Julabo LH 40, Presto LH 40 Operating Manual

Page 1
19512761.doc Print date: 13.06.07
Operating Manual
High Dynamic Temperature System
with integrated programmer
Presto
®
LH 40
Printed in Germany Changes without prior notification reserved
1.951.2761BE4 03/07
Innovative Temperature Technology JULABO Labortechnik GmbH
77960 Seelbach / Germany +49 (0) 7823 / 51-0
+49 (0) 7823 / 24 91 info@julabo.de www.julabo.de
Page 2
2
Congratulations!
You have made an excellent choice. JULABO thanks you for the trust you have placed in us. This operating manual has been designed to help you gain an understanding of the principles of operating and possibilities of our instruments. For optimum utilization of all functions, we recommend that you thoroughly study this manual prior to beginning operation.
Safety Warnings
Take care your unit is operated only by qualified persons. Make sure you read and understand all instructions and safety precautions listed in this manual before installing or operating your unit. If you have any questions concerning the operation of your unit or the information in this manual, contact JULABO.
Performance of installation, operation, or maintenance procedures other than those described in this manual may result in a hazardous situation and may void the manufacturer's warranty.
Transport the unit with care. Sudden jolts or drops may cause damages in the interior of the unit.
Observe all warning labels. Never remove warning labels.
Never operate damaged or leaking equipment. Never operate the unit without bath fluid in the bath. Always turn off the unit and disconnect the mains cable from the power source before
performing any service or maintenance procedures, or before moving the unit. Always empty the bath before moving the unit. Never operate equipment with damaged mains power cables. Refer service and repairs to a qualified technician.
In addition to the safety warnings listed above, warnings are posted throughout the manual. These warnings are designated by an exclamation mark inside an
equilateral triangle. „Warning of a dangerous situation (Attention ! Please follow the documentation).“ The danger is described according to an alarm keyword. Read and follow these important instructions.
Warning:
Describes a possibly highly dangerous situation. If this is not avoided, serious injury and danger to life could result.
Caution:
Describes a possibly dangerous situation. If this is not avoided, slight or minor injuries could result. A warning of possible damage can also be contained in the text.
Notice:
Describes a possibly harmful situation. If this is not avoided, the product or anything in its surroundings can be damaged.
Page 3
Presto
®
3
TABLE OF CONTENTS
1. OPERATING CONTROLS AND FUNCTIONAL ELEMENTS...............................4
2. QUALITY MANAGEMENT SYSTEM....................................................................8
3. UNPACKING AND CHECKING............................................................................8
4. DESCRIPTION.....................................................................................................8
4.1. The Presto® principle with closed external system...............................................9
5. PREPARATIONS...............................................................................................10
5.1. Bath liquids ........................................................................................................ 10
5.2. Tubing................................................................................................................13
5.3. Set up ................................................................................................................14
5.4. Connect the external consumer.........................................................................14
5.5. Power connection ..............................................................................................16
5.6. Filling .................................................................................................................16
5.6.1. Filling of external, closed systems..............................................................17
5.7. Degasifying........................................................................................................19
5.8. Draining .............................................................................................................20
6. OPERATING PROCEDURES............................................................................21
6.1. Switching on / Selecting the language...............................................................21
7. MANUAL OPERATION......................................................................................22
7.1. Start - Stop.........................................................................................................22
7.2. Direct setting of the working temperature ..........................................................23
7.3. Settings in the SET menu ..................................................................................23
7.3.1. Setting the working temperature................................................................23
7.3.2. Warning functions......................................................................................24
7.3.3. Setting the pump pressure stage...............................................................25
7.4. Setting the safety temperature (with shutdown function)...................................26
7.5. Internal / external control ...................................................................................28
8. MENU FUNCTIONS...........................................................................................28
8.1. Configuration .....................................................................................................30
8.2. Control parameters ............................................................................................ 33
8.3. Start of a profile .................................................................................................35
8.3.1. Interrupting a profile...................................................................................37
8.4. Integrated programmer ......................................................................................38
8.5. Analog inputs/outputs ........................................................................................41
8.6. Limits .................................................................................................................44
8.7. Interface.............................................................................................................44
8.8. Sensors..............................................................................................................45
8.9. Pump .................................................................................................................46
9. TROUBLESHOOTING GUIDE / ERROR MESSAGES ......................................47
10. SAFETY RECOMMENDATIONS .......................................................................49
11. ELECTRICAL CONNECTIONS..........................................................................50
12. REMOTE CONTROL .........................................................................................53
12.1. Setup for remote control....................................................................................53
12.2. Communication with a PC or a superordinated data system..............................53
12.3. List of commands...............................................................................................55
12.4. Status messages / error messages....................................................................58
13. MAINTAINING THE COOLING PERFORMANCE..............................................60
14. DISPOSAL OF THE UNIT..................................................................................60
15. CLEANING THE UNIT .......................................................................................61
16. RESPONSIBILITY OF THE OPERATOR...........................................................63
17. MAINTENANCE.................................................................................................63
18. TECHNICAL SPECIFICATIONS ........................................................................64
19. EC DECLARATION OF CONFORMITY.............................................................66
20. WARRANTY CONDITIONS ...............................................................................67
Page 4
Operating controls and functional elements
4
1. Operating controls and functional elements
Front view
1 Mains power switch,
illuminated
2 Local operating board
3 Socket board
4 Removable control module
RD
5 Filling funnel (hinged)
6 Handle (foldaway)
7 Venting grid, removable
8 Drain with drain port
2 Local operating board
2.1
VFD-Info-Display
Header: Control indicators see section 2.2 Line 1: Actual value Int or Ext
To swap, press the key (see below)
Line 2: Working temp. setpoint, constantly S xxx.xx
or indication of the safety temperature (TANK)
Line 3: Miscellaneous values
To swap, press the key (see below)
or indication of the safety temperature (RES)
Page 5
Presto
®
5
2.2 Control indicators in the header: Heating / Cooling / Alarm / Remote control Temperature indication Internal or External actual value Temperature indication in °C or °F Display for the adjusted pump pressure stage (five grades),
adjustable via the key . Liquid level display (five grades)
for the reservoir.
2.3
Key to swap line 3 on the VFD
ID xx Identification no. of control module RD L xx Capacity in % E xxx.xx or I xxx.xx Actual value (external or internal) P x.xx Pump pressure in bar
Int
2.4
S 120.00 E 120.00
Key to swap line 1 on the VFD
Actual value Int or Ext alternating with line 3
2.5
TANK 150
RES 80
Key to indicate the safety temperature on the VFD Line 2: TANK - Safety temperature in internal bath
Line 3: RES - Safety temperature in internal reservoir
2.6
Adjustable excess temperature protection (safety temperature) Used for setting the safety temperature in the internal bath, called "TANK" on the display
2.7
°C
10
30
60
130
180
220
Adjustable safety temperature. Used for setting the safety temperature in the internal reservoir, called "RES" on the display
2.8
Key for automatic filling and air purge of the unit as well as the connected external system.
3 Socket board
3.1 REG+E-PROG
Programmer input and temperature recorder output
3.2 STAND-BY
Stand-by input (for external emergency switch-off)
3.3 ALARM
Alarm output (for external alarm signal)
3.4 EXT. Pt100
Connector for external measurement and control sensor
3.5 SERIAL Interface RS232/RS485
3.6 RD
Connector: control cable of control module RD
Page 6
Operating controls and functional elements
6
4 Control module RD
4.0
Setp: 120.00°C
IntAct 21.00°C
ExtAct: 20.00°C
Control: Intern
DIALOG-DISPLAY (LCD) Standard indication Line 1: Setpoint in °C Line 2: Internal actual value in °C Line 3: External actual value in °C Line 4: Control type: internal / external control
Indicating messages (e. g. warnings)
4.1
Start / stop key To switch the circulation pump, heating element and cooling unit.
4.2
>Setp.: 120.00°C
Overt.:255.00°C
Subtmp:-55.00°C St.Pump: 2
SET Menu Key - Indicating and setting setpoint values Set the following values:
in Line 1: the working temperature Setp.:
Line 2: the high temperature limit Overt.: Line 3: the low temperature limit Subtmp: Line 4: the pump pressure stage St.Pump:
4.3
Control type: internal / external control
To swap, the unit has to be in the STOP MODE. Indicated in line 4 on the DIALOG-DISPLAY (LCD)
4.3
>Configuration
Control param. Profile Start
Int. Programmer
MENU key - for selecting the menu functions
(Menu see page 28)
4.5
Cursor keys - Select menu items
4.6
P-key Selecting parameters
4.7
ESC
Escape key 1) Cancel entries
2) Return to a higher menu level
4.8
Enter key 1) Store value / parameter
2) Next lower menu level
4.9 ....
Numeric keypad: numerals 0 to 9; minus / decimal point
Page 7
Presto
®
7
Rear
10
Control connector 230 V / max. 0.1 A
11 4 Mains circuit breakers
(resettable) 16 A
16
A M P
16
A M P
16
A M P
16
A M P
F1
F4F2
F3
F1 and F3 Compressor F2 and F4 Heater, Pump
12 Mains power cable with
plug
13 + 14
Pump connectors Return Feed M16x1
15
Overflow connector M16x1
16
Connector for expansion vessel M16x1
17
Castor (at the back)
Page 8
Quality Management System
8
2. Quality Management System
Quality Management System
ISO 9001
2000
W
e
a
r
e
c
e
r
t
i
f
i
e
d
The JULABO Quality Management System: Development, production and distribution of temperature application instruments for research and industries conform to the requirements according to DIN EN ISO 9001:2000. Certificate Registration No. 01 100044846
3. Unpacking and checking
Unpack the instrument and accessories and check for damages incurred during transit. These should be reported to the responsible carrier, railway, or postal authority, and a request for a damage report should be made. These instructions must be followed fully for us to guarantee our full support of your claim for protecting against loss from concealed damage. The form required for filing such a claim will be provided by the carrier.
4. Description
Presto®high dynamic temperature systems have been designed for external temperature application to liquids. They offer rapid heating and cooling, wide working temperature ranges without changing fluids as well as highest performance with a small footprint. Besides the cooling unit, the main functional elements are the heater, circulation pump and control electronics. Via an external Pt100 control sensor, a self-optimizing, electronic proportional temperature control (PID characteristic) adapts the heat supplied to the thermal requirements of the external system. The high pump capacity can be reduced by regulating the motor speed in five grades. It may
thus be adapted to sensitive vessels.
The cooling unit may be cooled with air. Setting is rapid and simple using the splash-proof keypads. The operating elements consist
of the local operating board with a bright VFD-Info-Display, as well as the removable control module RD connected with a cable. The microprocessor technology allows four temperature values to be stored and indicated on the DIALOG-DISPLAY (LCD) of the control module RD: working temperature, high and low temperature warning limits as well as pump pressure stage.
The digital RS232 / RS485 port permits modern process engineering without additional
interface.
The excess temperature protection (safety temperature) according to DIN 12 876-1-2000, a
safety feature functioning independent of the regulator circuit, is adjusted and indicated via the VFD-Info-Display.
The integrated programmer allows programming of setpoint and time values for six
temperature profiles.
The following analog sockets are available:
- The REG+E-PROG socket for setpoint selection via an external, analog programmer. At the same time, this socket provides three analog outputs for temperature recorders.
- The external Pt100 socket for external control.
- The alarm output for an external signal.
- The stand-by input for external emergency switch-off.
Presto®high dynamic temperature systems conform to the safety requirements specified by
DIN 12 876-1-2000 (safety class III), as well as DIN 58 966, and the guideline for first voltage range EN 61010-1.
Page 9
Presto
®
9
4.1. The Presto® principle with closed external system
(e.g. double-sided glass vessel).
Operating:
The operation of the temperature system and the indication is effected via the local control panel (2) and the removable operating device RD(4).
Filling :
First connect the external consumer. The menu option >Mode< is set on >Fill<. The unit is filled at the hinged filling funnel (5) via the internal reservoir (5a). The bath liquid spreads from here into the external reservoir (16a) and into the heat exchanger (20). The filling pipe (25) represents narrows. Therefore the filling should be done slowly. The air from the heat exchanger (20) escapes via the venting valve. In a first step approximately 2,6 liters of bath liquid is filled in until
the level indication indicates 3 or 4 batons (see –Filling volume- page 16). Then, by pressing
the key an automatic filling and venting mode with activation of the circulating pump (23) is started. In intervals the tempering liquid is pumped via connection (14) into the external system (33) and led back into the heat exchanger (20) via connection (13). At the end of the filling process the menu option >Mode< has to be set on >Sys close<.
Working:
In case of a closed external system the filling pipe (25) remains open and allows a change in volume of the bath liquid caused by temperature during operation. In case of emergency it has to be possible that the expanding bath liquid can drain off at the overflow (15) into a suitable vessel. If necessary the external reservoir (16a) can be mounted at connection (16).
Theair cooled temperature system is started with the key . The heating (21), the cooling aggregate (22) and the circulating pump (23) start according to the desired adjustments at the operating device RD (4). In the line to the pumpe exit (14) the pump pressure (29) and the actual temperature of the internal control sensor (28a) is permanently measured. If the temperature control has to be effected externally a Pt100 external sensor (28b) has to be connected and switched over to external control at the operating device RD(4).
Safety:
In the internal reservoir (5a) there are the level sensor (26) as well as a safety sensor (27b). The safety sensor (27a) as high temperature protection according to DIN 12876 is located directly at the heater (21). If the external circuit is interrupted (e.g. with a shut-off valve), an emergency circuit is maintained via an internal Bypass (30).
Page 10
Preparations
10
5. Preparations
5.1. Bath liquids
Caution:
Carefully read the safety data sheet of the bath liquid used, particulary with regard to the fire piont! If a bath fluid with a fire point of 65 °C is used, only supervised operation is possible.
Recommended bath liquids for external, c l o se d s ys t e m s :
Order No. Bath liquid Temperature
range
[°C]
Flash point
[°C]
fire point
[°C]
Color Quantity
[liters] 8 940.106 Thermal H5S -40 ... 250 >110 >130 10 8 940 107 Thermal H5S -40 ... 250 >110 >130
slightly
brown
5 8 940 122 Thermal HL45 -45 ... 250 >121 >162 transparent 10 8 940 123 Thermal HL45 -45 ... 250 >121 >162 transparent 5 8 940 120 Thermal HL80 -85 ... 170 >63 >112 transparent 10 8 940 121 Thermal HL80 -85 ... 170 >63 >112 transparent 5
Warning: Thermal H5S, Thermal HL 45, Thermal HL 80:
These bath liquids may only be used in e xt e r n a l , c l os e d s ys t e m s (loop circuits) up to the indicated max. working temperature.
Caution:
Please contact JULABO before using other than recommended bath liquids. JULABO takes no responsibility for damages caused by the selection of an unsuitable bath liquid. Unsuitable bath liquids are liquids which e.g. are very highly viscous
(much higher than 50 mm2x s-1at the respective working temperature)
are of low viscosity and have creep capacities
have corrosive characteristics or tend to cracking.
No liability for use of other bath liquids!
ATTENTION: The maximum permissible viscosity is 50 mm2x s
-1
.
Caution:
The use of water in purified or unpurified form is not allowed. Examples: Tap water, distilled water, water-glycol mixture, CaCl2-brine
Page 11
Presto
®
11
Important notice concerning the recommended bath liquids:
Bath liquids with a range of application above the fire point ? This temperature system is mainly operated in a closed external system (loop
circuit). The contact of the bath liquid with atmospheric oxygen only takes place in the internal reservoir, which is not located directly in the termperature circuit.
A safety device supervises and controls the the temperature in the internal reservoir.
The temperature of the bath liquid is maintained constant at approx. +20°CThe safety device with an adjustable temperature value >RES< works
independently from the control circuit. When actuating this safety device (too much hot fluid streams into the internal reservoir) the temperature system is switched off all-polo and permanently.
Adjust the safety temperature >RES< at at least 20 K below the fire point of the bath liquid.
Page 12
Preparations
12
Diagram 1: JULABO Thermal oils Change in volume in dependence on the temperature of bath liquid.
Examples:
Rough estimate for LH45 (2,6 liters) with an external closed system (2,4 liters).
Example A: Filling quantity at ambient temperature 5 liters
Intended working temperature range -40 °C bis +250 °C Change in volume caused by temperature 1,75 liters Here an external expansion vessel is required (Order no.: 8 970 830)
Example B: Filling quantity at ambient temperature 5 liters
Intended working temperature range +20 °C bis +200 °C Change in volume caused by temperature 1,2 liters Here no external expansion vessel is required
(see table „Filling volume“ Page 16).
Page 13
Presto
®
13
5.2. Tubing
Recommended tubing:
Metal tubing, triple insulated, M16x1, Temperature range -100 °C ... +350 °C
Order No. Length 8 930 209
8 930 210 8 930 211 8 930 214
0.5 m
1.0 m
1.5 m
3.0 m
Metal tubing, insulated, M16x1, Temperature range -50 °C ... +200 °C
Order No. Length 8 930 220
8 930 221 8 930 222 8 930 223
0.5 m
1.0 m
1.5 m
3.0 m
Pressure max. 6.0 bar at +20 °C
4.6 bar at +200 °C
3.8 bar at +350 °C
Warning:
Tubing: At high working temperatures the tubing used for temperature application and cooling water supply represents a danger source.
A damaged tubing line may cause hot bath liquid to be pumped out within a short time.
This may result in:
Fire hazard Explosion hazard Burning of skin Difficulties in breathing due to hot atmosphere
Safety recommendations
Employ suitable connecting tubing. Make sure that the tubing is securely attached. Avoid sharp bends in the tubing, and maintain a sufficient distance from
surrounding walls.
Regularly check the tubing for material defects (e.g. for cracks).
Page 14
Preparations
14
5.3. Set up
The Presto®temperature systems may be placed on or underneath a lab bench.
Place the unit on an even surface on a pad made of
non-flammable material. Lift the handle (6) and using the castor (19) move the unit to the intended location.
Keep at least 20 cm of open space on the front and
rear venting grids.
Do not set up the unit in the immediate vicinity of heat
sources and do not expose to sun light.
Before operating the unit after transport, wait about
one hour after setting it up. This will allow any oil that has accumulated laterally during transport to flow back down thus ensuring maximum cooling performance of the compressor.
The place of installation should be large enough and provide sufficient
air ventilation to ensure the room does not warm up excessively because of the heat the instrument radiates to the environment. (Max. permissible ambient temperature: 40 °C). With regard to a disturbance in the cooling loop (leakage), the guideline EN 378 prescribes a certain room space to be available for each kg of refrigerant. The necessary amount of refrigerant is specified on the type plate. > For 0.48 kg of refrigerant R404A, a room space of 1 m
3
is required.
5.4. Connect the external consumer
The temperature systems are designed for temperature application to closed, external systems (loop circuits). The temperature application of external, open systems is also possible. However, this requires a series of special measures which Julabo cannot influence like e.g. the protection of the bath liquid from environmental influences such as oxygen and air humidity. To profit from the system's rapid performance, ensure the tubing line between the temperature system and the connected external system is as short as only possible.
Caution:
Fasten tubing to prevent slipping.
Connecting the external system: Temperature application to external, closed systems.
Remove the cap nuts from the pump connectors (13, 14) and using
tubing connect the external system (M16x1 / wrench 19 mm). To prevent the formation of bubbles in the loop circuit, the pressure line (13) is to be connected to the lower nozzle of the external system. Also see the description on page 9
Temperature application to external, open systems.
Remove the cap nuts from the pump connectors (13, 14) and using
tubing connect the external system (M16x1 / wrench 19 mm). Also see the description on page 9.
Page 15
Presto
®
15
Important:
Connect a piece of tubing to the overflow connector (15) and drain into a suitable vessel. (M16x1 / wrench 19 mm), which always has to be placed
lower thant the exit „Overflow“.
If required, the connector (16) may be
used for connecting an expansion vessel. (M16x1 / wrench 19 mm)
Close the expansion vessel with the
cover.
Order No. 8 970 830 Expansion vessel
The use of an expansion vessel is depending on the highest temperature and the volume of the bath liquid in the loop circuit. (see diagram 1 page 12).
Note:
At the desired highest temperature, drain overflowing bath liquid into a suitable vessel via the connector (15). If at the desired lowest temperature, low liquid level alarm is not triggered, there is no need to use an external expansion vessel.
Notice:
If an expansion vessel is not used, make sure the connector (16) is closed with a cap nut. If an external expansion vessel is mounted later, a part of the bath liquid should be drained before (see chapter Emptying on page 20). It might be helpful to put the castors at the back on a base which is approximately 10-15 mm high. So the bath fluid can be collected in the front part of the internal reservoir.
Warning:
An external expansion vessel is heated up by the wam outgoing air, especially in small rooms or if there is not enough distance between the wall and the unit.
In this case only bath liquids with a fire point of 100 °C are allowed to be used.
Page 16
Preparations
16
5.5. Power connection
Caution:
Only connect the unit to a power socket with earthing contact
(PE – protective earth)! We disclaim all liability for damage caused by incorrect line voltages!
Check to make sure that the line voltage matches the supply voltage specified on the identification plate. Deviations of ±10 % are permissible
Connect the mains plug (12) to the earthed mains socket !
5.6. Filling
Caution:
Take care of the bath liquid's changing volume varying with the working temperature of the Presto®temperature system.
Guideline:
A volume change of 12 % per 100 °C temperature variation is to be considered.. The maximum change in volume in the internal reservoir for the different models is included in the table below.
Filling is performed in two sections. In section 2, the temperature system starts an automatic filling process enabling convenient filling.
Notice:
First connect the external system! (see page 14)
Example: LH 40 Indication max: 3,2 liters
Indication min: 2,6 liters
Take care no bath liquid enters the interior of the unit. Filling volume LH40
(without external approx. liters system connected) 2,6 ... 4,0
- in the heat exchanger 2,6
- in the internal reservoir 1,4
Recommendation:
For filling, use for example an approx. 2 liters measuring jug. Select the bath liquid suitable for the temperature application
task. (see also diagram 1 page 12). For temperature applications to +250 °C fill up to marker "HT",
for applications to for example –50 °C fill up to marker "TT".
(only important with closed, external system)
Page 17
Presto
®
17
5.6.1. Filling of external, closed systems
ALARM
CODE 14
Section 1
Connect the unit to a mains power socket (see page 16)
and turn on the unit with the mains power switch (1). During the self-test all segments of the VFD-Info-Display, all control indicators and the DIALOG-DISPLAY light up. After the self-test, the VFD-Info-Display signals low liquid level alarm. >CODE 14< and a signal tone sounds.
Press (5.1) to open the filling funnel (5). Slowly pour in bath
liquid into the opening (5.2) and observe the liquid level display.
Notice: Filling quantity [liters] The external system stands
- higher than Presto
®
2,6 l
- lower than Presto
®
2,6 l + Filling quantity ext. system
1.0 Watch the level indication . During the filling
procedure 3 or 4 steps of the level indication can light-up, in the end they should light-up.
Section 2
Pump >Pump OFF
Mode:Sys close
Turn the unit off and on again with the mains power switch (1).
Wait until the self-test is completed.
Press the key to start the automatic filling process.
As soon as the pump pressure indication in the 3rdline of the VFD­Info-Display
(„P X.XX“) has scaled up to at least 0.1 bar, the tempering liquid is pumped into the external system. In intervals of 10 seconds bath liquid is pumped into the external system - air purge is carried out in the breaks.
Notice: The filling mode has to stay activated for at least 5 minutes in order to fully de-air the system.
The liquid level in the unit falls.
In case of a WARNING >CODE 40< again slowly fill in tempering liquid into the opening (5.2). In case of a ALARM >CODE 14< return to the final condition of section 1 and restart section 2.
If the liquid level display remains unchanged after some minutes,
complete filling according to the application task. See page 16 - marker "HT" or "TT".
Press to finish the automatic filling process. In the sub >Pump< the unit has to be set on
>Mode:< >sys close< . (see page 18 Adjusting Mode: )
The unit is now ready for operation .
Page 18
Preparations
18
Adjusting Mode:
Notice concerning the filling
The temperature system was emptied last, therefore the menu option >Mode< now still stands on >drain<. In the configuration of this unit the >Mode< >fill< means the same as >drain< and therefore does not have to be adjusted.
Explanation of terms:
>Mode: sys close< stands for closed, external system (Presto®principle page 9)
Press the respective keys in the following order:
1. MENUE key 1x
2. Cursor key up to Submenu "Pump"
3. Enter key 1x
4. Cursor key 1x up to "Pump"
5. P- key sys open / sys close / fill / drain
6. Enter key 1x
7. Escape key
ESC
2x
The DIALOG-DISPLAY (LCD) helps to follow up the individual settings.
The VFD-Info Display shows the recently chosen operating status for approx. 3 seconds.
Switch over to > sys open < OPEN SYSTEN Switch over to > sys close < CLOSED SYSTEM Switch over to > fill < FILL SYSTEM Switch over to >drain< DRAIN SYSTEM
Page 19
Presto
®
19
5.7. Degasifying
S 180.00
-DEGAS-
Setp: 180.00°C
IntAct 78.00°C
ExtAct: --.--°C
Control: Intern
degasing activ
If the temperature system is operated in a closed, external consumer, >Mode: sys close<, an automatic degasifying is carried out after the start.. During the degasifying unwelcome components of the bath liquid are are drawn off . Examples:
Air bubbles which were enclosed in the bath liquid during
the filling for the unit.
Slightly volutile components which are eventually in the
fluid.
Eventually existing water components, which reached the
bath liquid during the storage.
When operating in the >Mode: sys open< there is no need for degasifying, because the unwelcome components can escape via the open bath tank.
The automatic degasifying is a part of the program in the unit, which is always active in the background. Experience shows that the activity is only noticed after a first or new filling of the unit. During the heating-up phase, e.g. to a working temperature of 180°C, the VFD-Info-Display shows >DEGAS<. Parallely to this, in line 4 in the DIALOG-DISPLAY the message >Degasifying active< is inserted. In this phase the temperature rise is stopped, the pump motor and the ventilation valve are activated alternately (audible). During the heating-up phase this degasifying mode can be repeated with the most different temperatures. The automatic degasifying can be stopped by :
Operating the key or adjusting the set temperature on at least 50°C lower than the current set temperature.
Caution:
With different substances the change-over to the steam phase and therefore also an enormous change of volume is carried out very quickly. The fluid, for which there is no more room in the internal reservoir, now has to drain off controlled via the overflow.
Important:
Connect a piece of tubing to the overflow connector (15) and drain into a suitable vessel. (min. 2 liters) (M16x1 / wrench 19 mm), which
always has to be placed lower than the exit „Overflow“
Recommendation on LH40 For this unit an external expansion vessel is recommended. (see page 15) Sometimes the internal reservoir is not able to take up the quickly expanding fluid. In fact, via the overflow there is a correct draining, however, if the liquid is needed again after the expansion phase, the unit can give low level alarm. The „automatic degasifying“ is stopped.
Page 20
Preparations
20
5.8. Draining
Notice:
Exercise caution when emptying hot bath liquids! Store and dispose the used bath liquid according to the laws for environmental protection.
S 20.00 P x.xx
Pump
>Pump OFF
Mode: drain
6
Draining
Turn on the temperature system with the mains power
switch or press the stop key to make the unit enter the STOP-
MODE.
In the submenu >Pump<, set the menu items >Mode< to
>drain<.
(see page 18 Adjusting Mode: )
The reset to another mode can only take place after the
next filling.
Reason: During the >ALARM – CODE 14< there is no possibility for access to the menu functions !
Pull the venting grid (8.1) to the front and remove.Place a suitable vessel (8.2) for accepting the used bath
liquid underneath the drain.
Slide a short piece of tubing onto the drain port and hold
the end into the vessel.
Unscrew the drain screw by some turns.The liquid level in the unit falls.
Now the VFD-Display of the unit should show low level, WARNING >CODE 40< and then ALARM >CODE 14<.
Press enter to quit the audible signal.
Drain the external system:
At the upper nozzle of the external system, disconnect the tubing to the pump connector "return" (14) until an air stream moves in. (see sketch on page 14)
Tighten the drain screw after draining the unit.
The internal reservoir should additionally be emptied via the
connection for the expansion vessel (16) on the rear side of the temperature system. The unit can be lifted up by 4-5 cm by using the handle (6)
(Cleaning the unit see page 61)
Page 21
Presto
®
21
6. Operating procedures
6.1. Switching on / Selecting the language
JULABO
P R E S T O
V1.45-1
Switching on: The unit is operated by pressing the mains power switch
(1). The integrated pilot lamp illuminates.
During the self-test all segments of the VFD-Info-Display,
all control indicators and the DIALOG-DISPLAY light up. Then the software version number (example: V1.45-1) appears for a short moment and the message "OFF" indicates the unit is ready to operate.
Message >WAIT< when adjusting >Mode: sys close<:.
During the message >WAIT< the ventilation valve is opened for 10 seconds. So, the air which has eventually been collected during the standstill, can escape.
The unit returns to the previous operating mode that was
active before it was turned off:
keypad control mode
(manual operation via the unit itself/RD)
or
remote control mode
(operation via PC).
Selecting the language:
There are two options for the language of the DIALOG­DISPLAY (LCD): German or English. Select the desired language in the MENU level under the submenu >Configuration.
Soll: 20.00°C IntIst xxx.00°C ExtIst: Regelung:
>Konfiguration
Regelparameter
Konfiguration
Identif. xxxxx
Sollwert xxxxx
Autostart xxx
Standby xxxx
>Sprache xxxxxxx
Setp.: 20.00°C
IntAct xxx.xx°C
ExtAct: xxx.xx°C
Control: intern
Press the respective keys in the following order:
1. MENU key 1x
2. Enter key 1x
3. Cursor key up to Submenu "Sprache/Language"
4. P-key 1x
5. Enter key 1x
6. Escape key
ESC
2x
The DIALOG-DISPLAY (LCD) helps to follow up the individual settings (example: swap the language from German to English).
Page 22
Manual operation
22
7. Manual operation
7.1. Start - Stop
Setp.: 20.00°C IntAct 21.00°C ExtAct: --.--°C Control: Intern
S 20 .00
P x.xx
Start:
Press the start/stop key .
The actual bath temperature is displayed. For approx. 3 seconds the VFD-Info-Display shows the
adjusted >Mode< . Adjustment > sys open < OPEN SYSTEM Adjustment > sys close < CLOSED SYSTEM
The temperature system runs.
Notice:
The message >SELECT SYSTEM<is a demand to make an adjustment in the menu >Pump< according to the connected system. The insertion is effected cyclicly until the adustment has been made (see page 18 Adjusting Mode: )
In the >Mode< > fill < bzw. >drain<>SELECT SYSTEM< is shown when starting.
Notic: For physical reasons, refrigeration units provide full cooling performance only after some minutes. After the start up to 5 minutes can go by, until the cooling capacity is given.
Setp.: 20.00°C
IntAct 21.00°C ExtAct: --.--°C Control: Intern
Stop-Mode
S 20.0 0
ID 0
Stop:
Press the start/stop key .
The VFD indicates "OFF" and the message STOP-MODE flashes in line 4 on the LCD.
The unit also enters the safe operating state "OFF" after a mains power interruptance. The temperature values entered via the keypad remain in memory. With the temperature system in keypad control mode, press the start/stop key to restart operation. With the instrument in remote control mode, the personal computer must first resend the parameters set via the interface before the temperature system may be restarted.
Page 23
Presto
®
23
7.2. Direct setting of the working temperature
Setp.: 20.00°C IntAct 21.00°C ExtAct: --.--°C Control: Intern
This setting may be carried out with the temperature system being in operating state Start or Stop!
The value previously set appears on the DIALOG-
DISPLAY (LCD) (example: 20.00 °C). A flashing segment indicates that a value needs to be entered.
Use the keypad to enter the new value and press enter
to store the selected value.
(examples: 120.00 °C; 228.50 °C; -15.00 °C).
7.3. Settings in the SET menu
>
Setp.: 120.00°C
Overt.:255.00°C
Subtmp:-55.00°C
St.Pump: 2
Press the key to call up the SET menu. It is then
indicated on the DIALOG-DISPLAY (LCD). Set the following values:
in Line 1: the working temperature in °C Setp.:
Line 2: the high temperature limit in °C Overt.: Line 3: the low temperature limit in °C Subtmp: Line 4: the pump pressure stage St.Pump:
Enter the desired values via the keypad. Settings may be
carried out with the temperature system being in operating state Start or Stop!
Use the cursors to swap the lines.
Press escape
ESC
to quit the SET menu.
7.3.1. Setting the working temperature
>Setp.: 200.00°C
Overt.: 255.00°C
Suptmp: -55.00°C
St.Pump: 2
>Setp.: 120.00°C
Overt.:255.00°C
Subtmp:-55.00°C St.Pump: 2
>Setp.: Setting the working temperature
Setting in line 1.
The value previously set appears on the DIALOG­DISPLAY (LCD) (example: 100.00 °C). A flashing segment indicates that a value needs to be entered.
Use the keypad to enter the new value
(examples: 120.00 °C; 228.50 °C; -15.00 °C).
Press enter to store the selected value.
Page 24
Manual operation
24
7.3.2. Warning functions
  
The high and low temperature warning functions accompany the working temperature value. An audible signal sounds in intervals when the actual temperature exceeds one of the set limits (patented). The corresponding message appears in line 4 on the DIALOG-DISPLAY (LCD).
Setp.: 120.00°C
>Overt.:130.00°C
Subtmp:-55.00°C St.Pump: 2
>Overt: Setting the high temperature limit
Setting in line 2.
The value previously set appears on the DIALOG­DISPLAY (LCD). A flashing segment indicates that a value needs to be entered.
Use the keypad to enter the new value
(examples: 130.00 °C; -13.00 °C).
Press enter to store the selected value.
Setp.: 120.00°C
Overt.:130.00°C
>Subtmp:110.00°C
St.Pump: 2
>Subtmp: Setting the low temperature limit
Setting in line 3.
The value previously set appears on the DIALOG­DISPLAY (LCD). A flashing segment indicates that a value needs to be entered.
Use the keypad to enter the new value
(examples: 110.00 °C; -17.00 °C).
Press enter to store the selected value.
Note:
The warning functions will only be triggered when the actual bath temperature, after start from the "OFF" or "rOFF" mode, lies within the set limits for 3 seconds.
Example:
Setp: 120.00°C
IntAct 130.50°C
ExtAct: --.--°C
Control: Intern
Excess temp.
t
150
130 120 110
20
°C
The corresponding message appears in line 4 on the DIALOG­DISPLAY (LCD).
Page 25
Presto
®
25
7.3.3. Setting the pump pressure stage
The pressure of the circulation pump is adjustable in five grades. After setting, the VFD-Info-Display indicates the corresponding value.
Setp.: 120.00°C
Overt.:130.00°C
Subtmp:110.00°C
>St.Pump: 4
>St.Pump: Setting the pump pressure stage
Setting in line 4.
The value previously set appears on the DIALOG­DISPLAY (LCD). A flashing segment indicates that a value needs to be entered.
Use the keypad to enter the new value
(example: 4).
Press enter to store the selected value.
Note: The mechanical rotation of the circulation pump produces heat that is radiated into the bath liquid. The lowest working temperature may thus only be reached if the pump pressure is set to grade 1.
Page 26
Manual operation
26
7.4. Setting the safety temperature (with shutdown function)
TANK 150
RES 10 0
°C
10
30
60
130
180
220
°C
0
40
80
160
240
320
ALARM
CODE 14
ALARM!
IntAct: xx.xx°C
ExtAct: --.--°C
Temp/level alarm
This safety feature functions independent of the regulator circuit. When the temperature of the bath liquid has reached the safety temperature, a complete shutdown of the heater and pump is effected.
Safety temperature in the heat exchanger >TANK<
(excess temperature protection)
Press the key to indicate the safety temperature value
in line 2 >TANK< on the VFD-Info-Display and using a screwdriver simultaneously turn the setting screw to the desired value (example: 150 °C).
Setting range: 0 °C to 320 °C
in 2 °C steps
The alarm is indicated by optical and audible signals (continuous tone).
The error messages opposite appear on the DIALOG-DISPLAY (LCD) and VFD-Info-Display.
ALARM
CODE 13
ALARM!
IntAct: xx.xx°C
ExtAct: --.--°C
RESERVOIR
Safety temperature in the internal reservoir >RES<
This supplementary safety installation supervises and controls the temperature of the bath liquid in the internal reservoir.
Press the key to indicate the safety temperature value
in line 3 >RES< on the VFD-Info-Display and using a screwdriver simultaneously turn the setting screw to the desired value (example: 100 °C).
Setting range: 10 °C to 220 °C
in 2 °C steps
The alarm is indicated by optical and audible signals (continuous tone). The error messages opposite appear on the DIALOG-DISPLAY (LCD) and VFD-Info-Display.
Page 27
Presto
®
27
Press enter to quit the audible signal.
After eliminating the malfunction, press the mains power
switch off and on again to cancel the alarm state.
Warning:
Recommendation for external, closed systems: (see page 9)
Set the safety temperature >TANK< 15 °C above the working temperature
setpoint.
The safety temperature value >RES<should be set at least 25 °C below the
fire point of the bath liquid used.
Important:
From time to time the safety device has to be checked. With a screwdriver turn back the adjustable excess temperature protection until the shut-down point (actual temperature). After eliminating the malfunction, press the mains power switch off and on again to cancel the alarm state.
Page 28
Menu functions
28
7.5. Internal / external control
ext. Pt100
The temperature system offers the possibility of internal temperature control in the internal bath or external control directly in an external system.
Setup for external control:
Connect a Pt100 sensor to the socket "EXT" of the Presto
®
temperature system, if necessary perform a calibration using the "ATC Ext:" function (see page 45) and then securely fix the sensor in the external system.
S xx.x x
ID 0
ESC
Setp: 120.00°C
IntAct 21.00°C
ExtAct: 20.00°C
Control: Intern
To swap internal to external control:
Press the key in operating state "OFF" to select the
control type.
The DIALOG-DISPLAY (LCD) indicates the effective
control type in line 4 >Control: intern< or > Control: extern<
Setp: 120.00°C
IntAct 21.00°C
ExtAct: 20.00°C
Control: Extern
Int
S 120. 00
E 20.0 0
Press the start/stop key .
Temperature indication:
The DIALOG-DISPLAY (LCD)
simultaneously indicates both actual temperatures.
The VFD-Info-Display
indicates the actual temperature in line 1. In the header the corresponding symbol >Int< or >Ext< is illuminated.
Press the key to swap the display.
It is useful, to set line 3 to show the actual temperature
>E xx.xx°C< by pressing the key .
Caution:
Place the external sensor into the bath medium and securely fix the sensor.
8. Menu functions
Press the MENU key to enter the menu level. Use the up/down cursor keys to select the desired
submenu and press enter .
Press escape to return to the previous menu level.
Page 29
Presto
®
29
Page 30
Menu functions
30
8.1. Configuration
>Configuration
Controlparam. Profile Start Int.Programmer Inputs/Outputs Limits Interface Temp.Sensor Pump
Configuration Identif. xxxxx Setpoint xxxxx Autostart xxx Standby xxxx Language xxxxxx IdentNo x
By means of the configuration functions, operation of the instrument can be optimized for the current application.
Press enter to select the configuration submenu.Use the up/down cursor keys to select the
desired option. A flashing line indicates that a value needs to be entered.
Press the P-key to select the parameter and press
enter .
Press escape to return the previous menu level.
> Identification
When performing an identification for the controlled system (temperature application system), the control parameters Xp, Tn and Tv will be automatically determined and stored.
Possible parameters: off - no identification.
The control parameters ascertained during the last identification are used for control purposes.
once - single identification
The instrument performs a single identification of the controlled system after start. After the identification process the parameter is automatically set to "off".
always - continual identification
The instrument performs an identification of the controlled system whenever a new setpoint is to be reached. NOTE: Use this setting only when the temperature application system changes permanently.
Important:
For physical reasons, refrigeration units provide full cooling performance only after some minutes. During identification this is given consideration by waiting for 5 minutes after switch-on.
Page 31
Presto
®
31
Note:
Requirement for an identification of the controlled system: The temperature system must heat to a setpoint
temperature at least 10 °C above the previous setpoint using the adjusted heating power.
When the adjusted control parameters Xp, Tn and Tv are
too high, this requirement may not be given with respect to on how much the setpoint temperature has to change. In this case, prior to carrying out an identification in the "OFF" state, set the control parameters to lower values.
Recommended setting for internal control:
Xp = 1.0 °C Tn = 80 s Tv = 8 s
Setp.: 50.00°C IntAct: 50.00°C ExtAct: 50.00°C Control: intern
Eprog: 50.00°C
IntAct: 50.00°C
Power: 50 %
Control: intern
Rs232: 50.00°C
IntAct: 50.00°C
Power: 50 %
Control: intern
S xx. xx
ID 0
R
REG+E-PROG
SERIAL
> Setpoint
The instrument provides three possibilities for setpoint selection. The active mode is indicated on the DIALOG­DISPLAY (LCD). The control indicator >R< (REMOTE) is illuminated in the header of the VFD-Info-Display if setpoint selection is effected via the EPROG or SERIAL input.
Possible parameters:
keyb- via keypad (Setp.:) or via the integrated programmer.
eprog - via the analog interface REG+E-PROG (3.1) through
an external programmer.
RS232 - via the serial RS232/RS485 interface (3.5) through a
PC or superordinated data system.
>Autostart Note:
The temperature system has been configured and supplied by JULABO according to N.A.M.U.R. recommendations. This means for the start mode, that the unit must enter a safe operating state after a power failure (non-automatic start mode). This safe operating state is indicated by "OFF", resp. on the VFD-Info-Display. A complete shutdown of the main functional elements such as heater and circulation pump is effected simultaneously. Only with setpoint adjustment the AUTOSTART-function can be executed via >Taste< and >EPROG< (see above).
Page 32
Menu functions
32
Should such a safety standard not be required, the AUTOSTART function (automatic start mode) may be activated, thus allowing the start of the instrument directly by pressing the mains power switch or using a timer.
Possible parameters:
on - AUTOSTART on off - AUTOSTART off
Warning :
For supervised or unsupervised operation with the AUTOSTART function, avoid any hazardous situation to persons or property. The instrument does no longer conform to N.A.M.U.R. recommendations.
Take care you fully observe the safety and warning functions of the instrument. If the setpoint is given via the serial interface, no AUTOSTART is possible.
STAND-BY
>Stand-by input
External stand-by for emergency switch-off (connector - see page 52)
Possible parameters:
no - stand-by input is ignored yes - stand-by input is active
> Language
There are two options for the language of the DIALOG­DISPLAY (LCD): German or English.
Possible parameters:
German (deutsch) English (engl).
S xx.x x
ID 0
>IdentNo
The identification number identifies the removable control module RD. Assign identification numbers if more than one Presto
®
temperature system is available.
Adjustable parameters:
0 ... 999
Indicated also on the VFD-Info-Display.
Page 33
Presto
®
33
8.2. Control parameters
Xp =
When performing an identification for the controlled system (temperature applications system) (see page 30), the control parameters Xp, Tn, Tv and Xpu will be automatically determined and stored.
Each parameter may be manually set via the keypad if necessary, to allow optimum control performance.
Press enter to select the submenu "control
parameters".
Use the up/down cursor keys to select the
desired option. A flashing segment indicates that a new value needs to be entered.
Use the numerals to set the value and then set with enter
(example: Xp = 2.5 °C).
or at >DynInt<
Press the P-key to select the parameter and press enter .
Press escape to return to the previous menu level.
Proportional range >Xp<
The proportional range is the range below the selected temperature value in wich the the control circuit reduces the heating power from 100 % to 0 %.
Resetting time >Tn< (Integral component)
Compensation of the remaining control deviation due to proportional regulation. An insufficient resetting time may cause instabilities to occur. Excessive resetting time will unnecessarily prolong compensation of the control difference.
Lead time >Tv< (Differential component)
The differential component reduces the control settling time. An insufficient lead time will prolong the time required to compensate for disturbance effects and cause high overshooting during run-up. An excessive lead time could cause instabilities (oscillations) to occur.
Proportional range >Xpu<
The proportional range Xpu of the cascaded controller is only needed for external control.
Page 34
Menu functions
34
°C
t
aperiod.
standard
setpoint
temp. stability
°C
t
aperiod.
standard
temperature ramp
temp. stability
>DynInt< - Dynamics
This parameter affects the march of temperature only in case of internal control (see page 28)
Adjustable parameter: standard The temperature rises quicker, however
can overshoot up to 5 %. If a ramp is defined, the march of temperature often follows this ramp.
aperiod. The temperature rises chronologically
without overshoot.
With both adjustments a sufficient temperature stability is reached after approximately the same time.
°C
t
setpoint
5
3
0
Temp. intern
Temp. extern
>CoSpeed< 0 up to 5 This parameter affects the march temperature only in
case of external control (see page 28). The adjustment affects the calculation of the control parameter when identifying and so the control course.
Optimization instructions for the PID control parameters:
optimum setting
°C
t
The heat-up curve reveals inappropriate control settings.
Inappropriate settings may produce the following heat-up curves:
Xp too low
°C
t
Tv/Tn too low
°C
t
Xp too high or Tv too high
°C
t
Tv/Tn too high or Xp too high
°C
t
Page 35
Presto
®
35
8.3. Start of a profile
1.
S xx.x x
ID 0
2.
S 100.00
ID 0
The start menu of the integrated programmer allows calling up and defined starting of one of six previously stored temperature profiles. The profiles are started manually or via the integrated timer.
There are two possibilities for manually starting a program:
1. Starting a profile from the OFF state: The temperature system switches back to the OFF state at the end of the program.
2. Starting a profile from the operating state. The temperature system is started with the start key ,
and the bath is heated to the desired temperature, for example 100 °C. At the end of the program, the programmer switches to the operating state and holds the bath temperature stable at 100.00 °C.
Press enter to select the submenu "Profile Start".Use the up/down cursor keys to select the
desired option. A flashing segment indicates that a number needs to be
entered.
Start Profile 0 to 5 at Step 0 to 60 Loops 1 to 99
Enter the desired number and set each entry with enter
.
Start no / yes  (manual start)
or
time  (via integrated timer) A flashing line indicates that a parameter needs to be entered.
Press the P-key to select the respective parameter and press enter .
Page 36
Menu functions
36
Example: hour.min 6:00 h
When selecting the parameter time, a new menu level is
called up for entry of the start time. A flashing segment indicates that a start time needs to be entered.
hour.min Start time Day.Mon day and month Year year
Set each entry with enter .
Start no / yes
A flashing line indicates that the parameter "yes" needs to be entered.
Press the P-key to select the parameter and press enter .
The temperature system switches to waiting mode and a
flashing line "wait" appears on the DIALOG-DISPLAY (LCD). The start time and actual time are permanently indicated on the display.
Int
S 120.00 E 120.00
Indication after starting the profile:
DIALOG-DISPLAY (LCD) 1st line: Setpoint of the programmer 2nd line: Actual temperature value
at internal control = IntAct: xxx.xx
at external control = ExtAct: xxx.xx 3rd line: Selected profile and the actual section 4th line: Remaining time of the actual section
VFD-Info-Display: Line 1 indicates the actual temperature value.
In the header the corresponding symbol >Int< or >Ext< is illuminated.
Press the key to swap the values in line 1 and line 3.
Page 37
Presto
®
37
8.3.1. Interrupting a profile
Interrupting a profile:
Press the start/stop key to interrupt or continue a
profile. The setpoint and time period set for the corresponding section are thus stopped at the values presently achieved. The instrument is put on hold and the message "pause" flashes on the DIALOG DISPLAY (LCD).
STAND-BY
A profile can be interrupted or restarted by an external
emergency shut-off (see page 52).
CAUTION:
This is not an actual emergency switch-off.
The setpoint control and the timer are interrupted by
breaking the contact "AK”.
The instrument is put on hold and the message "Stand-By" flashes on the DIALOG-DISPLAY (LCD).
Important: To achieve this, the stand-by condition must first be activated and the AUTOSTART function turned on (See page 32).
Warning:
Following a power interruption, it would be possible in this condition for the instrument to restart automatically. The safety and warning functions of the instrument should always be used to their fullest capacity.
See Warning page 32
Termination of a profile:
A profile can be terminated by pressing the escape key . The programmer switches back to the Start menu.
Press the escape key again to leave the menu
or use the cursor keys to remain in the Start menu.
The execution of another temperature profile can now be prepared if necessary.
Page 38
Menu functions
38
8.4. Integrated programmer
The integrated programmer allows any desired temperature program sequences to be realized. Such a temperature sequence is called profile. A profile consists of individual sections defined by duration (t:) and target temperature. Target temperature is the setpoint (T:), that is achieved at the end of a section. The programmer uses time and temperature difference values within a section to calculate a temperature ramp.
Control param.
Profile Start
Int.Programmer
Inputs/Outputs
Limits Interface Temp.Sensor
Int.Programmer >Edit
Delete Set Clock
Press enter to select the submenu "Int. Programmer".Use the up/down cursor keys to select the
desired option. Then press enter to open. A flashing segment indicates that a number or value needs to be entered. Edit Compile profiles
Display sections
Delete Delete sections Set clock Set the real time on the instrument
Int.Programmer
Edit Delete
>Set Clock
>hour.min 11:09
Day.mon 18.04
Year 1997
Examples:
Setting clock
The integrated clock allows starting a profile at any date and time. The clock is preset in the factory.
Lines 1 to 3:
Check for correctness of the preset date and time and correct if necessary.
The time is diplayed permanently in line 4.
Use the numerals to set time, date and year and set each
entry with enter .
Press escape to return to the previous menu level.
Page 39
Presto
®
39
Int.Programmer >Edit
Delete Set Clock
>Edit Profile: 1
Step: 6
Setp: 100.00°C
Time[h.m] 01:05
Examples: Profile No 1: Step Setpoint
Time
Edit
Compile profiles: A flashing segment indicates that a number needs to be
entered. Under submenu "Edit Profile" enter a profile number. Six profiles may be stored (nos. 0 to 5).
Then programme the desired values for each section.
Use the keypad to set section number, target temperature and time period. Set each entry with enter .
When the program is running, only sections having complete information for target temperature and time period are considered. It makes sense, to leave out section numbers in the profile, in order to use them later for corrections in the profile.
Important:
If a time of 00:00 is set for a profile, the profile is continued with the next section only after the setpoint temperature (±0.2 °C) is reached.
Press escape to return to the previous menu level.
Example: Step (No.) 1 3 5 6 9 11 14 Setpoint (°C) 50 50 100 100 80 80 20 Time (h.m) 00:08 00.02 00:10 01:05 00:10 00:05 00:30
Step
Display sections:
1. Use the cursor keys to select the submenu "Step", enter the desired number and press enter .
or
2. If the submenu „Set“ is selected, section by section can be
shown in ascending order by the P-key .
3. Each previously set value is displayed.
Page 40
Menu functions
40
Delete
A flashing segment indicates that the respective profile
number needs to be entered in which one or more consecutive sections are to be deleted.
In lines 2 and 3 of the DIALOG DISPLAY (LCD) enter the
numbers of the sections to be deleted. Press enter .
delete no / yes
Press the P-key to select the parameter "yes" and press enter .
Line 4 indicates the deletion. Example:
Delete section 8 to section 34 in profile 3.
Press escape to return to the previous menu level.
Page 41
Presto
®
41
8.5. Analog inputs/outputs
or
This submenu enables setting of the input and output values for the programmer input and the temperature recorder outputs of socket REG+E-PROG (21).
Press enter to select the inputs/outputs submenu.Use the up/down cursor keys to select the
desired option and press enter to open.
Chan.1 voltage output for recorder (V) Chan.2 voltage output for recorder (V) Chan.3 current output for recorder (mA) EPROG external programmer input
First define the desired output value for channels 1 to 3:
Press the P-key to select the desired output value and set with enter
.
Setpoint active setpoint temperature
(Keypad, integr. programmer/ext. programmer)
ActInt internal actual temperature value
(bath temperature)
ActExt external actual temperature value
(external sensor)
Power periodic or intermittent heating or cooling
Then select the display size for channels 1 to 3:
Channel 1 and 2 voltage outputs
Assign the voltage values of 0 V to the lowest and 10 V to the highest necessary temperature or power rating required as an output value (°C / %).
Current output channel 3
Assign the current values 0 mA or 4 mA to the lowest and 20 mA to the highest temperature or power rating required as an output value (°C / %).
The current output offers 2 ranges for selection: 0 to 20 mA and 4 to 20 mA
Select the desired range by pressing the P-key and set with enter
.
The LCD display changes automatically.
Page 42
Menu functions
42
Examples:
lowest temperature value: 10 °C highest temperature value 210 °C Fig. shows 200 C scaled to paper width rise: 50 mV/°C
lowest temperature value: 197 °C highest temperature value: 202 °C Fig. shows 5 C scaled to paper width rise: 2000 mV/°C
1.
REG+E-PROG
Configuration Identif. xxxxx Setpoint EPROG Autostart xxx
Inputs/Outputs
chan.2: ActInt
chan.3: ActExt
>EPROG: Current
>EPROG: Current
L Value 0.0°C
H Value 300.0°C
ExtSet 50.0°C
2.
3.
EPROG - Input
This input is necessary when the nominal value is to be determined and set by an external programmer (see page 31 )
1. Connect the external programmer to socket (3.1) REG+E-PROG of the instrument.
2. Adjust the menu option >Setpoint< on >EPROG< in the menu >Konfiguration< (see page 31)
3. The programmer input of the instrument can be matched to the output signal of the external programmer.
Voltage voltage input Current current input
Select the desired input value with the P-key and set with enter
.
"L Value" - Setting the LOW value::
Adjust and set the lowest desired working temperature on the programmer (e.g. 0 C). Enter this same temperature on the instrument by pressing the appropriate buttons on the keypad and press enter
to set.
"H Value" - Setting the HIGH value:
Adjust and set the highest desired working temperature on the programmer (e.g. 300 C). Enter this same temperature on the instrument by pressing the appropriate buttons on the keypad and press enter
to set.
Return to the standard display by pressing escape
.
Example:
Setting a temperature of 50 C on the external programmer! The value adjusted and set on the external programmer is
displayed in line 4 of the DIALOG-DISPLAY (LCD) for control purposes (Example: ExtSet: 50.0 C). After returning the LCD display to standard display by pressing
escape ("Setpoint" - see page 31) this value is displayed in line 1 (Example: EPROG 50.00 C).
Page 43
Presto
®
43
This EPROG input enables the use of different voltage and current values as program parameters.
"L Value" - Setting the LOW value:
1) Adjust and set the lowest desired value on the voltage or current source resp. (Example A: 1 V).
2) Assign a lower temperature threshold value to this adjusted voltage/current value by pressing the appropriate buttons on the keypad of the instrument (Example A: 20 C
) and set by pressing enter
.
"H Value" - Setting the HIGH value:
1) Adjust and set the highest desired value on the voltage or current source resp. (Example A: 10 V).
2) Assign an upper temperature threshold value to this adjusted voltage/current value by pressing the appropriate buttons on the keypad of the instrument
(Example A: 200 C) and set by pressing enter .
Return to the standard display by pressing escape . Example B in the diagram serves to illustrate that the end
point values are freely selectable.
Example out of diagram A:
Adjusting the voltage source for an output of 7.6 V! Line 4 of the DIALOG-DISPLAY (LCD) shows the externally
set setpoint value. The instrument calculates this value from the rise angle of the two predecided end points (in example A:
7.6 V correspond to an external setpoint temperature of
152.0 C ). After returning the LCD display to standard display by
pressing escape , this value is displayed in line 1 (Example: EPROG 152.00 C).
Notice:
If this adjustment is not correctly performed at two different points, the setpoint setting will be incorrect.
Page 44
Menu functions
44
8.6. Limits
Int.Programmer Inputs/Outputs Limits Interface Temp.Sensor
Limits
>IntMax 400.00°C
IntMin -99.99°C
Band 30K
HeatingMax 100%
CoolingMax 100%
The limits IntMax and IntMin are only valid under external control (see 7.5. Internal / external control). They restrict the temperature of the internal bath to the desired maximum/minimum, also if the controller would require a higher/lower temperature for the external system. As a result the external setpoint may thus not be reached.
When operating the temperature system under external control, band limiting is active. The preset value determines the maximum temperature difference between the internal bath and the external load. This adjustment possibility prevents sensitive equipment and temperature devices from damage.
Heating and cooling power of the instrument are adjustable. 100 % corresponds to the values in the technical specifications of the equipment.
Select the submenu "Limits" with enter .Select the desired option with the up/down cursor keys
.
A flashing digit indicates that a value needs to be entered.
IntMax see temperature range LHxx IntMin see temperature range LHxx Band 0 to 200 °C HeatingMax 0 to 100 % in steps of 1 % CoolingMax 0 to 100 % in steps of 1 %
Set the newly entered value by pressing enter .Return to the previous menu level by pressing escape
.
8.7. Interface
The interface parameters are set by selecting the submenu "Interface" on the temperature system. Normally, this is a one­time-only adjustment.
Press enter to select the submenu "Interface".Select the desired option with the up/down cursor keys
.
Enter the desired value for the flashing digit.
Type RS232 / RS485 Baudrate 4800/9600 Parity none/even/odd Handshake software handshake/hardware
handshake Address 0 to 127
Press the P-key to select the desired parameter and
set with enter
.
Return to the previous menu level with escape
.
Page 45
Presto
®
45
8.8. Sensors
ATC - Absolute Temperature Calibration
Select the submenu "Temp.Sensor" with enter .Select the desired option with the up/down cursor keys
.
A flashing digit indicates that a value needs to be
entered i.e. set.
ATC Int: internal sensor ATC Ext: external sensor
Enter the desired compensating value and set this value by
pressing enter .
Notice:
ATC Int: Do not alter the factory-setting!
ext. Pt100
Calibrated thermometer (TM)
Presto: Pt100 sensor (T
ExtIst
)
Setp.: xx.00°C
IntAct xx.00°C
ExtAct: 51.22°C
Control: Intern
ATC Ext:
serves calibration of an external Pt100 sensor.
Immerse the external Pt100 sensor and a calibrated
thermometer together in a calibration bath at 50°C, for example, and allow the reading to stabilize.
Read the temperatures of the calibrated thermometer (TM)
and the external Pt100 sensor (T
ExtIst
) in their respective
displays.
Calculate the temperature difference and enter and set this
difference value as the ATC external compensating parameter. (Example: T = T
ExtIst
- T M= 1.22 K)
Use the keypad to enter the desired compensating value
(e.g. 1.22 °C) and set with enter .
Important:
The ATC function remains active until reset to 00.00 °C.
Page 46
Menu functions
46
8.9. Pump
Pump
>Pump Off
Mode: drain
Limits Interface Temp.Sensor
>Pump
In this submenu the circulation pump can be turned on separately, without heating element or cooling unit.
The menu option „Modus“ refers to the filling valve and the ventilation valve. Depending on the operating status (drain / fill / sys open / sys close) the valves are switched off automatically.
Press enter to select the submenu "Pump".Select the desired option with the up/down cursor keys
.
Enter the desired value for the flashing digit.
Pump OFF/ON Mode: drain / fill / sys open / sys close
Press the P-key to select the desired parameter and
set with enter
.
Return to the previous menu level with escape
.
Explication of terms: >Mode: System closed<stands for closed, external system. (Presto® principle
page 9) In this operating status the filling valve is opened and the ventilation valve is closed.
>Mode: drain<. (Chapter „Draining“ see page 20)
In this operating status the filling valve and the ventilation valve are opened.
In the configuration of this unit the >Mode: fill< means the same as >Mode: drain<.
Page 47
Presto
®
47
9. Troubleshooting guide / Error messages
+
ALARM
CODE 14
Whenever the microprocessor electronics registers a failure, a complete shutdown of the temperature system is performed.
The VFD-Info-Display indicates the cause for the alarm in form of a code.
The alarm light " " illuminates and a continuous signal tone sounds.
CODE 02
Defect temperature sensor in refrigeration circuit.
Repair by authorized JULABO service personnel.
CODE 05
Cable of the working temperature sensor interrupted or short-
circuited.
CODE 06
Defect of the working or safety temperature sensor.
Working temperature and safety sensors report a temperature difference of more than 25 °C.
CODE 07
Other errors (I2C-BUS errors)
CODE 12
Error in A/D converter.
CODE 13
Sensor in the internal reservoir >RES< is defect The safety temperature value lies below the working temperature
setpoint. Set the safety temperature to a higher value.
CODE 14
Safety sensor defect >TANK< The safety temperature value lies below the working temperature
setpoint. Set the safety temperature to a higher value.
The temperature system is operated without bath liquid, or the
liquid level is insufficient. Replenish the bath tank with the bath liquid.
Tube breakage has occured (insufficient filling level due to
excessive bath liquid pumped out). Replace the tubing and replenish the bath tank with the bath liquid.
The float is defect (e. g., because damaged in transit). Repair by
authorized JULABO service personnel.
CODE 15
External control selected, but external Pt100 sensor not connected.
CODE 16
Heating circuit interrupted.
CODE 17
Heating circuit short-circuited.
CODE 31
Communication between control module RD and instrument
interrupted.
Page 48
Troubleshooting guide / Error messages
48
Warning
CODE 40
Warnings without a complete shutdown of the unit
CODE 03
Excess temperature warning
CODE 04
Low temperature warning
CODE 20
Cooling of the condenser is affected. Clean air-cooled condenser.
Check the flow rate and cooling water temperature on water-cooled condenser.
CODE 21
Compressor stage 1 does not work.
Check mains circuit breakers F1 and F3, both might have triggered. Reset circuit breakers if necessary (see below).
CODE 40
Low liquid level warning in the internal reservoir
These messages appear every 10 seconds as long as the
compressor is not switched on although requested by the instrument.
After a short cooling interval, the motor will be automatically
reconnected and the message " CODE XX " no longer appears.
Press enter to quit the audible signal.
After eliminating the malfunction, press the mains power switch off
and on again to cancel the alarm state.
If the unit cannot be returned to operation, contact an authorized JULABO service station.
Disturbances that are not indicated. Pump motor overload protection
The pump motor is protected against overloading. After a short
cooling interval, the motor will automatically start running.
16
A M P
16
A M P
16
A M P
16
A M P
F1
F4F2
F3
Fuses: Mains circuit breakers (resettable).
Page 49
Presto
®
49
10. Safety recommendations
Follow the safety recommendations to prevent damage to persons or property. Further, the valid safety instructions for working places must be followed.
See also chapter 16.Responsibility of the operator
Only connect the unit to a power socket with earthing contact (PE – protective
earth)!
Place the instrument on an even surface on a pad made of non-inflammable
material.
Set the value for safety temperature.Pay attention to the thermal expansion of bath oil during heating to avoid
overflowing of the liquid.
Prevent water from penetrating into the hot bath oil.Exercise caution when emptying hot bath liquids!Employ suitable connecting tubing.Make sure that the tubes are securely attached.Avoid sharp bends in the tubing, and maintain a sufficient distance from
surrounding walls.
Regularly check the tubing for material defects (e.g. for cracks)..Before cleaning the unit, disconnect the power plug from the mains socket.
Notice:
When you have finished the application, it is recommended to keep on circulating the liquid in the bath or the external system for some time. Simultaneously set the working temperature to +20 °C to allow the temperature in the system to decrease slowly. Thus fractional over-heating of the bath liquid is prevented.
Inportant:
Please check the safety device from time to time.
Excess temperature protection according to DIN 12876-1-2000
With a screw driver turn back the adjustable excess temperature protection until the shut-down point (actual temperature).
Low level protection
To check the function of the float of this unit it cannot be operated manually. The 5-graded level display should therefore be observed whenver refilling. If the bath liquid thickens or cracks, the instrument should be cleaned and checked by qualified personnel.
Page 50
Electrical connections
50
11. Electrical connections
SERIAL
RS232/RS485 serial interface (3.5)
This port can be used to connect a computer with an RS232 or RS485 cable for remote control of the temperature system.
Pin assignments: RS232
Pin 2 RxD Receive Data Pin 3 TxD Transmit Data Pin 5 0 VD Signal GND Pin 6 DTR Data terminal ready Pin 7 RTS Request to send Pin 8 CTS Clear to send
Pin assignments: RS485
Pin 3 A Pin 5 0 VD Signal GND Pin 8 B
Pin 1; 2; 6; 7; 9 Reserved - do not use!
Interface correspondence:
Instrument Computer Instrument Computer
9-pole 25-pole 9-pole 9-pole Pin 2 RxD Pin 2 TxD Pin 2 RxD Pin 3 TxD Pin 3 TxD Pin 3 RxD Pin 3 TxD Pin 2 RxD Pin 5 GND Pin 7 GND Pin 5 GND Pin 5 GND Pin 6 DTR Pin 6 DSR Pin 7 RTS Pin 5 CTS Pin 7 RTS Pin 8 CTS Pin 8 CTS Pin 4 RTS Pin 8 CTS Pin 7 RTS
RS232 interface cable 9-pin / 9-pin, 2.5 m - Order No.: 8 980 073
Important:
Use shielded cables only. The shield of the connecting cable is electrically connected to the plug housing.
Page 51
Presto
®
51
REG+E-PROG
Programmer input / temperature recorder output (3.1)
Analog inputs / outputs see page 41 Pin Signal
1 Voltage output Channel 1 0 ... 10 V 2 Voltage output Channel 2 0 ... 10 V 3 GND for outputs 0 V 4 Programmer input EPROG 0 to 10 V / 0 to 20 mA 5 Current output Channel 3 0 to 20 mA / 4 to 20 mA 6 GND for Progammer 0 V
ALARM
Alarm output (3.3)
(for external alarm signal) This potential-free change-over contact is activated in case of an
alarm when pins 2 and 3 are connected.
Switching capacity max. 30 W / 40 VA Switching voltage max. 125 V/ Switching current max. 1 A
ext. Pt100
1
4
2
3
Shield
Plug
Look on
soldering side.
Pt100
Socket for external Pt100 sensor (3.4)
Pin assignment:
Pin Signal
1 I+ 2 U+ 3 U­4 I-
The shield of the connecting cable is electrically connected to the plug housing and the sensor tube.
Important:
Use shielded cables only. The shield of the connecting cable is electrically connected to the plug housing.
Page 52
Electrical connections
52
STAND-BY
STAND-BY input (3.2)
(for external emergency switch-off) Pin assignment: Pin Signal
1 not connected 2 5 V / DC 3 0 V
Use shielded cables only.
Activate the stand-by input: Under menu item Stand-by, set the parameter to "yes"
(see page 32).
Connect an external contact 'AK' (e.g. for emergency switch-off)
or an alarm contact of the superordinated system.
In case the connection between Pin 2 and Pin 3 is interrupted by opening the contact 'AK', a complete shutdown of the circulation pump and heater is effected, and the unit enters the condition "OFF". As long as the contact remains open, line 4 of the DIALOG­DISPLAY (LCD) flashes and displays the message "STAND-BY".
If the contact is reclosed, the instrument returns to the stand-by state and "OFF" is displayed.
Additional tips for using the STAND-BY input:
The stand-by function can be used in conjunction with the AUTOSTART feature (see page 32)
1. If the Autostart function is NOT turned ON, the stand-by input should be used as described above.
2. If the Autostart funcion is enabled, the instrument will revert back to the original method of entering the setpoint (i.e. keypad, RS232, Analog input, etc.).
Entering the setpoint with the keypad.
As described above, a bipolar shut-down is accompanied by the "STAND-BY" display and the OFF state. The programmable controller starts again when the contact is reclosed. The temperature of the bath liquid changed during the STAND-BY state.
Entering the setpoint with the programmer (see pages 35 and
37). The display "STAND-BY" appears. The setpoint value and the time are both held at the current value. The temperature of the bath liquid will be held constant at this temperature. The programmer continues once the contact is reclosed.
Warning: this is not an actual shutoff feature.
Page 53
Presto
®
53
1
2
3
4
Connector for removable control module RD (3.6) Extension cable for operating device RD:
Order No. 8 980 126 2 m long Order No. 8 980 127 5 m long
Control connector (10)
Output voltage is applied when the unit runs, for example after pressing the start/stop key .
Output voltage: 230 V/ max. 0.1 A
12. Remote control
12.1. Setup for remote control
RS232 RS485
Select the "Configuration" submenu and select the option "Setpoint" to define the interface (see page 31).
The interface parameters are set by selecting the submenu "Interface" on the instrument. Normally, this is a one-time-only adjustment. (Selecting and setting menu items, see page 44.)
Factory settings:
RS232 BAUDRATE 4800 bauds
PARITY even parity
HANDSHAKE Protocol RTS/CTS
(hardware handshake) Data bits 7 Stop bit 1
Like all parameters which can be entered through the keypad, interface parameters are stored in memory even after the instrument is turned off.
12.2. Communication with a PC or a superordinated data system
Suitable terminal programs for communicating with a PC are:
MS-Windows - TERMINAL.EXE (included with MS-Windows).MS-DOS - Procomm Plus, Datastrom Technologies.MS-DOS - Norton Utilities.
Page 54
Remote control
54
S xx. xx
ID 0
R
If the temperature system is put into remote control mode via the configuration level, the display will read "R -OFF-" = REMOTE STOP.
In general, the computer (master) sends commands to the instrument (slave). The instrument sends data (including error messages) only when the computer sends a query.
D A transfer sequence consists of:
address (RS485 interface only)commandspace (; Hex: 20)  parameter (the character separating decimals in a group is the
period)
end of file (; Hex: 0D)
The commands are divided into in or out commands.
in commands: asking for parameters to be displayed out commands: setting parameters
The out commands are valid only in remote control mode.
When the RS485 interface is used, the three-digit instrument address stands in front of each command. (example: address Ad32 = A032)
Examples:
Command to set the working temperature to 55.5 °C
out_sp_00 55.5
A032_out_sp_00 55.5
Command to ask for the working temperature T1:
in_sp_00
A032_in_sp_00
Response from the instrument:
55.5
A032_55.5
Page 55
Presto
®
55
12.3. List of commands
When the RS485 interface is used, the instrument address stands in front of each command (Axxx_).
in commands: Asking for parameters or temperature values to be displayed.
Command
Parameter Response of instrument
version
none Number of software version (V X.xx)
status
none Status message, error message (see page 58)
in_pv_00
none Actual bath temperature.
in_pv_01
none Heating power being used (%).
in_pv_02
none Temperature value registered by the external Pt100 sensor.
in_pv_03
none Temperature value registered by the safety sensor. >TANK<
in_pv_05
none Pump pressure in bar.
in_sp_00
none Working temperature
in_sp_03
none
High temperature warning limit
in_sp_04
none
Low temperature warning limit .
in_sp_05
none Setpoint temperature of the external programmer
(socket 3.1 - REG+E-PROG) .
in_sp_07
none Pump pressure stage
in_hil_00
none Max. cooling power (%).
in_hil_01
none Max. heating power (%).
in_mode_02
none Identification type:
0 = no identification 1 = single identification 2 = continual identification
in_mode_03
none Type of the programmer input:
0 = Voltage 0 V to 10 V 1 = Current 0 mA to 20 mA
in_mode_04
none Internal/external temperature control:
0 = Temperature control with internal sensor. 1 = Temperature control with external Pt100 sensor.
Page 56
Remote control
56
Command
Parameter Response of instrument
in_mode_05
none Temperature system in Stop/Start condition:
0 = Stop 1 = Start
in_mode_08
none Adjusted control dynamics
0 = aperiodic 1 = standard
in_par_01
none Time constant of the external bath.
in_par_02
none Internal slope.
in_par_03
none Time constant of the internal bath.
in_par_04
none Band limiting (max. difference between the temperatures in
the internal bath and external system).
in_par_06
none Xp control parameter of the internal controller.
in_par_07
none Tn control parameter of the internal controller.
in_par_08
none Tv control parameter of the internal controller.
in_par_09
none Xp control parameter of the cascade controller.
in_par_10
none Proportional portion of the cascade controller.
in_par_11
none Tn control parameter of the cascade controller.
in_par_12
none Tv control parameter of the cascade controller.
in_par_13
none Adjusted maximum internal temperature of the cascade
controller.
in_par_14
none Adjusted minimum internal temperature of the cascade
controller.
Page 57
Presto
®
57
out commands: Setting parameters or temperature values.
Command
Parameter Response of instrument
out_mode_01
0 Use working temperature
out_mode_02
0 No identification.
Temperature control by using the stored parameters.
out_mode_02
1 Single identification of controlled system after the next start.
out_mode_02
2 Continual identification of controlled system whenever a new
setpoint is to be reached.
out_mode_04
0 Temperature control of internal bath.
out_mode_04
1 External control with Pt100 sensor.
out_mode_05
0 Stop the unit = R –OFF-.
out_mode_05
1 Start the unit.
out_mode_08
0 Set the control dynamics - aperiodic
out_mode_08
1 Set the control dynamics - standard
out_sp_00
xxx.x Set working temperature.
out_sp_03
xxx.x
Set high temperature warning limit .
out_sp_04
xxx.x
Set low temperature warning limit .
out_sp_07
x Set the pump pressure stage (1 ... 5).
out_hil_00
-xxx Set the desired maximum cooling power (0 % to 100 %).
Note: Enter the value with a preceding negative sign!
out_hil_01
xxx Set the desired maximum heating power (10 % to 100 %).
out_par_04
xxx Band limiting during external control.
Setting the maximum difference between the temperatures in the internal bath and external system.
out_par_06
xxx Xp control parameter of the internal controller.
out_par_07
xxx Tn control parameter of the internal controller.
out_par_08
xxx Tv control parameter of the internal controller.
out_par_09
xxx Xp control parameter of the cascade controller.
out_par_10
xxx Proportional portion of the cascade controller.
Page 58
Remote control
58
Command
Parameter Response of instrument
out_par_11
xxx Tn control parameter of the cascade controller.
out_par_12
xxx Tv control parameter of the cascade controller.
out _par_13
xxx Maximum internal temperature of the cascade controller.
out _par_14
xxx Minimum internal temperature of the cascade controller.
12.4. Status messages / error messages
The instrument sends data (including error messages) only when the computer sends a query.
Status messages Description
00 MANUAL STOP Presto®in "OFF" state. 01 MANUAL START
or
01 MANUAL START,DEGASING
Presto®in keypad control mode
or
Presto®in keypad control mode and degasifying active
02 REMOTE STOP Presto®in "r OFF" state. 03 REMOTE START
or
03 REMOTE START,DEGASING
Presto®in remote control mode.
or
Presto®in remote control mode and degasifying active
Page 59
Presto
®
59
Error messages Description
-02 REFRIGERATOR ALARM
Defect temperature sensor in refrigeration circuit.
-03 EXCESS TEMPERATURE WARNING
High temperature warning " ".
-04 LOW TEMPERATURE WARNING
Low temperature warning " ".
-05 WORKING SENSOR ALARM
Working temperature sensor short-circuited or interrupted.
-06 SENSOR DIFFERENCE ALARM
Sensor difference alarm. Working temperature and safety sensors report a temperature difference of more than 25 °C.
-07 I2C-BUS ERROR
Internal error when reading or writing the I2C bus.
-08 INVALID COMMAND
Invalid command.
-09 COMMAND NOT ALLOWED IN CURRENT OPERATING MODE
Invalid command in current operating mode.
-10 VALUE TOO SMALL
Entered value too small.
-11 VALUE TOO LARGE
Entered value too large.
-12 TEMPERATURE MEASUREMENT ALARM
Error in A/D converter.
-13 WARNING : VALUE EXCEEDS TEMPERATURE LIMITS
Value lies outside the adjusted range for the high and low temperature warning limits. But value is stored.
-14 TEMPERATURE/LEVEL ALARM
Safety temperature alarm
-15 EXTERNAL SENSOR ALARM
External control selected, but external Pt100 sensor not connected.
-16 TRIAC/RELAY CONNECTION OPEN
Heating circuit interrupted.
-17 TRIAC SHORTED
Heating circuit short-circuited.
-20 WARNING: CLEAN CONDENSOR OR CHECK COOLING WATER CIRCUIT OF REFRIGERATOR
Cooling of the condenser is affected. Clean air-cooled condenser. Check the flow rate and cooling water temperature on water-cooled condenser.
-21 WARNING: COMPRESSOR STAGE 1 DOES NOT WORK
Compressor stage 1 does not work. Check mains circuit breakers F1 and F3, both might have triggered. Reset circuit breakers if necessary.
-26 WARNING: STAND-BY PLUG IS MISSING
External stand-by contact is open. Stand-by input - see pages 32 and 52.
-31 INTERNAL COMMUNICATION ERROR
Communication between remote module RD and instrument interrupted.
-40 NIVEAU LEVEL WARNING
Low liquid level warning in the internal reservoir.
Page 60
Maintaining the cooling performance
60
13. Maintaining the cooling performance
Air-cooling:
To maintain the full cooling performance, clean the condenser from time to time.
Switch off the unit, disconnect mains power cable.Hold the venting grid, pull out and remove.Clean the ribbed condenser with a vacuum cleaner.Replace the venting grid.Switch on the unit.
14. Disposal of the unit
Notice:
The unit contains R404A or R23 refrigerant which is not harmful to ozone as it looks today. However, during the long time of use the regulations for disposal might change. Subsequently, only specialists should take care of disposal.
Valid in EU countries Directive 2002/96/EC of the European Parliament and of the Council of 27 January 2003 on waste electrical and electronic equipment (WEEE). This directive requires electrical and electronic equipment marked with a crossed-out trash can to be disposed of separately in an environmentally friendly manner. Contact an authorized waste management company in your country. Disposal with household waste (unsorted waste) or similar collections of municipal waste is not permitted!
Page 61
Presto
®
61
15. Cleaning the unit
Caution:
Before cleaning the unit, disconnect the power plug from the mains socket! Prevent humidity from entering into the unit.
Cleaning the unit outside
Clean the outside of the unit using a wet cloth and low surface tension
water (e.g., soap suds).
Before applying a cleaning or decontamination method different from the one recommended by JULABO, the user has to make sure with the manufacturer, that the planned method does not damage the unit.
Cleaning the inside:
If you change the bath liquid or want to use a different one, carefully clean the parts in contact with the bath liquid. The heat exchanger, internal reservoir, connecting tubing and external system should be rinsed several times using cleaning liquid.
S 20.0 0
ID 0
Caution:
Choose the detergent according to the bath liquid which is used.
E.g. Ethanol, Silicon remover, paint remover can be used.
Take care the room where cleaning takes place is well ventilated. Set the working temperature setpoint.
Recommendation: 20 °C
16
A M P
16
A M P
16 A M P
16 A M P
IN
OUT
13
14
15
16
16.1
16.2
Preparations:
1. Drain the temperature system. See chapter 5.8. Draining
2. If only the Presto®temperature system is to be cleaned, connect the pump connectors (13, 14) using a tubing.
3. Connect a tubing to the connector (16) "Reservoir extern". First hold the end of the tubing towards position 16.1, to prevent the cleaning liquid from flowing down instantly.
4. Hold the tubing from the overflow connector (15) into a suitable vessel.
Page 62
Cleaning the unit
62
Cleaning is performed in three steps. First rinse the internal reservoir, then the remaining parts of the instrument. As third step, carefully remove the cleaning liquid.
6
1. Cleaning the internal reservoir:
Switch off the unit with the mains switch!
Thus both valves "Fill" and "De-air" remain closed.
Slowly fill the temperature system via the funnel (5) on the front.
The cleaning liquid should drain via the overflow connector (15). Thus the internal reservoir is rinsed. Empty the internal reservoir by holding the end of the tubing from connector (16) towards position 16.2. Additionally the unit can be lifted up by 4-5 cm by using the handle (6) Repeat this procedure according to the degree of decontamination.
Pump
>Pump OFF
Mode: Sys close
Pump
>Pump OFF
Mode: drain
2. Cleaning the tubing lines and heat exchanger:
Fill the temperature system with cleaning liquid.
See chapter 5.6. Filling
In the submenu >Pump< the unit has to be adjusted on the
operating status >Sys close< .
Set the working temperature setpoint.
Recommendation: 20 °C
Press the start key and allow the liquid to be pumped
through the unit for about 15 minutes.
Press the stop key .
Drain the temperature system. In the submenu >Pump< adjust the menu option >Mode< on >drain< stellen. See chapter 5.8.Draining
3. Removing the cleaning liquid:
Switch on the unit with the mains switch!
Both valves "Fill" and "De-air" remain open.
Blow through the temperature system with dry, warm air.
The air is fed in turns through the different connectors on the temperature system. Begin with the connectors (15, 16) leading to the internal reservoir. Then blow through the pump connectors (13, 14) leading to the heat exchanger and the drain port (8) on the front.
Allow the system to dry (wait until the humidity evaporates).
Then reconnect the temperature system or close the connectors according the intended use. Tighten the drain screw on the front.
Page 63
Presto
®
63
16. Responsibility of the operator
Caution:
Take care your unit is operated only by qualified persons.
The temperature systems have been designed for temperature application to liquids in a reactor, for example. We do not know which substances are contained within these vessels. Many substances are:
inflammable, easily ignited or explosive hazardous to health environmentally unsafe i.e. dangerous
You alone are responsible for the handling of these substances!
The following questions shall help to recognize possible dangers and to reduce the risks to a minimum.
Are all tubes and electrical cables connected and installed?
Note: sharp edges, hot surfaces in operation, moving machine parts, etc.
Do dangerous steams or gases arise when heating?
Is an exhaust needed when working?
What to do when a dangerous substance was spilled on or in the unit?
Before starting to work obtain information concerning the substance and determine the method of decontamination.
17. Maintenance
The unit is designed for continuous operation under normal conditions. Periodic maintenance is not required.
Repairs Before asking for a service technician or returning a JULABO instrument for
repair, please contact an authorized JULABO service station.
When returning the unit: Empty completely, remove the expansion tank, close tightly the connections
with nuts and closing caps.
Careful and appropriate packing is important. During transport the unit has to stand upright. Mark the packing
correspondingly. When returning a unit, take care of careful and adequate packing. JULABO is not responsible for damages that might occur from insufficient packing.
JULABO reserves the right to carry out technical modifications with repairs for providing improved performance of a unit.
Page 64
Technical specifications
64
18. Technical specifications
Working temperature range °C -40 ... 250 Temperature stability °C ±0.01 ... ±0.05 Cooling capacity
1)
°C 200 / 20 -20 -40 (bath liquid: Thermal / Ethanol) kW 1.5 / 1.0 0.4 0.05 Cooling compressor 1-stage Refrigerant R404A Heater wattage Watts 1800 Pressure pump, adjustable in five grades pressure min ... max. at 0 liter bar 0.8 ... 1.6 discharge, max. at 0 bar l/min 24 ... 33 Noise level, 1 m distance dBA 66 Ambient temperature °C 5 ... 40 Mains power connection ±10 % V / Hz 230/50 / 230/60 Total power consumption W 2400 Filling volume Liters 2,5 Overall dimensions (WxDxH) cm 30 x 49 x 64 Weight kg 71
1)
Cooling capacity measured at pumpe stage 1=24 l/min. – 0,8 bar
All measurements have been carried out at: rated voltage and frequency ambient temperature: 20 °C Technical changes without prior notification reserved.
Temperature selection digital
via Removable control module RD indication on DIALOG-Display (LCD) remote control via personal computer indication on monitor
Temperature indication VFD-Info-Display
DIALOG-DISPLAY (LCD) Resolution K 0.01 from -9.99 °C to +249.99 °C Pump pressure display on VFD-Info-Display in five grades Liquid level display on VFD-Info-Display in five grades
Absolute Temperature Calibration
(ATC1) K ±3 (ATC2) K ±9
Temperature control ICC - Intelligent Cascade Control, self-optimizing
Cascade, parameter can be called-in and modified Working temperature sensor Pt 100 Safety temperature sensor Pt 100 Electrical connections: Computer interface RS232 or RS485 or Profi Programmer input -100 °C to 400 °C = 0 to 10 V or 0 to 20 mA or 4 to 20 mA Temperatur recorder outputs 0 to 10 V (0 V = -100 °C, 10 V = 400 °C)
0 to 20 mA (0 mA = -100 °C, 20 mA = 400 °C)
4 to 20 mA (4 mA = -100 °C, 20 mA = 400 °C) Stand-by input External alarm device 24-0 V DC / max. 25 mA External measurement and control sensor Pt100, 4-lead technique Control connector (10) Output voltage: 230 V/ max. 0.1 A
Page 65
Presto
®
65
Safety installations according to IEC 61010-2-010: Excess temperature protection >TANK< adjustable from 0 °C ... 320 °C Excess temperature protection >RES< adjustable from 0 °C ... 220 °C Low level protection float switch
Liquid level display optical, 5-graded Classification according to DIN 12876-1 class III FL Supplementary safety installations High temperature warning function optical + audible (in intervals)
Low temperature warning function optical + audible (in intervals) Supervision of the working sensor plausibility control Reciprocal sensor monitoring between
working and safety sensors difference >25 °C Alarm indication optical + audible (permanent)
Standards:
EMC regulations EN 61326 Guideline for first voltage range EN 61010-1, EN 61010-2-010 Pressure equipment directive EN 378
Protection class IP31 acc. IEC 529 Environment:
Use only indoor. Altitude up to 2000 m - normal zero. Ambient temperature: +5 ... +40 °C (for storage and transportation)
Air humidity acc. DIN EN 61 010, part 1:
Max. rel. humidity 80 % for temperatures up to +31 °C, linear decrease down to 50 % rel. humidity at a temperature of +40 °C
Power supply: acc. to class 1, VDE 0106 T1
not for use in explosive atmosphere
Max. mains fluctuation of ±10 % are permissible. Overvoltage category II Pollution degree 2
Page 66
EC Declaration of Conformity
66
19. EC Declaration of Conformity
The following unit complies with the essential safety requirements outlined by the EC Directives concerning the guidelines for electromagnetic compatibility (89/336/EEC), low voltage regulations (73/23/EEC) and the pressure equipment directive (97/23/EEC).
High Dynamic Temperature System: LH40
This unit is manufactured in compliance with the following guidelines
electrical equipment for control technology and laboratory application – EMC requirements outlined by
EN 61326
safety regulation for electrical devices for measuring, control and laboratory application specified by
EN 61010
refrigerated and heating circulators – safety and environmental – conscious requirements outlined by
EN 378
Julabo Labortechnik GmbH Eisenbahnstr. 45 D-77960 Seelbach / Germany
G. Juchheim, Managing Director
Page 67
Presto
®
67
20. Warranty conditions
JULABO Labortechnik GmbH warrants its products against defects in material or in workmanship, when used under appropriate conditions and in accordance with appropriate operating instructions
for a period of ONE YEAR.
Extension of the warranty period – free of charge
With the ‘1PLUS warranty’ the user receives a free of charge extension to the warranty of up to 24 months, limited to a maximum of 10 000 working hours.
To apply for this extended warranty the user must register the unit on the JULABO web site
www.julabo.de, indicating the serial no. The extended warranty will apply from the date of
JULABO Labortechnik GmbH’s original invoice.
JULABO Labortechnik GmbH reserves the right to decide the validity of any warranty claim. In case of faults arising either due to faulty materials or workmanship, parts will be repaired or replaced free of charge, or a new replacement unit will be supplied.
Any other compensation claims are excluded from this guarantee.
Loading...