Kidde Code One A Owner's Manual

SMOKE ALARM FEATURES
• All models powered by a 9-volt battery.
• Unique “battery missing” signal. The smoke alarm will not attach to the mount­ing bracket if a battery is not in the battery pocket.
• Low battery signal. The smoke alarm will sound a short beep about once a minute if the battery needs replacement.
• Optional tamper-resist feature can serve as a safeguard against tampering.
• Loud alarm horn-85 decibels at 10 feet-sounds to alert you to a fire emergency.
• Test button checks smoke alarm operation. Model C also features a False Alarm Control. When activated, this quiets unwanted alarms for up to 10 minutes.
IMPORTANT SAFETY INFORMATION
PLEASE READ AND SAVE THESE
INSTRUCTIONS
WARNING
This smoke alarm requires a working 9-volt battery to operate. It will not work if the battery is removed, dead, or improperly connected. DO NOT remove or disconnect battery to quiet false alarms. Test weekly and replace the battery at least once a year or when the low battery signal sounds. We recommend you install smoke alarms that operate from both battery and AC power. Having smoke alarms that work from two different power sources can give extra pro­tection in case of a dead battery or an AC power failure. If you have repeated false alarms, move the smoke alarm to a different location, or install specialized smoke alarms such as Model C with False Alarm Control or Model PB with pho­toelectric sensor.
This smoke alarm is designed to be used inside a single-family household. In multi-family buildings, each individual living unit should have its own alarms. It is not a substitute for a complete commercial alarm system. It should be used only as supplemental protection in hotels, motels, dormitories, hospitals, nursing homes, or group homes.
This smoke alarm is not designed for buildings which require complete fire alarm systems. Buildings of this type include hotels, motels, dormitories, hospitals, nursing homes, and group homes. This is true even if they were once single family homes.
1
SMOKE ALARM
OWNERS MANUAL
MODELS A, B, C IONIZATION TYPE
MODEL PB PHOTOELECTRIC TYPE
BATTERY OPERATED
WARNING: THIS SMOKE ALARM MAY SOUND A SHORT BEEP WHEN POWER IS CONNECTED. D
O NOT USE THIS SMOKE ALARM WITH ANY EXTERNAL BUG SCREENS OR SMOKE ALARM
GUARDS
. USE OF THESE TYPES OF DEVICES MAY REDUCE SMOKE ALARM RESPONSE TIME.
110-949C
PLEASE READ AND SAVE
INSTALLER: Please leave this manual with the product.
!
The ionization type alarms are generally more effective at detecting fast, flaming fires which consume combustible materials rapidly and spread quickly. Sources of these fires may include flammable liquids or paper burning in a waste container. The photoelectric type alarms are generally more effective at detecting slow, smoldering fires which smolder for hours before bursting into flame. Sources of these fires may include cigarettes burning in couches or bedding. However, both types of alarms are designed to provide adequate detection of both types of fires. If you desire the benefits of both systems, you should install smoke alarms that combine in one alarm both photoelectric and ionization sensing technologies.
110-949C English 11/6/06 10:34 AM Page 1
DO NOT connect this smoke alarm to any other smoke alarm or devices. DO NOT use external bug screens or alarm guards.
This may cause
improper operation.
Smoke alarms sound their alarm horns when they detect smoke.
They do not detect heat, flame, or gas. They will not operate if smoke does not reach the smoke alarm.
Install a smoke alarm in every room and on every level of the home. Smoke may not reach the smoke alarm for many reasons. For example, if a fire starts in a remote part of the home, on another level, in a chimney, wall, roof, or on the other side of a closed door, smoke may not reach the smoke alarm in time to alert household members. A smoke alarm will not promptly detect a fire EXCEPT in the area or room in which it is installed.
This smoke alarm meets all NFPA requirements for existing homes and can be used as additional protection in locations not required, but recommended for new construction.
Per the National Fire Protection Association (NFPA) Standard 72, Chapter 2, this type of smoke alarm can be used to meet the minimum requirements for existing residential dwellings. The standard requires that smoke alarms for new residential dwellings be AC pow­ered and interconnected. Therefore, this smoke alarm CANNOT be used to meet the minimum requirements for new construction residential dwellings. This type of smoke alarm can, however, be used in new construction as additional protection in recommended areas not required by NFPA 72. See page 3 for specific NFPA requirements.
Smoke alarms may not alert every household member every time. There may be limiting circumstances where a household member may not hear the alarm (e.g., outdoor or indoor noise, sound sleepers, drug or alcohol usage, the hard of hearing, etc.). If you suspect this smoke alarm may not alert a house­hold member, install and maintain specialty smoke alarms. Current studies have shown smoke alarms may not awaken all sleeping individuals, and that it is the responsibility of individuals in the household that are capable of assisting others to provide assistance to those who may not be awakened by the alarm sound, or to those who may be incapable of safely evacuating the area unassisted.
This smoke alarm will not provide adequate escape or rescue time in extremely fast moving fires. Fast fires include gas fires, flammable liquid fires, or fires set on purpose. The smoke alarm will not give adequate escape time to people very close to the fire. Such examples might be children playing with matches or smokers who fall asleep and drop a cigarette into their bed.
Smoke alarms have limitations. This smoke alarm is not foolproof and is not warranted to protect lives or property from fire. Smoke alarms are not a substi­tute for insurance. Homeowners and renters should insure their lives and prop­erty. In addition, it is possible for the smoke alarm to fail at any time. For this reason, you must test the smoke alarm weekly and replace it every 10 years.
Smoke alarms must not be used with detector guards unless the combination of alarm and guard has been evaluated and found suitable for that purpose.
SMOKE ALARM LOCATIONS
Code One Safety recommends complete coverage protection achieved by installing a smoke alarm in every room of your home. The National Fire Protection Association’s (NFPA) MINIMUM requirement for locating smoke alarms in family living units is detailed in NFPA Standard 72, Chapter 2. It reads as follows:
“2-2.1.1.1 Smoke detectors shall be installed outside of each separate sleep­ing area in the immediate vicinity of the bedrooms and on each additional story of the family living unit including basements and excluding crawl spaces and unfinished attics. In new construction a smoke detector also shall be installed in each sleeping room.”
Further, section 2-2.2.1 states that:
“In new construction, where more than one smoke detector is required by 2-
2.1, they shall be so arranged that operation of any smoke detector shall
cause the alarm in all smoke detectors within the dwelling to sound.”
The NFPA, 1993 Edition, Appendix A, however, clearly points out that: “The required number of smoke detectors (as defined in the paragraphs above) may not provide reliable early warning protection for those areas separated by a door from the areas protected by the required smoke detectors. For this reason, it is recommended that the householder consider the use of addition­al smoke detectors for those areas for increased protection. The additional areas include: basement, bedrooms, dining room, furnace room, utility room, and hallways not protected by the required smoke detectors.”
Further, the California State Fire Marshal states that the minimum number of required smoke alarms is not enough to give the earliest warning under all conditions. The California State Marshal states that: “Early warning fire detec­tion is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: A smoke detector installed in each separate sleeping area (in the vicinity, but outside the bedrooms), and heat or smoke detectors in the living rooms, dining rooms, bedrooms, kitchens, hallways, attics, furnace rooms, closets, utility and storage rooms, basements and attached garages.”
It is clear from the above abstracts that the earliest warning of a developing fire is best achieved by the installation of smoke alarms in all rooms and areas of the residence. Accordingly, Code One Safety recommends that you install smoke alarms in every room of your residence, even though this is not required by the typical code or standard.
2
110-949C English 11/6/06 10:34 AM Page 2
SMOKE ALARM LOCATIONS (CONT.)
FOR MAXIMUM COVERAGE, WE RECOMMEND THAT YOU INSTALL A SMOKE ALARM IN EVERY ROOM OF THE HOME, INCLUDING BASEMENTS AND ATTICS. In addition, we recom­mend interconnecting all smoke alarms capable of being inter­connected. (These smoke alarms CANNOT be interconnected.)
Code One Safety recommends a minimum of two smoke alarms in every home, no matter how small the home (including efficiency apartments). Code One Safety also recommends maximum coverage by installing smoke alarms in both required and recommended locations as illustrated and described below.
Existing Homes:
• The NFPA requires a smoke alarm on every level and outside each sleeping area in existing construction. An existing household with one level and one sleeping area is required to have one smoke alarm.
New Construction Homes:
• The NFPA requires AC-powered interconnected smoke alarms to be installed inside each bedroom, out­side each bedroom area, and on every level of the home. They also require a minimum of two AC-pow­ered, interconnected smoke alarms in any new construction home.
WARNING: Models A, B, C and PB smoke alarms DO NOT
meet NFPA minimum requirements for new con­struction. Use these models only in recommended smoke alarm locations.
KEY
NFPA minimum REQUIRED smoke alarm locations
Smoke Alarm RECOMMENDED by Code One Safety, NFPA, and California State Fire Marshal
RECOMMENDED type with False Alarm Control or Photoelectric type
Denotes interconnection
Mobile Home Installation:
• For minimum protection, smoke alarms should be installed in compliance with H.U.D. Manufactured Home Construction Safety Standards Title 24 CFR, Section 3280.208 and Section 3282.
• For additional protection, see single-story residence smoke alarm requirements/recommendations for existing homes and new construction above.
ADDITIONAL SMOKE ALARM
LOCATION INFORMATION:
• Install a smoke alarm as close to the center of the ceiling as possi­ble. If this is not practical, mount no closer than 4 inches from a wall or corner. Also, if local codes allow wall mounting, install smoke alarms on walls between 4 and 12 inches from ceiling/wall intersections.
• Install a smoke alarm in each room that is divided by a partial wall (either coming down from the ceiling at least 24 inches, or coming up from the floor).
3
Bedroom
Bedroom Bedroom
Hall
Hall
Kitchen
Basement
Living Room
Utility Room
Δ
TWO STORY RESIDENCE
!
Δ
110-949C English 11/6/06 10:34 AM Page 3
SINGLE STORY RESIDENCE/APARTMENT
Bedroom
Living Room
MOBILE HOME
Kitchen
Δ
Bedroom
Bedroom
Bedroom
SINGLE STORY RESIDENCE/APARTMENT
Bedroom
Kitchen
Δ
Living Room
MOBILE HOME
Bedroom
Bedroom
Bedroom
Bedroom
Bedroom Bedroom
Living Room
Utility Room
Hall
Hall
Kitchen
Basement
TWO STORY RESIDENCE
Δ
STUB WALL
CEILING
ACCEPTABLE HERE
NEVER HERE
TOP OF DETECTOR ACCEPTABLE HERE
SOFFIT
4 IN
(0.1m)
4 IN
(0.1m)
MINIMUM
12 IN
(0.3 m)
MAXIMUM
SIDE
WALL
24"
Loading...
+ 5 hidden pages