Kidde Firex Duct Detector Accessories English Owner's Manual

PRODUCT DESCRIPTION
The remote accessory is available with only the single gang remote indicator/control (591 Series), or with the addition of a single gang strobe assembly (592 Series), or as an optional field upgrade kit for existing installed 591 Series (593 Series). All versions are compatible with standard Decora style cover plates (base color choice plate included).
The indicator/control assembly provides
• Visual indication of detector Pilot, Trouble and Alarm Functions
• Selectable audible indication of Alarm, Trouble or both
• Lamp/Buzzer test function
• Key-Operated detector Test and Reset functions
• Lever-operated “No-Tools” terminal block
• Port for plugging in Strobe Assembly
The strobe assembly provides visual indication of alarm conditions, and is connected to the indicator/control assembly via the provided connector (observing connector polarity).
**
NOTE: The strobe and audible buzzer features are not ADA
compliant, and not intended for life safety notification or evacuation purposes (public mode). These functions are for duct smoke detector status indication only (private mode).
STROBE CONNECTION
To install the Strobe module, simply plug the provided con­nector onto the pins as indicated on the rear of the indica­tor/control module. Snap the strobe lens into the cover plate, and install cover plate following completion of remote module wiring.
AUDIBLE BUZZER CONFIGURATION
There are two jumpers located on the rear of the indicator/control assembly. To enable audible buzzer operation for Alarm or Trouble conditions, simply leave the jumpers in place. To disable either or both functions, remove the appropriate jumper(s).
SILENCE AND RINGBACK FUNCTIONS
On the occasion where an audible alarm or trouble condition needs to be silenced while the detector condition is inspected and remedied, the indicator/control module provides a silence function. The slide switch located on the front of the module is pushed DOWN to activate the silence function.
Upon correction of the notified condition, the silenced buzzer will resume sounding. This the ringback feature which serves as a reminder to reset the silence switch to the “normal”, UP position.
Note that the strobe module, when used, will not stop operating when the silence function is engaged.
DUCT SMOKE DETECTOR REMOTE ACCESSORY
INSTALLATION GUIDE
191 E. North Avenue Carol Stream, IL 60188 USA
Tech. Service Phone: +1 800 445 8299 • E-mail: technicalservice@invensys.com • www.invensys.com
INST APD0340 A060829
A COPY OF THESE INSTRUCTIONS SHOULD BE LEFT WITH THE EQUIPMENT UNTIL INSTALLATION BY ALL TRADES IS FULLY COMPLETE.
FOLLOWING FINAL INSPECTION, A COPY SHOULD BE LEFT WITH THE OWNER/USER.
NOTICE: The information contained in this document is the most current available at the time of shipment of accompanying product, and is subject to change without notice. Future references should always be made to the most current revision of this document. The information contained in all this document should be considered before installing or using the product. Any example applications shown are subject to the most cur­rent enforced local/national codes, standards, approvals, certifications, and/or the authority having jurisdiction. All of these resources, as well as the specific manufacturer of any shown or mentioned related equipment, should be consulted prior to any implementation. For further information or assistance concerning this product, contact Invensys. Invensys reserves the right to change any and all documentation without notice.
© Invensys Climate Controls Americas 2006
AVAILABLE ACCESSORIES FOR USE WITH
FIREX
®
DUCT SMOKE DETECTORS
REMOTE ACCESSORIES
591 Series Remote Accessory Controllers
591W Remote Indicator/Control Assembly w/ White Single Gang Cover Plate
591R Remote Indicator/Control Assembly w/ Red Single Gang Cover Plate
591S Remote Indicator/Control Assembly w/ Stainless Steel Single Gang Cover Plate
592 Series Remote Accessory Controllers with Strobe
592WC Remote Indicator/Control Assembly w/ Strobe Assembly (Clear Lens); White Double Gang Cover Plate
592WO Remote Indicator/Control Assembly w/ Strobe Assembly (Opaque Lens); White Double Gang Cover Plate
592RC Remote Indicator/Control Assembly w/ Strobe Assembly (Clear Lens); Red Double Gang Cover Plate
592RO Remote Indicator/Control Assembly w/ Strobe Assembly (Opaque Lens); Red Double Gang Cover Plate
592SC Remote Indicator/Control Assembly w/ Strobe Assembly (Clear Lens); Stainless Steel Double Gang Cover Plate
592SO Remote Indicator/Control Assembly w/ Strobe Assembly (Opaque Lens); Stainless Steel Double Gang Cover Plate
593 Series Remote
Accessory Strobes (as an optional field upgrade kit for existing installed 591 Controllers)
593RC Strobe Assembly (Clear Lens); Red Double Gang Cover Plate
593RO Strobe Assembly (Opaque Lens); Red Double Gang Cover Plate
593SC Strobe Assembly (Clear Lens); Stainless Steel Double Gang Cover Plate
593SO Strobe Assembly (Opaque Lens); Stainless Steel Double Gang Cover Plate
593WC Strobe Assembly (Clear Lens); White Double Gang Cover Plate
593WO Strobe Assembly (Opaque Lens); White Double Gang Cover Plate
SMOKE TEST GAS
565 Solo Aerosol Test Gas with Nozzle for 2650-760/761 Series Test Port
NOTCHED SAMPLING TUBES (2650-760/761 SERIES)
552 For duct widths of 1.0’ TO 2.5’
553 For duct widths of 2.5’ TO 5.0’
554 For duct widths of 5.0’ TO 10.0’
SAMPLING TUBES (2650-660/661, 2650-560/561 SERIES)
532 For duct widths of 1.0’ TO 2.5’
533 For duct widths of 2.5’ TO 5.0’
534 For duct widths of 5.0’ TO 10.0’
WEATHERPROOF ENCLOSURES
555 Weatherproof Enclosure for 2650-760/761 Series Detectors
590 Weatherproof Enclosure for 2650-660/661, 2650-560/561 Series Detectors
Normal
“Standby”
Mode
Silenced
Mode
ALM
TBL
Buzzer will function
on both Alarm
and Trouble conditions
ALM
TBL
Buzzer will function
on Alarm condition
only
ALM
TBL
Buzzer will function
on Trouble condition
only
ALM
TBL
Buzzer will not function
on Alarm or Trouble
conditions
REAR OF INDICATOR/CONTROL
191 E. North Avenue Carol Stream, IL 60188 USA Tech. Service Phone: +1 800 445 8299 E-mail: technicalservice@invensys.com www.invensys.com
591W
592WC
INST APD0340 A060829
2
INST APD0340 A060829
3
2650-760/761 Series Duct Smoke Detectors
**
NOTE: A jumper wire must be placed between Terminals 20 and 15. The Trouble LED will illuminate when
the detector cover is removed, or if the smoke detector head is removed and the cover replaced. Trouble con­tacts CANNOT
be connected to a Fire Alarm Control Panel when using this option without the use of a slave
relay.
**
NOTE: If duct smoke detectors are interconnected for common functions, please refer to unit installation
guide for connection options for remote alarm functions.
2650-660/661 Series Duct Smoke Detectors
**
NOTE: A jumper wire must be placed between Terminals 14 and 18. The Trouble LED will illuminate when
the smoke detector head is removed. Trouble contacts CANNOT
be connected to a Fire Alarm Control Panel
when using this option without the use of a slave relay.
**
NOTE: If duct smoke detectors are interconnected for common functions, please refer to unit installation
guide for connection options for remote alarm functions.
2650-560/561 Duct Smoke Detectors
**
NOTE: A jumper wire must be placed between Terminals 16, 11 and 14. The Trouble LED will illuminate
when the smoke detector head is removed. Trouble contacts CANNOT
be connected to a Fire Alarm Control
Panel when using this option without the use of a slave relay.
**
NOTE: Use of a 590 Series Remote Accessory with these detector models requires the dedicated use of
one set of alarm contacts.
**
NOTE: These models of duct smoke detectors are not intended for interconnection when using the
590 Series Remote Accessories. For further information and assistance with this application, please contact our technical hotline.
C+
TB+
P+
C-
AL+
T/R
20
1
2
12
19
4
15
JUMPER
C+
TB+
P+
C-
AL+
T/R
18
20
21
17
19
13
14
JUMPER
C+
TB+
P+
C-
AL+
T/R
16
18
19
12
20
13
11
JUMPER
LAMP AND BUZZER TEST FUNCTION
The indicator/control module includes an integrated LED and Buzzer test function, to ensure that the visual and audible indicators are functioning and haven’t “burned out”. Simply depress the “LED TEST” button on the front of the module to activate test. If the remote accessory is functioning properly, all of the LEDs will illuminate, and the buzzer will sound (unless in “silence” mode or jumper programmed to not sound on alarm or trou­ble). Releasing the “LED TEST” button will return the unit to normal condition.
TECHNICAL SPECIFICATIONS
Power Requirements: Standby 13mA
Alarm LED 22mA Trouble with Buzzer 33mA Trouble Silenced 33mA Trouble without Buzzer 13mA Alarm with Buzzer 37mA Alarm Silenced with Buzzer 37mA Alarm with Buzzer and Strobe 154mA Alarm Silenced with Buzzer and Strobe 157mA Lamp Test with Buzzer 62mA Lamp Test with Buzzer Silenced 52mA
Sound Pressure: 60db @ 10 ft
Dimensions: Single Gang Plate 4½” (114.3mm)H x 2¾” (69.85mm)W
Double Gang Plate 4½” (114.3mm)H x 4½” (114.3mm)W
Wiring: 14-28AWG, Solid or Stranded
Approvals: UL Listed by Air Products and Controls Inc. for use with all Firex duct smoke detectors. Please refer to detector
and accessory cross reference table (page 3) for listed part numbers. UL URRQ.S7425 CSFM 7300-1004:107 MEA 73-92-E Vol.31
**
NOTE: For proper installation, testing, operation and maintenance of a duct smoke detector, please refer to the detector installation guide.
The following wiring diagrams are applicable only to compatible, current limited, UL Listed remote accessories from Firex. Use of any other devices may result in damage to the duct smoke detector or those devices, potential injury, and will void any applicable warranties.
WIRING INSTRUCTIONS
FRONT OF INDICATOR/CONTROL
14
PART NUMBER CROSS REFERENCE TABLE Models UL Listed as the following Air Products and Controls Inc. part numbers.
Remote Accessories Duct Smoke Detectors
PACKAGE CONTENTS AND STROBE CONSTRUCTION
Remote accessories that include the indicator/control unit are shipped with the following parts:
• Installation Instructions
• Indicator/Control Unit with back box mounting screws (back box not supplied)
• Keys for Test/Reset function
• Decora Style Cover Plate with mounting screws (single gang)
• “Duct Smoke Detector” Decal for optional use on cover plate
Remote accessories that include the indicator/control unit and strobe assembly are shipped with the following parts:
• Installation Instructions
• Indicator/Control Unit with back box mounting screws (back box not supplied)
• Keys for Test/Reset function
• Strobe Assembly with back box mounting screws (back box not supplied)
• Adhesive Strobe Shroud
(place over strobe assembly upon removal of paper bulb protector, refer to illustration at right)
• Strobe Lens
• Strobe Lens Decals for optional use: “SMOKE”, “FIRE”
(2 of each version in horizontal orientation plus 2 each vertically set)
• Decora Style Cover Plate with mounting screws (double gang)
• “Duct Smoke Detector” Decal for optional use on cover plate
Remote accessories that include the strobe assembly are shipped with the following parts:
• Installation Instructions
• Strobe Assembly with back box mounting screws (back box not supplied)
• Adhesive Strobe Shroud
(place over strobe assembly upon removal of paper bulb protector, refer to illustration at right)
• Strobe Lens
• Strobe Lens Decals for optional use: “SMOKE”, “FIRE”
(2 of each version in horizontal orientation plus 2 each vertically set)
• Decora Style Cover Plate with mounting screws (double gang)
• “Duct Smoke Detector” Decal for optional use on cover plate
FOR FURTHER PRODUCT SUPPORT
CONTACT OUR TOLL-FREE TECHNICAL ASSISTANCE HOTLINE: +1 800 445 8299
OR SEND AN E-MAIL: technicalservice@invensys.com
Cover Plate
w/decal
Strobe Lens
w/decal
Adhesive Strobe
Shroud
Strobe Assembly
STROBE CONSTRUCTION
Firex
®
Air Products and Controls Inc. 591W MSR-100R/W 591R MSR-100R/R 591S MSR-100R/S 592WC MSR-100RS/W/C 592WO MSR-100RS/W/O 592RC MSR-100RS/R/C 592RO MSR-100RS/R/O 592SC MSR-100RS/S/C 592SO MSR-100RS/S/O 593RC MSR-100S/R/C 593RO MSR-100S/R/O 593SC MSR-100S/S/C 593SO MSR-100S/S/O 593WC MSR-100S/W/C 593WO MSR-100S/W/O