Kohler 8-10-12RESVL, 8-10-12RESV User Manual

Residential/Commercial Generator Sets
Models:
8/10/12RESV
8/10/12RESVL
Controllers:
RDC2
DC2
TP-6880 10/14a
California Proposition 65
WARNING
Engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
Product Identification Information
Product identification numbers determine service parts. Record the product identificationnumbersin the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits.
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Designation Specification Number Serial Number
Accessory Number Accessory Description
Controller Identification
Record the controller description from the generator set operation manual, spec sheet, or sales invoice.
Controller Description
Engine Identification
Record the product identification information from the engine nameplate.
Manufacturer Model Designation Serial Number
Table of Contents
Safety Precautions and Instructions 5.........................................................
Introduction 9...............................................................................
Service Assistance 11.........................................................................
Section 1 Descriptions and Service Views 13...................................................
1.1 Introduction 13...........................................................
1.2 Engine 13...............................................................
1.3 Generator Set Enclosure 13...............................................
1.4 Alternator 13.............................................................
1.5 Transfer Switch 13........................................................
1.6 Controllers 13............................................................
1.7 OnCue Plus Generator Management System 15..............................
1.8 Accessories 16...........................................................
1.8.1 Carburetor Heater 16.............................................
1.8.2 Programmable Interface Module (PIM) 16...........................
1.8.3 Load Control Module (LCM) 16.....................................
1.8.4 Load Shed Kit 16.................................................
1.9 Service Views 17.........................................................
Section 2 Generator Set Operation 19..........................................................
2.1 Prestart Checklist 19......................................................
2.2 Exercising the Generator Set 21............................................
2.3 Generator Set Operation 21................................................
2.3.1 Local Starting and Stopping 21.....................................
2.3.2 Automatic Starting and Stopping 21.................................
2.3.3 Remote Starting and Stopping 21...................................
2.3.4 Engine Start Crank Cycle 21.......................................
2.3.5 Engine Cooldown 21..............................................
2.3.6 Automatic Operation with Model RXT Transfer Switch 21..............
2.3.7 Automatic Operation with Other Transfer Switches 22.................
2.4 Exercise 22..............................................................
2.4.1 Setting the Exerciser 22...........................................
2.4.2 Unloaded Cycle Exercise with Complete System Diagnostics 22........
2.4.3 Unloaded Full-Speed Exercise 23..................................
2.4.4 Loaded Full-Speed Exercise (with RXT only) 23......................
2.4.5 Power Failure During Exercise Cycle 23.............................
2.5 Faults 24................................................................
2.5.1 Warnings 24.....................................................
2.5.2 Shutdowns 24....................................................
2.5.3 ATS Communication Errors 24.....................................
2.5.4 Resetting the Controller after a Fault Shutdown 24....................
2.6 Generator Enclosure Thermostat 27........................................
Section 3 RDC2 Controller Operation 29.......................................................
3.1 RDC2 Generator Set/ Transfer Switch Controller 29...........................
3.2 Controls and Indicators 29.................................................
3.2.1 Controller Keypad 30.............................................
3.2.2 LED Indicators 30................................................
3.2.3 LCD Display 31
3.3 Controller Power 32.......................................................
3.4 Battery Charging 32......................................................
3.5 Changing Settings 32.....................................................
3.6 Setting the Exerciser 34...................................................
3.6.1 Setting the Exerciser at Controller Power-up 34......................
3.6.2 Changing the Exercise Settings 34..................................
3.7 RDC2 Controller Menus 36................................................
3.8 Main Menu 36............................................................
3.9 Overview Menu 37........................................................
3.10 Engine Metering Menu 37.................................................
3.11 Generator Metering Menu 38...............................................
3.12 Generator Set Information Menu 39.........................................
3.13 Genset Run Time Menu 39................................................
..................................................
TP-6880 10/14 Table of Contents
Table of Contents, continued
3.14 Genset System Menu 40..................................................
3.15 ATS Status Menu 41......................................................
3.16 ATS Configuration Menu 42................................................
3.17 Date and Time Menu 43...................................................
3.18 Networking Information Menus 43..........................................
3.18.1 Networking Status Submenu 44....................................
3.18.2 Networking Configuration Submenu (OnCue Plus Password) 45........
3.18.3 RBUS Information 47.............................................
3.18.4 Remote Devices Submenu 48......................................
3.19 Programmable Interface Module (PIM) Status Menu 49........................
3.20 Load Control Module (LCM) or Load Shed Kit Menus 50.......................
3.21 Event Log 51............................................................
Section 4 DC2 Controller Operation 53.........................................................
4.1 DC2 Generator Set/ Transfer Switch Controller 53............................
4.2 Controls and Indicators 53.................................................
4.2.1 Controller Keypad 54.............................................
4.2.2 LED Indicators 54................................................
4.2.3 LCD Display 55..................................................
4.3 Controller Power 55.......................................................
4.4 Battery Charging 55......................................................
4.5 Exercise 56..............................................................
4.5.1 Exercise Modes 56...............................................
4.5.2 Setting the Exerciser 56...........................................
4.5.3 Exerciser Reset 56...............................................
4.6 Event Log 56............................................................
4.7 Maintenance Timer 57....................................................
4.8 OnCue Plus Password 57.................................................
Section 5 Scheduled Maintenance 59..........................................................
5.1 Scheduled Maintenance 60................................................
5.1.1 Service Schedule 61..............................................
5.2 Lubrication System 62....................................................
5.2.1 Low Oil Pressure Shutdown 62.....................................
5.2.2 Oil Check 62.....................................................
5.2.3 Engine Oil Recommendation 62....................................
5.2.4 Oil Change Procedure 62..........................................
5.2.5 Resetting the Maintenance Timer 64................................
5.3 Spark Plugs 64...........................................................
5.4 Air Cleaner Service 65....................................................
5.4.1 Air Cleaner, 8RESV/RESVL Models 65..............................
5.4.2 Air Cleaner, 10/12RESV/RESVL Models 66..........................
5.5 Cooling System 66.......................................................
5.6 Exhaust System 67.......................................................
5.7 Battery 68...............................................................
5.8 Storage Procedure 69.....................................................
5.8.1 Lubricating System 69............................................
5.8.2 Fuel System 69..................................................
5.8.3 Cylinder Lubrication 69............................................
5.8.4 Exterior Preparation 69............................................
5.8.5 Battery 69
Section 6 Troubleshooting 71.................................................................
6.1 Introduction 71...........................................................
6.2 USB Port 71.............................................................
6.3 Fault Messages 71.......................................................
6.4 Circuit Protection 71......................................................
6.4.1 Controller Internal Circuit Protection 71..............................
6.4.2 Line Circuit Breaker 71............................................
6.4.3 Auxiliary Winding Circuit Breaker 71................................
6.5 Troubleshooting 72.......................................................
Appendix A Abbreviations 73...................................................................
.......................................................
TP-6880 10/14Table of Contents
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury, death,orsubstantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
WARNING
Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks.
Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid
can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death.
Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
TP-6880 10/14 5Safety Precautions and Instructions
Battery gases. Explosion can cause severe injury or death. Battery gases
can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Engine Backfire/Flash Fire
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator
set with the air cleaner removed.
Servicing the fuel system. A flash fire can cause severe injury or death.
Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor.
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.
Carbon monoxide detectors. Carbon monoxide can cause severe nausea, fainting, or death. Install
carbon monoxide detectors on each level of any building adjacent to the generator set. Locate the detectors to adequately warn the building’s occupants of the presence of carbon monoxide. Keep the detectors operational at all times. Periodically test and replace the carbon monoxide detectors according to the manufacturer’s instructions.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
TP-6880 10/146 Safety Precautions and Instructions
Fuel System
Hazardous Noise
WARNING
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly
explosive. Use extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an
explosion. Check the LP vapor gas or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6--8 ounces per square inch (10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
CAUTION
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets
not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
Hazardous Voltage/ Moving Parts
DANGER
Hazardous voltage. Will cause severe injury or death.
This equipment must be installed and serviced by qualified electrical personnel.
WARNING
Hazardous voltage. Can cause severe injury or death.
Moving parts.
Hazardous voltage. Backfeed to the utility system can cause property damage, severe injury, or death.
If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply.
CAUTION
Welding the generator set. Can cause severe electrical equipment damage.
Never weld components of the generator set without first disconnecting the battery, controller wiring harness, and engine electronic control module (ECM).
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Operate the generator set only when all guards and electrical enclosures areinplace.
TP-6880 10/14 7Safety Precautions and Instructions
Welding on the generator set. Can cause severe electrical equipment damage. Before welding on the
generator set perform the following steps: (1) Remove the battery cables, negative (--) lead first. (2) Disconnect all engine electronic control module (ECM) connectors. (3) Disconnect all generator set controller and voltage regulator circuit board connectors. (4) Disconnect the engine battery­charging alternator connections. (5) Attach the weld ground connection close to the weld location.
Hot Parts
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Notice
NOTICE
Canadian installations only.For
standby service connect the output of the generator set to a suitably rated transfer switch in accordance with Canadian Electrical Code, Part 1.
Connecting the battery and the battery charger. Hazardous voltage can cause severe injury or death.
Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies). Have a qualified electrician install the battery(ies).
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install
a transfer switch in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts.
The engine and exhaust system components become extremely hot during operation.
Servicing the engine heater. Hot parts can cause minor personal injury or property damage. Install the
heater before connecting it to power. Operating the heater before installation can cause burns and component damage. Disconnect power to the heater and allow it to cool before servicing the heater or nearby parts.
Heavy Equipment
WARNING
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Do not use lifting eyes. Lift the generator set using lifting bars inserted through the lifting holes on the skid.
TP-6880 10/148 Safety Precautions and Instructions
Introduction
This manual provides operation and maintenance instructions for residential/commercial model 8/10/12RESV and RESVL generator sets equipped with Kohler RDC2 or DC2 generator set/transfer switch controllers. See Figure 1. The RDC2 and DC2 controllers control the generator set and the optional Model RXT transfer switch.
This generator set is approved for use in stationary applications in locations served by a reliable utility power source. Have the generator set installed by an authorized distributor/dealer or service technician. Refer to TP-6879, Installation Manual, for installation instructions.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
The equipment service requirements are very important to safe and efficient operation. Inspect the parts often and perform required service at the prescribed intervals. Obtain service from an authorized service distributor/ dealer to keep equipment in top condition.
List of Related Literature
Figure 2 identifies related literature available for the generator sets covered in this manual. Only trained and qualified personnel should install or service the generator set.
Generator Set Literature Part Number
Installation Manual, Model 8/10/12RESV/RESVL Generator Set
Transfer Switch Literature
Operation/Installation Manual, Model RXT Automatic Transfer Switch
Operation/Installation Manual, Model RDT Automatic Transfer Switch
Installation Manual, Model RSB Automatic Transfer Switch
Operation Manual, Model RSB Automatic Transfer Switch
Accessory Literature
Operation Manual, OnCuer Plus Software
Operation Manual, SiteTecht Software TP-6701
Installation Instructions, Load Control Module (LCM)
Installation Instructions, Programmable Interface Module (PIM)
Instructions, Firmware Update Using USB Utility
Instructions, Load Shed Kit TT-1609
Figure 2 Related Literature
TP-6879
TP-6807
TP-6345
TP-6486
TP-6487
TP-6928
TT-1574
TT-1584
TT-1636
Figure 1 RESV/RESVL Generator Set
TP-6880 10/14 9Introduction
Nameplate
Refer to the certification label for engine displacement.
The following illustration shows a typical generator set nameplate. Copy the model, serial, and specification numbers from the nameplate into the spaces provided in the product information section on the inside front cover of this manual. See the service views in Section 1.9 for the nameplate location.
GM12070
Emission Inform ation
The exhaust emission control system for the SV620 engines (8RESV/RESVL) is EM for U.S. EPA, California, and Europe.
The exhaust emission control system for the KT725 engine (10RESV/RESVL and 12RESV/RESVL) is EM for U.S. EPA, California, and Europe.
Generator Set Application
Kohlerr Power Systems (KPS) ensures that all Kohlerr generator sets are certified to applicable standards for their intended application. It is the owner/operator’s responsibility to operate Kohlerr generator sets exclusively according to the directions provided in the accompanying operation manuals.
Kohlerr generator sets designated as Stationary Standby, Emergency or Emergency Standby may only be operated for emergency power generation and for maintenance/testing. Emergency power generation is limited to power production when electric power from a local utility (or the normal power source, if the facility runs on its own power production) is interrupted.
The Kohlerr Model SV620 engine used on the 8RESV/RESVL generator set is certified to operate using natural gas or propane fuel.
The Kohlerr Model KT725 engine used on the 10RESV/RESVL and 12RESV/RESVL generator set is certified to operate using natural gas or propane fuel.
The Emission Compliance Period referred to on the Emission Control or Air Index label indicates the number of operating hours for which the engine has been shown to meet CARB or EPA emission requirements. Figure 3 provides the engine compliance period (in hours) associated with the category descriptor, which may be found on the certification label.
Emission Compliance Period
EPA
CARB
Category C
250 hours
Moderate 125 hours
Category B
500 hours
Intermediate
250 hours
Category A 1000 hours
Extended 500 hours
Figure 3 Emission Compliance Period
The US Clean Air Act explicitly prohibits using Emergency Standby generators as a primary electric power source regardless of whether a site is connected to the electrical grid. Emergency Standby generators may NOT be used to power sites which are not connected to an electric utility. The U.S. Clean Air Act authorizes owner/operator fines of up to $3,750 per day of operation in violation of the generator set’s certification.
Owners/operators should familiarize themselves with and perform all testing, maintenance, notification, reporting and record keeping as required by the Clean Air Act. In most cases, performance testing is not required if the generator is operated and maintained according to the operation manual. However, owners/operators must retain maintenance records.
TP-6880 10/1410 Introduction
Service Assistance
For professional advice on generator set power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric.
D Visit the Kohler Power Systems website at
KOHLERPower.com.
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
office.
Headquarters Europe, Middle East, Africa (EMEA)
Kohler Power Systems Netherlands B.V. Kristallaan 1 4761 ZC Zevenbergen The Netherlands Phone: (31) 168 331630 Fax: (31) 168 331631
Asia Pacific
Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
China
North China Regional Office, Beijing Phone: (86) 10 6518 7950
(86) 10 6518 7951 (86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America
Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131
TP-6880 10/14 11Service Assistance
Notes
TP-6880 10/1412 Service Assistance
Section 1 Descriptions and Service Views
1.1 Introduction
The generator set specification sheets provide specific generator and engine information. Refer to the spec sheet for data not supplied in this manual. Consult the generator set service manual, engine operation manual, and engine service manual for additional specifications. Obtain copies of the latest spec sheets, manuals, diagrams, and drawings from your local distributor/ dealer.
1.2 Engine
The 8RESV generator set has a four-cycle, single cylinder, air-cooled Kohlerr engine and 10/12RESV generator sets have a four-cycle, twin cylinder, air-cooled Kohlerr engine. The engines operate on clean-burning natural gas or LPG. Engine features include:
D Efficient overhead valve design and full pressure
lubrication for maximum power, torque, and reliability under all operating conditions.
D Dependable, maintenance-free electronic ignition.
D Precision-formulated cast iron construction of parts
subjected to the most wear and tear.
D Field-convertible multi-fuel systems that allow fuel
changeover from natural gas to LPG (and vice- versa) while maintaining EPA emission certification.
1.4 Alternator
The generator uses Kohler’s unique PowerBoostt voltage regulation system, which provides instant response to load changes.
PowerBoostt ensures reliable motor starting and consistent voltage levels. PowerBoostt utilizes a voltage excitation system that employs a winding independent of the main output windings to provide excitation voltage.
1.5 Transfer Switch
The RDC2 and DC2 controllers are designed to interface with and control the Kohler Model RXT Automatic Transfer Switch (ATS). Do not use the Kohler Model RRT transfer switch with the RDC2 or DC2 controller.
If the power system uses a different model transfer switch, the RDC2 and DC2 controllers will not control the transfer switch. An ATS other than the Model RXT must be equipped with a transfer switch controller and engine start contacts that connect to the remote engine start terminals on the generator set.
1.6 Controllers
RESV models are equipped with the RDC2. RESVL models use the DC2. See Figure 1-1.
The controller provides integrated control for the
1.3 Generator Set Enclosure
The generator set is housed in a steel enclosure which is dipped in e-coat for extra corrosion protection and painted with a durable powder coat finish. The enclosure has a hinged, locking roof that allows easy access to the generator set controller when required, but locks securely to prevent unauthorized access.
To open the roof, insert the tool provided with the enclosure and turn counterclockwise 1/4 turn. Then just raise the roof. The roof stays open until you are ready to close it.
Be sure to close and lock the enclosure, and keep the tool in a secure location.
TP-6880 10/14 13Section 1 Descriptions and Service Views
generator set, Kohlerr Model RXT transfer switch, programmable interface module (PIM), and load control module (LCM) or load shed kit.
The controller’s 2-line LCD screen displays status messages and system settings that are clear and easy to read, even in direct sunlight or low light.
RDC2 (RESV) DC2 (RESVL)
Figure 1-1 Controllers
RDC2 Controller Features
D Built-in 2.5 amp battery charger
D Six-button keypad
d OFF, AUTO, and RUN pushbuttons
d Select and arrow buttons for access to system
configuration and adjustment menus
D LED indicators for OFF, AUTO, and RUN modes
D LED indicators for utility power and generator set
source availability and ATS position (Model RXT transfer switch required)
D LCD display
d Two lines x 16 characters per line
d Backlit display with adjustable contrast for
excellent visibility in all lighting conditions
D Scrolling system status display
d Generator set status
d Voltage and frequency
d Engine temperature
d Oil pressure
d Battery voltage
d Engine runtime hours
D Date and time displays
D Smart engine cooldown senses engine temperature
D Digital isochronous governor to maintain
steady-state speed at all loads
D Digital voltage regulation: ±0.5% RMS no-load to
full-load
D Automatic start with programmed cranking cycle
D Remote two-wire start/stop capability for optional
connection of Model RDT or RSB transfer switches
D Diagnostic messages
d Displays diagnostic messages for the engine,
generator, Model RXT transfer switch, programmable interface module (PIM), and load control module (LCM) or load shed kit
d Over 70 diagnostic messages can be displayed
D Maintenance reminders
D System settings
d System voltage, frequency, and phase
d Voltage adjustment
d Measurement system, English or metric
D ATS status (Model RXT ATS required)
d Source availability
d ATS position (normal/utility or
emergency/generator)
d Source voltage and frequency
D ATS control (Model RXT ATS required)
d Source voltage and frequency settings
d Engine start time delay
d Transfer time delays
d Voltage calibration
d Fixed pickup and dropout settings
D Programmable Interface Module (PIM) status
displays
D Programmable exerciser can b e set to start
automatically on any future day and time, and run every week or every two weeks
D Exercise modes
d Unloaded weekly exercise with complete system
diagnostics
d Unloaded full-speed exercise
d Loaded full-speed exercise (Model RXT ATS
required)
D Front-access mini USB connector for SiteTecht
connection or the Kohler USB utility
D Integral Ethernet connector for Kohlerr OnCuer
Plus
d Input status (active/inactive)
d Output status (active/inactive)
D Load control module (LCM) or load shed kit menus
d Load status
d Test function
TP-6880 10/1414 Section 1 Descriptions and Service Views
DC2 Controller Features
D Four-button keypad: OFF, AUTO, RUN, and
EXERCISE pushbuttons
D LED indicators for OFF, AUTO, and RUN modes
D LCD display:
d Two lines x 16 characters per line
d Backlit display with adjustable contrast for
excellent visibility
d Loaded full-speed exercise (Model RXT ATS
required)
D Front-access mini USB connector for SiteTecht
connection or the Kohler USB utility
D Integral Ethernet connector for Kohlerr OnCuer Plus
D Built-in 2.5 amp battery charger
D Remote two-wire start/stop capability for optional
connection of Model RDT or RSB transfer switches
D Scrolling system status display
d Generator set status
d Voltage and frequency
d Engine temperature
d Oil pressure
d Battery voltage
d Engine runtime hours
d Maintenance reminders
d OnCuer Plus status (connected/disconnected)
D Date and time displays
D Smart engine cooldown senses engine temperature
D Digital isochronous governor to maintain
steady-state speed at all loads
D Digital voltage regulation: ±0.5% RMS no-load to
full-load
D Automatic start with programmed cranking cycle
D Exercise modes
d Unloaded weekly exercise with complete system
diagnostics
d Unloaded full-speed exercise
D Diagnostic messages
d Displays diagnostic messages for the engine,
generator set, model RXT transfer switch, and optional programmable interface module (PIM) and load control module (LCM) or load shed kit
d Over 70 diagnostic messages can be displayed
D A laptop computer and Kohlerr SiteTech software
can be used to change system settings
D A laptop computer and Kohlerr SiteTech software or
Kohler USB Utility software can be used to update controller firmware
See the generator set Installation manual for more information.
1.7 OnCue Plus Generator Management System
The OnCuer Plus Generator Management System comes included with your generator and allows monitoring and control of your generator set from a personal computer, smart phone, or tablet. OnCuer Plus can be configured to send email or text message notifications in the event of a generator set fault. See TP-6928, OnCuer Plus Software Operation Manual, for software instructions.
TP-6880 10/14 15Section 1 Descriptions and Service Views
1.8 Accessories
1.8.4 Load Shed Kit
The following optional accessories are offered for the RESV and RESVL generator sets.
1.8.1 Carburetor Heater
An optional carburetor heater is recommended for improved cold starting in locations where the ambient temperature drops below 0_C(32_F). The carburetor heater prevents condensation and carburetor icing. The heater requires a continuous source of 120 VAC power.
1.8.2 Programmable Interface Module (PIM)
The optional Programmable Interface Module (PIM) provides two programmable inputs and six programmable dry contact outputs for connection to customer-supplied equipment. The outputs are controlled by the RDC2 controller, and can also be controlled remotely using the OnCuer Plus program.
The PIM is mounted in a NEMA 3R a luminum enclosure, which can be mounted indoors or outdoors. See the installation instructions provided with the PIM.
The optional Load Shed Kit functions in a similar fashion as the Load Control Module (LCM) and provides an automatic load management system to comply with Section 702.5 of NEC 2008. The installer is r esponsible for ensuring that the power system installation complies with all applicable state and local codes.
The Load Shed Kit automatically manages up to six residential loads, four customer-supplied power relays and two relays to control two independent air conditioner loads.
The Load Shed Kit is controlled by the RDC2/DC2 controller. The load on the generator set is monitored, and loads are added or shed in the order of their priority. See specification sheet G11-124 and installation instructions TT-1609 for more information.
Either a Model RDT or Model RXT transfer switch is required for the load shed kit installation. The load shed kit mounts inside the Model RDT or Model RXT transfer switch enclosure and is available for single-phase generators sets only.
Note: Do not install both a load shed kit and a load
control module (LCM) on the same system.
1.8.3 Load Control Module (LCM)
The optional Load Control Module (LCM) provides an automatic load management system to comply with Section 702.5 of NEC 2008. The installer is r esponsible for ensuring that the power system installation complies with all applicable state and local codes.
The LCM automatically manages up to six residential loads. Four power relays are provided for management of non-essential secondary loads, and two relays are available to control two independent air conditioner loads.
The LCM is controlled by the RDC2/DC2 controller. The load on the generator set is monitored, and loads are added or shed in the order of their priority. See specification sheet G6-120 and the LCM installation instructions for more information.
TP-6880 10/1416 Section 1 Descriptions and Service Views
1.9 Service Views
11
10
1
13
15
12
14
2
16
9
8
7 6
4
5
1. Hinged roof
2. Air cleaner
3. Nameplate location
4. Thermostat
5. Engine starting battery location (battery purchased separately)
6. Gas regulator assembly and fuel selector valve
7. Fuel solenoid valve
8. Fuel inlet
9. Field-connection terminal block and 20 amp resettable circuit breaker (behind panel)
17
18
19
3
ADV-8539
10. Line circuit breaker
11. 120 VAC receptacles for optional carburetor heater (not shown)
12. Lock
13. Locking tool, provided with generator set
14. USB port
15. RDC2 or DC2 controller
16. Oil check (dipstick) and oil fill
17. Oil drain valve
18. Oil filter
19. Muffler
Figure 1-2 Service View
TP-6880 10/14 17Section 1 Descriptions and Service Views
21
20
22
20. Lifting holes
21. Air intake
Figure 1-3 Service View
22. Exhaust outlet
TP-6880 10/1418 Section 1 Descriptions and Service Views
Section 2 Generator Set Operation
2.1 Prestart Checklist
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
WARNING
Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks.
Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes.
Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke
or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause
blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
TP-6880 10/14 19Section 2 Generator Set Operation
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.
Carbon monoxide detectors. Carbon monoxide can cause severe nausea, fainting, or death. Install carbon
monoxide detectors on each level of any building adjacent to the generator set. Locate the detectors to adequately warn the building’s occupants of the presence of carbon monoxide. Keep the detectors operational at all times. Periodically test and replace the carbon monoxide detectors according to the manufacturer’s instructions.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Connecting the battery and the battery charger. Hazardous voltage can cause severe injury o r death.
Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies). Have a qualified electrician install the battery(ies).
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
To ensure continued satisfactory operation, perform the following checks or inspections before or at each startup, as designated, and at the intervals specified in the service schedule. In addition, some checks require verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner element to prevent unfiltered air from entering the engine.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer’s instructions regarding battery care and maintenance.
Exhaust System. Check for exhaust leaks and blockages. Check the muffler condition.
D Inspect the exhaust system components for cracks,
leaks, and corrosion. Check for tight exhaust system connections.
D Check for corroded or broken metal parts and replace
them as needed.
D Check that the exhaust outlet is unobstructed.
DANGER
Hazardous voltage. Will cause severe injury or death.
This equipment must be installed and serviced by qualified electrical personnel.
Oil Level. Check the oil level before starting the generator set and at the intervals given in Section 5, Scheduled Maintenance. Maintain the oil level at or near, not over, the full mark on the dipstick.
Operating Area. Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave rags, tools, or debris on or near the generator set.
TP-6880 10/1420 Section 2 Generator Set O peration
2.2 Exercising the Generator Set
2.3.5 Engine Cooldown
Operate the generator set without load once each week for 20 minutes. See Section 2.4 for information about loaded and unloaded exercise modes. For instructions to set the exerciser, see:
D Section 3.6 for the RDC2 controller
D Section 4.5 for the DC2 controller
2.3 Generator Set Operation
2.3.1 Local Starting and Stopping
Start: Press the RUN button to immediately start the
generator set.
Stop: Press the OFF button. The engine stops.
Run the generator set with no load for at least 2 minutes to ensure adequate engine cooldown.
2.3.2 Automatic Starting and Stopping
An automatic transfer switch monitors the utility power and signals the generator set to start when utility power is lost. The ATS then transfers the load to the generator set.
When utility power is restored, the transfer switch transfers the load back to utility, runs the generator set with no load to cool down the engine, and then stops the generator set.
2.3.3 Remote Starting and Stopping
A remote switch connected to terminals 3 and 4 can be used to start and stop the generator set. Close the switch to start and run the generator set. Open the switch to stop the generator set.
Run the generator set with no load for at least 2 minutes to ensure adequate engine cooldown.
2.3.4 Engine Start Crank Cycle
The controller attempts to start the generator set three times (three crank cycles, 15 seconds crank and 15 seconds off). If the generator set does not start in three attempts, the system shuts down on an overcrank fault. See Section 2.5.
Cranking 1, 2, and 3 are displayed during the crank cycle. Pressing the OFF button during the crank cycle stops the cranking. No other buttons are acknowledged during the crank cycle.
The engine cooldown time delay allows the engine to run after the loads have been removed.
The engine cooldown time delay is set to 5 minutes. The engine stops before the cooldown time delay expires if the temperature drops below the cooled-down temperature level, or if the temperature rises above the high limit during the cooldown cycle.
If a transfer switch other than the Model RXT is used, an additional engine cooldown time delay may be programmed on the transfer switch. To allow the smart engine cooldown on the RDC2/DC2 controller to operate most efficiently, set the cooldown time on the transfer switch controller to zero or the minimum time allowed. Refer to the instructions provided with the transfer switch for more information.
2.3.6 Automatic Operation with Model RXT Transfer Switch
The Model RXT transfer switch connects to the RDC2/DC2 controller through the ATS interface board on the transfer switch. Also see the Model RXT Transfer Switch Operation/Installation Manual for more information about transfer switch operation.
The controller must be in AUTO mode for automatic transfer switch operation.
Automatic Start
The RDC2/DC2 controller receives utility source voltage sensing data from the Model RXT transfer switch.
1. If the utility source voltage falls below an acceptable level, the controller starts the engine start time delay.
2. If the utility source is not restored before the time delay expires, the generator set starts.
3. After the Normal-to-Emergency time delay, the ATS is signaled to transfer the load to the emergency source.
Automatic Stop with Engine Cooldown
1. When the utility source is restored, the Emergency-to-Normal time delay starts.
2. When the Emergency-to-Normal time delay expires, the load is transferred to the utility.
3. The generator set runs through the engine cooldown cycle and then stops.
TP-6880 10/14 21Section 2 Generator Set Operation
2.3.7 Automatic Operation with Other Transfer Switches
If a transfer switch other than the Model RXT (such as a Kohler Model RDT or RSB) is used, the engine start contacts from the ATS must be connected to engine start leads 3 and 4 on the generator set.
more detailed instructions to change settings on the RDC2. See Section 3.6 for more detailed instructions to set the exerciser or change the exercise settings.
The DC2 controller does not prompt you to set the exerciser. See Section 4.5 for instructions to set the exerciser on the DC2.
The controller must be in AUTO mode to respond to remote start/stop signals from an ATS or remote switch. Press the AUTO button to put the controller into automatic mode.
Automatic Start
The engine start contacts on the ATS close to signal the generator set to start, and remain closed while the generator set is running.
Automatic Stop
The engine start contacts on the ATS open to signal the generator set to stop.
2.4 Exercise
The RDC2 and DC2 controllers can be set to automatically run the generator set at the same time and day each week. Exercising the generator set weekly or every two weeks is required to keep the engine and alternator in good operating condition.
Three exercise modes are available: unloaded cycle, unloaded full speed, and loaded full speed. See Sections 2.4.2 through 2.4.4 for information about the exercise modes. A loaded exercise can be set at the RDC2 controller only if a Model RXT transfer switch is connected.
Note: With transfer switches other than the Model RXT,
it is possible to have two exercise settings (one unloaded exercise set at the generator set controller, and another exercise set at the ATS controller). If the e xercise times overlap, the ATS exercise setting takes priority.
If a transfer switch other than the Model RXT is used, refer to the instructions provided with the transfer switch to set a loaded exercise at the ATS, if desired.
2.4.2 Unload ed Cycle Exercise with Complete System Diagnostics
An unloaded exercise runs the generator set without signalling the transfer switch to transfer the electrical load from the utility source to the generator set. The Unloaded Cycle exercise with diagnostics is the recommended exercise mode and is the default exercise setting.
The Unloaded Cycle exercise runs the engine for 20 minutes in the cycle shown in Figure 2-1 and described below.
D Runs at reduced speed for 10 minutes to warm up
and exercise the engine.
D Ramps up and runs at full speed for 3 minutes.
Engine diagnostics are performed during this full-speed portion of the cycle, which provides the best test of engine and alternator power backup capability. Diagnostic tests at full speed can identify potential problems with the power output and alert the operator before an emergency event.
D Ramps down and runs at reduced speed for 5
minutes to cool down the engine before shutting down automatically.
3min.
1min.
Engine Speed, RPM
10 min. 5 min.
Engine
Exercise
Full-Speed
Diagnostics
1min.
Cooldown
2.4.1 Setting the Exerciser
When power is applied to the RDC2 controller (that is, when the battery is connected), you will be prompted to set the date and time, and then to set the exerciser.
The first setting will flash. Press the Up and Down arrow buttons to change the setting. Press Select to save the setting and move on to the next. See Section 3.5 for
Figure 2-1 Unloaded Exercise Cycle
TP-6880 10/1422 Section 2 Generator Set O peration
System Diagnostics
2.4.3 Unloaded Full-Speed Exercise
During the unloaded exercise, the controller monitors the following data. The controller display indicates that the generator set is running, unless a fault is detected as described below.
D ATS connection. The controller verifies that the
Model RXT ATS interface board is connected.
D Battery voltage. Battery voltage is checked before
exercise to verify engine starting capability. Battery voltage provides a measurement of battery health. If the controller detects low battery voltage, the condition is indicated on the display.
D Communication integrity tests. J1939, RBUS,
Ethernet, and USB are monitored for messages indicating that the controller and wiring are reliable.
D Engine speed. Engine speed is measured at
reduced speed and full speed. An overspeed or underspeed condition will result in a fault condition and shutdown.
D Generator output frequency and voltage.
Operating the generator at full speed allows the RDC2/DC2 controller to check the output power for correct voltage, frequency, and stability. When the engine is running at full speed, the controller verifies that the voltage and frequency are within acceptable limits. A fault message is displayed if the voltage or frequency is out of range.
The unloaded full-speed exercise runs the generator set at full speed for 20 minutes without transferring the load.
To set an unloaded full-speed exercise, follow the procedure in Figure 3-8 and select Exercise Mode: Unloaded Full.
2.4.4 Loaded Full-Speed Exercise (with RXT only)
A loaded exercise starts the generator set, ramps up to full speed, and then transfers the electrical load from the utility source to the generator set. After 20 minutes, the load is transferred back to the utility source. The engine runs without load for 5 minutes or until cool, and then shuts down automatically.
Note: With a loaded exercise, power to the building is
lost for up to 10 seconds during load transfer.
For a loaded exercise controlled by the RDC2 or DC2 controller, a Model RXT transfer switch must be connected to the generator set. To set a loaded exercise, follow the procedure in Figure 3-8 and select Exercise Type: Loaded.
For a loaded exercise with a transfer switch other than a Kohlerr Model RXT, program the exercise at the transfer switch controller. Refer to the transfer switch operation manual for instructions.
D Oil pressure. Oil pressure is verified to ensure
proper lubrication of critical engine components. Pressure is monitored at both reduced and full speeds. If the oil pressure is low,the Low Oil Pressure message is displayed and the generator set shuts down.
2.4.5 Power Failure During Exercise Cycle
If the utility power is lost during an unloaded exercise, the ATStransfers to the emergency source, the exercise is ended and the control remains in the AUTO mode.
If the utility power is lost during a loaded exercise, the exercise is ended. The ATS remains in the emergency position and the control goes into the AUTO mode.
The generator set continues to run and supply power to the load for the duration of the utility power outage. When Utility power is restored, the ATS will re-transfer to the utility source through normal timing sequences.
TP-6880 10/14 23Section 2 Generator Set Operation
2.5 Faults
The RDC2/DC2 controller displays fault messages for generator set warnings and shutdowns. Selected fault messages are shown in Figure 2-3.
2.5.1 Warnings
The controller displays a fault message but the generator set does not shut down on a warning. The controller resets automatically after a warning condition is corrected.
2.5.2 Shutdowns
Under a fault shutdown condition, the generator set shuts down automatically and the controller displays a fault message. The OFF LED flashes. In some cases, the engine cooldown cycle runs before the engine shuts down. See Figure 2-3.
Shutdown switches (such as the low oil pressure switch or high engine temperature switch) on the generator set will automatically reset when the problem is corrected. However, the fault condition at the controller does not clear until the controller is reset.
The generator set cannot be restarted until the fault condition is corrected and the controller is reset. See Section 2.5.4 for instructions to reset the controller after a fault shutdown.
2.5.3 ATS Communication Errors
When a Model RXT transfer switch is used, an ATS fault indicates that the connection to the interface board on the transfer switch has been lost. Check the connection to the ATS interface board.
2.5.4 Resetting the Controller after a Fault Shutdown
Always identify and correct the cause of a fault shutdown before resetting the controller.Check the fault message displayed on the controller and refer to Figure 2-3 to identify and correct the fault condition before proceeding. Contact an authorized distributor/dealer for service, if necessary.
RDC2 Controller
Press the OFF button to reset the controller, or follow the procedure below. See Figure 2-2.
1. While the fault message is displayed, press the Select button to go to the Overview menu.
2. Press Select again. The active fault message is displayed.
3. Press Select. Confirm Clear Fault: NO is displayed.
4. Press the Down arrow button. Confirm Clear Fault: YES is displayed.
5. Press the Select button to enter YES and clear the fault.
6. Press the Select button to return to the overview menu. The controller changes to OFF mode.
7. Press AUTO to put the generator set into automatic mode.
DC2 Controller
Press the OFF button to clear the fault message on the controller.
Fault Message
Overview -- -->
1.2 h
Figure 2-2 Clearing a Fault on the RDC2 Controller
Fault Message
Press Up arrow button.
Confirm Clear Fault: NO
Confirm Clear Fault: YES
tp6809
TP-6880 10/1424 Section 2 Generator Set O peration
Warning (W) or
Fault Message
AC Sens Loss W(1sec.)
Shutdown (SD)
SD (3 sec.) *
Condition Check
AC sensing lost. In Auto mode, generator output AC sensing is lost. Detection begins 10 seconds after crank disconnect.
Warning: after 1 second if no output detected after crank disconnect.
Shutdown: after 3 seconds if voltage was present and then lost.
Accy PwrOver Warning
W Accessory Power Overload. An over current fault
(short circuit) on the accessory controller power output.
Alt Protect SD High generator current has been detected. The
generator set shuts down to protect the alternator from damage caused by overheating the windings (10RESV and 12RESV only).
ATS ComError W ATS communication error. Warning is displayed
if ATS interface connection is lost. See Section 2.5.3.
ATS PhaseRot W ATS phase rotation mismatch. Transfer switch
phase rotation does not match, ATS will not transfer.
Aux Input SD * Auxiliary input. An optional customer-connected
input is closed. (Digital input from optional PIM.)
Batt Chg Flt W Battery charger fault. Input to PIM from an
external battery charger (not the built-in battery charger).
Battery High W Engine starting battery voltage rises above 16
VDC for more than 10 seconds. Inhibited during the engine crank cycle.
Clears when the battery voltage returns to an acceptable level.
Battery Low W Engine starting battery voltage falls below 12.5
VDC for more than 90 seconds when the engine is not running. Not operative during the engine crank cycle.
Clears when the battery voltage returns to an acceptable level.
Battery CrLo Warning
W Engine starting battery voltage falls below 11
Volts for more than 10 seconds. Inhibited during the engine crank cycle.
Clears when the battery voltage returns to an acceptable level.
Eng Speed High
SD * Engine speed exceeds 115% of the normal
running speed for more than 0.3 seconds.
Eng Speed Low SD * Engine speed drops below 85% of the normal
running speed for more than 3 seconds.
Exer Not Sch W Exercise not scheduled. No exercise is
scheduled on the controller.
Contact an authorized distributor/dealer for service.
Contact an authorized distributor/dealer for service.
Reduce the load.
Check communication wiring between transfer switch interface board and generator set.
Correct the ATS connection. Refer to the ATS Installation manual, wiring diagrams, and labels on the transfer switch.
Check customer-supplied equipment.
Check external battery charger.
Check the battery rating and condition.
Check the battery charger operation.
Check the battery rating and condition.
Check the battery charger operation.
Charge or replace the battery.
Check the battery rating and condition.
Check the battery charger operation.
Charge or replace the battery.
Contact an authorized distributor/dealer for service.
Reduce the load.
Contact an authorized distributor/dealer for service.
See Section 3.6 or 4.5 for instructions to set the exerciser.
* Engine cooldown runs before shutting down.
TP-6880 10/14 25Section 2 Generator Set Operation
Warning (W) or
Fault
Shutdown (SD)
Condition Check
Frequency High SD * Governed frequency exceeds 110% of the
system’s frequency setpoint for more than 10 seconds. Function becomes active 10 seconds after engine start (10 second inhibit).
Frequency Low SD * Governed frequency falls below 90% of the
system frequency setting for more than 10 seconds, or 1 Hz below the system frequency setting for more than 60 seconds.
Function becomes active 10 seconds after engine start (10 second inhibit).
Lo Crank Vlt W Low cranking voltage. Battery voltage falls below
8 VDC for more than 6 seconds while the starter is engaged.
MainPwrOverL SD Main power overload. An over current fault on
the 70 controller power output (short circuit).
Not in Auto W The generator set is not in Automatic (standby)
mode. Remote start and stop commands from a transfer switch or remote switch will be ignored.
Contact an authorized distributor/dealer for service.
Reduce the load and restart the generator set.
Contact an authorized distributor/dealer for service.
Charge or replace the battery.
Contact an authorized distributor/dealer for service.
Check for shorted run relay.
Check wiring for short circuits.
Press AUTO to place the generator set in Automatic mode, when appropriate.
Oil Pres Low SD * The LOP switch indicates low oil pressure for
more than 5 seconds. Function becomes active 30 seconds after crank disconnect (30 second inhibit).
Note: The low oil pressure shutdown does not protect against low oil level. Check the engine oil level regularly as recommended in Section 5.
Check for leaks in the lubrication system.
Check the oil level and add oil if the level is low.
Check the oil pressure switch and wiring
Over Crank SD Three unsuccessful starting attempts. Check the fuel supply, spark plug,
and battery.
Reset the thermostat.
Check for loose connections.
Contact an authorized distributor/dealer for service.
Spd Sens Flt SD Engine speed sensor has failed or engine
stalled.
Total Power High
SD Measured load is greater than 102% of the
generator set power rating for more than 1
Contact an authorized distributor/dealer for service.
Reduce the load.
minute (10RESV and 12RESV only).
Volts L1-L2 High
SD * Generator voltage high. Output voltage exceeds
120% of the system nominal voltage for more
Contact an authorized distributor/dealer for service.
than 2 seconds.
Volts L1-L2 Low SD * Generator voltage low. Output voltage falls
below 80% of the nominal system voltage for more than 10 seconds.
Reduce the load and restart the generator set.
Contact an authorized distributor/dealer for service.
* Engine cooldown runs before shutting down.
Figure 2-3 Controller Fault Messages
TP-6880 10/1426 Section 2 Generator Set O peration
2.6 Generator Enclosure Thermostat
8RESV(L), 10RESV(L), and 12RESV(L) generators include a resettable thermostat in the air intake compartment. The thermostat detects excess heat inside the enclosure. If the thermostat trips, the generator will shut down and the controller will display a fault (underspeed, underfrequency, or undervoltage). If the thermostat trips for some reason other than high temperature (i.e. a nuisance trip), follow these steps to reset the thermostat.
1. Disconnect the utility power to the generator by opening (turning OFF) the corresponding circuit breaker at the building’s distribution panel.
2. Open the enclosure roof.
1
3. Press the button on the thermostat to reset it. See Figure 2-4 for the thermostat location.
4. Reconnect utility power to the generator set by closing the circuit breaker in the distribution panel.
5. Reset the fault on the RDC2/DC2 controller. See Section 2.5.4.
1. Thermostat
Figure 2-4 Thermostat Location
TP-6880 10/14 27Section 2 Generator Set Operation
Notes
TP-6880 10/1428 Section 2 Generator Set O peration
Section 3 RDC2 Controller Operation
3.1 RDC2 Generator Set/ Transfer Switch Controller
Model RESV generator sets are equipped with the RDC2 generator set/transfer switch controller.
Model RESVL generator sets are equipped with the DC2 controller. See Section 4 for DC2 controller operation information.
The RDC2 controls the following power system components:
D Model 8RESV, 10RESV, or 12RESV generator set
D Model RXT Automatic Transfer Switch (ATS)
D Load Control Module (LCM) or load shed kit
D Programmable Interface Module (PIM)
The RDC2 controller features include:
1
2
GM77569
1. User Interface; see Figure 3-2
2. USB port (mini-B); see Section 6.2.
D Two-line x 16 character backlit digital display with
adjustable contrast
D OFF, AUTO, and RUN generator set master control
buttons
D Generator set status indicating LEDs (OFF, AUTO,
RUN)
D Up, Down, and Select buttons for navigation through
menus and adjustments
D Power system indicator LEDs to show utility and
generator source status, and to show which source (utility or generator) is supplying power to the load
3.2 Controls and Indicators
Figure 3-1 illustrates the RDC2 controller. See Figure 3-2 for details of the controller’s user interface.
Figure 3-1 RDC2 Controls and Indicators
1
11
10
6789
GM77569
1. 2-line LCD display
2. Up button
3. Select button
4. Down button
5. RUN button and LED
6. Generator power available LED*
7. Building on generator power LED*
8. Building on utility power LED*
9. Utility power available LED*
10. OFF button and LED
11. AUTO button and LED
* These LEDs operate only if a Model RXT transfer switch is
connected.
2
3
4
5
Figure 3-2 RDC2 User Interface
TP-6880 10/14 29Section 3 RDC2 Controller Operation
3.2.1 Controller Keypad
3.2.2 LED Indicators
The RUN, OFF, and AUTO buttons control the generator set as described in Figure 3-3.
Use the Select, Up arrow, and Down arrow buttons to navigate through the menus and change settings, if necessary. See Section 2.3 for operation instructions.
LEDs above the RUN, OFF, and AUTO buttons indicate the mode of operation as shown in Figure 3-4.
Power System LEDs indicate the status of the utility power and the generator set, and indicate which source is supplying power to the building (based on the position of the RXT transfer switch). See Figure 3-2 and Figure 3-4.
Note: The power system LEDs operate only if a Model
RXT transfer switch is connected. They will not operate if a different transfer switch is used.
Button Button Function
RUN Starts the generator set. The engine start time delay is ignored.
OFF Stops the generator set. The cooldown time delay is ignored.
During the engine crank cycle, pressing OFF will stop the crank cycle.
Press OFF to clear faults and reset the controller.
AUTO Places the generator set in Automatic (standby) mode.
Down arrow
Select
Up arrow
Use to navigate through menus and change settings. This manual contains instructions to navigate the controller menus and adjust settings on the RDC2 controller.
Figure 3-3 RDC2 Controller Pushbutton Operation
LED LED Operation
RUN Lights when the generator set has been started locally by pressing the RUN button.
OFF
AUTO Lights when the generator is in automatic (standby) mode. Generator set will respond to
Utility Power Available * Lights when utility power is available.
Building on Utility Power * Lights when the building load is connected to utility power through the RXT transfer
Generator Power Available * Lights when generator power is available.
Building on Generator Power * Lights when the building load is connected to generator power through the RXT transfer
* These LEDs operate only if a Model RXT transfer switch is connected.
Remote start and stop commands are ignored.
Lights for 2 seconds, then flashes every 2 seconds when the generator set and controller are off. Remote start/stop commands have no effect. The exercise cycle will not run.
In Auto mode, OFF LED flashes quickly to indicate a fault shutdown. Attention required. Identify and correct the fault condition before resetting the controller.
engine start and stop commands from the controller (for example, exercise start and stop commands) or an ATS. Time delays operate as described in Section 2.3.
switch.
switch.
Figure 3-4 RDC2 Controller LED Operation
TP-6880 10/1430 Section 3 RDC2 Controller Operation
3.2.3 LCD Display
The controller is equipped with a two-line x 16 character backlit digital display with adjustable contrast. When the generator is running, the controller automatically scrolls through the displays shown in Figure 3-5. When the system is in AUTO, the screens shown in Figure 3-6 are displayed.
When a fault or warning condition exists, the controller will show the corresponding message. See Section 2.5 for more information about faults.
The display contrast is adjustable. Navigate to the Genset System menu and step down to the Contrast screen. Press the Select button, and then use the up and down arrow buttons to adjust the contrast. See Section
3.5, Changing Settings, and Section 3.14, Genset System Menu.
The display backlight turns off after about a minute of no activity. The backlight turns on when a button is pressed or when the generator set starts.
Controller menus display power system information, including status information for the engine, generator, and optional RBUS accessories, exercise settings, and event history. Some menus allow changes to the controller settings. See Sections 3.7 through 3.21 for menu diagrams.
Active Alert
Genset Status Running
Voltage: 240V Freq: 60.0Hz
Engine: 123F Oil Pressure: OK
Active Alert
Genset Status Standby
Battery
12.3V
Engine Runtime:
12345.6 h
Date: 02DEC2011 Time: HR:MNpm
Next Exercise: 09:00p 09Dec2011
Battery
12.3V
Engine Runtime:
12345.6 h
Date: 02DEC2011 Time: HR:MNpm
Figure 3-6 Autopaging Displays, Automatic Mode
Sample data shown.
tp6804
Next Maintenance: 150 h or Mar2012
Sample data shown.
Figure 3-5 Autopaging Displays, Generator Running
TP-6880 10/14 31Section 3 RDC2 Controller Operation
tp6804
3.3 Controller Power
The RDC2 controller is powered by the generator set engine starting battery and the built-in battery charger.
Note: To disconnect controller power, disconnect the
utility power to the generator set and disconnect the battery .
If controller power is disconnected and reconnected, you will be prompted to set the time, date, and exerciser. The first setting will flash. Press the Up and Down arrow buttons to change the setting. Press Select to save the setting and move on to the next. Repeat until all settings are saved and the controller returns to the main menu. See Section 3.5 for more detailed instructions to change settings on the RDC2. See Section 3.6 for more detailed instructions to set the exerciser or change the exercise settings.
3.4 Battery Charging
The controller includes a built-in battery charger to maintain the engine starting battery. The RDC2 controller monitors the battery voltage and provides a constant 14.0 ±2% VDC voltage and maximum 2.5 amps to charge the battery.
The installer must connect 120 VAC/60Hz utility power provided from the building on a breaker-protected circuit for the built-in battery charger.
3.5 Changing Settings
Some settings can be changed from the controller keypad. The controller settings and generator set output are factory-set and should not require field adjustment under normal circumstances. Check and adjust the settings and/or output when:
The following procedure explains how to change settings. See Figure 3-7 for an example using the Date and Time settings.
Note: Use caution when navigating the controller
menus. In some menus, pressing the Select button can enable editing of the controller settings. Changing the settings to incorrect values can adversely affect generator set operation or render the unit inoperable.
Procedure to Change Settings
1. Press the Select button to enter the main menu.
2. Press the down arrow button until the desired menu is displayed. The Genset System menu is used for this example. See Figure 3-9.
3. Press the Select button to enter the genset system displays. See Figure 3-7.
4. Press the down arrow button to step through the generator set system settings.
5. To change any of the genset system settings, press the Select button. The selected setting flashes.
6. Press the up or down arrow buttons to increase or decrease the setting.
7. When the desired setting is shown, press Select. The value stops flashing. If there are additional adjustable settings on the screen, the next setting flashes. For example, in the date menu, the day, month, and year can be adjusted.
8. Repeat steps 6 and 7 for each setting on the screen.
9. Press the down arrow to step to the next screen.
D The controller has been replaced.
D The voltage requires adjustment for a particular
application.
D Troubleshooting generator set problems.
Have controller setup and adjustment performed only by an authorized Kohler distributor/dealer or authorized representative.
10. To exit, press the down arrow button until Return is displayed. Press the Select button to exit the menu.
11. Press the AUTO or OFF button to exit the main menu.
Note: If no buttons are pushed, the controller exits the
menus and returns to the generator set status display after 5 minutes.
TP-6880 10/1432 Section 3 RDC2 Controller Operation
Changing Settings on the RDC2 Controller
1. Press the Select button to enter the main menu.
Press: Display:
Overview -- -->
1.2 h
2. Press the down arrow button until the desired menu is displayed. See Figure 3-9. Date and Time are used for this example.
Press:
Display:
D a t e -- -- >
and Time
3. Press the Select button to enter the Date and Time menu.
Press: Display:
Date:
05Dec2011
4. To change the date and time settings, press the Select button again. The year will flash.
8. When the correct date is shown, press the Select button. The saved date is shown.
Press: Display:
Date:
03Jan2012
9. Press the down arrow button to step to the next menu.
Press: Display:
Time:
01:49pm
10. Repeat steps 5 and 6, using the arrow and select buttons to set and save the time.
Note: To change from am to pm, press the up arrow
key to increase the hour until the correct hour and pm is displayed.
11. In the time format menu, press Select and then press the up or down arrow button to change the format, 12 hr. or 24 hr. Press Select to save the displayed format.
Press: Display:
Date:
05Dec2011
5. Press the up or down arrow buttons to change the year.
Press:
OR
Display:
Date:
05Dec2012
6. When the correct year is shown, press the Select button. The year is saved and the next setting (month) flashes.
Press: Display:
Date:
05Dec2012
7. Repeat steps 5 and 6, using the arrow and select buttons to set the month and the date.
Figure 3-7 Changing Settings
12. Press the down arrow button. Return is displayed.
Press: Display:
<---- Return
13. Press Select to return to the Date and Time menu.
Press: Display:
Date ---->
and Time
14. Press the Up or Down arrow buttons to step to a different menu.
15. Press Auto to signal the controller to exit the menus and return to the generator set status display.
Press:
Display:
AUTO
Genset State
Standby
Note: If no buttons are pressed, the controller returns
to the status display after 5 minutes.
TP-6880 10/14 33Section 3 RDC2 Controller Operation
3.6 Setting the Exerciser
Set the exerciser to automatically run the generator set for 20 minutes every week or every two weeks.
3.6.1 Setting the Exerciser at Controller Power-up
When battery power is connected to the controller, you will be prompted to set the date and time, and then to set the exerciser.
The first setting will flash. Press the Up and Down arrow buttons to change the setting. Press Select to save the setting and move on to the next. See Section 3.5 for more detailed instructions to change settings on the RDC2.
If the battery is disconnected and reconnected during generator set maintenance or service, the time, date, and exercise settings will need to be re-entered.
3.6.2 Changing the Exercise Settings
This section explains how to change the exercise settings after the initial setup.
Follow the procedure below and see the flowchart in Figure 3-8 to set the exercise time and date, mode, and frequency.
7. Press the Select button. The setting flashes to show that it can be changed. For example, HR flashes to show that the hour can be changed.
8. Press the Up or Down arrow buttons to change the setting.
9. Press the Select button to save the setting and move to the next. For example, save HR setting and move to MN.
10. Repeat steps 5 through 9 to change the next item on the line until the desired settings are displayed.
11. Press Select to save after all settings have been selected. Settings will stop flashing.
12. If the generator set is connected to a Kohlerr Model RXT transfer switch, the exercise can be changed to a loaded exercise. Set the Exercise Mode to Unloaded Cycle, Unloaded Full, or Loaded Full (RXT ATS required) as shown in Figure 3-8. Unloaded Cycle is recommended. See Sections
2.4.2 through 2.4.4 for information about the exercise modes.
13. Set the exercise frequency (weekly or every two weeks). Weekly exercises are recommended.
14. Press the down arrow button to step to the Return menu. Press the Select button to return to the main menu.
Procedure to Set the Exerciser
1. Press the AUTO button o n the controller.
2. Press the Select button to go to the main menu. SeeFigure3-9.
3. Press the down arrow button to step to the Genset System menu.
4. Press the Select button to enter the Genset system menu. See Figure 3-8.
5. Use the down arrow button to step to the Next Exercise menu. If the exerciser is not set, No Exercise Scheduled will be displayed.
6. Press and HOLD the Select button to enable editing.
After a scheduled exercise run, the next exercise time and date will be updated automatically based on the Exercise Frequency setting.
Other transfer switches: For a loaded exercise with a transfer switch other than a Kohlerr Model RXT ATS, refer to the transfer switch operation manual for instructions.
Exerciser Reset
To reset the exerciser to run at a different day and/or time or to change the exercise mode, follow the procedure in Section 3.6.2 to change the exerciser settings.
TP-6880 10/1434 Section 3 RDC2 Controller Operation
Genset ---->
System
System Freq:
XX.X Hz
System Phase
System Volt
Battery V:
HOLD:
Next Exercise *
HR:MN PM MM/DD/YY
Exercise Mode:
Loaded
Exercise Freq:
Weekly
Language:
Contrast:
50
Next Exercise
HR:MN PM MM/DD/YY
HOLD:
Exercise Mode:
Unloaded Cycle/Unloaded Full/ Loaded Full
HOLD:
Exercise Freq:
Weekly/Bi-Weekly
<---- Return
* If the exerciser has not been set, No Exercise Sch will be displayed.
Figure 3-8 Procedure to Set the Exerciser on the RDC2 Controller
TP-6880 10/14 35Section 3 RDC2 Controller Operation
tp6804
3.7 RDC2 Controller Menus
Controller menus display power system information, including status information for the engine, generator, and optional RBUS accessories, exercise settings, and event history. Some menus allow changes to the controller settings. Status information, including the engine runtime, cannot be changed by the operator.
Diagrams in the following sections show how to navigate through the menus.
Note: Use caution when navigating the controller
menus. In some menus, pressing the Select button can enable editing of the controller settings. Changing the settings to incorrect values can adversely affect generator set operation or render the unit inoperable.
If a setting on the controller display is flashing, edit mode has been enabled. Press the OFF or AUTO button to exit the edit mode.
3.8 Main Menu
Press the Select button once to bring up the main menu. Overview is displayed. See Figure 3-9. Press the down arrow button to step to the next menu, Engine Metering. Use the UP and DOWN arrow buttons to step up and down through the menus shown in Figure 3-9.
The controller will exit the main menu after 5 minutes if no buttons are pressed. To exit the main menu immediately, press the controller’s OFF or AUTO button.
Status Displays
Press the Up and Down arrow buttons to move between menus. Press OFF or AUTO to exit the menus.
Overview -- -->
1.2 h
Engine ----> Metering
Generator----> Metering
Genset ----> Information
Genset ----> Run Time
Genset ----> System
ATS - - - -> Configuration *
D a t e -- -- > and Time
Network ----> Information
PIM ----> Status [
Load ----> Control ]
ATS -- - -> Status
* ATS Configuration appears only if a Model RXT transfer switch is connected.
[ PIM Status appears only if a programmable interface module is connected. ] Load Control appears only if a load control module (LCM) or load shed kit is connected.
Figure 3-9 RDC2 Main Menu
Event Log-- -->
tp6804
TP-6880 10/1436 Section 3 RDC2 Controller Operation
3.9 Overview Menu
Overview -- -->
1.2 h
Active Alert (if any)
3.10 Engine Metering Menu
The engine metering menu displays engine status information as shown in Figure 3-11. This menu displays status information only. No settings can be changed from this menu.
Genset Status Standby
Voltage: 240V Freq: 60.0Hz
Engine: 123F Oil Pressure: OK
Battery
12.3V
Engine Runtime:
12345.6 h
Date: 02DEC2011 Time: HR:MNpm
Engine ---->
Metering
Eng Speed:
3600 RPM
Oil Pressure: Switch: Normal
Oil Temp:
Battery:
<-- -- Return
Note: Actual settings may vary.
Figure 3-11 Engine Metering Menu
123 F
12.3 V
tp6810
Next Exercise: 09:00p 09Dec2011
Next Maintenance: 150 h or Mar2012
SW Version:
12.34
<---- Return
Note: Actual settings may vary.
tp6804
Figure 3-10 Overview Menu
TP-6880 10/14 37Section 3 RDC2 Controller Operation
3.11 Generator Metering Menu
Voltage Calibration
The generator metering menu displays the generator voltage and frequency. See Figure 3-12.
Generator ---->
Metering
DANGER
Hazardous voltage. Will cause severe injury or death.
This equipment must be installed and serviced by qualified electrical personnel.
The voltage calibration mode can be entered from the Generator Metering menu. Contact a Kohler-authorized distributor/dealer for service.
The Reset Calibration menu allows you to set the voltage reading back to the original value after calibration, if necessary. See Figure 3-12.
Three-phase
Volts L1--L2:
Volts L2--L3:
Volts L3--L1:
Frequency:
240 V
240 V
240 V
60.0 Hz
Volts:
Frequency:
Reset Calibration
<-- -- Return
Single-phase
Note: Actual settings may vary.
240 V
60.0 Hz
Reset Calib? No
Reset Calib? Yes
Figure 3-12 Generator Metering Menu
tp6810
TP-6880 10/1438 Section 3 RDC2 Controller Operation
3.12 Generator Set Information Menu
The generator set model number and serial numbers are displayed. No changes are allowed from this menu.
Model and serial numbers are factory set and should not require changes in the field, except in the event that the controller is being replaced. A personal computer running Kohler SiteTech software is required to enter the generator set model number and serial numbers on a replacement controller. Contact an authorized Kohler distributor/dealer for service.
Genset ----> Information
Genset M/N:
20RESV
Genset S/N:
########
3.13 Genset Run Time Menu
The data shown in Figure 3-14 are displayed. No changes are allowed from this menu.
Eng Runtime displays the total number of hours that the generator set engine has run. The runtime is not resettable.
The Next Maintenance menu shows the number of hours of generator set operation until maintenance is required. The estimated date for the next scheduled maintenance is also displayed. The maintenance reminder intervals are based on the engine manufacturer’s recommendation for changing the oil. Refer to Section 5, Scheduled Maintenance, for maintenance instructions.
After changing the oil and performing other recommended maintenance, go to the Overview menu to reset the maintenance timer. See Section 5.2.5 for instructions to reset the maintenance timer.
Controller S/N:
########
<-- -- Return
Figure 3-13 Generator Set Information Menu
tp6804
Genset ----> Run Time
Eng Runtime:
12345.6 h
Eng Starts:
123456
Next Maintenance: 150 h or Mar2012
<-- -- Return
Note: Sample data shown.
Figure 3-14 Generator Set Run Time Menu
tp6810
TP-6880 10/14 39Section 3 RDC2 Controller Operation
3.14 Genset System Menu
The genset system menu displays the system information shown in Figure 3-15. Generator sets are factory set and should not require changesto the system settings in the field.
A Kohler authorized distributor or dealer can adjust these settings, if necessary. If the generator set is reconnected to a different voltage or the system settings require adjustment for some other reason, see Section
3.5 for instructions to enable editing and change the
system settings.
Note: Use caution when navigating the controller
menus. In some menus, pressing the Select button can enable editing of the controller settings. Changing the settings to incorrect values can adversely affect generator set operation or render the unit inoperable.
Voltage Regulator (VR) Voltage Adj
The generator set voltage is factory set and typically does not require adjustment in the field. If voltage adjustment is required, contact a Kohler authorized distributor or dealer for service. Refer to the generator set Installation Manual for instructions to adjust the voltage.
Setting the Exerciser
Genset ---->
System
System Voltage:
240 V
System Freq:
60 Hz
VR Voltage Adj:
240.0V
System Phase:
Single
System Battery:
12 V
Next Exercise
06:30p 15Dec2011
Exercise Mode:
Unloaded Variable
Use the Genset System menus to set the generator set exerciser. Refer to Section 2.4 for instructions to set the exerciser and for more information about exercising the generator set.
After a scheduled exercise run, the Next Exercise time and date will be updated automatically based on the Exercise Frequency setting.
Adjusting the Display Contrast
To adjust the display contrast, use the down arrow button to step to the Contrast menu. Press the Select button, and then use the up and down arrow buttons to adjust the contrast. Press the Select button to save the contrast setting.
Exercise Freq:
Weekly
Meas System:
English
Contrast:
<---- Return
Note: Actual settings may vary.
Figure 3-15 Genset System Menu
50
tp6810
TP-6880 10/1440 Section 3 RDC2 Controller Operation
3.15 ATS Status Menu
ATS menus appear if a Model RXT transfer switch is connected to the generator set. If no transfer switch is connected, or another model ATS is connected to the engine start connections, Remote ATS is displayed on the ATS Status screen.
The ATS Status menu displays Model RXT transfer switch and source information.
The voltage shown in these menus can be calibrated. Follow the safety precautions at the beginning of this manuals. Use a voltmeter to measure the line-to-line voltage and follow the instructions in Figure 3-16 to calibrate the voltage readings.
ATS --- -> Status
ATS Position: Normal
Normal Status: Not/Acceptable
Emerg. Status: Standby
Single-phase
Normal Volts:
Normal Freq.:
Emerg Volts:
240.0 V
60.0 Hz
240.0 V
Note: If there is no Model RXT transfer
switch connected to the generator set, Remote ATSis displayed and the other screens on this page do not appear.
Note: Sample data shown.
Three-phase
Normal Voltage:
L1--L2 240 V
Normal Voltage:
L2--L3 240 V
Normal Voltage:
L3--L1: 240 V
Emerg. Freq.:
60.0 Hz
Reset
Calibration
<-- -- Return
Normal Freq.:
60.0 Hz
Normal Rotation:
Similar screens appear for the emergency source.
Reset Calib? No
Reset Calib? Yes
Figure 3-16 ATS Status Menu, with Calibration
TP-6880 10/14 41Section 3 RDC2 Controller Operation
tp6810
3.16 ATS Configuration Menu
Note: The ATS Configuration menu appears only if a
Model RXT transfer switch is connected.
Use the ATSConfiguration submenu to check the Model RXT transfer switch system settings and time delays, and change the settings, if necessary.
Changing ATS Configuration Settings
To enable editing, press the select button. The value flashes to indicate that it can be changed. Press the up and down arrow buttons to change the value. Press the Select button to save the value shown.
Use the up and down arrow buttons to move to the next value to be changed. Repeat the adjustment process until all values are correct.
Press the down arrow until Return is displayed. Press the select button to return to the main menu.
ATS ---- >
Configuration
Normal Freq:
12.3 Hz
Normal Voltage:
12345.6 V
Emerg. Freq:
12.3 Hz
Emerg. Voltage:
12345.6 V
Emerg. Engine Start: 3 sec
Transfer From
Normal:3sec
Transfer From Emerg.: 120 sec
<-- -- Return
Note: Actual settings may vary.
Figure 3-17 ATS Configuration Menu
tp6810
TP-6880 10/1442 Section 3 RDC2 Controller Operation
3.17 Date and Time Menu
The date and time will typically be set at controller power--up. To change the date, time, or time format (12 hour or 24 hour), use the Date and Time menu. See Figure 3-18.
3.18 Networking Information Menus
Date and Time
Date:
02Dec2011
Time:
12:34pm
Use the networking menus to view and adjust communication settings for systems with remote RBUS devices such as a PIM or LCM or load shed kit, and for systems that use the Kohlerr OnCuer Plus Generator Management System.
RBUS is a proprietary RS-485 communications protocol.
The Networking Information menu leads to submenus for network and RBUS communication settings.
Networking-- --> Information
Networking-- --> Status
Networking-- --> Configuration
RBUS ---->
Information
Time Format:
12hr|24hr
<---- Return
To change the date and time, press the Select button See Figure 3-7 for instructions.
Figure 3-18 Date and Time Menu
NS
See Figure 3-20.
NC
See Figure 3-21.
RB
See Figure 3-22.
tp6804
<-- -- Return
Figure 3-19 Networking Information Menu
TP-6880 10/14 43Section 3 RDC2 Controller Operation
tp6810
3.18.1 Networking Status Submenu
The Networking Status submenu contains settings for OnCuer Plus. See the OnCue Plus Software Operation Manual for information about the appropriate network settings for OnCue Plus. Changes to these settings are not typically required.
If DHCP is enabled, IP parameters are not displayed. If DHCP is disabled (i.e., if a static IP address is used), the IP parameters are displayed.
To enable or disable DHCP and change the IP settings, go to the Networking Configuration menu. See Section 3.18.2.
Networking-- --> Information
Networking-- -->
Status
OnCue Status: Connected
DHCP:
Enabled
IP Address:
123.456.789.123
Subnet Mask:
123.456.789.123
Gateway:
123.456.789.123
DNS 1:
123.456.789.123
Figure 3-20 Network Status Submenu
DNS 2:
123.456.789.123
Ethernet Status:
Disconnected
OnCue Server:
123.456.789.123
<-- -- Return
tp6804
TP-6880 10/1444 Section 3 RDC2 Controller Operation
3.18.2 Networking Configu ration
Submenu (OnCue Plus Password)
The Networking Configuration menu includes settings used for communication with the Kohlerr OnCuer Plus Generator Management System.
Password
Note: Use the OnCue password shown on the
controller display for OnCue Plus applications.
For the initial OnCue Plus setup, you will be required to reset the OnCue password on the RDC2 controller, and then enter it into the OnCue Plus software. To reset the password, follow the instructions in Figure 3-21.
Note: The password is displayed for only 10 seconds.
Be sure to write down the password and serial number.
A new password is generated each time the reset password procedure is performed. If the password is
reset after the OnCue Plus system has been set up, the connection will be lost. Disconnect the battery power to the controller, wait a minute, then reconnect power.
DHCP Submenu
For most applications, the Dynamic Host Configuration Protocol (DHCP) is enabled and the IP settings cannot be changed from the controller keypad. If DHCP is enabled, IP parameters are not displayed.
If DHCP is disabled (i.e., if a static IP address is required), then the IP parameters can be modified. For applications that require static IP addresses, press and hold the select button to enable editing, disable DHCP, and then step to the next parameters and enter the information.
If an error occurs while setting a parameter, an error message is displayed and then the controller exits the edit mode. Previous settings are preserved.
TP-6880 10/14 45Section 3 RDC2 Controller Operation
Networking-- -->
Information
Networking-- -->
Status
HOLD
Networking Configuration
RBUS ----> Information
Reset OnCue Password
DHCP: Enabled
Reset OnCue Password? No
UP arrow for YES, Down arrow for NO.
Reset OnCue Password? Yes
Press Select to enter YES or NO as displayed. New password is displayed for approximately 10 seconds.
S/N: 1234567 New PW: 12345
HOLD
DHCP: Disabled
UP arrow to enable, Down arrow to disable.
IP Address:
123.456.789.123
<-- -- Return
Figure 3-21 Network Configuration Submenu
Subnet Mask:
123.456.789.123
Gateway:
123.456.789.123
DNS 1:
123.456.789.123
DNS 2:
123.456.789.123
tp6804
TP-6880 10/1446 Section 3 RDC2 Controller Operation
3.18.3 RBUS Information
D Model RXT transfer switch
The RBUS Information menu contains settings for remote modules that communicate with the RDC2 controller using RBUS protocol. This includes the following optional modules:
Networking-- -->
Information
Networking-- -->
Status
Networking-- -->
Configuration
RBUS ---->
Information
<-- -- Return
D Programmable Interface Module (PIM)
D Load Control Module (LCM) or load shed kit
Modules Connected: 2
R e m o t e -- -- > Devices
See Figure 3-23.
Net Cycle Time: 123ms
RD
Figure 3-22 RBUS Information Submenu
Module Timeouts: 1234
Module Errors: 1234
< ---- Return
tp6804
TP-6880 10/14 47Section 3 RDC2 Controller Operation
3.18.4 Remote Devices Submenu
Check the status of remote devices communicating through RBUS. Device types can include:
D Model RXT ATS
D Programmable Interface Module (PIM)
D Load Control Module (LCM) or load shed kit
From Figure 3-22:
R e m o t e -- -- > Devices
The serial numbers for the PIM and LCM or load shed kit are printed on the circuit boards inside the enclosures.
S/N: XXXXXXXXX <<*DeviceType*>>
Module Status: Connected
Comm. Errors: 12345
Comm. Timeouts: 12345
Module ID: 12
Firmware Ver.: 122
(Dis)Connected: MM/DD/YY 12:12
S/N: XXXXXXXXX <<*DeviceType*>>
Connected: Displays the date and time that the device was connected. Disconnected: Displays the last date and time of successful communication.
<-- -- Return
R e t u r n -- -- >
Figure 3-23 Remote Devices Submenu
tp6804
TP-6880 10/1448 Section 3 RDC2 Controller Operation
3.19 Programmable Interface Module (PIM) Status Menu
The PIM status menu displays the status of inputs and outputs connected to the programmable interface module (PIM). this menu appears only if a PIM is connected. This is a status d isplay menu only. Input and output settings cannot be changed from the RDC2 controller’s user interface.
A personal computer running Kohlerr SiteTecht software is required to change the input and output settings. Contact an authorized distributor or dealer for service.
The Kohlerr OnCuer Plus Management System can be used to turn outputs on and off. See the OnCuer Plus Software Operation Manual for instructions.
PIM Status:
P I M 1 -- -- >
<-- -- Return
Input 1 In/Active
Input 2 In/Active
Output 1: In/Active
Output 2: In/Active
Output 3: In/Active
Output 4: In/Active
Output 5: In/Active
Output 6: In/Active
<-- -- Return
Figure 3-24 Programmable Interface Module (PIM) Status Menu
TP-6880 10/14 49Section 3 RDC2 Controller Operation
tp6810
3.20 Load Control Module (LCM) or Load Shed Kit Menus
The Load Control menu displays the status of the Load Control Module (LCM) or load shed kit inputs and outputs, and allows a test of the LCM or load shed kit output relays. This menu appears only if an LCM or load shed kit is connected.
Generator current is displayed as a percent of the maximum generator capacity. The load control module
or load shed kit adds and sheds loads based on the generator current.
The test function cycles the relays in the order of their priority. For detailed information about the LCM operation, refer to TT-1574, provided with the LCM kit. For detailed information about the Load Shed kit operation, refer to TT--1609, provided with the Load Shed kit.
Load -- --> Control
Generator Current: 123 %
Load -- --> Control 1
<-- -- Return
Test Outputs Push Select
Input 1: In/Active
Input 2: In/Active
Output 1: Add/Shed
Output 2: Add/Shed
Output 3: Add/Shed
Output 4: Add/Shed
(blinking)
Output 5: Add/Shed
Output 6: Add/Shed
<-- -- Return
Figure 3-25 Load Control Module (LCM) or Load Shed Kit Status Menu
tp6810
TP-6880 10/1450 Section 3 RDC2 Controller Operation
3.21 Event Log
The event log displays up to 1000 controller faults and notices, starting with the most recent event. Events are numbered 1--1000, with 1 being the most recent. Each event is displayed with the date and time of the event, the number of the event, a code to indicate whether the event was a warning ( W ), shutdown (S), or informational notice ( I ), the engine hours at the time of the event, and the event description.
The time and date for notices (I) are not stored in the controller.
Procedure to View Event History
1. Press Select to enter the main menu.
To stop viewing the event history before the last event, press the select button to return to the main menu.
Date MO/DA/YEAR
Event Log ---->
Press UP and Down arrow buttons to scroll through events
time HR:MN
event number, W/S/I, engine hours
event name
Date MO/DA/YEAR
time HR:MN
event number, W/S/I, engine hours
event name
2. Press the down arrow to step down to the event log.
3. Press Select to display the most recent event.
4. Press the down arrow to step to the next event.
5. Use the up and down arrow buttons to view events.
6. Press the Select button to exit the event log.
Press Select button at any time to return to the main menu.
Figure 3-26 Event Log
tp6810
TP-6880 10/14 51Section 3 RDC2 Controller Operation
Notes
TP-6880 10/1452 Section 3 RDC2 Controller Operation
Section 4 DC2 Controller Operation
4.1 DC2 Generator Set/ Transfer Switch Controller
Model RESVL generator sets are equipped with the DC2 generator set/transfer switch controller.
Model RESV generator sets are equipped with the RDC2 generator set/transfer switch controller. See Section 3 for RDC2 controller operation information.
The DC2 controls the following power system components:
D Model 8RESVL, 10RESVL, or 12RESVL generator
set
D Model RXT Automatic Transfer Switch (ATS)
1
2
D Load Control Module (LCM) or load shed kit
D Programmable Interface Module (PIM)
DC2 controller features include:
D Two-line x 16 character backlit digital display with
adjustable contrast
D OFF, AUTO, RUN, and EXERCISE generator set
control buttons
4.2 Controls and Indicators
Figure 4-1 illustrates the DC2 controller. See Figure 4-2 for details of the controller’s user interface.
1. User Interface
2. USB port (mini-B); see Section 6.2.
Figure 4-1 DC2 Controls and Indicators
1
4 35 2
1. 2-line LCD display
2. EXERCISE button
3. RUN button and LED
4. OFF button and LED
5. AUTO button and LED
GM77569
GM77569
Figure 4-2 DC2 User Interface
TP-6880 10/14 53Section 4 DC2 Controller Operation
4.2.1 Controller Keypad
4.2.2 LED Indicators
The RUN, OFF, and AUTO buttons control the generator set as described in Figure 4-3.
LEDs above the RUN, OFF, and AUTO buttons indicate the mode of operation as shown in Figure 4-4.
Use the EXERCISE button to set the exerciser on the DC2 controller. See Section 4.5 for instructions to set the exerciser.
Note: A personal computer (laptop) with Kohlerr
SiteTecht software is required for changing settings on the DC2 controller.
Button Button Function
RUN Press to start the generator set. The engine start time delay is ignored.
The software version and engine model are displayed briefly when RUN is pressed.
OFF Stops the generator set. The cooldown time delay is ignored.
During the engine crank cycle, pressing OFF will stop the crank cycle.
Press to clear faults and reset the controller.
Press and hold to access the event log.
AUTO Press to place the generator set in Automatic (standby) mode.
Press to exit the event log.
Press and hold AUTO and OFF to reset the maintenance timer.
EXERCISE When the controller is in AUTO mode, press to set the exerciser. See Section 4.5.
When the controller is OFF, press and hold to reset the OnCue password. See Section 4.8.
Figure 4-3 DC2 Controller Pushbutton Operation
LED LED Indication Description
RUN RUN LED is on. Generator set is running. Remote start and stop commands are ignored.
OFF
AUTO AUTO LED is on. Automatic (standby) mode. Generator set will respond to engine start and
OFF LED lights for 2 seconds, then flashes every 2 seconds.
In Auto mode, OFF LED flashes quickly to indicate a fault shutdown.
Generator set and controller are off. Remote start/stop commands have no effect. The exercise cycle will not run.
Attention required. Identify and correct the fault condition before resetting the controller.
stop commands from the controller (for example, exercise start and stop commands) or an ATS. Time delays operate as described in Section 2.3.
Figure 4-4 DC2 Controller LED Operation
TP-6880 10/1454 Section 4 DC2 Controller Operation
4.2.3 LCD Display
The controller is equipped with a two-line x 16 character backlit digital display with adjustable contrast. When the generator set is running, the messages shown in Figure 4-5 are displayed. When the system is in AUTO, the LCD display steps through the status messages shown in Figure 4-6.
Active Alert (if any)
Genset State Standby
When a fault or warning condition exists, the controller will show the corresponding message. See Section 2.5 for more information on fault and warning messages.
The display backlight turns off after about a minute of no activity. The backlight turns on when a button is pressed or when the generator set starts.
Active Alert (if any)
Running ATS : Norma l *
Voltage: 240V Freq: 60.0Hz
Engine: 123F Oil Pressure: OK
Battery 12.3V
Runtime: 12345.6 h
Next Exercise:
7d 6h 42m
Next Maint:
123h or 12months
OnCue Status:
Disconnected
Sample data shown.
[ OnCue status is displayed only if OnCue password has
been reset.
Figure 4-6 Status Displays, Generator in Standby
4.3 Controller Power
Battery 12.3V
Runtime: 12345.6 h
Next Exercise:
7d 6h 42m
OnCue Status:
Disconnected [
Sample data shown.
* Model RXT ATS required [ OnCue status is displayed only if OnCue password has
been reset.
Figure 4-5 Status Displays, Generator Running
The DC2 controller is powered by the generator set engine starting battery.
Note: To disconnect controller power, disconnect the
utility power to the generator set and disconnect the battery (negative lead first).
4.4 Battery Charging
The controller includes a built-in battery charger to maintain the engine starting battery. The DC2 controller monitors the battery voltage and provides a constant 14 ±2% VDC voltage and maximum 2.5 amps to charge the battery.
The installer must connect 120 VAC/60Hz utility power provided from the building on a breaker-protected circuit for the built-in battery charger. See the Installation Manual for instructions to connect power.
TP-6880 10/14 55Section 4 DC2 Controller Operation
4.5 Exercise
4.5.3 Exerciser Reset
The DC2 controller can be set to automatically run the generator set at the same time and day each week. Exercising the generator set weekly is required to keep the engine and alternator in good operating condition.
A laptop computer with Kohlerr SiteTecht software can be used to change the exercise frequency to every two weeks. Use a USB cable to connect the controller to the computer and see TP-6701, SiteTech Operation Manual for instructions.
4.5.1 Exercise Modes
Unloaded Cycle or Loaded Full-Speed exercises can be set from the DC2 controller. The Unloaded Cycle exercise mode is the default exercise mode. A Model RXT transfer switch is required for the Loaded Full-Speed exercise mode. See Section 2.4 for more information about the exercise modes.
A laptop computer with Kohlerr SiteTecht software can be used to change the exercise mode to Unloaded Full Speed.
To reset the exerciser to run at a different day and/or time, follow the procedure in Section 4.5.2 to enter the new exerciser settings. The old settings will be replaced by the new time and day.
4.6 Event Log
The event log displays up to 10 controller faults and notices, starting with the most recent event. Events are numbered 1--10, with 1 being the most recent. Each event is displayed with the date and time of the event, the number of the event, a letter to indicate whether the event was a warning ( W ), shutdown (S), or informational notice ( I ), the engine hours at the time of the event, and the event description. See Figure 4-7.
Hold
Any Screen
OFF
Event number, W/S/I, engine hours
Event name
Press OFF
4.5.2 Setting the Exerciser
Set the exerciser to automatically run the generator set for 20 minutes every week. Follow the procedure below to set the exerciser.
Procedure to Set the Exerciser
1. Press AUTO. Verify that the AUTO LED is on and Utility power is available.
2. Press the exercise button to start an unloaded exercise.
3. If a loaded exercise is required, press the Exercise button again within 5 seconds.
4. After 5 seconds, the generator begins its crank cycles. During the crank cycles, the number of the crank cycle is displayed. No button presses are acknowledged during the crank cycles.
5. The generator runs through the exercise cycle described in Section 2.4.2. The controller monitors the system during the unloaded exercise as described in System Diagnostics.
Event number, W/S/I, engine hours
Event name
Press AUTO button at any time to exit the event log.
Figure 4-7 Event Log
Procedure to View Event Log
1. Press the OFF button. The controller must be OFF to display the event log.
2. Press and hold the OFF button until the first event appears on the display.
3. Press OFF to step through the other events.
4. To exit the Event Log, hold the OFF button or p ress the AUTO button.
tp6804
6. After 20 minutes, the engine stops automatically.
The exercise time is set to the time the exercise button is pressed. An unloaded or loaded exercise, as selected above, will occur at the same time every seven days.
TP-6880 10/1456 Section 4 DC2 Controller Operation
4.7 Maintenance Timer
4.8 OnCue Plus Password
The maintenance timer keeps track of the time until the next recommended maintenance according to the maintenance schedule for the generator set. Reset the maintenance timer after changing the oil and performing the other maintenance tasks recommended in Section 5.
To reset the maintenance timer:
1. Press and hold the OFF and AUTO buttons together until Maintenance Timer Reset is displayed.
2. Release the OFF and AUTO buttons.
To set the OnC u e r Plus password on the DC2 controller,
1. Press the OFF button and verify that the generator set is not running.
2. Press and hold the Exercise button until Press Again to Reset OnCue PW is displayed.
3. Release the Exercise button and press it again within 5 seconds.
Note: If the Exercise button is not pressed within 5
seconds, the controller exits the password reset mode.
4. The genset serial number and new password (PW) will be displayed for 10 seconds. Record the password for entry into the OnCuer Plus program.
TP-6880 10/14 57Section 4 DC2 Controller Operation
Notes
TP-6880 10/1458 Section 4 DC2 Controller Operation
Section 5 Scheduled Maintenance
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
DANGER
Hazardous voltage. Will cause severe injury or death.
This equipment must be installed and serviced by qualified electrical personnel.
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Moving parts.
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the alternator. Hot parts can cause severe injury or death. Avoid touching the alternator field or exciter
armature. When shorted, the alternator field and exciter armature become hot enough to cause severe burns.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely hot during operation.
Servicing the engine heater. Hot parts can cause minor personal injury or property damage. Install the heater
before connecting it to power. Operating the heater before installation can cause burns and component damage. Disconnect power to the heater and allow it to cool before servicing the heater or nearby parts.
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator set with
the air cleaner removed.
Servicing the fuel system. A flash fire can cause severe injury or death. Do not smoke or permit flames or sparks near
the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor.
TP-6880 10/14 59Section 5 Scheduled Maintenance
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly explosive. Use
extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an explosion. Check
the LP vapor gas or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6--8 ounces per square inch (10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
LP liquid withdrawal fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an
explosion. Check the LP liquid withdrawal gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to at least 90 psi (621 kPa). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
See the Safety Precautions and Instructions at the beginning of this manual before attempting to service, repair,or operate the generator set. Have an authorized distributor/dealer perform generator set service.
Routine Maintenance. Refer to the following generator set service schedule, the engine service schedule, and the runtime hours displayed on the generator set controller to determine when to schedule routine maintenance. Service the generator set more frequently if it is subject to extreme weather, long operating hours, or dusty or dirty conditions.
Maintenance Reminders. The RDC2 and DC2 controllers display a reminder message every 100 hours of engine run time. Change the oil and perform other maintenance tasks listed on the service schedule. Then reset the reminder. See Section 5.2.5 for instructions to reset the maintenance reminder.
Service Schedule. Perform maintenance on each item in the service schedule at the designated interval for the life of the generator set.
Tools. Tools and instruments used to perform some maintenance items are not generally available to the generator set owner. Therefore, have service performed by an authorized distributor/dealer.
5.1 Scheduled Maintenance
Refer to the following service schedules and the runtime hours displayed on the controller display to schedule routine maintenance. Intervals are shown in hours of operation and/or time intervals (i.e. weekly, monthly, quarterly, etc.) Have an authorized distributor/dealer service the generator set at the designated intervals in the service schedule for the life of the generator set. Service units subject to extreme weather, long operating hours, or dusty or dirty conditions more frequently.
Contact an authorized distributor/dealer for parts.
TP-6880 10/1460 Section 5 Scheduled Maintenance
5.1.1 Service Schedule
Procedure
See
System Component or Procedure
Section
Fuel
Flexible lines and connections X R Quarterly Main tank supply level X Weekly Fuel piping X Yearly
Lubrication
Oil level
Crankcase breather hose X Yearly or 500 hours Change oil X Yearly or 100 hours Replace filter X Yearly or 100 hours
Cooling
Air ducts, louvers X X Yearly
Exhaust Line
Leakage X X Weekly Insulation, fire hazards X Yearly Obstructions or combustible materials near
exhaust outlet
DC Electrical System
Battery charger operation, charge rate (if equipped)
Remove corrosion, clean and dry battery and rack X X Yearly Clean and tighten battery terminals and inspect
boots
Battery electrolyte level and specific gravity * X Yearly
5.2
5.5
5.6
5.7
AC Electrical System
Tighten control and power wiring connections X Yearly Remote control system, if equipped X Monthly Visible wear or damage X Quarterly Wire abrasions where subject to motion X X Six Months Wire-cable insulation condition X 3 Years or 500 hours
Engine and Mounting
Visible wear or damage X Weekly Air cleaner service [
Spark plugs (apply anti-seize lubricant for easy removal)
Have valve lash checked/adjusted, 8RESV(L) Engine SM D 100 hours Have valve lash checked/adjusted, 10/12RESV(L) Engine SM D 500 hours Replace stepper motor coupling and bushing D 500 hours
5.4
5.3
Generator
Visible wear or damage X Quarterly Exercise generator set X Weekly Brushes and collector ring D D Yearly or 300 hours Measure and record resistance readings of
windings with insulation tester (Meggerr,with SCR assembly or rectifier and load leads disconnected) *
General Condition of Equipment
Evidence of vibration, leakage, excessive noise, temperature, or deterioration
Interior of sound enclosure X X Quarterly * Not necessary for maintenance-free batteries. [ Service more frequently under extremely dusty/dirty conditions.
Meggerr is a registered trademark of Biddle Instruments.
Visually
Inspect
XAction D Authorized distributor/dealer only
R Replace as necessary
Check Change Clean Test
X X
X Weekly
X Monthly
X X Yearly
150 300
X Yearly or 500 hours
X X X Weekly
Yearly or hours
D 3 Years
Frequency
8 hours or before use
shown
TP-6880 10/14 61Section 5 Scheduled Maintenance
5.2 Lubrication System
5.2.3 Engine Oil Recommendation
See the service schedules in Section 5.1 for oil change and oil filter replacement intervals. See the service views in Section 1.9 for the oil drain, oil check, oil fill, and oil filter locations.
5.2.1 Low Oil Pressure Shutdown
The low oil pressure (LOP) shutdown feature protects the engine against internal damage if the oil pressure drops below a minimum pressure because of oil pump failure or other malfunction.
Note: The LOP shutdown feature does not protect
against damage caused by operating when the oil level is low; it is not a low oil level shutdown. Check the oil level regularly, and add oil as needed.
5.2.2 Oil Check
The generator set is shipped with oil. Before operating the generator set, check the engine oil in the crankcase.
To check the oil level, shut down the generator set and wait several minutes. Remove the dipstick and wipe the end clean, reinsert, and remove. See Figure 5-1. Maintain the oil level between the Add and Full marks on the dipstick. Add 5W-30 synthetic oil when the oil level is low.
Check the oil level before each use. For extended operation, check the oil level every 8 hours. Do not check the oil level when the generator set is running.
Use 5W-30 API (American Petroleum Institute) Service Class SG, SH, or SJ synthetic oil. Synthetic oil oxidizes and thickens less than other oils and leaves the engine intake valves and pistons cleaner.
5.2.4 Oil Change Procedure
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
WARNING
1. Oil dipstick/oil fill
2. Oil drain valve
Figure 5-1 Oil Check (typical)
Fire. Can cause severe injury or death.
Do not smoke or permit flames or
1
Servicing the fuel system. A flash fire can cause severe injury or death. Do not smoke or permit flames or sparks near
2
6515
the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor.
sparks near fuels or the fuel system.
TP-6880 10/1462 Section 5 Scheduled Maintenance
Note: Dispose of all waste materials (engine oil, fuel,
filter, etc.) in an environmentally safe manner.
Note: The oil change procedure requires the use of
rags, a drain tube, and a funnel. Follow the instructions and use caution to prevent oil from spilling on or into the alternator.
1. Drain the oil.
a. Press the OFF button on the generator set
controller.
f. Lightly thread the new oil filter by hand until you
feel Resistance. Then, tighten the filter an additional 3/4 turn with an oil filter wrench.
3. Fill with oil.
Note: When the oil is drained, some oil remains in the
engine. The amount of oil needed to refill the engine may be less than the capacity shown in Figure 5-2. Use the dipstick shown in Figure 5-1 to check the oil level during the fill. Do not fill past the full mark on the dipstick.
b. Disconnect the utility power to the generator
set.
c. Disconnect the generator set engine starting
battery, negative (--) lead first.
d. Remove the side panel on the exhaust side of
the enclosure.
e. Clean the area around the dipstick and oil fill
cap.
f. To prevent oil from spilling into the alternator,
completely cover the alternator with rags around the areas near the oil drain valve and oil filter.
g. Insert a drain tube (3/8 in. inside diameter) onto
the oil drain valve and place the end of the tube into a drain pan. The tube will reduce the potential for spilled oil.
h. Open the oil drain valve on the engine.
i. Remove the dipstick and oil fill cap. Allow time
for the engine oil to drain completely.
j. Close the oil drain valve and remove the oil
drain tube.
k. Replace the dipstick.
2. Replace the oil filter.
a. Clean the area around the oil filter.
b. Loosen the oil filter by rotating it
counterclockwise with an oil filter wrench.
Generator Set Model Oil Capacity, L (qt.)
8RESV/RESVL 1.5 (1.6)
10/12RESV/RESVL 1.9 (2.0)
Figure 5-2 Engine Oil Capacity (new, dry engine)
a. See Section 5.2.3 for the recommended oil
type. To prevent spilling, use a funnel to add oil through the oil fill port. Use the dipstick to check the oil level before starting to add the final quart of oil. Fill the engine to the F mark on the dipstick.
b. Reinstall the dipstick and the oil fill cap.
c. Remove all rags near the alternator and oil
drain valve.
d. Reconnect the generator set engine starting
battery, negative (--) lead last.
e. Reconnect the utility power to the generator
set.
f. Press the RUN button on the generator set
controller. The generator set will start.
g. Run the generator set for a minute to allow the
oil pressure to reach operating range.
h. Stop the generator set, wait 1 minute, and then
recheck the oil level. Add oil to bring the level up to the F mark on the dipstick.
4. Check for leaks.
a. Check for oil leaks.
c. As you remove the oil filter, tilt the filter upward
b. Fix leaks and recheck the oil level.
to prevent oil from spilling.
c. Reinstall the side panel.
d. Clean the gasket sealing surface of the oil filter
adapter.
5. Reset the maintenance timer on the controller.
e. Apply a light coat of clean oil to the rubber seal
of the new oil filter.
TP-6880 10/14 63Section 5 Scheduled Maintenance
5.2.5 Resetting the Maintenance Timer
Model RESV (RDC2):
2. Remove the spark plug and check its condition. Replace the spark plug if it is worn or if its reuse is questionable.
1. From the Overview menu, step down to the Genset Run Time menu.
2. Press the Select button and then step down to the Next Maintenance screen.
3. Press the Select button.
4. Press the Up arrow button so that “Reset Maint Timer? Yes” is displayed.
5. Press the Select button. After about two minutes, the new maintenance interval and date are displayed.
Model RESVL (DC2):
1. Press and hold the OFF and AUTO buttons together until Maintenance Timer Reset is displayed.
2. Release the OFF and AUTO buttons.
5.3 Spark Plugs
3. Check the spark plug gap using a wire feeler gauge. See Figure 5-3 for the recommended spark plug gap. Adjust the gap by carefully bending the ground electrode. See Figure 5-4 and Figure 5-5.
4. For easy removal, apply a light coating of anti-seize lubricant to the cleaned spark plug threads. Wipe away any excess compound.
5. Reinstall the spark plug into the cylinder head. Torque the spark plug to 24.4--29.8 Nm (18--22 ft. lb.)
Generator Set Model Spark Plug Gap
8/10/12RESV/RESVL 0.508 mm (0.020 in.)
Figure 5-3 Spark Plug Gap
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
1--514
Figure 5-4 Checking the Spark Plug Gap
1-- 511
Figure 5-5 Adjusting the Spark Plug Gap
Reset the spark plug gap or replace the plugs with new plugs as necessary.
1. Clean the area around the base of the spark plug to keep dirt and debris out of the engine.
TP-6880 10/1464 Section 5 Scheduled Maintenance
5.4 Air Cleaner Service
WARNING
1
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator set with
the air cleaner removed.
5.4.1 Air Cleaner, 8RESV/RESVL Models
The engine has a replaceable high-density paper air cleaner element. See Figure 5-6.
Check for a buildup of dirt and debris around the air cleaner system. Keep this area clean. Also check for loose or damaged components. Replace all bent or damaged air cleaner components.
2
1. Air cleaner base
2. Air cleaner element
3. Element cover
4. Air cleaner knob
3
4
586536
Figure 5-6 Air Cleaner Components
Paper Element Service
Use the following procedure to replace the paper element at the intervals specified in the service schedule. Replace the paper element more often under extremely dusty or dirty conditions.
1. Press the OFF button on the generator set controller.
2. Disconnect the utility power to the generator set.
3. Disconnect the generator set engine starting battery, negative (--) lead first.
4. Loosen the cover retaining knobs and remove the cover.
5. Remove the paper element.
Note: Do not wash the paper element or clean it
with pressurized air, as this will damage the element.
6. Replace the element if it is dirty, bent, or damaged.
7. Check the air cleaner base. Make sure it is secure and not bent or damaged. Also check the element cover for damage and fit. Replace all damaged air cleaner components. Remove any loose dirt or debris from the air cleaner base. Wipe the base carefully so that no dirt drops into the intake throat. Check the condition of the rubber seal on the air cleaner stud and replace the seal if necessary.
8. Reinstall the paper element and the air cleaner cover. Secure the cover with the cover retaining knobs.
Note: Operating the engine with loose or damaged air
cleaner components could allow unfiltered air into the engine causing premature wear and failure.
TP-6880 10/14 65Section 5 Scheduled Maintenance
9. Reconnect the utility power to the generator set.
10. Reconnect the generator set engine starting battery, negative (--) lead last.
5.4.2 Air Cleaner, 10/12RESV/RESVL Models
The engine is equipped with a replaceable, high density paper air cleaner element. See Figure 5-7.
5
4
1. Air cleaner cover lever
2. Air cleaner element
3. Base
4. Blower housing
5. Air cleaner cover
Figure 5-7 Air Cleaner Components
Check the air cleaner daily or before starting the engine. Check for a buildup of dirt and debris around the air cleaner system. Keep this area clean. Also check for loose or damaged components. Replace all bent or damaged air cleaner components.
Note: Operating the engine with loose or damaged air
cleaner components could allow unfiltered air into the engine causing premature wear and failure.
Paper Element Service
Replace the paper element at the intervals indicated in the service schedule. See Figure 5-7 for the air cleaner components.
1. Press the OFF button on the generator set controller.
2. Disconnect the utility power to the generator set.
3. Disconnect the generator set engine starting battery, negative (--) lead first.
1
2
3
tp6515
6. Do not wash the paper element or use pressurized air, as this will damage the element. Replace a dirty, bent, or damaged element. Handle new elements carefully; do not use if the sealing surfaces are bent or damaged.
7. When servicing the air cleaner, check the air cleaner base. Make sure it is secured and not bent or damaged. Also, check the element cover for damage or improper fit. Replace all damaged air cleaner components.
Note: If any loose dirt or debris fell on the air cleaner
base when the element was removed, carefully remove it and wipe the base clean. Be careful that none of it drops into the intake throat.
8. Reinstall the paper element onto the air cleaner base. Make sure the element is flat and properly seated.
9. Position the air cleaner cover with levers outward over air cleaner; turn levers inward to lock.
10. When element replacement is necessary, order genuine Kohler parts.
11. Reconnect the power to the battery charger.
12. Reconnect the generator set engine starting battery, negative (--) lead last.
5.5 Cooling System
The engine fan draws cooling air through the openings in the sides and end near the battery. The alternator fan draws cooling air through openings on the side walls of the enclosure. The cooling air mixes with the engine exhaust and is discharged at the exhaust outlet. See the service view in Section 1.9 for air intake and exhaust locations. To prevent generator set damage caused by overheating, keep the housing cooling inlets and outlets clean and unobstructed at all times.
Note: Do not block the generator set cooling air inlets or
mount other equipment above them. Overheating and severe generator damage may occur.
FRONT VIEW
1
2
4. Rotate the air cleaner cover levers outward to unlock cover; remove the air cleaner cover.
5. Remove the paper element from the base.
1. Air intake
2. Exhaust outlet
Figure 5-8 Cooling Air Intake and Exhaust
TP-6880 10/1466 Section 5 Scheduled Maintenance
5.6 Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.
Carbon monoxide detectors. Carbon monoxide can cause severe nausea, fainting, or death. Install carbon
monoxide detectors on each level of any building adjacent to the generator set. Locate the detectors to adequately warn the building’s occupants of the presence of carbon monoxide. Keep the detectors operational at all times. Periodically test and replace the carbon monoxide detectors according to the manufacturer’s instructions.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
CAUTION
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely hot during operation.
Remove all combustible materials from the exhaust location. Combustible materials include building materials as well as natural surroundings. Keep dry field grass, foliage, and combustible landscaping material a minimum of 1.5 m (5 ft.) from the exhaust outlet.
Periodically inspect the exhaust system components for cracks, leaks, and corrosion.
D Check for corroded or broken metal parts and replace
them as needed.
D Check that the exhaust outlet is clear.
TP-6880 10/14 67Section 5 Scheduled Maintenance
5.7 Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause
blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery short circuits. Explosion can cause severe injury or death. Short circuits can cause bodily injury and/or
equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Refer to this section for general battery information and maintenance. Also consult the battery manufacturer’s instructions for battery maintenance.
All generator set models use a negative ground with a 12-volt engine electrical system. Consult the generator set nameplate for the engine electrical system voltage. Consult the generator spec sheet for battery capacity recommendations for replacement purposes. Wiring diagrams provide battery connection information. See Figure 5-9 for typical battery connections.
1
2
Battery acid cleanup. Battery acid can cause severe injury or death. Battery acid is electrically conductive and
corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with4L(1gal.)ofwaterandmixthe neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke
or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
EZ-273000-J
1. To positive (+) terminal on starter solenoid.
2. To ground (--) terminal on or near starter motor.
Figure 5-9 12-Volt Engine Electrical System Single
Starter Motor, Typical Battery Connection
Clean the battery and cables and tighten battery terminals using theservice schedule recommendations. To prevent corrosion, maintain tight, dry electrical connections at the battery terminals. To remove corrosion from battery terminals, disconnect the cables from the battery and scrub the terminals with a wire brush. Clean the battery and cables with a solution of baking soda and water. After cleaning, flush the battery and cables with clean water and wipe them with a dry, lint-free cloth.
After reconnecting the battery cables, coat the battery terminals with petroleum jelly, silicone grease, or other nonconductive grease.
TP-6880 10/1468 Section 5 Scheduled Maintenance
5.8 Storage Procedure
5.8.3 Cylinder Lubrication
Perform the following storage procedure before removing the generator set from service for three months or longer. Follow the engine manufacturer’s recommendations for storage, if available.
Note: Run the generator set monthly whenever
possible.
5.8.1 Lubricating System
1. Operate the generator set until it reaches operating temperature, or about 15 minutes.
2. Stop the generator set.
3. While the engine is still warm, drain the engine lubrication oil from the engine crankcase.
4. Refill engine crankcase with oil. See Section 5.2.3 for oil recommendations.
5. Run the generator set for a few minutes to distribute the clean oil.
6. Stop the generator set.
1. Remove the spark plugs.
2. Pour one tablespoon of engine oil into each spark plug hole. Install the spark plugs and ground the spark plug leads. Do not connect the leads to the
plugs.
3. Crank the engine two or three revolutions to lubricate the cylinders.
5.8.4 Exterior Preparation
1. Clean the exterior surface of the generator set.
2. Seal all openings in the engine with nonabsorbent adhesive tape.
3. Mask all areas to be used for electrical contact.
4. Spread a light film of oil over unpainted metallic surfaces to prevent rust and corrosion.
5.8.5 Battery
Perform battery storage last.
5.8.2 Fuel System
1. Start the generator set.
2. With the generator set running, shut off the gas supply.
3. Run the generator set until the engine stops.
4. Press the OFF button on the generator set controller.
1. Press the OFF button on the generator set controller.
2. Disconnect the battery, negative (--) lead first.
3. Clean the battery.
4. Place the battery in a warm, dry location.
5. Connect the battery to a float/equalize battery charger, or charge the battery monthly using a trickle charger. Follow the battery charger manufacturer’s recommendations.
TP-6880 10/14 69Section 5 Scheduled Maintenance
Notes
TP-6880 10/1470 Section 5 Scheduled Maintenance
Section 6 Troubleshooting
6.1 Introduction
Use the troubleshooting charts in this section to diagnose and correct common problems. First check for simple causes such as a dead engine starting battery, loose connections, or an open circuit breaker. The charts include a list of common problems, possible causes of the problem, and recommended corrective actions.
If the procedures in this manual do not explain how to correct the problem, contact an authorized Kohler distributor/dealer. Maintain a record of repairs and adjustments performed on the equipment. Use the record to help describe the problem and repairs or adjustments made to equipment.
6.2 USB Port
A USB port is located on the front of the controller. See Figure 1-2 for location. Use a USB cable with a mini-B connector to connect the controller to your personal computer (laptop).
Some controller settings can be adjusted using a laptop computer with Kohlerr SiteTecht software. SiteTech software is available to Kohler authorized distributors and dealers. See TP-6701, SiteTecht Software Operation Manual, for more information.
Identify and correct the cause of the fault condition. Then reset the controller after a fault shutdown. See Section 2.5.4.
6.4 Circuit Protection
If the generator set circuit breaker trips repeatedly, contact an authorized Kohler distributor/ dealer for service.
6.4.1 Controller Internal Circuit Protection
The controller is equipped with internal circuit protection. A fault message, Accy PwrOver Warning or MainPwrOverL Shutdown, is displayed if this internal protection is activated. Press OFF to reset. Contact an authorized Kohler distributor/ dealer for service.
6.4.2 Line Circuit Breaker
The line circuit breaker interrupts the generator output in the event of a fault in the wiring between the generator and the load. If the circuit breaker trips, reduce the load and switch the breaker back to the ON position.
6.4.3 Auxiliary Winding Circuit Breaker
6.3 Fault Messages
The RDC2/DC2 controller displays fault messages to aid in troubleshooting. Selected fault messages and recommended checks are listed in Figure 2-3.
A resettable circuit breaker protects the alternator. The circuit breaker is located in the junction box area. See Figure 1-2.
TP-6880 10/14 71Section 6 Troubleshooting
6.5 Troubleshooting
Figure 6-1 contains generator set troubleshooting, diagnostic, and repair information. Check for loose connections before replacing parts.
Problem Possible Cause Corrective Action
Controller display backlight is off.
Controller displayisoff.
The generator set does not crank.
The generator set cranks but does not start, starts hard, lacks power, or operates erratically.
No AC output.
Low output or excessive drop in voltage.
Generator set stops suddenly.
Backlight turns off after about 1 minute with no activity.
Low or no battery voltage. Check connections.
Battery weak or dead. Recharge or replace the battery. Battery connections reversed or poor. Check the connections. Fault shutdown. Check the controller display for fault messages. See
Generator set in the OFF mode. Press the RUN button to start the engine or press AUTO
Gererator thermostat tripped. For trips other than temperature (nuisance trips), reset
Air cleaner clogged. Clean and/or replace the air cleaner. Battery weak or dead. Recharge or replace the battery. Battery connection poor. Clean and tighten the battery connections. Spark plug wire connection loose. Check the spark plug wires. Low oil pressure shutdown. Check for oil leaks. Check the oil level and add oil if
Fuel pressure insufficient. Check the fuel supply and valves. Engine malfunction. Contact an authorized Kohler distributor/dealer. Gererator thermostat tripped. For trips other than temperature (nuisance trips), reset
Line circuit breaker in the OFF position. Place the circuit breaker in the ON position. Line circuit breaker tripping because of
overload.
Line circuit breaker tripping because of short circuit.
Auxiliary winding circuit breaker tripped. Reset the circuit breaker (located in junction box).
Generator set overloaded. Reduce the load.
Low oil pressure shutdown. Check for oil leaks. Check the oil level and add oil if
Outoffuel. Check fuel supply. Overcrank shutdown. Reset the controller. If the overcrank fault occurs again,
Auxiliary winding circuit breaker tripped. Reset the circuit breaker (located in junction box.)
Fault shutdown. Check the controller display for fault messages. See
Generator set in the OFF mode. Press the RUN button to start the engine or press AUTO
Remote stop command received from a remote switch, ATS, or OnCuer Plus.
Engine malfunction. Contact an authorized Kohler distributor/dealer.
Backlight will turn on when a button is pressed or the generator set starts.
Check generator set battery. See Figure 6-1.
Section 2.5. Correct the fault condition and reset the controller.
to allow remote starting.
the thermostat. See Section 2.6.
necessary.
the thermostat. See Section 2.6.
Reduce the load on the generator set.
Contact an authorized Kohler distributor/dealer for service.
Contact an authorized Kohler distributor/dealer for service if breaker trips repeatedly.
necessary.
contact an authorized Kohler distributor/dealer.
Contact an authorized Kohler distributor/dealer for service if breaker trips repeatedly.
Section 2.5. Correct the fault condition and reset the controller.
to allow remote starting.
Check the remote switch position. Check OnCue Plus.
Figure 6-1 General Troubleshooting Chart
TP-6880 10/1472 Section 6 Troubleshooting
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, amp ampere ABDC after bottom dead center AC alternating current A/D analog to digital ADC advanced digital control;
adj. adjust, adjustment ADV advertising dimensional
Ah amp-hour AHWT anticipatory high water
AISI American Iron and Steel
ALOP anticipatory low oil pressure alt. alternator Al aluminum ANSI American National Standards
AO anticipatory only APDC Air Pollution Control District API American Petroleum Institute approx. approximate, approximately APU Auxiliary Power Unit AQMD Air Quality Management District AR as required, as requested AS as supplied, as stated, as
ASE American Society of Engineers ASME American Society of
assy. assembly ASTM American Society for Testing
ATDC after top dead center ATS automatic transfer switch auto. automatic aux. auxiliary avg. average AVR automatic voltage regulator AWG American Wire Gauge AWM appliance wiring material bat. battery BBDC before bottom dead center BC battery charger, battery
BCA battery charging alternator BCI Battery Council International BDC before dead center BHP brake horsepower blk. black (paint color), block
blk. htr. block heater BMEP brake mean effective pressure bps bits per second br. brass BTDC before top dead center Btu British thermal unit Btu/min. British thermal units per minute C Celsius, centigrade cal. calorie CAN controller area network CARB California Air Resources Board CAT5 Category 5 (network cable) CB circuit breaker CC crank cycle cc cubic centimeter CCA cold cranking amps ccw. counterclockwise CEC Canadian Electrical Code cert. certificate, certification, certified cfh cubic feet per hour
analog to digital converter
drawing
temperature
Institute
Institute (formerly American Standards Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
cfm cubic feet per minute CG center of gravity CID cubic inch displacement CL centerline cm centimeter CMOS complementary metal oxide
com communications (port) coml commercial Coml/Rec Commercial/Recreational conn. connection cont. continued CPVC chlorinated polyvinyl chloride crit. critical CSA Canadian Standards
CT current transformer Cu copper cUL Canadian Underwriter’s
CUL Canadian Underwriter’s
cu. in. cubic inch cw. clockwise CWC city water-cooled cyl. cylinder D/A digital to analog DAC digital to analog converter dB decibel dB(A) decibel (A weighted) DC direct current DCR direct current resistance deg., degree dept. department dia. diameter DI/EO dual inlet/end outlet DIN Deutsches Institut fur Normung
DIP dual inline package DPDT double-pole, double-throw DPST double-pole, single-throw DS disconnect switch DVR digital voltage regulator
2
E
PROM, EEPROM
E, emer. emergency (power source) ECM electronic control module,
EDI electronic data interchange EFR emergency frequency relay e.g. for example (exempli gratia) EG electronic governor EGSA Electrical Generating Systems
EIA Electronic Industries
EI/EO end inlet/end outlet EMI electromagnetic interference emiss. emission eng. engine EPA Environmental Protection
EPS emergency power system ER emergency relay ES engineering special,
ESD electrostatic discharge est. estimated E-Stop emergency stop etc. et cetera (and so forth)
substrate (semiconductor)
Association
Laboratories
Laboratories
e. V. (also Deutsche Industrie Normenausschuss)
electrically-erasable programmable read-only memory
engine control module
Association
Association
Agency
engineered special
exh. exhaust ext. external F Fahrenheit, female FHM flat head machine (screw) fl. oz. fluid ounce flex. flexible freq. frequency FS full scale ft. foot, feet ft. lb. foot pounds (torque) ft./min. feet per minute ftp file transfer protocol ggram ga. gauge (meters, wire size) gal. gallon gen. generator genset generator set GFI ground fault interrupter
GND, gov. governor gph gallons per hour gpm gallons per minute gr. grade, gross GRD equipment ground gr. wt. gross weight H x W x D height by width by depth HC hex cap HCHT high cylinder head temperature HD heavy duty HET high exhaust temp., high
hex hexagon Hg mercury (element) HH hex head HHC hex head cap HP horsepower hr. hour HS heat shrink hsg. housing HVAC heating, ventilation, and air
HWT high water temperature Hz hertz (cycles per second) IBC International Building Code IC integrated circuit ID inside diameter, identification IEC International Electrotechnical
IEEE Institute of Electrical and
IMS improved motor starting in. inch in. H in. Hg inches of mercury in. lb. inch pounds Inc. incorporated ind. industrial int. internal int./ext. internal/external I/O input/output IP internet protocol ISO International Organization for
J joule JIS Japanese Industry Standard k kilo (1000) Kkelvin kA kiloampere KB kilobyte (2 KBus Kohler communication protocol kg kilogram
ground
engine temp.
conditioning
Commission
Electronics Engineers
O inches of water
2
Standardization
10
bytes)
TP-6880 10/14 Appendix 73
2
kg/cm
kgm kilogram-meter kg/m
kilograms per square centimeter
3
kilograms per cubic meter kHz kilohertz kJ kilojoule km kilometer kOhm, kkilo-ohm kPa kilopascal kph kilometers per hour kV kilovolt kVA kilovolt ampere kVAR kilovolt ampere reactive kW kilowatt kWh kilowatt-hour kWm kilowatt mechanical kWth kilowatt-thermal L liter LAN local area network L x W x H length by width by height lb. pound, pounds
3
lbm/ft
pounds mass per cubic feet LCB line circuit breaker LCD liquid crystal display LED light emitting diode Lph liters per hour Lpm liters per minute LOP low oil pressure LP liquefied petroleum LPG liquefied petroleum gas LS left side L
wa
LWL low water level
sound power level, A weighted
LWT low water temperature m meter, milli (1/1000) M mega (10
3
m
3
m
3
m
units), male
cubic meter
/hr. cubic meters per hour /min. cubic meters per minute
6
when used with SI
mA milliampere man. manual max. maximum MB megabyte (2
20
bytes) MCCB molded-case circuit breaker MCM one thousand circular mils meggar megohmmeter MHz megahertz mi. mile mil one one-thousandth of an inch min. minimum, minute misc. miscellaneous MJ megajoule mJ millijoule mm millimeter mOhm, mmilliohm MOhm, Mmegohm MOV metal oxide varistor MPa megapascal mpg miles per gallon mph miles per hour MS military standard ms millisecond m/sec. meters per second mtg. mounting MTU Motoren-und Turbinen-Union MW megawatt mW milliwatt F microfarad N, norm. normal (power source) NA not available, not applicable nat. gas natural gas NBS National Bureau of Standards
NC normally closed NEC National Electrical Code NEMA National Electrical
NFPA National Fire Protection
Manufacturers Association
Association Nm newton meter NO normally open no., nos. number, numbers NPS National Pipe, Straight NPSC National Pipe, Straight-coupling NPT National Standard taper pipe
thread per general use NPTF National Pipe, Taper-Fine NR not required, normal relay ns nanosecond OC overcrank OD outside diameter OEM original equipment
manufacturer OF overfrequency opt. option, optional OS oversize, overspeed OSHA Occupational Safety and Health
Administration OV overvoltage oz. ounce p., pp. page, pages PC personal computer PCB printed circuit board pF picofarad PF power factor ph., phase PHC Phillipsr head Crimptiter
(screw) PHH Phillipsr hex head (screw) PHM pan head machine (screw) PLC programmable logic control PMG permanent magnet generator pot potentiometer, potential ppm parts per million PROM programmable read-only
memory psi pounds per square inch psig pounds per square inch gauge pt. pint PTC positive temperature coefficient PTO power takeoff PVC polyvinyl chloride qt. quart, quarts qty. quantity R replacement (emergency)
power source rad. radiator, radius RAM random access memory RBUS RS-485 proprietary
communications RDO relay driver output ref. reference rem. remote Res/Coml Residential/Commercial RFI radio frequency interference RH round head RHM round head machine (screw) rly. relay rms root mean square rnd. round RO read only ROM read only memory rot. rotate, rotating rpm revolutions per minute RS right side RTDs Resistance Temperature
Detectors
RTU remote terminal unit RTV room temperature vulcanization RW read/write SAE Society of Automotive
Engineers scfm standard cubic feet per minute SCR silicon controlled rectifier s, sec. second SI Systeme international d’unites,
International System of Units SI/EO side in/end out sil. silencer SMTP simple mail transfer protocol SN serial number SNMP simple network management
protocol SPDT single-pole, double-throw SPST single-pole, single-throw spec specification specs specification(s) sq. square sq. cm square centimeter sq. in. square inch SMS short message service SS stainless steel std. standard stl. steel tach. tachometer TB terminal block TCP transmission control protocol TD time delay TDC top dead center TDEC time delay engine cooldown TDEN time delay emergency to
normal TDES time delay engine start TDNE time delay normal to
emergency TDOE time delay off to emergency TDON time delay off to normal temp. temperature term. terminal THD total harmonic distortion TIF telephone influence factor tol. tolerance turbo. turbocharger typ. typical (same in multiple
locations) UF underfrequency UHF ultrahigh frequency UIF user interface UL Underwriter’s Laboratories, Inc. UNC unified coarse thread (was NC) UNF unified fine thread (was NF) univ. universal URL uniform resource locator
(web address) US undersize, underspeed UV ultraviolet, undervoltage Vvolt VAC volts alternating current VAR voltampere reactive VDC volts direct current VFD vacuum fluorescent display VGA video graphics adapter VHF very high frequency Wwatt WCR withstand and closing rating w/ with WO write only w/o without wt. weight xfmr transformer
TP-6880 10/1474 Appendix
TP-6880 10/14
E 2014 by Kohler Co. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044 Phone 920-457-4441, Fax 920-459-1646
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
For the nearest KOHLER authorized installation, service, and sales dealer in the US and Canada: Call 1-800-544-2444 or visit KOHLERPower.com
Loading...