Klaxon Inferno Installation Instruction

Option: Multiple units
Multiple units can be attached together forming either a semi circle or a full circle. The Semi-circle
unit can be mounted
either on the wall or the ceiling while the Omni ve
rsion works best hanging from the ceiling.
INSTALLATION INSTRUCTIONS
1
2
QUICK INSTALLATION
Indusec makes no representation that this product will prevent personal injury or property loss or that the product will in all cases provide adequate warning or protection. Purchaser should understand that a properly installed and maintained a
larm system may only reduce the
risk of a burglary, robbery or fire without warning
, but the alarm is not insurance or a guarantee tha
t such will not occur or that there will
be no personal injury or property loss as a result. THEREFORE, INDUSEC, SHALL NOT BE LIABLE FOR ANY CO
NSEQUENTIAL
OR INCIDENTAL DAMAGES IN CONNECTION WITH THE USE, I
NSTALLATION AND/OR MAINTENANCE OF THE PRO-
DUCT. Including, but not limited to the liability for any property demage, bodily injury, ot other los
s based on a claim that the product
failed to give warning, or any cost of expense of providing substitute equipment or service during per
iods of malfunction, nonuse or main-
tenence. In no event shall the liability of Indusec
exceed the purchase price of the product.
- Test is recommended.
- The unit should be charged 6 h before use.
The Inferno Sound Barrier is intended for professio
nal use only and should be handled and installed by
author-
ized installers.
- Do not connect the unit to other supplies than 12
(12-16) V DC.
- It will not work properly before the unit has been charged for 6 hours.
- The battery must be changed every third year.
- While dealing with the PCB’s inside the unit, pre
cautions must be observed for handling electrostati
c dis-
charge sensitive devices.
- It´s recommended to use earplugs when installing
Tools needed:
- Screwdriver
- Torx wrench
- Screws and drill for mounting the unit
In the interest of improving internal design, opera
tional function, and/or reliability, Indusec reserves the right to make changes to the products described in this document without notice.
Indusec does not assume any liability that may occu
r due to the use or application of the product(s) o
r circuit layout(s) described herein.
Copyright Klaxon Signals Ltd — all rights reserved
2) MOUNTING
www.klaxonsignals.com
3) CONNECTION AND SETUP
5) TEST
We recommend testing the unit either before mounting or during assembling.
Without a connected Tamper loop it is only necessary to connect the two PCB’s, the battery and power.
Test procedure (The battery will need about 20 minutes to charge before testing.);
1. Set Dip switch 3 to ON position.
2. Activate either Trigger signal.
3. The unit should generate four short different-pitched sound signals indicating that the unit works.
4. Switch off the Trigger signal.
5. Set Dip switch 3 to OFF position. (Normal operation mode)
6. The test is complete.
6) SPECIFICATIONS
Coverage Up to 150 cubic meters (60 square meters x 2.5)
Electrical interface
Power Supply 12 – 16 V DC, < 150 mA Activation Signals Trig ( - ): 0 – 0.5 V, (10 mA) Trig ( + ): 9 – 18 V, (10 mA) Cables 0.25 – 1.0 square mm, ( AWG 22 – 18 )
Battery 9.6 V Ni-MH, NI-MH batteries performance is improved if charged/discharged. Capacity 1800 mAh, (sufficient for 30 minutes continuous alarm) Charge time The unit should be charged 6 hours before use. Standby w/o battery charge 1 month Life time 3 years, then it has to be replaced
Sound output 125-127 ± 1 dB(A) @ 1m, user selectable Output frequency 2—5 kHz
Option: Tamper
The tamper loop is an extra mechanical security protection. It is not needed for the function of the siren.
The tamper loop consists of a series connection that enters at the Connector at SAB IN goes through the microswitch at the end of the board, runs through the CPU board through the middle connector to the speaker board through the mi­croswitch on that very end and back to the Connector at SAB OUT.
The loop can contain other normally-closed switches such as magnetic contacts or mercury tilt switches in the alarm set­up.
3
4
4) ASSEMBLING THE UNIT
1. Before applying power to the unit, ensure that Dip switch 3 is in the ON position = Test mode.
2. Assemble the two PCB’s and the battery. Attach the battery cable to the connector.
3. Power can now be applied.
4. Set Dip switch 1 to ON. A red LED on the CPU circuit board should light up.
5. Dip switch 1 can be in either in ON or OFF mode.
6. Set the Dip switch 3 to OFF = Normal mode. Attach the grid and the two end caps.
7. The Inferno is assembled and ready for use.
1. Charging Indication ON = A red light will lit when charging. OFF = No indication when charging. (default)
2. Delay between received trigger signal and the alarm soun­ding. ON = 30 s OFF = 0 s (default)
3. Test Mode ON = Test mode, four short different-pitched sound signals. OFF = Normal mode (default)
4. Alarm Signal Length ON = Infinite alarm OFF = 3 min, after a new trig is needed (default)
5. Reserve
6. Fixed Alarm Signal Length ON = 45 s OFF = Normal mode (default)
7. Sound level ON = 127 ± 1 dB(A) @ 1m. 20 s and then 124 ± 1 dB(A) @ 1m. NOTE! Very high sound level. OFF = 125 ± 1 dB(A) @ 1m (default)
8. Automatic Battery Check ON = Bad battery signal on pin 7 on Connector, see below OFF = Led flash => Bad battery (default)
DIP SWITCH
GND = Ground TRG OUT = Bad battery signal, see below TRG + = Positive activation TRG - = Negative activation 12 V IN = Charge +12 V DC
9.6 V OUT = Reserve SAB OUT = Tamper out SAB IN = Tamper in
Bad battery signal
- Dip switch: 8 ON
- Connector: pin 7 and 8 (TRG OUT and GND)
CONNECTOR
www.klaxonsignals.com
In the interest of improving internal design, operational function, and/or reliability, Klaxon Signals Ltd reserves the right to make changes to the products described in this document without notice.
Klaxon Signals Ltd does not assume any liability that may occur due to the use or application of the product(s) or circuit layout(s) described herein.
18-185454/4
Copyright Indusec eserved