Kolpak PR Installation Manual

550001058-6
February 11, 2016
Refrigeration System
Installation & Operation
Manual
2915 Tennessee Avenue North
Parsons, TN 38363
Phone: 800-225-9916
www.manitowocfsusa.com
www.manitowocfsusa.com 800-225-9916 1
Table of Contents
Safety Information .…………………..………………………………………. 3 Receiving Inspection ……………………………………………………. ….. 4 Locating and Mounting Condensing Units ………………………………… 4 - 5 Locating and Mounting Evaporator Coils …………………………………. 6 Wiring …………………………………………………………………………. 7 Piping …………………………………………………………………………. 7 - 10 Leak Test ……………………………………………………………………… 11 Evacuation ……………………………………………………………………. 12 Refrigerant Charging ………………………………………………………… 13 Operational Start-Up ….……………………………………………………… 13 – 15 Compressor Superheat ……………………………………………………… 16 Evaporator Superheat ………………………………………………………. 17 Electric Defrost Timer ……………………………………………………….. 18 Air Defrost Timer …………………………………………………………….. 19 Maintenance ………………………………………………………………….. 20 Troubleshooting Charts ……………………………………………………… 21 – 23 Warranty Information ………………………………………………………… 23 System Start-Up Data Sheet ………………………………………………… 24
Wiring Diagrams………………………………………………………………. 25 46 Condensing Unit 115/1/60………………………...…………………………. 25
Condensing Unit 208-230/1/60…………………...…………………………. 26 Condensing Unit 208-230/3/60……………………………………………… 27 Condensing Unit 460/3/60……………………………………………………. 28 Condensing Unit 208-230/1/60 w/Timer ……...…………………………….. 29 Condensing Unit 208-230/3/60 w/Timer………….……...………………….. 30
Condensing Unit Medium Temp Scroll 208-230/1/60.…………………....... 31
Condensing Unit Medium Temp Scroll 208-230/3/60.…………………....... 32
Condensing Unit Low Temp Scroll 208-230/1/60.………………………….. 33 Refrigeration System Low Temp Scroll 208-230/1/60.…………………….. 34 Condensing Unit Low Temp Scroll 208-230/3/60.………………………….. 35 Refrigeration System Low Temp Scroll 208-230/3/60.…………………….. 36 Air Defrost Evaporator 115/1/60.……………………………………………… 37 Air Defrost Evaporator 115/1/60 w/Timer.…………………………………… 38 Air Defrost with 2 Evaporators 115/1/60……..………………………………. 39 Air Defrost with 2 Evaporators w/Timer 115/1/60…………………………… 40 Air Defrost Evaporator 230V..………………………………………………… 41 Air Defrost Evaporator 230V w/Timer.……………………………………….. 42 Air Defrost with 2 Evaporators 230V……..…………………………………… 43 Air Defrost with 2 Evaporators 230V w/Timer ………………………………. 44 Electric Defrost Evaporator 208-230/1/60.………..…………………………. 45 Electric Defrost with 2 Evaporators 208-230/1/60………..…………………. 46
www.manitowocfsusa.com 800-225-9916 2
General Safety Information
WARNING
Text in a Warning box alerts you to a potential personal injury situation. Read each Warning statement before proceeding and work carefully.
CAUTION
Text in a Caution box alerts you to a situation in which you could damage the refrigeration system. Read each Caution statement before proceeding and work carefully.
Read this manual carefully before beginning the installation and operation of the refrigeration system. Special attention is required to all sections identified with the following warning and caution notices:
Disregarding these special notices may result in personal injury and/or damage to the refrigeration system.
Safety Notices:
Installation and maintenance/servicing are to be performed only by trained and
qualified personnel familiar with commercial refrigeration systems.
Ensure that all field wiring conforms to the equipment requirements and all
applicable local and national codes.
Disconnect all power sources before servicing the refrigeration equipment. Sheet metal and coil surfaces have sharp edges. Use appropriate protective
gloves to prevent injury.
Use appropriate eye protection during installation and servicing.
www.manitowocfsusa.com 800-225-9916 3
Receiving Inspection
WARNING
Do not lift the condensing unit by the refrigerant tubing or components. These features will not support the condensing unit weight. Injury and unit damage may occur!
CAUTION
Do not leave the condensing unit mounted to the wooden skid. This prevents all of the unit supports from contacting the mounting surface. Excessive vibration and premature equipment failure can occur.
Check the shipment carefully and compare to the bill of lading. Account for all items listed and inspect each container for damage. Carefully inspect for any concealed damage. Report any shortages or damages to the carrier, note on the bill of lading, and file a freight claim.
Damaged material cannot be returned to the manufacturer without prior approval. A Return Material Authorization (RMA) must be obtained. Contact a sales representative at 800-826-7036.
Locating and Mounting Condensing Unit
General Guidelines:
Check the selected installation location to ensure that racks, braces, flooring,
foundations, etc. are adequate to support the condensing unit weight.
The installation location is clean, dry, and level. Locate away from corrosive and noise sensitive atmospheres. Use the condensing unit skid and base when moving the unit. Do not remove
unit from skid until the unit is moved to the mounting location.
Mount the condensing unit base to pads or structural rails using properly sized
bolts through the unit base.
www.manitowocfsusa.com 800-225-9916 4
Clearance Requirements:
CAUTION
Failure to observe clearance and air flow requirements will result in poor system performance and premature equipment failure!
BUILDING WALL
(VIEWED FROM ABOVE)
AIR
FLOW
AIR
FLOW
MINIMUM
DISTANCE
24”
INTAKE AIR
MINIMUM DISTANCE 24”
24”
INTAKE AIR
MINIMUM DISTANCE 24”
24”
Locate where there is a sufficient and unrestricted supply of clean ambient air. Locate where this is adequate space for the removal of the heated discharged air
from the condensing unit area.
Do not position multiple units so that discharge air from one unit is blowing into
the condenser inlet air of the other unit.
All sides of the unit should be positioned a minimum distance equal to the total
width of the condensing unit away from any other unit, wall, or obstruction.
Example of Multiple Units with Horizontal Airflow
www.manitowocfsusa.com 800-225-9916 5
Locating and Mounting Evaporator Coil
CAUTION
Failure to observe clearance and air flow requirements will result in poor system performance and premature equipment failure!
Evaporator
Mounting
Bracket
Nylon Bolt
1” O.D. washer
1-5/8” O.D. washer
Nut
1” O.D. washer
Note: Fasteners are
supplied in the
mounting kit.
General Guidelines:
Do not place the evaporator above or close to door openings. This will help
prevent potential icing problems.
Allow a minimum clearance equal to or greater than the coil height on all sides of
the coil for proper air flow and service access.
Use the evaporator coil for a template to locate and drill the mounting holes (1/2”
diameter).
Place a 1” and a 1-5/8” washer on each nylon bolt and insert through the drilled
mounting holes.
Lift the evaporator coil until the nylon bolts extend through the mounting
brackets.
Install washers and secure with nuts. Tighten until the coil is firm against the
ceiling. The evaporator coil must be level.
Additional information is available in the installation manual supplied with the
evaporator.
Evaporator Coil Mounting Diagram
www.manitowocfsusa.com 800-225-9916 6
WARNING
All wiring must comply with local and national codes. Wiring must be performed only by a refrigeration technician or certified electrician. Failure to follow these guidelines may result in injury!
CAUTION
Check all wiring connections, including factory terminals, before operation. Connections can become loose during shipment and installation.
Wiring
All electrical connections and routing must comply with local and national codes. Do not modify the factory installed wiring without written factory approval. The field wiring must enter through the knockouts provided. Refer to the nameplate on the condensing or evaporator coil to determine the proper electrical power supply. Wire type should be of copper conductor only and properly sized to handle the electrical load. The unit and coil must be properly grounded. Condensing unit wiring diagrams are attached inside the electrical box cover. Evaporator coil wiring diagrams are located inside the installation folder. Copies of the wiring diagrams are also available in the back of this manual.
Piping
General Requirements:
All refrigeration piping and components are to be installed in accordance with applicable local and national codes and in conformance with industry refrigeration guidelines to ensure proper operation of the refrigeration system. Only refrigeration grade copper tubing should be used. Long radius elbows should be used. Short radius elbows have points of excessive stress concentration and are subject to breaking at these points, do not use short radius elbows. Suction lines must be insulated with a minimum ¾” thick armaflex to reduce heat pick-up.
www.manitowocfsusa.com 800-225-9916 7
Cleanliness:
CAUTION
The maximum air exposure for dehydrated condensing units is 15 minutes. Systems exposed longer than 15 minutes must have the compressor oil and drier filter replaced. Leaving a system exposed to the atmosphere for more than 15 minutes can result in premature system failure.
CAUTION
The use of saws to cut tubing can contaminate the system with copper chips causing premature system failure.
CAUTION
Dry inert gas must be passed through the system while brazing to prevent scaling and oxidation. Scaling and oxides can clog refrigeration components resulting in system failure.
Condensing units and evaporator coils are cleaned and dehydrated at the factory. The condensing unit must remain closed and pressurized until the piping is complete and final connections are ready to be made.
Do not remove system tubing covers until work is ready to be performed. Ensure that all refrigeration tubing is clean and dry prior to installation. Use only tubing cutters when trimming tubing to the proper length. Do not use saws to cut tubing.
Brazing joints require a dry inert gas, typically nitrogen, be passed through the lines at a low pressure to prevent scaling and oxidation. Use only silver solder brazing alloys. Minimize the amount of flux to prevent internal contamination. Flux only the male portion of the joint. Thoroughly clean fluxed joints after brazing.
Pipe Supports: All tubing should be supported in a least two locations (near the end of each tubing run).
Long runs will require additional support. As a guide, support 3/8” to 7/8” pipe every five feet, 1-1/8” to 1-3/8” every seven feet, and 1-5/8” to 2-1/8” every ten feet. Do not leave a corner unsupported when changing directions. Place supports within 2 feet of each direction change. Piping that is attached to a vibrating object (such as a compressor or compressor base) must be supported in a manner that will not restrict the movement of the vibrating object. Rigid mounting will fatigue the tubing causing refrigerant leaks.
www.manitowocfsusa.com 800-225-9916 8
Oil Traps:
CAUTION
Failure to properly install oil traps can prevent sufficient oil return to the compressor resulting in premature compressor failure.
P-Trap
Pitch drain line
½” per foot
Seal and
Insulate
Typical Drain Installation
To ensure proper oil return to the compressor, a P-type oil trap should be installed at the base of each suction riser of four feet or more. The suction trap must be the same size as the suction line. Additional traps are necessary for long vertical risers. Add a trap for each length of pipe (approximately 20 feet) to insure proper oil return. Suction lines must slope ¼” per 10 feet toward the compressor. Install a suction line trap at the evaporator outlet if the suction line rises to a point higher than the connection on the evaporator.
Drain Lines: Evaporator coil drain lines should be pitched a minimum of ½” per foot to allow proper
drainage and exit the walk-in as quickly as possible. Insulate and seal the drain line where it passes through the wall. Copper drain line is required. If the refrigerated space is 33°F or lower, drain line insulation and heat tape are required. Drain lines must be insulated with minimum ½” thick armaflex. The drain line heat tape must be wrapped around the copper drain line. Do not locate bends, elbows, or drain traps within the refrigerated space. Do not reduce the drain line size. Locate a drain line P­trap outside of the refrigerated space. Any traps exposed to low ambient temperatures should be wrapped with a drain line heater (provide 20 watts of heat per foot of drain line at 0°F, 30 watts per foot at -20°F.
www.manitowocfsusa.com 800-225-9916 9
Pre-Charged lines and Quick Connects:
WARNING
Do not loosen and disconnect the quick connect fittings before reclaiming the refrigerant and depressurizing the system. Disconnecting a pressurized system can result in injury!
CAUTION
Quick connects are for one time use only. Once disconnected, the coupling cannot be re-used. Refrigerant leaks will occur if the couplings are re-used resulting in poor system performance.
Diaphragms
Cutter
Route the suction and liquid line sets between the condensing unit and evaporator coil following the piping guidelines identified in this manual. Remove the dust caps from the quick connect fittings and verify that the o-rings are intact. Wipe the coupling seals and threaded surfaces with a clean cloth to prevent contamination. Lubricate the threads and o-rings with Polyol Ester oil. Thread the coupling halves together by hand to
ensure proper thread mating. Tighten with a wrench until the coupling bodies “bottom”
or until there is definite resistance. Tighten an additional ¼ turn to ensure proper brass­to-brass seating. Once the system is opened and pressurized, check each fitting for refrigerant leaks. If a leak is detected, tighten until the leak stops.
www.manitowocfsusa.com 800-225-9916 10
Leak Testing
CAUTION
If a braze joint is detected leaking, dry inert gas must be passed through the system while repairing the joint to prevent scaling and oxidation. Scaling and oxides can clog refrigeration components resulting in system failure.
CAUTION
Always use the system specified refrigerant when pressuring to perform a leak test.
After all connections are complete the refrigeration system must be tested for leaks. Failure to perform a leak test can result in unsatisfactory system performance, additional servicing and service costs, and possible system failure. Leak test should be performed using an electronic leak detector. All joints and components, both factory and field installed, should be thoroughly inspected for leaks. The system installation must be leak free!
Leak Testing “PR” model systems:
Open both the liquid and suction service valves. Ensure the solenoid valve is energized and open. Add 50 psi refrigerant, then pressurize with dry nitrogen to the low side test
pressure identified on the unit rating label.
Allow thirty minutes for refrigerant to reach all parts of the system. Check all joints and components with an electronic leak detector.
Leak Testing “PC” model systems:
Leave the service valves closed, the condensing unit is charged with refrigerant. Ensure the solenoid valve is energized and open. Add 50 psi refrigerant, then pressurize with dry nitrogen to the low side test
pressure identified on the unit rating label.
Allow thirty minutes for refrigerant to reach all parts of the system. Check all joints and components with an electronic leak detector.
Leak Testing “PCL” model systems:
Open both the liquid and suction service valves. Ensure the solenoid valve is energized and open. Allow thirty minutes for refrigerant to reach all parts of the system. Check all joints and components with an electronic leak detector.
If a leak is detected, relieve the pressure and/or reclaim the refrigerant and repair the leak. If additional brazing is required, pass a dry inert gas (nitrogen) through the system to prevent contamination. Reference page 10 of this manual for leaks located at quick connects couplings. Retest the system as outlined above until no leaks are detected.
www.manitowocfsusa.com 800-225-9916 11
System Evacuation
CAUTION
Do not use the system compressor to evacuate the system. Do not start the compressor while the system is under vacuum. This may damage to the compressor and cause premature system failure.
Evacuation of the refrigeration system is necessary to remove all air and moisture from the system. A reliable rotary vacuum pump with an accurate deep vacuum gauge is recommended. Do not use the system compressor as a vacuum pump and do not operate the compressor while the system is under vacuum.
Evacuation of “PR” model systems:
Open both the liquid and suction service valves. Ensure the solenoid valve is energized and open. Connect vacuum pump to the liquid and suction service valves. Evacuate the system to 250 microns and maintain for a minimum of 4 hours. Perform a vacuum decay test for a minimum of ten minutes to ensure the system
is leak free and dry.
Evacuation of “PC” model systems:
Leave the service valves closed, the condensing unit has been evacuated and is
charged with refrigerant.
Ensure the solenoid valve is energized and open. Connect vacuum pump to the liquid and suction service valves. Evacuate the system to 250 microns and maintain for a minimum of 4 hours. Perform a vacuum decay test for a minimum of ten minutes to ensure the system
is leak free and dry.
Evacuation of “PCL” model systems:
“PCL” systems do not require evacuation; this process has been performed at
the factory.
www.manitowocfsusa.com 800-225-9916 12
Refrigerant Charging
CAUTION
Do not charge liquid refrigerant into the suction service valve. Do not overcharge the system. These conditions can permit liquid refrigerant to enter the compressor and cause damage to internal components resulting in premature system failure.
The refrigerant charge should be added to the system through the liquid line service valve. Do not charge liquid refrigerant into the suction service valve! The initial charge should be determined by weight and sight glass indication. Start the system. If the condensing temperature is 105° F or greater, charge the system until the sight glass clears. If the condensing unit temperature is below 105° F, reduce the condenser face surface area to raise the discharge pressures above 105° F and proceed to charge to a clear sight glass. Return to a full condenser face area when charging is complete.
Operational Start-Up
The first 2 – 4 hours of operation after initial start-up is a critical time. Do not just start the system and leave. Pressure values, compressor and evaporator superheat, and inspecting for excessive vibrations and loose connections are some of checks that must be performed prior to leaving the system.
Pre-Start Checks:
Verify that all service valves are fully open. Ensure that all refrigerant and electrical connections are tight. Verify that the wiring and piping is properly routed and secured. The compressor mounting bolts are properly adjusted (see compressor mounts
on page 14).
All fan motors and mounting brackets are tight. The condensing unit base and evaporator coil are properly secured.
www.manitowocfsusa.com 800-225-9916 13
Compressor Mounts:
CAUTION
Failure to ensure the compressor mounts are properly tightened can result in fatigue to the system piping causing leaks and poor system performance.
Compressor
Mounting Foot
Mounting Nut
(Upper)
Mounting
Stud
Rubber
Spacer
Mounting
Spring
Mounting
Base
Locking
Device
Mounting Nut
(Lower)
Properly Adjusted Compressor Mount
Hermetic Compressors – hermetic compressor springs are mounted internally; check the compressor mounting bolts to ensure the nuts have not become loose during shipment.
Semi-Hermetic Compressors – most semi-hermetic compressors have external spring mounts and are factory assembled. The following actions are required once the condensing unit is installed and before system start-up:
Loosen the upper mounting nuts. Remove the spring steel clips from the mounting springs. Retighten the upper mounting nuts until the compressor can float on the springs
approximately 1/16” between the mounting nut and rubber grommet.
www.manitowocfsusa.com 800-225-9916 14
Start-Up Procedure:
CAUTION
Do not start the system while in a vacuum. Do not leave the system unattended until normal operating conditions are achieved.
Operate the system for a minimum of two hours and perform checks of the following:
Check the compressor discharge and suction pressures to ensure they are in the
normal operating range.
Check the liquid line sight glass for proper refrigerant charge. Monitor the compressor oil level (semi-hermetic compressors), add oil as
necessary to keep the level at ¾ sight glass when idle and ½ sight glass when running.
Check the voltage and amperage at the compressor terminals. Voltage must be
within +10% or -5% of the rating indicted on the condensing unit name plate. On three phase compressors, verify there is a balanced load.
Check all fans on the evaporator coil and condensing unit to be sure they are
operational and turning in the correct direction.
Check the piping and electrical connections for vibration. Add supports and
strapping if needed.
Check the crankcase heater operation (if equipped). Set the defrost control time and verify the defrost initiation settings. See pages
18 - 19 for additional details.
Set temperature control to desired temperature range. Check the compressor and evaporator superheat (reference pages 16 - 17).
After all system checks have been checked, properly adjusted, and verified, replace all Schrader caps, service valve caps, electrical box covers, housings, etc. File a copy of this manual for future reference.
www.manitowocfsusa.com 800-225-9916 15
Loading...
+ 33 hidden pages