Kenmore 580.75251500 Owner's Manual

Owner's Manual Manual del Propietario
®
ROOM AIR CONDITIONER
ACONDICIONADOR DE AIRE DE VENTANA
Model, Modelo 580. 75251
Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.A.
www.sears.com
Features ................................................. 10
Important Safety Instructions ...................... 3
INSTALLING THE POWER CORD....4
Installation Requirements ......................... 5
installation ................................................ 6
How to Install ............................................ 6
Removal from Window ................................. 8
How and Why ........................................... 9
Normal Sounds ........................................ 9
Capacity and Running Time ..................... 9
Using the Air Conditioner ....................... 10
Display ................................................... 11
Remote Control ...................................... 12
MAINTENANCE .....................................13
Air Filter Cleaning ................................... 13
Air Conditioner Cleaning ........................ 13
How to Remove the Front Gdlle .................. 13
How to Replace the Front Grille .................. 13
TROUBLESHOOTING .........................14
Before Calling for Service ...................... 14
ESPANOL ................................................15
MASTER PROTECTION
AGREEMENTS ......................................31
SERVICE NUMBERS ............ Back Cover
FULL ONE YEAR WARRANTY ON ROOM AIR CONDITIONER
For one year from the date of purchase, when this air conditioner is operated and maintained for normal room cooling according to the instructions in
this owner's manual, Sears will repair this air conditioner, free of charge, if defective in material or workmanship.
FULL FIVE-YEAR WARRANTY ON SEALED REFRIGERATION SYSTEM
For five years from the date of purchase, when this air conditioner is operated and maintained for
normal room cooling according to the instructions in this owner's manual, Sears will repair the sealed refrigeration system (consisting of refrigerant, connecting tubing, and compressor), free of charge, if defective in material or workmanship.
WARRANTY SERVICE IS AVAILABLE BY CONTACTING SEARS SERVICE AT 1-800-4-MY-HOME ®.
Warranty coverage applies only to air conditioners
used for non-commercial, private household purposes.
This warranty applies only while this product is in use in the United States.
This warranty gives you specific legal rights, and
you may also have other right which vary from state to state.
Sears, Roebuck and Co., D/817WA,
Hoffman Estates, IL 60179 U.S.A.
-2-
IMPORTANT SAFETY INSTRUCTIONS
The safety instructions below will tell you how to use your room air conditioner to avoid harm to yourself or damage to your ROOM AIR CONDITIONER.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Read product labels for flammability and
other warnings.
PREVENT ACCIDENTS
To reduce the risk of fire, electrical shock, or injury to persons when using your air conditioner, follow
basic precautions, including the following:
Be sure the electrical service is adequate for the
model you have chosen.
If the air conditioner is to be installed in a window,
you will probably want to clean both sides of the glass first. If the window is a triple-track type with a
screen panel included, you may want to remove the screen completely before installation.
Be sure the air conditioner has been securely and
correctly installed according to the separate installation instructions provided with this manual.
Save this manual and installation instructions for possible future use in removing or reinstalling this
unit.
Use gloves when handling the air conditioner.
Be careful to avoid cuts from sharp metal fins on front and rear coils.
V.'_V_Vl-'1;t_ll_[qELECTRICAL INFORMATION The complete electrical rating of your new room air
conditioner is stated on the serial plate. Refer to the
rating when checking the electrical requirements.
Be sure the air conditioner is properly grounded.
To minimize shock and fire hazards, proper grounding is important. The power cord is equipped with a three-prong grounding plug for protection against shock hazards.
Your air conditioner must be plugged into in a
properly grounded wall receptacle. If the wall receptacle you intend to use is not adequately
grounded or protected by a time delay fuse or circuit breaker, have a qualified electrician install the proper receptacle.
Do not run air conditioner with a protective
covering. This could result in mechanical damage within the air conditioner.
Do not use an extension cord or an adapter
plug.
_ Avoid fire hazard or electric shock. Do not use an extension cord or an adapter plug.
Do not remove any prong from the power cord.
3-prong
grounding plug
--3-prong
Reset_
Ground prong
supply cord
grounding type wall
receptacle
ENERGY SAVINGIDEAS
The capacity of the room air conditioner must fit the room size for efficient and satisfactory
operation.
Install the room air conditioner on the shady side of your home. A window that faces north is best
because it is shaded most of the day.
Do not block air conditioner flow inside with blinds, curtains, or furniture, or outside with shrubs, enclosures, or other buildings.
Close the floor and wall registers and the fireplace damper so cool air does not escape up the chimney or into the duct work.
Keep blinds and drapes in other windows closed during the sunniest part of the day.
Clean the air filter as recommended in the
MAINTENANCE section of this manual.
Proper insulation and weather stripping in your home will help keep warm air out and cool air in.
External house shading with trees, plants or awnings will help reduce the air conditioner's work
load.
Operate heat producing appliances such as
ranges, washers, dryers, and dishwashers during
the coolest part of the day.
-3-
OBSERVEALL LOCALCODESANDORDINANCES.
DONOT, UNDERANY CIRCUMSTANCES,REMOVE THE POWERSUPPLYCORDGROUNDPRONG.
ELECTRICALGROUNDISREQUIREDONTHIS APPLIANCE.
For230/208volt60 Hz,AC only, 15Afused and properlygroundedelectricalsupplyis required.A time delayfuseor time delaycircuitbreakeris recommended.Useadedicatedcircuit,servingonly thisappliance.
DONOT USEAN EXTENSIONCORD.
115V~ 230V~
x=J
NOTE: The shape maybe different according to its model.
Use Wall Receptacle Power Supply
3-wire grounding Standard 125V,
receptacle rated
15A, 125V AC
Standard 250V, 3-wire grounding receptacle r_ed
15A,250V AC
Standard 250V, 3-wire grounding receptacle rated 20A, 250V AC
Use 15 AMP. time delayfuse or 15 AMP.
circuit breaker.
Use 20 AMP. time delayfuse or 20 AMP.
circuit breaker.
RECOMMENDEDGROUNDINGMETHOD
Foryourpersonalsafety,thisappliancemustbegrounded. Thisappliancehasa powersupplycordwitha3-prong groundingplug.Tominimizepossibleshockhazard,the cordmustbepluggedintoamatinggroundingtypewall
receptacleandgroundedinaccordancewiththe National
ElectricalCode(ANSI/NFPA70)latesteditionandalllocal codesandordinances.If amatingwall receptacleisnot available,it isthe personalresponsibilityandobligationof thecustomertohaveaproperlygrounded3-prongwall
receptacleinstalledbya qualifiedelectrician.
Powercord mayinclude a current interrupter device. Atest and reset button is provided on the plug case. The device should be tested on a periodic basis by first pressing the TEST button
and thenthe RESET button. Ifthe TEST button does nottrip or if the RESET button will not stay
engaged, discontinue use of the air conditioner and contact a qualified service technician.
Electrical Shock Hazard Plug into a grounded 3 prong outlet.
Do not remove ground prong. Do not use an adapter.
Do not use an extension cord. Failure tofollow these instructions can result in
death, fire, or electrical shock.
You can choose between two methods below according to your window sill shape and preference.
USING SLIT "A" Fasten the stopper using 2 screw holes, and lead
out the power cord through slit "A".
USING SLIT "B"
Fasten the stopper using left screw hole, and rotate properly to lead the power cord out through slit "B".
Power Cord
-4-
INSTALLATION REQUIREMENTS
Your air conditioner will install into standard double
hung windows with actual clear opening widths of
29 to 41 inches (737mm to 1041mm) (FIG. 1)
Lower sash must open sufficiently to allow a clear
vertical opening of 19 inches (483mm). Side louvers and the rear of the air conditioner must have clear
air space to allow enough airflow through the condenser for heat removal. The rear of the unit
must be outdoors, not inside a building or garage.
H..........Sash
. 29,,to4t,,-t/
19"min. / , . ,
Inner sillL [ _ wlnaow
,',,2_<> _--Offset
, si,
f"--,_; Exterior
/""J 1/ FIG 1
Interior wall "- .... "
ELECTRICAL SERVICE
Check your available electrical service. The power supply available must be the same as that shown on
the unit nameplate (found on right side of cabinet).
All models are equipped with a 3-prong service plug to provide proper service and safe positive
grounding. Do not change plug in any way. Do not
use an adapter plug. If your present wall outlet does not match your plug, call a qualified electrician to
make the necessary corrections.
SAVE CARTON and this OWNER'S MANUAL for future reference. The carton is the best way to store
unit during winter or when not in use.
To avoid risk of personal injury, property damage, or product damage dueto the weight of this device and sharp edges that may be exposed:
Air conditioners covered in this manual pose an excessiveweight hazard. Two or more people
are needed to moveand installthe unit. To prevent injury or strain, use proper lifting and
carrying techniques when moving unit.
Carefully inspect location where airconditioner
will be installed. Be sure itwill support the weight of the unit over an extended period of
time.
Handle air conditioner with care.Wear protective gloves whenever lifting or carrying the
unit. AVOID the sharp metal fins of front and rear coils.
Make sure air conditioner doesnot fall during installation.
INSTALLATION HARDWARE
B C D E
F G H I J K
L
FIG. 2
ITEM NAME OF PARTS Q'TY
A SIDE CURTAIN 2
B SUPPORT BRACKET 2
C SILL BRACKET 2
D LOCK NUT 4 E SCREW: 25/64" 11
F SCREW: 13/16'' 7 G SCREW: 9/16" 5 H M-SCREW 2
I CARRIAGE BOLT 2 J FOAM SEAL 1 K FOAM STRIP 1 L WINDOW LOCKINGBRACKET 1
M DRAIN PIPE 1
REQUIRED TOOLS:
Tight Fitting gloves
Standard screwdriver
Phillips screwdriver
Pliers
Sharp knife
3/8-inch open end wrench or adjustable wrench
1/4-inch hex socket and ratchet
Tape measure
Electric drill
1/4qnch drill bit
-5-