Kendro CRYOFUGE 6000i, CRYOFUGE 8500i Service manual

Service Manual
Cryofuge 6000iCryofuge
6000i
Cryofuge 8500iCryofuge
8500i
CRYOFUGE 6000i / 8500i
Cat.No.: 75007520 / 75007521 / 75007550 / 7500755175007526 /
PN 12007520
SERVICE
Table of Contents
Section Title Page 1 OPERATING INSTRUCTIONS Cryofuge 6000/8500i
2 SERVICE
2.1 SERVICING SCHEDULE 2-1+2
2.2 TROUBLE SHOOTING 2-3/7
2.3 TEST POINTS ON MAIN BOARD 2-8/10
2.4 ADJUSTMENT OF IMBALANCE SWITCH 2-11
2.5 CLEANING OF INSTRUMENT PARTS 2-12
2.6 ELECTRICAL SAFETY CHECK 2-12
3 FUNCTIONAL DESCRIPTION
3.1 BLOCK FUNCTIONS 3-1
3.2 CONTACTOR PLATE (MAINS INPUT) 3-2
3.3 MAIN BOARD FUNCTIONS 3-3+4
3.4 KEY AND INDICATION BOARD 3-5
3.5 SPEED DETECTION BOARD 3-5
3.6 IMBALANCE SWITCH 3-6
3.7 COOLING PLANT 3-6 COOLING PLANT – FLOW CHART 3-7
4DIAGRAMS
4.1 BLOCK DIAGRAM 4-1/4-3
4.2 WIRING DIAGRAMS 4-4/4-7
4.3 WIRING CONNECTION DIAGRAMS 4-8/4-13
4.4 MAIN BOARD - COMPONENT PLAN 4-14
4.5 MAIN BOARD - WIRING DIAGRAM 4-15/4-22
4.6 KEY AND DISPLAY BOARD - COMPONENT PLAN 4-23
4.7 KEY AND DISPLAY BOARD - WIRING DIAGRAM 4-24
4.8 NOISE FILTER BOARD - COMPONENT PLAN 4-25
4.9 NOISE FILTER BOARD – WIRING DIAGRAM 4-26
4.10 INTERFACE BOARD - COMPONENT PLAN AND WIRING DIAGRAM 4-27
4.11 SPEED DETECTION BOARD - COMPONENT PLAN AND WIRING DIAGRAM 4-28
4.12 FRONT KEYBOARD - COMPONENT PLAN AND WIRING DIAGRAM 4-29
5 REPLACEMENT OF COMPONENTS
5.1 DISMANTLING THE HOUSING 5-1
5.2 DISMANTLING OF SEALING ELEMENTS 5-2
5.3 REPLACEMENT OF MECHANICAL COMPONENTS 5-3+4
5.4 REPLACEMENT OF ELECTRICAL COMPONENTS 5-5+6
5.5 REPLACEMENT OF DRIVE ELEMENTS 5-7
5.6 REPLACEMENT OF CONDENSER FAN 5-8
5.7 REPLACEMENT OF PARTS OF COOLING PLANT - CHARGING INFORMATION 5-8+9
6 BREAK DOWN DRAWINGS AND LIST OF SPARE PARTS
6.1 BREAK DOWN DRAWINGS 6-1/14
6.2 SPARE PARTS LIST
7 CERTIFICATE
8 TECHNICAL BULLETINS
Edition: 01 Contents
7-1/3
Cryofuge 6000i/8500i
SERVICE
Important Note
Technical Information for use of Cryofuges 6000i/8500i
__________________________________________________________________
Cat. No. 75007520 Cryofuge 6000i 3 x 400V 50/60Hz – 4,2kW Cat. No. 75007521 Cryofuge 6000i 3 x 230V 50Hz – 4,4 kW Cat. No. 75007526 Cryofuge 6000i Single Phase 230 V 50 Hz – 3,6 kW
Cat. No. 75007550 Cryofuge 8500i 3 x 400V 50/60Hz – 6 kW Cat. No. 75007551 Cryofuge 8500i 3 x 230V 50Hz – 6 kW
Required door-width : 80 cm Dimensions : 800 mm x 905 mm without wooden palette Weight : Centrifuge 430 kg / Rotor 60 kg Ground pressure : approx. 1450 N/m Noise Level: CF 6000i - <64 dB(A); CF 8500i – <67 dB(A)
2
Voltage : 3 x 400V, 50/60 Hz, N capable handling Required Fuses : 32 Amp slow blown Connection 3 x 400V : Plug Cekon Type CEE 17, 32 A-6 H
3 L + N + PE or directly installed via master power switch
Voltage : 3 x 230V/ 50 Hz Required Fuses : 32 Amp. slow blown Connection 3 x 230V : Plug Cekon Type CEE 17, 32 A-9 H
3 L + PE or directly installed via master power switch
Voltage : Single Phase 230 V/50 Hz Required Fuses: 32 Amp. slow blown Connection 1 x 230V without plug
Heat rejection to environment : 15.120 kJ/h (14.330,993 BTU) CF 6000i
19.440 kJ/h (18.425,562 BTU) CF 8500i
12.960 kJ/h (12.283,708 BTU) Single Phase
Edition: 01 Contents
Cryofuge 6000i/8500i
®
CRYOFUGES
LARGE VOLUME REFRIGERATED CENTRIFUGES
HS/Cf 1e
CRYOFUGES
LARGE VOLUME REFRIGERATED CENTRIFUGES
Precision for practical work: in blood banks and biotechnology.
Quality Products. Lifetime Care.
®
The Cryofuge 6000i is an attractively designed, large volume floor standing refrigerated centrifuge by Kendro Laboratory Products offering optimised technology for lowspeed applications.
It is ideal for use in blood banks, biotech­nology and the pharmaceutical industry, where large volumes are centrifuged at high speeds and constant temperatures. It is also used for routine separation tasks in laboratories and production facilities.
The use of sophisticated microelectronics systems and high strength materials for rotors and accessories guarantees out­standing reproducibility and highly accurate centrifugation.
With a large 6 litre capacity and a top speed of 4240 rpm (6010 x g), the Cryofuge 6000i is designed for a wide range of separation tasks. It can accom­modate 1.5 ml tubes, 1 litre containers and quad blood bags.
The Cryofuge 6000i is competitively priced and comes with a wind-shielded rotor and an extensive range of accesso­ries. Back up from an international support and service organisation ensures maximum performance and reliability.
Typical applications
The Cryofuge is designed, in particular, for the qualified production of human blood components in blood banks. It is also used for blood fractionation, serum extraction, radio immuno assays (RIA), cell preparation, fractionating protein and enzyme precipitates, separating fine crystal deposits – and in fact, in every situation where high performance and capacity are required.
Powerful technology
The Cryofuge is equipped with a power­ful, maintenance free induction drive for
quiet and smooth operation. Its refri­geration system uses the environmentally friendly CFC free refrigerant R 404a.
Acceleration and braking times have been optimised for all application require­ments. An automatic digital temperature compensation system prevents samples from freezing.
User friendly
A new automatic lid lock enables the Cryofuge to be closed easily. The ergo­nomically designed keypad allows simple entry and storage of operating para­meters. Main control functions are conveniently arranged for easy access, while the
SEPACONTROL
®
control system makes operation straightforward. The "delay" function permits users to delay system start-up.
Microprocessor control
The Cryofuge is equipped with 33 centri­fugation programs for routine applications. Nine acceleration and nine braking profiles ensure reproducibility of all centrifugation parameters. The Cryofuge is now also equipped with a profile program for defining up to 10 cut-off points with time, speed, braking and acceleration curves. Speed is controlled digitally with auto­matic RCF adjustment. Centrifuges can also be connected to a computer for data recording via a serial interface.
Safety
When designing the Cryofuge, all inter­national safety standards were kept in mind to guarantee the highest level of safety. Diagnostic and fault messages are clearly visible. Pre-selection of buckets protects against overspeeding. The lid lock system and steel armoured rotor chamber further ensure safe operation. A key operated switch safeguards against unauthorised use.
Service friendly
The Cryofuge is equipped with a digital self diagnosis system for monitoring operability. If a fault is detected, a mes­sage is immediately displayed. Should an error occur, however, our fast and efficient international service team can be relied upon.
The Cryofuge 6000i Refrigerated Centrifuge is used for the qualified production of human blood components in blood banking.
CRYOFUGE 6000i REFRIGERATED CENTRIFUGE
CRYOFUGE 6000i REFRIGERATED CENTRIFUGE
02
Conveniently arranged function keys and easy to read digital display for simple operation and quick access. Ergonomically designed keypad allows simple reproduction of operating parameters.
Keys for controlling basic functions are also located on the front of the Cryofuge for immediate access.
03
CRYOFUGE 6000i GMP AND 8500i GMP
Wind-shielded rotor and lid, showing a selection of the extensive range of buckets and adaptors.
CRYOFUGE 6000i GMP AND 8500i GMP
Convenient operation
The SEPACONTROL operating panel is systematically arranged, clearly displays all functional areas and permits easy access to operating parameters. The user simply presses a few keys to select the required centrifugation program and start the Cryofuge. A design which eliminates knobs and dials ensures high reproducibility and easy cleaning of the control panel.
SEPACONTROL provides users with up-to-date information on the status of the system. Visual diagnostic indicators and acoustic signals supplement the information supplied by the microcom­puter. This makes it easy to use the centrifuge right from the start.
Key operated switch
This switch protects programs against unauthorised access. Depending on the position of the switch, users are either permitted to freely program the system, call up one of the 33 programs in memory or simply repeat the program last used.
Panel
Five visual displays facilitate the identifi­cation of problems during centrifugation. When the lid is opened (check lid), the rotor is unevenly balanced (imbalance), in the event of a system error (system check), programming error (progr. error) or if the temperature limit has been exceeded (overtemp), an LED signals a warning.
Memory control
33 memory locations are available to save run parameters for future use. New programs generated using the function panel can be immediately added to the library.
Status
The status field is systematically arranged into the following areas: start-up and braking curves, speed and rotor data, time and temperature. LEDs prevent the user from confusing the values on the display.
Programming
The programming field permits easy setting of the required parameters. Only 5 keys are required for completely pro­gramming all parameters! The keys are used for changing the display setting, values displayed and confirming input.
Simple, functional operation
The basic functions for opening the centrifuge lid, starting and stopping the system and quick-stop are located on the front of the Cryofuge for immediate access.
Rotor and accessories
An aerodynamic wind-shielded rotor and 6 different types of bucket ensure maxi­mum performance and flexibility. The wind­shielded rotor is included in the basic centrifuge package. The vast range of accessories is listed in the tables overleaf.
Four buckets have been specially devel­oped for centrifuging blood and pro­ducing thrombocyte concentrates. The system can handle all standard blood pack systems. Additional accessories such as plastic inserts and balancing accessories round off the package.
Two other buckets used in combination with various adaptors permit all tubes with nominal volumes between 1.5 ml and 1000 ml to be centrifuged.
HERANET data documentation
The Heraeus HERANET data documen­tation system is available for data documentation in accordance with GMP. Please request our HERANET brochure from your Kendro representative.
The Cryofuge 6000i GMP (Good Manu­facturing Practice) offers the same perfor­mance and accessories as the Cryofuge 6000i. The Cryofuge 8500i GMP attains a maximum centrifugal force of 8525 x g and a maximum speed of 5050 rpm. GMP Cryofuges are specially designed for use in clean room applications.
Special features of the Cryofuge 6000i GMP and 8500i GMP
The special encapsulated casing is sealed to prevent particles from escaping and contaminating the clean room. The space between the centrifuge and floor is equip­ped with a rubber gasket. Thanks to its special smooth finish, the casing is very easy to clean. The 6000i GMP and 8500i GMP are equipped with connections for an external cooling water system; the flow rate of the cooling water is kept to a mini­mum. On request, the system can be connected to an external cooling system. The enclosed and sealed casing and vibration insulation system ensure low noise generation during operation. Heat radiation is also minimised.
Before installing the Cryofuge GMP, please be sure to contact the Kendro Service Department.
04
Model Cryofuge 6000i Cryofuge 8500i Technical data Max speed (rpm) 4,000 4,000 Operation with blood packs double-quint
Max. RCF (x g) 5,312 5,312 No. of pack systems/bucket 2 Max. capacity 2 x 800 ml 2 x 800 ml Polyamide plastic inserts: Max. perm. mass (g) 3,500 3,500 Order no. M
2)
76007667
Min. temp. at max. RCF* –5 °C –5 °C Opening M (mm) 110 x 57 Max. acceleration time (s) 140 140 Order no. L
1)
76007647
Min. braking time (s) 180 180 Opening L (mm) 110 x 70 Radius (cm) 29.9 29.9 Order no. XL
3)
76007657 Opening XL (mm) 110 x 76 Order no. XXL
4)
76007677 Opening XXL (mm) 110 x 88
* At ambient temp. of 25 °C M, L and XL plastic inserts come complete with balancing weights 75007645. One set of balancing weights includes 4 weights of 6 and 15 g each. Balancing plates 75005759 can be used to compensate big weight differences. One set includes 2 plates at 35 and 65 g each. The balancing insert 75007668 consists of an XL plastic insert, 2 balancing weights and 30 balancing plates, enabling compensation of up to a full bucket load.
1)
Suitable for triple and quad systems.
2)
Suitable for double systems.
3)
Suitable for quad systems, systems with soft filters.4)Suitable for quad and quintuple systems, systems with filters.
Double bucket for blood packs – Order no. 75007617
Model Cryofuge 6000i Cryofuge 8500i Technical data Max speed (rpm) 4,240 5,050 Operation with blood packs double-trip.
Max. RCF (x g) 5,768 8,182 No. of pack systems/bucket 2 Max. capacity 2 x 750 ml 2 x 750 ml Opening measurements (mm) 99 x 70 Max. perm. mass (g) 3,700 3,700 Plastic insert order no. 75006695 Min. temp. at max. RCF* –4 °C +6 °C Plastic insert opening (mm) 95 x 60 Max. acceleration time (s) 150 190 Plastic insert material PE Min. braking time (s) 190 220 Radius (cm) 28.7 28.7
* At ambient temp. of 25 °C Bucket for blood packs 75006695 comes with plastic insert 75006694.
Double bucket for blood packs – Order no. 75006694
Model Cryofuge 6000i Cryofuge 8500i Technical data Max. speed (rpm) 4,000 4,000 Operation with blood packs double-trip.
Max. RCF (x g) 5,170 5,170 No. of pack systems/bucket 2 Max. capacity 2 x 750 ml 2 x 750 ml Opening measurements (mm) 99 x 139 Max. perm. mass (g) 3,100 3,100 Plastic insert order no. 75006609 Min. temp. at max. RCF* –5 °C –5 °C Plastic insert opening (mm) 99 x 57 Max. acceleration time (s) 140 140 Plastic insert material PP Min. braking time (s) 180 180 Radius (cm) 28.9 28.9
* At ambient temp. of 25 °C
Double bucket for blood packs – Order no. 75006801
Double bucket for blood packs 75007617
Double bucket for blood packs 75006801
Double bucket for blood packs 75006694
05
Nominal volume of tube (ml) 1.5 7 7 15 15 15 25 25 50 50 50 50 50 100 150 No. of tubes per adaptor 40 20 12 12 11 6
1)
542262111 No. of tubes per rotor 480 240 144 144 132 72 60 48 24 24 36 24 12 12 12 Type of tube ML DIN B. Coll. DIN B. Coll. Falc. DIN Univ. DIN Falc. Falc. Univ. Oil DIN DIN Max. length of tube (mm) 45 110 110 111 109 121 100 120 130 120 117 120 S 120 120 Max. tube ø (mm) 11 13 14 17 17 17 25 25.5 35 29.5 29 29.5 S 45 55 Max. cap ø (mm) 14 18 18 19.5 23 25.9 31 36 37.5 35 37.5 S 48 – Colour of adaptor black yellow grey red white brown orange green green gr./yel. nat. gr./yel. nat. blue black Adaptor order no. (7500xxxx) 5335 5321 5330 5322 5327 5387 5323 5391 5324 5386 2261 5389 5339 5325 5326 Stand. tube order no. (7500xxxx) 1163a)9001b)– 9003b)– 2845c)9006
b)
9005b)2844e)2844e)– 3113d)9007b)1132
b)
1)
Make sure that the bucket swings out correctly when all places are used.
Type of tube: ML = microlitre tube; B. Coll. = blood collection tube ("Vacutainer", "Monovette", etc.); Falc. = "Falcon
®
" (conical tube); Oil test = oil test tube, pear shaped; Univ. = universal container (with vertical edge, Falcon type). Standard tube:
a)
1.5 ml microlitre tubes, b)borosilicate glass, c)12 ml Nunc. screw cap tube, d)oil test tube, pear shaped, e)50 ml Falcon screw cap tube.
Adaptors can be used with tubes with the following shape bottom: F = flat, R = round, C = conical, S = special
Model Cryofuge 6000i Cryofuge 8500i Technical data Max. speed (rpm) 4,000 4,000 Operation with blood packs double-trip.
Max. RCF (x g) 5,310 5,310 No. of pack systems/bucket 2 Max. capacity 2 x 700 ml 2 x 700 ml Opening measurements (mm) 95 x 55 Max. perm. mass (g) 3,100 3,100 Accessories: Min. temp. at max. RCF* –5 °C –5 °C Metal handles 75006728 Max. acceleration time (s) 140 140 Rubber spacer for shorter Min. braking time (s) 180 180 packs fitted with Radius (cm) 29.7 29.7 handle 75006728 76014725
* At ambient temp. of 25 °C
Double bucket for blood packs – Order no. 75006680
Additional accessories for blood pack operation Order no. 75006683 Pack of "shoe horns" for inserting blood packs,
incl. 1 set of rubber rings
Order no. 75006684 Set of non stick plastic bags (150 each) for smooth insertion and removal of
blood packs
Order no. 75006681 12 rubber volume compensation plates Order no. 75005759 4 rubber balancing plates
Model Cryofuge 6000i Cryofuge 8500i Max. speed (rpm) 4240/3006 5050/3006
Max. RCF (x g) 4984/2506 7070/2506 Max. capacity 24 x 15 ml/3 racks
1)
24 x 15 ml/3 racks
1)
Max. perm. mass (g) 2500/1800 2500/1800 Min. temp. at max. RCF* –4 °C +6 °C Max. acceleration time (s) 150 190 Min. braking time (s) 190 220 Radius (cm) 24.8 24.8
* At ambient temp. of 25 °C
1)
Boehringer Mannheim or Hitachi-5 sample racks
Double rectangular bucket – Order no. 76008078/75015501
Double bucket for blood packs 75006680
Double rectangular bucket 76008078 with adaptors for stan­dard tubes
Double rectangular bucket 76008078
Accessories for standard tubes in double bucket 76008078
06
C F/R F/R F/R CF/R F/R F/R S R RF/CC F/R F
Round bucket 75008165 with adaptors for standard tubes
Adaptor for large volume tubes for round bucket 75008165
Model Cryofuge 6000i Cryofuge 8500i Max. speed (rpm) 4,240 5,050
Max. RCF (x g) 6,010 8,525 Max. capacity 1 x 1000 ml 1 x 1000 ml Max. perm. mass (g) 3,200 3,200 Min. temp. at max. RCF* –4 °C +8 °C Max. acceleration time (s) 150 190 Min. braking time (s) 190 220 Radius (cm) 29.9 29.9
* At ambient temp. of 25 °C Aerosol tight cap (order no. 75008081) available on request.
Round bucket – Order no. 75008165
Nominal volume of tube (ml) 250 2502)250 500 650 750 1000 1000 Bp. DACS No. of tubes per adaptor 11111–1–1 1 No. of tubes per rotor 666666666 6 Type of tube DIN Div./H. Corni. H DIN H H HST Sing.-trip. DACS Max. length of tube (mm) 190 190 190 190 1953)148 190 175 – Max. tube ø (mm) 59 62.5 61.5 70 84 100 100 99.5 – – Max. cap ø (mm) –––––8787–– – Colour of adaptor nat. nat. nat. nat. nat. - - - nat. black Adaptor order no. (7500xxxx) 66494)8144 8147 8145 66376)– 6639 5254 Stand. tube order no.(7500xxxx) 1135b)7894 – 7718 11587)8149 6613 6640 –
Nominal volume of tube: Bp. = blood pack, DACS = Density Associated Cell Sorting (DACS™ 300, Fresenius) Type of tube: Div. = diverse, Corni. = Corning bottle, H = Heraeus tube, HST = Heraeus stainless steel tube Standard tube:
b)
borosilicate glass.
2)
Additional pad for conical tubes required from manufacturer, 3)Only use without cap 75008081,
4)
Pad 75001808 required, 6)Pad 75001913 required, 7)max. speed – 2,600 rpm
Adaptors can be used with tubes with the following shape bottom: F = flat, R = round, C = conical, S = special
Accessories for large volume tubes in round bucket 75008165
Round bucket 75008165
Nominal volume of tube (ml) 1.5/2 7 7 15 15 15 25 50 50 100 No. of tubes per adaptor 48 35 19 19 17 12 7 4 4 2 No. of tubes per rotor 288 210 114 114 102 72 42 24 24 12 Type of tube ML DIN B. Coll. DIN B. Coll. Falc. DIN DIN Falc. DIN Max. length of tube (mm) 42 177 177 177 177 177 177 177 177 177 Max. tube ø (mm) 11 13 14 17 17 17 25 35 29.5 45 Max. cap ø (mm) 14 18.5 18.5 20 23.7 31 39 39 47.5 Colour of adaptor black yellow grey red white brown orange green gr./br. blue Adaptor order no. (7500xxxx) 8132 8133 8134 8135 8136 8137 8138 8140 8141 8142 Stand. tube order no. (7500xxxx) 1163
a)
9001
b)
9003
b)
2845
c)
9006
b)
9005
b)
2844
e)
9007
b)
Type of tube: ML = microlitre tube; B. Coll. = blood collection tube ("Vacutainer", "Monovette", etc.); Falc. = "Falcon" (conical tube). Standard tube:
a)
microlitre tubes, b)borosilicate glass, c)15 ml Falcon screw cap tube, e)50 ml Falcon screw cap tube.
Adaptors can be used with tubes with the following shape bottom: F = flat, R = round, C = conical.
Accessories for standard tubes in round bucket 75008165
07
F/C F/R F/R F/R F/C RF/R F/R F/R F/C
SFFF
C
FR
F
3)
R
S
S
TECHNICAL DATA
Model Cryofuge 6000i Cryofuge 8500i Description Large volume refrigerated Large volume refrigerated
floor standing centrifuge floor standing centrifuge
Max. speed 4240 rpm 5050 rpm Max. RCF 6010 x g 8525 x g Max. capacity 6 x 1000 ml bottles or 12 blood pack 6 x 1000 ml bottles or 12 blood
systems of 800 ml each pack systems of 800 ml each
Control and drive High performance induction drive, High performance induction drive,
SEPACONTROL with SEPACONTROL with microprocessor microprocessor
Acceleration and braking profiles 9/10 profiles 9/10 profiles Runtime 1 min – 99 hrs, continuous operation 1 min – 99 hrs, continuous operation Program memory 33 user centrifugation programs, one of which with freely combinable
braking and acceleration curves, key operated switch for protection against unauthorised access, data last used saved, in the case of a power interruption data saved for unlimited period of time.
Temperature control range –20 °C to +40 °C –20 °C to +40 °C Safety features Lid lock and interlock, imbalance cut-out, steel armoured chamber Design Sturdy, torsion resistant steel design with stainless steel rotor chamber Dimensions (hxwxd) 1178 x 800 x 905 mm 1178 x 800 x 905 mm Weight (excl. rotor) 445 kg 445 kg Power consumption 4.2 kW 5.4 kW Refrigeration unit 1.9 kW 1.9 kW Recommended fuse 25A 25A Designed and tested IEC 1010, UVV VBG 20, UVV VBG 7z, UVV VBG 4, DIN 58970 part 1,2, in acc. with 4, radio interference suppression in compliance with VDE 0871 B
Rotor Wind-shielded rotor 75006606 75006606
included in basic package included in basic package
Order number Cryofuge 6000i Cryofuge 8500i
220 V/3 Ph/50 Hz 75007521 230 V/1 Ph/50 Hz 75007526 400 V/3 Ph/50 Hz 75007520
GMP model
400 V/3 Ph/50 Hzwith built-in refrigeration unit 75007562 75007561
with external refrigeration unit 75007566
ORDER NUMBERS
The Cryofuges 6000i and 8500i are now even more convenient to operate with a load-relief lid for easy opening and closing.
TECHNICAL DATA
ORDER NUMBERS
Australia Kendro Laboratory Products · Lane Cove DC · NSW 2066 · Tel. +61 (02) 9936 1540 · Fax. +61 (02) 9427 9765 · info@kendro.com.au Austria Kendro Laboratory Products GmbH · Wien · Tel. +43 (1) 801 40-0 · Fax +43 (1) 801 40 40 · office@kendro.at Canada Kendro Laboratory Products International Sales · Newtown · USA · Tel. +1 (203) 270-2080 · Fax. +1 (203) 270-2166 · info@kendro.com Denmark Kendro Laboratory Products AB · Albertslund · Tel. +45-43 62 46 47 · Fax +45-43 62 46 41 · info@kendro.dk France Kendro Laboratory Products · Courtaboeuf cedex · Tel. +33 (1) 69 18 77 77 · Fax +33 (1) 60 92 00 34 · info@kendro-lab.fr Germany Kendro Laboratory Products GmbH · Hanau · Tel +49 (6181) 35-300 · Fax: +49 (6181)35-59 44 · info@kendro.de India Kendro Laboratory Products (India) Pvt. Ltd. · New Delhi · Tel. +91 (11) 618 58 40 · Fax +91 (11) 618 53 97 · kendro.india@vsnl.com Italy AHSI S.p.A. · Cavenago Brianza · Tel. +39 (02) 95 08 11 · Fax +39 (02) 95 08 12 77 · ahsidue@tin.it Poland Kendro Spólka z.o.o.
· Warszawa · Tel. +48 (22) 663 43 23 · Fax +48 (22) 663 43 25 · kendro.warszawa@kendro.com.pl
Portugal Heraeus S.A. · Cacem · Tel. +351 (1) 912 08 65 · Fax +351 (1) 912 08 60 · heraeus@mail.telepac.pt PR China Kendro Laboratory Products (H.K.) Ltd. · Hong Kong SAR · Tel. +852 2711-3910 · Fax +852 2711-3858 · 106122.205@compuserve.com Spain Heraeus S.A. · Madrid · Tel. +34 (91) 358 19 96 · Fax +34 (91) 358 20 67 · heraeus@mx3.redestb.es Sweden Kendro Laboratory Products AB · Upplands Väsby · Tel. +46 (8) 59 07 21 90 · Fax +46 (8) 59 03 16 00 · info@kendro.se Switzerland Kendro Laboratory Products AG · Zürich · Tel. +41 (1) 454 12 12 · Fax +41 (1) 454 12 99 · kendro-ag@swissonline.ch
Kendro Laboratory Products SA · Carouge-Genève · Tel. +41 (22) 343 21 67 · Fax +41 (22) 342 38 31 · kendro-sa@swissonline.ch
U.K./Ireland Kendro Laboratory Products Limited · Bishop’s Stortford · Herts · Tel.+44 (1279) 827700 · Fax +44 (1279) 827750 · kendro@kendro.co.uk USA Kendro Laboratory Products L.P. · Newtown · Tel. +1 (800) 522-7746 · Fax. +1 (203) 270-2166 · info@kendro.com
All other International Sales in Europe, Middle East, Africa
Kendro Laboratory Products International Sales · Hanau · Germany · Tel. +49 (6181) 35-300 · Fax +49 (6181) 35 59 44 · info@kendro.de
Asia Pacific Kendro Laboratory Products (H.K.) Ltd. · Hong Kong SAR · Tel. +852 2711-3910 · Fax +852 2711-3858 · 106122.205@compuserve.com Latin America Kendro Laboratory Products International Sales · Newtown · USA · Tel. +1 (203) 270-2080 · Fax. +1 (203) 270-2210 · info@kendro.com
Internet http://www.kendro.com .http://www.heraeus-instruments.com
Kendro Laboratory Products – a worldwide company formed by the merger of Heraeus Instruments and Sorvall.
Should your country not be included in the address list, please contact Kendro Laboratory Products International Sales in Germany or USA. Subject to change without notice. Printed in Germany 6C 07/99 VN 4t Frotscher
SERVICE
2. SERVICE
2.1 Servicing Schedule (Yearly Procedure)
2.1.1 Maintenance Routine without Dismantling the Centrifuge
1. Electrical Installation and Safety
Switch OFF the centrifuge and disconnect the unit from power. Check voltage supply and mains fusing (3 x 32 Amps slow blow characteristic or other for corresponding line voltages) Check condition of plug and wall socket - replace defective parts. Check main contactor for burnt out poles. Check cord condition and fixing - replace or refit it.
2. Location and Mechanical Installation
Check the base for resonance-free and stable conditions. Check for a well ventilated place and sufficient distances to walls or adjacent equipment (min. 30 cm), avoid direct sunlight. Check the levelling of the centrifuge - use a spirit level.
3. Lid Locking Mechanism and Safety Device
Connect the centrifuge to power and switch ON Check for easy lid closing and self-acting lid opening - if in disorder, re-adjust lid looped hooks and/or hinges and/or move lid lock assembly aside and smear hooks slightly with grease. Check the central rubber gasket for lid sealing and replace it, if damaged. Open the lid and turn the rotor by hand, then close the lid and try to open it using the lid key: the lid must not be opened as long as the speed values (> 10 rpm) are indicated - if safety circuit is out of function, replace main board.
4. Cleanliness of Spin Chamber and Motor Cover
Open the lid and remove the rotor: for loosening turn rotor's collar nut with use of 19 mm fixed spanner anti clock wise (in arrow direction - see rim of rotor bowl), thereby hold the rotor on it's cross. There is an additionally turn resistance after approx. one revolution which has to be overcome with an further lever pressure of the fixed spanner. Then turn the drive shaft clockwise with the 10 mm socket wrench as long as the rotor can be lifted up. Two persons are necessary to seize the rotor by it arms on opposite and to lift the rotor carefully out of the bowl. Clean the wind-shield with a dry and absorbent cloth (remove all dust and moisture - see also
2.5 Cleaning) Check the correct seat and condition of the motor cover. Take care of the cleanliness of the annular slot around the motor shaft: there is shaft packing of felt which has to be soaked with oil. - Penetrating fluids can damage the upper motor bearing.
5. Rotor and Bucket Condition and Sealing
Check the condition of rotor and buckets (especially all supporting or stressed partitions as jib arms, rim of the bucket's bearing surface etc.): the rotor and/or buckets must not be used any longer, if there are visible traces of mechanical damage or rust. Check the condition of rotor and/or bucket sealing and replace them in case of malfunction
6. Rotor Fixing and Motor Shaft
Check the condition of the drive motor shaft: the centrifuge must not be used any longer, if the drive shaft is damaged (bend, thread is worn out, horizontal grooves etc.)
7. Temperature Control Circuit
Clean the condenser (use a vacuum cleaner). Check the thermal isolated fixing of the temperature sensor. Re-install the rotor and run the centrifuge at 2000 rpm (1500 rpm with buckets #7719) and at 4°C Check the temperature 30 minutes later: the displayed and measured value should be approximately the same (tolerances +/-2K)
Edition: 02 Service
18.04.02 MH Page: 2-1
Cryofuge 6000i/8500i
SERVICE
2.3.2 Maintenance Routine after Dismantling the Centrifuge Casing (see Section 5)
1. Motor Supporting Elements
Check the supporting and damping motor elements (enlarged rubber abrasion, often imbalance runs) and replace them by worse condition or at least every 3 years.
2. Imbalance Switch
Check the function of the imbalance switch and replace in case of malfunction.
3. Braking Circuit
Check the function of the braking circuit (warming up of brake resistor, even and noiseless brake effect) and replace defective parts in case of malfunction.
4. Lead and Screwing Connections
Check the terminal and plug connections of leads on all boards and electrical components, replace defective parts. Check the screwing connections of boards, mechanical and electrical components and tighten them if necessary.
5. Protection Earth Core and Grounding Connections
Check the protection earth core for continuity and all grounding plug connectors (see also 2.6 Electrical Safety Check). Check insulation resistance and measure the substitutional leakage current (see 2.6)
Edition: 02 Service
18.04.02 MH Page: 2-2
Cryofuge 6000i/8500i
SERVICE
Trouble Shooting
Error Indication Error Cause Possible
Error Source
"check lid" LED on, interval sound
circuit for lid switches
"check lid" LED on and "OPEn"
"imbalance"
LED on, interval sound
2) base is not sturdy
3) centrifuge is not
4) disjusted or faulty
5) leads to imbalance
6) faulty component of
"overtemp" LED on, interval sound
2) without programming
E-00 appears system check
LED on and interval sound
2) motor is jammed 2) remove drive, replace
faulty speed signal
2) faulty processing
motor didn't start 1) connection: drive to
2) defective drive 2) check resistance of
3) faulty main board 3) replace main board
lid opened mechanically during run FORBIDDEN!
interrupted
during run
15 V circuit for lid switches is interrupted
at standstill
imbalance circuit has released
just after starting: drive is
switched off
during longer operation:
rotor coasts to standstill without braking
rotor didn't turn 1) rotor is jammed 1) check for easy
easy check:
turn rotor by hand and close lid - speed values must be indicated
mechanical emergency lid opening must only be used at standstill
lid switches or leads are interrupted
1) leads to lid switches interrupted or defective lid switch
1) rotor not symmetrically loaded
enough and comes into vibrations
correctly levelled
imbalance switch
switch are interrupted
imbalance circuit
t alarm Rotor chamber must be
1) t is programmed 1) check minimum
of t
1) faulty plug or lead connections or faulty speed detection board
circuit on main board
main board
Corrective Procedure
close lid immediately, turn power OFF/ON, press start to continue run, press stop to finish run
check leads to the lid switches, if micro switch is faulty, change lid lock assembly
1) check leads to lid switches, if micro switch is faulty - replace lid lock assembly
1) open lid, check load, close lid again and start
2) change or reinforce the base
3) level the centrifuge drive correctly, use a spirit level on top of installed rotor
4) readjust imbalance switch or replace in case of malfunction
5) check leads with ohmmeter and replace if faulty
6) replace main board
precooled before ∆t activation
reachable temperatures at maximum speed and 20°C, check cooling plant in case of big deviation
2) check compressor and cooling plant (loss of refrigerant)
movement, remove any jamming objects
faulty parts
1) check plug contacts and leads - measure speed detection signal on XW1, XW3 - replace faulty parts
2) replace main board
1) check terminal and lead connections, replace faulty parts
motor windings, replace faulty parts
Edition: 02 Service
18.04.02 MH Page: 2-3
Cryofuge 6000i/8500i
SERVICE
Trouble Shooting
E-02 flashes system check
LED on and interval sound
E-03 flashes system check
LED on and interval sound
E-04 flashes system check
LED on and interval sound
2) defective amplifier or
E-06 flashes system check
LED on and interval sound
2) faulty tracks or
E-08 flashes System check
LED on and interval sound
2) faulty intermediate
2) faulty frequency
E-10 appears system check
LED on and interval sound
E-12 flashes system check
LED on and interval sound
E-15 appears system check
LED on and interval sound
E-17 appears system check
LED on and interval sound
2) defective lid lock
E-22 appears system check
LED on and interval sound
program sequence disturbed
faulty speed signal
during run
faulty temperature measuring
data lines to keyboard disturbed during operation
over voltage in DC
intermediate circuit
over current in DC
intermediate circuit
over temperature of the
electronics
program sequence disturbed
temperature signal disturbed
program sequence disturbed
micro switch didn't open after pressing lid key
NV-RAM and micro controller can not cooperate
bad ground connection check all ground
connections, tighten loose screws
see E-00 or e.g. missing rotor
1) faulty temperature sensor (PT100) or leads
converter test:
substitute PT100 by
100 and 120
1) faulty plug contact or connecting leads
components
1) leads to brake resistor interrupted or defective resistor
circuit
1) defective motor 1) disconnect the motor,
converter
insufficient cooling of power electronics
NV-RAM not initialised insert the correct NV-RAM
see E-04 see E-04
reading error of NV- RAM (checksum)
1) faulty leads or micro switch
micro controller or NV­RAM are mixed up
wait until rotor has come to standstill, then see E-00
1) check plug connection and resistance of
PT 100, replace faulty
sensor
2) set the temperature to 20 °C and watch the display: after power ON 100 ->(0±2)°C 120 ->(50±2)°C replace defective main board
1) replace plug contacts or connecting leads
2) change key and indication board or main board
1) check leads and brake resistor, replace defective parts
2) replace main board
check motor windings, replace defective motor
2) replace main board
check wall distance, air ventilation and fan function, change bad conditions, replace defective parts
if error indication occurs repeatedly replace NV­RAM
1) replace defective parts
2) replace lid lock assembly check the correct identification No's of micro controller and NV-RAM
Edition: 02 Service
18.04.02 MH Page: 2-4
Cryofuge 6000i/8500i
SERVICE
Trouble Shooting
E-23 appears system check
LED on and interval sound
2) defective driving of
2) F4: motor over
3) F5: over pressure
2) faulty driving of
displays remain dark no mains voltage supply
2) defective mains cord
2) faulty keyboard 2) replace keyboard
3) faulty main board 3) replace main board interrupted program
all displays elements are shortly illuminated
2) bad or missing
mains contactor didn't
pull up, hour counter doesn't run
mains contactor has been cut off, rotor coasts to
standstill without braking
mains contactor has pulled, hour counter runs,
rotor doesn't start or coasts to standstill without braking
no low voltage supply for
key and display board
sequence
processor reset
caused by electromagnetic disturbance
1) interruption of the mains security path
mains contactor
main security path is interrupted by one of the safety elements:
1) F3: compressor’s over current protection
temperature switch
switch of cooling plant
1) missing mains phase for supply of frequency converter or defective 35 slow blown fuse
preloading for intermediate circuit
1) Phase L2 or fuse F2 failed
or mains switch
1) faulty connection from main board to key board
NV-RAM out of socket or not correctly inserted
1) reduced voltage supply (< 10%)
ground connection
1) check F3,F4,F5 and closing contacts of K2 inclusive all connecting lines and replace defective parts
2) replace contactor or main board
1) F3: check main phases, measure the compressor current and compare with adjustion of protection switch, check compressor windings, replace defective compressor
2) F4: check air ventilation and motor windings, replace defective parts
3) enlarge the lateral wall distance, clean conden­ser, replace defective fan or make clogged injection valve free
1) check mains phase or replace defective fuse, if it blows again check for other faults (drive resistance's, intermediate circuit), replace defective parts
2) check the switching action of relay K1 and replace main board in case of malfunction
1) check phase and fuse or circuit breaker and if faulty, replace or switch on again
2) check leads and switch, replace defective parts
1) check plug connections on main and key board, check connecting leads ­replace faulty parts
insert the right NV-RAM correctly
1) if the voltage supply drops often, use a voltage stabiliser
2) check all ground connections and screwings of main board
Edition: 02 Service
18.04.02 MH Page: 2-5
Cryofuge 6000i/8500i
SERVICE
Trouble Shooting
drive makes noises -
no good centrifugation results
2) motor bearing 2) replace motor
2) defective driving
drive accelerates but doesn't brake normally -
(noisy braking)
2) defective brake control
mechanical
electrical
faulty brake circuit 1) defective lead or brake
1) wear out of motor rubber mounts
1) defective terminal connection or faulty lead or mot. winding
circuit
resistor
circuit
1) replace motor rubber mounts (damping elements)
1) check voltage on motor terminal (see test points on main board), replace defective parts
2) replace main board
1) check connection and leads and brake resistor 25 , replace faulty parts
2) change main board
Edition: 02 Service
18.04.02 MH Page: 2-6
Cryofuge 6000i/8500i
SERVICE
2.3 Test Points on Main Board
Test Points Unit Value Condition
1) mains terminal XT
(L2 for low voltage supply)
2) mains terminal L1 to N (or 2
phase)(intermediate circuit)
terminal XM 1 to XM 3 motor voltage measured
inter 2 motor leads ­voltage values must be the same between all 3 motor leads after the selected speed is reached
motor current
cable 1 cable 2 cable 3
max. acceleration current
intermediate circuit voltage UD
bridge rectifier V49
current of intermediate circuit
through control resistor R29
measured as voltage drop: U = I x R
motor winding resistance
inter 1 -> 2, 2 -> 3 and 1 -> 3
plug XD
resistance of brake resistor
plug XE
imbalance switch voltage drop inter pin 1 and 4
plug XW
voltage drop speed detection board inter pin 1 and 3: inter pin 1 and 2:
terminal XC
resistance of lid solenoid
terminal XC1/XC2
nd
230 V AC
230 V AC (-/+10%)
260 V AC 255 V AC 245 V AC
8.0 A
8.0 A
8.0 A
15 A rotor 75006606 with buckets 75008078
320 V DC 355 V DC
300 V DC 280 V DC
8.5 mV DC 31 mV DC
103 mV DC 250 mV DC
-12 mV DC
0.5
25
6.5 V DC 12 V DC
0 V DC
12.0 V DC
10.7 V DC
0.3 V DC
120
8
all given values refer to 230V
rotor 75006606 with buckets 75008078 1 000 rpm 2 500 rpm 4 240 rpm, acc. time: 95s, dec. time: 180s
soft iron or moving-iron or digital effective current measuring instrument rotor 75006606 with buckets 75008078 set speed = 4 240 rpm
(in the speed range of 2000 to 3000 rpm)
at standstill during braking phase
rotor 75006606 with buckets 75008078 set speed = 4 240 rpm shortly by max. acceleration
rotor 75006606 with buckets 75008078 set speed = 1 000 rpm set speed = 2 500 rpm set speed = 4 240 rpm shortly by max. acceleration shortly during braking phase
motor temperature: 20 °C
resistor temperature: 20 °C
installation: mechanically closed, electrically opened
plug inserted, open switch (no imbalance) plug removed, or leads interrupted (imbalance message) switch closed (plug re-inserted, active imbalance signal)
active circuit UB
transistor is cut in (slot position) transistor is cut out
speed signal: two pulses per revolution
2 x 240 parallel – old version latch motor pin 3 to 4
Edition: 02 Service
18.04.02 MH Page: 2-7
Cryofuge 6000i/8500i
Test Points on Main Board
plug XA
micro switches for lid locking
terminal XB
motor over temp. switch
terminal XN
compressor thermal over current switch
terminal XO
pressostat
plug XU
voltage drop on PT100
compressor terminal box
1) voltage
2) current
3) resistance of compressor winding
between C + R (C + P) between C + S (C + A) between R + S (A + P)
SERVICE
30 V DC
230 V AC
230 V AC
230 V AC
95 mV DC
3 x 400 V AC; 3 x 230 V AC;
single phase 230V
(depending on version)
3 x 3.8 A (400 V) 3 x 7,5 A (230 V)
7,5 A (single-phase)
3 x 400 V ; 3 x 230 V; 1 x 230V
6 1,8 1,9 6 1,8 6,4 6 1,8 7,9
by open lid
contact open
contact open
contact open
20 °C temperature indication
if contactor K3 has pulled
after 2 minutes run at room temperature at 20 °C
compressor temperature 20 °C
Edition: 02 Service
18.04.02 MH Page: 2-8
Cryofuge 6000i/8500i
SERVICE
2.4 Adjustment of Imbalance Switch
2.4.1 Meaning of Imbalance Switch
The imbalance switch has the task to switch off the centrifuge by incorrect loading of the rotor before reaching the normal speed.
NOTE!
1) Before starting with the re-adjustment procedure check the greasing of rotor trunnions and cleanliness of bucket groves. Opposing buckets and racks must be identical and equal in weight.
2) Check the motor's rubber mounts and the levelling of the drive with installed rotor (use a spirit level).
2.4.2 Adjusting Procedure
Tools and accessories:
Rotor 75006606 with buckets 75008078 check weights: 40g + 80g
Procedure
Disconnect unit from power and open the front door. Loosen both M6 screws on bottom of mounting angle of imbalance switch to keep it movable. Pull imbalance assembly away from the drive. Move the assembly very slowly in direction to the drive until a clicking noise is audible. Refix both screws and start the test run.
2.4.3 Test Run Performance
Install the rotor 75006606 with all buckets 75008078. Load one bucket with the check weight of 80g. Close the lid, select acceleration curve 9 and then press the start key. The imbalance message "bal" must appear when passing 1400 rpm. If no imbalance signal occurs, correct the adjustment by pulling the assembly a little away from
the drive. Exchange now the 40g weight and repeat the procedure. The rotor must reach the max. programmed speed without imbalance signal
NOTE! Both imbalance tests (with 40 and 80 grams) must be performed with in the buckets 1, 3 and 5 that means 6 test runs are necessary.
Edition: 02 Service
18.04.02 MH Page: 2-9
Cryofuge 6000i/8500i
SERVICE
2.5 Cleaning of Instrument Parts
ATTENTION - WARNING! Do not clean the electrical and electronic components with moist cleaners! For Cleaning the housing or accessories see Operating Instructions section 1 §10.
1) Electronic components Clean dusty components carefully with a dry and soft brush.
2) Fans Scratch off carefully with a knife or similar tool the crusted dirt from the fan blades. Resulting grooves or marks must be removed subsequently with a fine abrasive cloth. Loose dirt is to remove with a vacuum cleaner.
3) Condenser of the cooling unit The vents between the heat air deflectors have to be vacuum cleaned. By persistent dirt, the unit must be carried to an appropriate place where the condenser can be cleaned from the inside to the outside with compressed air.
2.6 Electrical Safety Check
ATTENTION! A final electrical safety check must be performed after each maintenance and/or repair.
Resistance check of protective conductor
The resistance between the mains plug's earthing pin and the earthing conductors of the motor, electronic chassis and the casing must not exceed 200 m.
Isolation resistance Check
Check also the isolation resistance between the poles of the mains plug and the earthing conductor; the resistance value must be higher than 2 MΩ.
Accessible current measured to EN 61010
The accessible current must not exceed 3.5 mAmps in single fault condition (interrupted protection earth wire)! In accordance with the EN61010, IEC1010 and UL3101 such a fault condition can be reproduced by the following measuring circuit.
Steckergehäuse / plug-in casing
10k
5%
0,022µF
5%
1500
5%
0,22µF
5%
mV
AC
500
1%
L3 N
L2
L1
PE
Spezifaktionen für Meßgerät
- TRMS, DC - 5kHz oder mehr
- Eingangswi derstand > 1M
- Toleranz 5% oder besser
- Crest Faktor 5 oder besser
Edition: 02 Service
18.04.02 MH Page: 2-10
Körperstrom:
accessible current:
U = 1750mV I = 3,5mA
max
I [mA] = U [mV] / 500:
max
Specifaction for the meter
- TRMS, DC - 5kHz or more
- Input resistance > 1M
- Tolerance 5% or better
- Crest Factor 5 or better
Cryofuge 6000i/8500i
Service
3. FUNCTIONAL DESCRIPTION
3.1 Block Functions
The Cryofuge 6000i/8500i is a microprocessor controlled and programmable floor standing centrifuge with cooling plant and induction drive motor.
Following boards and components are located inside the unit (see also block diagram section 4 page 4-1):
Mains switch S1.
Mains input angle plate with fuses F1, F2, contactors K2, K3 and hour counter h.
Main board with central processor and ASIC80 component.
Indication board with key and display processor (SEPACONTROL programming) with key switch for protection of all program parameters.
Serial interface board (RS 232) with plug connection for transferring the operational parameters to a PC or Heranet system.
Driving stage for mains contactor K2
Main security path with protection for motor overtemperature F4, thermal compressor overload F3 and overpressure of cooling plant F5.
Noise filter board.
Three phase induction drive motor with an integrated thermal overtemperature switch (cut-out at 140°C).
Speed detection board is mounted underneath the drive motor.
Imbalance switch S6 mounted aside and in front of the drive motor (for adjustment see section 2 page 2-9).
Two lid lock assemblies each with motor locking system and integrated micro switches (S2, S3 and S4, S5).
Temperature sensor V1 (PT100).
Driving stage for compressor contactor K3 (cuts in compressor M2).
Heating element as brake resistor R1 with integrated fan M6 (mounted behind the casing's back panel).
Three more Fans for cooling
a) of condenser, drive and compressor (M3) b) of condenser also (M4, not used for models with water cooling) c) of power electronics on main board (M5)
Edition: 01 Functional Description
26.12.01 MH Page: 3-1
Cryofuge 6000i/8500i
Service
3.2 Contactor Plate (Mains Input)
The following components are mounted on an angle plate, they are accessible after opening the front door (see also wiring connection diagram in section 4 page 4-9 from right to left):
Terminal for protection earth (PE) connection of mains cable (yellow green).
Terminal for neutral line (N) of mains cable (blue, 400 V version only).
Screw fuse F2 (6 Amp slow blown) for protection of control circuit connected to mains phase L2 (point 3 on mains contactor) via mains switch S1.
(Second 6 Amp fuse slow blown at 3 x 230 V units)
Screw fuse F1 (20 Amp slow blown) for protection of DC intermediate circuit for the drive's power electronics connected to mains phase L1 via noise filter board.
(Second 20 Amp fuse slow blown at 3 x 230 V units)
Mains contactor K2 with 3 phased mains connection (points 1,3,5) to supply
1.) DC intermediate circuit for drive's power electronics on phase L1 (point 2)
2.) 3 pole compressor contactor K3 (terminal 2,4,6 and 1,3,5 supply via mains contactor) to switch the compressor ON and OFF via the thermal over current fuse F3 (manual reset).
Thermal over current fuse F3 attached on compressor contactor's output to protect the compressor indirectly for thermal overload (part of the mains security path, points 95,96). Selected to running current of the compressor
Two double RC combinations are fixed with tape (bilateral adhesive) on both sides of the compressor contactor to reduce the voltage spikes when switching the compressor ON and OFF (bypassing K3 and F3 contacts).
Hour counter h is parallel connected to the main contactor's coil to determine the operational time when the centrifuge is switch ON and the lid is closed. This is generally the possible condition for the compressor's operation (standstill cooling).
Edition: 01 Functional Description
26.12.01 MH Page: 3-2
Cryofuge 6000i/8500i
Service
3.3 Main Board Functions
The main board is mounted beneath the operational panel behind the unit's back wall. The components on main board are arranged in following groups (see wiring diagram).
Triac stage for coil of compressor contactor K3
Triac stage for fan M4 of cooling plant (condenser)
Triac stage for both parallel connected lid solenoids Y1 and Y2 (old mechanical latch)
Triac stage for three parallel connected fans (M3 for condenser and drive, M5 for electronics on main board and M6 for brake resistor)
Triac stage for coil of main contactor K2 and hour counter h via main security path (F3, F4 motor overtemperature switch and F5 high pressure control switch)
Driver of new style motor latch system
Noise filter block (in interaction with the external noise filter board) for suppression of radio interference, caused by the fast switching power electronics (<10 kHz), in accordance with the German Regulation VDE 871, grade B
Bridge rectifier for DC intermediate circuit supplying brake control path and frequency converter
Power pack for 3 different low voltage levels
Microcontroller (central processing unit) in interaction with ASIC80 functions for frequency converter, speed and imbalance detection, temperature measuring and calibration
3.3.1 Power Pack
Transformer T1 with 2 different secondary coils, each connected to bridge rectifiers and voltage regulators used for the following circuits:
1.) U1 = 5V: supplies central processor, key and indication board and temperature measuring circuit reference potential: connected to protective conductor (GND)
2.) U2 = 12V: supplies the circuits of speed measuring and imbalance detection reference potential: GND2
Transformer T2 generates the low voltage supply for the power electronics:
3.) U3 = 15V: a) contacts of relay K1 (pre-loading of intermediate circuit)
- on troubles "Err. 23" will be displayed b) and all lid switches (S2,S3,S4,S5)
- on troubles "OPEn" at standstill and "LId" during rotation will be displayed
reference potential: UD-
Edition: 01 Functional Description
26.12.01 MH Page: 3-3
Cryofuge 6000i/8500i
Service
3.3.2 Intermediate Circuit with Brake Path and Frequency Converter
The DC intermediate circuit serves as an energy store between the AC power input and the transmitted motor performance. The intermediate circuit consists of a bridge rectifier and 12 parallel connected reservoir capacitors which are softly charged at the beginning over heavy-duty resistors (R61 and R100 parallel connected). When the capacitor's loading has reached the defined value, the resistors are bypassed by the relay K1 to supply frequency converter with maximum main power during operation.
Brake Path
Electrical power is fed back into the intermediate circuit during motor deceleration (motor acts as generator). This braking power is transformed into heat by brake resistor R1 (terminal XD) so that the intermediate circuit voltage does not rise to an excessive level (see section 2 - test points on main board). The brake resistor R1 is switched into the intermediate circuit by a fast switching transistor. This transistor is voltage dependent controlled by a self-acting stage (closed loop).
Frequency Converter
The motor is 3-phased provided with chopped direct voltage blocks. These blocks are variable in frequency and pulse width modulation and are dephased to 120° between the motor windings. Beginning with low frequency and small pulse width chopped blocks, both parameters will be increased up to the operators set speed. By this variation the acceleration power of the drive motor can be effected. For deceleration the frequency and pulse width parameters will be reduced. The frequency converter is dynamically and absolutely protected against overcurrent and overvoltage and also absolutely protected against excessive temperature. When exceeding one of the absolute values (overcurrent, overvoltage or excessive temperature), the message "Err.08" will be displayed.
3.3.3 Microcontroller (Central Processing Unit)
The controller block includes the central processor unit (CPU) P87C51FC and two of the data storage (NV-RAMs) 93S66 with the software identification No's. for:
CPU: 0599 (second displayed No. in speed field)
1. NV-RAM: 7571 (third displayed No. in speed field) 7572 in CF 8500i only
2. NV-RAM: 7573 (fourth displayed No. in speed field)
The second parts of these No.'s (displayed in the time field) will be upgraded if necessary. The ROM with control program is integrated in the CPU. The most important operating parameters (e.g. the maximum data or the last operator settings) are stored in the non volatile (NV) -RAM. The CPU co-operates with the ASIC 80 component via the 8 bit data bus and some control lines. The ASIC 80 is a specially designed integrated circuit for the driving of Kendro centrifuges (with induction motors), containing additional functions for speed and temperature measuring and electronics protection.
Edition: 01 Functional Description
26.12.01 MH Page: 3-4
Cryofuge 6000i/8500i
Service
3.3.4 Latch Control-system
The mainboard allows a controlling of the new electrical latch system with current software (CPU
599) and controlling of the old mechanical latch with old software (CPU 498) as well.
Note! The new Software does not control the old latch system.
Electrical latch Both latches are connected to the board via terminal XC1 and XC2. Each latch will be driven forward and backward via a relay by a special driver IC which changes the polarity of the voltage depending on status of the wanted operation - open or close the door. The activating of the door latches is several times protected by addition status controls of the CPU. The door can only be opened if the speed is “0” and the lid opening button was pushed.
Mechanical latch These mechanical latches are connected at the terminal XC. They are controlled by a triac which is fired via photodiac by CPU. Two tachogenator signal trigged flip-flops prevent an opening of the door whilst rotor is spinning.
3.3.5 Temperature measurement
The temperature will be detected by a PT 100 temperature sensor. Two reference resistors 100 ohm = 0°C and 120 ohm = 50°C will give the reference value. The auto-calibration is done by the CPU which controls an analogue switch where the signals will be transferred to a voltage/frequency converter. This select signals to the switch IC will come from the ASIC TEMP_1 and TEMP_2.
3.4 Key and Indication Board
The SEPACONTROL key and indication board is mounted behind the operational panel. A special microcontroller (P87C51FC) is located on this board controlling the 7 segment displays, the control key LEDs and the operating keys The communication with the central processor on the main board takes place via serial data lines in both directions (plug XI). The reading of the keys and the displaying of values takes place by multiplex operation. All operational parameters and user programs are stored unlimited in 6 NV-RAMs (type 93C46). The constant identification No. of the key board processor is 0497 (first displayed No. in speed field). There is a second No. displayed in the time field at the same time. This version No. is subject of the permanently technical outgrowth and will be counted up at any program changes on CPU or parameter changes on NV-RAMs.
3.5 Speed Detection Board
The speed detection takes place opto-electronically through a slit in the motor shaft. A light-emitting infrared diode and a photo-transistor are mounted on the speed detection board and located on opposing sides of the motor shaft So 2 trapezoidal pulses per motor revolution are generated and transformed into stable rectangle pulses (Schmitt trigger circuit on board), by which the micro controller calculates the real rotor speed or rcf value. The speed detection board is connected to the main board via the 3-pin plug XW.
Edition: 01 Functional Description
26.12.01 MH Page: 3-5
Cryofuge 6000i/8500i
Service
3.6 Imbalance switch
If abnormal imbalance of the rotor occurs the imbalance switch will be triggered by the moving motor. The switch closes and this signal will be given to the CPU which detects this as “imbalance”
The connection to the switch is made of 4-pole wiring which allows a check of the cable for defect. In this case the imbalance signal will also be displayed.
3.7 Cooling plant
The Cryofuge is equipped with a high-grade cooling plant, to meet it’s requirements of driving power and compact design. The CFC free refrigerant R404A evaporates at low temperatures ( -20°C) and absorbs through this the frictional heat from chamber produced by the spinning rotor. Two fans serve for even air flow through condenser so that the refrigerant’s condensing temperature is kept on a low level.
A condenser serves for essential under-cooling of the condensed refrigerant to ensure an optimum evaporation and a perfect operation of the expansion valve. To maintain low evaporation and resultant condensation temperatures on one hand and to support the starting procedure of the compressor on other hand, a thermostatic expansion valve is used.
The minimum achievable sample temperatures are depending on speed, rotor type and a little on ambient temperature. After a compensating time (at max speed – 3 hours) as optimal result, the rotor has reached the selected set temperature within a tolerance of ± 2K.
Edition: 01 Functional Description
26.12.01 MH Page: 3-6
Cryofuge 6000i/8500i
37 ­45°C
Verflüssiger
condenser
Kälteanlage
Cooling
Verdampferkessel
evaporator chamber
Lüfter Kühlmaschine fans for cooling plant
2.2
J
07.05.01 MH
Sammler accumulator
CPU
1
c.o.
>P
"E-23"
18bar c.i.
Druck-
28bar
wächter
pressure
switch
Fließbild / Flowchart
3-7
114 - 118°C
p = 13,8 bar
-26 -
-16°C
thermostatisches Expansionsventil
R404A
Verdichter
compressor
thermostatic expansion valve
Trockner+Schauglas Dryer+Inspectionglas
p = 1,7 bar
0
Wärmetauscher
heat exchanger
7 - 8°C
TC
-45 ­+30°C
CRYOFUGE 6000i/8500i
2.3
Netz mains
noise filter board
3
Hauptschütz main contactor
K2
F1
Funkentstör-
platte
3
KM-Schütz compressor contactor
Kühlmaschine compressor
Kurbelwannen-
heizung
crankcase
filament
K3
Netzschalter mains switch
M2
S1
F2
Unwucht-
schalter
imbalance
switch
S6
2 Impulse pro Motorumdrehung 2pulses per motor revolution
Drehzahler-
fassungsplatte
speed detection
board
SCHALTPLÄNE
SCHEMATIC DIAGRAMS
Schlüsselschalter key switch
nicht belegt
not used
Temperatur-
sensor
temperature
sensor
V1
XJ XJ
Deckelschloss
Latch
Right
S2
S3
S4
Left
Motor M8Motor M7
S5
S6
S7
Tasten-und Anzeigenplatte key and indication board
X2
RS-232
Schnittstelle
interface
X1
XI
operating panel
XZ
XZ
Bedienplatte
XY
XY
Option
NPE
L
XM1 XM2 XM3
Motor
23.04.01 MH
M1
XB
F4
Motorüber­temperatur motor over
temperature
XT
XH
Motor/KM
Lüfter
motor/compr.
fan
M3
XE XW XL XU XA
XC 1
Hauptplatte main board
F3
TsÜ (KM)
thermal
fuse
XN
F5
P
Pressostat
overpressure
switch
4-1
XO XP
Deckelspulen
lid solenoids
K2
Ansteuerung Hauptschütz
mains contactor
coil
XF
FET-Lüfer
fan for
electronics
M5
XS
Lüfter Brems-
widerstand
fan of braking
resistor
M6
Blockschaltbild / Block Diagram
Y1,Y2
Old/alte
XC
fan for cooling
(entfällt bei Wasser-
*
kühlung not used with water cooling
Legende / legend
XC 2
KM-Lüfter
plant
M4
XK
XI
XG
K3
Ansteuerung
Kühlmaschine
compressor
coil
3x400V+N+PE
XD
Bremswider-
stand
brake resistor
R1
Steckverbindung / plug connection
Schraubverbindung / screwing connection
CRYOFUGE 6000i/8500i
Netz mains
F1
noise filter board
3
Hauptschütz main contactor
K2
F2
Funkentstör-
platte
F3
F4
3
KM-Schütz compressor contactor
Kühlmaschine compressor
Kurbelwannen-
heizung
crankcase
filament
K3
Netzschalter mains switch
M2
S1
Unwucht-
schalter
imbalance
switch
S6
2 Impulse pro Motorumdrehung 2pulses per motor revolution
Drehzahler-
fassungsplatte
speed detection
board
SCHALTPLÄNE
SCHEMATIC DIAGRAMS
Schlüsselschalter key switch
nicht belegt
not used
Temperatur-
sensor
temperature
sensor
V1
XJ XJ
Deckelschloss
Latch
Right
S2
S3
S4
Left
Motor M8Motor M7
S5
S6
S7
Tasten-und Anzeigenplatte key and indication board
X2
RS-232
Schnittstelle
interface
X1
XI
operating panel
XZ
XZ
Bedienplatte
XY
XY
Option
NPE
L
XM1 XM2 XM3
Motor
23.04.01 MH
M1
XB
F4
Motorüber­temperatur motor over
temperature
XT
XH
Motor/KM
Lüfter
motor/compr.
fan
M3
XE XW XL XU XA
XC 1
Hauptplatte main board
F3
TsÜ (KM)
thermal
fuse
XN
F5
P
Pressostat
overpressure
switch
4-2
XO XP
Deckelspulen
lid solenoids
K2
Ansteuerung Hauptschütz
mains contactor
coil
XF
FET-Lüfer
fan for
electronics
M5
XS
Lüfter Brems-
widerstand
fan of braking
resistor
M6
Blockschaltbild / Block Diagram
Y1,Y2
Old/alte
XC
fan for cooling
(entfällt bei Wasser-
*
kühlung not used with water cooling
Legende / legend
XC 2
XK
KM-Lüfter
plant
M4
3x230V+PE
XI
XG
K3
Ansteuerung
Kühlmaschine
compressor
coil
XD
Bremswider-
stand
brake resistor
R1
Steckverbindung / plug connection
Schraubverbindung / screwing connection
CRYOFUGE 6000i/8500i
Loading...
+ 104 hidden pages