Termination (continued)
Vent Screens are required
B
C
Vent Screens
are required
Vent
Screens are
required
Page 29
The FT Series Heating Only, Boiler
• Direct Vent - Optional Side wallTerminations
4. Concentric Vent Termination
• Direct Vent - Optional Horizontal and Vertical Concentric Vent
12” (30cm) Minimum
clearance above
highest anticipate
snow level.
Vent
12” Minimum clearance
above highest anticipated
snow level or grade,
whichever is greater.
Side Wall Kit
(2” or 3”)
Exterior Wall
Exhaust
Combustion Air
12” Minimum clearance
above highest anticipated
snow level or grade,
whichever is greater.
Side Wall Kit
(2” or 3”)
Exterior Wall
Exhaust
Concentric Vent Termination
• Direct Vent - Optional Horizontal
and Vertical Concentric Vent
Page 29
Exterior Wall
1" (25mm) to
12” Minimum clearance
above highest anticipated
snow level or grade, whichever
4" (100mm)
is greater.
Strap
Side Wall Kit
(2” or 3”)
12” Minimum clearance
above highest anticipated
snow level or grade,
whichever is greater.
Combustion Air
Vent
Exhaust
12” (30cm) Minimum
clearance above
highest anticipate
snow level.
Vent
Combustion Air
Page 30
Page 30
4.9 Gas Supply and Piping
Gas piping should be supported by suitable hangers or
oor stands, not the appliance.
Review the following instructions before proceeding with
the installation.
1. Verify that the appliance is tted for the proper type
of gas by checking the rating plate. FT will function
properly at elevations up to 10,000 feet
(3050 m). Refer to Section 4.12 for High Altitude
Settings.
2. For minimum and maximum gas supply pressures.
See Section 2.2 on page 5
3. Refer to Table 7, Table 8 and Table 9 to size piping.
4. Run gas supply line in accordance with all
applicable codes.
5. Locate and install manual shutoff valves in
accordance with state and local requirements.
6. A sediment trap must be provided upstream of the
gas controls.
7. All threaded joints should be coated with piping
compound resistant to action of liqueed petroleum
gas.
8. The appliance and its individual shutoff valve
must be disconnected from the gas supply piping
during any pressure testing of that system at test
pressures in excess of 1/2 PSIG (3.45kPa).
9. The unit must be isolated from the gas supply
system by closing its individual manual shutoff valve
during any pressure testing of the gas supply piping
system at test pressures equal to or greater than
1/2 PSIG (3.45kPa).
10. The appliance and its gas connection must be leak
tested before placing it in operation.
11. Purge all air from gas lines.
CAUTION
PRV (included) must be installed immediately at the
top of boiler outlet to PRV, with no valves between.
Refer to Section 4.15
__________________________________________
WARNING:
Open ame can cause gas to ignite and result in
property damage, severe injury, or loss of life.
NOTE: The FT appliance and all other gas appliances
sharing the gas supply line must be ring at maximum
capacity to properly measure the inlet supply pressure.
The pressure can be measured at the supply pressure
port on the gas valve. Low gas pressure could be an
indication of an undersized gas meter, undersized gas
supply lines and/or an obstructed gas supply line.
SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY
NOMINAL PIPE SIZE @ 11" W.C. INLET AND 0.5" W.C. PRESSURE DROP
SIZE1/2" 3/4" 1"
LENGTH MAXIMUM CAPACITY IN THOUSANDS OF BTU PER
HOUR
NOTES: 1. Follow all local and national propane gas codes for line sizing and
equipment requirements. 2. Verify that inlet gas pressure remains between
4 and 13 inches of water column before and during operation.
Source: ANSI Z223.1-80 National Fuel Gas Code.
UNDILUTED PROPANE
Table 7. Nominal Pipe Size, Propane
SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC GRAVITY NATURAL GAS
NOMINAL PIPE SIZE @ 0.30" W.C. PRESSURE DROP
LENGTH 3/4" 1"
FT CUBIC FEET OF GAS PER HOUR
20 190 350
40 130 245
60 105 195
80 90 170
100
Table 8. Nominal Pipe Size, Natural Gas
ATTENTION
PRV (inclus) doit être installé immédiatement en haut
de la chaudière sortie de PRV, sans les vannes entre.
Se reporter à la Section 4.15
__________________________________________
EQUIVALENT LENGTHS OF STRAIGHT PIPE FOR TYPICAL SCH 40 FITTINGS
NOMINAL PIPE SIZE
FITTING 1/2" 3/4" 1"
LINEAR FEET
90° ELBOW 3.6 4.4 5.2
TEE 4.2 5.3 6.6
Table 9. Equivalent Pipe Lengths
Page 31
The FT Series Heating Only, Boiler
Natural Gas Pipe Sizing (Maximum)
Maximum capacity of pipe in cubic feet of gas per hour for gas pressures of 0.5psi or less
and a pressure drop of 0.5 Inch water column. (Based of a 0.60 Specic gravity gas)
For reference only. Referenced from gas pipe manufacturer specications for actual delivery capacity. The
DOE standard for Natural Gas is 1100 BTU/ ft3. Contact the local gas supplier for actual BTU/ ft3 rating.
Page 31
Pipe
Length (ft)
size
10203040506080100150200
1/2˝82584741373729262018
3/4˝19213711297878069624844
1˝3832692181881681531321189182
1-1/4˝639456374325292267232208171148
1-1/2˝1260888723625559509440393320277
2˝2930208017001470132012001040933762661
Table 10. Length of Corrugated Stainless Steel Pipe.
(Refer to the ANSI Z223.1 NATIONAL
FUEL GAS CODE 2012 EDITION)
Pipe
Length (ft)
size
10203040506080100150200
1/2˝1721189581726556504034
3/4˝3602471991701511371171048371
1˝678466374320284257220195157134
1-1/4˝1390957768657583528452400322275
1-1/2˝209014301150985873791677600482412
2˝40202760222019001680152013001160928794
Table 11. Length of Black Iron Pipe (Schedule 40 Metallic)
(Refer to the ANSI Z223.1 NATIONAL
FUEL GAS CODE 2012 EDITION)
Page 32
Page 32
4.9 Gas Supply and Piping (continued)
Propane Gas Pipe Sizing (Maximum)
Intended use : Pipe Sizing Between Single-or Second-Stage (Low Pressure) Regulator and Appliance.
For reference only. Referenced from gas pipe manufacturer specications for actual delivery capacity. The
DOE standard for Natural Gas is 1100 BTU/ft3. Contact the local gas supplier for actual BTU/ft3 rating.
Inlet Pressure : 11 in. w.c / Pressure Drop : 0.5in. w.c / Specic Gravity : 1.5
Pipe
Length (ft)
size
10203040506080100150200
1/2˝129917464585345413128
3/4˝303216177153137126109987569
1˝605425344297265241208186143129
1-1/4˝971661528449397359307270217183
1-1/2˝199014001140988884805696621506438
2˝4640329026802330208019001650148012101050
Table 12. Length of Corrugated Stainless Steel Pipe.
(Refer to the ANSI Z223.1 NATIONAL
FUEL GAS CODE 2012 EDITION)
Length (ft)
Pipe
size
10203040506080100150200
1/2˝291200160137122110101948467
3/4˝608418336287255231212197175140
1˝1150787632541480434400372330265
1-1/4˝2350162013001110985892821763677543
1-1/2˝352024201940166014801340123011401010814
2˝6790466037503210284025702370220019501570
Table 13. Length of Black Iron Pipe (Schedule 40 Metallic)
(Refer to the ANSI Z223.1 NATIONAL
FUEL GAS CODE 2012 EDITION)
Page 33
The FT Series Heating Only, Boiler
Page 33
The gas connection tting on the unit is 3/4˝ male
NPT.
The supply line must be sized for the maximum
output of the boiler model being installed. If there
are additional gas appliances from the main
supply line, you must measure sizes of the supply
line according to the COMBINED total maximum
BTUH draw for the appliances as if they were all
operating at the same time.
Measure the length of the gas supply line from
the gas meter to the Boiler.
Use the tables in this manual or refer to the gas
line manufacturers sizing information to determine
the correct supply pipe size.
The gas shut-off valve in the gas supply line
should be installed close to the unit.
To facilitate any future maintenance, it is also
recommended that an approved gas union tting
be installed in the supply line between the shut-off
valve and the
Boiler.
1) Install an approved gas line pipe to gas line
connection under the Boiler.
Include manual shut off valve and gas union
connection, as shown.
2) Test gas pressure to make sure it meets the
minimum standards and does not exceed the
maximum standards for the boiler.
3) Leak test the gas line pipe before placing the
unit in operation. Use approved leak detector
liquid solutions only to check for leaks.
Do Not Operate the boiler until all connections have
been completed, checked for leaks, and the heat
exchanger is lled with water.
3
/4˝ male NPT connection on the
UNION FITTING
MANUAL SHUT OFF VALVE
GAS PIPE
CLOSED POSITION
Page 34
Page 34
4.9 Gas Supply and Piping (continued)
Suggested Natural Gas (NG) Layout
Sediment
Trap
Other Appliance
Suggested Propane Gas (LP) Layout
Sediment Trap
Gas Regulator
(Supply Press 12˝ )
LP GAS TANK
Other Appliance
Boiler must be installed downstream of the gas meter for adequate gas supply.
Boiler gas connection pipe not less than a 1/2”.
Page 35
The FT Series Heating Only, Boiler
4.10 Gas Supply Pressure
The minimum and maximum inlet gas line pressures must be
Natural GasLP Gas
Maximum Pressure10.5˝ WCMaximum Pressure13.0” WC
Minimum Pressure3.5˝ WCMinimum Pressure8.0” WC
Gas Valve
80 - 140 MBH
Inlet Gas Pressure Port
Page 35
Manifold Pressure Port
Manifold Pressure Port
Gas Valve
199 MBH
Inlet Gas Pressure Port
CAUTION
The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any
pressure testing of the system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve
during any pressure testing of the gas supply piping system at test pressures equal to or greater than 1/2 psi (3.5
kPa).
Loosen the pressure port screws before you check the gas inlet pressure.
Page 36
Page 36
Document 4296D
Table B DIP Switch Settings
These 3 bottom switches must be set per unit SIZE.
Per Table B, set DIP Switch
5 to OFF
for LP Propane.
Turn ON the GAS and WATER supply to the FT. Turn ON the FT.
Connect a manometer to the manifold pressure port. For dual port manometers, use the positive pressureside. Check for proper manifold gas pressure. Refer to Table C.
ONOFF
MIN FireNormal Operation
MAX FireNormal Operation
NG NaturalLP Propane
3” Vent Size
2” Vent Size
ONOFFONOFFON
ON
OFFONONOFFOFF
ON
OFFOFFOFFONON
ON
Figure D
Gas Valve for 80 to 140 MBH
Gas Valve for
199 MBH
The gas valve on
the smaller models is
mounted vertically.
Manifold Pressure Port
Manifold pressure Propane Gas (LP) Natural Gas (NG)
MFTHW 80/100
-0.102˝ WC-0.102˝ WC
0.00˝ WC 0.00˝ WC
MFTHW 120/140
-0.216˝WC-0.216˝WC
0.00˝ WC 0.00˝ WC
CO2 value
Propane Gas (LP) Natural Gas (NG)
2˝ VENT3˝ VENT2˝ VENT3˝ VENT
MFTHW 80/100
120/140/175/199
9.5~11%8.5~10.5%
9~10.5 %8~10%
Refer to the below table.
Manifold pressure Propane Gas (LP) Natural Gas (NG)
MFTHW 80/100
-0.102˝ WC-0.102˝ WC
0.00˝ WC 0.00˝ WC
MFTHW 120/140
-0.216˝WC-0.216˝WC
0.00˝ WC 0.00˝ WC
MFTHW 175
-0.169˝ WC -0.129˝ WC
-0.015˝ WC -0.015˝ WC
MFTHW 199
-0.173WC-0.134˝ WC
-0.015˝ WC -0.015˝ WC
CO2 value
Propane Gas (LP) Natural Gas (NG)
2˝ VENT3˝ VENT2˝ VENT3˝ VENT
MFTHW 80/100
120/140/175/199
9.5~11%8.5~10.5%
9~10.5 %8~10%
Refer to the below table.
Shown is a
Model 140
with 3"
Venting and using
Natural Gas
Document 4296D
CO2 value
Propane Gas (LP) Natural Gas (NG)
2˝ VENT3˝ VENT2˝ VENT3˝ VENT
MFTHW 80/100
120/140/175/199
9.5~11%8.5~10.5%
9~10.5 %8~10%
All sizes
(and all altitudes)
4.11 Gas Setup and Adjustment
For the Step by step process to measure CO2 values on the FT, please refer to Steps 12 thru
Step 22 in Section 4.13 of this Installation Manual.
WARNING
Installer is required to verify combustion settings as part of
the installation process.
Standard Factory Setting is for MAX Fire. 9.0%
CO
@ 0-2,000 ft altitude (Natural Gas).
2
Table 14. CO2 Values
Table 15. Manifold Pressures
All sizes
and all altitudes
Page 37
The FT Series Heating Only, Boiler
AUTODESK ����������
AUTODESK ����������
AUTODESK � � � �� � � � � �
AUTODESK ����������
AUTODESK ����������
4.12 High Altitude Installations. 2,000’ to 10,000’
The FT is shipped with a default factory setting for installation at an
altitude of 0 to 2000’ (approx). For maximum efciencies at higher
altitudes (2,000’ to 10,000’), the FT does have an adjustment in the
Installer Parameters Mode.
Follow these instructions if your installation is at 2,000’ - 10,000’.
1. With the Power turned OFF, press the 'Modes button' for
5 seconds to get into the Installer Parameters Mode.
Page 37
2. Turn the dial (E) until ‘
33:HA’ appears.
3. Press the dial (E).
4. Set the high altitude value by turning the dial.
Refer to table.
#Altitude of Installation
00~1999 ft (0~609 m)
12,000~4,499 ft (610~1,645 m)
24,500~7,699 ft (1,646~2,346 m)
47,700~10,000 ft (2,347~3,048 m)
5. Press the dial again (E) to save the setting.
6. Press the ‘Modes button’ for one second, to Save the
number and to go back to initial status.
Page 38
Page 38
Document 4296D
The FT Series, Heating Only, Gas Conversion Kit
AUTODESK ����������
AUTODESK ����������
4.13 Natural Gas to Propane Conversion
Kit # R20773
The FT Series, heating only, condensing boiler
is confi gured for Natural Gas (NG) from the
factory.
Kit is included with every FT. The gas conversion
kit will show you how to convert your FT boiler
to propane gas. If your FT does not have the bag
containing the conversion kit, a replacement kit can
be obtained. Contact the manufacturer and request a
replacement gas conversion kit.
If your installation altitude is greater than 2000 ft, check
that the ‘High Altitude’ Installer Setting has been adjusted
to suit your installation altitude. Refer to Section 4.12 of theInstallation and Operation Instructions (Document1342).
This boiler has been assembled at the factory to burn
natural gas, but can be converted to burn LP gas. Be
sure to confi rm that the gas at this installation is propane
gas (LP), before performing this conversion, and then
placing the boiler into operation.
A Natural Gas to Propane Conversion
NOTICE
CAUTION
ON / OFF
Steps 1 thru 24
Turn OFF the FT. The
1.
ON / OFF button is located
at the bottom left of the Control Display .
Turn OFF the GAS and WATER supply to the FT (valves
2.
are located on the plumbing pipes.)
ModelNat Gas (NG) Part # Propane (LP) Part #
FTHW
FTHW
FTHW
80
100
120
FT1943FT1946
FT1944FT1947
FT1945FT1948
Nozzles
WARNING
This conversion shall be installed by a qualified service
agency in accordance with the manufacturer's instructions
and all applicable codes and requirements of the
authority having jurisdiction. If the information in these
instructions is not followed exactly, a fi re, an explosion
or production of carbon monoxide may result causing
property damage, personal injury or loss of life. The
qualifi ed service agency is responsible for the proper
and complete installation of this kit. The installation
is not proper and complete until the operation of
the converted appliance is checked as specified in the
manufacturer's instruction supplied with the kit. Installation
must conform to local codes and the latest edition of the
National Fuel Gas Code, ANSI Z223.1 and CAN-B149.1.
Failure to follow instructions could result in serious injury or
property damage. The qualifi ed agency performing this work
assumes responsibility for gas conversion.
FTHW
FTHW
140
199
FT1412NFT1412P
FT1780FT1802
Table A. Gas Conversion Parts
A VERTISSEMENT
Ce conversion doit être installé par un organisme de service
conformément aux instructions du fabricant et tous les codes et
les exigences de l’autorité compétente. Si les informations
contenues dans ces instructions n’est pas suivi à la
lettre, un incendie, une explosion ou de la production de
monoxyde de carbone mais résultat causant des dommages
matériels, des blessures ou des pertes de vie. Le service
est responsable pour la bonne et complète l’installation de
ce kit. L’installation n’est pas correcte et complète jusqu’à
ce que le fonctionnement de l’appareil converti est vérifi ée
comme spécifi é dans le manuel d’instruction fourni avec le kit.
L'installation doit être conforme aux codes locaux et la dernière
édition du National Code de gaz combustible, ANSI Z223.1 et
peut-B149.1. Non-respect des instructions peut entraîner des
blessures graves ou des dommages matériels. L'organisme
qualifié effectuant ce travail suppose la responsabilité de
conversion au gaz.
Orifi ce
pg 1 of 4
Page 39
The FT Series Heating Only, Boiler
Document 4296D
The FT Series, Heating Only, Gas Conversion Kit
BLOWER
GAS
VALVE
GAS
VALVE
COMBUSTION
TEST PORT
COMBUSTION
TEST PORT
COVER
BLOWER
COVER
GAS
INLET PIPE
GAS
INLET PIPE
( FTHW
80/100120/140
) ( FTHW
199
)
Figure A
( FTHW
80/100/120/140
) ( FTHW
199
)
BRASS FITTINGS
NOZZLE
BRASS FITTINGS
PACKING
PACKING
ORIFICE
3.
Using a Phillips screwdriver, remove the 4 screws on the front cover. See Figure A.
4.
Locate the Gas Inlet Pipe at the top of the unit as is shown in Figure A, and loosen the Brass Fittings at both ends
of the Gas Inlet Pipe.
5.
Completely un-thread the Brass Fittings at the blower end of the Gas Inlet Pipe, and then carefully swing the Gas
Inlet Pipe to the left, just enough so that it is out of the way . See Figure B.
6.
Remove the existing Natural Gas Nozzle (or Orifi ce). Save the Packing for re-use. It is also advised to
save the
nozzle or orifi ce just in case the unit needs to be converted back to natural gas at any time in the future.
7.
Replace the old Nozzle (or Orifi ce) with the new one for LP (propane). Re-use the Packing from previous.
8.
Return the Gas Inlet Pipe to its original position and tighten both of the Brass Fittings.
Figure B
Flat Side
Inward
Page 39
Page 40
Page 40
Document 4296D
The FT Series, Heating Only, Gas Conversion Kit
Manifold pressure Propane Gas (LP) Natural Gas (NG)
MFTHW 80/100
-0.102˝ WC-0.102˝ WC
0.00˝ WC 0.00˝ WC
MFTHW 120/140
-0.216˝WC-0.216˝WC
0.00˝ WC 0.00˝ WC
CO2 value
Propane Gas (LP) Natural Gas (NG)
2˝ VENT3˝ VENT2˝ VENT3˝ VENT
MFTHW 80/100
120/140/175/199
9.5~11%8.5~10.5%
9~10.5 %8~10%
Refer to the below table.
Manifold pressure Propane Gas (LP) Natural Gas (NG)
MFTHW 80/100
-0.102˝ WC-0.102˝ WC
0.00˝ WC 0.00˝ WC
MFTHW 120/140
-0.216˝WC-0.216˝WC
0.00˝ WC 0.00˝ WC
MFTHW 175
-0.169˝ WC -0.129˝ WC
-0.015˝ WC -0.015˝ WC
MFTHW 199
-0.173WC-0.134˝ WC
-0.015˝ WC -0.015˝ WC
CO2 value
Propane Gas (LP) Natural Gas (NG)
2˝ VENT3˝ VENT2˝ VENT3˝ VENT
MFTHW 80/100
120/140/175/199
9.5~11%8.5~10.5%
9~10.5 %8~10%
Refer to the below table.
4.13 Natural Gas to Propane Conversion (continued)
ONOFF
MIN FireNormal Operation
MAX FireNormal Operation
NG NaturalLP Propane
3” Vent Size
ONOFFONOFFON
OFFONONOFFOFF
OFFOFFOFFONON
MBH 80 100 120 140 N/A 199
These 3 bottom switches must be set per unit SIZE.
Table B DIP Switch Settings
Per Table B, set DIP Switch
9.
Turn ON the GAS and WA TER supply to the FT.
10.
Turn ON the FT.
11.
Connect a manometer to the manifold pressure port. For dual port manometers, use the positive pressure
12.
side. Check for proper manifold gas pressure. Refer to Table C.
2” Vent Size
5 to OFF
ON
ON
ON
Model 140
Venting and using
for LP Propane.
Shown is a
with 3"
Natural Gas
Manifold Pressure Port
13.
Manifold Pressure Port
Figure D
The gas valve on
the smaller models is
mounted vertically.
Gas Valve for 80 to 140 MBH
Table C
Establish a call for heat. You may need to disconnect the outdoor reset if you are making this gas
conversion during warm weather.
Gas Valve for
199 MBH
pg 3 of 4
Page 41
The FT Series Heating Only, Boiler
Document 4296D
The FT Series, Heating Only, Gas Conversion Kit
CO2 value
Propane Gas (LP) Natural Gas (NG)
2˝ VENT3˝ VENT2˝ VENT3˝ VENT
MFTHW 80/100
120/140/175/199
9.5~11%8.5~10.5%
9~10.5 %8~10%
Page 41
All sizes
(and all altitudes)
Table D
Setup your combustion analyzer and place the sensor into the combustion test port
14.
Per Table B for Max Fire
15.
WAIT for your combustion analyzer to stabilize. This may take up to 3 minutes depending on your
16.
combustion analyzer. Then measure the CO
combustion readings Do NOT adjust CO2 at MAX Fire. ONLY in MIN Fire, so...
Per Table B for MIN Fire, change dip switch 6 to OFF and 7 to ON. The unit will cycle down to MIN Fire.
17.
WAIT for your combustion analyzer to stabilize. Then measure the CO
18.
acceptable MIN fi re combustion readings
Open the Gas Valve Adjustment Port by removing the cap screw with a 4mm Allen wrench.
19.
Then use the 4 mm Allen wrench to make a minor adjustment (1/8 turn) to either increase or decrease CO2.
20.
It may be necessary to go back and forth between HI Fire and LOW Fire several times (and making
21.
adjustments only at LOW Fire), before CO2 at both are within acceptable levels. Be sure to put the
adjustment port cap screw back onto the valve when done.
,
change dip switch 6 to ON and 7 to OFF. The unit will cycle up to MAX fi re.
for MAX fi re. Refer to Table C for acceptable MAX fi re
2
for MIN fi re. Refer to Table D for
2
Once the CO2 and manifold pressure measurements for both MIN and MAX Fire are acceptable per Table
22.
C, set DIP switches 6 and 7 to the OFF position for Nominal Fire (normal operation).
Write in the correct conversion date and the technicians name to the included gas conversion sticker. See
23.
Figure E. Then apply that sticker adjacent to the rating plate.
Put the boiler cover back on and assemble/tighten the 4 screws that hold the cover in place.
24.
This unit was converted on ____/____/___to _____gas
with kit #____________by______________________
(name and company __________________________
accountable)_________________________________
___________________________________________
Cette unité a été converti ____/____/____ten ______gaz
en utilisant le kit numéro _____ par______________
(nom et société_________________________________
responsable)___________________________________
_____________________________________________
Figure E (Conversion label)
pg 4 of 4
Page 42
Page 42
4.14 Plumbing Guidelines
4.14.1 External Plumbing and Water
Connection Guidelines
- Ensure pipe material meets local codes and
industry standards.
- The pipe end must be clean and free of debris.
- Do not apply torch heat within 12˝ of the bottom
connections of the unit.
- The CH supply and return connections are 1-1/4”.
The system piping must be a minimum of 1-1/4”.
(See Sections 1.14.4 & 4.14.5)
- Isolation valves(Shutoff valve) will be used.
- All piping should be insulated.
4.14.2 Backow Preventer and Boiler Feed
Valve
- Apply a Backow Preventer and Boiler Feed
Valve to the unit as required by local codes.
4.14.3 Diaphragm type Expansion tank
- The air in a diaphragm-type expansion tank is
separated from the water by a exible rubber
membrane. When the tank is installed in and
connected to the piping of the system, water
enters the other side of the tank chamber and
presses down on the diaphragm.
- You should always install an ‘Automatic Air Vent
on the top of the air separator to remove
residual air from the system.
- Automatic air vent has been installed on the
inside of the boiler.
- The installation of an additional air vent is
optional.
- If the boiler is installed in a closed water supply
system, such as one having a backow preventer
in the cold water supply line, it will control thermal
expansion.
CAUTION
Use at least the MINIMUM pipe size for the entire
boiler loop piping (connecting boiler to and from
the primary/secondary connection). Use only
primary/secondary piping as shown.
Failure to follow these guidelines could result in
system problems.
CH pipe minimum size : 1-1/4˝
CAUTION
For guidelines in the use of Glycol Products.
Please refer to Section on page 78
CAUTION
Scalding Risk: Manufacturer
strongly recommends the
use of an anti-scald mixing
valve at domestic hot water
outlet (boiler location) to
reduce potential for scalding.
Contact Manufacturer for
recommended models.
Check with local codes.
__________________________________________
Page 43
The FT Series Heating Only, Boiler
PRIMARY LOOP
CH SUPPLY
1”
Min
Piping
(SPACE HEATING)
ZONE 1
ZONE 2
ZONE 3
SECONDARY LOOP (SPACE HEATING)
Do not exceed
12" See Note
P
Make-Up Water
DHWPump
PRIMARY LOOP
CH
SUPPLY
CH RETURN
1”
Min
Piping
(SPACE HEATING)
ZONE 1
ZONE 2
ZONE 3
SECONDARY LOOP
(SPACE HEATING)
Do not
exceed
12"
See
Note
P
Make-Up Water
DHW
Pump
Indirect DHW Tank
4.14 Plumbing Guidelines
4.14.2 Zoning with zone valves
- In a valve based system, there is one
circulator pump at the boiler and each
heating zone has a zone valve which opens
when the zone demands it.
- Each thermostat is wired directly to the
corresponding zone valve. Contacts in the
zone valves provide a proper signal to the
boiler when the valve is opened.
Page 43
Differential
P
Pressure By-Pass
Expansion tank
(Diaphragm-type)
Automatic air vent
Air separator
Circulation pump
Check valve
Drain valve
valve
Backflow preventer
Pressure Relief Valve
Anti-scald rated
Mixing Valve
Auto Fill Valve
and Backow Preventer
Valves are NOT included
(Field Supplied).
1. This piping diagram is meant to show system piping concept only. Installer is responsible for all
equipment and detailing required by local codes.
2. All closely spaced tees shall be 12” (or 4 pipe dia) center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all
closely spaced tees.
4. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
5. Install a check valve on the return line to the boiler.
6. Manufacturer strongly recommends the use of an anti-scald mixing valve at domestic hot water outlet
(boiler location) to reduce potential for scalding.Contact Manufacturer for recommended models.
Check with local codes.
Page 44
Page 44
PRIMARY LOOP
CH
SUPPLY
CH RETURN
(SPACE HEATING)
ZONE 1
ZONE 2
ZONE 3
1”
Min
Piping
Do not
exceed
12"
See
Note
SECONDARY LOOP
(SPACE HEATING)
Make-Up Water
Circulation pump
Check valve
Drain valve
Gate valve
Backflow preventer
Pressure Relief Valve
Expansion tank
Air separator
(Diaphragm-type)
Automatic air vent
Anti-scald rated
Mixing Valve
PRIMARY LOOP
CH SUPPLY
(SPACE HEATING)
ZONE 1
ZONE 2
ZONE 3
1”
Min
Piping
Do not exceed
12" See Note
SECONDARY LOOP (SPACE HEATING)
Make-Up Water
4.14 Plumbing Guidelines
4.14.3 Zoning with
circulation pumps
- Each heating zone of a pump
based system has its own
circulator pump which runs
when that zone demands it.
- Each zone thermostat goes to
a controller which controls the
pumps.
1. This piping diagram is meant to show system piping concept only. Installer is responsible for all
equipment and detailing required by local codes.
2. All closely spaced tees shall be 12” (or 4 pipe dia) center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all
closely spaced tees.
4. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
5. Install a check valve on the return line to the boiler.
6. Manufacturer strongly recommends the use of an anti-scald mixing valve at domestic hot water outlet
(boiler location) to reduce potential for scalding.Contact Manufacturer for recommended models.
Check with local codes.
Page 45
The FT Series Heating Only, Boiler
CH
SUPPLY
CH RETURN
ZONE 1
ZONE 2
ZONE 3
Make-Up Water
DHW
Pump
Indirect DHW Tank
4.14 Plumbing Guidelines
4.14.4 Indirect Water Heating
- Installer is responsible for all equipment and detailing required by local codes.
- The minimum pipe size of CH piping should be 1 ¼˝ in diameter.
and Backow Preventer
Valves are NOT included
Page 45
Auto Fill Valve
(Field Supplied).
1. This piping diagram is meant to show system piping concept only. Installer is responsible for all
equipment and detailing required by local codes.
2. All closely spaced tees shall be 12” (or 4 pipe dia) center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all
closely spaced tees.
4. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
5. Install a check valve on the return line to the boiler.
6. Manufacturer strongly recommends the use of an anti-scald mixing valve at domestic hot water outlet
(boiler location) to reduce potential for scalding.Contact Manufacturer for recommended models.
Check with local codes.
Page 46
Page 46
4.14 Plumbing Guidelines
4.14.5 Multiple units using
zones pumps and an
indirect for DHW
ZONE 1
ZONE 2
ZONE 3
Expansion tank
(Diaphragm-type)
Automatic air vent
CASCADE
SYSTEM
SENSOR
SECONDARY LOOP
(SPACE HEATING)
Do not
exceed
12"
See
Note
1
/
”
1
4
Min
Piping
Make-Up Water
FollowerLeader
Air separator
Circulation pump
Check valve
Drain valve
Gate valve
Backflow preventer
Pressure Relief Valve
Anti-scald rated
Mixing Valve
PRIMARY LOOP
(SPACE HEATING)
CH
SUPPLY
CH RETURN
CH
SUPPLY
DHW
Pump
CH RETURN
Indirect DHW Tank
1. This piping diagram is meant to show system piping concept only. Installer is responsible for all
equipment and detailing required by local codes.
2. All closely spaced tees shall be 12” (or 4 pipe dia) center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all
closely spaced tees.
4. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
5. Install a check valve on the return line to the boiler.
6. Manufacturer strongly recommends the use of an anti-scald mixing valve at domestic hot water outlet
(boiler location) to reduce potential for scalding.Contact Manufacturer for recommended models.
Check with local codes.
7. Auto Fill Valve and Backow Preventer Valves are NOT included (Field Supplied).
8. DHW Sensor/Aquastat must connect to LEAD boiler
Page 47
The FT Series Heating Only, Boiler
4.15 Pressure Relief Valve
External pressure relief valves must be installed.
Observe the following. Failure to comply with the
guidelines on installing the pressure relief valve and
discharge piping can result in personal injury, death
or substantial property damage.
WARNING
Do not operate this appliance before the
pressure relief valve supplied is installed with
sufcient relieving capacity in accordance
with the ASME Rating Plate on the boiler.
Page 47
This boiler is provided with 30 psi safety relief valve
that complies with the ANSI/ASME Boiler and Pressure
Vessel Code, Section IV (“Heating Boilers).(Model :
CASE ACME F-82)
This safety relief valve (30 psi) is shipped loose for eld
installation.
For safety, the relief valve(s) must be installed into it’s
designed location and not be removed or plugged.
Failure to comply with the guidelines on installing the
pressure relief valves and discharge piping can result in
personal injury, death or substantial property damage.
Direct the discharge piping of the pressure relief valve
so that hot water will not splash on anyone or any
nearby equipment. Attach the discharge line to the
pressure relief valve and run the end of the line within
6-12″ (150-300mm) of the oor.
WARNING
DO NOT install a CH pipe line relief valve with a
pressure higher than 30psi. This is the maximum
allowable relief valve setting for the boiler.
Test the operation of the valve after lling and
pressurizing system by lifting the lever. Make sure the
valve discharges freely. If the valve fails to operate
correctly, replace it with a new relief valve. Ensure that
the discharge capacity of the pressure relief valve is
equal to or greater than the maximum pressure rating
of the boiler.
Ensure that the maximum BTU/H rating on the
pressure relief valve is equal to or greater than the
maximum input BTU/H rating of the boiler.
Pressure Relief Valve must be installed on the CH
supply line as close to the unit as possible. (CH
supply line: maximum 30psi). No other valves should
be placed between the pressure relief valve and the
appliance.
This appliance has a high-temperature shut off switch
built in as a standard safety feature .Therefore a
“pressure only” relief valve is required.
3/4” 30psi Relief Valve
Page 48
Page 48
4.16 Disposal of Condensate
High efciency gas condensing Boilers create
condensation when operating. Condensation has
acidic (pH) of approximately 4-5.
Condensate must be drained in accordance with all
local regulations. Follow your local code with regards
to the disposal of condensation.
One of 4 disposal methods must be followed
1. to oor drain
2. to neutralizer (optional kit)
3. to laundry tub
4. to condensate pump (eld supplied)
If a neutralizer is installed, periodic replacement of the
lime stone (or neutralizing agent) will be required. The
rate of depletion of the lime stone varies upon usage
of the boiler. During the rst year of operation, please
check the neutralizer every few months for depletion.
Apply only corrosion-resistant materials for the
condensate drain lines such as 1/2˝ PVC, CPVC,
Polypropylene pipe or included plastic hose.
Condensate
Trap
Condensate
drain pipe
Category II & IV water heaters must be installed with a
means provided for the drainage of condensate.
les chaudières de catégories II et IV doivent être
installées de façon à empêcher l'accumulation de
condensat; et
si nécessaire, les chaudières de catégories II et IV
doivent être pourvues de dispositifs d'évacuation du
condensat.
Condensate is mildly acidic (pH=5), and may harm
some oor drains and/or pipes, particularly those
that are metal. Ensure that the drain, drainpipe, and
anything that will come in contact with the condensate
can withstand the acidity, or neutralize the condensate
before disposal. Damage caused by failure to install
a neutralizer kit or to adequately treat condensate
will not be the manufacturer’s responsibility.
Contact Manufacturer to order
Neutralizer Kit# A2123601
_________________________________________
NOTICE
AVIS
CAUTION
23
1
Various condensate disposal methods
4
Page 49
The FT Series Heating Only, Boiler
4.17 Electrical Wiring Connections
WARNING
Install wiring and electrically ground boiler in accordance with authority having jurisdiction or, in the
absence of such requirements, follow the National Electrical Code, NFPA 70, and/or CSA C22.1
Electrical Code-Part 1 in Canada.
ELECTRICAL SHOCK HAZARD — For your safety, turn off electrical power supply at service
entrance panel before making any electrical connections to avoid possible electric shock hazard.
Failure to do so can cause severe personal injury or death.
This appliance must be electrically grounded. Ensure the electrical receptacle that the boiler will be plugged
into, is properly grounded; if wiring directly.
Do not attach the ground wire to either the gas or the water piping as plastic pipe or dielectric unions may
isolate the Boiler electrically.
The wiring diagrams contained in this manual are for reference purposes only.
Refer to these diagrams and diagrams from external controls used with this appliance. Read, understand,
and follow all wiring instructions.
Do not disconnect the power supply when the unit is in normal operation. Damage caused by freezing is not
covered under the warranty.
Manual (Rocker) switch maximum allowable current for each circulator is 16 amps at 125VAC.
( Housing : Nylon #66 UL 94V-2 , Rocker : Nylon #66 UL 94V-2, Terminal : Copper Alloy )
Terminal block (External power connector) : DFT-20A-10P (20 amps at 300VAC)
Page 49
Manual Switch
Electrical Connections
External Power Connections
Low Voltage Connections
( O/S : Outdoor sensor connector )
DHW and CH pump terminals for external pump are live 120V limited to 2.0 A. They operate respective to an
external call (e.g T-T) for heat.
Page 50
Page 50
Document 4296D
The FT Series, Heating Only, Gas Conversion Kit
Table B DIP Switch Settings
MBH 80 100 120 140 N/A 199
These 3 bottom switches must be set per unit SIZE.
9.
Per Table B, set DIP Switch
5 to OFF
for LP Propane.
10.
Turn ON the GAS and WATER supply to the FT.
11.
Turn ON the FT.
ONOFF
MIN FireNormal Operation
MAX FireNormal Operation
NG NaturalLP Propane
3” Vent Size
2” Vent Size
ONOFFONOFFON
ON
OFFONONOFFOFF
ON
OFFOFFOFFONON
ON
Shown is a
Model 140
with 3"
Venting and using
Natural Gas
4.18 DIP Switches
DIP switches 6 and 7 have to be set in the OFF position when the boiler is running normally.
DIP switches 1, 2, and 3 are system switches and are factory set to the boiler model and size
DHW temperature sensor or
Mechanical
aquastat connection
System temperature sensor
SELV (5V)
SELV (5V)
SELV (5V)
CN3
SMW250-06D
1
2GNDSELV (5V)
3Voltage inputSELV (5V)
4-6FLUX1Unuse-
APS
VCCSELV (5V)
Page 55
The FT Series Heating Only, Boiler
SECTION 5 Control Display and Operation
5.1 Control Dial and Buttons
The Control Display
E
Page 55
Status Light
(constant green
when operating
normally)
The Control Display has a Control Dial (E), 4 buttons (A, B, C, D), and a Liquid
Crystal Display (with 72 back-lit segments). This section of this manual gives
instruction on how to navigate into the many functions of the FT and to change
temperature set points, set system variables and controller parameters.
Buttons
A
B ModesTap to return to menu
C
D
E
Display Power
Heating
Water
Time / Date
Set
Scroll / Select
Turns Control Display ON / OFF
PRESS (Tap)PRESS and HOLD (5 seconds)
CH set-point change mode
(Maxium 82
Menu select or value
up(+)/down(-) or setting dial.
°C(180°F))
No ChangeTo SET: Year/Month/Week/Day/Time/Min
Functionality
(If Display Power was On )
(If Display Power was Off ) Installer Mode
Status Display Mode
• Temperature Specications
Operating ambient Temperature Range : -10 to 60°C.
Operating Relative Humidity up to: 90% at 40°C.
Shipping & Storage Temperature Range of : -20 to 80°C.
WARNING
Do not use this appliance if any part has been under
water. Immediately call a qualied service technician
to inspect the appliance and to replace any part of
the control system and any gas control that may have
been under water.
Page 56
Page 56
5.2 LCD Overview
SymbolNameDescription
Service Reminder modeService Reminder mode indication
Outside Temperature ModeOutside Temp setting indication
Anti-freeze modeAnti-freeze mode indication
Storage modeStorage mode indication
Information modeInformation mode indication
Communication stateCommunication state indication
Time setting modeTime /Dispaly/Install mode indication
Fahrenheit modeIndicated as Fahrenheit temperature
Heat demand modeHeat demand mode indication
DAY modeCurrent day mode indication
Cascade System connecting
mode
Cascade System operating mode
The LCD will illuminate when a user action is detected (a button is pressed) and will turn back off after 20 seconds.
Cascade System connecting mode
indication
Cascade System operating mode
indication
Page 57
The FT Series Heating Only, Boiler
5.3 Operating Mode
Operating Mode
After the Power is turned on, and/or the Control Display is turned on , the Control Display
will go through a ‘Start Up’ checklist and briey show a sequence of diagnostic codes before
entering into the ‘Operating Mode. It will then display the following information.
BC
Page 57
AD
IndicateIndicator
Current Operating Temperature Set-Point
If the Fan is operating
If a ame is detected
Celsius or Fahrenheit
Date and Time indicator
If Outside Temperature Sensor is operating
If there is a Demand for Central Heat (CH)
If CH pump state is
If Internal recirculation pump is operating
operating
E
or
If Communication state is activated
The Control Display can operate through user and service modes that have specic LCD output
and dedicated controls:
* Control Display will not allow changing of button in case of lock mode activated.
Page 58
Page 58
5.4 Setting the Clock
BC
AD
The P-950EH Control Display does NOT have a daily timer or programmable thermostat.
Setting the Clock
a. Press and hold the ‘Clock button’ for about 5 seconds. Set the ‘Year’ by turning the dial E. And
then, press the dial E to Save.
b. Set the ‘MON’ (Month) by turning the dial E to the desired month number. Then press the dial E to Save.
c. Set the ‘DATE’ (1-31, Day of the Month) by turning the dial E. Then press the dial E to Save.
d. Set the ‘HOUR’ (1-24, Hour of the Day) by turning the dial E. Then press the dial E to Save.
e. Set the ‘MIN’ (1-60, Minute of the Hour) by turning the dial E. Then press the dial E to Save.
f. Set the ‘Day’ (Sun - Sat) by turning the dial E. Then press the dial E to Save.
E
To Exit at any time, tap the button.
Page 59
The FT Series Heating Only, Boiler
5.5 CH Set Point Change Mode
CH Set point Change Mode
BC
Page 59
AD
To change CH Setpoint, press the C
CH Setpoint will ash.
Turn the E dial clockwise to increase, and counterclockwise to decrease CH setpoint, until
desired temperature is reached.
Press E dial to save changes and to Exit.
IndicateIndicator
Current CH Temperature Set-Point
Celsius or Fahrenheit
If Communication state is activated
If ame is detected
Date and Time indicator
E
button. The CH Icon and current
or
If CH pump is operating
If there currently a Demand for Central Heat (CH)
Default CH set-point is 180°F (82°C)
CH set-point range is 86°F ~180°F (30.0°C ~ 82.0°C)
Page 60
Page 60
5.6 Status Display Mode
To change any Status Parameter,
Press and Hold Button B
to get into the Status Display Mode.
Rotate Dial E until you nd the Parameter that you wish to change. Tap Dial E to enter that Parameter.
Adjust to the setting that you require and then press (tap) Dial E to save and to Exit.
NOTE: For Cascading
Installations, please refer to
document 1349 ‘Cascading
BC
the FT Series Boiler’,
available online.
AD
Digital Display
O: otOutdoor temperatureCurrent outdoor sensor temperature
A: In0-10 V displayCurrent voltage of (0-10V input)
b: ttCH target temperature in cascade system
C: ItCH return water temperature Current CH return water temperature
d: FrFAN speed ( rpm)Current FAN speed ( RPM)
E: oP
F: EhExhaust gas temperatureCurrent exhaust gas temperature
Status Display Parameter
CH supply temperature (Operating temperature)
E
Description
Current CH target temperature or Current
System target temperature in a cascade system
Current heating temperature
Indirect DHW tank temperature
H: dH
I: oHOverheat water temperatureCurrent Overheat water temperature
1: PH
2: rh
L: rt
M:
CC
N: St
3: rH
4: ItCycle for ignition
5: IH
SELFPercentage of self units running. Percentage of self units running.
ALL
F1 – F
19
* If temperature sensor is not connected
then it will display with 0°F (0°C).
Time for supply power
Time for burner
operation
Burner Operation
Time
Capacity for all operating
cascade units
Capacity for individual boilers
System Temperature (cascade
mode) * If system temperature
sensor is not connected then it will
display with 0°F (0°C).
Time for burner
operation
Cycle for ignition
Percentage of all cascade units running.
This screen shows the overal cascade power output. The
range of this value of boilers communicating with theMaster
x 100. For example, if 8 boilers are connected and
communicating, the maximum cascade power is 800%.
Range: 0-100%
Percentage of each cascade units running.
Ex. F1, F2, ….
Current System Temperature (cascade mode)
Current DHW tank temperature
Unit : 1000hour
Unit : 1hour
L: rt on display
on sub menu
Unit : 1,000hour
Cycle : 10 times the
displayed unit
Cycle : 10,000 times the
displayed unit
Page 61
The FT Series Heating Only, Boiler
5.7 Installer Mode
These changes are to be made only by a qualied technician.
BC
Page 61
AD
To c hange any of the Installer Parameters,
Display Control.
Then, with the power OFF, Press and HOLD (more than 5 seconds) the Button B to get into the Installer Mode.
Rotate Dial E until you nd the Installer Parameter (full list on facing page) that you wish to change. Tap Dial E
to enter that Parameter.
Adjust to the setting that you require and then press (tap) Dial E to save and to Exit.
Finish by pressing button B
Index
Numbers
1: EH
2: cE
Error history up to 10Check last 10 error codes (E0 - E9)
Delete Error history
ParameterDescription
Select “ON” to delete error code history
Range: ON or OFF,Default OFF
E
Start by turning OFF the Power to the
3: In
4: OH
5: OL
6: cH
System initializeSelect “ON” to reset to factory setting,Default OFF
When used with an outdoor sensor, sets the maximum outdoor
Maximum Outdoor
Temperature
Minimum Outdoor
Temperature
Maximum Supply
temperature
design temperature for the system design. Maximum outdoor
temperature must be set at least 9°F above the minimum outdoor
temperature. Range: (Minimum Outdoor Temperature + 9°F) to
110°F , Default 68°F
Sets the minimum outdoor design temperature for the system.
Minimum outdoor temperature must be set at least 9°F below the
maximum outdoor temperature.
Range: -4°F to (Maximum Outdoor Temperature - 9°F), Default 5°F
Sets the maximum design supply temperature based on the
minimum outdoor design temperature. Maximum supply temperature
must be set at least 9°F above the minimum supply temperature.
Range: (Minimum Supply Temperature + 9°F) - 180°F, Default 180°
F
Page 62
Page 62
5.7 Installer Mode (continued)
Numbers
7: cL
8: OF
9: bt
10: bd
11: bI
12: FH
13: FL
14: dr
15: dI
16: Ft
17: bo
18: cb
19: db
20:PE
21: dH
22: dd
23: Pr
24: dP
25: St
26: FP
Index
ParameterDescription
Sets the design supply water temperature based on the
Minimum Supply
temperature
Warm Weather
Shutdown
Boost Function
Boost Degree
Boost Interval
Maximum Fan speed
Minimum Fan speed
Initialized burner
operation time
Initialized ignition cycle
CH Anti-Cycling time
Set differential
temperature to turn
burner “ON”
Heating capacity
DHW capacity
Heating Pump Post-
Purge Time,
T/T Satised
Indirect Storage Tank
Temperature Set Point
Indirect Storage Tank
Differential Set Point
DHW Pump Post Run
Time
DHW Priority Timer
Boiler Supply Indirect
Storage Tank
Temperature
System Freeze
Protection Mode
maximum outdoor design temperature. Minimum supply
temperature must be set at least 9°F below the maximum
supply temperature. Range: 40°F to (Maximum Supply
T emperature - 9°F) , Default 86 °F
This warm weather temperature setting will shut down CH
Mode Range : 50 °F- 110°F, Default 68 °F
This function boosts CH temperature to the maximum if
set point is not reached within the set period of time.
Range: 0 - 120 min, Default 0
The boiler will add this temperature to the boiler target set
point based on outdoor reset curve. Range: 5-15°F
Default: 10°F
The boiler will index the temperature based on time
interval set on 11 bI. Range: 0-120 MIN
Default: 20 MIN
Adjusts Maximum Fan Speed
Range: -30 to +30,Default 00
Adjusts Minimum Fan Speed
Range: -30 to +30,Default 00
Select ON to Initialize burner operation time
Range: NO or YES,Default NO
Select ON to Initialize ignition cycles
Range: NO or YES,Default NO
This function delays burner operation during CH mode
Range: 0 - 20 min, Default 1
When set, the appliance will operate to heat CH water
when water temperature falls below a differential setting.
Example: If set point is 180°F and differential is 27°F, the
appliance will turn on when CH water temperature falls
below 153°F. Range: 5°F - 30°F, Default 30°F
Allows the user to set the appliance pump post purge time
once the thermostat is satised. Range: 1-5 minutes ,
Default 1
Sets Maximum Indirect storage tank Temperature
Range:95 - 180°F , Default 120 °F
DHW Differential Set Point
Range: 5°F-30°F, Default 7 °F
DHW Pump Post Run Time
Range: 0-10 Min , Default 1 Min
DHW Priority Timer
Range: 0 – 60 Min , Default 30 Min
Boiler Supply Indirect Tank Temperature
Range: 120 °F– 180 °F , Default 180 °F
System Freeze Protection Mode. This mode should be
turned OFF for snow melt application. NOTE: This mode
should be ON during normal operation. Range: ON/OFF
Page 63
The FT Series Heating Only, Boiler
Page 63
Numbers
27: Cn
28: CP
29: Eh
30:Cr
31: Ct
32: Cd
33: HA
Index
Auto
Cr:Ct
AP:cP
ParameterDescription
Cascade Number
Cascade Parameter
Common Vent
Automatic rotation
Cascade Rotation time
Cascade System
temperature
Cascade System
Temperature Differential
(burner ON)
High Elevation Mode
Internal CH Pump, CH
Pump and DHW Indirect
Pump Test Mode
Cascade Number
Range: 0 (Master), 1(slave 1), …., 19(slave 19)
“29: CP” has to be set with the total number of units in the
cascade before “28: Cn” can be set. Default 0
Number of units cascaded
Range: 1- 20 , Default 1
Common Vent
Range: ON / OFF, Default OFF
The rst unit to operate when there is a T/T call is the unit
that ran the least amount of time during the prior heat calls.
Cascade Rotation time
Range: 0-240 Hours, Default 48 Hours
Cascade System temperature:
Range: 9°F – 180°F, Default 180°F
Cascade System Temperature Differential (burner ON)
Range: 5°F-30°F, Default 10°F
High Elevation Mode ( 0-2, 2-5, 5-8, 8-10 ),
Default HA 0
This function sets the time to run both the Internal CH and
Internal DHW Storage pumps to purge air from the system.
Range: 1 – 30 minutes,Default 5
P1:oF or
34:AP
P1:on
P2:oF
or
P2:on
SS:Sd
35: SS
SS: br
FAH(°F)
36: UC
CEL(°C)
37: CM OFF
38: dM OFF
AquA
39: SA
SEnS
Internal CH Pump and
CH Pump Test Mode
Internal CH Pump and
DHW Indirect Pump Test
Mode
Allows the user to set the
year of next service
reminder
Allows the user to set the
service reminder based
on BURNER RUN HOURS
Allows the user to
change the unit
CH Step Modulation
DHW Step Modulation
Select Aquastat (contact)
Type
Select DHW NTC
Sensor Type
Turn this function on to activate Internal CH and CH pump
testing. Only works in installation mode. Turns off when in
normal mode. Default OFF
Turn this function on to activate Internal CH and DHW
Indirect pump testing.
Only works in installation mode. Turns off when in normal
mode. Default OFF
Allows the user to set the year of next service reminder
XX / XX / XXXX (MONTH / DAY / YEAR)
Allows the user to set the service reminder based on
BURNER RUN HOURS
(0: OFF, 1~9000Hours) , Default 0
Allows the user to change the unit
Range: °F or °C
Allows the user to turn ON the step modulation, which
regulates burner output in six steps at one minute intervals.
Step modulation will start at the last modulation rate of the
boiler and work up one minute at a time.
Default: OFF (Selection: OFF or ON).
This mode is aquastat (contact) type.
This mode is NTC sensor type.
NOTE: If Parameter 39 does not appear in the Installer
mode, reset the unit using Parameter 3. After a factory reset,
Parameter 39 will again appear.
Page 64
Page 64
5.8 Storage Mode
Storage Mode / Indirect Water Heater
BC
AD
E
To change Storage Mode Temp, First turn OFF the power to the Control Display.
Then Press and Hold Button B
Rota te Dial E until you nd 25:St Tap Dial E to enter Storage Mode. Storage Mode indicates that the
boiler is heating the water held in an indirect water heater. When Storage Mode is active, the display will
appear as shown.
Turn the E dial clockwise to increase, and counterclockwise to decrease setting.
Press E dial to save changes and to Exit.
IndicateIndicator
Current CH set-point of temperature
Celsius or Fahrenheit
If ame detected
to get into the Installer Mode.
or
Storage mode indication
If there is a Demand for Central Heat (CH)
Page 65
The FT Series Heating Only, Boiler
5.9 Outdoor Reset Adjustment
Outdoor Reset varies the control setpoint based on
the outdoor temperature. The reset function works
as shown in Figure ‘CH Outdoor Reset’. When the
outdoor air temperature reaches 4:OH “high outdoor
temperature setpoint”, the control point setting is
adjusted to 7:cL “low boiler temperature setpoint”.
When the outdoor air temperature reaches 5:OL “low
outdoor temperature setpoint” the control setpoint is
adjusted to 6:cH “high boiler temperature”.
Page 65
Operating condition
Default outdoor reset setpoint is 100°F (38°C)
The Outdoor Temperature Mode Icon on the display
will ash if an Outdoor Sensor or 0-10 Volt is not
connected to the appliance.
To check the CH Target Temperature while using
Outdoor Temperature Mode, press the
while the appliance is operational and the display
panel is powered on.
Connect to terminal strip as outlined 4.17 Electrical Connections.
NOTE: 0 - 10VDC terminals may not be used for both outdoor reset and 0 - 10VDC temp
setpoint simultaneously.
button
Outdoor Reset
5.10 External Set Point Temperature Control
A signal from a building management system may be connected to the appliance to enable remote
control. This signal should be a 0-10 volt DC signal. When this input is enabled, a building control
system can be used to control the set point temperature of the appliance.
(warm weather shutdown)
The control interprets the 0-10 volt signal as follows; when the signal is between 0 and 1.5 volts, the
appliance will be in standby mode, not ring.
When the signal rises above 1.5 volts, the appliance will ignite. As the signal continues to rise
towards its maximum of 10 volts, the appliance will increase in set point temperature. Adjust 6:cHand 7:cL to set MIN and MAX boiler water temperatures respectively.
Connect a building management system or other auxiliary control signal to the terminals marked
for this purpose on the appliance terminal block (shown in Piping Diagrams, this manual). Caution
should be used to ensure that the 0-10 VOLT + connection does not become connected to ground.
Connect to terminal strip as outlined 4.17 Electrical Connections.
NOTE: 0 - 10VDC terminals may not be used for both outdoor reset and 0 - 10VDC temp
setpoint simultaneously.
Page 66
Page 66
5.11 Error Mode
The Control Display will show the following information when an Error is presented.
IndicateIndicator
Flashing
Error ‘ Er : ’ sign Segment
Error Code
If Communication state is activated
NOTE: When communication between the Control Display and the main controller is lost, the
will not be displayed.
Er:11
Page 67
The FT Series Heating Only, Boiler
SECTION 6 Error Codes
6.1 Error Code Table
Page 67
Error
Code
10
11
16
20
28
32
33
Error Code
Description
Flame has
Extinguished 8 (Eight)
Times
Ignition has Failed 10
(Ten) Times
Operating
Temperature Sensor
detects Water
Temperature Greater
than 203°F (95°C)
Condensate – Closed
is Normal, Open is
Fault (Condensate
Drain Trap)
Overheat Sensor Open
or Short
DHW Sensor Open or
Short
CH Temperature
Sensor Open or Shor t
Possible Remedies
Press the Power button to clear the Error Code.
If Error happens again:
1. Monitor the gas pressure to the appliance while in operation. Ensure pressure is
between 3.5" to 10.5” WC (Natural Gas) and 8" to 13" WC (Propane).
2. Check gas valve wire. Ensure connection is secure.
3. Check ame detection sensor. Ensure connections are secure. Normal operating
settings are more than 2.5DC before ignition, less than 2.5DC after ignition.
4. Check vent terminations. Ensure there are no blockages.
5. Assure that the ame is stable when lit.
6. If the problem persists, replace the main control.
Press the Power button to clear the Error Code.
If Error happens again:
1. Monitor the gas pressure to the appliance while in operation. Ensure pressure is
between 3.5" to 10.5” WC (Natural Gas) and 8" to 13" WC (Propane).
2. Check gas valve wire. Ensure connection is secure.
3. Check ame detection sensor. Ensure connections are secure. Normal operating
settings are more than 2.5DC before ignition, less than 2.5DC after ignition.
4. Check igniter transformer for proper connection.
5. Clean the spark igniter with steel wool to remove oxides. Ensure proper separation (3-4 mm).
6. Replace the spark igniter if damaged.
7. Assure that the ame is stable when lit.
8. If the problem persists, replace the main control.
Press the Power button to clear the Error Code.
If Error happens again:
1. Check if dip switch Max Fire setting is ON. Switches 6 and 7 should be OFF for
normal operation.
2. Check if CH inlet pipe is blocked. Ensure there is enough water owing to the
appliance.
3. Check Operating Temperature sensor at CH heat exchanger outlet. If resistance is
zero, replace the sensor.
4. If the problem persists, replace the main control
Press the Power button to clear the Error Code.
1. Check Condensate and main controller connections. Ensure all are secure.
2. Check Condensate sensor resistance. If resistance is zero, replace the switch.
3. Check Condensate hose. Ensure it is connected and in good condition.
4. Check condensate line and termination for blockages.
5. Check Vent Pipe for blockages.
6. If the problem persists, replace the main control.
This Error Code will go away when CH temperature decreases.
If Error happens again:
1. Check overheat temperature sensor. Ensure connections are secure.
2. Check overheat sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
This Error Code will go away when outlet DHW temperature decreases.
If Error happens again:
1. Check DHW outlet temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
This Error Code will go away when CH temperature decreases.
If Error happens again:
1. Check CH temperature sensor. Ensure connections are secure.
2. Check CH sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
Recover
methods
Hard
Lock
Hard
Lock
Hard
Lock
Hard
Lock
Soft Lock
Soft Lock
Soft Lock
Page 68
Page 68
Error Code Table (continued)
Error
Code
35
37Abnormal Supply Frequency
38
40
41
42LWCO Jumper Disconnected
43
44
45
61
Error Code DescriptionPossible Remedies
Venting (Exhaust) Sensor
Open or Short
Error Appears When Control
Stores Data, but Data is not
Saved
Gas Leakage is Detected for
Greater than 5 seconds, or
three times within 10 minutes
Fan Speed too High with
Flame On
Burner Overheat Switch
Open
Air Pressure Sensor (APS)
Fault
Air Pressure Sensor (APS)
Open
Fan Speed Feedback Signal
Abnormal
This Error Code will go away when exhaust temperature decreases.
If Error happens again:
1. Check Venting (exhaust) temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. Check vent pipes for blockage.
4. If the problem persists, replace the main control
Supply frequency is too high to operate. This Error Code will go away when
supply frequency returns to normal operating range.
If Error happens again:
1. Ensure appliance is properly wired to a power source meeting the
requirements on the rating plate.
2. If problem persists, replace the main control.
Press the Power button to clear the Error Code.
Replace the main control.
IMPORTANT: If you smell gas, STOP! Follow the instructions on page 2, this
manual, and call a qualied ser vice technician or the fuel gas utility.
Press the Power button to clear the Error Code.
If Error happens again:
1. Check the appliance cover. Ensure it is secure.
2. Check gas connections for leakage with a soapy solution. Fix any leaks.
3. Check condition of the burner assembly.
4. If the problem persists, replace the main control.
Press the Power button to clear the Error Code.
If Error happens again:
1. Check the vent connections for blockages.
2. Check the burner assembly.
3. Check fan operation. If fan appears to be operating normally but RPMs are too
high, replace the fan.
4. If the problem persists, replace the main control.
Press the Power button to clear the Error Code.
If Error happens again:
1. Ensure the LWCO Jumper is properly connected.
2. If the problem persists, replace the main control.
Press the Power button to clear the Error Code.
If Error happens again:
1. Check burner overheat switch connections. Ensure connections are secure.
2. Check switch resistance. If resistance is zero, replace the switch.
3. If the problem persists, replace the main control.
Press the power button to reset
If error happens again:
1. Check the vent pipe for blockages.
2. Check the vent pipe for blockages.
3. If error do not clear, replace the APS
4. If the problem persists, replace the main control.
Check the aps connection.
1.If APS is closed and connections are secure, check APS connection.
2. If the problem is not happen, replace the APS
3. If the problem persists, replace the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check the connections to the fan. Ensure all are secure.
2. If the fan does not rotate during the ignition sequence, check for AC8V~26.5V
power at the fan connection. If AC8V~26.5V power is present at the control,
replace the fan. If the blower does not have AC8V~26.5V power, check power at
the control. If AC8V~26.5V power is not present at the control, replace the control.
3. If the problem persists, replace the main control.
Recover
methods
Soft Lock
Soft Lock
Hard Lock
Hard Lock
Hard Lock
Soft Lock
Hard Lock
Hard Lock
Soft Lock
Soft Lock
Page 69
The FT Series Heating Only, Boiler
Page 69
Error
Code
70
72
76
78Cascade ErrorPlease refer to Manufacturer Document 1349 for Cascading the FT.
80
81Low Water Level Circuit
85
94
Error Code DescriptionPossible Remedies
Register, Ram, Rom, I/O
Port, AD Abnormal, Impor tant
EPROM Data or Safe Data
Abnormal
Flame Signal Detected before
Ignition
Poor Communication
(Control Display)
Low Water Level Sensor
(Low Water Level Detected
Four (4) Consecutive times)
Freeze Protection
(Appliance has detected
water temperature below
34°F(1°C)
Exhaust Sensor detects Vent
Temperature is Greater than
190oF (88oC)
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Turn power OFF and ON at the main power switch internal to the appliance.
2. If the problem persists, replace the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check the appliance cover. Ensure it is secure. Flame detection sensor can detect
an external light source.
2. Check flame detection sensor. Ensure connections are secure. Normal operating
settings are more than 2.5DC before ignition, less than 2.5DC after ignition.
3. If the problem persists, replace the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check connections from main control to display panel.
2. If the problem persists, replace the display and/or the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Ensure all valves are open to the appliance and there are no leaks.
2. Ensure all air has been purged from the system.
3. Check wiring connections to low water level sensor. Ensure all are secure.
4. Check low water level sensor resistance. If resistance is zero, replace the sensor.
5. If the problem persists, replace the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Ensure all valves are open to the appliance and there are no leaks.
2. Check wiring connections to low water level sensor. Ensure all are secure.
3. Check low water level sensor resistance. If resistance is zero, replace the sensor.
4. If the problem persists, replace the main control.
This Error Code will go away when the freezing condition is remedied.
If Error happens again:
1. Ensure appliance is located in a mechanical room protected from freezing conditions.
2. Ensure all valves are open to the appliance, there are no leaks.
2. Check wiring connections to low water level sensor. Ensure all are secure.
3. Check low water level sensor resistance. If resistance is zero, replace the sensor.
4. If the problem persists, replace the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check if dip switch Max Fire setting is ON. Switches 6 and 7 should be OFF for
normal operation.
2. Check exhaust temperature sensor. Ensure connections are secure.
3. Check sensor resistance. If resistance is zero, replace the sensor.
4. Check exhaust vent for blockage.
5. If the problem persists, replace the control.
6. If the problem persists, replace the heat exchanger.
E28DHW NTC open or short
E33OP NTC open or short
E35Exhaust NTC open or short
Page 72
Page 72
SECTION 7 Trouble Shooting
7.1 Diagnostics
QuestionAnswer
Make sure that the ON/OFF button on the Control Display has been turned ON.
If the monitor on the Control Display is blank, make sure the power cord is
plugged and 4A fuses on the main controller in the units are good.
Burner does not ignite
when the hot water is
opened.
Make sure that there is water supplied to the unit. The unit activates once
the inlet water ow is over 0 gpm.
Make sure the cold and hot water lines are not plumbed in reverse side.
Make sure that the cold water and gas supply lines are opened.
Make sure that the water lines are not frozen.
Check that the setting temperature on the unit is not too low
Make sure that the lter in the cold water supply line is not clogged with debris.
Water is not hot enough.
Water is too hot.
Hot water temperature
uctuates at the opened
tap.
The blower is still
operating after the
combustion stops.
Temperature Rise
too Quickly
Abnormal sounds come
from unit during
operation.
Heater doesn’t re when
DHW ow is initiated
CH Temp drops lower
than expected before
unit re-res
Make sure that the gas supply type is correct.
Check the supply and manifold gas pressures are in accordance with specications.
Make sure that the water ow sensor with three wires has been properly
connected on the top of heat exchanger.
Make sure that the setting temperature on the unit is not too hot.
Make sure that the lter in the cold water supply line is not clogged with debris.
Make sure that the gas supply type is correct.
Make sure that the lter in the cold water supply line is clean.
Make sure that the gas supply type is correct.
Check the supply gas pressure is sufcient.
This is normal because the blower keeps operating for 1 minute to vent
(exhaust) the ue gas from the chamber once the combustion has stopped.
Occurs when supply water temperature in heat exchanger rises faster
than 2°F per second during the rst two minutes the burner is on.
Automatically resets after a few minute delay or using manual reset on
Control Display. See message displayed TEMPERATURE SENSOR and
follow procedure for loose connections.
A leak of combustion gas between sealed chamber and exhaust tube
inside the unit. Call a qualied service technician for evaluation.
Improper venting termination, make sure that the venting termination
complies with specication.
Check the supply gas pressure is sufcient. Insufcient gas pressure will
cause unstable burner ame and noise.
Potentially the domestic water ow is too low. Min allowable is 0.75 gpm.
Check in Manual Mode OTO AGA
Change Parameter 14:bo to 10degrees F (5.5 degrees C)
Page 73
The FT Series Heating Only, Boiler
7.2 Suggested Corrective Actions
This controller is able to record information about the boiler’s condition at the time of the ve previous faults or
errors. Refer to the Section ‘5.10 Error Mode’ of this manual.
DisplayConditionDiagnosticCorrective Action(s)
Page 73
Nothing shown
on display
Control Display
and blower
running at full
speed.
Nothing is shown
in display Control
Display and no
other boiler
components are
operating.
Control is not
receiving power.
Control is not
receiving 120V power.
Check wiring for short
circuit or incorrect
wiring.
Check transformer
connection to the
control per wiring
diagram. Check for
12V output of
transformer.
Check service switch
and/or circuit breaker
to boiler turned is on.
Is there 120 Volts at
the service switch?
Is the ON/OFF
POWER
SWITCH (inside boiler
case) turned on?
Check for 120 volts at
the line voltage
terminal block located
inside the boiler case.
Correct wiring per wiring diagram
including connection of transformer to
the control.
Replace transformer if it is receiving
120V, but not outputting 12Vac.
Turn on service switch to power boiler.
Troubleshoot and correct the power
supply to the manual switch.
Turn ON the manual power switch
inside the boiler case.
Correct wiring inside the boiler case
using the wiring diagram in this
manual.
Nothing is shown
on
Control Display,
but boiler is
operating.
Occurs when the
communication is lost
from the control to the
display.
Inspect the fuse.
Replace if necessary.
Check for loose
connections and
proper pin alignment/
engagement on the
Control's plug.
Cycle power off and on
using boiler power
switch and check for
operation.
Replace the fuse with proper part
found in the replacement part section
of this manual. If fuse blows again
recheck wiring per diagram.
Check for continuity on the wire
harness from the display to the control.
See repair parts section for proper
replacement part.
Replace with new display module. See
repair parts section for proper
replacement part.
Page 74
Page 74
7.2 Suggested Corrective Actions (continued)
FaultConditionDiagnosticCorrective Action(s)
Occurs when a
temperature
TEMPERATURE
SENSOR
FLAME FAULT
sensor has
electrically
shorted
(SHORT) or has
become
disconnected
(OPEN).
Occurs when
ame is
detected when
there should be
no ame.
Reset using manual
reset screen on
Control Display.
(Power button)
Reset using manual
reset screen on
Control Display.
(Power button)
Check all the temperature readings of
the boiler on the DIAGNOSTICS
- TEMPERATURES menu to determine
if any sensors are currently displayed
as SHORT or OPEN.
Check wire harness for loose
connections and pin engagement at
sensor Connection and Control
module.
If problem persists after checking items
above replace Control. Refer to repair
parts section for kit number.
Burner may be operating too hot due
to incorrect combustion. Inspect ame
and conduct combustion test.
Check for ame at burner via ame
current with burner off. Turn boiler off
and watch ame through observation
port. If ame continues after shutdown
replace gas valve.
Check wire harness for loose
connections and pin engagement at
blower.
Connections.
BLOWER FAULT
IGNITION
FAU LT
GAS VALVE
FAU LT
Blower unable
to reach
required speed
or does not
reach 0 RPM
when turned off.
Even if boiler
went through 8
ignitron
attempts, but
cannot detect
ame
The Control has
detected a
problem with it
gas valve
output circuit.
Reset using manual
reset screen on
Control Display.
(Power button)
Power off and on.
Reset using manual
reset screen on
Control Display.
(Power button)
Boiler in standby mode and blower not
running. If BLOWER SPEED is not 0
RPM then replace blower.
If blower does not rotate during ignition
sequence check for 120V power at
blower connection. If 120Vac power at
blower motor and it doesn't start
replace blower. Check power at
Control. If 120Vac is not present at
Control when boiler is powered replace
Control.
Dirty burner and/or heat exchanger will
cause high back pressure and poor
ignition.
Visual inspection of ue ways often will
not be able to diagnose condition.
Check incoming gas pressure with
boiler off and at Max re. Adjust within
limits on rating label.
Check for ue pipe and intake pipe
restrictions or blockage
Check burner fasteners and gaskets
Check air intake pipe and proper
propane orice
Check wire harness connections
between gas valve and Control.
If lockout re-occurs replace Control.
Page 75
The FT Series Heating Only, Boiler
SECTION 8 Maintenance
8.1 Annual startup & general maintenance
Page 75
Regular Maintenance
- This Manual should be placed in a safe and dry
location near the Boiler. Maintenance instructions
should be carried out by the following guidelines.
Maintenance procedures [ Daily ]
- Check that the boiler casing is closed.
Check if there is any problem with the Boiler casing
and the two upper and lower screws are tightened
well. Boiler casing must be closed while it is
running.
WARNING
To prevent potential severe personal injury,
death or substantial property damage,
remove all contaminated materials.
If contaminants are found:
Remove products immediately from the area.
In order to check the status of Boiler, call
a qualied service technician to inspect
the Boiler for possible damage from acid
corrosion.
WARNING
DO NOT store combustible materials, gasoline
or any other ammable vapors or liquids near
the Boiler. Remove them immediately or store
them other places.
- Check the power source.
Make sure that the power cord is correctly
connected. The main power line is connected to
the manual switch box inside a Boiler. (Power line
through the strain relief in the bottom of the boiler
casing and x it.)
- Check the status of the Control Display
Check status of the power supply. Please check for
any debris on the button.
Maintenance procedures [ Monthly ]
- Check the vent pipe.
Visually inspect the ue gas vent piping for detecting
any signs of blockage, leakage or deterioration
of the piping. Please contact a qualied service
technician immediately if you nd any problem.
- Check the air inlet pipe.
Visually inspect the air inlet to be sure it is
unobstructed. Inspect entire length of air piping
for ensuring that piping is intact and all joints
are properly sealed. Call your qualied service
technician if you notice any problems.
- Check the relief valve.
Inspect the Boiler relief valve and the relief valve
discharge pipe for any signs of weeping or leakage.
If the relief valve often weeps, immediately contact
your qualied service technician for inspecting the
Boiler and system.
- Check the condensate outlet.
While the Boiler is running, check the discharge end
of the condensate drain tubing.
Make sure that no ue gas is escaping from the
condensate drain tubing.
If ue gas is continuously escaping, it is a serious
problem. Call your qualied service technician for
inspecting the Boiler and condensate line. Also, rell
the condensate trap if problem persists regularly.
- Check the vent terminal screen vent (rodent
screen).
If you encounter a problem of combustion
specications, visually inspect the terminal screen.
And then replace it with spare parts or clean the
screens.
Page 76
Page 76
8.1 Annual startup & general maintenance (continued)
- Check the air vent
If the air vent valve seems to work freely without
leaking, replace cap “A” by twisting all the way on.
Loosen cap “A” one turn to allow vent to operate.
If vent does not operate correctly, replace the vent.
A
lever completely, the valve or discharge line may be
blocked. Shut down the Boiler immediately. Call your
qualied service technician to inspect the boiler and
system.
- Check the burner state
You can clean the exterior of burner. However, if you
need to clean the inside of the burner stage, you
should call an expert.
Maintenance procedures [Every 6 Months]
- Check the boiler piping (gas and water)
Visually inspect for leaks around internal water
piping. Also inspect external water piping,
circulators, relief valve and ttings. Immediately
call a qualied service technician to repair any
leaks. Leaks must be xed by a qualied service
technician immediately.
Failure to comply with this instruction could result in
severe personal injury, death or substantial property
damage.
- Check the operate relief valve
WARNING
Leaks must be xed by a qualied service technician
immediately. Failure to comply with this instruction
could result in severe personal injury, death or
substantial property damage. This discharge line
must be installed by a qualied heating
installer or a service technician.
8.2 Flushing the Boiler
- Flushing the Boiler
Flushing the Heat Exchanger of boiler is a complicated
procedure. Refer to the following instructions
carefully before attempting the procedure. If you
do not understand about the procedure, contact an
authorized technician or licensed professional. Keep
in mind that improper maintenance can void your
warranty.
V3
V1
V4
V2
Before proceeding the procedures, verify that relief
valve outlet has been piped to a safe place of
discharge, avoiding any possibility of scalding from
hot water. If water ows freely, release the lever
and allow the valve to seat. Watch the end of the
relief valve discharge pipe to ensure that the valve
does not weep after the line has had time to drain.
If the valve weeps, lift the seat again to attempt
to clean the valve seat. If the valve continues to
weep, contact your qualied service technician for
inspecting the valve and system. If water does not
ow from the valve even though you have lifted the
1. Disconnect electric power to the boiler.
2. Close the shutoff valves on both hot water outlet
and cold water inlet lines. (V1 & V2)
3. Connect one hose “D1” to the valve “V3” and
place the free end in the bucket. Connect one
of the hoses “D3” to the circulation pump outlet
and the cold water inlet line at the valve “V4”.
Connect other hose “D2” to the circulation pump
inlet and place the free end in the bucket.
Page 77
The FT Series Heating Only, Boiler
4. Pour the cleaning solution into the bucket.
Place the drain hose (D1) and the hose (D2) to the
pump inlet into the cleaning solution.
5. Open service valves (V3 & V4) on the hot water
outlet and cold water inlet lines.
6. Turn on the circulation pump (Operate the pump and
allow the cleaning solution to circulate through the
boiler for at least 1 hour at a rate of 4 gallons per
minute.)
7. Rinse the cleaning solution from the boiler as follows:
- Remove the free end of the drain hose (D1) from
the bucket.
- Close service valve, (V4), and open shut off valve,
(V2).
Do not open shut off valve, (V1).
- Allow water to ow through the boiler for 5 minutes.
- Close shut off valve (V2).
Page 77
D1
D2
D3
8. Ensure service valves (V3 & V4) are closed and shut off valves (V1 & V2) are open.
9. Disconnect all hoses.
10. Remove the cold water inlet lter from the boiler and clean out any residues.
11. Reinsert the lter and ensure the lter cap is securely tightened.
12. Connect electrical power to the boiler.
8.3 Freeze Protection
FT Series Boilers are certied for indoor use only, and
are not design-certied for placement outdoors.
Proper precautions for freeze protection are
recommended for boiler installations in areas where
the danger of freezing exists.
Power outage, interruption of gas supply, failure of
system components, activation of safety devices, etc.,
may prevent a boiler from ring. Any time a boiler
is subjected to freezing conditions, and the boiler
is not able to re, and/or the water is not able to
circulate, there is a risk of freezing in the boiler
or in the pipes in the system. When water freezes,
it expands which may result in bursting of pipes, or
damage to the boiler, which could result in leaking or
ooding conditions.
Different glycol products may provide varying degrees
of protection. Glycol products must be maintained
properly in a heating system, or they may become
ineffective. Consult the glycol specifications, or the
glycol manufacturer, for information about specific
products, maintenance of solutions, and set up
according to your particular conditions.
Not all pumps are capable of maintaining the reduced
temperature rise required with glycol concentrations
greater than 35%.
NOTICE
NOTICE
Page 78
Page 78
Freeze Protection (continued)
WARNING
Do NOT use automotive antifreeze or ethylene
glycol. Use only inhibited propylene glycol
solutions which are specially formulated for
hydronic systems. Ethylene glycol is toxic
and can attack gaskets, seals, and metallic
components used in hydronic systems. A
correct glycol concentration and inhibitor level
is critical.
Some items to consider are
• Consider the effects of reduced heat transfer and
an increase in head pressure against the system
circulator. For example: A 30% mixture of glycol will
result in a BTU output loss of 15% with a 5% increase
in head against the system circulator.
• Glycol mixtures should not exceed 50%. A 50%
mixture of glycol will result in a BTU output loss of
30% with a 50% increase in head against the system
circulator.
• The glycol solution should be tested as
recommended by the glycol manufacturer but not
less than annually. Some items of concern are pH
additive breakdown, inhibitor reduction, etc.
• Glycol/antifreeze solutions expand more than water;
therefore, system design must take this into account.
For example: a 50% by volume solution expands
4.8% in volume for a temperature increase from 32◦F
to 180◦F, while water expands 3% over the same
temperature rise.
Caution
It is highly recommended to follow the manufacturers
recommended concentrations, expansion
requirements, and maintenance recommendations.
You must carefully calculate the additional friction
loss in the system as well as the reduction in the heat
transfer coefcients.
_________________________________________
SECTION 9 Installation Check
9.1 Quick View
Before Installing
- Make sure that there is enough space for installing
Water and gas line.
Verify vent/air termination is located as required.
- All models need for propane Conversion which
requires a separate gas conversion manual.
Install Water Piping
- Boiler loop piping must be sized to the minimums
listed in the Boiler manual. Using smaller piping will
cause performance problems.
Install Vent & Air Piping
- Slide the air inlet pipe and vent pipe into the Boiler
pipe connector.
- Make sure the terminations are placed as required in
the manual and that air intakes are at least 12 inches
above normal snow line.
- Refer to the material check list in this guide for a list
of items needed.
Install Condensate Piping / Tubing &
Components
- Fill out the material check list in this guide to ensure
you have the tubing or PVC pipe and all components
needed for the condensate piping.
- Connect internal components that are supplied with
the Boiler.
Install Gas Piping
- Install a union and shutoff valve.
Wire the Boiler
- Connect power wiring and control wiring per boiler
manual wiring diagram.(Section 4.19)
Start up, Adjust & Test
- Follow the Boiler manual instructions to clean the
system if needed, then ll and check water chemistry.
Page 79
The FT Series Heating Only, Boiler
9.2 Final Check Lists
Page 79
Final check : Installation Conditions.
• Is the Boiler properly mounted on the wall?
• Is there space for a drain which is close to the
Boiler?
• Are there any combustible materials near the
Boiler and vent pipe?
• Is the air supply sufcient for proper operation of
the Boiler?
• Are the proper service clearances maintained?
• Is the distance between the Boiler and point of
vent termination minimized?
• Is the proper distance from windows, doors, and
other intake vents maintained?
Final check : Gas pipe installation
• Is the gas supply line equipped with a manual
shut off valve?
• Is the gas supply line a minimum of 3/4˝ inner
diameter?
• Is the gas supply line length and diameter
adequate to deliver the required BTU’s?
• Has the gas supply line pressure been
measured?
• Does the supply gas type match the type
indicated on the boiler rating plate?
Final check : Connecting the power supply
• Please check that the power is 120V AC.
• Have you checked the polarity of the electrical
connection?
Final check : Pressure relief valve
• Have you properly installed an approved pressure
relief valve on the boiler?
Final check : Burner ames
• The burner ame must be checked periodically for
a constant proper blue color.
• If the ame does not appear normal, the burner
may need to be cleaned.
• If the burner needs to be cleaned, it must be
performed by a qualied service technician.
Final check: Air/Vent pipe installation
• Has the Boiler been vented with 3˝ or 2” PVC,
CPVC, Polypropylene or BH Special
Gas Vent (S636 PVC, CPVC) for Category IV
appliances in accordance with this manual and/or
your local code?
• Is the vent termination at least 12˝ above the
exterior grade?
• Is the total vent length within the maximum vent
length restriction?
• Have you checked the air/vent piping for leaks?
• Have you properly supported the vent
termination?
• Are all vent runs properly supported?
• Is the vent sloped upward toward the vent
termination at a rate of 1/4˝ per foot (2% grade)?
Final check : Condensate drain installation
• Have you installed a condensate drain line from
the Boiler to a drain or laundry tub?
Final check : Setting the DIP switches
• Are all DIP switches correctly set on the main
board?