Safety Information .…………………..………………………………………. 3
Receiving Inspection ……………………………………………………. ….. 4
Locating and Mounting Condensing Units ………………………………… 4 - 5
Locating and Mounting Evaporator Coils …………………………………. 6
Wiring …………………………………………………………………………. 7
Piping …………………………………………………………………………. 7 - 10
Leak Test ……………………………………………………………………… 11
Evacuation ……………………………………………………………………. 12
Refrigerant Charging ………………………………………………………… 13
Operational Start-Up ….……………………………………………………… 13 – 15
Compressor Superheat ……………………………………………………… 16
Evaporator Superheat ………………………………………………………. 17
Electric Defrost Timer ……………………………………………………….. 18
Air Defrost Timer …………………………………………………………….. 19
Maintenance ………………………………………………………………….. 20
Troubleshooting Charts ……………………………………………………… 21 – 23
Warranty Information ………………………………………………………… 23
System Start-Up Data Sheet ………………………………………………… 24
Wiring Diagrams………………………………………………………………. 25 – 46
Condensing Unit 115/1/60………………………...…………………………. 25
Condensing Unit 208-230/1/60…………………...…………………………. 26
Condensing Unit 208-230/3/60……………………………………………… 27Condensing Unit 460/3/60……………………………………………………. 28
Condensing Unit 208-230/1/60 w/Timer ……...…………………………….. 29
Condensing Unit 208-230/3/60 w/Timer………….……...………………….. 30
Condensing Unit Medium Temp Scroll 208-230/1/60.…………………....... 31
Condensing Unit Medium Temp Scroll 208-230/3/60.…………………....... 32
Condensing Unit Low Temp Scroll 208-230/1/60.………………………….. 33
Refrigeration System Low Temp Scroll 208-230/1/60.…………………….. 34
Condensing Unit Low Temp Scroll 208-230/3/60.………………………….. 35
Refrigeration System Low Temp Scroll 208-230/3/60.…………………….. 36
Air Defrost Evaporator 115/1/60.……………………………………………… 37
Air Defrost Evaporator 115/1/60 w/Timer.…………………………………… 38
Air Defrost with 2 Evaporators 115/1/60……..………………………………. 39
Air Defrost with 2 Evaporators w/Timer 115/1/60…………………………… 40
Air Defrost Evaporator 230V..………………………………………………… 41
Air Defrost Evaporator 230V w/Timer.……………………………………….. 42
Air Defrost with 2 Evaporators 230V……..…………………………………… 43
Air Defrost with 2 Evaporators 230V w/Timer ………………………………. 44
Electric Defrost Evaporator 208-230/1/60.………..…………………………. 45
Electric Defrost with 2 Evaporators 208-230/1/60………..…………………. 46
www.manitowocfsusa.com800-225-9916 2
General Safety Information
WARNING
Text in a Warning box alerts you to a potential personal injury situation. Read each
Warning statement before proceeding and work carefully.
CAUTION
Text in a Caution box alerts you to a situation in which you could damage the
refrigeration system. Read each Caution statement before proceeding and work
carefully.
Read this manual carefully before beginning the installation and operation of the
refrigeration system. Special attention is required to all sections identified with the
following warning and caution notices:
Disregarding these special notices may result in personal injury and/or damage to the
refrigeration system.
Safety Notices:
Installation and maintenance/servicing are to be performed only by trained and
qualified personnel familiar with commercial refrigeration systems.
Ensure that all field wiring conforms to the equipment requirements and all
applicable local and national codes.
Disconnect all power sources before servicing the refrigeration equipment.
Sheet metal and coil surfaces have sharp edges. Use appropriate protective
gloves to prevent injury.
Use appropriate eye protection during installation and servicing.
www.manitowocfsusa.com800-225-9916 3
Receiving Inspection
WARNING
Do not lift the condensing unit by the refrigerant tubing or components. These features
will not support the condensing unit weight. Injury and unit damage may occur!
CAUTION
Do not leave the condensing unit mounted to the wooden skid. This prevents all of the
unit supports from contacting the mounting surface. Excessive vibration and premature
equipment failure can occur.
Check the shipment carefully and compare to the bill of lading. Account for all items
listed and inspect each container for damage. Carefully inspect for any concealed
damage. Report any shortages or damages to the carrier, note on the bill of lading, and
file a freight claim.
Damaged material cannot be returned to the manufacturer without prior approval. A
Return Material Authorization (RMA) must be obtained. Contact a sales representative
at 800-826-7036.
Locating and Mounting Condensing Unit
General Guidelines:
Check the selected installation location to ensure that racks, braces, flooring,
foundations, etc. are adequate to support the condensing unit weight.
The installation location is clean, dry, and level.
Locate away from corrosive and noise sensitive atmospheres.
Use the condensing unit skid and base when moving the unit. Do not remove
unit from skid until the unit is moved to the mounting location.
Mount the condensing unit base to pads or structural rails using properly sized
bolts through the unit base.
www.manitowocfsusa.com800-225-9916 4
Clearance Requirements:
CAUTION
Failure to observe clearance and air flow requirements will result in poor system
performance and premature equipment failure!
BUILDING WALL
(VIEWED FROM ABOVE)
AIR
FLOW
AIR
FLOW
MINIMUM
DISTANCE
24”
INTAKE AIR
MINIMUM DISTANCE 24”
24”
INTAKE AIR
MINIMUM DISTANCE 24”
24”
Locate where there is a sufficient and unrestricted supply of clean ambient air.
Locate where this is adequate space for the removal of the heated discharged air
from the condensing unit area.
Do not position multiple units so that discharge air from one unit is blowing into
the condenser inlet air of the other unit.
All sides of the unit should be positioned a minimum distance equal to the total
width of the condensing unit away from any other unit, wall, or obstruction.
Example of Multiple Units with Horizontal Airflow
www.manitowocfsusa.com800-225-9916 5
Locating and Mounting Evaporator Coil
CAUTION
Failure to observe clearance and air flow requirements will result in poor system
performance and premature equipment failure!
Evaporator
Mounting
Bracket
Nylon Bolt
1” O.D. washer
1-5/8” O.D. washer
Nut
1” O.D. washer
Note: Fasteners are
supplied in the
mounting kit.
General Guidelines:
Do not place the evaporator above or close to door openings. This will help
prevent potential icing problems.
Allow a minimum clearance equal to or greater than the coil height on all sides of
the coil for proper air flow and service access.
Use the evaporator coil for a template to locate and drill the mounting holes (1/2”
diameter).
Place a 1” and a 1-5/8” washer on each nylon bolt and insert through the drilled
mounting holes.
Lift the evaporator coil until the nylon bolts extend through the mounting
brackets.
Install washers and secure with nuts. Tighten until the coil is firm against the
ceiling. The evaporator coil must be level.
Additional information is available in the installation manual supplied with the
evaporator.
Evaporator Coil Mounting Diagram
www.manitowocfsusa.com800-225-9916 6
WARNING
All wiring must comply with local and national codes. Wiring must be performed only by
a refrigeration technician or certified electrician. Failure to follow these guidelines may
result in injury!
CAUTION
Check all wiring connections, including factory terminals, before operation. Connections
can become loose during shipment and installation.
Wiring
All electrical connections and routing must comply with local and national codes. Do not
modify the factory installed wiring without written factory approval. The field wiring must
enter through the knockouts provided. Refer to the nameplate on the condensing or
evaporator coil to determine the proper electrical power supply. Wire type should be of
copper conductor only and properly sized to handle the electrical load. The unit and coil
must be properly grounded. Condensing unit wiring diagrams are attached inside the
electrical box cover. Evaporator coil wiring diagrams are located inside the installation
folder. Copies of the wiring diagrams are also available in the back of this manual.
Piping
General Requirements:
All refrigeration piping and components are to be installed in accordance with applicable
local and national codes and in conformance with industry refrigeration guidelines to
ensure proper operation of the refrigeration system. Only refrigeration grade copper
tubing should be used. Long radius elbows should be used. Short radius elbows have
points of excessive stress concentration and are subject to breaking at these points, do
not use short radius elbows. Suction lines must be insulated with a minimum ¾” thick
armaflex to reduce heat pick-up.
www.manitowocfsusa.com800-225-9916 7
Cleanliness:
CAUTION
The maximum air exposure for dehydrated condensing units is 15 minutes. Systems
exposed longer than 15 minutes must have the compressor oil and drier filter replaced.
Leaving a system exposed to the atmosphere for more than 15 minutes can result in
premature system failure.
CAUTION
The use of saws to cut tubing can contaminate the system with copper chips causing
premature system failure.
CAUTION
Dry inert gas must be passed through the system while brazing to prevent scaling and
oxidation. Scaling and oxides can clog refrigeration components resulting in system
failure.
Condensing units and evaporator coils are cleaned and dehydrated at the factory. The
condensing unit must remain closed and pressurized until the piping is complete and
final connections are ready to be made.
Do not remove system tubing covers until work is ready to be performed. Ensure that
all refrigeration tubing is clean and dry prior to installation. Use only tubing cutters when
trimming tubing to the proper length. Do not use saws to cut tubing.
Brazing joints require a dry inert gas, typically nitrogen, be passed through the lines at a
low pressure to prevent scaling and oxidation. Use only silver solder brazing alloys.
Minimize the amount of flux to prevent internal contamination. Flux only the male
portion of the joint. Thoroughly clean fluxed joints after brazing.
Pipe Supports:
All tubing should be supported in a least two locations (near the end of each tubing run).
Long runs will require additional support. As a guide, support 3/8” to 7/8” pipe every five
feet, 1-1/8” to 1-3/8” every seven feet, and 1-5/8” to 2-1/8” every ten feet. Do not leave
a corner unsupported when changing directions. Place supports within 2 feet of each
direction change. Piping that is attached to a vibrating object (such as a compressor or
compressor base) must be supported in a manner that will not restrict the movement of
the vibrating object. Rigid mounting will fatigue the tubing causing refrigerant leaks.
www.manitowocfsusa.com800-225-9916 8
Oil Traps:
CAUTION
Failure to properly install oil traps can prevent sufficient oil return to the compressor
resulting in premature compressor failure.
P-Trap
Pitch drain line
½” per foot
Seal and
Insulate
Typical Drain Installation
To ensure proper oil return to the compressor, a P-type oil trap should be installed at
the base of each suction riser of four feet or more. The suction trap must be the same
size as the suction line. Additional traps are necessary for long vertical risers. Add a
trap for each length of pipe (approximately 20 feet) to insure proper oil return. Suction
lines must slope ¼” per 10 feet toward the compressor. Install a suction line trap at the
evaporator outlet if the suction line rises to a point higher than the connection on the
evaporator.
Drain Lines:
Evaporator coil drain lines should be pitched a minimum of ½” per foot to allow proper
drainage and exit the walk-in as quickly as possible. Insulate and seal the drain line
where it passes through the wall. Copper drain line is required. If the refrigerated
space is 33°F or lower, drain line insulation and heat tape are required. Drain lines
must be insulated with minimum ½” thick armaflex. The drain line heat tape must be
wrapped around the copper drain line. Do not locate bends, elbows, or drain traps
within the refrigerated space. Do not reduce the drain line size. Locate a drain line Ptrap outside of the refrigerated space. Any traps exposed to low ambient temperatures
should be wrapped with a drain line heater (provide 20 watts of heat per foot of drain
line at 0°F, 30 watts per foot at -20°F.
www.manitowocfsusa.com800-225-9916 9
Pre-Charged lines and Quick Connects:
WARNING
Do not loosen and disconnect the quick connect fittings before reclaiming the refrigerant
and depressurizing the system. Disconnecting a pressurized system can result in
injury!
CAUTION
Quick connects are for one time use only. Once disconnected, the coupling cannot be
re-used. Refrigerant leaks will occur if the couplings are re-used resulting in poor
system performance.
Diaphragms
Cutter
Route the suction and liquid line sets between the condensing unit and evaporator coil
following the piping guidelines identified in this manual. Remove the dust caps from the
quick connect fittings and verify that the o-rings are intact. Wipe the coupling seals and
threaded surfaces with a clean cloth to prevent contamination. Lubricate the threads
and o-rings with Polyol Ester oil. Thread the coupling halves together by hand to
ensure proper thread mating. Tighten with a wrench until the coupling bodies “bottom”
or until there is definite resistance. Tighten an additional ¼ turn to ensure proper brassto-brass seating. Once the system is opened and pressurized, check each fitting for
refrigerant leaks. If a leak is detected, tighten until the leak stops.
www.manitowocfsusa.com800-225-9916 10
Leak Testing
CAUTION
If a braze joint is detected leaking, dry inert gas must be passed through the system
while repairing the joint to prevent scaling and oxidation. Scaling and oxides can clog
refrigeration components resulting in system failure.
CAUTION
Always use the system specified refrigerant when pressuring to perform a leak test.
After all connections are complete the refrigeration system must be tested for leaks.
Failure to perform a leak test can result in unsatisfactory system performance,
additional servicing and service costs, and possible system failure. Leak test should be
performed using an electronic leak detector. All joints and components, both factory
and field installed, should be thoroughly inspected for leaks. The system installation
must be leak free!
Leak Testing “PR” model systems:
Open both the liquid and suction service valves.
Ensure the solenoid valve is energized and open.
Add 50 psi refrigerant, then pressurize with dry nitrogen to the low side test
pressure identified on the unit rating label.
Allow thirty minutes for refrigerant to reach all parts of the system.
Check all joints and components with an electronic leak detector.
Leak Testing “PC” model systems:
Leave the service valves closed, the condensing unit is charged with refrigerant.
Ensure the solenoid valve is energized and open.
Add 50 psi refrigerant, then pressurize with dry nitrogen to the low side test
pressure identified on the unit rating label.
Allow thirty minutes for refrigerant to reach all parts of the system.
Check all joints and components with an electronic leak detector.
Leak Testing “PCL” model systems:
Open both the liquid and suction service valves.
Ensure the solenoid valve is energized and open.
Allow thirty minutes for refrigerant to reach all parts of the system.
Check all joints and components with an electronic leak detector.
If a leak is detected, relieve the pressure and/or reclaim the refrigerant and repair the
leak. If additional brazing is required, pass a dry inert gas (nitrogen) through the system
to prevent contamination. Reference page 10 of this manual for leaks located at quick
connects couplings. Retest the system as outlined above until no leaks are detected.
www.manitowocfsusa.com800-225-9916 11
System Evacuation
CAUTION
Do not use the system compressor to evacuate the system. Do not start the
compressor while the system is under vacuum. This may damage to the compressor
and cause premature system failure.
Evacuation of the refrigeration system is necessary to remove all air and moisture from
the system. A reliable rotary vacuum pump with an accurate deep vacuum gauge is
recommended. Do not use the system compressor as a vacuum pump and do not
operate the compressor while the system is under vacuum.
Evacuation of “PR” model systems:
Open both the liquid and suction service valves.
Ensure the solenoid valve is energized and open.
Connect vacuum pump to the liquid and suction service valves.
Evacuate the system to 250 microns and maintain for a minimum of 4 hours.
Perform a vacuum decay test for a minimum of ten minutes to ensure the system
is leak free and dry.
Evacuation of “PC” model systems:
Leave the service valves closed, the condensing unit has been evacuated and is
charged with refrigerant.
Ensure the solenoid valve is energized and open.
Connect vacuum pump to the liquid and suction service valves.
Evacuate the system to 250 microns and maintain for a minimum of 4 hours.
Perform a vacuum decay test for a minimum of ten minutes to ensure the system
is leak free and dry.
Evacuation of “PCL” model systems:
“PCL” systems do not require evacuation; this process has been performed at
the factory.
www.manitowocfsusa.com800-225-9916 12
Refrigerant Charging
CAUTION
Do not charge liquid refrigerant into the suction service valve. Do not overcharge the
system. These conditions can permit liquid refrigerant to enter the compressor and
cause damage to internal components resulting in premature system failure.
The refrigerant charge should be added to the system through the liquid line service
valve. Do not charge liquid refrigerant into the suction service valve! The initial charge
should be determined by weight and sight glass indication. Start the system. If the
condensing temperature is 105° F or greater, charge the system until the sight glass
clears. If the condensing unit temperature is below 105° F, reduce the condenser face
surface area to raise the discharge pressures above 105° F and proceed to charge to a
clear sight glass. Return to a full condenser face area when charging is complete.
Operational Start-Up
The first 2 – 4 hours of operation after initial start-up is a critical time. Do not just start
the system and leave. Pressure values, compressor and evaporator superheat, and
inspecting for excessive vibrations and loose connections are some of checks that must
be performed prior to leaving the system.
Pre-Start Checks:
Verify that all service valves are fully open.
Ensure that all refrigerant and electrical connections are tight.
Verify that the wiring and piping is properly routed and secured.
The compressor mounting bolts are properly adjusted (see compressor mounts
on page 14).
All fan motors and mounting brackets are tight.
The condensing unit base and evaporator coil are properly secured.
www.manitowocfsusa.com800-225-9916 13
Compressor Mounts:
CAUTION
Failure to ensure the compressor mounts are properly tightened can result in fatigue to
the system piping causing leaks and poor system performance.
Compressor
Mounting Foot
Mounting Nut
(Upper)
Mounting
Stud
Rubber
Spacer
Mounting
Spring
Mounting
Base
Locking
Device
Mounting Nut
(Lower)
Properly Adjusted Compressor Mount
Hermetic Compressors – hermetic compressor springs are mounted internally; check
the compressor mounting bolts to ensure the nuts have not become loose during
shipment.
Semi-Hermetic Compressors – most semi-hermetic compressors have external spring
mounts and are factory assembled. The following actions are required once the
condensing unit is installed and before system start-up:
Loosen the upper mounting nuts.
Remove the spring steel clips from the mounting springs.
Retighten the upper mounting nuts until the compressor can float on the springs
approximately 1/16” between the mounting nut and rubber grommet.
www.manitowocfsusa.com800-225-9916 14
Start-Up Procedure:
CAUTION
Do not start the system while in a vacuum. Do not leave the system unattended until
normal operating conditions are achieved.
Operate the system for a minimum of two hours and perform checks of the following:
Check the compressor discharge and suction pressures to ensure they are in the
normal operating range.
Check the liquid line sight glass for proper refrigerant charge.
Monitor the compressor oil level (semi-hermetic compressors), add oil as
necessary to keep the level at ¾ sight glass when idle and ½ sight glass when
running.
Check the voltage and amperage at the compressor terminals. Voltage must be
within +10% or -5% of the rating indicted on the condensing unit name plate. On
three phase compressors, verify there is a balanced load.
Check all fans on the evaporator coil and condensing unit to be sure they are
operational and turning in the correct direction.
Check the piping and electrical connections for vibration. Add supports and
strapping if needed.
Check the crankcase heater operation (if equipped).
Set the defrost control time and verify the defrost initiation settings. See pages
18 - 19 for additional details.
Set temperature control to desired temperature range.
Check the compressor and evaporator superheat (reference pages 16 - 17).
After all system checks have been checked, properly adjusted, and verified, replace all
Schrader caps, service valve caps, electrical box covers, housings, etc. File a copy of
this manual for future reference.
www.manitowocfsusa.com800-225-9916 15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.