Laars DP2000, DP3000 Installation, Operation And Service Manual

Installation, Operation and Service Instructions
Installation, Operation and Service Manual for the
XL-3 Oil-Fired Pool Heater
Models DP2000 and DP3000
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in pool heater installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
H0223500-
Page 2
TABLE OF CONTENTS
SECTION 1. General Information
1A. Warranty....................................................... 3
SECTION 2. Assembly & Installation
2A. Shipping Damage.........................................3
2B. Assembly and Location ................................3
2C. Outdoor Installation .......................................5
2D. Indoor Installation .......................................... 5
2D-1. Venting ......................................................... 5
2D-2. Clearances.................................................... 6
2D- 3. Combustion Air Supply.................................. 6
2E. Oil Piping ...................................................... 6
2F. Water Piping ................................................. 8
2F-1. Water Connections........................................ 8
2G. Pressure Relief Valve .................................... 9
2H. Automatic Chlorinators .................................. 9
2I . Electrical Wiring............................................9
2J. Time Clock Installation ................................ 10
2K. Special Pressure Switch ............................. 10
SECTION 3. Operating Instructions
3A. Start Up Procedure..................................... 10
3B. Setting the Time Clock...............................11
3C. Winter Shutdown ........................................ 12
3D. Periodic Maintenance ................................. 12
SECTION 4. Maintenance
4A. Trouble-Shooting........................................12
4B. Cleaning the Heat Exchanger .................... 13
4C. Trouble-Shooting Guide ............................. 13
4D. Operating Sequence................................... 14
4E. Trouble-Shooting........................................14
4E-1. Burner will not start (motor and
transformer do not come on) ...................... 14
4E-2. Burner Tries to Start, but the Primary
Control 10 Shuts Off (either motor or
transformer or both come on)..................... 15
4E-3. Oil Burner Will Not Shut Off....................... 15
4E-4. Setting the Correct Fuel-Air Mixture........... 15
4E-5. Regular Maintenance .................................16
SECTION 5. Service Information
5A. Control and Cad Cell Tests ........................ 17
5B. Control & Cad Cell
Trouble-Shooting Guide .............................17
SECTION 6. Parts List for Model DP Oil-Fired Heater
6A. Parts List .................................................... 18
Model DP Oil-Fired Heater
Page 3
SECTION 1. General Information
NOTICE TO INSTALLER: Deliver all
documents that come with the heater to the pool owner. These include the Owner’s Information and Operating Manual and this Installation Manual.
For your safety, do not store gasoline or other flammable liquids or vapors in the vicinity of this or any other appliance.
Use only #2 fuel oil or #2 diesel fuel. Heavier fuels will not operate satisfactorily, and their use will void the warranty.
NOTE: Read the Owner’s Information Manual
before starting this installation, and before starting up the heater the first time.
1A. Warranty
The XL-3 pool heater is sold with a limited
warranty. Details are specified on the back page of this manual. Make warranty claims to an authorized Laars representative or to the factory. Claims must include the serial number and model of the heater, installation date and name of the installer.
masonry must be laid with ends unsealed and joints matched to provide a free circulation of air through the masonry. Maintain the minimum clearances to combustible surfaces as specified in Sections 2C and 2D of this manual. The heater must be level.
The XL-3 is shipped with the inner stack packaged on top of the control panel door in the box with the heater. The inner stack must be assembled and installed before mounting the vent cap or vent
SECTION 2. Assembly & Installation
2A. Shipping Damage
After unpacking the heater, check for visible damage from shipment mishandling. Water Pik Technologies carefully manufactures, inspects and packages the heater before delivering it to the freight carrier. Immediately file any claim for damage against the freight carrier.
2B. Assembly and Location
Only use the XL-3 heater with pools filled with potable water. Using the heater with mineral water, salt water, sea water or other non-potable water will void the warranty. The installation must comply with all local building and safety codes.
Typically, install the heater on a noncombustible surface. Under Standard NFPA No. 31, it is permissible to install the heater on a combustible surface when the installation complies with the requirements of the American Insurance Association. These requirements specify that the surface under the heater must be hollow masonry not less than 4" thick, covered with at least 24 gauge sheet metal. The
DP-2000: 22½" DP-3000: 26¾"
Figure 1. XL-2 Oil-Fired Heater.
Page 4
Figure 2. Non-Combustible Platform. Figure 4. Inner Stack.
pipe. To assemble the inner stack, remove the tape and small envelope from the sheet metal coil. Expand the coil until the holes on each end are aligned. Use the two screws supplied in the small envelope to secure the ends together. Install the inner stack, 7" (18cm) diameter, on the collar of the flue collector before attaching the vent cap (outdoor installation) or vent pipe (indoor installation) as shown in Fig. 4. The XL-3 can be installed with the water connections on either side. Water Pik Technologies ships the heater with the water connections on the right side, but changing the connections to the left side could simplify the installation or improve access for service and maintenance. Make the change before locating and connecting the heater.
Follow these step-by-step instructions and
Figure 3 to reverse the heat exchanger:
Figure 3. Heat Exchanger Reversal.
1. Remove the control compartment door.
2. Remove the chimney cap assembly, or barometric draft control if one is installed, and the inner stack (1).
3. Remove the eight screws securing the top assembly (2) and lift off.
4. Bend back retaining tabs and lift out the wire guard (3). Take off the four V-baffles (2 each side).
5. Lift out the flue collector assembly (4).
6. Remove the siphon loop cover (5) located on the right side of the heater under the In-Out header.
7. Remove both gap spacers (6).
8. Disconnect the siphon loop on the header (7). Remove both drain cocks (8) (one at each end of the heat exchanger).
Model DP Oil-Fired Heater
9. Lift off both heat exchanger baffles.
10. Carefully remove the insulation at each corner of the heat exchanger; it will be re-used. Remove the four hold-down screws (10).
11. Unplug the electrical connector at the switch box inside the control compartment. At the other end of the conduit, loosen the brass compression fitting one or two turns. Rotate the conduit assembly and lay it on top of the heat exchanger.
FOR YOUR SAFETY: It is recommended that
two people perform the next step.
Page 5
12. Lift out and rotate the heat exchanger. Make sure the insulation strips stay in position under the header bars.
13. Put the screws through the hold-down clips at each corner of the heat exchanger. Put the insulation back in the corners.
14. Rotate the conduit assembly and attach it to the switch box. Tighten the compression nut on the other end.
15. Replace the heat exchanger baffles and the flue collector assembly.
16. Install the drain cocks and pipe plug according to the illustration (see Fig. 5).
17. Straighten the siphon loop tubing and connect it to the header where the drain plug was removed.
18. Replace the gap spacers, siphon loop cover and rubber plugs and grommets.
19. Install the T-baffles on the gap spacers to match the screw holes in the top assembly.
20. Replace the wire guard. Bend the tabs to secure it in place.
21. Attach the top assembly. Install the inner stack
Figure 6. Minimum Clearances, Outdoor Installation.
22. Install the chimney cap assembly, or barometric draft control if one was removed.
2C. Outdoor Installation
Install the Laars XL-3 heater in the open, or in an
enclosure without a roof. The chimney cap supplied with the heater must be installed. The danger of fire requires a minimum clearance from combustible surfaces or shrubbery of 6 inches (15cm) (see Fig. 6). The flue products must be dispersed in the outside air, and fresh air available for proper combustion. Do not install the heater under eaves where roof drainage could fall directly on the heater.
It is possible that prevailing winds could cause a
downdraft. Therefore, keep the side of the heater at least 3 feet (91 cm) from the face of any wall or fence.
2D. Indoor Installation
2D-1. Venting
If the heater is installed in an occupied building,
Figure 5. Connection Locations.
Figure 7. Incorrect Installation.
Page 6
Figure 8. Venting, Indoor Installation.
the room containing the heater must have its own combustion and ventilation openings as described below (see Fig. 8).
Vent the XL-3 to a permanent chimney or through the roof with an approved stack when it is installed indoors. You must install a barometric draft control between the heater and the stack with a minimum 13" clearance between the chimney connector and any combustible surface. Observe NFPA Standard No. 31 and all national and local ordinances.
Run the vent pipe as directly as possible with minimum turns. Never use a vent smaller than 9" (23cm). On lateral runs, maintain a minimum pitch of 1/4" (.6cm) per linear foot. If a chimney is used, the total equivalent straight length of flue piping between the heater and the chimney should not exceed 75% of the vertical height of the chimney above the flue pipe connection. The chimney should be at least 9" (23cm) diameter. Maintain adequate clearances between the vent pipe and combustible materials. Check local codes and the vent manufacturer’s instructions for proper clearances. The 7" (18cm) dia. inner stack must be in place.
Any change in the amount of draft in the combustion chamber can affect the flame characteristics. An approved barometric draft control must be used on all indoor installations to maintain a
clean and consistent flame. When the system is properly adjusted, the pressure in the stack below the draft control will be approximately minus .03" W.C. If this draft pressure cannot be achieved, the chimney is too short or too small. Take corrective action.
Avoid locating the chimney termination in a location susceptible to down draft conditions, or near ventilation inlets to the building.
2D-2. Clearances
Provide the following minimum clearances from combustible surfaces:
Water Inlet/Outlet side 24" (61cm)
Other side and rear 6" (15cm)
Front Control compartment 24" (61cm)
Chimney connector 13" (33cm)
2D-3. Combustion Air Supply
Do not install the heater in a room that does not have enough air supply to support combustion. There must be two openings to outside air provided; each opening must have a free area equal to 80 sq. in. (516.1 sq. cm). It is good practice to put one opening near the floor and the other near the ceiling.
When installing the heater in an interior room, all doors communicating with outside air must have specified openings (see Fig. 9). There must be no
Loading...
+ 14 hidden pages