Klaxon 18-980666, 18-980623, 18-980622, 18-980665, 18-980589 User Manual

...
EN DE
FR
NL ES
Nexus 110 DC Sounder & Sounder-Beacon
Installation Instructions
one Tone Type Tone Description / Application Dip Switch 3rd Stage Peak Sound Sounder
T
S1/S2) Tone Level (dBA@1m) Current (mA Avg)
(
1. 970Hz (BS5839-1:2002) O-O-O-O-O-O 18 110 45 . 800Hz/970Hz @ 2Hz (BS5839-1:2002) O-O-O- O-O -I 1 110 44
2
. 800Hz – 970Hz @ 1Hz (BS5839-1:2002) O-O-O- O-I -O 1 110 43
3
. 970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002) O- O-O -O - I- I 1 110 25
4
. 970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002) O -O- O-I-O-O 1 110 39
5
. 554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32 001 ) O-O -O - I- O-I 1 107 24
6
7. 500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000) O-O -O - I- I-O 1 110 28
8. 420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone) O - O - O -I-I-I 1 105 9
9. 500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia AS1670 Evacuation tone) O-O-I- O-O -O 1 110 13
10. 550Hz/440Hz @ 0.5Hz O-O -I - O- O-I 19 107 26
1. 970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone) O- O-I -O- I- O 1 110 19
1
2. 2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone) O-O - I - O - I - I 1 112 16
1
3. 1200Hz – 500Hz @ 1Hz (DIN 33 404) O-O -I - I- O-O 1 110 34
1
4. 400Hz O - O - I -I-O-I 18 105 21
1
5. 550Hz, 0.7s/1000Hz, 0.33s O - O - I -I-I-O 1 111 33
1
16. 1500Hz – 2700Hz @ 3Hz (Vandal Alarm) O - O - I - I - I - I 1 116 46
17. Simulated Bell O-I-O- O-O -O 1 112 26
18. 840Hz O-I -O - O- O-I 1 113 34
19. 660Hz O-I -O - O- I-O 10 109 31
0. 660Hz 1.8s ON/1.8s OFF O - I - O -O-I-I 19 108 16
2
1. 660Hz 0.15s ON/0.15s OFF O-I -O - I- O-O 19 107 17
2
2. 510Hz, 0.25s/ 610Hz, 0.25s O - I - O -I-O-I 1 107 28
2
3. 800/1000Hz 0.5s each (1Hz) O - I - O - I -I-O 1 111 44
2
24. 250Hz – 1200Hz @ 12Hz O - I - O - I - I - I 1 105 24
25. 500Hz – 1200Hz @ 0.33Hz. O- I-I -O - O- O 1 110 31
6. 2400Hz – 2900Hz @ 9Hz O- I - I - O - O - I 1 116 45
2
27. 2400Hz – 2900Hz @ 3Hz O - I - I -O-I-O 1 116 45
28. 800Hz – 970Hz @ 100Hz O - I - I - O - I - I 1 110 42
9. 800Hz – 970Hz @ 9Hz O - I - I -I-O-O 1 110 43
2
30. 800Hz – 970Hz @ 3Hz O - I - I - I - O - I 1 110 43
31. 800Hz, 0.25s ON/1s OFF O - I - I - I - I - O 1 108 10
32. 500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220) O - I - I - I - I - I 1 110 29
33. 340Hz I-O-O- O-O -O 1 106 18
34. 1000Hz I-O -O - O- O-I 18 111 47
35. 1400Hz – 1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265) I-O -O - O- I-O 1 110 44
36. 660Hz 6.5s ON/13s OFF I - O - O - O - I - I 19 108 31
37. 1000Hz/2000Hz, 1s each I- O-O -I - O- O 1 113 41
38. 720Hz, 0.7s ON/0.3s OFF I - O - O -I-O-I 1 106 26
39. 970Hz, 0.25s ON/OFF I - O - O - I - I -O 1 110 25
40. 2800Hz, 1s ON/OFF I - O - O - I - I - I 1 113 22
41. 2800Hz 0.25s ON/OFF I-O -I - O- O-O 1 113 21
42. 2400/2900 @ 2Hz I - O - I -O-O-I 1 115 43
43. Chime, 554Hz/440Hz Single shot ‘ding dong’ I - O - I -O-I-O1 104 15
44. Chime, 554Hz/440Hz Repeating ‘ding dong’ I - O - I - O - I - I 1 107 15
45. Chime, 970Hz/800Hz Single shot ‘ding dong’ I- O - I - I-O-O 1 106 36
46. Chime, 970Hz/800Hz Repeating ‘ding dong’ I - O - I - I - O - I1 106 36
47. Hooter, Repeating I - O - I - I - I - O 1 107 13
48. Gentle alarm - Tone 2, rises slowly to full volume over 30s I - O - I - I - I - I 1 109 44
49. Time-Out Alarm – As Tone 2, cuts off after 10 mins I-I -O - O- O-O 1 109 44
50. Time-Out Alarm – As Tone 2, cuts off after 2 mins I - I - O -O-O-I 1 109 44
51. 750Hz 0.33s ON/0.51s OFF I - I - O - O - I - O 1 106 12
52. 750Hz 0.51s ON/0.33s OFF I - I - O - O - I - I 1 107 25
53. 550Hz, 0.33s/1000Hz, 0.7s I - I - O -I-O-O 1 111 41
54. 600Hz – 900Hz/ 0.9s I - I - O - I - O - I 1 109 37
55. 660Hz – 680Hz/ 0.9s I - I - O - I - I - O 1 105 33
56. 670Hz – 725Hz/ 0.9s I - I - O - I - I - I 1 107 33
57. 920Hz – 750Hz/ 0.9s I - I - I -O-O-O 1 110 41
58. 700Hz - 900Hz, 0.3s/0.6s OFF I - I - I - O - O - I 1 109 15
59. 900Hz - 760Hz, 0.6s/0.3s OFF I - I - I - O - I - O 1 110 28
60. 750Hz I - I - I - O - I - I 18 107 39
61. Power Only – Use with Stage 3 control for manual/intermittent chime triggering I - I - I - I - O - O 43
62. Power Only – Use with Stage 3 control for manual/intermittent chime triggering I - I - I - I - O - I 43
63. Power Only – Use with Stage 3 control for manual/intermittent horn triggering I - I - I - I - I - O 47
64. Reserved for future use I - I - I - I - I - I
EN54-3 Fire Alarm Device – Sounder Type B: For indoor or outdoor use 18-980544/555/556/660/662/589/622/623/664/665/666 Technical Data: Document 18-186529
Klaxon Signals Ltd, Oldham, OL4 1HW, UK Phone +44 161 287 5555 Fax +44 161 287 5511 E-mail sales@klaxonsignals.com
0832
07
0832-CPD-0618 (Sounder-LED Beacon) 0832-CPD-0619 (Sounder-Xenon Beacon) 0832-CPD-0620 (Sounder)
Issue 6 (January 2008) 18-186458
Copyright © Klaxon Signals Ltd
www.klaxonsignals.com
From Controller To Next Unit
1st Stage 2nd Stage 3rd Stage
Beacon
Sounder
+
-
+
-
1st Unit 2nd Unit
Nexus 110 DC Sounder & Sounder-Beacon
Installation Instructions
EN
Installation Manual
Installation
a. The sounder is installed by first mounting the base unit and making the
external wring connections to the base. The head unit then automatically connects when it is attached to the base.
b. The sounder head is separated from the base by unlocking the four
¼-turn fasteners in the corners of the sounder. (Recommended screwdriver: Philips No. 2, min 100mm long).
c. Note that the head only fits onto the base one way around. If a beacon
is fitted, care should be taken when mounting the base to ensure that the beacon will be positioned in the desired orientation after the sounder is attached
Wiring
The sounder and beacon have separate wiring terminals. Each terminal is duplicated to enable simple ‘daisy-chain’ connection of multiple units.
Line Terminal Marking
Sounder Positive Supply (10 to 60V DC)
Sounder Negative Supply (0V)
2nd Stage Alarm Control (Connect to 0V to activate)
3rd Stage Alarm Control (Connect to 0V to activate)
Beacon Positive Supply (10 to 60V DC)
Beacon Negative Supply (0V)
Controls
a. Tone Selection
The first and second stage alarm tones are independently set using 6-way dipswitches S1 and S2 respectively. The required settings are shown in the table overleaf. The third stage alarm tone is pre-set to complement the selected first stage tone as shown in the table.
b. Volume Control
The sound output of the unit can be reduced by up to 20dBA by adjusting the potentiometer.
c. Beacon Flash Controls (If fitted)
The flash mode of the beacon can be altered using the 2-way dipswitch marked
+
-
S2
S3
+
-
XENON BEACON LED BEACON
Switch Off On Off On
1 60 flashes per min 30 flashes per min Single Flash Double Flash
2 Single Flash Double Flash Flashing Static
Technical Specification:
Supply Voltage Range 10-60V DC
Current – Sounder 10-50mA* (Typ. 45mA @ 24V, Tone 1)
Current –Beacon Xenon - 250mA Average, 700mA Peak*,
(Where fitted) LED - 18mA (Flashing) or 65mA (Static)*
Peak Sound Level 104-116 dBA at 1m*
(Typ. 110dBA @ 24V, Tone1)
Number of Tones 64
Volume Control 20dBA typical
Remote Tone Switching Provision for 3 alarm stages
(Negative voltage activation)
Operating Temperature - 25°C to +70°C
Casing High Impact Polycarbonate/ABS
IP Rating IP66
Synchronisation Automatic with Klaxon Nexus and
Sonos Sounders
*depends on selected tone and input voltage. See tone table for details.
EN54-3 certified on tones 1,2,3,6,7 & 13 & > 17V DC only.
The European directive “Waste Electrical and Electronic Equipment” (WEEE) aims to minimise the impact of electrical and electronic equipment waste on the environment and human health. To conform with this directive, electrical equipment marked with this symbol must not be disposed of in European public disposal systems. European users of electrical equipment must now return end-of-life equipment for disposal. Further information can be found on the following website: http://www.recyclethis.info/.