M product numbers are for Mexico (i.e. K-12345M)
Los números de productos seguidos de M corresponden a México
(Ej. K-12345M)
Français, page ″Français-1″
Español, página ″Español-1″
1217542-2-B
IMPORTANT INSTRUCTIONS
WARNING: When using electrical products, basic precautions should always be followed,
including the following:
WARNING: Risk of electric shock. Connect only to a circuit protected by a Ground-Fault
Circuit-Interrupter (GFCI)*. Grounding is required. The unit should be installed and grounded by a
qualified service representative.
WARNING: Risk of electric shock. A qualified electrician should route all electrical wiring.
WARNING: Risk of electric shock. Disconnect power before servicing.
WARNING: Unauthorized modification may cause poor performance of the valve. Do not make
modifications to the valve as this could adversely affect the performance of the valve and void the
warranty. Kohler Co. shall not be liable under its warranty or otherwise for personal injury or
damage caused by any such unauthorized modification.
WARNING: Risk of injury or property damage. Please read all instructions thoroughly before
beginning installation.
NOTICE: Follow all plumbing, electrical, and building codes.
NOTICE: Provide generous, unrestricted service access to the valve. Provide access for servicing the
valve and interface. This access must be located immediately next to the valve. Refer to the roughing-in
information.
NOTICE: The valve manufacturer’s minimum flow rate is 1.6 gal/min (6 l/min).
*Outside North America, this device may be known as a Residual Current Device (RCD).
Specifications
Pressures
Maximum Static Pressure125 psi, 862 kPa, 8.6 bar
Supply Pressure Differential*Max 5 psi, 34.5 kPa, 0.34 bar (Equal pressures recommended.)
Minimum Flow Rate1.6 gal/min (Less than 72 psi dynamic pressure.)
Temperatures
Programmable TemperatureMax 120°F (49°C) Min 86°F (30°C) Full cold may also be selected.
Default Temperature at Start-up100°F (38°C)
Minimum Mixed Temperature
Differential from Hot Supply
Temperature Stability at Recommended
Supply Conditions
Ambient TemperatureGreater than 34°F (1°C), Max 104°F (40°C)
Maximum Relative Humidity95% non-condensing
Electrical
Electrical Rating120 V, 15 A, 60 Hz
User Interface Cable Length (supplied)20 ft (6.1 m)
6 l/min (Less than 500 kPa maintaining pressure.)
2.1 gal/min (Greater than 72 psi dynamic pressure.)
8 l/min (Greater than 500 kPa maintaining pressure.)
3.6°F (2°C)
+/- 1.6°F (1°C)
*In commercial applications where there is a large difference in hot and cold supply pressures or frequent
fluctuation in either supply line is anticipated, it is strongly recommended that pressure regulators be
installed.
1217542-2-B2Kohler Co.
Tools and Materials
Plus:
• (2) 1/2" Union Connectors
• Wood and Framing Materials
• PEX Tubing, Copper Tubing, or PVC
• (2) Water Hammer Arrestors (Recommended)
• (2) Supply Shut-Off Valves
Hacksaw or Tube CutterSealant
Tape
SolderPropane
Torch
Kohler Co.31217542-2-B
1-1/2"
(38 mm)
2-11/16"
(68 mm)
12" (305 mm)
15-1/8" (384 mm)
12-1/2"
(318 mm)
9-1/2"
(241 mm)
3-3/8"
(86 mm)
8-1/16" (205 mm)
3/4"
(19 mm)
1-5/16"
(33 mm)
1-3/8"
(35 mm)
2-3/8"
(60 mm)
2-3/8"
(60 mm)
2"
(51 mm)
1-13/16
(46 mm)
1"
(25 mm)
10-5/16" (262 mm)
11-5/8" (295 mm)
13-3/8" (340 mm)
Roughing-In
Before You Begin
NOTICE: Do not install the valve under a whirlpool surround or any location where the temperature may
exceed 104°F (40°C). The valve and its integrated power supply is rated to operate in temperatures up to
104°F (40°C).
NOTICE: Do not apply excessive heat near the valve or apply flux or acids directly onto the valve. This
valve contains plastic and rubber components which will melt if heat is directly applied.
NOTICE: Do not apply petroleum-based lubricants to the valve components. Doing so will damage the
valve components.
NOTICE: Do not use oil-based, non-setting compounds, such as plumbers putty, on the threaded
connections.
NOTICE: Do not remove the check valves from the inlets as this can damage the product.
NOTICE: If the valve will be used for a bath/shower application, the bath fill supply line must be routed
from the #1 outlet port.
Read these instructions and determine the locations of all required components before beginning
installation.
For optimum performance, 1/2″ dedicated water supply lines are recommended.
When possible, install the valve before installing the interface(s).
If possible, flush all piping thoroughly before installing the valve. If the pipes are flushed after the
valve is installed, clean the inlet screens before using the system.
1217542-2-B4Kohler Co.
Before You Begin (cont.)
This valve is not intended for single- or dual-outlet use.
A qualified electrician should install a 120 V GFCI electrical outlet, within the stud framing, in close
proximity to the valve.
If possible, install the electrical outlet prior to installing the valve.
Kohler Co.51217542-2-B
Mounting on a Horizontal SurfaceMounting on a Vertical Surface
Cable
Sockets
Inlets
1. Mounting Configurations
NOTICE: Do not mount the valve with the inlets located at the top. Doing so will damage this product.
Vertical and horizontal mounting options are shown above. Do not mount the valve with the inlets
or cable sockets pointing up.
1217542-2-B6Kohler Co.
Outlet
Power
Cord
Outlets
Interface
NOTE: Only one interface, installed
inside the shower, is required.
Interface
Drip
Loop
Coupler
Drip Loop
20' (6.1 m) Cables
Supply Inlets
2. Plan the Component Locations
NOTICE: If the valve will be used for a bath/shower application, the bath fill supply line must be routed
from the #1 outlet port.
NOTE: Only one interface is required, located inside the showering enclosure. A second interface can be
installed outside the showering enclosure. The interfaces are identical and either can be used for the
primary and secondary connection.
Determine the locations of all required components before beginning installation.
When routing piping, the numbers marked at each valve outlet must correspond to the appropriate
showering component for pre-programmed or custom showering experiences to function properly.
Kohler Co.71217542-2-B
Cross Brace MountBoard Mount
2-3/4"
(70 mm)
Min
Drip Loop
18"
(457 mm) Min
Place the outlet
higher than
the valve.
9-1/2"
(241 mm)
Notch bottom brace.
18"
(457 mm) Min
11-5/8"
(295 mm)
12-1/2"
(318 mm)
3. Prepare the Site
NOTICE: The valve will not fit within a standard stud cavity. A minimum 18″ (457 mm) x 18″ (457 mm)
cavity is required.
NOTE: Horizontal wall installation is shown. The valve can also be wall-mounted vertically or mounted
to a horizontal surface. Refer to the ″Mounting Configurations″ section.
Construct a minimum 18″ (457 mm) wide 2x4 stud cavity.
Install adequate bracing for mounting the valve. Notch the bracing as needed to accommodate the
inlets and outlets.
4. Install the Electrical Outlet
NOTICE: Do not install the valve under a whirlpool surround or any location where the temperature may
exceed 104°F (40°C). The valve and its integrated power supply is rated to operate in temperatures up to
104°F (40°C).
Install a 120 V GFCI electrical outlet within the stud framing, in close proximity to the valve. Locate
the outlet above the valve.
1217542-2-B8Kohler Co.
O-Ring
Screen (Inlets Only)
Inlet/Outlet Tube
Adapter Lock
Solder this connection.
Adapter Nut
1/2" Union
5. Assemble the Adapters and Unions
NOTICE: Do not apply excessive heat near the valve or apply flux or acids directly onto the valve. This
valve contains plastic and rubber components which will melt if heat is directly applied.
Disassemble the adapter. Ensure all rubber and plastic components are removed.
Slide the union nut onto the inlet/outlet tube.
Solder the inlet/outlet tube to the union. Allow to cool completely.
Assemble the union.
Slide the adapter nut onto the inlet/outlet tube.
Assemble the adapter lock onto the inlet/outet tube and slide the assembly into the adapter nut.
Slide the O-ring onto the inlet/outlet tube.
For inlet tubes only: Insert the screen into the end of the inlet tube.
Reinstall the adapter assembly to the valve.
Repeat for all inlet/outlet tubes as required.
Kohler Co.91217542-2-B
Offset Foot
Board Mount
Cross Brace Mount
1/2" Union
Water Hammer Arrestor
Shut-Off Valve
6. Install the Valve
NOTICE: Do not apply excessive heat near the valve or apply flux or acids directly onto the valve. This
valve contains plastic and rubber components which will melt if heat is directly applied.
IMPORTANT! If your water supply has high amounts of particulates, install wye strainers in the supply
lines.
Route 1/2″ dedicated water supply lines. Use unions to install removable pipe segments to the
valve inlets to allow access for periodic cleaning of the inlet screens.
Install shut-off valves and water hammer arrestors in the supply lines prior to the valve.
Hold the valve up to the installation location. Verify fit and mark the hole locations.
Pre-drill the holes.
Secure the valve with the washers and screws. Do not overtighten.
IMPORTANT! Make sure the shower components are connected to the corresponding numbered outlet(s)
on the valve.
Route the piping from the valve outlets to the appropriate shower components.
Connect the hot and cold supply lines to the appropriate valve inlets. Hot is red and marked with
″HOT,″ cold is blue and marked with ″COLD.″
Secure all piping to the framing.
1217542-2-B10Kohler Co.
Slide the split boot onto the
interface cable.
Solid Boot
Split Boot
7. Complete the Installation
If an interface is not available, proceed to the ″Installation Checkout″ section, and ″Test for Leaks without an
Interface.″
NOTICE: Do not plug in the power cord until all interface cables are connected.
NOTE: Make drip loops in all cables and cords.
Route the interface cable(s) in the wall from the valve location to the interface installation
location(s).
If not already installed, install the interface(s) according to the instructions packed with the product.
Attach a split boot to each interface cable.
Connect the interface cable(s) to the valve.
Press the boot over the connection and into the valve socket. If only one interface is installed, insert
a solid boot into the unused socket.
Verify there is power to the 120 V GFCI electrical outlet.
Plug the power cord into the outlet.
Kohler Co.111217542-2-B
8. Installation Checkout
Turn on the water supply to the valve.
Test for Leaks without an Interface
Disconnect the power from the valve.
Connect the jumper to the valve, then reconnect the power.
Wait 10 seconds for the valve to initialize; the outlets will activate.
Check all connections for leaks.
Disconnect the power, then remove the jumper.
Reconnect the power to the valve.
Jumper
Test for Proper Operation (Requires an Installed Interface)
Press the power icon on the user interface. The interface screen should be lit.
If not already completed, refer to the ″Digital Interface Homeowners Guide″ to set up the interface.
NOTE: For more information about using the interface, refer to the ″Digital Interface Homeowners
Guide.″
Use the interface to turn on the water outlets.
Check for leaks and make any adjustments as needed.
Verify that the water flow is sufficient for your showering needs.
Exercise the Valve (Requires an Installed Interface)
NOTE: Valves which have been recently installed, or have not been used for some time should be
exercised before running tests or setting the maximum temperature.
NOTE: The maximum water temperature to the outlets is limited to 120°F (49°C). The valve will
automatically shut down if the temperature exceeds 120°F (49°C).
Verify that the hot and cold water supply lines are connected to appropriate valve inlets.
Using the up and down arrow icons on the user interface, adjust the temperature from cold to hot
and back to cold several times, pausing for 30 seconds at each extreme.
1217542-2-B12Kohler Co.
Check Valve
Boot
Copper Tube
Nut
Seal
Screen
O-Ring
Clean the Inlet Screens
Disconnect the power and turn off the water supply.
Unthread the plastic nuts from the hot and cold inlets.
Remove the copper tubes. The O-ring and screen may be attached to the end of the tube.
If the screen remains in the check valve, use a small bladed screwdriver to gently pull the check
valve from the valve inlet.
Remove the screens from the copper tubes or check valves.
Clean the screens to remove any dirt or debris.
Rinse or replace the check valves and screens.
Reassemble the inlet connections.
Split
Boot
Troubleshooting
WARNING: Risk of electric shock. Disconnect power before servicing.
CAUTION: Risk of personal injury. The valve may contain hot water; be careful when draining
any residual water.
NOTICE: Valve maintenance should be performed by a KOHLER Authorized Service Representative.
NOTE: For service parts information, visit your product page at www.kohler.com.
This troubleshooting guide is for general aid only. For service and installation issues or concerns, call
1-800-4KOHLER.