A-Location
B-Packaging
C-Adjusting the Casters
D-Cord & Plug
E-Power Supply
F-Placing Equipment On Top Of Unit
4. OPERATION
A-Refrigerators
5. CARE & MAINTENANCE
A-Cleaning The Condenser/Filter
B-Replacing The Gaskets
C-Cleaning The Cabinet Surface
6. DRAWERS
A-Removing The Drawers And Frame Module
7. MICROPROCESSOR CONTROL
A-Control Features
B-Alarm Explanations
C-Control Panel Diagram
D-Notes To The User
E-Enter The Service
F-Service Parameters
G-Adjusting Thermostat Set Point High
H-Adjusting Thermostat Set Point Low
I-Changing The Temperature Scale
J-Setting The 24-Hour Clock
K-Setting The Date
L-Setting Daylight Savings Time
M-Starting A Manual Defrost
N-Setting Defrost Lockouts
O-Adjusting The Drawer Perimeter Heaters
P-Adjusting The Room Temperature Offset
Q-Setting The Audible Alarm Style
R-Viewing Sensor Temperatures
The serial tag is a permanently afxed label on which is recorded vital electrical and refrigeration data
about your Kairak product, as well as the model and serial number. This tag is located in the right interior
compartment on all standard Equipment Stand models.
READING THE SERIAL TAG
• Serial = The permanent ID# of your Kairak unit
• Model = The model # of your Kairak unit
• Volts = Voltage
• Hz = Cycle
• PH = Phase
• Total Current = Maximum amp draw
• Minimum Circuit = Minimum circuit ampacity
• Lights = Light wattage
• Heaters = Heater amperage (Hot Food units only)
• Refrigerant = Refrigerant type used
• Design Pressure = High & low side operating pressures and refrigerant charge
• Agency Labels = Designates agency listings
SERIAL MODEL
VOLTS HZ PH
TOTAL CURRENT AMPS
MINIMUM CIRCUIT AMPS
MAXIMUM OVERCURRENT PROTECTION AMPS
LIGHTS WATTS
HEATERS AMPS
REFRIGERANT TYPE OZ
DESIGN PRESSURE HIGH LOW
REFRIGERANT TYPE OZ
DESIGN PRESSURE HIGH LOW
EQUIPMENT STAND
PAGE 3
2. RECEIPT INSPECTION
All Kairak products are factory tested for performance and are free from defects when shipped. The utmost
care has been taken in crating this product to protect against damage in transit.
You should carefully inspect your Kairak unit for damage during delivery. If damage is detected, you should
save all the crating materials and make note on the carrier’s Bill Of Lading describing the damage. A freight
claim should be led immediately. If damage is subsequently noted during or immediately after installation,
contact the respective carrier and le a freight claim. There is a fteen (15) day limit to le freight damage
with the carrier. Under no condition may a damaged unit be returned to Kairak without rst obtaining written
permission (return authorization). You may contact Kairak customer care at (714) 870-8661 or Toll-Free
(800) 833-1106 to request a return.
3. INSTALLATION
3A - LOCATION:
Unit must be placed on leveled oor for proper usage.
3B - PACKAGING:
Your Kairak unit is shipped from the factory packaged with stretch wrap material.
Most exterior stainless steel surfaces have a protective blue vinyl covering to prevent scratching during
manufacturing, shipping and installation. After the unit is installed in place of application peel, remove and
discard the covering from all surfaces.
The equipment stands are shipped on a skid that is designed to allow a unit to be slid off the skid onto the
factory installed casters. When a unit is being removed from the skid two or more runners will act as slides
and will remain with the unit while it is being removed. These runners prevent damage to the machine
when it drops off the skid to the oor. The runners are retained by the bolts located in the top holes of the
mounting brackets (B).
To unload the machine, remove the exterior packaging. Next remove the retaining brackets. This bracket
is held in place by two bolts into the skid and two screws into the caster channel. There are two of these
brackets per skid segment. Next remove the remaining bolts in the lower holes of the mounting brackets (A)
leaving the bolts in the upper holes (B) in place. Next push the machine off the skid keeping the length of
the machine parallel to the skid’s 4x4 pieces. On longer machines this may require two or more individuals.
When the machine is on its casters the 2x4 runners can be removed by removing the bolts from the top
holes (B) in the mounting brackets. The mounting brackets are removed from the caster channel by twisting
the bracket 90 degrees.
EQUIPMENT STAND
PAGE 4
3. INSTALLATION (CONTINUED)
RETAINING BRACKET
B
CASTER CHANNEL
B
RUNNER
B
A
A
NOTE: Kairak does not recommend laying
SKID
the unit on its front, side or back. If you
must, please allow the unit to remain in
an upright position for 24 hours before
plugging it in so that the compressor oils
and refrigerant may settle.
FIG. 1
3C - ADJUSTING THE CASTERS:
To adjust the caster loosen the two bolts and move caster to desired location, spacing between casters not to
exceed 48 inches. Casters on each end of the unit can not exceed 8 inches from the end of the cabinet.
BOLT
CASTER
CHANNEL
CASTER PLATE
FIG. 2
EQUIPMENT STAND
PAGE 5
3. INSTALLATION (CONTINUED)
3D - CORD & PLUG:
All self-contained models are shipped standard with a NEMA 5-15P plug and 9 foot cord and spring retainer
attached at the rear of the cabinet. Select only a dedicated electrical outlet for power source.
NOTE: Do not under any circumstances, cut or remove the round grounding prong from the plug, or use
an extension cord.
3E - POWER SUPPLY:
The supply voltage should be checked prior to connection to be certain that proper voltage for the cabinet
wiring is available (refer to the serial tag to determine correct unit voltage). Make connections in accordance
with local electrical codes. Use qualied electricians.
Use of a separate, dedicated circuit is required. Size wiring to handle indicated load and provide necessary
overcurrent protector in circuit (see amperage requirements on the unit’s serial tag).
3F - PLACING EQUIPMENT ON TOP OF UNIT:
Equipment may be placed on top of your Kairak equipment stand. A stainless steel worktop, provided
standard is required on cabinets being used to support equipment weighing in excess of 100 lbs. or
producing heat in excess of 140°F to the top surface. Refer to below chart to determine Maximum Top
Load Capacity for your unit.
MODEL MAX TOP LOAD
CAPACITY LBS.
KE036 625
KE048 625
KE0601200
KE0651200
KE0721200
KE0841500
KE0961500
KE1101500
KE1252000
KE1392000
EQUIPMENT STAND
PAGE 6
4. OPERATION
4A - REFRIGERATORS:
Refrigerators do not require manual defrosting. During normal operation, a refrigerator continuously
circulates above freezing cabinet air through the coil. A compressor “OFF” cycle occurs every 2 1/2 Hours
for 20 minutes to melt any frost which may accumulate on the coil during the compressor “ON” cycle. The
control will read “dEF” and the green water drop will be illuminated. With standard holding refrigerators,
high relative humidity is also maintained to prevent dehydration of stored product.
MICROPROCESSOR CONTROL
FIG. 3
5. CARE & MAINTENANCE
5A - CLEANING THE CONDENSER/FILTER:
The most important thing you can do to insure a long, reliable service life for your Kairak is to regularly
clean the condenser coil and or lter if provided.
The microprocessor control will notify you through a “CLN-FIL” message when the condensing temperature
of the refrigerator reaches 140 degrees F or greater. If the condensing temperature reaches 160 degrees F the
compressor will automatically turn off . When the temperature drops below 140 degrees F the compressor
will restart and when the temperature drops below 120 degrees F the alarm will reset.
WARNING: DISCONNECT ELECTRICAL POWER SUPPLY BEFORE CLEANING ANY PARTS OF THE
UNIT.
To clean the condenser/lter, rst disconnect electrical power to the cabinet and remove the front louver
assembly. To do so, place hands under the louver panel and pull out and up to get louver panel off bracket
of the unit. See diagram below.
FIG. 4
EQUIPMENT STAND
PAGE 7
5. CARE & MAINTENANCE (CONTINUED)
5A - CLEANING THE CONDENSER/FILTER (CONTINUED):
Proceed to vacuum or brush any dirt, lint or dust from the nned condenser coil/lter, the compressor and
other cooling system parts. If signicant dirt is clogging the condenser ns or lter, use compressed air to
blow this clear.
To replace the louver assembly reverse the process.
5B - REPLACING THE GASKETS:
To remove the gasket to be replaced, grasp it rmly by one corner and pull it out. Before attempting to install
a new gasket, both the unit and the gasket itself must be at room temperature. Insert the four corners rst
by using a rubber mallet (or hammer with a block of wood). After the corners are properly inserted, work
your way towards the center from both ends by gently hitting with a mallet until the gasket is completely
seated in place (see gure 5 for proper gasket placement).
NOTE: The gasket may appear too large, but if it is installed as indicated above it will slip into place.
SIDE DRAWER PANEL
VERTICAL GASKET RETAINER
GASKET ASSEMBLY
FIG. 5
5C - CLEANING THE CABINET SURFACES:
WARNING: DISCONNECT ELECTRICAL POWER SUPPLY BEFORE CLEANING ANY PARTS OF THE
UNIT.
Exterior stainless steel should be cleaned with warm water, mild soap and a soft cloth. Apply with a
dampened cloth and wipe in the direction of the metal grain.
Avoid the use of strong detergents and gritty, abrasive cleaners as they may tend to mar and scratch the
surface. Do NOT use cleansers containing chlorine, such as bleach, this may promote corrosion of the
stainless steel.
Care should also be taken to avoid splashing the unit with water, containing chlorinated cleansers, when
mopping the oor around the unit.
For stubborn odor or spills, use baking soda and water (mixed to a 1 tbsp baking soda to 1 pint water
ratio).
A stainless steel polish is recommended for shining of unit.
EQUIPMENT STAND
PAGE 8
6. DRAWERS
6A - REMOVING THE DRAWERS AND FRAME MODULE:
Remove the drawer (s) from the drawer frame by lifting up on the drawer and pull out.Once the drawer(s)
have been removed, the drawer frame module can also be removed by loosening the black front and back
clamping knobs (2 of each) located on the cross rail locks and liner locks. Slide the front cross rail locks
towards the center of the drawer frame module and allow the liner locks to drop down from the top of the
liner. Pull the door frame module forward, tip forward and pull out. The entire frame assembly is now free
to slide out of the cabinet.
FRONT CLAMPING KNOBS
FRONT CROSS RAIL LOCKS
BACK CLAMPING KNOBS
FIG. 6
FIG. 7
EQUIPMENT STAND
PAGE 9
7. MICROPROCESSOR CONTROL
Your new refrigerator cabinet is equipped with a state-of-the-art microprocessor control, which
precisely regulates operation and provides alarms when problems occur. It is supplied from the factory
completely ready for use and requires no adjustments, but without the audible alarms activated. See
pages 10 thru 26 for more information.
MICROPROCESSOR CONTROL
FIG. 8
7A - CONTROL FEATURES:
1 - INTERNAL TIME CLOCK
• Eliminates external defrost time clock.
• Defrost cycle can be quickly adjusted to suit individual location and use.
• Must be set at power-up. (See page 17, “Setting the 24-Hour Clock”)
• Will automatically update for Daylight Savings Time.
2 - WATER RESISTANT HOUSING
The face of the control is water resistant to provide for protection during cleaning.
3 - PARAMETER/SERVICE LEVELS
• See “Customer / Service Parameters” on Page 14.
4 - DEFROST LOCKOUTS
Customers can set up to 4 different defrost lockout periods. The lockout prevents the unit from going into
a defrost cycle during peak kitchen use.
(See “Setting Defrost Lockouts” on page 21)
Note: The 24-hour clock must be set for this feature to operate correctly.
5 - COMMUNICATION ABILITY
A NAFEM Data Protocol (NDP) compliant RS-485 serial communications port is available to interface with data
collection software (by others). All microprocessor control equipped models are capable of communicating
within a NAFEM Data Protocol network if provided with an optional Gateway Hub (available from Kairak).
The actual communications software is available from a number of third party software vendors.
6 - ANTI-CONDENSATE DOOR PERIMETER HEATER CONTROL
The “No-Sweat” feature is an energy savings system that allows the customer to adjust the percent of
time for the drawer heater to be “On” as needed for the prevailing ambient conditions (from 0 - 100% of
the time each day). It is used to prevent condensation from forming around the perimeter of the drawers.
The factory default setting is 100%. Adjust this set point down to a point just before condensation forms
to save energy.
EQUIPMENT STAND
PAGE 10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.