Klaxon IS-XN User Manual


The Syrex IS
-XN beacon is CE marked for
European EMC Directive 89/336/EEC

compliance with the European Explosive
Atmospheres Directive 94/9/EC and the
1. INTRODUCTION
The Syrex IS-XN is an ATEX certified intrinsically safe beacon which will produce a visual warning in a hazardous area. Red, Amber, Green and Blue output models are available.
2. DESCRIPTION
The device will start to flash when power is applied to terminals + and -. The beacon has two flash rates one double flash per second and two double flashes per second. The flash rate is selected by setting an internal pin header. The unit is factory set to produce two double flashes per second.
3. SUPPLY VOLTAGE
The Syrex IS-XN beacon has been designed to operate in a hazardous area via a 28V 300 ohm ATEX certified Zener barrier or galvanic isolator. The beacon may be tested or used in safe areas without a Zener barrier or galvanic isolator, but at supply voltages above 16V the internal current limit will function and the brightness may be reduced. The beacon should not be continuously operated without a barrier or isolator with a supply voltage greater than 16V.
4. INTRINSIC SAFETY CERTIFICATION
4.1 ATEX certificate
The Syrex IS-XN beacon complies with the following standards:-
EN50014 : 1997 + A1 and A2 EN50020 : 2002 EN50284 : 1999
II 1G EEx ia IIC T4 (-40ºC <= Ta <= +60ºC)
The EC-Type Examination Certificate SIRA 05ATEX2269X has been issued by the Notified Body Sira. This confirms compliance with the European ATEX Directive 94/9/EC for Group II, Category 1G equipment. The beacon carries the Community Mark and subject to local codes of practice, may be installed in any of the EEA member countries.
_______________________________________________________________________________________________________________________________ Klaxon Signals Ltd. Wrigley Street, Oldham, Lancashire UK OL4 1HW sales@klaxonsignals.com Tel: +44 (0)161 287 5555
www.klaxonsignals.com Fax: +44 (0)161 287 5511 Document No. Klaxon Syrex IS-XN Issue: A 11-11-05 Sheet 1 of 3

This instruction sheet describes installations which conform to BS EN 60079:Part14:2003 Electrical Installation in Hazardous Areas. When designing systems for installation outside the UK, the local Code of Practice should be consulted.
Enclosure: ABS Plastic Lens: Polycarbonate
1) The certification marking is as follows:
Syrex IS-XN Beacon
II 1G EEx ia IIC T4 (-40ºC <=Ta<= +60°C)
Ui = 28V Pi = 1.2W
SIRA 05ATEX2269X
WARNING:
Klaxon Signals Ltd.
2) The equipment may be used in zones 0, 1 and 2 with flammable gases and vapours with apparatus groups IIA, IIB & IIC and with temperature classes T1, T2, T3 and T4.
3) The equipment is only certified for use in ambient temperatures in the range -40oC to +60oC and should not be used outside this range.
4) The certificate number has an ‘X’ suffix, which indicates that the certificate contains one of more special conditions for safe use. Those installing or inspecting the equipment should refer to this section of the certificate.
5) The equipment has not been assessed as a safety­related device (as referred to by Directive 94/9/EC Annex II, clause 1.5).
6) Installation of this equipment shall be carried out by suitably-trained personnel in accordance with the applicable code of practice.
7) Repair of this equipment shall only be carried out by the manufacturer or in accordance with the applicable code of practice.
8) The certification of this equipment relies on the following materials used in its construction:
If the equipment is likely to come into contact with aggressive substances, then it is the responsibility of the user to take suitable precautions that prevent it from being adversely affected, thus ensuring that the type of protection is not compromised.
“Aggressive substances” - e.g. acidic liquids or gases that may attack metals, or solvents that may affect polymeric materials.
“Suitable precautions” - e.g. regular checks as part of routine inspections or establishing from the material’s data sheet that it is resistant to specific chemicals.
Ci = 0 Li = 0
Year / Serial No. 05 / 6MB000001
TO AVOID A POSSIBLE ELECTROSTATIC
CHARGE ONLY CLEAN WITH A DAMP CLOTH
Oldham OL4 1HW. UK. www.klaxonsignals.com
0518
SPECIAL CONDITIONS FOR SAFE USE (as stated in the EC Type Examination Certificate SIRA 05ATEX2269X)
'O' Ring Seal
Conditions for Syrex IS-XN Beacon
The equipment has an ingress protection rating of IP65. However, if it has been supplied without cable entry devices, then the user shall ensure that the devices that are fitted will provide an ingress protection that is appropriate to the environment in which it is installed i.e. IP20 or better. If only
Input Terminals
Flash Rate Header Pins
Syrex IS-XN
Beacon
+ -
2Hz 1Hz Flash Rate
one of the two cable entries are used, then the unused entry 'knockout' shall be left intact or fitted with a blanking device that ensures ingress protection appropriate to the environment in which it is installed i.e. IP20 or better.
The equipment shall not be directly installed in any process where its enclosure might be electro-statically charged by the rapid flow of a non-conductive media.
4.2 Zones, Gas Groups and T Rating The Syrex IS-XN beacon has been certified EEx ia IIC T4. When connected to an approved system it may be installed in:
Zone 0 explosive gas air mixture
continuously present.
Zone 1 explosive gas air mixture likely to occur in
normal operation.
Zone 2 explosive gas air mixture not likely to occur,
and if it does, it will only exist for a short time.
Be used with gases in groups:
Group A propane Group B ethylene
Group C hydrogen
Having a temperature classification of:
T1 450ºC T2 300ºC T3 200ºC T4 135ºC
4.3 Terminals + and - power supply
Power is supplied to the beacon via terminals + and - which have maximum input safety parameters of:
Ui = 28V
Fig 1 Location of field terminals and controls.
5. INSTALLATION
In addition to the certification requirements shown in section
4.2, the environmental conditions must be within the limits shown on the product specification. The beacon enclosure provides IP65 protection and is suitable for installation in an exterior location if an appropriate sealed cable entry is used. Syrex IS-XN beacons should only be installed by trained competent personnel.
5.1 Mounting The Syrex IS-XN beacon may be secured to any flat surface by inserting two mounting screws through the back of the round base (see figure 2). The enclosure provides IP65 protection and is suitable for installation in exterior locations provided that the area around the two mounting screws through the back of the base moulding has been sealed and that suitable cable glands with the required IP rating have been used. The lens should be aimed towards the area where maximum visibility is required.
5.2 Installation procedure
a. Unscrew the beacon unit security screw and remove
the beacon section from the base by turning it anti­clockwise. Ensure that the ‘O’ ring seal remains in place.
b. Remove the required 20mm knockout section(s)
depending on system wiring and mount the base to a flat surface by inserting two screws through the back of the base.
c. Fit the required number of 20mm cable glands or
conduit entries into the base and connect the field wiring to the appropriate beacon terminals as shown in section 6 and Fig 1 of this manual.
d. Check that the ‘O’ ring seal is correctly located on the
beacon section (see Fig. 1) and insert the beacon section into the base. Push it fully home and turn it clockwise to align the mouldings before tightening the security screw.
Pi = 1.2W
Ci = 0 Li = 0
Fit mounting screws through base
20mm knockouts
Syrex IS-XN beacons may be powered from ATEX certified Zener barriers or galvanic isolators certified by an EC Approved Body which have output parameters equal to or less than 28V and 1,2W
Up to three Syrex IS-XN beacons can be connected in parallel and be powered from a common barrier or isolator. Parallel connection of beacons will significantly reduce the brightness of each device.
The maximum permitted cable parameters defined by the barrier or isolator certificate must not be exceeded.
_______________________________________________________________________________________________________________________________ Klaxon Signals Ltd. Wrigley Street, Oldham, Lancashire UK OL4 1HW sales@klaxonsignals.com Tel: +44 (0)161 287 5555
www.klaxonsignals.com Fax: +44 (0)161 287 5511 Document No. Klaxon Syrex IS-XN Issue: A 11-11-05 Sheet 2 of 3