Juniper Networks, Inc.
1194 North Mathilda Avenue
Sunnyvale, CA 94089
USA
408-745-2000
www.juniper.net
Part No. 162-00468-02 Rev. A00
Juniper Networks is registered in the U.S. Patent and Trademark Office and in other countries as a
trademark of Juniper Networks, Inc. Broadband Cable Processor, ERX, ESP, G1, G10, G-series,
Internet Processor, JUNOS, JUNOScript, M5, M10, M20, M40, M40e, M160, M-series, NMC-RX,
SDX, ServiceGuard, T320, T640, T-series, UMC, and Unison are trademarks of Juniper Networks,
Inc. All other trademarks, service marks, registered trademarks, or registered service marks are the
property of their respective owners. All specifications are subject to change without notice.
Products made or sold by Juniper Networks (including the M5, M10, M20, M40, M40e, M160, and
T320 routers, T640 routing node, and the JUNOS software) or components thereof might be covered
by one or more of the following patents that are owned by or licensed to Juniper Networks: U.S.
Patent Nos. 5,473,599, 5,905,725, 5,909,440, 6,333,650, 6,359,479, and 6,406,312.
Writers: John Borelli, Helen Shaw, Nathaniel Woodward
Editor: Fran Mues
Revision History
November 2002
Juniper Networks assumes no responsibility for any inaccuracies in this document. Juniper Networks
reserves the right to change, modify, transfer, or otherwise revise this publication without notice.
Federal Communications Commission (FCC) Statement
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
This equipment is designed for use with properly shielded and terminated cables. Refer to the
installation sections of this manual before operation.
Reference: CFR 47, Part 15J, Sect 15.105 April 18, 1989
Caution: Changes or Modifications to this equipment not expressly approved by the party
responsible for compliance could void the user’s authority to operate the equipment.
FCC Requirements For Consumer Products
This equipment complies with FCC rules, Part 68. On the back side of this equipment is a label that
contains, among other information, the FCC Registration Number and Ringer Equivalence Number
(REN) for this equipment. If requested, provide this information to your telephone company.
If this equipment causes harm to the telephone network, the Telephone Company may discontinue
your service temporarily. If possible, they will notify you in advance. But if advance notice isn't
practical, you will be notified as soon as possible. You will be advised of your right to file a complaint
with the FCC.
Your telephone company may make changes in its facilities, equipment, operations, or procedures
that could affect the proper operation of your equipment. If they do, you will be given advance notice
so as to give you an opportunity to maintain uninterrupted service.
If you experience trouble with this equipment, please contact the manufacturer for warranty/repair
information. The telephone company may ask that you disconnect this equipment from the network
until the problem has been corrected or until you are sure that the equipment is not malfunctioning.
Food and Drug Administration, Center for Devices and Radiological
Health
This equipment complies with 21 CFR 1040.10 and 1040.11 for the safe use of lasers.
Canadian Department Of Communications Radio Interference
Regulations
This Class B (or Class A, if so indicated on the registration label) digital apparatus meets the
requirements of the Canadian Interference-Causing Equipment Regulations.
Réglement sur le brouillage radioélectrique du ministère des
communications
Cet appareil numérique de la Classe B (ou Classe A, si ainsi indiqué sur l’étiquette d’enregistration)
respecte toutes les exigences du Reglement sur le Materiel Brouilleur du Canada.
Industry Canada Notice CS-03
The Industry Canada label identifies certified equipment. This certification means that the equipment
meets certain telecommunications network protective, operation and safety requirements as
prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The
Department does not guarantee the equipment will operate to the user's satisfaction. Before
installing this equipment, users should ensure that it is permissible to be connected to the facilities of
the local telecommunications company. The equipment must also be installed using and acceptable
method of connection. The customer should be aware that compliance with the above conditions
may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier.
Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give
the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power
utility, telephone lines and internal metallic water pipe system, if present, are connected together.
This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves, but should contact the
appropriate electric inspection authority, or electrician, as appropriate.
Notice: The Ringer Equivalence Number (REN) assigned to each terminal device provides an
indication of the maximum number of terminals allowed to be connected to a telephone interface.
The termination on an interface may consist of any combination of devices subject only to the
requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.
Avis CS-03 d’Industrie Canada
L’étiquette du ministère des Communications du Canada indique que l’appareillage est certifié,
c’est-à-dire qu’il respecte certaines exigences de sécurité et de fonctionnement visant les réseaux
de télécommunications. Le ministère ne garantit pas que l’appareillage fonctionnera à la satisfaction
de l’utilisateur. Avant d’installer l’appareillage, s’assurer qu’il peut être branché aux installations du
service de télécommunications local. L’appareillage doit aussi être raccordé selon des méthodes
acceptées. Le client doit toutefois prendre note qu’une telle installation n’assure pas un service
parfait en tout temps.
Les réparations de l’appareillage certifié devraient être confiées à un service d’entretien canadien
désigné par lefournisseur. En cas de réparation ou de modification effectuées par l’utilisateur ou de
mauvais fonctionnement del’appareillage, le service de télécommunications peut demander le
débranchment de l’appareillage.
Pour leur propre sécurité, les utilisateurs devraient s’assurer que les mises à la terre des lignes de
distribution d’électricité, des lignes téléphoniques et de la tuyauterie métallique interne sont
raccordées ensemble. Cette mesure de sécurité est particulièrement importante en milieu rural.
Attention: Les utilisateurs ne doivent pas procéder à ces raccordements eux-mêmes mais doivent
plutôt faire appel aux pouvoirs de réglementation en cause ou à un électricien, selon le cas.
Avis: Veuillez prendre note que pour tout appareillage supportant des lignes de type “loopstart,”
l'indice d'équivalence de la sonnerie (IES) assigné à chaque dispositif terminal indique le nombre
maximal de terminaux qui peuvent être raccordés à une interface. La terminaison d'une interface
téléphonique peut consister en une combinaison de quelques dispositifs, à la seule condition que la
somme d'indices d'équivalence de la sonnerie de tous les dispositifs n'excède pas 5. Le REN figure
sur l’étiquette “FCC Rules Part 68” située sur le support du module ou à l’arrière de l’unité.
The Canadian Department of Communications label identifies certified equipment. This certification
meets certain telecommunication network protective, operational and safety requirements. The
department does not guarantee the equipment will operate to the users satisfaction.
Before installing the equipment, users should ensure that it is permissible to be connected to the
facilities of the local telecommunications company. The equipment must also be installed using an
acceptable method of connection. In some cases, the company’s inside wiring associated with a
single line individual service may be extended by means of a certified connector assembly
(telephone extension cord). The customer should be aware that compliance with the above condition
may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility
designated by the supplier. Any repairs or alterations made by the user to this equipment, or
equipment malfunctions, may give the telecommunications company cause to request the user to
disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power
utility, telephone lines and internal metallic water pipe system, if present, are connected together.
This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves, but should contact the
appropriate electrical inspection authority, or electrician, as appropriate.
Notes explicatives du ministère des Communications: limites visant
les accessoires
L’étiquette du ministère des Communications du Canada indique que l’appareillage est certifié,
c’est-à-dire qu’il respecte certaines exigences de sécurité et de fonctionnement visant les réseaux
de télécommunications. Le ministère ne garantit pas que l’appareillage fonctionnera à la satisfaction
de l’utilisateur.
Avant d’installer l’appareillage, s’assurer qu’il peut être branché aux installations du service de
télécommunications local. L’appareillage doit aussi être raccordé selon des méthodes acceptées.
Dans certains cas, le câblage interne du service de télécommunications utilisé pour une ligne
individuelle peut être allongé au moyen d’un connecteur certifié (prolongateur téléphonique). Le
client doit toutefois prendre note qu’une telle installation n’assure pas un service parfait en tout
temps.
Les réparations de l’appareillage certifié devraient être confiées à un service d’entretien canadien
désigné par le fournisseur. En cas de réparation ou de modification effectuées par l’utilisateur ou de
mauvais fonctionnement de l’appareillage, le service de télécommunications peut demander le
débranchment de l’appareillage.
Pour leur propre sécurité, les utilisateurs devraient s’assurer que les mises à la terre des lignes de
distribution d’électricité, des lignes téléphoniques et de la tuyauterie métallique interne sont
raccordées ensemble. Cette mesure de sécurité est particulièrement importante en milieu rural.
Attention: Les utilisateurs ne doivent pas procéder à ces raccordements eux-mêmes mais doivent
plutôt faire appel aux pouvoirs de réglementation en cause ou à un électricien, selon le cas.
EC Declaration of Conformity
The EC Declaration of Conformity is available at the end of this manual.
Voluntary Control Council for Interference (VCCI) Statement for Japan
SOFTWARE LICENSE AGREEMENT
JUNIPER NETWORKS, INC. IS WILLING TO LICENSE THE ENCLOSED SOFTWARE AND
ACCOMPANYING USER DOCUMENTATION (COLLECTIVELY, THE “PROGRAM”) TO YOU ONLY
UPON THE CONDITION THAT YOU ACCEPT ALL OF THE TERMS AND CONDITIONS OF THIS
LICENSE AGREEMENT. PLEASE READ THESE TERMS AND CONDITIONS CAREFULLY
BEFORE COPYING OR USING THE ACCOMPANYING SOFTWARE OR INSTALLING THE
HARDWARE UNIT WITH PRE-ENABLED SOFTWARE OR USING THE ACCOMPANYING USER
1
DOCUMENTATION.
BY USING THE ACCOMPANYING SOFTWARE OR INSTALLING THE HARDWARE UNIT WITH
PRE-ENABLED SOFTWARE, YOU AGREE TO BE BOUND BY THE TERMS AND CONDITIONS
OF THIS LICENSE AGREEMENT. IF YOU DO NOT AGREE TO BE BOUND BY THE TERMS OF
THIS LICENSE AGREEMENT, JUNIPER NETWORKS IS UNWILLING TO LICENSE THE
PROGRAM TO YOU, IN WHICH EVENT YOU SHOULD PROMPTLY WITHIN TEN (10) DAYS
FROM SHIPMENT RETURN THE UNUSED SOFTWARE, USER DOCUMENTATION, AND
RELATED EQUIPMENT AND HARDWARE TO THE PLACE OF PURCHASE AND YOU WILL
RECEIVE A FULL REFUND OF YOUR LICENSE FEE. THIS LICENSE AGREEMENT
REPRESENTS THE ENTIRE AGREEMENT CONCERNING THE PROGRAM BETWEEN YOU AND
JUNIPER NETWORKS, AND IT SUPERSEDES ANY PRIOR PROPOSAL, REPRESENTATION OR
UNDERSTANDING BETWEEN THE PARTIES.
1. License Grant. Juniper Networks, Inc. (“Juniper Networks”) and its suppliers and licensors
hereby grant to you and you hereby accept a nonexclusive, personal and nontransferable license to
use the computer software and/or hardware unit with pre-enabled software, including all patches,
error corrections, updates, and revisions thereto in machine-readable, object code form only (the
“Software”), and the accompanying User Documentation on the Juniper Networks product owned by
you and only as authorized in this License Agreement. You may make one (1) archival copy of the
Software for backup purposes provided you affix to such copy all copyright, confidentiality, and
proprietary notices that appear on the original. Except as authorized under this paragraph, no copies
of the Program or any portions thereof may be made, in whole or in part, by you or any person under
your authority or control.
The Software and User Documentation are protected under copyright laws. The title to Software and
User Documentation shall remain solely with Juniper Networks and its suppliers.
Except as authorized above, you shall not: copy, in whole or in part, the Software or the related User
Documentation; modify, reverse assemble, reverse compile, or otherwise translate, dissemble, or
obtain source code for the Software or User Documentation, in whole or in part, or permit a third party
to do so; rent, lease, distribute, sell, or create derivative works of the Software; pledge, lease, rent,
sublicense or share its rights under this License Agreement; or, without Juniper Networks’ prior
written consent, assign or transfer its rights hereunder.
2. Juniper Networks' Rights. You agree that the Software, including the User Documentation,
embodies Juniper Networks' and its suppliers' and licensors' confidential and proprietary intellectual
property protected under U.S. copyright law and you will use your best efforts to maintain their
confidentiality. You further acknowledge and agree that Juniper Networks or its suppliers and
licensors own all right, title, and interest in and to the Software, including all intellectual property
rights therein. You shall take no action inconsistent with Juniper Networks' or its suppliers' ownership
of such Software. You shall not sublicense, assign, or otherwise disclose to any third party the
Software or any information about the operation, design, performance, or implementation of the
Software and User Documentation without prior written consent of Juniper Networks. You agree to
implement reasonable security measures to protect such confidential and proprietary information and
copyrighted material. This License Agreement does not convey to you an interest in or to the
Program, but only the limited right of use revocable in accordance with the terms of this License
Agreement.
3. License Fees. The license fees paid by you are paid in consideration of the license granted
under this License Agreement.
4. Term. This license is effective upon opening of the package(s) or use of the hardware containing
the Software, and shall continue until terminated. You may terminate this License at any time by
returning the Software, including any User Documentation, and all copies or portions thereof to
Juniper Networks. This License will terminate immediately without notice from Juniper Networks if
you breach any term or provision of this License. Upon such termination by Juniper Networks, you
1. If you and Juniper Networks, Inc., have executed another license agreement for the Program which
is now in effect, then such agreement (“Negotiated Agreement”) shall supersede this Software License Agreement and shall exclusively govern the use and license terms of the Program.
must return the Software, including any User Documentation, and all copies or portions thereof to
Juniper Networks. Termination of this License Agreement shall not prejudice Juniper Networks' rights
to damages or other available remedy.
5. Limited Software Warranty: Juniper Networks warrants, for your benefit alone, that for a period
of ninety (90) days from the date of shipment from Juniper Networks that the Software substantially
conforms to its published specifications.
The limited warranty extends only to you as the original licensee. Your exclusive remedy and the
entire liability of Juniper Networks and its suppliers under this limited warranty will be, at Juniper
Networks' option, repair or replacement of the Software, or refund of the amounts paid by you under
this License Agreement. You agree that this is your sole and exclusive remedy for breach by Juniper
Networks, its suppliers or its licensors of any warranties made under this License Agreement.
In no event does Juniper Networks warrant that the Software is error free or that you will be able to
operate the Software without problems or interruptions. Juniper Networks does not warrant: 1) that
the functions contained in the software will meet your requirements; 2) that the Software will operate
in the hardware or software combination that you may select; 3) that the operation of the Software
will be uninterrupted or error free; or 4) that all defects in the operation of the Software will be
corrected.
This warranty does not apply if the product: 1) has been altered, except by Juniper Networks; 2) has
not been installed, operated, repaired, or maintained in accordance with instruction supplied by
Juniper Networks; or 3) has been subjected to or damaged by improper environment, abuse, misuse,
accident, or negligence.
EXCEPT FOR THE WARRANTIES SET FORTH ABOVE, THE SOFTWARE IS LICENSED “AS IS,”
AND JUNIPER NETWORKS DISCLAIMS ANY AND ALL OTHER REPRESENTATIONS,
CONDITIONS, AND WARRANTIES, WHETHER EXPRESS, IMPLIED, OR STATUTORY,
INCLUDING, WITHOUT LIMITATION, ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE OR ANY WARRANTIES FOR NONINFRINGEMENT OR
ARISING FROM A COURSE OF DEALING, USAGE, OR TRADE PRACTICE. ANY AND ALL SUCH
WARRANTIES ARE HEREBY EXCLUDED TO THE EXTENT ALLOWED BY APPLICABLE LAW.
JUNIPER NETWORKS' SUPPLIERS AND LICENSORS DO NOT MAKE OR PASS ON TO YOU OR
ANY THIRD PARTY ANY EXPRESS, IMPLIED, OR STATUTORY WARRANTY OR
REPRESENTATION, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR ANY WARRANTIES FOR
NONINFRINGEMENT.
6. Proprietary Rights Indemnification. Juniper Networks shall at its expense defend you against
and, subject to the limitations set forth elsewhere herein, pay all costs and damages made in
settlement or awarded against you resulting from a claim that the Program as supplied by Juniper
Networks infringes a United States copyright or a United States patent, or misappropriates a United
States trade secret, provided that you: (a) provide prompt written notice of any such claim, (b) allow
Juniper Networks to direct the defense and settlement of the claim, and (c) provide Juniper Networks
with the authority, information, and assistance that Juniper Networks reasonably deems necessary
for the defense and settlement of the claim. You shall not consent to any judgment or decree or do
any other act in compromise of any such claim without first obtaining Juniper Networks’ written
consent. In any action based on such a claim, Juniper Networks may, at its sole option, either: (1)
obtain for you the right to continue using the Program, (2) replace or modify the Program to avoid the
claim, or (3) if neither (1) nor (2) can reasonably be effected by Juniper Networks, terminate the
license granted hereunder and give you a pro rata refund of the license fee paid for such Program,
calculated on the basis of straight-line depreciation over a five-year useful life. Notwithstanding the
preceding sentence, Juniper Networks will have no liability for any infringement or misappropriation
claim of any kind if such claim is based on: (i) the use of other than the current unaltered release of
the Program and Juniper Networks has provided or offers to provide such release to you for its then
current license fee, or (ii) use or combination of the Program with programs or data not supplied or
approved by Juniper Networks if such use or combination caused the claim.
7. Limitation of Liability. IN NO EVENT WILL JUNIPER NETWORKS OR ITS SUPPLIERS OR
LICENSORS BE LIABLE FOR ANY COST FOR SUBSTITUTE PROCUREMENT; SPECIAL,
INDIRECT, INCIDENTAL, PUNITIVE, EXEMPLARY, OR CONSEQUENTIAL DAMAGES; OR ANY
DAMAGES RESULTING FROM INACCURATE OR LOST DATA OR LOSS OF USE OR PROFITS
ARISING OUT OF OR IN CONNECTION WITH THE PERFORMANCE OF THE SOFTWARE, EVEN
IF JUNIPER NETWORKS HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
Juniper Networks' cumulative liability to you or any other party for any loss or damages resulting from
any claims, demands, or actions arising out of or relating to this License Agreement shall not exceed
the total fees paid to Juniper Networks for the Software.
8. Export Control. Software, including technical data, is subject to U.S. export control laws,
including the U.S. Export Administration Act and its associated regulations, and may be subject to
export or import regulations in other countries. You agree to comply strictly with all such regulations
and acknowledge that you have the responsibility to obtain licenses to export, re-export, or import
Software.
9. Government Licensees: If any Software or associated documentation is acquired by or on
behalf of a unit or agency of the United States government, the government agrees that such
Software or documentation is a “commercial item” as that term is defined in 48 C.F.R. 2.101,
consisting of “commercial computer software” or “commercial computer software documentation” as
such terms are used in 48 C.F.R. 12.212 of the Federal Acquisition Regulations and its successors
and 48 C.F.R. 227.7202-1 through 227.7202-4 of the DoD FAR Supplement and its successors. The
use, duplication, or disclosure by the United States government of technical, data, computer software
and documentation is subject to the restrictions set forth in FAR section 12.212(a), FAR section
52.227-14(g)(2), FAR section 52.227-19, DFARS section 252.227-7015(b), DFARS section
227.7202-1(a), and DFARS section 227.7202-3(a), as applicable. All United States government end
users acquire the Software with only the rights set forth in this License Agreement.
10. General: This License shall be governed by and construed in accordance with the laws of the
Commonwealth of Massachusetts, United States of America, as if performed wholly within the state
and without giving effect to the principles of conflict of law. Any dispute arising out of this Agreement
shall be referred to an arbitration proceeding in Boston, Massachusetts, in accordance with the
commercial arbitration rules of the American Arbitration Association (the “AAA”). If the parties cannot
agree upon an arbitrator, arbitration shall be conducted by a neutral arbitrator selected by the AAA
who is knowledgeable in electronics equipment manufacturing and software licensing. The parties
shall share the procedural costs of arbitration equally, and each party shall pay its own attorneys'
fees and other costs and expenses associated with the arbitration, unless the arbitrator decides
otherwise. The arbitrator's award shall be in writing and shall include a statement of reasons, but the
arbitrator shall not be permitted to award punitive or indirect damages. The arbitrator's decision and
award shall be final and binding and may be entered in any court having jurisdiction. The terms of
this section shall not prevent any party from seeking injunctive relief in any court of competent
jurisdiction in order to protect its proprietary and confidential information. If any term or provision
hereof is found to be void or unenforceable by a court of competent jurisdiction, the remaining
provisions of this License Agreement shall remain in full force and effect. This License Agreement
constitutes the entire agreement between the parties with respect to the use of the Software and
User Documentation and supersedes any and all prior oral or written agreements, discussions,
negotiations, commitments, or understandings. No amendment, modification, or waiver of any
provision of this License Agreement will be valid unless in writing and signed by the authorized
representative of the party against which such amendment, modification, or waiver is sought to be
enforced. The waiver by either party of any default or breach of this License Agreement shall not
constitute a waiver of any other or subsequent default or breach. This License Agreement shall be
binding upon the parties and their respective successors and permitted assigns.
Should you have any questions about this agreement, please contact:
Juniper Networks, Inc.
1194 North Mathilda Avenue
Sunnyvale, CA 94089
Attn: Contracts Administrator
Copying Release Files from One ERX System to Another . . . . . . . . . . . . . . . . . . E-14
Upgrading Systems That Are Operating with Two SRP Modules . . . . . . . . . . . E-15
xiii
ERX Edge Routers
Appendix F
Declaration of Conformity
Index
xiv
Contents
About This Guide
This ERX Installation and User Guide provides the information you
need to install and start the ERX edge router.
Note: If the information in the ERX Release Notes differs from the information in
this guide, follow the ERX Release Notes.
Your ERX system is shipped with the latest system software installed. If
you need to install a future release or reinstall the system software, refer to
the procedures in Appendix E, Installing ERX System Software.
ERX Edge Routers
Four models of the ERX edge router are available:
• ERX-1440 system
• ERX-1410 system
• ERX-705 system
• ERX-700 system
All models use the same software. For information about the differences
between the models, see Chapter 1, ERX System Overview.
In the ERX documentation, the term ERX-1400 series refers to both the
ERX- 14 40 sy stem and t he ERX-1410 s ystem. S i milarly, the te r m
ERX-700 series refers to both the ERX-705 system and the ERX-700
system. The terms ERX-1440 system, ERX-1410 system, ERX-705
system, and ERX-700 system refer to the specific models.
xvi
About This Guide
Audience
This guide is intended for experienced system and network specialists who
will configure a Juniper Networks ERX system in an Internet access
environment.
Conventions
Table 1, Tabl e 2, and Table 3 list all the conventions used in the ERX
documentation. Table 1 def ines notice icons. Tabl e 2 shows text
conventions used throughout the book, except for command syntax.
Table 3 provides command syntax conventions used primarily in the
ERXCommand Reference Guide. For more information about
command syntax, see ERX System Basics Configuration Guide,
Chapter 2, Command Line Interface.
Tab l e 1 Notice icons
IconMeaningDescription
Informational noteIndicates important features or instructions.
CautionIndicates that you may risk losing data or damaging your hardware.
WarningAlerts you to the risk of personal injury.
Tab l e 2 Text conventions (except for command syntax)
ConventionDescriptionExamples
Bold typefaceRepresents commands and
keywords in text.
Bold Courier typefaceRepresents text that the user must
type.
Key name in angle bracketsIndicates the name of a key on the
keyboard.
Key names linked with a plus sign
(+) in angle brackets.
Plain Courier typefaceRepresents information as displayed
Indicates that you must press two or
more keys simultaneously.
on your terminal’s screen.
• Command example:
Issue the clock source command.
• Keyword example:
Specify the keyword exp-msg.
user input
Press <Enter>.
Press <Ctrl+B>.
host1#show ip ospf 2
Routing Process OSPF 2 with
Router ID 5.5.0.250
Router is an Area Border
Router (ABR)
ERX Edge Routers
Tab l e 2 Text conventions (except for command syntax) (continued)
ConventionDescriptionExamples
Italics• Emphasize words.
• Identify variables.
• Identify chapter, appendix, and
book names.
Tab l e 3 Syntax conventions in Command Reference Guide
ConventionDescriptionExamples
Words in plain textRepresent keywords.terminal length
Words in italicsRepresent variables.mask, accessListName
Words separated by the | symbol Represent a choice to select one
keyword or variable to the left or
right of this symbol. (The keyword or
variable may be either optional or
required.)
Words enclosed in [ brackets ]Represent optional keywords or
variables.
Words enclosed in [ brackets ]*Represent optional keywords or
variables that can be entered more
than once.
Words enclosed in { braces }Represent required keywords or
variables.
• There are two levels of access,
user and privileged.
• clusterId, ipAddress.
• Appendix A, System Specifications.
diagnostic | line
[ internal | external ]
[ level1 | level2 | l1 ]*
{ permit | deny } { in | out }
{ clusterId | ipAddress }
Documentation
xvii
Documentation
The ERXInstallation Quick Start poster is shipped in the box with all
new systems. This poster provides the basic procedures to help you get the
system up and running quickly.
The document set contains the following books and online resources:
• ERXInstallation and User Guide – Provides the necessary procedures
for getting your system operational, including information on
installing, cabling, powering up, configuring your system for
management access, and general troubleshooting.
• ERXSystem Basics Configuration Guide – Describes planning and
configuring your network, managing the system, passwords, and
security, and configuring the system clock and virtual routers.
• ERXPhysical and Link Layers Configuration Guide – Describes
about configuring policy management and quality of service (QoS).
• ERXBroadband Access Configuration Guide – Provides information
about configuring remote access.
• ERXCommand Reference Guide – Contains important information
about all system commands implemented in the system software. Use
to look up command descriptions, command syntax, a command’s
related mode, or a description of a command’s parameters. It is
intended to be used with the ERX Configuration Guides.
• ERXProduct Overview Guide – Gives a thorough overview of the
system from a software and hardware perspective. It provides
illustrations and configuration examples that present the “big picture.”
• ERXRelease Notes – Contains information about features, changes,
known problems, and limitations. Provides final information that did
not make it into the documentation.
• ERXOnline Documentation CD – Provides an online version of this
guide and the documents listed above. The online documents contain
numerous links between guides, giving easy access to a vast amount of
technical information.
A complete list of abbreviations used in this document set, along with
their spelled-out terms, is provided in the ERX System Basics
Configuration Guide, Appendix A, Abbreviations and Acronyms.
Using the Online Documentation CD
To use the Online Documentation CD:
1Place the Online Documentation CD in your CD drive.
2Follow the instructions located on the inside cover of your CD jewel
case to install Acrobat Reader.
3From the Documentation folder on the CD, open the CDtips.pdf file
for information on using Adobe Acrobat Reader.
4From the Documentation folder on the CD, open the Welcome.pdf
file for access to the documentation set.
Comments About the Documentation
We encourage you to provide feedback, comments, and suggestions so
that we can improve the documentation to better meet your needs. Please
e-mail your comments to:
• techpubs-comments@juniper.net
Using the Online Documentation CD
ERX Edge Routers
xix
Along with your comments, be sure to indicate:
• Document name
• Document part number
• Page number
Contacting Customer Support
For technical support, contact Juniper Networks at support@juniper.net,
or at 1-888-314-JTAC (within the United States) or 408-745-2121 (from
outside the United States).
xx
About This Guide
ERX System Overview
This chapter provides information about the system.
Top icPage
The ERX System1-1
Where the ERX System Fits In1-6
ERX System Modules1-7
Network Management Tools1-11
Redundancy Features1-11
The Next Step1-15
The ERX System
1
The ERX edge routers are modular, carrier-class networking devices that
deliver performance, reliability, and service differentiation to both
business and consumer Internet users. The systems offer high port
density, low power consumption, and fully redundant Internet access
routing and edge aggregation. The ERX edge routers offer the complete
edge solution for IP-optimized carriers.
Four models of the ERX edge router are available:
• ERX-1440 system
• ERX-1410 system
• ERX-705 system
• ERX-700 system
CHAPTER 1
1-2
ERX System Overview
ERX-1400 Series
All models use the same software. However, the specific model
determines:
• The combination of line modules supported
• The conditions for line rate performance of line modules
In the ERX documentation, the term ERX-1400 series refers to both the
ERX-1440 system and the ERX-1410 system. The terms ERX-1440
system and ERX-1410 system refer to the specific models.
The ERX-1440 system manages an extremely high volume of network
traffic and uses a 40-Gbps switch route processor (SRP) module, either
the SRP-40G or SRP-40G+ module. (The SRP-40G+ module obsoletes
the SRP-40G module; however, the software continues to support both
modules.) In this model, all line modules operate at full wire speed
simultaneously.
The ERX-1410 system manages high levels of network traffic, and uses
the 10-Gbps SRP module (SRP-10G). You can configure the ERX-1410
system to enable the line modules either to operate at full line rate
performance or to allow line modules to operate at a rate dependent on
the resources available. The former option restricts the allowed
combinations of line modules. For information on configuring
performance of line modules, see ERX System Basics Configuration
Guide, Chapter 5, Managing Line Modules and SRP Modules.
Externally, the ERX-1440 chassis is the same as the ERX-1410 chassis
(see Figure 1-1 and Figure 1-2). Both systems contain fourteen vertical
slots to accommodate modules and have the same power requirements.
Installation procedures and operating procedures are identical for both
systems. All ERX systems use the same SRP I/O modules.
Note: The system may look different from the systems shown in the figures in this
chapter, depending on the line modules in the slots.
Internally, the ERX-1440 chassis differs from the ERX-1410 chassis, and
includes a special midplane for the 40-Gbps SRP module.
Line module (slot 0)
Redundant SRP module
The ERX System
ERX Edge Routers
1-3
Figure 1-1 ERX-1400 series front view
ERX
-1400
Top bezel
Ejector
Flange
SRP module
Line module (slot 13)
PCMCIA slot
Bottom bezel
Plenum
CHAPTER 1
1-4
ERX System Overview
Fan assembly
SRP I/O module
OC3 I/O module
(slot 13)
Power input module
Power switches
CT3 I/O module
(slot 0)
ERX-700 Series
Plenum
Figure 1-2 ERX-1400 series rear view
In the ERX documentation, the term ERX-700 series refers to both the
ERX-705 system and the ERX-700 system. The terms ERX-705 system
and ERX-700 system refer to the specific models.
The ERX-705 system is a compact, high-performance model that
manages low traffic density and uses a 5-Gbps SRP module, the
SRP-5G+ module. The ERX-700 system is a robust, high-density system
with less capacity than the ERX-1400 series. The ERX-700 system uses
either the SRP-10G module or a 5-Gbps SRP module, the SRP-5G
module. (Although the SRP-5G+ module obsoletes the SRP-5G module;
the software continues to support both modules.)
You can configure the ERX-700 series to enable the line modules either
to operate at full line rate performance or to operate at a rate dependent
on the resources available. For information about configuring
performance of line modules, see ERX System Basics Configuration
Guide, Chapter 5, Managing Line Modules and SRP Modules.
The ERX System
ERX Edge Routers
The ERX-705 chassis is the same as the ERX-700 chassis (see Figure 1-3
and Figure 1-4). The chassis contains seven slots to accommodate
modules. Installation procedures and operating procedures are identical
for both systems. All ERX systems use the same SRP I/O modules.
Note: The system may look different from the systems shown in the figures in this
chapter, depending on the line modules in the slots.
OC3 line module (slot 6)
CT3 line modules
Ejector
T3 ATM line modules
Redundant SRP module (slot 1)
SRP module (slot 0)
1-5
Flange
Figure 1-3 ERX-700 series front view
OC3 I/O module
CT3/T3 I/O modules
Power input module
Figure 1-4 ERX-700 series rear view
PCMCIA slot
SRP I/O modulePower switches
CHAPTER 1
1-6
ERX System Overview
Where the ERX System Fits In
Figure 1-5 and Figure 1-6 illustrate the position of the system as an edge
router in an end-to-end Internet network. Communications with the
system can take place over a variety of media. In Figure 1-5, the
customers are businesses using T1/T3 communication lines. In
Figure 1-6, the customers are using digital subscriber lines (DSLs) with a
DSL access multiplexer (DSLAM).
Desktop
Home office
Remote
access
router
Hub
Figure 1-5 ERX system communicating over T1/T3 lines
DSLAM
ERX system
T1/T3
ERX system
DS3
Internet
OC3
Core router
OC3
Internet
Desktop
Core
router
Desktop
Remote
access router
Hub
Remote
access router
Hub
Figure 1-6 ERX system communicating over DSL lines
ERX System Modules
The system supports an SRP module and a selection of line modules. You
can use any line module for access or uplink. Access line modules receive
traffic from low-speed circuits, and the system routes the traffic onto
higher-speed uplink line modules and then to the core of the Internet.
Each module connects to a corresponding I/O module via a passive
midplane. See Figure 1-7.
The front panel of each system module contains a collection of status
LEDs (light-emitting diodes). See Figure 1-8. For information about how
to interpret the LEDs, see Chapter 8, Troubleshooting.
Connection via
passive midplane
I/O modulesI/O modulesSRP I/O module
ERX System Modules
ERX Edge Routers
1-7
Line modules
Figure 1-7 Modules in the ERX-1400 series
Switch route processor (SRP)
with optional redundant SRP
Line modules
CHAPTER 1
1-8
ERX System Overview
SRP Module
The SRP module (see Figure 1-8) is a two-board assembly; both boards
connect to the system’s midplane and to each other:
• The fabric board is a switch fabric server that queues packets for the
line modules. The fabric server houses a flexible hardware queuing
resource that empowers IP QoS for each physical and logical interface,
providing weighted scheduling for preferential packet delivery.
• The system processor board is the dedicated processor that boots the
system, manages diagnostics, and supports routing protocol
processing.
An SRP module must be present for the system to boot. For details about
installing SRP modules, see Chapter 3, Installing ERX Modules. For
specifications of SRP modules, see Appendix B, Module Specifications.
Caution: Do not remove the SRP module while the system is running.
You can install two SRP modules of the same type in the system. If you
do, the first SRP module serves as the primary; the second as a
redundant module, which enhances the system’s reliability. See
Redundancy Features, later in this chapter.
Nonvolatile Storage
The PCMCIA slot on the front of the SRP module holds a Type II
PCMCIA nonvolatile storage (NVS) card. This card retains the system’s
configuration and software. See Figure 1-8. The PCMCIA card is factory
installed.
Ejector
Functional
status LEDs
Redundancy
status LEDs
Board reset button
Nonmaskable interrupt
(NMI) button
PCMCIA
NVS card
Ejector
Midplane connectors
Fabric board
ERX System Modules
ERX Edge Routers
System processor board
1-9
SRP I/O Module
Figure 1-8 SRP module
A single corresponding input/output module called the SRP I/O module
interfaces with one or two SRP modules through the system’s midplane.
The same SRP I/O works with all models of the SRP module. This I/O
module is two slots wide. See Figure 1-2 and Figure 1-4.
The SRP module provides standard craft management interfaces,
including:
• 10/100Base-T – a port for Ethernet management
• RS-232 – a port for VT100 management access
• External timing inputs – ports for external timing sources
For details about installing the SRP I/O module, see Chapter 3, Installing
ERX Modules.
CHAPTER 1
1-10
ERX System Overview
Line Modules
Line modules process data from different types of network connections.
For information about the available line modules and which SRP
modules support specific line modules, see Appendix B, Module
Specifications.
Figure 1-9 shows a representative line module. For details about installing
line modules, see Chapter 3, Installing ERX Modules.
Packet Classification
Each line module supports packet classification on ingress. A
classification engine on the line module matches specific fields (such as
source and destination IP address, source and destination port, and
protocol), the ingress IP interface, layer 2 fields, or some combination of
these against user-configured filters at wire speed.
Midplane connectors
Power supply units
Ejector
Functional
status LEDs
Interface
status LEDs
Board reset button
NMI button
Ejector
Figure 1-9 Representative line module
I/O Modules
Most line modules have a corresponding input/output (I/O) module that
provides the physical interconnection to the network. Insert each I/O
module in the back of the system, directly behind its corresponding line
module. For information about which line modules pair with which I/O
modules, see Appendix B, Module Specifications. For details about
installing I/O modules, see Chapter 3, Installing ERX Modules.
Network Management Tools
You can use different management tools to configure the system to meet
the specific networking requirements.
CLI Management
The CLI provides fully developed and automated configuration and
status functionality through a local RS-232 port, an Ethernet connection,
or Telnet through any reachable network. For a full discussion of the CLI,
see ERX System Basics Configuration Guide, Chapter 2, Command
Line Interface.
Network Management Tools
ERX Edge Routers
1-11
SNMP MIB Management
The system offers a complete SNMP interface for configuration, status,
and alarm reporting. The system supports both Standard and Enterprise
MIBs (Management Information Bases). The ERX Enterprise MIB is
ASN.1 notated for easy importing into third-party SNMP management
applications. For more information, see ERX System Basics
Configuration Guide, Chapter 3, Configuring SNMP.
NMC-RX Device Management System
The NMX-RX application provides a global method of managing all
edge routers, line modules, and ports.
Redundancy Features
The system has the following redundancy features:
SRP Modules
The SRP module uses a 1:1 redundancy scheme. When two SRP
modules of the same type are installed in the system chassis, one acts as a
primary and the second as a standby. Both SRP modules share a single
CHAPTER 1
1-12
ERX System Overview
SRP I/O module located in the rear of the chassis. If the primary SRP
fails, the redundant SRP module assumes control without rebooting or
initializing itself. (As a consequence, if you upgrade software, you must
copy the software to the redundant SRP and reboot it.) For information
about configuring and managing SRP module redundancy, see ERX
System Basics Configuration Guide, Chapter 5, Managing Line Modules
and SRP Modules.
After you install two SRP modules, the modules negotiate for the primary
role. A number of factors determine which module becomes the primary;
however, preference is given to the module in the lower-numbered slot.
The SRP modules record their latest roles and retain them the next time
you switch on the system. For information about installing SRP modules,
see Chapter 3, Installing ERX Modules.
NVS Cards
If you have two SRP modules installed in a system, you can use NVS
cards of different capacities on the SRP modules. The effective capacity
of the higher-capacity NVS card will equal that of the lower-capacity
NVS card. For information about installing NVS cards, see Chapter 3,
Installing ERX Modules.
When you install new NVS cards or SRP modules, you must issue the
synchronize command to match the file system of the NVS card on the
redundant SRP module with the file system of the NVS card on the
primary SRP module. (The NVS card on the redundant SRP module will
hereafter be referred to as the redundant NVS card; the NVS card on the
primary SRP module will hereafter be referred to as the primary NVS
card.)
If the capacity of the primary NVS card is equal to or smaller than that of
the redundant NVS card, the system copies all the files from the primary
NVS card to the redundant NVS card. However, if the capacity of the
primary NVS card exceeds that of the redundant NVS card, the system
creates an invisible synchronization reserve file on the primary NVS
card, provided that there is enough space for the f ile.
The purpose of the synchronization file is to prevent the creation of data
that will not fit on the redundant NVS card. The file contains no useful
data, and is not visible when you view the files in NVS. The size of the file
is equal to the difference in capacities of the two NVS cards. For example,
if the primary NVS card has a capacity of 224 MB, and the redundant
NVS card has a capacity of 220 MB, the size of the synchronization file is
4 MB, and only 220 MB of space is available on the primary NVS card.
Line Modules
Redundancy Features
ERX Edge Routers
If there is not enough space on the primary NVS card to create the
synchronization reserve file, the synchronize command fails, and you
see a warning message on the console. To resolve this issue, either delete
unwanted files from the primary NVS card or replace the redundant
NVS card with a higher-capacity NVS card.
The ERX system supports line module redundancy for several line
modules. For details about which line modules support redundancy, see
Appendix B, Module Specifications. In this scheme, an extra line access
module in a group of identical line modules provides redundancy in case
of line module failure. To use this feature, you need a:
• Spare line module
• Redundancy midplane
• Redundancy I/O module
A redundancy midplane may cover 2–6 slots. It provides additional
connectivity that enables the spare line module to assume control of the
I/O module associated with any failed line module in the redundancy
group. The spare I/O module provides connectivity from the spare line
module to the redundancy midplane.
1-13
The process by which the system switches to the spare line module is
called switchover. When switchover occurs, the system:
1Breaks the connection between the primary I/O module and the
primary line module.
2Connects the primary I/O module to the spare line module via the
redundancy midplane and redundancy I/O module.
Protocol processing then takes place on the spare line module.
Figure 1-10 shows the data flow when a spare line module becomes
active.
CHAPTER 1
1-14
ERX System Overview
1
A packet arrives at the primary
I/O module.
2
The packet passes along the
redundancy midplane from the
primary I/O module to the
redundancy I/O module.
3
The packet passes from the
redundancy I/O module to the
spare line module.
4
The spare line module
processes the packet.
Figure 1-10 Data flow when a spare line module is active
3
4
Spare
line module
Redundancy
I/O module
Primary
line module
Primary
I/O module
2
1
Midplane
Redundancy
midplane
Power
For information about installing modules for line module redundancy, see
Chapter 3, Installing ERX Modules. For information about configuring
and managing SRP module redundancy, see ERX System Basics
Configuration Guide, Chapter 5, Managing Line Modules and SRP
Modules, for more information.
The system provides a power architecture that distributes redundant
–48 VDC feeds through the system to each line module, SRP module,
and fan module where DC-to-DC converters provide local conversion to
the required secondary voltages. The system design prevents a failure of
any one of the power components from causing any other component in
the system to fail.
Fans
The Next Step
The Next Step
ERX Edge Routers
Forced air-cooling keeps the temperature of the ERX modules and
components within normal operating limits. In the ERX-1400 series, six
cooling fans are located in a tray at the top of the system (see Figure 7-5).
In the ERX-700 series, four cooling fans are located in a tray on one side
of the system (see Figure 7-7).
The system monitors the temperature of each module. If the temperature
of a module exceeds the maximum limit, the system immediately goes
into thermal protection mode. In this mode, the modules consume
extremely low levels of power. For information about troubleshooting
high operating temperatures, see Chapter 8, Troubleshooting.
The fan tray has two redundant converters that power the fans (for the
ERX-1400 series, a –24 V, 50 W converter; for the ERX-700 series, a
–12 V, 15 W converter). If one converter fails, the other takes over. In
addition, the system software reports an alarm if any of the fans
overrotate or underrotate or if one of the converters fails.
1-15
Go to Chapter 2, Installing the ERX System.
CHAPTER 1
1-16
ERX System Overview
Installing the ERX
System
This chapter provides procedures for installing the ERX-1400 series and
the ERX-700 series either as freestanding devices or in a distribution
rack.
Top icPage
Before You Begin2-1
Unpacking the ERX-1400 Series2-1
Unpacking the ERX-700 Series2-4
Freestanding Installation2-5
Rack-Mounted Installation2-6
The Next Step2-10
2
Before You Begin
Before you begin unpacking the system, be sure you have the following
items:
• A No. 2 Phillips screwdriver
• A utility knife
Unpacking the ERX-1400 Series
The ERX-1400 series come boxed, bolted, and strapped to a skid. See
Figure 2-1.
For your convenience, we recommend that you unpack the ERX system
in the location where you want to install it.
CHAPTER 2
2-2
Installing the ERX System
Shipping
straps
Shipping
carton
Clips
Figure 2-1 Packaged ERX-1400 series
Shipping
skid
To unpack the ERX-1400 series:
1Cut the two straps that secure the carton to the skid. See Figure 2-1.
2Open the carton from the top.
3Remove the box of accessories that sits on top of the router.
4Unlock the four plastic clips that hold the box to the skid by
squeezing them in their center and pulling out. See Figure 2-1.
5Lift the carton off the router. See Figure 2-2.
Unpacking the ERX-1400 Series
ERX Edge Routers
Shipping
carton
2-3
L-brackets
Clips
Figure 2-2 Lifting the carton off an ERX-1400 series
ERX-1400
system
Clips
Shipping
skid
6Use a Phillips screwdriver to remove the three screws (10-32 x 3/8 in)
that attach each of the two L-brackets to the router.
7To move the router more easily from the skid, unscrew one of the
L-brackets from the skid by removing the three screws that attach it
to the skid. See Figure 2-3.
CHAPTER 2
2-4
Installing the ERX System
L-brackets
Hex bolts
Figure 2-3 Removing an L-bracket
Shipping
skid
8Depending on where you want to position the system, proceed to
Freestanding Installation or Rack-Mounted Installation, later in this
chapter.
Unpacking the ERX-700 Series
The ERX-700 series come boxed but not attached to a skid.
For your convenience, we recommend that you unpack the ERX system
in the location where you want to install it.
To unpack the ERX-700 series:
1Open the carton from the top.
2Remove the box of accessories that sits on top of the system.
3Before you remove the unit from its carton, proceed to Freestanding
Installation or Rack-Mounted Installation, later in this chapter.
Freestanding Installation
This section provides instructions for installing the system on a table top
or in any other freestanding mode. See Appendix D, Preparing Your Site,
for information about site requirements.
ERX-1400
Freestanding Installation
ERX Edge Routers
Flange
2-5
Figure 2-4 ERX-1400 series front view
Warning: Two people are required to lift an ERX system. The system is extremely
heavy.
To install the system as a freestanding device:
1One person should stand on the left side of the system, and the other
should stand on the right side.
2Grasp the lower back of the unit with one hand and the front f lange
(see Figure 2-4) with the other.
3Bend your knees and carefully lift the unit into position.
4Carry the system to the location where it will operate.
Caution: Leave enough space around the system for adequate ventilation. See
Appendix A, System Specifications, for details.
5Position the router with easy access to the connections that it needs
for power, local communications, and remote communications.
Note: Connectors are located on the I/O modules and the power input module.
See Figure 2-5. You install these modules from the rear of the router. See
Chapter 4, Cabling the ERX System, for cabling installation procedures.
CHAPTER 2
2-6
Installing the ERX System
OC3 I/O
connectors
CT3 I/O
connectors
Power
connectors
Console
connector
Power input
Figure 2-5 ERX-700 series rear view
Rack-Mounted Installation
We recommend that you use a standard EIA distribution rack. Refer to
Rack Requirements in Appendix D, Preparing Your Site, for detailed
rack information. Before installing the systems in the rack, consider the
following guidelines:
• You can install up to three ERX-1400 series systems in a single 84-inch
rack.
Installing multiple systems in a single rack allows you to maximize
your available space. An ERX-1400 series system has a plenum that
allows air to circulate between systems.
• You can install an ERX-1400 series system and an ERX-700 series
system together in the same rack.
If you install an ERX-700 series system above an ERX-1400 series
system in the same rack, you must install a plenum between the
ERX-700 series system and the ERX-1400 series system so that the air
can circulate between the systems. See Figure 2-6. This plenum is
available from Juniper Networks.
module
Fast Ethernet
connector
SRP I/O
connectors
If you install an ERX-1400 series system above an ERX-700 series
system, there is no need to install a plenum between the units because
the ERX-1400 series system has one at its base.
Safety Guidelines
Rack-Mounted Installation
ERX Edge Routers
Observe the following safety guidelines when mounting the system in a
rack.
Rack Installation Warning: Install equipment in the rack from the bottom upward.
This will maintain the stability of the rack and reduce the chance of the rack’s
tipping over.
Heavy Equipment Warning: Three people are required to install the ERX system
in a rack: two to lift the system into position and one to screw it to the rack. The
system is extremely heavy.
Branch Circuit Warning: Evaluate the overall loading of the branch circuit before
you install any equipment into a rack.
Ground (Earth) Warning: Connect the ERX system or rack to ground (earth), and
ensure that a reliable grounding path is maintained in the rack.
Lightning Activity Warning: Do not work on the system or connect or disconnect
cables during lightning activity.
DC Power Disconnection Warning: Before powering on the ERX system,
remove power from the DC circuit by deactivating the circuit breaker on the panel
board that services the DC circuit.
2-7
Installation
Servicing Unit Warning: Before servicing the ERX system, turn off the power.
Jewelry Removal Warning: Remove jewelry (including rings, necklaces, and
watches) before working on equipment that is connected to power lines. Metal
objects heat up when connected to power and ground and can cause serious
burns or become welded to the terminals.
Metal Objects Warning: Do not insert any metal object, such as a screwdriver,
into an open slot or the backplane. Doing so may cause electric shock and serious
burns.
To complete the installation of the system in a rack, you need:
• A Phillips screwdriver
• Eight 10-32 x 3/8 Phillips screws (provided with the system) for each
system to be installed
Warning: Three people are required to install the ERX system in a rack: two to lift
the system into position and one to screw it to the rack. The system is extremely
heavy.
CHAPTER 2
2-8
Installing the ERX System
To install the system in the rack:
1On the rack, identify and mark the holes that you want to use for
mounting the system.
2One person should stand on the left side of the system, and another
should stand on the right side.
3Grasp the lower back of the unit with one hand and the lower front
of the unit (see Figure 2-4) with the other hand.
4Bend your knees and carefully lift the unit into position in the rack.
5With the help of the third person, align the holes in the system’s
flanges with the holes in the rack, and hold the system in position.
6Starting at the bottom, the third person should screw the f lange on
each side of the system into the four holes on each side of the rack.
7Connect the necessary cables (see Chapter 4, Cabling the ERX
System, for instructions on installing the cables).
Figure 2-6 illustrates a distribution rack with one ERX-1410 system and
two ERX-700 systems installed.
Rack-Mounted Installation
2-9
ERX Edge Routers
3CO
3TC
3TC
3TC
3TC
ERX-700 system
PPRRSS
P
P
R
R
S
S
Plenum
ERX-1400 system
CT3
CT3
CT3
CT3
CT3
CT3
SRP
SRP
SRP
SRP
OC3
CT3
CT3
CT3
CT3
OC3
OC3
CT3
CT3
ERX-700 system
CT3
CT3
SRP
SRP
SRP
SRP
Figure 2-6 Rack with ERX-700 systems and an ERX-1410 system
CHAPTER 2
2-10
Installing the ERX System
The Next Step
After you finish installing the system:
• If the system was delivered with the modules already installed, go to
Chapter 4, Cabling the ERX System, for instructions on connecting
cables.
• If you need to install any modules, go to Chapter 3, Installing ERX
Modules.
Installing ERX Modules
This chapter describes how to physically install and remove ERX
modules. If the modules you want are already installed in the system, you
can skip this chapter and go to Chapter 4, Cabling the ERX System.
For information about managing installed modules, see ERX System
Basics Configuration Guide, Chapter 5, Managing Line Modules and
SRP Modules.
Top icPage
Overview3-1
Protecting Modules and Slots3-4
Safety Guidelines3-6
Installing SRP I/O and SRP Modules3-6
Installing Line Modules and Their I/O Modules3-10
Removing a Module3-13
Installing Components for Line Module Redundancy3-14
The Next Step3-17
3
Overview
In the ERX-1400 series, modules mount vertically in a chassis with 14
slots, whereas in the ERX-700 series, modules mount horizontally in a
chassis with 7 slots. See Figure 3-1. For information about compatibility
between lines modules and SRP modules, see Table B- 1 in Appendix B,
Module Specifications.
CHAPTER 3
3-2
Installing ERX Modules
Slot Groups
ERX-700 seriesERX-1400 series
Figure 3-1 Orientation of line modules in the ERX-700 series and ERX-1400 series
For details about available line modules, see Appendix B, Module
Specifications.
The slots in the ERX-700 series’ and the ERX-1410 system’s chassis are
divided into groups. The number of groups and number of slots per
group depend on the system. There are no slot groups in the ERX-1440
system.
Slot Groups for the ERX-1410 System
A slot group in the ERX-1410 system comprises three adjacent chassis
slots. The groups for the ERX-1410 system consist of the following slots
(Figure 3-2):
• Slot group 1 – slots 0 through 2
• Slot group 2 – slots 3 through 5
• Slot group 3 – slots 8 through 10
• Slot group 4 – slots 11 through 13
Slots 6 and 7 are reserved for the SRP modules.
Chassis slots
0123 54678910 1311 1 2
E
C
T
T
T
1
1
1
CT1
CT1 CT1
M
P
T
C
T
3
3
Y
SRP
OC3
CT3
SRP
SRP
SRP
E
C
O
C
C
E
C
O
M
P
C
T
3
Y
OC3
C
M
P
T
Y
C
T
T
T
3
3
3
CT3
CT3
CT3
ERX Edge Routers
Overview
3-3
Slot
group 2
{
{
Slot
group 1
Figure 3-2 ERX-1400 slot groups
Slot
group 3
{
Slot
group 4
{
Slot Groups for the ERX-700 Series
A slot group in the ERX-700 series comprises one slot or two adjacent
slots. The groups for the ERX-700 series consist of the following slots
(Figure 3-3):
• Slot group 1 – slots 2 and 3
• Slot group 2 – slot 4
• Slot group 3 – slot 5
• Slot group 4 – slot 6
Slots 0 and 1 are reserved for the SRP modules.
CHAPTER 3
3-4
Installing ERX Modules
.
Figure 3-3 ERX-700 series slot groups
Combinations of Line Modules
For information about allowed combinations of line modules, see ERX
System Basics Configuration Guide, Chapter 5, Managing Line Modules
and SRP Modules.
Replacing and Managing Modules
For information about software procedures associated with replacing and
managing modules, see ERX System Basics Configuration Guide,
Chapter 5, Managing Line Modules and SRP Modules.
OC3
Empty
E3 ATM
CE1
CE1
OC3
CE1 E3 ATM
CE1
SRP
SRP
SRP
SRP
Slot group 4
Slot group 3
Slot group 2
Slot group 1
Hot-Swapping Modules
The ERX-700 series and ERX-1400 series support hot-swapping of
modules. Hot-swapping allows you to add or remove a module without
powering down the system.
Required Tools and Safety Items
You need the following tools to install a line module:
• A Phillips screwdriver
• An ESD (electrostatic discharge) wrist strap
Protecting Modules and Slots
To protect the modules and slots, observe the following guidelines when
installing modules:
Caution: When handling modules, use an antistatic wrist strap connected to the
ERX system’s ESD grounding jack. This action helps to protect the module from
damage by electrostatic discharge.
Protecting Modules and Slots
ERX Edge Routers
On the ERX-1400 series, the grounding jacks are inside the front bezel in
the lower-left area of the front of the chassis (Figure 3-4) and in the
upper-right corner on the rear of the chassis. On the ERX-700 series, the
grounding jack is in the lower-right corner on the rear of the chassis.
Caution: Always handle the module by its edges. Do not touch the components,
pins, leads, or solder connections.
Caution: Be sure to cover every empty slot with a blank faceplate to protect the
system from dust or other foreign substances and to ensure proper system cooling.
CT3CT3
3-5
Order of Installation
ESD grounding jackAnti-static wrist strap
Figure 3-4 Connecting the wrist strap to the ERX-1400 series (front)
Before you attempt to install or replace a module (inserted in the front of
the chassis), the corresponding I/O module (inserted in the rear of the
chassis) should already be in place. The system diagnostics run when a
module is installed in a chassis slot. If the corresponding I/O module is
not present, the diagnostics fail, and you need to remove and reinsert the
module.
CHAPTER 3
3-6
Installing ERX Modules
Safety Guidelines
Before and during the installation process, observe the following
precautions:
Lightning Activity Warning: Do not work on the system or connect or disconnect
cables during lightning activity.
DC Power Disconnection Warning: Before powering on the ERX system,
remove power from the DC circuit by deactivating the circuit breaker on the panel
board that services the DC circuit.
Jewelry Removal Warning: Remove jewelry (including rings, necklaces, and
watches) before working on equipment that is connected to power lines. Metal
objects heat up when connected to power and ground and can cause serious
burns or become welded to the terminals.
Metal Objects Warning: Do not insert any metal object, such as a screwdriver,
into an open slot or the backplane. Doing so may cause electric shock and serious
burns.
Repair Warning: Never attempt to repair parts of modules yourself. Only trained
customer service personnel are authorized to service parts. Call Juniper Networks
Customer Service to make arrangements to return defective modules for repair.
See Appendix F, Customer Service.
Installing SRP I/O and SRP Modules
You should install SRP modules only in chassis slots 6 and 7 of the
ERX-1400 series and slots 0 and 1 of the ERX-700 series.
Note: Install the SRP I/O module before you install the SRP module; otherwise, the
ERX system diagnostics fail.
Installing an SRP I/O Module
To install an SRP I/O module:
1Connect the antistatic wrist strap to the ESD grounding jack on your
ERX system.
Caution: When handling modules, use an antistatic wrist strap connected to the
ERX system’s ESD grounding jack. This action helps to protect the module from
damage by electrostatic discharge.
2With a Phillips screwdriver, loosen the top and bottom captive screws
securing the blank faceplate covering the empty slot. See Figure 3-5.
3Remove the faceplate.
counterclockwise
Figure 3-5 Removing the blank faceplate
Installing SRP I/O and SRP Modules
ERX Edge Routers
3-7
Caution: Always handle the module by its edges. Do not touch the components,
pins, leads, or solder connections.
4Remove the SRP I/O module from its antistatic bag.
5Position the module as follows:
• For the ERX-1400 series, position the module vertically so that
the labeling is upright.
• For the ERX-700 series, position the module horizontally so that
the alarm leads are to the right.
6Position the module into the chassis by placing it between the guides
of the selected slot, and slide the module until it stops.
Figure 3-6 shows how to install an SRP I/O module in the ERX-1400
series.
CHAPTER 3
3-8
Installing ERX Modules
Figure 3-6 Installing an SRP I/O module in the ERX-1400 series
7Tighten the module’s captive screws using a Phillips screwdriver.
Turn both screws several times before tightening them completely to
allow the module to sit correctly.
Installing an SRP Module
To install an SRP module:
1Connect the antistatic wrist strap to the ESD grounding jack on your
ERX system.
Caution: When handling modules, use an antistatic wrist strap connected to the
ERX system’s ESD grounding jack. This action helps to protect the module from
damage by electrostatic discharge.
2Choose the chassis slot where you want to insert the module.
For the ERX-1400 series, use slot 6 or 7; for the ERX-700 series, use
slot 0 or 1.
3With a Phillips screwdriver, loosen the top and bottom screws that
secure the blank faceplate covering the empty chassis slot.
4Remove the faceplate.
Installing SRP I/O and SRP Modules
ERX Edge Routers
Caution: Always handle the module by its edges. Do not touch the components,
pins, leads, or solder connections.
5Remove the SRP module from its antistatic bag.
6Make sure that the ejectors are in position 1, as shown in Figure 3-7.
2
1
3-9
1
2
Figure 3-7 Positioning the ejectors
7Position the module as follows:
• For the ERX-1400 series, position the module vertically so that
the labeling is upright.
• For the ERX-700 series, position the module horizontally so that
the labeling is to the right.
8Position the module in the chassis by placing it between the guides of
the selected slot, and slide the module until it stops.
The module stops sliding when the ejectors make contact with the
front of the chassis. Figure 3-8 shows how to install an SRP module
in the ERX-1400 series.
CHAPTER 3
3-10
Installing ERX Modules
Ejector in open position
ERX-1400
Figure 3-8 Installing an SRP module
9Insert the module into the backplane by simultaneously depressing
both ejectors (as shown in Figure 3-7) and exerting forward pressure
on the module.
10 Tighten the module’s captive screws using a Phillips screwdriver.
Turn both screws several times before tightening them completely to
allow the module to sit correctly.
Installing Line Modules and Their I/O Modules
This section describes the procedures for installing line and I/O modules.
Note: Install the I/O module before you install the corresponding line module;
otherwise, the ERX system diagnostics fail, and after the line module has tried to
reboot, its status will be “inactive” when you issue a show version command.
Installing a Line or I/O Module
To install a module:
1Connect the antistatic wrist strap to the ESD grounding jack on your
ERX system.
Caution: When handling modules, use an antistatic wrist strap connected to the
ERX system’s ESD grounding jack. This action helps to protect the module from
damage by electrostatic discharge.
2Choose the slot where you want to insert the module.
For the ERX-1400 series, you can install line modules in slots 0
through 5 and slots 8 through 13; for the ERX-700 series you can
choose slots 2 through 6.
3With a Phillips screwdriver, loosen the top and bottom screws that
secure the blank faceplate covering the empty chassis slot, as shown
in Figure 3-5.
4Remove the faceplate.
Caution: Always handle the module by its edges. Do not touch the components,
pins, leads, or solder connections.
Installing Line Modules and Their I/O Modules
ERX Edge Routers
3-11
5Remove the module from its antistatic bag.
6Make sure that the ejectors are in position 1, as shown in Figure 3-7.
7Position the module as follows:
• For the ERX-1400 series, position the module vertically so that
the labeling is upright.
• For the ERX-700 series, position the module horizontally so that
the labeling is to the right.
8Guide the module into the chassis by placing it between the guides of
the selected slot, and slide the module until it stops.
The module stops sliding when the ejectors make contact with the
front of the chassis. Figure 3-9 shows how to install an I/O module
and a line module in the ERX-1400 series.
CHAPTER 3
3-12
Installing ERX Modules
Ejector in open position
Line ModuleI/O Module
Figure 3-9 Installing a module in the ERX-1400 series
9Insert the module into the midplane by simultaneously depressing
both ejectors (as shown in Figure 3-7) and exerting forward pressure
on the module.
10 Tighten the module’s captive screws using a Phillips screwdriver.
Turn both screws several times before tightening them completely to
allow the module to sit correctly.
Removing a Module
To remove a module:
Caution: If you do not use the halt command before removing or powering down
an SRP, the system’s NVS card may become corrupted.
1Enter the halt command.
Caution: When handling modules, use an antistatic wrist strap connected to the
ERX system’s ESD grounding jack. This action helps to protect the module from
damage by electrostatic discharge.
2Connect the antistatic wrist strap to the ESD grounding jack on your
3Use a screwdriver to loosen the thumb screws located at the top and
Removing a Module
ERX Edge Routers
See ERX System Basics Configuration Guide, Chapter 5, Managing
Line Modules and SRP Modules for information about the halt
command.
ERX system.
bottom of the module panel, as shown in Figure 3-5.
3-13
4Raise the ejector handles located at the top and bottom of the
module so that they are in position 2, as shown in Figure 3-7.
Caution: Always handle the module by its edges. Do not touch the components,
pins, leads, or solder connections.
5Carefully slide the module out of the chassis, as shown in Figure 3-9.
6Place the module in its antistatic bag.
7Cover the empty chassis slot with a blank faceplate. Tighten the
faceplate’s top and bottom captive screws using a Phillips
screwdriver, as shown in Figure 3-10. Turn both screws several times
before tightening them completely.
CHAPTER 3
3-14
Installing ERX Modules
clockwise
Figure 3-10 Installing the blankfaceplate
If you remove an I/O module and not the corresponding line module, the
line module reboots, and then its status will be “inactive” when you issue
a show version command. If you remove a line module and do not
delete the corresponding configuration, the status of the line module will
be “not present” when you issue a show version command.
Installing Components for Line Module Redundancy
The ERX system allows a spare line module to provide redundancy for a
group of identical line modules. For line module redundancy to operate,
you must install:
• The line modules, including the spare line module
• The redundancy midplane
• The I/O modules, including the redundancy I/O module
Warning: Do not insert any metal object, such as a screwdriver, or place your hand
into an open slot or the backplane when the ERX system is on. Remove jewelry
(including rings, necklaces, and watches) before working on equipment that is
connected to power lines. These actions prevent electric shock and serious burns.
Caution: When handling modules, use an antistatic wrist strap connected to the
ERX system’s ESD grounding jack, and hold modules by their edges. Do not touch
the components, pins, leads, or solder connections. These actions help to protect
modules from damage by electrostatic discharge.
Installing the Line Modules
To install the line modules in a redundancy group:
1Install the spare line module in the lowest-numbered slot of the
redundancy group.
2Install the other line modules in the remaining slots. (See Installing
Line Modules and Their I/O Modules, earlier in this chapter).
Installing the Redundancy Midplane
To install the redundancy midplane in a redundancy group:
Caution: If you do not use the halt command before removing or powering down
an SRP, the system’s NVS card may become corrupted.
1Enter the halt command.
Installing Components for Line Module Redundancy
ERX Edge Routers
3-15
See ERX System Basics Configuration Guide, Chapter 5, Managing
Line Modules and SRP Modules for information about the halt
command.
Warning: Turn off the ERX system before you install the redundancy midplane.
Working inside the ERX system when it is on can lead to electric shock and serious
burns.
2Turn off the power switches located on the power input module in
the rear of the system (see Figure 3-11).
3Remove the I/O modules from the slots that the redundancy
midplane will span.
4Place the redundancy midplane in the chassis so that it rests against
the guides below the chassis midplane (see Figure 3-11).
5Align the screw holes in the redundancy midplane with the screw
holes in the guides so that the midplane covers the slots for the
redundancy group.
6Using a Phillips screwdriver and the screws provided, loosely attach,
but do not tighten, the redundancy midplane to the guides.
CHAPTER 3
3-16
Installing ERX Modules
7Carefully insert an I/O module in one slot to ensure that the
redundancy midplane is aligned correctly; then tighten the screws.
A misaligned redundancy midplane can result in bent pins on the
boards and poor contact between the I/O modules and the
redundancy midplane.
Chassis midplane
Redundancy midplane
Figure 3-11 Installing a redundancy midplane
Installing the I/O Modules
To install the I/O modules in a redundancy group:
1Install the redundancy I/O module in the lowest-numbered slot of
the redundancy group.
Caution: When setting up a redundancy group with line modules, be sure to install
the redundancy I/O module in the lowest-numbered slot of the redundancy group.
It is possible to install the redundancy I/O module in other slots; however, doing so
may damage other I/O modules connected to the redundancy midplane.
2Install the corresponding I/O module for the line module of each slot
in the redundancy group. (See Installing a Line or I/O Module,
earlier in this chapter.)
Power input module
Power switches
Verifying the Installation
To verify that the installation is complete:
1Turn on the power switches.
The system will reboot.
2Issue the show redundancy command, and verify that the display
shows the redundancy hardware.
The Next Step
After you have installed the modules and are confident that they sit
correctly in their respective chassis slots, you are ready to connect cables.
For instructions on installing cables for your ERX system, see Chapter 4,
Cabling the ERX System.
The Next Step
ERX Edge Routers
3-17
CHAPTER 3
3-18
Installing ERX Modules
Cabling the ERX
System
This chapter describes how to cable the ERX system. Before you cable
the system, ensure that you have completed all installation instructions
identified in previous chapters.
Top icPage
Before You Begin4-1
Cabling Your ERX System4-2
Safety Guidelines4-3
Cabling the Power Input Module4-4
Cabling the SRP I/O Module4-7
Cabling I/O Modules4-10
The Next Step4-17
4
Before You Begin
Before you cable the ERX system, read Cabling Recommendations in
Appendix D, Preparing Your Site.
CHAPTER 4
4-2
Cabling the ERX System
Cabling Your ERX System
Cabling the system takes only a few minutes. You need these items:
• A 1/8" flathead screwdriver – to connect the alarm leads
• A 3/8" wrench or 3/8" nut-driver – to loosen and tighten hex nuts on
Power A and Power B leads
• A No. 2 Phillips screwdriver – to remove the power input module
cover
• Two ground wires – we recommend a minimum of 10-AWG ground
wire with a ring-style terminal.
• A #10 kep nut to connect the ground (earth) wire to the ground
terminal.
We recommend that you use shielded cables where appropriate and
perform the cabling tasks in this order:
1Familiarize yourself with the module ports. See Figure 4-1.
2Ensure that you have the cables and wires needed to complete each
cabling procedure.
3Read and understand all safety warnings.
4Connect the power cables from the power source to the power input
module.
5Connect cables to the SRP I/O module.
6Connect cables to the line I/O modules.
Safety Guidelines
ALARMS
SRP I/O
EXTERNAL TIMINGCONSOLE
10/100
BASE T
RS-232
T1 120 OHM
CLOCK IN
A
B
T
G
R
T
G
R
E1 75 OHM
CLOCK IN
A
B
MINOR
MAJOR
CRITICAL
+
-
+
-
+
-
CT3
I/O
MULTI
MODE
OC3
I/O
CT1
I/O
CT3
I/O
CT3
I/O
THIS PRODUCT IS EQUIPPED WITH
TWO POWER FEEDS. DISCONNECT
BOTH FEEDS PRIOR TO SERVICE.
POWER A POWER B
POWER APOWER B
-48VDC-48VDCRTNRTN
-48VDC RTN -48VDC RTN
WARNING!
NO OPERATOR ACCESSIBLE
COMPONENTS. AUTHORIZED
SERVICE PERSONNEL ONLY.
!
O
OFF
|
ON
O
OFF
|
ON
CT3
I/O
ERX Edge Routers
4-3
Alarm leads
SRP I/O module
(slot positions 6 and 7)
External timing ports (Europe)
CT3 I/O module
(slot 5)
TX
CT1 I/O module
(slot 10)
External timing ports (North America)
RX
OC3 I/O module
(slot 13)
TX
RX
CT3 ports
TX
RX
10/100 BASE T port
RS-232 terminal port
Power input module
Power A and Power B
on/off switches
OC3 ports
(MMF or SMF)
RX
TX
RX
TX
CT1 ports
Ejector
Captive screw
Safety Guidelines
Blank faceplate
Figure 4-1 Cabling your ERX system
ERX-1400 rear view
Power A and Power B
input connectors
Ground terminals
Observe the following guidelines when cabling your ERX system.
Ground (Earth) Warning: Connect either the freestanding ERX system or the rack
to ground (earth), and ensure that a reliable grounding path is maintained in the
rack.
CHAPTER 4
4-4
Cabling the ERX System
Lightning Activity Warning: Do not work on the system or connect or disconnect
cables during lightning activity.
DC Power Disconnection Warning: Before powering on the ERX system,
remove power from the DC circuit by deactivating the circuit breaker on the panel
board that services the DC circuit.
Servicing Unit Warning: Before servicing the ERX system, turn off the power.
Jewelry Removal Warning: Remove jewelry (including rings, necklaces, and
watches) before working on equipment that is connected to power lines. Metal
objects heat up when connected to power and ground and can cause serious
burns or weld the metal object to the terminals.
Metal Objects Warning: Do not insert any metal object, such as a screwdriver,
into an open slot or the backplane. Doing so may cause electric shock and serious
burns.
Note: If you plan on using a cable-management bracket, install it before you begin
cabling your ERX system. Cable-management brackets are helpful to keep
network interface cables untangled and orderly and to prevent cables from
hindering access to other slots.
Cabling the Power Input Module
Input power is supplied to the system by two redundant and independent
–48 VDC line feeds. If one line fails, the other can carry the full load of
the system. See Appendix A, System Specifications for the power
requirements for the ERX system.
Table 4-1 identifies the power input module cabling requirements.
Tabl e 4 - 1 Power input module cables/wires needed
Cable/WireFromTo
One 10-AWG
ground wire
Two 10-AWG wire
leads
Two 10-AWG wire
leads
Power input module ground
terminal
Power input module Power A
–48 VDC and RTN leads
Power input module Power B
–48 VDC and RTN leads
Termination ground
Appropriate leads on power
source No. 1
Appropriate leads on power
source No. 2
Cabling the Power Input Module
ERX Edge Routers
Follow the procedure in this section to connect power cables to the
system. Refer to Figure 4-2 as needed.
Caution: Before you begin this procedure, ensure that both Power A and Power B
switches are in the OFF position.
1Loosen the four screws from the clear power input module cover.
2Remove the cover by sliding it upward so that the screw heads line
up with the holes in the cover.
3Set the cover and screws aside for later use.
4Connect the ground wire to the ground terminal on the lower
portion of the power input module, and secure it with a #10 kep nut.
Note: We recommend a minimum of 10-AWG ground wire with a ring-style
terminal.
5Connect the other end of the ground wire to the appropriate ground
termination lead.
Warning: Be sure the power source is turned off and the ERX system is turned off
before continuing with this procedure.
4-5
6With the wrench or nut driver, loosen the 3/8" hex nuts from the
bottom –48 VDC and RTN leads of Power A, and connect a
10-AWG wire to each.
7With the wrench or nut driver, tighten the hex nuts on both leads.
8Attach the opposite end of Power A’s wire leads to the appropriate
leads on your power source.
Note: To provide redundancy, Power A and Power B leads should not terminate at
the same power source.
9Repeat Steps 6–8 for Power B.
10 Reattach the clear power input module cover that you removed in
step 1 by securing the four screws.
CHAPTER 4
POWER APOWER B
POWER B
-48VDCRTN
-48VDCRTN
O
OFF
|
ON
O
OFF
|
ON
WITH
POWER A POWER
POWER B
-48VDCTNRTN
O
OFF
|
ON
O
OFF
|
ON
PO
-48VDC
-48VDC
OFF
4-6
Cabling the ERX System
THIS PRODUCT IS EQUIPPED WITH
TWO POWER FEEDS. DISCONNECT
BOTH FEEDS PRIOR TO SERVICE.
POWER A POWER B
|
ON
O
OFF
POWER APOWER B
-48VDC-48VDCRTNRTN
|
ON
O
OFF
Power A
leads
-48VDCRTN-48VDCRTN
WARNING!
NO OPERATOR ACCESSIBLE
!
COMPONENTS. AUTHORIZED
SERVICE PERSONNEL ONLY.
Ground
Power B
leads
Figure 4-2 Power input module
Power input
module cover
Cabling the SRP I/O Module
The next step in cabling the system is to connect cables to your SRP I/O
module. See Figure 4-3.
Note: The alarm function on the SRP I/O module is currently not implemented.
Cable connections to your SRP I/O module are divided into two sections:
external timing ports and console ports. Table 4- 2 shows the
specifications for each section.
Tabl e 4 - 2 SRP I/O ports
Port Description
External Timing
Ports
Console Ports• One 10/100Base-T Ethernet management port with an RJ-48C
Cabling the SRP I/O Module
ERX Edge Routers
• Two 3-pin wire-wrap posts for US external clock sources;
primary (A) and secondary (B)
• Two BNC connectors for E1 clock sources; primary (A) and
secondary (B)
connector
• One RS-232 port with a DB-9 connector for VT100 management
access
4-7
External Timing Ports
Two external clock source input ports provide a method of ensuring that
the system’s clock timing remains synchronized with the network’s system
clock. The primary clock is labeled A; the secondary, redundant clock is
labeled B. Use the connector type appropriate for your location:
• Two 75-ohm E1 2.048-Mbps inputs with BNC connectors
• Two 100-ohm T1 inputs with three pin wire-wrap connectors. Pins are
Note: Use shielded cables to connect the external clock sources to the clock
source input ports.
labeled T (Tip), G (Ground), and R (Ring). We recommend using
26-AWG wire minimum.
CHAPTER 4
4-8
Cabling the ERX System
SRP I/O
26-AWG wire
BNC (Europe)
Wire-wrap connectors
(North America, Japan)
RJ-45
ALARMS
EXTERNAL TIMINGCONSOLE
MINOR
MAJOR
CRITICAL
E1 75 OHM
CLOCK IN
T1 100 OHM
CLOCK IN
10/100
BASE T
+
-
+
-
+
-
A
B
A
B
T
G
R
T
G
R
DB-9
Figure 4-3 SRP I/O module
RS-232
Console Ports
Cabling the SRP I/O Module
ERX Edge Routers
To connect the clock source input ports:
1Depending on the connector type, complete one of the following
tasks:
• E1: Attach the BNC connector to Clock A’s External Timing
port.
• T1: Wrap the “Tip” wire on pin marked T of Clock A’s External
Timing port, the “Ground” wire on G pin, and the “Ring” wire
on R pin.
Note: You can use a wire-wrap gun to attach wires to pins.
2Attach the opposite end of the External Timing cable or wires into
your network’s clock source A.
3Repeat steps 1 and 2 for the Clock B connections.
There are two ports located in the Console section (as shown in
Figure 4-3) that allow management access.
4-9
• The 10/100Base-T Ethernet port accepts an RJ-45 (male)
connector. This port provides an out-of-band connection. (We
ship an Ethernet cable with the system.)
• The RS-232 port accepts a DB-9 (female) connector. This port
allows direct CLI access.
Follow this procedure to connect the Console ports. Refer to Figure 4-3 as
needed.
1Insert the male RJ-45 connector into the 10/100Base-T port until it
clicks into place.
2Attach the opposite end of the cable to your appropriate network
device.
3Insert the female DB-9 connector into the RS-232 port until it is
secure.
4Hand-tighten the DB-9 connector screws.
5Attach the opposite end of the cable to your terminal (VT100/ANSI).
See Chapter 5, Accessing the ERX System, for more information about
management access.
CHAPTER 4
4-10
Cabling the ERX System
Cabling I/O Modules
Cabling BNC Connectors
The following sections describe how to cable I/O modules with different
types of connectors. For information about the connectors on the
different line modules, see Appendix B, Module Specifications.
To cable I/O modules with BNC connectors:
1Insert the RX male BNC connector into the selected port.
2Terminate the other end in the appropriate network interface, such
as a multiplexer (MUX) device.
3Repeat steps 1 and 2 for the TX connector.
4Repeat steps 1–3 for all ports.
.
CT3
RX
I/O
Cabling HSSI
Connectors
BNC
TX
Figure 4-4 I/O module with BNCs
TX
Port 0
RX
TX
Port 1
RX
TX
Port 2
RX
The HSSI I/O module uses a standard 50-pin HSSI connector.
Caution: Do not terminate HSSI connections with SCSI connectors. Although
SCSI connectors look very similar to HSSI connectors, using SCSI connectors on
HSSI connections may lead to data loss.
Cabling I/O Modules
ERX Edge Routers
To cable I/O modules with HSSI connectors:
1Insert the HSSI connector into the selected port.
2Terminate the other end in the appropriate network connection.
3Repeat steps 1 and 2 for the other ports.
HSSI-3
I/O
0
4-11
Figure 4-5 HSSI I/O module with 50-pin HSSI connector
Cabling RJ-45 Connectors
To cable I/O modules with RJ-45 connectors:
1Insert the RJ-45 connector into the selected port.
2Terminate the other end in the appropriate network connection.
3Repeat steps 1 and 2 for the other ports.
1
CHAPTER 4
4-12
Cabling the ERX System
Figure 4-6 I/O module with RJ-45 connector
Cabling RJ-48C Connectors
To cable I/O modules with RJ-48C connectors:
1Insert the RJ-48C connector into the selected port.
2Terminate the other end in the appropriate network interface, such
RJ-45
as a multiplexer (MUX) device.
10/100
FE-2
I/O
Port 0
Port 1
3Repeat steps 1 and 2 for all ports.
.
RJ-48C
Figure 4-7 I/O module with RJ-48C connectors
CE1
I/O
Port 0
Port 1
Port 2
Port 3
Port 4
Cabling LC Duplex Connectors
In accordance with EN60825-1, Safety of Laser Products - Part 1:
Equipment Class, Requirements, and User’s Guide (2001), multimode
I/O modules with LC connectors are defined as follows:
CLASS 1 LED PRODUCT.
In accordance with EN60825-1, Safety of Laser Products - Part 1:
Equipment Class, Requirements, and User’s Guide (2001), single-mode
I/O modules with LC connectors are defined as follows:
CLASS 1 LASER PRODUCT.
To cable I/O modules with LC duplex connectors:
Warning: Do not look directly into LC-style fiber connectors. The fiber-optic laser
used in single-mode fiber (SMF) meets the regulatory requirements for casual
exposure to the eye; however, looking directly into a laser can cause eye damage.
Warning: IEC 825, Class 1 laser fiber connectors are for connection only to Class
1 laser devices.
1Insert the TX male fiber connector into the selected port.
Cabling I/O Modules
ERX Edge Routers
4-13
2Terminate the other end in the appropriate network connection.
3Repeat steps 1 and 2 for the RX fiber connector.
4Repeat steps 1–3 for the remaining ports.
CHAPTER 4
4-14
Cabling the ERX System
Fiber
RX
TX
OC3
I/O
Figure 4-8 I/O module with LC full duplex connectors
Cabling SC Duplex Connectors
In accordance with EN60825-1, Safety of Laser Products - Part 1:
Equipment Class, Requirements, and User’s Guide (2001), multimode
I/O modules with SC connectors are defined as follows:
CLASS 1 LED PRODUCT.
In accordance with EN60825-1, Safety of Laser Products - Part 1:
Equipment Class, Requirements, and User’s Guide (2001), single-mode
I/O modules with SC connectors are defined as follows:
CLASS 1 LASER PRODUCT.
To cable I/O modules with SC duplex connectors:
RX
TX
RX
TX
Port 0
Port 1
SINGLE
Warning: Do not look directly into SC-style fiber connectors. The fiber-optic laser
used in single-mode fiber (SMF) meets the regulatory requirements for casual
exposure to the eye; however, looking directly into a laser can cause eye damage.
Cabling I/O Modules
ERX Edge Routers
Warning: IEC 825, Class 1 laser fiber connectors are for connection only to
Class 1 laser devices.
1Insert the TX male fiber connector into the selected port.
2Terminate the other end in the appropriate network connection.
3Repeat steps 1 and 2 for the RX fiber connector.
4Repeat steps 1–3 for the remaining ports.
OC3
I/O
Fiber
TX
RX
4-15
Figure 4-9 I/O module with SC full duplex connectors
Cabling SMB Connectors
To cable I/O modules with SMB connectors:
1Pull back the metal sheath on the TX cable’s SMB connector.
2Insert the TX cable’s SMB connector into the selected port.
3Release the metal sheath on the TX cable’s SMB connector.
RX
TX
RX
TX
Port 0
Port 1
SINGLE
CHAPTER 4
4-16
Cabling the ERX System
4Terminate the other end in the appropriate network connection.
5Repeat steps 1–4 for the RX cable’s SMB connector.
6Repeat steps 1–5 for the remaining ports.
CT3/T3
12
RX
I/O
SMB
Figure 4-10 I/O module with SMB connectors
Cabling X.21/V.35 Connectors
Four cables are available for the X.21/V.35 I/O modules:
• X.21 DCE cable (terminated with 8 female X.21 connectors)
• X.21 DTE cable (terminated with 8 male X.21 connectors)
• V.35 DCE cable (terminated with 8 female V.35 connectors)
• V.35 DTE cable (terminated with 8 male V.35 connectors)
Each 200-pin proprietary socket on the I/O module provides connections
to 8 V.35 or X.21 ports. The remote end of the cable is terminated with
either 8 X.21 connectors or 8 V.35 connectors. The cable you attach to
the port on the I/O module determines whether the connection is X.21 or
V.35 and DCE or DTE.
TX
TX
RX
TX
RX
TX
RX
Port 0
Port 1
Port 2
To cable I/O modules with X.21/V.35 connectors:
1Insert the X.21/V.35 connector into the selected socket.
2Terminate the other end in the appropriate network connection.
3Repeat steps 1 and 2 for the other socket.
The Next Step
ERX Edge Routers
X.21/V.35
I/O
4-17
Figure 4-11 X.21/V.35 module with 50-pin X.21/V.35 connector
Cabling Redundant Ports
Some modules have redundant ports. See Appendix B, Module
Specifications for specifications. Cabling both ports provides a redundant
path to the ERX module.
Caution: For port redundancy to operate correctly on a GE I/O module that
supports SFPs, both the primary and redundant ports on an ERX GE I/O module
must use the same type of SFP.
The Next Step
After you have cabled the system, check that all connections go the right
places and are secure. Then proceed as follows:
• If you need to set up a console to communicate with the system, go to
Chapter 5, Accessing the ERX System.
• If you have already set up your console, go to Chapter 6, Powering Up
the System.
CHAPTER 4
4-18
Cabling the ERX System
Accessing the ERX
System
This chapter provides information on the various ways you can access the
system to manage it. Managing your router includes both configuring
and monitoring it. For basic information on the management of the
system, see ERX System Basics Configuration Guide, Chapter 4,
Managing the System.
Top icPage
Setting Up Management Access5-1
Console Port Setup5-2
Telnet Setup5-4
SNMP5-6
The Next Step5-6
5
Setting Up Management Access
Before you power up the system, you must set up a management console.
The console allows you to communicate with the system during the
power-up process and to manage the system using the command line
interface (CLI).
You can manage and monitor the system by accessing it in the following
ways:
• Connect a console (PC, Macintosh, or UNIX workstation) directly to
the system’s RS-232 serial port (DTE).
• Connect the system’s 10/100Base-T port on the SRP I/O module to an
Ethernet network, and run Telnet from a remote console.
CHAPTER 5
5-2
Accessing the ERX System
Console Port Setup
Using HyperTerminal
For initial access to the system, you need to physically connect your
console directly to the system’s RS-232 port. This connection allows you
to use the CLI to set an IP address on the system. Once you configure the
IP address, you can access the system remotely (for example, via Telnet).
You can connect a console (PC, Macintosh, or UNIX workstation)
directly to the system via the RS-232 terminal port on the SRP I/O
module. When you connect a console directly to the system, you can
configure the system without an IP address.
To communicate with the system, you must have a terminal emulation
program running on your PC or Macintosh. You can use any terminal
emulation program (such as HyperTerminal). A UNIX workstation can
use the emulator TIP.
If your console uses a version of Microsoft Windows (such as Windows 95
or Windows NT 4.0) that supports the HyperTerminal application, you
can access the system via Hyperterminal.
1Click the Start button and select Programs, Accessories, and
HyperTerminal.
2In the HyperTerminal window, select HyperTerminal.
3In the Connection Description window, enter a name for your router
(for example, erx1400) in the Name field.
4Select any icon to represent your terminal emulation, and click OK.
5In the Connect To dialog screen, in the Connect using field, select
the appropriate COM port to use (for example, COM1), and click
OK.
6In the COM1 Properties screen, select the following settings:
• Bits per second: 9600
• Data bits: 8
• Parity: None
• Stop bits: 1
• Flow control: Xon/Xoff
7Click OK.
Connecting Directly to the ERX System
When you connect a console directly to the system, use a cable
appropriate for your terminal connector. The cable must have a female
DB-9 connector to attach to the RS-232 port on the system. To connect a
console directly to the system:
1Connect the female DB-9 connector to the RS-232 port on the
system’s SRP I/O module. See Figure 5-1.
2Connect the crossover adapter connector to your PC’s serial port.
Console Port Setup
5-3
ERX Edge Routers
ERX-1400 system
CT3
CT3
CT3
CT3
I/O
I/O
I/O
I/O
CT3
CT3
CT3
CT3
CT3
CT3
CT3
CT3
I/O
I/O
I/O
I/O
I/O
I/O
CT3
CT3
CT3
CT3
I/O
I/O
I/O
I/O
I/O
I/O
ERX-700 system
CT3
CT3I/O
I/O
CT3
CT3
I/O
I/O
10/100 Base-T port
RS-232 port
Figure 5-1 ERX-700 series and ERX-1400 series management ports
3Power up the system.
When you power up the system, the CLI appears on your console’s
screen. The system is now in User Exec mode, and you can begin
configuration. For more information on using the CLI and
configuring the system, see the ERX System Basics Configuration
Guide.
Note: Direct access through the RS-232 serial port allows you to monitor the
system as it boots.
Assigning an IP Address
When your console is ready to communicate with the system, power up
the system (see Chapter 6, Powering Up the System), and set an IP
CHAPTER 5
5-4
Accessing the ERX System
address for the system. The system powers up in User Exec mode. To
assign an IP address:
1Enter the enable command at the User Exec prompt.
host1>enable
host1#
The system is now in Privileged Exec mode.
2Set an IP address on the Ethernet interface:
• Substitute the slot number where the SRP module is located for
the slotnumber variable.
• Use an IP address valid for the system.
host1#configure terminal
Enter configuration commands, one per line. End with CNTL/Z.
3Continue to configure the system’s parameters as needed.
Telnet Setup
After you have assigned an IP address to the system, you can
communicate remotely by running Telnet over an Ethernet network. See
the next section, Tel ne t S e tu p .
When you have configured an IP address for the system, you can run
Telnet on your console to access the system through its Ethernet port. To
connect the console to the system:
1Connect an Ethernet cable (RJ-45) to the system’s 10/100Base-T
(RJ-45) port on the SRP I/O module.
2Connect the other end of the cable to the appropriate Ethernet
network for an out-of-band connection.
Before you can access the system with Telnet, you must either configure a
password for Telnet access or disable the password requirement from the
management console. In the following example, you disable the
password.
1Enter the enable command.
host1>enable
host1#
Telnet Setup
ERX Edge Routers
The system is now in Privileged Exec mode.
2Enter the configure command.
host1#configure terminal
Enter configuration commands, one per line. End with CNTL/Z.
host1(config)#
The system is now in Global Configuration mode.
3Enter the line command.
host1(config)#line vty 0 4
host1(config-line)#
The system is now in Line Configuration mode.
4Disable the password.
host1(config-line)#no login
Note: In this example, you disabled the password requirement, but you can
choose to set a password instead. See the ERX System Basics Configuration
Guide, Chapter 6, Passwords and Security for information on setting a password.
5-5
5Run Telnet from the management console (on the same Ethernet
network as the system).
6Enter the IP address of the system to open the Telnet session.
The User Exec prompt appears when the Telnet session to the system
is established.
host1>
7Enter the enable command.
host1>enable
host1#
The system is now in Privileged Exec mode.
8Enter the configure command.
host1#configure terminal
Enter configuration commands, one per line. End with CNTL/Z.
host1(config)#
The system is now in Global Configuration mode, from which you
can configure the system. See ERX System Basics Configuration
Guide, Chapter 2, Command Line Interface.
CHAPTER 5
5-6
Accessing the ERX System
SNMP
The Next Step
Caution: Do not change the IP address for the Ethernet interface that you are
using to communicate with the system. If you change the address, you will lose the
Telnet session.
The system supports Simple Network Management Protocol (SNMP), a
standard management protocol for IP networks. You can configure the
system as an SNMP agent.
As an SNMP agent, the system provides access to management
information that it maintains. See the ERX System Basics Configuration
Guide, Chapter 3, Configuring SNMP for information on SNMP. See
the ERX Command Reference Guide for the commands that are
available for configuring the system as an SNMP agent.
Go to Chapter 6, Powering Up the System.
Powering Up the
System
This chapter provides instructions for powering up the system and
information on electrical specifications.
Top icPage
Before You Power Up the System6-1
Powering Up6-2
Status LEDs6-3
Powering Down6-3
The Next Step6-4
Before You Power Up the System
6
Before powering up the system, you should complete the tasks shown in
Table 6-1. Refer to the appropriate chapters in this guide for information
about these tasks.
Tabl e 6 - 1 Installation tasks
Installation TaskReference
Install an SRP module and SRP I/O module in slot 6 or 7 in
the ERX-1400 series chassis or slot 0 or 1 in the ERX-700
series chassis.
Install the line modules and their corresponding I/O modules
in the system.
Cover unused slots with blank faceplates.Chapter 3, Installing
Warning: Be sure the power source is turned off and the system is turned off
before performing the next task.
Chapter 3, Installing
ERX Modules
Chapter 3, Installing
ERX Modules
ERX Modules
CHAPTER 6
6-2
Powering Up the System
Powering Up
Tabl e 6 - 1 Installation tasks (continued)
Installation TaskReference
Connect DC power (–48 VDC) to the power input lugs on the
power input module.
Connect a management console to the system.Chapter 5, Accessing
(Optional) Connect the 10/100Base-T port to the network.Chapter 5, Accessing
Chapter 4, Cabling the
ERX System
the ERX System
the ERX System
This procedure assumes that the system is already connected to a DC
power source. See Chapter 4, Cabling the ERX System.
For specifications on the electrical requirements for the system, see
Appendix A, System Specifications. For details on the power consumed
by the different ERX modules, see Appendix B, Module Specifications.
Branch Circuit Caution: Evaluate the overall loading of the branch circuit before
you install any equipment into a rack.
To p owe r u p t h e s y st em :
1Turn on the power switches located on the power input module in
the rear of the system. See Figure 6-1.
2Monitor the LEDs on the front of the SRP modules to verify that the
system is booting properly. See Tabl e 8- 2 in Chapter 8,
Tro u b l e s ho oting.
When the prompt appears on the system console, the system is in
User Exec mode:
host1>
3Enter the enable command to access the Privileged Exec mode:
host1>enable
host1#
In Privileged Exec mode you can begin to configure the system. See
the ERX System Basics Configuration Guide, Chapter 2, Command
Line Interface for more information.
Status LEDs
ERX Edge Routers
6-3
Power input module
Figure 6-1 ERX-1400 series power switches
Initialization Sequence
Each ERX line module is initialized independently. As a result, the CLI
on the SRP module may become available before the line modules have
completed initialization. Commands relating to a line module may fail if
the module has not completed initialization. The show version
command can be used to display line module status. Do not enter
commands for a line module until its state is “online.”
Power switches
Status LEDs
Powering Down
For information on the system’s LEDs, see Chapter 8, Troubleshooting.
If you need to power down or remove the SRP module, first enter the
halt command to temporarily suspend the system’s operation. See ERX
System Basics Configuration Guide, Chapter 4, Managing the System for
more information.
Caution: If you do not use the halt command before removing or powering down
an SRP, the system’s NVS card may become corrupted.
If you shut down the system improperly, it will run an investigation of the
file allocation table (FAT) next time it reboots.
CHAPTER 6
6-4
Powering Up the System
The Next Step
If you have problems powering up the system, go to Chapter 8,
Troubleshooting , for help.
Maintaining the ERX
System
This chapter describes the procedures that you must complete to
maintain the ERX system and its components. Other maintenance
procedures must be performed by an authorized Juniper Networks
technician.
Top icPage
Required Tools and Items7-1
Storing Modules and Components7-2
Upgrading NVS Cards on SRP Modules7-2
Replacing SFPs on GE I/O Modules7-5
Cleaning the System7-9
Replacing Fan Trays7-9
7
Required Tools and Items
You will need the following tools and other items to replace ERX
components.
• Flathead and Phillips screwdrivers
• Insulated adjustable wrench
• Antistatic wrist strap
• Antistatic bags (or other protective packaging to hold components)
CHAPTER 7
7-2
Maintaining the ERX System
Storing Modules and Components
Caution: Failure to store electronic modules and components correctly may lead
to damage of these items.
Retain the packaging in which a module or component was shipped, and
use this packaging to store the item. Modules are shipped in antistatic
bags and protective packaging. Components, such as transceivers and
NVS cards, are shipped in antistatic plastic containers within an antistatic
padded box. Follow these guidelines for storing modules and components:
• Store each module in a separate antistatic bag.
• Store components in an antistatic plastic container. Some of these
containers can accommodate several components in separate
compartments.
• Do not store multiple modules or components in an antistatic bag or
container where they can touch other items.
• (Optional) Store the item in its antistatic bag or container within the
protective packaging or padded box that the item was shipped in.
Upgrading NVS Cards on SRP Modules
This section describes how to install higher-capacity NVS cards on SRP
modules. The procedure you use depends on the number of SRP modules
in the system. A new NVS card will contain the software release you
ordered.
Note: The new NVS card must contain the same software release that you are
running on the system.
Upgrading a System That Contains One SRP Module
If the system contains only one SRP module, you must power down the
system before you upgrade the NVS card. To upgrade the NVS card on a
system that contains one SRP module:
Caution: If you do not use the halt command before removing or powering down
an SRP, the system’s NVS card may become corrupted.
1Enter the halt command.
See ERX System Basics Configuration Guide, Chapter 5, Managing
Line Modules and SRP Modules for information about the halt
command.
Upgrading NVS Cards on SRP Modules
Warning: Do not insert any metal object, such as a screwdriver, or place your hand
into an open slot or the backplane when the ERX system is on. Remove jewelry
(including rings, necklaces, and watches) before working on equipment that is
connected to power lines. These actions prevent electric shock and serious burns.
Caution: When handling modules, use an antistatic wrist strap connected to the
ERX system’s ESD grounding jack. This action helps to protect the module from
damage by electrostatic discharge.
2Connect the antistatic wrist strap to the ESD grounding jack on your
ERX system.
3Power down the system (see Chapter 6, Powering Up the System).
4Remove the SRP I/O module.
5Replace the NVS card on the SRP module (see Replacing an NVS
Card, later in this chapter).
6Power up the system (see Chapter 6, Powering Up the System).
Upgrading a System That Contains Two SRP Modules
In a system that contains two SRP modules, you can upgrade the NVS
cards on the SRP modules without powering down the system.
7-3
ERX Edge Routers
Warning: Do not insert any metal object, such as a screwdriver, or place your hand
into an open slot or the backplane when the ERX system is on. Remove jewelry
(including rings, necklaces, and watches) before working on equipment that is
connected to power lines. These actions prevent electric shock and serious burns.
Caution: When handling modules, use an antistatic wrist strap connected to the
ERX system’s ESD grounding jack. This action helps to protect the module from
damage by electrostatic discharge.
To upgrade the NVS cards on the SRP modules in a system that contains
two SRP modules:
1Connect the antistatic wrist strap to the ESD grounding jack on your
ERX system.
2Reboot the redundant SRP module.
host1#reload slot 6
3Immediately remove the redundant SRP module from the chassis.
4Replace the NVS card on this SRP module (see Replacing an NVS
Card, later in this chapter).
5Reposition the SRP module into the chassis.
CHAPTER 7
7-4
Maintaining the ERX System
Replacing an NVS Card
6When this SRP module is available, synchronize the SRP modules.
host1#synchronize
7When the SRP modules are synchronized, reboot the SRP module
that you upgraded.
host1#reload slot 6
8When this SRP module is available, synchronize the SRP modules.
host1#synchronize
9When the SRP modules are synchronized, force the redundant SRP
module to take over from the primary SRP module.
host1#srp switch
10 Immediately remove the former primary SRP module.
11 Repeat steps 4–8 for the former primary SRP module.
To replace an NVS card on an SRP module:
1Obtain an antistatic container for the NVS card you will remove (see
Storing Modules and Components, earlier in this chapter).
2With a small flathead screwdriver, remove the faceplate from the
NVS card slot on the SRP module (see Figure 7-1).
3Use the screwdriver to depress the button next to the NVS card (see
Figure 7-1).
This action releases the NVS card.
Replacing SFPs on GE I/O Modules
ERX Edge Routers
NVS card
Faceplate
Release button
Figure 7-1 NVS card slot on SRP module
4Remove the NVS card and place it in the antistatic container.
5Insert the higher-capacity NVS card into the slot.
7-5
6Push the higher-capacity NVS card as far as you can in the slot.
When you push the card far enough, it will click into place.
7Replace the faceplate on the NVS card slot.
Replacing SFPs on GE I/O Modules
This section describes how to replace small form-factor pluggable
transceivers (SFPs) on Gigabit Ethernet (GE) modules that support these
devices. A range of SFPs that support different optical modes (multimode
and single mode) and cabling distances is available. You can replace the
SFPs without disabling the interfaces or removing the module from the
system.
Warning: Do not insert any metal object, such as a screwdriver, or place your hand
into an open slot or the backplane when the ERX system is on. Remove jewelry
(including rings, necklaces, and watches) before working on equipment that is
connected to power lines. These actions prevent electric shock and serious burns.
Caution: When handling electronic components, use an antistatic wrist strap
connected to the system’s ESD grounding jack, and hold components by their
edges. Do not touch, pins, leads, or solder connections. Store components in
antistatic bags. These actions help to protect modules from damage by
electrostatic discharge.
CHAPTER 7
7-6
Maintaining the ERX System
Removing SFPs
To remove the SFPs:
1Obtain an antistatic container for the SFPs you will remove (see
Storing Modules and Components, earlier in this chapter).
2Put the antistatic wrist strap on your wrist, and connect the strap to
the ESD grounding jack on the system.
3Disconnect the cables from one of the SFPs on the module.
4Identify the release mechanism for the SFP.
Different SFPs use different release mechanisms (see Figure 7-2).
Possible release mechanisms include:
• A button that you press inward
• A ring that you press inward
• A bar that you pull sideways, then outward
• A tab that you pull sideways, then outward
Transceiver
Release bar, button,
or tab
Figure 7-2 Possible release mechanisms on the SFP
5Release the SFP and pull it out of the slot.
6Place the SFP in an antistatic bag.
7If you are using the redundant port on the ERX GEI/O module,
Release bar, button,
or tab
Release ring
Module faceplate
repeat steps 3 through 6 for the other SFP.
Caution: For port redundancy to operate correctly, both the primary and redundant
ports on an ERX GE I/O module must use the same type of SFP.
Installing SFPs
Replacing SFPs on GE I/O Modules
ERX Edge Routers
To install SFPs:
1Put the antistatic wrist strap on your wrist, and connect the strap to
the ESD grounding jack on your system.
2Identify the following items on the SFP (see Figure 7-3):
• The connection circuitry on the base
• The cable connectors on the front
The cable connectors will be protected by a dust cover.
Connection
circuitry on
base
Cable connectors
on front
7-7
Figure 7-3 Example of SFP
Caution: Be sure to position the SFP correctly before you install it.
3Hold the SFP so that:
• The connection circuitry is adjacent to the TX and RX markings
on the module’s faceplate.
• The front will be visible when you install the SFP.
For a picture of the correct orientation, see Figure 7-4.
CHAPTER 7
7-8
Maintaining the ERX System
TX and RX markings
on I/O module
Connection circuitry
on base of SFP
Figure 7-4 Installing an SFP on an ERX GE I/O module
4Insert the SFP as far as you can into the I/O module.
The SFP should slide smoothly into the I/O module and should click
into place. If the SFP does not slide smoothly into the I/O module,
check that the orientation of the SFP is correct.
5Gently pull the SFP to confirm that it is inserted correctly.
The SFP should not move when you pull it. If the SFP comes out of
the slot when you pull it, repeat step 4.
6Remove the dust cover that protects the ports.
7Connect the new cables to the SFP.
If you are using the redundant port on the ERX GE I/O module, repeat
steps 2 through 7 for the other port.
Verifying the Installation
When you have replaced the SFPs and connected the cables, issue the
show interface gigabitEthernet command for each interface to check
that the interface is operational (up).
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.